Allen Bradley Guide Switchgear-controlgear Assembly

Embed Size (px)

Citation preview

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    1/16

    The easy way to build

    switchgear and controlgear

    assemblies in compliance with the regulations

    A guide for partially type-tested switchgear andcontrolgear assemblies in compliance with EN 60 439

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    2/16

    What are the requirements?

    My name is Rocky, and Im

    looking forward to showing

    you the way through these

    guidelines.

    Contents Page

    EN 60 439 is recognised as the

    established engineering practice for

    switchgear and controlgear assemblies 3

    What are the bases of

    the agencies requirements? 4

    Which control systems and

    installations are subject to EN 60 439? 5

    What is considered as a low-voltage

    switchgear and controlgear assembly -

    (ASSEMBLY) under EN 60 439? 6

    What is the difference between

    a TTA and a PTTA? 6

    What does EN 60 439 define? 8

    Directives for the utilisation of other

    components as those applied for the

    type-test of a TTA permit a range of freedom 10

    Type-tested components simplify work 10

    The added value performed by the ASSEMBLY

    maufacturer requires safety verification 11

    Calculation software simplifies verification

    of the temperature rise 12

    Special care with short-circuit

    currents above 10 kA 12

    Which tests must be performed on PTTA? 13

    How can the expense for the technical

    verification of PTTA be minimised? 13

    Important notes regarding national

    differences 13

    Compilation of verifications and tests

    of TTA and PTTA 14

    A Manufacturers

    Declaration, a Type-testing

    Report and Routine Test

    Protocol are required as asafety verification.

    2

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    3/16

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    4/16

    4

    What are the bases of the agencies

    requirements?

    The requirements are based upon the Low-voltage

    Directive 73/23/EEC and the EMC Directive

    89/336/EEC of the EU, as well as on their supple-

    mentation by Directive 93/68/EEC, which concerns

    the CE-marking.

    In its fundamental requirements, the Low-voltage

    Directive postulates the protection of persons, ani-

    mals and property from the hazards and damage

    which may result from electrical apparatus.

    The EMC Directive states in Article 4:

    The apparatus referred to in Article 2 shall be

    so constructed that:

    a) the electromagnetic disturbance it generates

    does not exceed a level allowing radio and

    telecommunication equipment and other

    apparatus to operate as intended;

    b) the apparatus has an adequate level of

    intrinsic immunity of electromagnetic distur-

    bance to enable it to operate as intended.

    ......

    The central focus is on the pro-

    tection of persons, animals andproperty as well as operation in

    the intended manner without

    malfunctions.

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    5/16

    Which control systems and

    installations are subject to EN 60 439?

    The standard cites (Subparagraph 1.1)

    - stationary or movable assemblies,

    - with or without enclosure,

    - for use in connection with generation, transmis-

    sion, distribution and conversion of electric

    energy and for the control of electrical energy

    consuming equipment.

    EN 60 439 does not apply to individual devices for

    which valid standards exist (motor starters in com-

    pliance with IEC 947, for instance).

    It follows from this that all electrical controls, distri-

    bution boards and switchgear and controlgear

    assemblies fall under EN 60 439.

    It may not be concluded that EN 60 439 is the sole

    standard to be applied. In the case of machine con-

    trols, for instance, additional requirements in com-

    pliance with EN 60 204 (Electrical Equipment ofMachines) must be fulfilled.

    The EU Directives for low-voltage devices

    (73/23/EEC) and for Electromagnetic Compatibility

    (89/336/EEC) are valid in all countries of the

    European Union (EU) and of the European Economic

    Area (EEA) and in Switzerland (Ordinance on elec-

    trical low-voltage equipment and Ordinance on

    electromagnetic compatibility). Similar rules

    which are based to a great extent on the directives

    of the EU are valid or will soon be introduced in

    other countries, such as the Commonwealth of

    Independent States (CIS) or Australia.

    5

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    6/16

    6

    What is the difference between a TTA

    and a PTTA?

    Type-tested low-voltage switchgear and

    controlgear assembly (TTA)

    EN 60 439-1 Subparagraph 2.1.1.1:

    A low-voltage switchgear and controlgear

    assembly conforming to an established type or

    system without deviations likely to significantly

    influence the performance, from the typical

    ASSEMBLY verified to be in accordance with

    this standard.

    A TTA is thus an ASSEMBLY which has been test-

    ed as a type (manner of construction) in compliance

    with EN 60 439. Examples are LV distribution

    boards and Motor Control Centers (MCC). A worst-

    case configuration is tested (e.g. regarding tempera-

    ture rise). TTA are designed for series production,

    whereby the individual TTA corresponds to the

    established type, but adapted to the specific applica-

    tion (e.g. number and performance of the outgoing

    circuits). TTA typically possess structural parts spe-

    cific to the manufacturer such as plug-in modules,

    busbar systems, locking devices, etc., which are not

    available as universally-applicable components.

    TTA are typically applied with installations

    designed for control and distribution and with

    installations with high short-circuit current level.

    Partially type-tested low-voltage switchgear

    and controlgear assembly (PTTA)EN 60 439-1 Subparagraph 2.1.1.2:

    A low-voltage switchgear and controlgear

    assembly, containing both type-tested and

    non-type-tested arrangements provided that

    the latter are derived (e.g. by calculation)

    from type-tested arrangements which have

    complied with the relevant tests ().

    What is considered as a low-voltage

    switchgear and controlgear assembly

    (ASSEMBLY) under EN 60 439?

    In accordance with EN 60 439-1, Subparagraph2.1.1., a low-voltage switchgear and controlgear

    assembly is

    A combination of one or more low-voltage

    switching devices together with associated con-

    trol, measuring, signalling, protective, regulating

    equipment, etc., completely assembled under the

    responsibility of the manufacturer with all the

    internal electrical and mechanical interconnec-

    tions and structural parts ().

    Note 3 states:

    For various reasons, for example transport or

    production, certain steps of assembly may be

    made in a place outside the factory of the manu-

    facturer.

    Thus, an ASSEMBLY is spoken of whenever low-volt-

    age switching devices and protective and regulating

    equipment are involved. EN 60 439 applies for

    ASSEMBLIES up to 1,000 volts a.c. and 1,500

    volts d.c.

    TTA are tested as a type and

    are frequently optimised forspecific applications.

    PTTA consist of type-tested

    components, or such which arederived from them.

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    7/16

    PTTA are thus controls and installations which are

    not tested in their entirety as a type. They are com-

    piled from components which are either type-tested(e.g. contactors, circuit breakers, load break switch-

    es, fuses etc.), or which are derived from type-tested

    arrangements (e.g. busbar system). The temperature

    rise, for example, can be derived (i.e. not mea-

    sured), either

    - in accordance with HD 528 S2 (IEC 890;

    A method of temperature-rise assessment by

    extrapolation for partially type-tested assem-

    blies (PTTA) of low-voltage switchgear and

    controlgear) or

    - with the aid of temperature-rise calculation

    software programs from enclosure manufac-

    turers (which are based in turn on type-tests)

    or

    - based on similarity with previously manufac-

    tured (and measured) ASSEMBLIES.

    The essential difference between TTA and PTTA

    exists in the fact that TTA are optimised for specific

    (repetitious) applications and that, thanks to the

    measurement, it is possible to utilize the compo-

    nents to the limit of their load capacity. TTA are

    procured as complete installations from one manu-

    facturer or built under his licence.

    In contrast to this, the PTTA construction method is

    typically selected by builders of switchgear and

    controlgear assemblies who opt forcomponents

    from different manufacturers instead of the costly

    type-test and the commitment to one manufacturer.

    They derive the correct selection of the components

    for their specific application from the type-tests of

    the manufacturers and install them in accordance

    with the established engineering practice. This

    applies for single assemblies and also for series pro-

    duction. PTTA generally possess more reserve (e.g.

    with regard to temperature rise and the selection of

    the conductor cross sections), since the derivation is

    based on general rules (e.g. regarding the selection

    of conductors).

    TTA and PTTA are equal in regard to the fulfilment of

    safety requirements.7

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    8/16

    8

    What does EN 60 439 define?

    EN 60 439 definesthe design and construction requirements which must

    be fulfilled in order to achieve the safety objectives,

    the definitions which are significant for ASSEMBLIES,

    the referential environmental conditions,

    the test requirements, etc.

    EN 60 439 thus represents an extremely useful set of

    instructions for the set-up and testing of ASSEMBLIES and

    forms a basis for communication between manufacturer,

    customer and agencies. The manufacturers and operators of

    ASSEMBLIES should become familiar with EN 60 439 in

    order to meet their responsibility for the safety of the equip-ment.

    EN 60 439 (Low-voltage switchgear and controlgear

    assemblies) is organised into the parts listed below:

    EN 60 439-1 Part 1: Type-tested and partially type-tested assemblies.

    EN 60 439-2 Part 2: Particular requirements for busbar trunking systems

    (busways)

    EN 60 439-3 Part 3: Particular requirements for low-voltage switchgear and

    controlgear assemblies intended to be installed in places

    where unskilled persons have access for their use

    Distribution boards

    EN 60 439-4 Part 4: Particular requirements for assemblies for construction

    sites (ACS)

    EN 60 439-5 Part 5: Particular requirements for assemblies intended to be

    installed outdoors in public places Cable distribution

    cabinets (CDCs) for power distribution in networks

    There are supplements for some of these Parts which are integrated into the

    respective basic Part upon revisions of the standards.

    The following documents supplement EN 60 439 for specific areas of technology:

    HD 528 S2 A method of temperature-rise assessment by extrapolation for(IEC 890) partially type-tested assemblies (PTTA) of low-voltage

    switchgear and controlgear.

    IEC 1117 A method for assessing the short-circuit withstand strength of

    partially type-tested assemblies (PTTA)

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    9/16

    9

    The contents of EN 60 439-1, the fundamental part of the regulatory ordi-

    nance, are compiled below:

    1. General

    2. Definitions

    3. Classification of ASSEMBLIES

    4. Electrical characteristics of ASSEMBLIES

    5. Information to be given regarding the ASSEMBLY

    5.1 Nameplates

    5.2 Markings

    5.3 Instructions for installation, operation and maintenance

    6. Service conditions

    7. Design and construction

    7.1 Mechanical design

    7.2 Enclosure and degree of protection

    7.3 Temperature rise

    7.4 Protection against electric shock

    7.5 Short-circuit protection and short-circuit withstand strength

    7.6 Switching devices and components installed in ASSEMBLIES

    7.7 Internal separation of ASSEMBLIES by barriers or partitions

    7.8 Electrical connections inside an ASSEMBLY: bars and insulated

    conductors

    7.9 Requirements for electronic equipment supply circuits

    7.10 Electromagnetic compatibility

    8. Test specifications8.1 Classification of tests

    8.2 Type-tests

    8.3 Routine tests

    Annexes

    A (normative) Minimum and maximum cross-sections of copper con-

    ductors suitable for connection

    B (normative) Method of calculating the cross-sectional area of pro-

    tective conductors with regard to thermal stresses due to currents of

    short duration

    C (informative) Typical examples of ASSEMBLIESD (informative) Typical arrangements of forms of separation by barri-

    ers or partitions

    E (informative) Items subject to agreement between manufacturer

    and user

    F (normative) Measurement of creepage distances and clearances

    G (normative) Correlation between the nominal voltage of the supply

    system and the rated impulse withstand voltage of the equipment

    H (informative) Bibliography

    ZA (normative) Other international publications cited in this standard

    with references to the relevant European publications

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    10/16

    10

    What must be observed in theand testing of a PTTA?

    Type-tested components simplify work

    PTTA represent the majority of control systems or

    distribution boards in unit production. Observing

    established engineering practice, careful selection of

    products, and competent construction, the assembly

    of a control system which conforms to directives

    poses no problem and corresponds to the established

    practice of reliable switchboard manufacturers.

    The documentation of the component manufacturers

    are an essential support tool for project planners as

    well as the builders of ASSEMBLIES. In accordance

    with the Low-Voltage and the EMC Directive, all

    components must fulfil the relevant directives and be

    type-tested. The type-tests of the components are

    performed in compliance with the respective stan-

    dards for the components (e.g. in compliance withEN 60 947 for low-voltage switching devices) and

    not in compliance with EN 60 439 (refer to EN

    60 439-1 Subparagraph 1.1: This standard does not

    apply to individual devices and self-contained com-

    ponents, such as motor starters, fuse switches, elec-

    tronic equipment, etc., complying with their relevant

    standards).

    The component manufacturers issue relevant

    Declarations of Conformity and identify theproducts for the EU with the CE-mark. The user of

    such type-tested components can assume that the

    relevant standards are fulfilled, provided that these

    components are installed in accordance with the

    manufacturers specifications (those which form the

    basis of the type-test). This applies for the areas of

    the Low-voltage Directive as well as the EMC

    Directives for the utilisation of other

    components as those applied for the

    type-test of a TTA permit a range of

    freedom

    EN 60 439 states in Subparagraph 8.1.1:

    If modifications are made to the components

    of the ASSEMBLY, new type tests have to be

    carried out only in so far as such modifica-

    tions are likely to adversely affect the results

    of these tests.

    This rule provides the manufacturer of a specific

    TTA a relatively wide range of freedom regarding

    the selection of the switchgear and other compo-

    nents. It is entirely feasible that devices other than

    those employed in the type-test may be installed

    without affecting the validity of the type-test, for

    example when:

    - the maximum temperature rise is not exceeded

    (e.g. through selection of devices of the same

    or lower power dissipation),

    - the insulation withstand strength is not low-

    ered (e.g. through selection of devices of the

    same or better insulation),

    - the short-circuit withstand strength is main-

    tained (e.g. through selection of circuit break-

    ers with the same or higher breaking capacity

    and the same or more favourable let-through

    values).

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    11/16

    11

    construction, modification

    Directive. Among other things which deserve special

    attention are the manufacturers specifications

    regarding load capacity with increased ambient tem-

    perature, the performance data for short-circuit

    stress, the safety distances from arcing apertures,

    etc.

    The job of the ASSEMBLY manufacturer is simpli-

    fied if he can refer to type-tests or technical docu-

    mentation from the component manufacturer forcomponent subassemblies, as is the case with the

    MCS-Star provided by Rockwell Automation for

    motor starters of the Modular Control System

    (MCS). He is thus freed from the burden of select-

    ing and dimensioning the components installed in

    the subassembly.

    The added value performed by the

    ASSEMBLY maufacturer requires

    safety verification

    While it is possible to rely upon the type-tests con-

    ducted for devices by the component manufacturer,

    the ASSEMBLY manufacturer bears the responsibil-

    ity for work he has performed, such as selectingcorrectly-dimensioned conductors and their protec-

    tion. Here, he can rely upon the relevant guidelines

    such as those set down in Harmonization Document

    HD 384.5.523, with consideration for the type of

    conductor, the temperature limit of the conductor

    insulation, the ambient temperature, the conductor

    loading and the method of installation.

    Helpful software tools such as

    MCS-Star produced by Rockwell

    Automation simplify the work of

    ASSEMBLY manufacturers.

    Which starter?

    Starter selection

    Circuit diagram

    Layout

    Assembly test

    Starter selection

    Catalog Nr.

    Bills of Materials Circuit diagram Project Terminate

    Function

    Star-Delta starter

    Mechanical locking

    Without mechanical locking

    Control type

    Short-circuit coordination

    Coordination Type "1"

    Control voltage

    220-230V 50Hz

    230V 50 / 60Hz

    230-240V 50Hz

    240V 50Hz / 277V 60Hz

    Motor protection

    Electrical motor protection relay,terminal 10 man.

    Current limiter

    Star-Delta time relay

    Electronic timer module, 30 seconds

    Assembly system

    Motor output at 400 /415 V 50 Hz

    7.50 kW / 14.8 A

    9.00 kW / 19.0 A

    11.0 kW / 21.5 A

    15.0 kW / 29.0 A

    170-C16NKF10-A1G-TY-E-X

    Layout

    Circuit diagram 170-005 Layout S00SEATX

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    12/16

    12

    Calculation software simplifies

    verification of the temperature rise

    Harmonization Document HD 528 S2 (IEC 890)

    applies as the established engineering practice for

    the determination of the temperature rise in the

    switchgear cabinet with natural cooling.

    Suppliers of enclosures and cabinets provide soft-

    ware for temperature-rise calculation based on

    proven calculation methods and which allow verifi-

    cation of temperature rise and any cooling measures

    required without undue outlays for the user.

    The project planner takes the power dissipation of

    the components from the catalogues or databases of

    the product manufacturers, while the software

    ensures the correct sizing.

    In the event that similar control units (e.g. same

    cabinet size with comparable power dissipation of

    the components in a similar construction) are built

    successively, the verification for temperature rise

    can also be derived from the observance of similari-

    ty with the first system whose temperature rise was

    either measured or calculated.

    Special care with short-circuit

    currents above 10 kA

    EN 60 439 exempts testing of short-circuit with-

    stand strength at rated short-circuit currents below

    10 kA. Nor is verification of the short-circuit with-

    stand strength required for protection with current-

    limiting devices such as current-limiting fuses or

    circuit breakers when the let-through current does

    not exceed 15 kA at rated breaking capacity.

    As a result, significant costs for testing are eliminat-

    ed for many control systems and installations.

    Short-circuit currents of 10 kA presuppose the

    direct connection to a transformer with an output of

    approx. 400 kVA (at 400 V secondary voltage and

    6% short-circuit voltage) and are rare with smaller

    loads. Because of the hazards of short circuits,

    extreme caution regarding the short-circuit with-

    stand strength should be taken and it must be

    ensured that either the limits of 10 kA and 15 kA

    respectively are not exceeded, or that the installation

    possesses the necessary robustness at higher levels

    of short circuit current.

    It is advisable to rely upon type-tested components

    and arrangements, even for PTTA where busbars are

    involved. The selection and application of the bus-

    bar in compliance with manufacturers specifica-

    tions (based on his type-test) ensures a design that

    conforms to requirements.

    In addition, Technical Report IEC 1117 provides

    instructions for the design of PTTA which is resis-

    tant to short-circuits, especially regarding connec-

    tion of the equipment.

    Current limiting circuit breakers can

    eliminate the necessity for verifica-

    tion of short-circuit withstand

    strength.

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    13/16

    Which tests must be performed on PTTA?

    Table 7 of EN 60 439-1 lists the tests which are tobe performed on PTTA (and TTA). In the selection

    of type-tested components, or those derived from

    them, and for the execution of calculations in com-

    pliance with recognised methods, verification may

    be achieved without difficulties.

    It is recommended that standardised protocols are

    prepared for the documentation of the tests or

    whenever available that protocol forms made

    available by professional societies are used.

    How can the expense for the technical

    verification of PTTA be minimised?

    Together with the selection of type-tested compo-

    nents for which no further verification is required

    since reference may be made to the type-test of the

    respective manufacturer, it is recommended to stan-

    dardise the internal bespoke documentation and pro-

    cedures for the services of the planning engineerand builder of ASSEMBLIES and to incorporate

    these standards into a quality assurance system.

    Given careful work in compliance with these inter-

    nal standards, technical verification for all installa-

    tions assembled in compliance with them is guaran-

    teed. With sizing for which either standards or

    industry-specific table references are available, for

    example, it is recommended that these be incorpo-

    rated. It may be anticipated that industrial societies

    will support their members increasingly in the fulfil-ment of this task.

    Important notes regarding national

    differences

    The standards and Harmonization Documents

    referred to in this brochure are cited with the num-

    bers and designations in accordance with CEN-

    ELEC or IEC. The numbers and designations may

    deviate in some countries because of national sys-

    tems. However, the national standards are identi-

    cal in their contents and cite the documents

    which form the basis at the European level in all

    cases.

    Software for calculation of temper-

    ature rise and short-circuit current

    are helpful support tools.

    Careful routine testing

    ensures the safety of the

    individual ASSEMBLY.

    13

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    14/16

    14

    Compilation of verifications and tests of TTA and

    recommendations for the practical execution with

    Seq Requirements Section TTA

    no. to be tested

    1 Limiting excess 8.2.1 Verification of compliance

    temperature of limiting excesstemperature by testing (type-test)

    2 Insulation withstand 8.2.2 Verification of the insulation

    strength withstand strength by testing

    (type-test)

    3 Short-circuit 8.2.3 Verification of short-circuit withstand

    withstand strength strength by testing (type-test)

    4 Efficiency of the 8.2.4 Verification of the proper connection

    protective conductor between conductive parts of the

    switchgear and controlgear

    Proper connection between 8.2.4.1 assembly and protective conductors

    conductive parts of the by inspection or resistance measurement

    switchgear and controlgear (type-test)

    assembly and protective

    conductors

    Short-circuit withstand 8.2.4.2 Verification of the short-circuit withstand

    strength of the protective strength of the protective conductor

    conductor by testing(type-test)

    5 Creepage distances and 8.2.5 Verification of the creepage

    clearances distances and clearances

    (type-test)

    6 Mechanical 8.2.6 Verification of the mechanical

    function function (type-test)

    7 Type of protection 8.2.7 Verification of the type of protection

    (type-test)

    8 Wiring, 8.3.1 Visual inspection of the switchgear and

    electrical function controlgear assembly, including the wiring

    and electrical function test where required

    (routine test)

    9 Insulation 8.3.2 Insulation test

    (routine test)

    10 Protective measures 8.3.3 Inspection of protective measures and visual

    inspection of the continuous protective

    conductor connection (routine test)

    11 Leakage resistance 8.3.4 -

    Subparagraphs 8 to 11 are routine tests

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    15/16

    15

    PTTA (Table 7 from EN 60 439-1) supplemented with

    PTTA.

    PTTA Comments for PTTA

    Verification of compliance Determination in accordance with HD 528 S2 or

    of limiting excess temperature with the use of temperature-rise calculationby testing or extrapolation of TTA software from enclosure manufacturers

    Verification of the insulation withstand The verification of the insulation resistance

    strength in compliance with Section 8.2.2 (measurement at 500 V) will be the

    or verification by insulation test in com- easiest to conduct in most instances.

    pliance with Section 8.3.2 or verification

    of the leakage resistance in compliance

    with Section 8.3.4 (refer to Seq. no. 11)

    Verification of short-circuit withstand Not required up to 10 kA (or 15 kA let-through current respectively).

    strength by testing or extrapolation of Beyond this, use of type-tested busbar systems recommended.

    similar type-tested arrangements Extrapolation in accordance with manufacturer's documents and

    execution in accordance with IEC 1117.Verification of the proper connection

    between conductive parts of the

    switchgear and controlgear

    assembly and protective conductors

    by inspection or resistance measurement

    Verification of the short-circuit withstand For PTTA, separate protective conductors must be provided (protective

    strength of the protective conductor by connections via constructional parts are not allowed) in such a manner

    testing or corresponding execution and that the influence of the electromagnetic forces of the busbars may bearrangement of the protective conductor ignored (i.e., at a distance from the busbars).

    (refer to Section 7.4.3.1.1, last paragraph)

    Verification of the creepage Use of type-tested components and special attention to the clearances

    distances and clearances from enclosures and other conducting parts.

    Observance of arcing spaces.

    Verification of the mechanical Especially for plug-in modules and locking devices. Occurs rarely with

    function PTTA or is covered by the use of type-tested components.

    Verification of the type of protection Use of suitable type-tested enclosures and installation components.

    Installation of components in the switchgear cabinet surface in

    compliance with instructions of the component manufacturer

    for the relevant type of protection.

    Visual inspection of the switchgear and

    controlgear assembly, including the

    wiring and electrical function test

    where required

    Insulation test or verification of the See note regarding Subparagraph 2

    leakage resistance in compliance with

    Section 8.3.4 (refer to Seq. no. 11)

    Inspection of protective measures Visual inspection of the protective conductor connections and random

    sample tests of the threaded connections.

    Verification of the leakage resistance, See note regarding Subparagraph 2

    if the test was not conducted in com-

    pliance with Section 8.2.2 or 8.3.2

    (refer to Seq. no. 2 and 9)

  • 8/10/2019 Allen Bradley Guide Switchgear-controlgear Assembly

    16/16

    More Than 500000 Ways To Make Automation Work

    Power devices Circuit breakers

    Motor contactors and starters

    Motor protection

    Motor Control centers

    Power monitoring

    Sensors Limit, photoelectric and proximity switches

    Pressure and temperature controls

    Radio frequency identification

    Bar code

    Encoders

    Vision systems

    Operator interface Push buttons and pilot devices

    Cam switches

    Message displays

    Operator panels, terminals

    Motion Control AC and DC drives

    Drive systemsComputer numerical controls

    General purpose motion control

    Logic devices Programmable controlers

    Universal I/O

    Control and information processing

    Relays

    Terminal blocks

    Communication Automation control networks

    products Multivendor connectivity (MAP)

    Application systems Custom engineered control systems

    Batch control

    Burner management systems

    Distributed discrete manufacturing control

    SCADA

    Stamping press control systems

    Quality management SPG/SQC data collection and analysis

    Global support Technical training

    services Field engineering and service

    Repair and exchange services

    Technical support