Air Source Heat PumpInstallation and Maintenance Manual

With Pre-Plumbed Cylinders & Underfloor Heating

Model NumbersMIM-E03 A and B N

AE 050-090-120-140-160JXYDEH

Installation Manual.indd 1 01/06/2019

19/07/19 Update

Page 2: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

2

Contents

Freedom Heat Pumps 3

Underfloor Heating 4

Samsung Warranty Registration 7 Year 5

Handover of the System 7

Maintenance of Monobloc Systems 12

Installation 13

Heating & Hot Water, Pre-Plumbed Installation 14

Heating & Hot Water Installation 20

Troubleshooting 27

What the unit comes with and what you will need 29

Wiring and Power Supply Information 31

How To Wire The Electric Meters 33

Other Systems Possible With Samsung EHS 34

Installation Manual.indd 2 31/08/2018 19:01:03

Page 3: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

3

Freedom Heat Pumps

Who are Freedom Heat Pumps?Freedom Heat Pumps are a wholesale distribution company for the Samsung EHS and the Hitachi Yutaki range of heat pumps and

underfloor heating systems. We offer technical support, training, design and consultancy services and operate the

www.samsungehs.co.uk and www.freedomhp.co.uk web sites and freedom heat pumps and Samsung EHS Facebook pages.

We launched Samsung’s eco heating systems in the UK in 2010 and have been market leaders in this sector with over 5000 units out in

the field. In 2016 we started distributing Hitachi’s Yutaki range of units to expand our heat pump portfolio and market influence.

How we workOur approach is very straightforward. If you have a set of plans or an outline of the requirements for a project, send them to

[email protected]. From there, we will produce a heat loss calculation in line with today’s standards, and put together a list of the

kit required at your cost price.

Alternatively, if you don’t currently have a heat pump project, but would like to become a heat pump installer, and don’t know where to

start, contact us on 02380 274833 or email us at [email protected] and we can set you on the correct course.

Homeowners:If you are the homeowner please ask your installer for the pdf homeowner manual or download it here www.freedomhp.co.uk scroll to

the bottom and click the link for end user manual. it shows how the unit should be used and how to get the best from it.

Installation Manual.indd 3 31/08/2018 19:01:03

Page 4: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

4

Underfloor Heating

If you are looking for an underfloor design which we guarantee will have the heat pump at the centre of the system design,

instead of as an add on, come and talk to us at Freedom HP.

Pipe

We supply a high quality 16x2mm

multilayer pipe, consisting of 5 layers of

polyethylene, adhesive and aluminium.

Typically rated at 95°C at 10bar, this strong

flexible pipe is well suited to underfloor

heating, and is manufactured within the

EU.

ControlsAt Freedom we provide a wide range of

controls manufactured by leading brands

such as Heatmiser, Danfoss and Reliance.

On offer are basic dial thermostats to

the latest digital phone app controlled

products.

ManifoldsOur brass manifolds are made in Germany,

and are supplied to us by Watts Industries.

This premium product has individual flow

meters, isolation ball valves, and is fitted

with an auto air vent and pressure gauge to

aid testing.

Plate SystemsOur plate system is generally used for a suspended floor. Insulation should be fixed

flush with the top of the existing joists to prevent downward heat loss. Battens are

fixed at 400mm centres at 90° to the existing joists. Aluminium trays are then laid and

stapled into position and the underfloor heating pipe is pressed into the grooves within

the trays.

The pipe warms the trays and the heat is spread across the floor. Chipboard or plywood

can then be laid and fixed to the battens.

Overlay SystemsOverlay panels provide many advantages over other insulation products when used

with warm water underfloor heating systems.

Our panel dimensions are 1250mm in length by 350mm in width and either 20mm or

25mm high.

Screed SystemsA Screed System is where the underfloor heating pipes are incorporated within the

solid floor structure. Staples, interlocking cliprail or castellation mats are fixed directly

on to the floor insulation. At Freedom Heat Pumps, we can provide everything from

staples to cliprail through to castellation mats in order to suit your project.

Quotations are provided without obligation, and a fully insured BS1264 compliant AutoCAD pipe layout can be prepared prior to delivery

and installation. This affords the client an opportunity to approve our suggestions prior to final acceptance.

Do you have a project which you would like us to provide a competitive underfloor heating quotation for?

If so, please email [email protected] or call 02380 274 833

Installation Manual.indd 4 31/08/2018 19:01:09

Page 5: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

5

Samsung Warranty Registration

You can now register for the Freedom HP 3 / 5 and 7 year parts and labour contribution warranty; the warranty will start from

the date of delivery to site. This warranty covers the Hitachi components only. The warranty does not cover radiators,

cylinders, UFH, valves, pumps etc.

Your maintenance company can extend to a 5 or 7 year Warranty in years 3 or 5, In the event of a warranty claim we will credit

the maintenance engineer a labour allowance for works completed, details are on the certificate.

In order to maintain your extended warranty you will need to have a maintenance agreement in place and ensure that

required checks are carried out annually

Your unit is not automatically registered for warranty, your installer needs to fill in a form Online at www.freedomhp.co.uk.

Once this is done a certificate and a maintenance book will be emailed to the applicant, please make sure you have a copy of

this certificate, and proof of maintenance. Hitachi may ask for this when a warranty claim is made.

Installation Details

Your Name

Your email address

Outdoor model number

Outdoor serial number

You will find this on the side of the heat pump

Indoor unit model number

Date commissioned / /

Name of Homeowner

End user email address

This is where the warranty certificate will be sent by Samsung

Installation address

Post code

Installation Details

Company name

Engineers name

Office telephone number

Is this your first Samsung install? YES / NO

Date commissioned

Will you or your company

be maintaining the Unit? YES / NO

If No, Freedom Heat Pumps will advise of an engineer who

can do this

Install PhotosPlease take at least 6 photos showing the outdoor unit, control

box and cylinder cupboard

Installation Manual.indd 5 1/6/2019

Page 6: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

6

Commissioning Data

Pre-plumbed / Separate Cylinder

It is useful to take these measurements at commissioning and testing. They are for your own records. They are not needed to register the unit for warranty.

What type of system do you have?

Is there a Header, Buffer or Heat Exchanger installed?

You need to measure the following and record the data:

Flow temperature at Heat Pump

Measure with pipe thermometer

Return temperature at Heat Pump

Flow temp into header / plate

Return from header / plate

Flow temp out of header /

plate to heating

Return from Heating into

header / plate

Flow rate from flow meter

Air temp at the back of the unit

Ambient air temperature Measure from the garden

Hot water cylinder model No.

Cylinder water temp at start-up

Measure from the remote controller

Cylinder water temp after 30mins Measure from the remote controller

Water flow temp at cylinder Measure with pipe thermometer

Water return temp at cylinder Measure with pipe thermometer

Flow Rate Measure from the flow meter

Hot Water Mode Commissioning DataYou must be running the heat pump in hot water mode for this section

Pump Z1

Header, Buffer or

Heat Exchanger

Pump HPH

HW

Flow and Return

at Heat Pump

Flow RateReturn from

Header

Flow out of

Header

Flow into

Header

Return from

Heating

Water temp in weather comp mode

Ambient temperature °C

Flow

tem

pera

ture

°C

-535

55

50

45

40

0 5 10 15

Installation Manual.indd 6 31/10/2018 19:01:12

Page 7: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

7

Handover of the System

Leave these 5 pages with the Homeowner. When you register the unit for warranty we will email you a manual that you can leave with them on site.

Please search YouTube for Freedom Heat pumps Handover Video for Samsung Heat Pump for Homeowners

Thank you for buying a Samsung EHS heat pump system, your Samsung heat pump heats the house and hot water cylinder much like a normal fossil fuel boiler, however there are a couple of differences which you should take notice of.

Your installer should have provided you with a room thermostat if you have radiators or a thermostat in every room if you have under

floor heating. The installer will be able to run through the operation of your stats with you. The heat pump will operate from the signal

sent by these stats back to the heat pump, please do not use the Samsung controller to control your heating.

Once the unit starts up it will take time to get to temperature, it is not instant. Within 10 minutes you should feel the radiators

beginning to warm up. Although it may take a few days to have everything to the required temperature, please do not switch your stats

off during this period.

Weather compensation and water lawThe radiator temperatures will be lower than you are used to with a gas or oil boiler. To add to this, we run them in a weather

compensation mode, this means that the unit measures the outside temperature and adjusts the radiator temperature to suit.

The colder it is outside the warmer the rads will be and vice versa. This function is automatic and is designed to save you money. In very

cold weather the radiator will be at their hottest, they will reach 50°C.

Running your machine efficientlyIt is very expensive to heat the house up from cold, with a heat pump the best advice is to maintain the house at as close to constant

temperature as possible all the time.

By far the cheapest way to run a heat pump is to leave it on 24/7 at one set temperature, dont turn it off and dont time clock it. But if

you insist on switching it off . Please DON’T set the room temperature too low when you leave the house, ideally drop it no more than 2

degrees below your normal set temperature when you go out or it will take a long time and a lot of money to recover.

To switch off the heating in summer set your room thermostats down to 16°C to avoid the heating starting up. Your radiators will have

thermostatic valves on them, you can adjust each room’s temperature with these.

Water temp in weather comp mode

Ambient temperature °C

Flow

tem

pera

ture

°C

-535

55

50

45

40

0 5 10 15

Installation Manual.indd 7 31/08/2018 19:01:12

Page 8: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

8

Handover of the System

General AdviceThe heat pump comes with a Samsung controller which looks like

this, you should not use this or press the buttons, it is used for

commissioning and fault diagnosing the system only.

On Youtube (search for freedom heat pumps) there are videos

showing how to use the controller, faults etc.

Normally the controller will show AU or 0.0c on the left and a tap

in the right hand top corner. This is normal, it means the system

is controlled by external thermostats. If it says 0.0c you can boost

your heating water temp using + or – but it costs more money if its

set above 0.0C

If the system goes into fault, the screen will show a number at the

bottom starting with E, for example E911 – A00. The green light

will go out and a red light will flash. The engineer will want to know

this number when you call.

Please avoid turning the unit off at the power supply especially

in cold weather. If the unit is off and the weather is very cold, it

cannot protect itself and your warranty will be at risk.

If the unit is off and the temperature outside is cold, it will

automatically run the pump for a few minutes to stop freezing.

In extreme weather, below -2°C the water pump will run

continuously, you cannot stop this.

Hot Water

At the top right of the controller you should see a tap with 2 dots, this means your unit is monitoring the cylinder temperature.

The unit it set up to maintain the water between 43 and 50°C all the time.

As you use the water the heat pump will constantly top up the cylinder. The hot water cylinder has priority over the heating, if the

cylinder temperature falls 5 degrees below its set point the unit will automatically switch to heating the cylinder. This should take less

than an hour.

Once set temperature is achieved the unit will go back to heating the house. The hot water cylinder loses almost no heat (1/3 a degree

an hour) if no hot water is used.

If you want to heat the cylinder very quickly you can press the DHW mode button, on the right until a bath shows, this will run the heat

pump and the immersion together. Please remember to return the tap with two dots when it is no longer required.

An anti-legionella / disinfection operation will be completed at a 3am every Wednesday morning.

The unit will heat the cylinder with the immersion to 60°C, the hot water will be hotter on a

Wednesday morning than the rest of the week. If legionella is not completed this e919 will flash on

screen, you need to call an engineer to check it.

If you don’t require 24/7 hot water It is possible to time clock the hot water to reduce costs, the timer video on you tube will show you

how to do this.

Installation Manual.indd 8 31/08/2018 19:01:14

Page 9: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

9

Handover of the System

The outing mode button sets the hot water cylinder temperature to 25°C but has no effect on heating, this is

ideal for when you go away on holiday etc. If you turn all thermostats down as well the heat pump won’t run

which will save money.

The Silent mode button is not used, due to risk of freezing up etc.

Location Function

1 Heating On / Off

2 Heating Mode Button

3 Plus / Minus Buttons

4 Silent Mode Button

5 Outing Mode Button

6 View Button

7 Set Button

8 Timer Button

Location Function

9 User Set Button

10 Escape Button

11 Delete Button

12 Up / Down / Left / Right Buttons

13 Set Button

14 Hot Water On / Off

15 Hot Water Mode Button

⑦⑧

②⑮

⑫⑬

⑩ ⑪⑥⑤

Installation Manual.indd 9 31/08/2018 19:01:14

Page 10: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

10

Status Indication

Location Symbol Function

1

Shows that the unit is operating in heating mode

Shows that the unit is operating in auto mode (Weather compensation)

Shows that the unit is operating in outing mode

Shows that the unit is operating in silent mode, never used

2System temperature (Water law, Indoor, Outdoor, flow and hot

water cylinder temperature)

3 Temperature display

4Timer Display (Daily/Weekly/Holiday)

daily shows a hot water timer is set up.

5 Current day or day display for timer function

6 Timer number

Handover of the System

④ ⑤ ⑥ ⑦

LED indicator (Green: Normal / Red: Need to be checked)

On/Off button

Temperature control button

⑧ ⑨ ⑫

Installation Manual.indd 10 31/08/2018 19:01:15

Page 11: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

11

Location Symbol Function

7 Current time or times for timer functions

8

Shows that the compressor is running and the outdoor unit is heating

Shows that the backup heater/boiler is running (if applicable)

Shows that the Immersion heater is running

Shows that the hybrid boiler is running (Hybrid systems only)

9

Shows that the water circulation pump is running

Shows that the hot water valve is open and the heat pump is heating the hot water cylinder

Shows that the unit is in defrost mode see defrost video on you tube

Shows that the unit is in freezing control mode (when the outdoor temp us below 10°C the unit runs the water circulation pump all

the time to keep the water in the system from freezing.

Shows that Legionella mode is active

10

Shows that the unit is running off of an external thermostat

This shows that the button you pressed can’t be used at this time (No function)

11

Shows when unit is in test mode.

This icon shows that you someone should check the unit (Normally shows with a fault code)

Shows the remote is locked

13

Shows that unit is checking the cylinder and will heat it when the temperature drops below the set point

Shows that the unit is running in a forced hot water mode

14 Eco level operation (1-5)

Handover of the System

Installation Manual.indd 11 31/08/2018 19:01:15

Page 12: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

12

Maintenance of Monobloc Systems

The Samsung heat pump should be maintained at least once a year to comply with warranty and RHI. Please leave maintenance

records with the homeowner, they may need them if they have a warranty claim. See end user manual for details.

Maintenance procedureStop the unit, clean the water filters, shut the valve, undo the back

and pull the strainer out and replace it.

Test the concentration of the Anti-freeze (glycol) in the system

using a Glycol tester the level should be 25%. If you don’t have a

glycol tester a glycol tester / refractometer can be bought from

your heat pump supplier or online.

Refill the unit, pressure should be 0-3 bar.

We need to test the operation of the unit against the hot water cylinder. So first we need to draw off 50 litres of water, run a couple of

taps for 5 mins to achieve this. The unit should start up automatically in hot water mode, if it doesn’t press the DHW power button on

the controller, in 3-4 mins it will start heating the cylinder, a coke can symbol will show in the status section of the remote controller.

The heat pump should be able to achieve 48°C cylinder temperature without using the immersion heater.

While running, check the outdoor unit for damage & debris, the coil needs washing, we recommend you use an approved EHS heat

pump cleaning chemical, your distributor will stock this. Instructions are given on the bottle. You also need to clean and polish the

outside casing we recommend car wax to do this.

Hot Water CylinderCheck electrical connections & sensor is above the immersion

and at least 100mm into the tank and the overheat thermostat is

set to 70°C. On a Telford cylinder set the stat to 5.

Press the mode button until a bath symbol shows on the Samsung

remote controller; this will force the immersion heater on. Check

immersion heater works properly, Measure the current drawn by

the heater; it should be 12-13 Amps.

Measure the temperature of the flow using the remote controller.

Measure the flow rate from the flow meter.

With the unit running flat out measure the temperature of the air as it enters the coil and the temperature of the air in the garden. They

should be the same check cold air is not recirculating.

Installation Manual.indd 12 31/08/2018 19:01:16

Page 13: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

13

Installation

Installing the Outdoor Unit (Boiler)Position the outdoor unit so that the air flows into an open area, where there are no plants and animals. If the unit is to be installed within

a mile of the sea you need to have the unit coated suing Blygold, ask us for details. If you are applying for RHI and going through MCS you

need to make sure the system meets MIS020.

Install the outdoor unit on a flat, stable surface, it needs to be securely mounted at least 100mm off the ground on rubber feet. The unit

must be bolted down for security using 10mm bolts and Zebedee’s.

The unit must have adequate drainage away from the unit; it can produce up to 6 L / hour of condensate. If you are installing the unit at

height you can install a drain pan under the unit but its best to let the unit drain into the ground.

Dimensions:

Size 16 - 1420mm (h) 940mm (w) 330mm (d) 103kg

Size 9 - 998mm (h) 940mm (w) 330mm (d) 75kg

Size 5 - 798mm (h) 880mm (w) 310mm (d) 59kg

The space around the unit is very important, allow:

300mm to the left hand side (facing the front of the unit),

600mm to the right of the unit,

300mm to the rear of the unit and 1500mm to the front of the

unit.

Installing the Control Box MIM-03ANThe control box contains the flow switch, cylinder sensor (blue) 2

red safety sensors, some cables for a backup heater, a black cable

for smart grid connections and the remote controller.

Install the control unit indoors, it’s not waterproof.

It needs to be sited within 15m of the hot water cylinder, less than

100m from the outdoor unit and as near as possible to the pump,

flow switch and any zone valves.

The box is 323mm wide, 339mm high, 131mm deep.

The Samsung remote controller MUST be in a heated space above

5 degrees C.

300 or more

300

or m

ore

1500

or m

ore

600 or more

Installation Manual.indd 13 31/08/2018 19:01:19

Page 14: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

14

Pump

Z1

To Heating Zone or

Zones

Put Zone Valves here if m

ore than 1 heating zone is required

Pump

HP H HW

Heating flow

and return can exit to the right as show

n but can be straight up or dow

n

Heating & Hot Water, Pre-Plumbed Installation

You need to connect the hot and cold feeds, the tundish and drains. You need to install an expansion vessel on the heat pump side and

the heating side of the system and one onto the cylinder. The 300l cylinder needs a floor area of 700 w

ide by 850 deep, the cylinder is

1650 high and 555mm

diameter. The 200l cylinder needs a floor area of 700 w

ide by 800 deep, the cylinder is 1500 high and 510mm

diameter.

Heating &

HW

Pre-Plumbed

Installation Manual.indd 14 31/08/2018 19:01:20

Page 15: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

15

Pump

Z1

To Heating Zone or

Zones

Put Zone Valves here if m

ore than 1 heating zone is required

Pump

HP H HW

Heating flow

and return can exit to the right as show

n but can be straight up or dow

n

Heating & Hot Water, Pre-Plumbed Installation

Pum

p H

P is

wire

d Li

ve to

B8

and

Neu

tral

to B

7, M

AX

pum

p po

wer

is 5

00W

.

2 po

rt v

alve

for H

ot w

ater

, wire

bro

wn

to B

17 a

nd b

lue

to B

15,

2 po

rt v

alve

for H

eati

ng

wire

bro

wn

to B

10 a

nd b

lue

to B

15. O

rang

e an

d G

rey

wire

s ar

e no

t use

d on

thes

e 2

valv

es.

The

heat

ing

run

sig

nal

link

s pe

rman

ent l

ive

B20

- B22

.If y

ou n

eed

Neu

tral

use

B19

.

Wiri

ng D

iagr

am P

re-P

lum

bed

Com

mun

icat

ion

Cab

le

2 co

re, 1

mm

(16V

dc)

Flow

Sw

itch,

2m

long

You

can

exte

nd th

is

Tank

Sen

sor,

15m

long

Don

’t cu

t thi

s

Pow

er In

put

16 A

mps

Run

sign

al fr

om U

FH,

ther

mos

tats

or Z

one

valv

es Z

1, Z

2 et

c.N

ote

on th

e zo

ne

valv

e H

W th

e gr

ey

and

oran

ge w

ires

are

not

use

d

Pum

p Z1

Pum

p H

P

Imm

ersi

onH

eate

r

HH

W

Pow

er s

uppl

y 24

0V16

A fo

r the

5kW

20A

for s

ize

932

A fo

r siz

e 16

F1F2

LN

Installation Manual.indd 15 31/08/2018 19:01:24

Page 16: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

16

Heating & Hot Water, Pre-Plumbed Installation

When commissioning this system, you will find its already been completely set up for you, but here are a few things you need to do.

Fill in the warranty card on page 5 and 6

Hand the end user pages 7-11.

Start-up ProcedureFilling and flushing, when installing any Heat pump, we insist on a thorough system flush prior to connection in line with the Building

Regulations for England and Wales, Part L, 2006. Using the power flusher fill the system with water and 25% Propylene Glycol, there is no

pressure sensor in the unit so we can operate from open vented to 3 bar maximum.

Setting up the cylinder immersion heater To avoid the immersion heater cutting out before the legionella function is complete

you have to set the stat in the immersion heater to 70°C minimum, set it to 5.

Check the tank sensorThe blue tank sensor MUST be installed above the immersion heater and it must be

securely fixed in the tank right into the back of the pocket, I would use heat paste and

cable ties to do this.

Powering UpMakes sure all your room thermostats are off and all underfloor run signals are off.

Apply power to outdoor and indoor unit, you should see red lights on the PCBs of both units check this If there are no lights you will need

the electrician to check for power.

The remote controller will be dead for about 4 minutes; after that it will come to life. You will see 00 first then 01 on the remote controller

screen for 90 seconds. If 00 continues to show the outdoor unit is not powered up or its not connected. Get the sparky to check this.

Valve Z2Power In

Valve Z1

Run Signal to Heat Pump

As many heating zone valves as you like can be connected to the system.

B20 B22Power In

Installation Manual.indd 16 31/08/2018 19:01:25

Page 17: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

17

Heating & Hot Water, Pre-Plumbed Installation

Setting the Clock and Backlight1. Press User Set once 1 shows on the screen.

2. Press up until 2 shows,

3. Press right twice, Year will show, use up to change year, press Set, 22 appears,

4. Press right Month will be flashing, adjust Month with up,

5. Press right, day will be flashing, adjust day with up,

6. Press Set. 22 shows, press up once, 23 shows,

7. Press right, day and time are shown, day will be flashing, use up to adjust day,

8. Press right, AM or PM will be flashing, use up to adjust AM, PM or both (24-hour clock),

9. Press right, hour will flash, press up to adjust hours,

10. Press right, minutes will flash, use up to adjust minutes,

11. Press Set.

12. 23 shows, Press left 2 flashes, press up twice 4 flashes,

13. Press right, 4 0511 shows, 05 flashes. This is the backlight time,

14. Press up until 30 flashes,

15. Press Set, it will now stay on for 30 seconds,

16. Press ESC to finish and return to normal screen.

Cylinder TimerTo avoid the cylinder heating being switched off accidentally we normally add 2 on timers a day, one at 3:00 am and one at 15:00 pm.

This stops nuisance tripping, resets the unit after power cuts and insures the cylinder is hot 24 hours a day. We don’t normally set any off

times.

To set the cylinder up as above:

1. Press Timer button once,

2. Press right, daily is flashing, daily is the hot water time clock, press right

3. Press right 1 will show,

4. Press right,

5. On systems with a 12-hour clock, pm shows, press up till am and pm shows (24hours).

6. Press right, hours will be flashing, use up to set hours to 0300.

7. Press right, minutes will be flashing.

8. Press right, ON will be flashing. *

9. Press right, the tap will appear,

10. Press Set

You will return to 2 above. Now repeat with a timer at 15-00 hours.

You can delete or adjust timers by entering timer mode, press Timer once and scrolling up and down to the timer you want to adjust,

just keep scrolling right to the part you want to change and then use up down to adjust it, then press Set to store. To delete a timer

select it with up and down and press Delete, to save the changes made press the Set button. When you are finished press ESC.

Don’t worry about the field settings, we have already had these done for you for use with your setup.

Installation Manual.indd 17 31/08/2018 19:01:25

Page 18: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

18

Heating & Hot Water, Pre-Plumbed Installation

Electrically testing the unitThe unit has a function to test all the wiring without any tools, this is really useful to check everything has been set up correctly. Test

each component one at a time to check its ok.

Operation Button Display

Enter test mode – hold the left and right buttons together for 4 seconds

Run the water circulation pump (Terminal B8 live) – Press the red Heating on/off button leave this running

You should check flow rates here see below

Run the immersion heater (Terminal A3&A4) – press the Mode button (Heating)

Open Valve HW for hot water (Terminal B17 live) – press the Outing Button

Heating valve 1 is normally open (B10 live), to close valve for heating Zone 1 – press the Set button

Turn up your room thermostats, when they come on heat will show. This shows a run signal is received at the unit, turn stats

down again test will reappearOperate Zone 1 thermostat

Checking flow rateFirst you need to clean the filter balls.

Shut the valve, undo the back of the valve, remove the strainer, clean it and replace it then open the

valve.

Press right and left button together for 6 seconds. The controller will display TEST or 7E57 or HEAT,

press the power on/off button to start the pump. When the pump is running you can see a picture

of a house with a circle around it.

The unit will be running in heating mode. Check the flow rate, we need 12l/min on the 5kW unit, 20l/

min of flow on the 9kW unit and 30l/min on the 16kW unit. If there is not enough flow the unit will

never operate and it will give fault E911 see fault code page.

If you look into the flow meter you can see the flow in litres per minute. The flow rate is the low

figure, in this picture you can see a flow rate indicated, this shows 0l/min NOT 16l/min. Make sure

you clean the filter ball, turn up all the pumps, open all the valves and get rid of the air to keep flow

rate up.

Testing the flow in Hot water mode

Clean the filter ball again, press oval set button, 2-1 appears on screen, the heating valve will close.

Manually open the HW valve with the toggle and leave it open. Now measure the flow rate through

the cylinder. As above.

Exit test mode – press the ESC button to get back to normal display

Installation Manual.indd 18 31/08/2018 19:01:27

Page 19: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

19

Heating & Hot Water, Pre-Plumbed Installation

Starting the unit in heating modePress the power button (top left) AU or 0.0C will show, the unit is automatic mode using an external

run signal. Turn up your thermostats or underfloor heating to send a run signal to the unit, the pump

will start within 3 minutes, a little house with a circle around it appears in the status window, the

compressor in the outdoor unit starts after 3 minutes, you will see the symbol for the compressor in

the status screen. It’s a little milk churn with a C in it. The pipework will begin to heat up.

Check the flow temperature by pressing oval View button, it will show 4 sensors. The house is the

temperature at the remote controller which is not used. The house with the circle around it is the

water outlet temperature from the heat pump. The Christmas tree is the air temperature outside.

The tap is the cylinder temperature. If the outdoor unit doesn’t start after 5-minutes, see problems

page.

Over time the unit will warm up, now check all the radiators or under floor loops are hot as well.

Starting the System in hot water modeClean the filter balls again.

Press DHW on/off (power) button to start the unit, top right button.

A picture of a tap appears with dots by it, press Mode until 2 dots appear. This means the HP will heat

the water with help from the immersion.

Set the cylinder temperature press the oval Set button then press + until 48°C shows. The heat

pump will start heating the cylinder if its colder than 43°C and will heat it up to 50°C then it will stop.

The unit will take up to 6 minutes to start in Hot water mode, be patient

When the unit is heating the cylinder, this coke can symbol shows on the controller. The HW valve will

open but the heating valve will not close for 40 seconds, this is normal.

Run test in hot water modePress View until a picture of a tap appears, this is the hot water cylinder temperature, note it down.

After 15 minutes of running check the hot water temperature again, it should have risen, again note the temperature. If the unit is

running well it should heat the cylinder to 48°C without needing the immersion heater. Now clean the filter ball again.

The Water storage temperature is lower (48°C) than a normal cylinder. It’s important to check that any shower or bath mixers do not

further reduce the water temperature. Using your thermometer check that the hot water comes out the tap at the same temperature

it leaves the cylinder. If it doesn’t you might need to make adjustments to taps mixers etc.. DON’T raise the cylinder temperature to

compensate.

Now handover the system to the end user, see page 7-11, fill in the warranty card on page 5 and online. Your system is now

fully commissioned, congratulations.

Installation Manual.indd 19 31/08/2018 19:01:27

Page 20: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

20

Pump Z1

Header,

Buffer or

Heat

Exchanger

Pump H

PH

HW

Heating & Hot Water Installation

Reduced Glycol System

.If you w

ant to reduce the amount of G

lycol to be used in the system, you can install a plate heat exchanger. The heat exchanger needs to

be suitably sized if in doubt please ask.

Heating &

Hot W

ater Systems

Installation Manual.indd 20 31/08/2018 19:01:29

Page 21: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

21

Heating & Hot Water InstallationW

iring

Dia

gram

Hea

ting

& H

ot W

ater

Com

mun

icat

ion

Cab

le

2 co

re, 1

mm

(16V

dc)

Flow

Sw

itch,

2m

long

You

can

exte

nd th

is

Tank

Sen

sor,

15m

long

Don

’t cu

t thi

s

Pow

er In

put

16 A

mps

Run

sign

al fr

om U

FH,

ther

mos

tats

or Z

one

valv

es Z

1, Z

2 et

c.N

ote

on th

e zo

ne

valv

e H

W th

e gr

ey

and

oran

ge w

ires

are

not

use

d

Pum

p Z1

Pum

p H

P

HH

W

Pow

er s

uppl

y 24

0V16

A fo

r the

5kW

20A

for s

ize

932

A fo

r siz

e 16

F1F2

LN

Pum

p H

P is

wire

d Li

ve to

B8

and

Neu

tral

to B

7, M

AX

pum

p po

wer

is 5

00W

.

2 po

rt v

alve

for H

ot w

ater

, wire

bro

wn

to B

17 a

nd b

lue

to B

15,

2 po

rt v

alve

for H

eati

ng

wire

bro

wn

to B

10 a

nd b

lue

to B

15. O

rang

e an

d G

rey

wire

s ar

e no

t use

d on

thes

e 2

valv

es.

The

heat

ing

run

sig

nal

link

s pe

rman

ent l

ive

B20

- B22

.If y

ou n

eed

Neu

tral

use

B19

.

Installation Manual.indd 21 31/08/2018 19:01:33

Page 22: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

22

Heating & Hot Water Installation

When commissioning this system, you need to follow the procedure below don’t skip this, if you do the unit won’t work properly

Fill in the warranty card on page 5 and 6.

Hand the end user pages 7-11.

Start-up ProcedureFilling and flushing, when installing any Heat pump, we insist on a thorough system flush prior to connection in line with the Building

Regulations for England and Wales, Part L, 2006. Using the power flusher fill the system with water and 25% Propylene Glycol, there is no

pressure sensor in the unit so we can operate from open vented to 3 bar maximum.

Setting up the cylinder immersion heater To avoid the immersion heater cutting out before the legionella function is complete

you have to set the stat in the immersion heater to 70°C minimum, on a Telford

cylinder set it to 5.

Check the tank sensorThe blue tank sensor MUST be installed above the immersion heater and it must be

securely fixed in the tank right into the back of the pocket, I would use heat paste and

cable ties to do this.

Powering UpMakes sure all your room thermostats are off and all underfloor run signals are off.

Apply power to outdoor and indoor unit, you should see red lights on the PCBs of both units. IIf there are no lights you will need the

electrician to check for power.

The remote controller will be dead for about 4 minutes; after that it will come to life. You will see 00 first then 01 on the remote controller

screen for 90 seconds. If 00 continues to show the outdoor unit is not powered up or its not connected. Get the sparky to check this.

Valve Z2Power In

Valve Z1

Run Signal to Heat Pump

As many heating zone valves as you like can be connected to the system.

B20 B22Power In

Installation Manual.indd 22 31/08/2018 19:01:34

Page 23: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

23

Heating & Hot Water Installation

Setting the Clock and Backlight1. Press User Set once 1 shows on the screen.

2. Press up until 2 shows,

3. Press right twice, Year will show, use up to change year, press Set, 22 appears,

4. Press right Month will be flashing, adjust Month with up,

5. Press right, day will be flashing, adjust day with up,

6. Press Set. 22 shows, press up once, 23 shows,

7. Press right, day and time are shown, day will be flashing, use up to adjust day,

8. Press right, AM or PM will be flashing, use up to adjust AM, PM or both (24-hour clock),

9. Press right, hour will flash, press up to adjust hours,

10. Press right, minutes will flash, use up to adjust minutes,

11. Press Set.

12. 23 shows, Press left 2 flashes, press up twice 4 flashes,

13. Press right, 4 0511 shows, 05 flashes. This is the backlight time,

14. Press up until 30 flashes,

15. Press Set, it will now stay on for 30 seconds,

16. Press ESC to finish and return to normal screen.

Field SettingsField settings define how the unit will work, each system will have different settings.

1. Enter field settings by pressing down and Set for 6 seconds, I do this with the middle finger of both hands, it’s easier. 10 will show on the screen.

2. Press up once, 20 will be shown, press right, 2011 will show.3. To adjust this setting press right, the value will appear at the left of the screen, adjust it with the up and down buttons, to store

this value press Set.4. Press left to go back to 2011, press up to the next field setting and repeat from step 3. See below list.5. When you have finished all your 20 settings press left twice, 20 will show on the screen, press the up button to move to the 30s

and repeat the procedure from 2 above.

6. When finished or if you get lost press ESC to return to the normal screen

If your system is used to heat the house enter these settings into the unit

2011 -2

2012 +15

2021 45°C

2022

2091

37°C

3

low ambient setting for weather comp, -5 in Scotland and 3°C for hybrid systems

high ambient temp for weather comp

for U floor 50°C for rads, flow temperature in cold weather

flow temperature in mild weather

tells unit to look for a run signal on terminal B22 and enhances weather comp

If your system is heating a hot water cylinder enter these settings into the unit

3011 1 tells unit it has a cylinder connected

3025 Max cylinder heating time, 50mins for 200ltr, 90mins for 300ltr

3032 Delay before immersion starts, 30mins for 200ltr, 60mins for 300ltr

3042 W Wednesday day legionella happens (always use Wednesday) *

3043 3am time it happens

3044 60°C legionella temp

* It is possible to scroll through the days & select every day, then legionella can be run daily rather than weekly.

Legionella setting 3042 -3044 must be set to adhere to local regulation

Installation Manual.indd 23 31/08/2018 19:01:34

Page 24: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

24

Heating & Hot Water Installation

Cylinder Timer, if you are heating a hot water cylinderTo avoid the cylinder heating being switched off accidentally we normally add 2 on timers a day, one

at 3-00 am and one at 15-00 pm. This stops nuisance tripping, resets the unit after power cuts and

insures the cylinder is hot 24 hours a day. We don’t normally set any off times.

To set the cylinder up as above:

1. Press Timer button once,

2. Press right, daily is flashing, daily is the hot water time clock, press right

3. Press right 1 will show,

4. Press right,

5. On systems with a 12-hour clock, pm shows, press up till am and pm shows (24hours).

6. Press right, hours will be flashing, use up to set hours to 0300.

7. Press right, minutes will be flashing.

8. Press right, ON will be flashing. *

9. Press right, the tap will appear,

10. Press Set

You will return to 2 above. Now repeat with a timer at 15-00 hours.

You can delete or adjust timers by entering timer mode, press Timer once and scrolling up and

down to the timer you want to adjust, just keep scrolling right to the part you want to change and

then use up down to adjust it, then press Set to store. To delete a timer select it with up and down

and press Delete, to save the changes made press the Set button.

When you are finished press ESC.

Systems with Solar cylinder heatingWith solar systems its best to switch off the cylinder heating during the day to give the solar the best

chance of heating the cylinder for free.

*If you want to set an off timer at step 8 above, press up to change on to off.

Installation Manual.indd 24 31/08/2018 19:01:34

Page 25: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

25

Heating & Hot Water Installation

Electrically testing the unitThe unit has a function to test all the wiring without any tools, this is really useful to check everything has been set up correctly. Test

each component one at a time to check its ok.

Operation Button Display

Enter test mode – hold the left and right buttons together for 4 seconds

Run the water circulation pump (Terminal B8 live) – Press the red Heating on/off button leave this running

You should check flow rates here see below

Run the immersion heater (Terminal A3&A4) – press the Mode button (Heating)

Open Valve HW for hot water (Terminal B17 live) – press the Outing Button

Heating valve 1 is normally open (B10 live), to close valve for heating Zone 1 – press the Set button

Turn up your thermostats, when they come on heat will show. Indicating a run signal comes back from terminal B22

leave stats onOperate Zone 1 thermostat

Run the Hybrid Boiler (Terminal B6 live) – press the Silent button For hybrid systems only

Checking flow rateFirst you need to clean the filter balls. Shut the valve, undo the back of the valve, remove the strainer,

clean it and replace it then open the valve.

Press right and left button together for 6 seconds. The controller will display TEST or 7E57 or HEAT,

press the power on/off button to start the pump. When the pump is running you can see a picture

of a house with a circle around it

The unit will be running only in heating mode. Check the flow rate, we need 12l/min on the 5kW unit,

20l/min of flow on the 9kW unit and 30l/min on the 16kW unit. If there is not enough flow the unit

will never operate and it will give fault E911 you look into the flow meter you can see the flow in litres

per minute. The flow rate is the low figure, in this picture you can see a flow rate indicated, this shows

0l/min NOT 16l/min. Make sure you clean the filter ball, turn up all the pumps, open all the valves and

get rid of the air to keep flow rate up.

Testing the flow in Hot water mode, Clean the filter ball again. Press oval set button, 2-1 appears

on screen, the heating valve will close. Manually open the HW valve with the toggle and leave it open.

Now measure the flow rate through the cylinder. As above.

Exit test mode – press the ESC button to get back to normal display

Installation Manual.indd 25 31/08/2018 19:01:35

Page 26: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

26

Heating & Hot Water Installation

Starting the unit in heating modePress the power button (top left) AU or 0.0C will show, the unit is automatic mode using an external

run signal. Turn up your thermostats or underfloor heating to send a run signal to the unit, the pump

will start within 3 minutes, a little house with a circle around it appears in the status window, the

compressor in the outdoor unit starts after 3 minutes, you will see the symbol for the compressor in

the status screen. It’s a little milk churn with a C in it. The pipework will begin to heat up,

Check the flow temperature by pressing oval View button, it will show 4 sensors.

The house is the temperature at the remote controller which is not used.

The house with the circle around it is the water outlet temperature from the heat pump. The

Christmas tree is the air temperature outside. The tap is the cylinder temperature. If the outdoor unit

doesn’t start after 5-minutes, see problems page.

Over time the unit will warm up, now check all the radiators or under floor loops are hot as well.

Starting the System in hot water modeClean the filter balls again.

Press DHW on/off (power) button to start the unit, top right button.

A picture of a tap appears with dots by it, press Mode until 2 dots appear.

This means the HP will heat the water with help from the immersion.

Set the cylinder temperature press the oval Set button then press + until 48°C shows.

The heat pump will start heating the cylinder if its colder than 43°C and will heat it up to 50°C then it

will stop.

The unit will take up to 6 minutes to start in Hot water mode, be patient

When the unit is heating the cylinder, this coke can symbol shows on the controller.

The HW valve will open but the heating valve will not close for 40 seconds, this is normal.

Run test in hot water modeFirst check the blue tank sensor is above the immersion heater and at least 100 mm into the cylinder pocket. In hot water mode check

that the 2 ports are sending water into the hot water cylinder only, Press View until a picture of a tap appears, this is the hot water

cylinder temperature, note it down.

After 15 minutes of running check the hot water temperature again, it should have risen, again note the temperature. If the unit is

running well it should heat the cylinder to 48°C without needing the immersion heater. Now clean the filter ball again.

The Water storage temperature is lower (48°C) than a normal cylinder. It’s important to check that any shower or bath mixers do not

further reduce the water temperature. Using your thermometer check that the hot water comes out the tap at the same temperature

it leaves the cylinder. If it doesn’t you might need to make adjustments to taps mixers etc.. DON’T raise the cylinder temperature to

compensate.

Now handover the system to the end user, see page 7-11, fill in the warranty card on page 5 and online. Your system is now

fully commissioned, congratulations.

Installation Manual.indd 26 31/08/2018 19:01:36

Page 27: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

27

Troubleshooting

00 shows on the remote controller00 shows when the MIM control box is first powered up it means the MIM PCB has activated but no

outdoor unit can be seen. Check the F1 F2 wiring is ok between the outdoor and indoor unit and

check the outdoor unit has power.

01 shows on the remote controller01 means that the remote controller has power and it can see the outdoor unit too, this is good, in a

few seconds this will disappear.

E911 low flow alarmIf your flow rate is good (see above) but you see an E911 low flow alarm you need to test your flow

switch.

Remove paddle switch from the water, unplug the flow switch from the PCB. Get a multi meter and

switch it to ohms Ω setting. Insert the meter probes into the flow switch plug (See picture). It should

display infinity ∞ or OL. Wiggle the paddle your meter will beep or go to 0 Ohms.

This shows the paddle switch is ok. Now put it back in the water but leave the meter connected. With

the pump off you should see infinity ∞ or OL

Press right and left button together for 6 seconds. The controller will display TEST or 7E57, press the

power on/off button to start the pump. When the pump is running you can see a picture of a house

with a circle round it.

Your meter should beep or show 0 ohms with the pump running, if it doesn’t the water is moving too

slowly. Make it move faster.

Cold Weather Protection, my unit won’t startThe Samsung unit has a number of cold weather protection functions these include:

The heat pump cannot operate if the water in the system is less than 10°C, if the unit detects the heat

exchanger is less than 10°C it does two things:

Press the blue view button you can see 4 sensor readings, press it until the pump symbol shows (a

circle around a house). This is the water temperature, if it’s below 10°C the unit will not start but the

pump will run.

If you are commissioning the unit from cold

You must warm up the water to get the unit to run, the easiest way to do this is to add a cylinder and

use the immersion to warm up the cylinder first, the warm water from the cylinder will preheat the

heat pump and it will start to operate.

Installation Manual.indd 27 31/08/2018 19:01:36

Page 28: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

28

Troubleshooting

E904 Indicates a problem with the blue hot water cylinder sensor E904 only shows if field setting 3011 is set

to 1 (unit has a hot water cylinder)

To test this sensor, press the view button until the tap icon appears, this will show the temperature

its measuring, if this reading is -50 the sensor is not plugged into the yellow socket on the control box

PCB

E101, E102, E201E101 shows on the indoor unit remote controller if the indoor unit cannot see the outdoor unit.E202

shows on the outdoor unit if it can’t see the indoor unit This error appears if the power has been reset

to either unit or the outdoor unit is not on.

First wait 3 mins to see if the error disappears, if not remove the cover of the outdoor unit (the one

with Samsung written on it) and check the outdoor PCB display is lit up, If its not there is no power to

the outdoor unit.

If there is power at the outdoor unit check F1 F2 cable is connected to the indoor PCB and the outdoor

unit correctly, the cable must have no breaks or switches in it. If the cable is ok, it’s possible one of the

PCBs is at fault. The hardest thing for an engineer to do is work out which end has the communication

error.

In the middle of the control box (indoor unit) PCB there are two LEDs, the red one shows the

communication leaving the control box, the orange / green led shows the communication coming

back from the outdoor unit. If there is a comms error E201 one or both of the LEDs will not be lit

indicating which PCB is at fault.

E198 –thermal fuse brokenOn the control box PCB, bottom left corner are two sets of white wires, these are 2 thermal fuses stuck

to the bottom of the power and immersion heater terminals of the PCB, they are there to protect the

PCB in places where there are no RCDS and MCBs protecting the unit. They are not really required in

the UK as we have adequate external protection

The fuses measure the temperature of these terminals, they blow if the terminals get too hot or if

the terminals are tightened too much. They are very fragile and cant be replaced. If the either of the

thermal fuses blow the fault E198 shows.

To fix this fault you need a new PCB but, you can fix it by switching off the power, unplugging the

big plugs and cutting them off, you need to connect the wires together to simulate the fuse like this

below. This photo shows one of the links fixed, you need to do both of them.

E919 legionella failureIf the cylinder does not reach the legionella set temperature in 8 hours, E919 shows on the screen. The immersion heater is switched off

automatically. The unit stops. If you reset it (press on off ) the unit will run for another week then trip again.

Check 3041 =1, 3042 = Wednesday, 3043 =3AM, 3044 = 60°C

Check the immersion works, check the tank sensor is in the tank 100mm and is above the immersion heater. Check the tank thermostat

on the immersion is set to above 60°C.

Every Samsung heat pump fault code is now available on YouTube, search freedom heat pumps and the fault code and a simple to use

video will show you what you need to know.

Installation Manual.indd 28 31/08/2018 19:01:38

Page 29: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

29

What the unit comes with and what you will need

Below is a list of the components you will need to buy for each of the systems:

Flexible hoses

The water connections to the back of the unit are 1 inch BSP male. We recommend

connecting the water pipework with flexible hoses for ease of maintenance and to avoid any

vibration from the unit going into the house. All external pipework has to be insulated to meet

MCS standards.

Mounting feet

The outdoor units need to be mounted 100mm above the ground, we recommend using

rubber feet with unistrut channel. These come with mounting bolts included.

An expansion vessel, pressure gauge, pressure relief valve and filling loop

In pressurised heating systems most, heating engineers use a Robokit which combines all

these components into one box. The expansion vessel is sized the same way as when using

a boiler. If you want to run the system open vented you don’t need these components, the

Samsung units are happy to run at anywhere from 0 – 3Bar pressure

Pump

Your pump needs to supply 12l/min for the 5kW, 20l/min for the 9kW and 30l/min for the

16kW unit. Don’t use a 15/60 pump use at least a 15/75 . As a rough guide.

Assuming you use a plate exchanger for heating, 2 zone valves and 6 elbows, a filter ball, flow

meter and our 15-75 pump you can run measuring from the heat exchanger to the heat pump

20m separation on 22mm copper for the 5kW, 20 m separation on 28mm copper for the 9kW,

7.5m separation on 28mm copper for the 16kW

If you use a low loss header instead of a plate

30m separation on 22mm copper for the 5kW, 30 m separation on 28mm copper for the 9kW,

20m separation on 28mm copper for the 16kW

If your runs exceed this give us a call as you might need 2 pumps.

Water Filter

In all cases a strainer needs to be installed in the return to the heat pump. The filters ensure

that debris/foreign materials do not cause damage to the heat exchanger in the unit, voiding

warranties.

Flow switch and flow meter

The heat pumps have to have continuous uninterrupted flow at all times despite the loading

on the system, it is ideal to have a hydraulic break in the system like a buffer or a low loss

header. To measure that the flow is correct there is a paddle type flow switch which needs to

go into the primary pipework. The flow switch comes with the control box.

The flow switch is not IP65 rated (weatherproof) and so must not be installed externally. It can

be installed in either horizontally or vertically with at least 150mm of straight pipe either side,

connection is 1” female BSP. The wire is 2m long and needs to connect into the wiring station.

This wire can be extended to suit.

We recommend a flow meter is installed in every system rated 0-40l/min

Installation Manual.indd 29 31/08/2018 19:01:45

Page 30: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

30

What the Unit Comes With and What You Will Need

Diverter valves

If you require domestic hot water and heating, 2 x 2 port diverter valves are required, you need

to supply these and they need to be 28mm diameter.

Glycol / anti-freeze

In Monobloc heat pumps the water goes outside the building. The unit can protect itself from

freezing up, but if the power goes off there is a risk that the unit will freeze causing damage.

To prevent this, we recommend putting propylene glycol mixture in the system. It is important

that the glycol concentration is adequate to protect the unit, if the unit freezes up there will be

no warranty. Manufacturer dependant, a mix of 25% is normal for UK conditions.

Adding too much glycol is not a good idea as it increases the water pump power and slightly

reduces the capacity of your system.

Heat meters

If you are using more than one heat source, heat pump + boiler you MUST measure the heat

produced by the heat pump and the electricity used. This is essential for RHI. The heat meter

goes in the return to the heat pump with a sensor in the flow. The electricity meter must

measure only the power consumed by heat pump. See hybrid drawings.

The Cylinder

If you want to heat water with a heat pump you need a dedicated heat pump cylinder.

The cylinder needs to be installed less than 15m from the control box to allow for the

temperature sensor cable. Note the size and weight of the cylinder. Full installation

instructions will be included with the cylinder.

Ideally Cylinders should only be used IF the coil area is more than 2.5m2. Smaller coils give very

long recovery times and increase usage of the immersion heater. Cylinders can be pressurised

or open vented. We can work out the run cost for you if you tell us the coil size.

Installation Manual.indd 30 31/08/2018 19:01:46

Page 31: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

31

Wiring and Power Supply Information

PowerThe EHS system needs 2 power supplies:

Outdoor unit, 16 Amp for the 5kW, 20 Amp for the 9kW and 32 Amp for the 16kW.

The control box needs a 16 Amp supply, this wires into the top of the breaker (MCB) in the box. Many people remove the MCB from the

control box as there is already one in the distribution board. In this case wire Live to L1 and Neutral to N2.

The Immersion heater is connected into the control box terminals A3 Live and A4 Neutral; the control box controls the operation of the

immersion heater. If a fused spur is used it must be labelled “do not turn off” as switching it off will cause an error.

Communication cable must be run from the outdoor unit terminals F1 F2 to the control box, terminals F1 F2. Use 2 core flex 0.5-1mm

(its 16V AC). It must not have any breaks in it or switches.

Remote controller is normally installed next to the control box out of easy reach, it is mainly used for commissioning. You need to

supply a 2 core 0.5 – 0.75mm 2 core flex from F3 and F4 in the remote controller to F3 and F4 in the control box. Maximum distance is

100m.

Push the two hooks at the bottom of the Wired Remote Controller at the same time, and then pull up the front cover to separate it from

the rear cover

When you open the control box you will find all these wires:

The red safety sensors are not used and can be thrown away.

Red and blue sensors ARE NOT INTERCHANGEABLE.

The black cable with the red plug is not used and can be thrown away.

The red, white and brown cables are not used throw them away

Installation Manual.indd 31 31/08/2018 19:01:47

Page 32: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

32

Wiring and Power Supply Information

Pump The circulation pump must be wired Live to B8 and Neutral to B7, MAX pump power is 500 Watts. If two pumps are used wire them both

to these terminals.

The blue cylinder sensor plugs into a yellow socket CNS042 on the controller PCB and into

the cylinder in the top ½ of the cylinder. It must install above the immersion heater. You

must fix it so it can’t be pulled out of the cylinder. Keep it well away from any mains cables.

Thermostats/ timers and under floor heating manifolds

The heating is controlled with a field supplied room stat / setback stat, time clock or a run signal from an under floor manifold. B20 is

permanently 240V AC. The run signal goes into B22.

When using multi zone heating systems on a header, buffer or HEX

When the stat is made it will drive its zone valve open, inside the zone valve a switch links the orange to the grey wire when the valve is

open. We connect the grey to B20 permanent live and the orange to B22, the run signal. So when the valves open the heat pump will

run. NOTE the pump will run on for 1minute after the unit is told to stop. Hot water production is not affected and will always take

priority.

Valve Z2Power In

Valve Z1

Valve Z2

Valve Z1Pump Z1

Pump Z1

Run Signal to Heat Pump

B20 B22

B19 B22

Power In

Header, Buffer or

Heat Exchanger

Installation Manual.indd 32 31/08/2018 19:01:54

Page 33: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

33

How To Wire The Electric Meters

It is now a requirement to measure the electricity being used by the heat pump so the end user can see what the unit costs to run. We

provide a Smart Process electric meter with every unit. Ideally it should measure the total draw for the heat pump (outdoor and indoor

unit combined). The outdoor unit takes most of the current so in many installations it will only be used to measure the outdoor unit.

Valve Z2Power In

Valve Z1

Valve Z2

Valve Z1Pump Z1

Pump Z1

Run Signal to Heat Pump

B20 B22

B19 B22

Power In

Header, Buffer or

Heat Exchanger

Neutral fom mains and out to heat pump

Live to heat pump

Live from mains

Installation Manual.indd 33 31/08/2018 19:01:57

Page 34: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

34

Pump Z1

Other Heat Sources into coil

Buffer with Coil

Cylinder stat set at 55°C

Pump HPH Z1

Z1HW

Other Systems Possible With Samsung EHS

Multi Fuel

2 Heat Pumps

Combi Boiler

Board is waterproof and mounts outside behind the heat pump

Boiler must be set to run below 65°C

To HeatingPump Z1

Header or Buffer Tank

Heating & Hot Water

Heating Only

Flow and returns pumped by field supplied pump

Pump HPH

Z1

Z1

HW

Pump HP

Installation Manual.indd 34 31/08/2018 19:02:41

Page 35: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

35

Pump Z1

Other Heat Sources into coil

Buffer with Coil

Cylinder stat set at 55°C

Pump HPH Z1

Z1HW

Other Systems Possible With Samsung EHS

Pool Pump

Header, Buffer or

Heat Exchanger

Pump HP

Heating Pools

Hybrid Fast Connect

Combi Boiler

Board is waterproof and mounts outside behind the heat pump

Boiler must be set to run below 65°C

To HeatingPump Z1

Header or Buffer Tank

Heating & Hot Water

Heating Only

Flow and returns pumped by field supplied pump

Pump HPH

Z1

Z1

HW

Pump HP

Installation Manual.indd 35 31/08/2018 19:02:54

Page 36: Air Source Heat Pump Installation and Maintenance Manual · Air Source Heat Pump Installation and Maintenance Manual With Pre-Plumbed Cylinders & Underfloor Heating Model Numbers

Freedom Heat Pumps Ltd

Unit 2 Warrior Park,

Eagle Close

Chandlers Ford,

Hampshire

SO53 4NF

Tel: 02380 274 833

Email: [email protected]

Copyright © 2015Freedom Heat Pumps Ltd. All rights reserved.

Samsung is registered trademarks of Samsung Electronics Co.,

Ltd. Specifications and designs are subject to change without

notice. Non-metric weights and measurements are approximate.

All data were deemed correct at time of creation. Samsung is not

liable for errors or omissions. All brand, product, service names

and logos are trademarks and/or registered trademarks of their

respective owners and are hereby recognized and acknowledged. v310818

Installation Manual.indd 36 31/08/2018 19:02:54