Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
Installation use and maintenance manual
WSAN-XIN 21 - 71
Air cooled inverter heat pump for outdoor installation
M0R940L1-11 13-11-2012
2
Dear Customer, We congratulate you on choosing these product. Clivet is being working for years to offer systems able to assure the maximum comfort for long time with high reliability, efficiency , quality and safety. The target of the company is to offer advanced systems, that assure the best com-fort, reduce the energy con-sumption, the installation and maintenance costs for all the life-cycle of the system. With this manual, we want to give you information that are useful in all the phases: from the reception, to the installation and use until the disposal so that a system so advanced offers the best procedure of installation and use. Best regards and have a nice reading ! CLIVET Spa
3
1
2
3
4
General 4
Reception 7
Positioning 8
Water connections 10
Electrical connections 12
Start-up 21
Regulation 25
Maintenance 40
Technical information 48
Disposal 53
Residual risks 54
5
6
7
8
9
10
11
INDEX
The data contained in this bulletin is not binding and may be changed
by the manufacturer without prior notice.
4
1 - GENERAL
1.2 GENERAL INSTRUCTIONS
Preliminaries The positioning, hydraulic system, refrigerating, electrics and
the channelisation of the air must be determined by the
system designer in accordance with local regulations in force.
Only qualified personnel can operate on the unit, as required
by the regulation in force.
Using the unit in case of breakdown or malfunction :
• voids the warranty
• may compromise the safety of the machine
• may increase time and repair costs.
Follow local safety regulations. .
Keep packing material out of children’s reach it may be
dangerous. .
Recycle and dispose of packing material in conformity with
local regulations. .
Risk situations The unit has been designed and created to prevent injures to
people.
During designing it is not possible to plane and operate on all
risk situation.
Read carefully "Residual risk" section where all situation
which may cause damages to things and injuries to people
are reported.
Installation, starting, maintenance and repair required specific
knowledge; if they are carried out by inexperienced personnel,
they may cause damages to things and injuries people.
Intended use Use the unit for cooling/heating water or a water and glycol
mix for air-conditioning only, within limits defined in the
technical bulletin and on this manual..
Any use other than intended does not involve the
manufacturer in any commitment or obligation. .
Installation Verify that the electrical line characteristics are in compliance
with data quotes on the unit serial number label.
Maitenance Plan periodic inspection and maintenance in order to avoid or reduce repairing costs.
Turn the machine off before any operation.
Modification All unit modifications will end the warranty coverage and the
manufacturer responsibility. .
Breakdown/Malfuction Disable the unit immediately in case of breakdown or
malfunction. .
Contact a constructor certified assistance service.
Use original spares parts only.
User training The installer has to train the user on :
• start-up / shutdown;
• set points change;
• standby mode;
• maintenance;
• what to do / what not to do in case of breakdown.
Data update Continual product improvements may imply manual data
changes .
Visit manufacturer web site for updated data.
Keep this manual with the wiring diagram in an accessible
place for the operator.
Note the unit lable data so you can provide them at the assi-
stance centre in case of intervention (see "Unit identification"
section).
Provide a machine notebook that allows any interventions
carried out on the machine to be noted and tracked making it
easier to suitably note the various interventions and aids the
search for any breakdowns.
In case of breakdown or malfunction:
• immediately deactivate the unit .
• contact a assistance service centre authorized by the
manifacturer.
• use original spares parts only
Ask the installer to format on:
• start-up / shutdown;
• set points change;
• standby mode;
• maintenance;
• what to do / what not to do in case of breakdown.
1.3 INDICATIONS FOR THE USER
The manual provides correct unit installation, use and
maintenance.
Pay particolar attention to:
Warning identifies particularly important operations or
information .
Prohibited operations that must not be carried out, that
compromise the operating of the equipment or may cause
damage to persons or things.
• It is advisable to read it carefully so you will save time
during operations.
• Follow the written indications so you will not cause
damages to things and injuries people. The preliminary
information must be read prior to carrying out any of the
following operations.
1.1 MANUAL
5
1 - GENERAL
1.5 ACCESSORIES
CONFIGURATIONS
400TN Supply voltage 400/3/50+N
230M Supply voltage 230/1/50
HYDRAULIC CIRCUIT
GCEC High efficiency EC circulation group
- Hydronic group utility side: not required
KTFL1X Water connection hoses with 1"
ELECTRIC CIRCUIT
RCTX Remote control with keyboard room
CMACSX Domestic hot water module
CMSC2X Serial communication module with RS485 serial
converter kit
INSTALLATION
AMRX Rubber antivibration mounts
X : separately supplied accessories
1.4 UNIT INDENTIFICATION
Serial number label The serial number label is positioned on the unit and allows to
indentify all the unit features.
It has not to be removed for any reason.
It reports the regulations indications such as:
• machine type, exmple:
Series WSAN-Xin
Size 21...41...
• serial number
12 characters Axxxxxxxxxxx
• year of manufacture
• wiring diagram number
• electrical data
• manufacturer logo and address .
Serial number It identifies uniquely each machine.
It identifies specific spare parts for the machine.
Assistance request
Note data from the serial number label and write them in the
chart on side, so you will find them easily when needed.
In case of intervention you have to provide data.
Serie
Size
Serial number
Year of manufacture
Wiring diagram
6
1 - GENERAL
1.6 DESCRIPTION UNIT
HIGH SEASONAL EFFICIENCY: Guaranteed by DC Inverter
technology applied on the compressor, with which the speed
can be modulated depending on the real energy requirement.
This solution further reduces consumptions and increases the
seasonal efficiency considerably, especially during partial load
situations, which coincide with the longer operation time of the
unit.
EUROVENT CLASS A: ELFOEnergy Extended Inverter
obtained Eurovent Energy Efficiency Class A in heating
mode for the use in systems provided with radiant panels and
traditional systems provided with terminal units.
CUTTING EDGE TECHNOLOGY: The constant drive for
improvement led Clivet introducing special constructive
features in ELFOEnergy Extended Inverter: the hydrophilic
coil ensures efficiency in any conditions, thermostatic
electronics optimises the cooling circuit operation with DC
Inverter compressor, the water kit simplifies the hydronic
circuit and facilitates maintenance. The unit can be equipped
with DC Inverter circulator (optional), which guarantees
further energy saving thanks to the modulation of the water
flow-rate depending on the load and pressure drops of the
system.
MAXIMUM SILENT OPERATION: ELFOEnergy Extended
Inverter is at the top of its class, due to an optimised profile of
the fan and modulation of both the fan and compressor,
according to the outdoor conditions and load of the system.
COMPACT DIMENSIONS: The constant research in the
product industrialisation allowed to manufacture a very
compact unit, which is the essential factor to meet the
aesthetic requirements and extremely flexible to adapt to the
features of any building.
per adattarsi alle caratteristiche di qualsiasi edificio.
A condensate water draining
B hydraulic pipes
C power supply
D 3-way valve (Not Provided )
E ELFOControl2
F domestic hot water module(option)
G probe tank (with tank)
H electrical resi stance (Not Provided )
I acqueduct
L ambient keyboard (option)
7
Operate in compliance with safety regulations in force .
2.1 PRELIMINARY INFORMATION
Before accepting the delivery you have to check:
• That the unit hasn’t been damaged during transport.
• Check that the materials delivered correspond with that
indicated on the transport document comparing the data
with the identification label ‘A’ positioned on the
packaging.
In case of damage or anomaly:
• Write down on the transport document the damage you
found and quote this sentence: "Conditional acceptance
— clear evidence of deficiencies/damages during
transport".
• Contact supplier and the carrier by fax and registered mail
with advice of receipt.
Any disputes must be made within the 8 days following the
delivery. Complaints after this period are invalid..
2.2 DELIVERY CONTROL
2.4 HANDLING
2- RECEPTION
Observe external packing instructions .
2.3 STORING
Verify unit weight and handling equipment lifting capacity .
Use single protection devices.
A
0
?
??
Identify critical points during handling (disconnected routes,
flights, steps, doors).
SIZE 21 31 41 51 71
Length mm 895 895 895 Depth mm 378 378 378 Height mm 992 992 992 Operating weight kg 112 116 124 Shipping weight kg 110 114 122
1038 410
1234 170 168
1038 410
1234 175 173
2
3
4
1
Be careful not to damage the unit.
Recycle and dispose of packing material in conformity with
local regulations.
2.5 PACKING REMOVING
Before handling verify that the unit keeps its balance.
Use protection to avoid the unit damaging .
8
3.1 PRELIMINARY INFORMATION • install flexible joints on the hydraulic.
A correct circulation of the air is indispensible to guarantee the
good working order of the machine.
Avoid therefore:
• obstacles to the airflow;
• exchange difficulties;
• leaves or other foreign bodies that can obstruct the
exchange batteries;
• winds that hinder or favour the airflow;
• heat or pollution sources close to the unit (chimneys,
extractors etc);
• stratification (cold air that stagnates at the bottom);
• recirculation (expelled air that is sucked in again);
• positioning below the level of the threshold, close to very
high walls, attics or in angles that could give rise to
stratification or recirculation phenomenons.
Ignoring the previous indications could:
• energy efficiency decrease;
• blocks due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter).
3.2 SPAZI FUNZIONALI
3.3 POSITIONING
Functional spaces are designed to:
• guarantee good unit operation
• carry out maintenance operations
• protect authorized operators and exposed people
Respect all functional spaces indicated
Double all functional spaces if two or more unit are aligned.
Units are designed to be installed:
• EXTERNAL
• in fixed positions.
Choose the installation place according to the following
criteria:
• Customer approval
• safe accessible position
• technical spaces requested by the unit
• spaces for the air intake/exhaust
• max. distance allowed by the electrical connections
• control points with capacity adequate to the unit weight
• condensate water draining
Prefer places where the unit doesn't disturb the neighbours.
Avoid installations next to bedrooms or windows.
Avoid snow accumulations on batteries.
Avoid installations in places subject to flooding
In case of ground installation provide a raised base to avoid
flood damages.
Limit vibration transmission:
• use antivibration devices on unit bearing points;
3 - POSITIONING
100
150
500
AB
C
Keep the min. distances from the podestrian areas.
Avoid snow (A) accumulations on batteries
Install the unit raised from the ground (B)
Provide a protection (C)
9
3 - POSITIONING
3.4 CONDENSATE WATER
When a heat pump is running it produces a considerable
amount of water due to the defrosting cycles of the external
coil.
The condensation must be eliminated in a manner to avoid
wetting pedestrian areas.
The unit anti-freeze electric resistance prevents the ice from
forming inside the tray.
With extensive very cold outdoor temperatures, condensation
could freeze outside the unit blocking the flow and causing a
slow build-up of ice; therefore special attention must be paid
to eliminating condensation, raising the unit off the ground and
evaluating whether antifreeze elements should be installed.
A Drain pan
Unit support
Condensate discharge connection Ø 13
B
C
C Provide windbreaks in locations with strong winds
Connection of the condensate discharge Ø 13 C
A
B
C
10
4 - WATER CONNECTIONS
4.1 PRELIMINARY INFORMATION
CUT-OFF VALVES
• Installed at inlet and outlet (both on the water technique
circuit as well as that of the hot domestic water) allow
maintenance operations without having to empty the
system .
THERMOMETERS AND MANOMETERS
• Installed at entry and exit of the main elements facilitate
inspection and maintenance.
AIR BLEED VALVE
• Installed in all of the highest points of the system allowing
the venting of the circuits air..
DRAINAGE TAPS
• Installed in the lowest points of the system to allow
bleeding.
EXPANSION TANK
• It keeps a correct system pressure when the water
temperature changes. It must be dimensioned as a
function of water plant volume and temperature.
SUPPORTS
• The hydraulic pipes weight mustn’t burden on the unit
connections .
ANTIVIBRATION JOINTS
• They avoid the vibration transmission on water connections
INERTIAL STORAGE TANK
• is necessary in the event of the following :
- the water in the system is very low
- the unit will not be used in a private house (in an
industrial process or other)
4.3 OPERATION SEQUENCE
1. Execute leakage test
2. Carefully wash the system by filling it and emptying it
several times with clean water.
Ignoring this operation will lead to several filter cleaning
interventions and at worst cases can cause damages to
the exchangers and the other parts.
3. Prepare anti-freeze solution if required
4. Fill the plant
5. vent the plant
6. Isolate the pipes to avoid heat dispersions and formation
of condensate isolate all the pipes.
Leave various point of service free (wells, vent-holes etc ).
4.4 WATER QUALITY
The water quality is determined by the following factors, avoid
therefore:
• Inorganic salts
• pH
• Biological load (seaweeds etc)
• Suspended solids
• Dissolved oxygen Water with inadequate characteristics can cause:
• pressure drop increase
• energy efficiency decrease
• corrosive symptom increase
The unit is equipped with an antifreeze function that activates
the circulator with water temperature < of 5°C.
The function is active only if the unit is on.
For greater safety if the unit or the relative water connections
can be subject to temperatures close to 0°C adopt measures
for prevent risk of freeze.
For example:
• Mix water with ethylene glycol
• Safeguard the pipes with heating cables placed under the insulation
• Empty the system in cases of long non-use and check that:
• there are no closed taps present that could trap water even after emptying
• there are no low points in which water can stagnate even after emptying; carry out any blowing required .
4.5 RISK OF FREEZE
4.6 ANTI-FREEZE SOLUTION
Consider that the use of anti-freeze solution determines an
increase in a pressure drop.
Make sure that the glycol type utilized is inhibited (not
corrosive) and compatible with the hydraulic circuit
components (pump etc).
Do not use different glicol mixture (i.e. ethylene with
propylene)
Selection and installation of system components must be
carry out by installer.
Following you will find some indications to integrate with what
is provided by the local regulations in force and by the good
technical laws.
4.2 RECOMMENDED COMPONENTS
11
4 - WATER CONNECTIONS
4.7 RECOMMENDED CONNECTION
IN
OUT
WATER FILTER
• Must be installed immediately in the water input of the unit,
in a position that is easily accessible for cleaning.
• The filter never should be removed, this operation
invalidates the guaranty
G
F
D
C
B
A Vent
Circulator
Output probe
Safety valve ( 6 bar )
Flow switch
Input probe
H Water discharge
E
A vent
B pump
F flow switch
D safety valve
E user side exchanger
H discharge cock
Plate exchanger
1. antivibration joints
2. supports
3. filter
4. cut-off valves
5. expansion tank
6. pressure switch/thermometer
7. filling valve
8. inertial storage tank
12
5 - ELECTRICAL CONNECTIONS
1
2
3
4
5
6
A, B : Ø 22 mm C : Ø 34 mm
Install the isolator switch near the unit.
The characteristics of the electrical lines must be determined
by specialized personnel able to design electrical installations;
moreover, the lines must be in conformity with regulations in
force.
The protection devices of the unit power line must be able to
stop the presumed short circuit current, whose value must be
determined in function of system features.
The power cables and the protection cable section must be
defined in accordance with the characteristics of the
protections adopted. All electrical operations should be
performed by trained personnel having the necessary
requirements by the regulations in force and being informed
about the risks relevant to these activities.
Operate in compliance with safety regulations in force .
5.1 PRELIMINARY INFORMATION
The serial number label reports the unit specific electrical
data, included any electrical accessories .
The electrical data indicated in the technical bulletin and in the
manual refer to the standard unit, accessories excluded.
Refer to the electrical data report on the serial number label.
5.2 ELECTRICAL DATA
5.3 CONNECTIONS
1. refer to the unit electrical diagram (the number of the diagram is shown on the serial number label)
2. verify that the network has characteristics conforming to the data shown on the serial number label
3. Before starting work, verify that the sectioning device at the start of the unit power line is open, blocked and equip-ped with cartel warning
4. Primarily you have to realize the earthing connection 5. Shelter the cables using adequate measure fairleads
5.5 ELECTRIC LINES INLET
5.4 SIGNALS / DATA LINES
Do not overpass the maximum power allowed, which varies, according to the type of signal. Lay the cables far from power cables or cables having a different tension and that are able to emit electromagnetic disturbances. Do not lay the cable near devices which can generate electromagnetic interferences.Do not lay the cables parallel to other cables; cable crossings are possible, only if laid at 90°. Connect the screen to the ground, only if there aren’t disturbances in only one point. Guarantee the continuity of the screen during the entire extension of the cable. Respect impendency, capacity and attenuation indications.
Fix the cables: if vacated may be subject to tearing.
The cable don't have to touch the compressor and the
refrigerant piping ( they reach high temparatures ).
F.L.A. full load ampere Full load current at max admissible conditions
F.L.I. Full load input Full load power input ( at max. admissible condition )
serial number label
VOLTAGE
FLA (A)
FLI (kW)
CMACSX
R
If the DHW module is present, consider the electric resistance absorption in the power supply line dimensionino.
CBA
6. Before power the unit, make sure that all the protections that were removed during the electrical connection work have been restored.
13
5.6 ELECTRICAL PANEL
AP1 Main control module
AP2 Electronic thermostatic management board
AP4 Fan control module
AP6 RS 485 module (optional)
C1 / C2 Fan condenser
T1 Transformer
5 - ELECTRICAL CONNECTIONS
FU2 Aux. circuit protection fuse
KA1 Aux. relay of inverter alarm
KA2 Compressor control relay
KA3 Control relay of the circulating pump
XT1 Terminal block of the Customer connections
FU1 Fuse
INPUTS INPUTS
RS485 A Signals B Power supply C
230/1/50 400/3/50+N
A B C A B C
14
5 - ELECTRICAL CONNECTIONS
5.7 CUSTOMER CONNECTIONS
1 Unit
2 Customer connections
3 Only for size 21-41
4 Only for size 51-71
A fuses (provided by the Customer)
B isolator switch (provided by the Customer)
FU1 fuses
QG electrical panel
KA3 relè
XT1 terminal block of the Customer connections
ALM alarm
AP7 ambient keyboard
SA2 remote SUMMER-WINTER
SA1 remote ON-OFF
M8 pump utility
1
2
230/1/50
14 61 81
M8
CN1-7 CN1-14 CN1-12 CN2-6 +12VDC SIGN GND CN2-7 CN2-8
SA1 SA2
3 4
ALM
1
2
400/3/50+N
14 61 81 CN1-7 CN1-14 CN1-12 CN2-6 +12VDC SIGN GND CN2-7 CN2-8
M8
SA1 SA2
ALM
15
QG unit electrical panel
XT1 Terminal block of the Customer connections
AP7 ambient keiboard
A Max. = 100 mt.
Cable section: Min. 0,35 Max.1 mm2
5 - ELECTRICAL CONNECTIONS
5.9 REMOTE CONTROL WITH AMBIENT KEYBOARD ACCESSORY PER90002 (RCTX)
CMACSX
137
96.
5
31.3
Ø 4mm
Ø 4mm
60
8460
LAN net: A + B = 100 mt. Max
CMACSX : DHW module
A
B
A
AP7
SA1 ON - OFF REMOTO
set parameter CL43 :
CL43 = - 2 SA1 = ON-OFF remote
hour scheduling enabled
CL43 = - 1 SA1 = standby remote (see * pag 27)
hour scheduling disabled
CL43 = -28 SA1 = only Domestic Hot Water remote
SA1 ON = DHW + system
SA1 OFF = only DHW
SA2 SUMMER - WINTER REMOTE
set parameter CL44 :
CL44 = 0 SA2 = disabled
CL44 = -3 summer - winter remote
change from keyboard disabled
SUMMER WINTER
16
5 - ELECTRICAL CONNECTIONS
5.8 SERIAL PORT RS485 WITH MODBUS PROTOCOL ACCESSORY PE1P0005 (CMSC2X)
seriale TTL
QUADRO ELETTRICO
AP6
AP1
XT1
1 Install the AP6 converter
2 Connect TTL serial
3 Wire as indicated in the wiring diagram.
Supervisory
The unit can be connected to an external supervisory system.
Enable the function:
Par CF01 protocol selection 0 = Disabled 1 = Modbus
CABLE CHARACTERISTICS Couple of twisted and shielded conductors
Section of the conductors 0.22mm2…0,35mm2
Nominal capacity among the conductors < 50 pF/m
Nominal impedance 120 Ω Recommended cable Belden 3105A or others with equal properties.
Parameter Description Range
CF30 ModBus address
1….255
CF31 BaudRate Baud Rate (0=1200 / 1=2400 / 2=4800 / 3=9600 / 4=19200) supervision serial
Main menu
Parameters
CF
CF01
Parameters modification
XT1
17
5 - ELECTRICAL CONNECTIONS
5.10 DOMESTIC HOT WATER MODULE ACCESSORY PER90001 / 3 (CMACSX)
CMACSX1 DHW module ( L.300 x P.220 x H.120 )
2 Water temperature probe Cable length 5 mt BT7
3-way valve
accessory 3DHWX
B C D Max. = 100 mt.
Cable section: Min. 0,35 Max. 1 mm2 Electric heater provided by the customer
CMACSX
LAN net: A + B = 100 mt. Max
CMACX : DHW module
A
B
CMACSX
BT7
R
LINE INPUT
D C
B
The resistance R can operate simultaneously to the
compressor.
Eg:
• antilegionella scheduling
• BT7 < (setpoint ACS - 19°C)
18
5 - ELECTRICAL CONNECTIONS
QG unit electrical panel
XT1 terminal block of the Customer connections
B LAN serial : L max = 100 mt
Cable section: Min. 0,35 Max. 1 mm2
YVACS DHW valve (accessory 3DHWX)
BT7 DHW storage probe
R6 Electric heaters of the DHW storage (provided by the
Customer)
ST storange high temperature safety thermostat
PER90001 - 230/1/50
B
B
PER90003 - 400/3/50+N
81
61
CN2-6
GND
SIGN
+12VDC
XT1
81
61
CN2-6
GND
SIGN
+12VDC
XT1
19
5 - ELECTRICAL CONNECTIONS
It is possible to automatically change the set-point according
to the outside temperature.
Enable the function:
Par dS00 set-point compensation of the outside temp.
0 = Disabled 1 = Proportional 2 = Fixed (by step)
5.11 WATER SET POINT COMPENSATION WITH EXTERNAL TEMPERATURE
Main menu
Parameters
dS
dS00
Parameter modification
COOLING
t ext °C
dS01 < 0
dS03
dS05 Setpoint
dynamic
differential
Example :
dS01 = - 6°C
dS03 = 4°C
dS05 = 36°C
setpoint = 10°C
Compensated setpoint = 14°C
t ext °C36°C 30°C
14°C
10°C
setpoint
Cool description
dS01 Differential proportional zone in Cool on external air
dS03 Max water set dynamic differential in Cool
dS05 Set point dynamic differential of external air
With low ext. temperature the refrigerant requirements are
reduced.
The internal comfort can also be obtained with a set-point
higher than standard.
20
5 - ELECTRICAL CONNECTIONS
HEATING
Example :
dS02 = 20°C
dS04 = - 7°C
dS06 = -5°C
setpoint = 35°C
Compensated setpoint = 28°C
t ext °C
15°C -5°C
35°C
28°C
setpoint
dS02 > 0
dS04 t ext °C
dS06 Setpoint
dynamic
differential
Heat description
dS02 Differential proportional zone in Heat on external air
dS04 Max water set dynamic differential in Heat
dS06 Set point dynamic differential of external air
5.12 WATER SET POINT COMPENSATION WITH
AMBIENT TEMPERATURE
Only with ambient keyboard option .
Function and parameters are the same of 5.11 paragraph.
On the ambient keyboard set parameter Cr 30 = 10
It is possible enable ambient compensation OR external
compensation, not ambient AND external compensation.
With outside mild temperatures the thermal requirements are
reduced.
The internal comfort can also be obtained with a lower set-
point.
21
6 - START-UP
PRELIMINARY CHECKS
To check before starting-up the unit . For details refer to the different manual sections.
√ Preliminary checks - Unit OFF power supply
Access in safety
Functional clearances
Air flow : free return and supply (no bypass, no stratification)
Structure integrity
Fans run freely
Unit on vibration isolators
Unit input water filter + shut-off valves for cleaning
Vibration isolators on water connections
Expansion tank (indicative volume = 5% system content)
Cleaned system
Loaded system + possibile glicole solution + corrosion inhibitor
Under pressure system
Vented system
Refrigerant circuit visual check
Earthing connection
Power supply features
Electrical connections provided by the customer
22
If present
6 - START-UP
√ Start-up sequence - Unit ON power supply
Compressor carter resistances operating at least since 8 hours
Off-load voltage measure
Phase sequence check (unit only 400/3/50)
Unit ON
Load voltage measure and absorptions
Check of all fan operating
Measure of return and supply water temperature and flow valutation
Super-heating and sub-cooling measure and discharge temperature
Check no anomalous vibrations are present
Set-point personalization
Impostare data e ora
Personalise scheduling
Personalise DHW *
Climatic curve personalization
Complete and available unit documentation
Set ambient keypad *
START-UP SEQUENCE
Operations to perform to start-up the unit. For details refer to the different manual sections.
*
23
6 - START-UP
Weight of glycol (%) 10 20 30 40
Freezing temperature (°C) -4 -9 -15 -23
Safety temperature (°C) -1 -4 -10 -19
6.1 PRELIMINARY INFORMATION
The indicated operations should be done by qualified
technician with specific training on the product.
Upon request, the service centres performing the start-up; the
electrical, water connections and the other system works are
by the installer.
Agree upon in advance the star-up data with the service
centre.
Verify that the unit is connected to the ground plant
Check the conductors tightening: the vibrations caused by
handling and transport might cause loosing
Feed the unit by closing the sectioning device, but leave it on
OFF.
Check the tension and line frequency values which must be
within the limits :
single-phase unit: 230 +/- 10%
three-phase unit : 400 +/- 10% Unit only three-phase:
Control the unbalancing of the phases
it must be lower than 2%
Example:
6.2 PRELIMINARY CHECKS
6.4 REFRIGERANT CIRCUIT
6.3 HYDRAULIC CIRCUIT
6.5 ELECTRICAL CIRCUIT
Before checking, please verify the following :
• the unit should be installed properly and in conformity with this manual.
• the electrical power supply line should be sectioned at the beginning.
• The line sectionalizing device is open, locked and equipped with the suitable warning
• make sure no tension is present
1. Check carefully the refrigerating circuit: the presence of oil
stains can mean leakage caused by transportation,
movements or other).
2. Verify that the refrigerating circuit is in pressure: Using the
unit manometers , if present, or service manometers.
3. Make sure that all the service outlets are closed with
proper caps; if caps are not present a leak of refrigerant
can be possible.
1. Before realizing the unit connection make sure that the
hydraulic system has been cleaned up and the clearing
water has been drained
2. Check that the water circuit has been filled and
pressurized
3. Check that the shut-off valves in the circuit are in the
"OPEN" position.
4. Check that there isn’t air in the circuit, if required,
evacuate it using the air bleed valve placed in the system
high points.
5. When using antifreeze solutions, make sure the glycol
percentage is suitable for the type of use envisaged. The working out of the limits can cause irreversible damages
and voids the warranty.
6.6 COMPRESSOR CRANKCASE RESISTANCES
Connect the oil resistances on the compressor crankcase at
least 8 hours before the compressor is to be starter :
• at the first unit start-up
• after each prolonged period of inactivity
1. Supply the resistances switching off the unit isolator
switch.
2. To make sure that hte resistances are working, check the
power input .
3. At start-up the compressor crank-case temperature on the
lower side must be higher at least of 10°C than the outside
temperature.
Do not start the compressor with the crankcase oil below
operating temperature.
L1 L2 L3
388 V
379 V
377 V
388 + 379 + 377
3= 381
388 (max) – 381 = 7
7
381x 100 = 1,83 OK
1)
2)
3)
24
6 - START-UP
Check that the air and water temperatures are included in the working limits
For information on the control system, refer to the paragraph CONTROL.
Start the unit
With unit of full load, namely in stable conditions and close to those of work, check :
• Power supply tension
• Total absorption of the unit
• Absorption of the single electric loads
6.6 TENSIONS
6.8 STARTING REPORT
Realize the operating objective conditions is useful for check
the unit over time.
With unit of full load, namely in stable conditions and close to
those of work, take the following data:
• Tension and general absorptions with unit at full load
• Absorption of varied electrical loads (compressors, fans, pumps etc)
• Temperatures and capacities of different liquid (water, air) in the inlet and outlet of the unit
• Temperatures and pressures on the refrigerant circuit characteristic points (compressor discharge, liquid, intake)
The remarks should be preserved and available during maintenance .
97/23 CE PED DIRECTIVE gives instructions for installers, users and maintenance technicians as well.
Refer to local actuation norms; briefly and as an example, see the following
• Compulsory verification of the first installation :
only for units assembled on the installer’s building site (for ex. Condensing circuit + direct expansion unit)
• Certification of setting in service :
for all the units
• Periodical verifications:
to be executed with the frequency indicated by the manufacturer (see the maintenance section)
6.9 CE 97/23 PED DIRECTIVE
• Check that the remote commands (ON-OFF, etc.) are connected and if necessary enabled with the relevant parameters as described in ELECTRICAL CONNECTIONS section
• Check that probes or optional components are connect and enable with the relative parameters( ELECTRICAL CONNECTION section)
6.7 REMOTE CONSENT
25
7 - CONTROL
ACTION
UP
- increases the value
- next voice - Silenced alarm
DOWN
- decreases the value
- previous voice - On / Off *
ESC
- esc WITHOUT SAVING MODIFICATIONS
- previous level mode - Heat / cool / stdby / as
SET
- confirm
- esc WITH MODIFICATION SAVING
- go to the next level
- STATA menu
- Inputs / clock / stby / active alarms / setpoint
+ - activate / disactivate the time bands
+ - access to the SETTING menu - Parameters / function /
password / alarms
FUNCTION (3 SEC)
icon fixed on flashing icon
Alarm on progress Silenced alarm
Capacity step
Heating mode
Antifreeze with active heat pump Remote heating mode
Primary circuit water pump
Cooling mode Remote cooling mode
ventilation
Standby from keypad Remote standby
LAMP TEST
At the start-up is performed a board automatic test :all the led flash for some seconds
Automatic defrosting Manual defrosting activated
ON : Domestic hot water flashing : D.H.W. mode - standby
Clock active scheduling
Clock setting scheduling
heater ON - D.H.W.
Not used 4
7.1 DISPLAY
* Unit in OFF the antifreeze function is not active.
26
7 - CONTROL
2 SEC
HEAT heat
COOL cool
StdBY standby - off
Pag.27 AS Domestic hot water
OPERATING MODE
Ai, di, AO, dO Inputs, outputs
CL clock
AL Active alarms
Pag.34 SP setpoint
STATA
+
PAR - parameters configuration
Fnc - functions
dEF - manual defrosting
tA - alarm reset
St - on / off
CC - copy card
EUr - alarm log reset
PASS - password
Pag.29 EU - alarms Alarm log
SCHEDULING
7.2 NAVIGATION
27
7 - CONTROL
CLOCK SETTING display
press
Ai
selct CLOCK menu /
CL
access
Hour
choose among :
- hour : HOUR
- date : DATE
- year : YEAR /
YEAR
confirm ! Value flashing !
3 sec ! 2010 !
set the value /
! 2011 !
confirm
2011
back to the previous menu
CHANGE THE OPERATING MODE display
press 2 sec
COOL
choose among - standby, off :STBY
- cool : COOL
- heat : HEAT
- DHW : AS
/ HEAT
confirm
WATER SETPOINT MODIFICATION display
press
Ai
select SP menu /
SP
access
COOL
choose among :
- COOL
- HEAT
- AS /
AS
confirm
50
set the value /
55
confirm
55
back to the previous menu
DISPLAY OF INPUTS - OUTPUTS display
press
Ai
choose among
Ai : analogical inputs
di : digital inputs
AO : analogical outputs
dO : digital outputs
/ di
access
diL1
press to see the value for digital inputs :
0 = input not active - open
1 = input active - closed
scroll the list /
diL4
ON - OFF display
press
3 sec OFF
press
3 sec ON
Off the unit is immediately stopped without respecting any timing.
Stanby the antifreeze function is active ( pump ON for water temperature < 4°C )
The circulator anti-blocking function is active ( pump ON at predefined intervals)
*
28
7 - CONTROL
ALARMS RESET display
press +
PAr
select FnC /
FnC
press
dEF
select tA /
tA
press
back to the previous level
ALARMS display
press
Ai
select ALARM menu /
Al
access to the 1° active alarm
Er01
scroll the other active alarms
/ Er07
back to the previous level
ALARM LOG display
press +
PAr
select EU /
EU
last registered alarm
EU00
access to alarm code info
Er01
hour of the alarm /
20:01
date of the alarm /
27.10
alarm output hour example : alarm still active
/ --:--
alarm output date example : alarm still active /
--:--
back to the previous level
type of alarm : - AUto - MAnu /
AUto
SILENCED ALARM display
the alarm code is flashing Er01
alternated to temperature 13.5°C
fixed ALARM led
press any button
/
ALARM led is flashing ! !
ALARMS LOG RESET display
press +
PAr
select FnC /
FnC
press
dEF
select EUr /
EUr
press 3 SEC.
YES
back to the previous level
29
7 - CONTROL
Label Acronym meaning (label) Parameters of:
CL Configuration Local Local I/O Configuration
CE Configuration Expansion Expansion I/O Configuration
Cr Conriguration Remote terminal Remote terminal I/O Configuration
CF ConFiguration Configuration
Ui User interface User interface
tr thermoregulation Thermoregulation
St Stati (Modi di funzionamento) Operating stata
CP ComPressori Compressor
PI Pump (Internal) Primary circuit water pump
FI Fan (Internal) Not used
FE Fan (External) Fans (external) of the disposable exchanger
PE Pump (External) Not used
Hi Electric Heaters (Internal) Electric heaters of the primary exchanger
HE Electric Heaters (External) Not used
HA Auxiliary Output Not used
br boiler Not used
dF deFrost Defrosting
dS dynamic Setpoint Dynamic Setpoint
Ad Adaptive Adaptive (adaptive function)
AF AntiFreeze Antifreeze
AS Acqua Sanitaria, Anti-Legionella Domestic hot water, Anti-Legionella
HP Heat Pump Not used
PL Power Limitation Not used
tE Time Events Time bands
AL ALarm Alarms
SETTING menu - PAR (configuration parameters)
30
Hour tE31 tE59 tE87 Minutes tE32 tE60 tE88
Mode 0= on 1= standby tE33 tE61 tE89
Cooling temperature tE34 tE62 tE90
Heating temperature tE35 tE63 tE91
DHW temperature tE36 tE64 tE92
Hour tE24 tE52 tE80 Minutes tE25 tE53 tE81
Mode 0= on 1= standby tE26 tE54 tE82
Cooling temperature tE27 tE55 tE83
Heating temperature tE28 tE56 tE84
DHW temperature tE29 tE57 tE85
Hour tE17 tE45 tE73 Minutes tE18 tE50 tE74
Mode 0= on 1= standby tE19 tE47 tE75
Cooling temperature tE20 tE48 tE76
Heating temperature tE21 tE49 tE77
DHW temperature tE22 tE50 tE78
7 - CONTROL
Main menu Parameter modification
Parameters
tE
tE00
It is possible to set 3 different schedulings. To each schedulino is possible to associate 4 events. To each day of the week is possible to associate a scheduling. In the example the schedulings have been assigned: scheduling 1 Monday, Tuesday, Wednesday scheduling 2 Thursday, Friday scheduling 3 Saturday, Sunday
Day Scheduling
1 Scheduling
2 Scheduling
3
Monday tE01 = 1 - -
Tuesday tE02 = 1 - -
Wednesday tE03 = 1 - -
Thursday - tE04 = 2 -
Friday - tE05 = 2 -
Saturday - - tE06 = 3
Sunday - - tE07 = 3
Description Event 1 Event 2 Event 3
Hour tE10 = 07 tE17 = 12 tE24 = 16
Minutes tE11 = 00 tE18 = 00 tE25 = 30
Mode 0= on 1= standby tE12 = 0 tE19 = 0 tE26 = 0
*Cooling temperature tE13 = - tE20 = - tE27 = -
*Heating temperature tE14 = 20 tE21 = 22 tE28 = 22
DHW temperature tE15 = 45 tE22 = 45 tE29 = 55
Scheduling 1
Event 4
tE31 = 22
tE32 = 00
tE33 = 0
tE34 = -
tE35 = 18
tE36 = 45
In the following example the scheduling 1 schedules: at 07:00 changes the heating set-point at 12:00 changes the heating set-point at 16:30 changes the DHW set-point at 22:00 changes the heating set-point and DHW
Sched. 1
(par.) Sched.2
(par.) Sched.3
(par.)
Hour tE10 tE38 tE66 Minutes tE11 tE39 tE67
Mode 0= on 1= standby tE12 tE40 tE68
Cooling temperature tE13 tE41 tE69
Heating temperature tE14 tE42 tE70
DHW temperature tE15 tE43 tE71
Eve
nt
2
Eve
nt
3
Eve
nt
4
Eve
nt
1
* If the unit is in Cooling is used the cooling temperature. * If the unit is in Heating is used the heating temperature.
7.3 SCHEDULING MANAGEMENT
To enable the hour scheduling :
Par tE00 hour scheduling 0 = disabled , 1 = enabled Par CL43 = -2 (see pag 15)
31
7 - CONTROL
The scheduling can be programmed for each day of the week. Parameter : AS20 antilegionella set-point AS04 DHW hysteresis
ANTILEGIONELLA SCHEDULING
Day Cycle duration (0= OFF
from 1 to 24 hours)
Hours Minutes
Monday AS25 = 0 AS26 AS27
Tuesday AS28 = 0 AS29 AS30
Wednesday AS31 = 1 AS32 = 23 AS33 = 00
Thursday AS34 = 0 AS35 AS36
Friday AS37 = 0 AS38 AS39
Saturday AS40 = 0 AS41 AS42
Sunday AS43 = 2 AS44 = 22 AS45= 30
In the following example the antilegionella cycle is scheduled: Wednesday duration 1 starting at 23:00 Sunday duration 2 starting at 22:30
7.4 DOMESTIC HOT WATER
To enable the DHW function:
Par AS00 DHW operating 1 = Enable the heat pump for DHW + DHW 3-way
valve 3 = Enable the heat pump for DHW + electric
heater + DHW 3-way valve
Parameters to setting :
Main menu
Parameters
AS
AS00
Parameter modification
DHW SCHEDULING
To enable the hour scheduling:
Par tE00 hour scheduling 0 = disabled 1 = enabled
Main menu
Parameters
tE
tE00
Parameter modification
Main menu
Parameters
AS
AS20
Parameter modification
Parameter : AS01 DHW setpoint AS04 DHW hysteresis
• CL90 = 9
• CE00 = 2
• CE30 = 11
• CE50 = 0
• CE90 = 28
• AS00 = 1
• AS04 = 5
• AS05 = 5
• AS06 = 20
32
7 - CONTROL
7.5 ALARM
A = AUTOMATIC reset M = MANUAL reset * after some interventions is necessary the manual reset
Code Description Type
E000 General alarm AUTO
E001 High pressure (digital) circuit 1 *
E003 High pressure (analogical) circuit 1 *
E007 Low pressure (analogical) circuit 1 *
E010 Inverter alarm *
E020 Primary circuit flow switch Time
E030 Primary circuit antifreeze AUTO
E035 Primary circuit output high temperature AUTO
E045 Faulty clock error AUTO
E046 Error: Clock to set AUTO
E047 Error of LAN communication between main module and electronic thermostatic module or ambient keyboard (if present) or DHW module (if present)
AUTO
E048 Anti-legionella AUTO
E060 Faulty water temperature probe or primary exchanger input AUTO
E061 Faulty water temperature probe or primary exchanger output AUTO
E062 Faulty exchanger temperature probe AUTO
E066 Faulty DHW temperature probe AUTO
E068 Faulty external temperature probe AUTO
E069 Faulty high pressure input circuit 1 AUTO
E080 Configuration error AUTO
E081 Signalling of compressor operating hour exceeding Manual
E085 Signalling of primary circuit pump operating hour exceeding Manual
E090 Signalling of alarm log record exceeding Manual
E065 Faulty ambient keyboard temperature probe AUTO
E071 Faulty compressor discharge temperature probe AUTO
33
7 - CONTROL
Code Description Type
E101 Faulty low pressure trasducer - dAI1 AUTO
E102 Faulty low pressure temperature probe - dAI2 AUTO
E103 Faulty discharge temperature probe - dAI3 probe AUTO
E106 Saturation output error AUTO
E107 MOP alarm AUTO
E108 Signalling of valve max opening AUTO
E110 NO link alarm AUTO
E111 Excessive current draw * Manual
E112 Winding 1 disconnection * Manual
E113 Winding 1 short circuit * Manual
E114 Winding 2 disconnection * Manual
E115 Winding 2 short circuit * Manual
7.6 ELECTRONIC THERMOSTATIC DRIVER ALARM
A = AUTOMATIC reset * switch on and off the electronic thermostatic driver
LED INVERTER
The access is riserve to the service centres. Danger of electrocution.
Led:
ON : normal operating
Slow flashing (ON 1sec. ,OFF 0.5 sec.): stanby compressor stopped
Fast flashing (ON 0.2 sec.,OFF 0.2 sec.): in alarm.
34
7 - CONTROL
Menu Code Description
Ai
AiE1 DHW temperature
Ai L1 Primary outlet temperature
Ai L2 Primary inlet temperature
Ai L3 Coil temperature
Ai L4 High pressure transducer
Ai L5 Outdoor temperature
1Ai 1 Low pressure transducer (thermostatic sensor on the driver)
1Ai 2 Return temperature (thermostatic sensor on the driver)
1Ai 3 Discharge temperature (thermostatic sensor on the driver)
di
di L1 High pressure
di L2 Compressor Alarm
di L3 Flow utility side
di L4 Remote On-Off
di L5 Remote Heat/Cool
AO
AO L1 Primary pump (it is a digital 0/1)
AO L2 Fan signal
AO L3 Compressor signal
AO L4 Primary pump signal (if in variable flow )
dO
dOE1 DHW heater (if present)
dO L1 DHW valve
dO L2 Reversing valve refrigerant circuit
dO L3 Frost Heater
dO L4 Auxiliary Heater
dO L5 Compressor start
dO L6 Cumulative alarm
E1
1rE1 Superheating temperature
1rE2 Condensing saturate temperature
1rE5 Superheating
1rE6 Gas pressure (=1Ai1)
1rE7 Opening percentage electronic thermostatic valve
1SP4 Superheating Setpoint
Sr Actual Setpoint : setpoint with compensation / operating limit
CP01 Hours compressor: dozens
PU01 Hours utility pump: dozens Hr
7.7 STATA
Main menu
SET
Ai - di - AO - dO
Ai L1
Stata display
35
7 - CONTROL
ACTION
UP - increases the value
- next voice - Silenced alarm
DOWN - decreases the value
- previous voice - On / Off *
ESC
- esc WITHOUT SAVING MODIFICATIONS
- previous level mode - Heat / cool / stdby / as
SET
- confirm
- esc WITH MODIFICATION SAVING
- go to the next level
- STATA menu - ambient temperature display
- Inputs / clock / stby / active alarms / setpoint
+ - activate / disactivate the time bands
+ - access to the SETTING menu - Parameters / function /
password / alarms
FUNCTION (3 SEC)
icon Fixed on Flashing icon
Alarm in progress Silenced alarm
Capacity step
Heating mode
Antifreeze with active heat pump Remote heating mode
Water pump of the primary circuit
Cooling mode Remote Cooling mode
Ventilation
Standby from keypad Remote standby
LAMP TEST
At the start-up is performed a board automatic test : all led flash for some seconds
defrosting Manual activated defrosting
Display shows Clock (not related to scheduling)
AUTO
Not used
DHW heater ON
ON : Domestic hot water flashing : D.H.W. mode - standby
4
The keyboard repeats all the built-in control functions.
7.8 AMBIENT KEYBOARD
* Unit in OFF the antifreeze function is not active.
4
36
7 - CONTROL
3 sec
HEAT heat
COOL cool
StdBY standby - off
AS Domestic hot water
OPERATING MODE
Ai, di, AO, dO Inputs, outputs
CL clock
AL Active alarms
SP setpoint
STATA
+
PAR - parameters configuration
Fnc - functions
dEF - manual defrosting
tA - alarm reset
St - on / off
CC - copy card
EUr - alarm log reset
PASS - password
EU - alarms Alarm log
SCHEDULING
7.9 NAVIGATION
37
7 - CONTROL
CLOCK SETTING display
press
Ai
selct CLOCK menu
/ Cl
access
Hour
choose among :
- hour : HOUR
- date : DATE
- year : YEAR /
YEAR
confirm ! Value flashing !
3 sec ! 2010 !
set the value
/ ! 2011 !
confirm
2011
back to the previous menu
CHANGE THE OPERATING MODE display
press 2 sec
COOL
choose among - standby, off :STBY
- cool : COOL
- heat : HEAT
- DHW : AS +
HEAT
confirm
WATER SETPOINT MODIFICATION display
press
Ai
select SP menu
/ SP
access
COOL
choose among :
- COOL
- HEAT
- AS /
ACS
confirm
50
set the value
/ 55
confirm
55
back to the previous menu
DISPLAY OF INPUTS - OUTPUTS display
press
Ai
choose among
Ai : analogical inputs
di : digital inputs
AO : analogical outputs
dO : digital outputs
/ di
access
diL1
press to see the value for digital inputs :
0 = input not active - open
1 = input active - closed
scroll the list
/ diL4
ON - OFF display
press 3 sec
OFF
press 3 sec
ON
Off the unit is immediately stopped without respecting any timing.
Stanby the antifreeze function is active ( pump ON for water temperature < 5°C )
The circulator anti-blocking function is active ( pump ON at predefined intervals)
*
*
38
7 - CONTROL
ALARM RESET display
press
+
ALARMS display
press
Ai
select ALARM menu
/ Al
access to the 1° active alarm
Er01
Scroll the other active alarms
/ Er07
back to the previous level
ALARM LOG display
press + PAr
select EU /
EU
last registered alarm
EU00
access to alarm code info
Er01
hour of the alarm /
20:01
date of the alarm /
27.10
alarm output hour example : alarm still active
/ --:--
alarm output date example : alarm still active
/ --:--
back to the previous level
type of alarm : - AUto - MAnu /
AUto
SILENCED ALARM display
the alarm code is flashing Er01
alternated to temperature 13.5°C
fixed ALARM led
press any button
/
ALARM led is flashing ! !
/
ALARMS LOG RESET display
press + PAr
select FnC /
FnC
press
dEF
select EUr /
EUr
press 3 SEC.
YES
back to the previous level
39
7 - CONTROL
1 display
press + PAr
press
PAr
select Cr /
Cr
press
Cr..
select Cr00 enable ambient probe
/ Cr00
confirm
0
select 2 /
2
confirm
2
back to the previous level
select Cr30 temperature display
/ Cr30
confirm
0
select 16
/ 16
confirm
16
back to the previous level
3 display
press 3 sec.
select Air1 /
Air1
press
Air1
2 display
press + PAr
press
PAr
select Ui /
Ui
press
Ui..
select Ui22 /
Ui22
confirm
0
select 1 /
1
confirm
1
back to the previous level
It is possible to set the keypad to display the ambient temperature. The probe is not used to perform the ambient thermoregulation. Follow these steps:
AMBIENT TEMPERATURE DISPLAY
Is it possible to disable the ambient keyboard :
Cr00 = 0
Cr30 = 0
To enable water setpoint compensation with ambient
temperature set :
par Cr 30 = 10 (see pag 20)
40
8.1 PERIODICAL CHECK LIST
Controls effected on ……………………………..By ………………………………………………. Of the Company…………………..……………………………….
Notes / interventions recommended to the owner
*European regulation 303/2008
Refer to the local actuation regulations; in short and just as an indication the regulation order as follow.
Companies and technicians that effect interventions of installation, maintenance/repairs, leak control and recovery must be CERTIFIED as expected by
the local regulations.
The leak control must be effected with annual renewal.
8 - MAINTENANCE
√ Frequency of intervention (months) 1 6 12
Presence of corrosions
Panel fixing
Fan fixing
Coil cleaning
Water filter cleaning
Check the exchanger efficiency
Circulating pumps
Check of the fixing and the insulation of the power lead
Check of the earthing cable
Electric panel cleaning
Capacity contactor status
terminal closing, cable insulation integrity
Voltage and phase unbalancing (no load and on-load)
Absorptions of the single electrical loads
Test of the compressor carter resistances
Leak control *
Survey of the refrigerant circuit operating parameters
Check of the 4-way change
Protective device test : safety valves, pressure switches, thermostats, flow switches etc
Control system test: setpoint, climatic compensations, capacity stepping, water / air flow-rate variations etc
Control device test : alarm signalling, thermometers, probes, pressure gauges etc
41
8 - MAINTENANCE
8.2 GENERAL
Maintenance must be done by authorized centres or by
qualified personnel
The maintenance enables:
• maintain the unit efficiency
• Reduce the deterioration speed to whom every equipment is subject over time
• Assemble information and data to understand the state of the unit efficiency and avoid possible damages
The inspections should be carried out at least every six months
The frequency, however, depends on the use . In the event of frequent use it is recommended to plan inspections at close intervals :
• frequent use (continuous or very intermittent use, near the operating limits, etc)
• critical use (service necessary) .
8.3 INSPECTIONS FREQUENCY
G C
B
D
A
F
A Coil
Inverter
ELectrical panel
B
C
D Exchanger
Circulator
Compressor
E
F
Fan G
MAIN COMPONENTS
A Vent
Output probe
Circulator B
C
D Safety valve ( 6 bar )
Plate exchanger
Flow switch
E
F
E
G
F
D
C
B
A
H
E
Input probe G
Water discharge H
42
8 - MAINTENANCE
It is very important for the exchanger to be able to provide the
maximum thermal exchange. Therefore, it is essential for the
inner surfaces to be clean of dirt and incrustations.
Periodically check the difference between the temperature of
the supply water and the condensation temperature. If the
difference is greater than 8 °C – 10 ° C it is advisable to clean
the exchanger.
The clearing must be effected :
• With circulation opposite to the usual one
• With a speed at least 1,5 times higher than the nominal one
• With an appropriate product moderately acid (95% water + 5% phosphoric acid
• After the cleaning rince with water to inhibe the detergent rests.
8.8 ELECTRIC FANS
8.7 WATER EXCHANGER
Check :
• the fans and the relative protection gridsare well fixed
• The fan bearings (evident by noise and anomalous vibrations )
• the terminal protection covers are closed and the cable holders are properly positioned
8.4 MACHINE BOOKLET
It’s advisable to create a machine booklet to take notes of the
unit interventions.
In this way will be easier marker the various interventions and
will be e facilitate any troubleshooting.
Report on the booklet :
• data
• type of intervention effected
• intervention description
• Carried out measures etc ..
If a long period of inactivity is foreseen
• Turn of the power in order to avoid electrical risks or
damages by lightning strike
• avoid the risk of frosts (empty or add glycol in the plant
sections subjected to temperatures below zero , power
antifreeze resistances if are present )
It’s recommended that the starter after the period of detention is
made by a qualified technician, especially after seasonal stops
or seasonal switch.
When restarting, refer to the START-UP section .
Schedule technical assistance in advance to avoid hitches and
be able to use the installation when necessary.
8.5 PUT A REST
Verify that there are no impurities which hinder the smooth
passage of water.
8.9 CIRCULATION PUMPS
Verify :
• no leaks
• Bearing status (anomalies are highlighted by abnormal noise and vibration)
• The closing of the terminals cover and the correct positioning of the cable glands.
8.6 WATER FILTER
43
8.11 PROBE POSITION
Fresh air probe
A
A
8 - MAINTENANCE
8.10 AIR COIL
Contact with the exchanger fins can cause cuts. Wear
protective gloves to perform the above described operations.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
It is extremely important that the battery gives the maximum
thermal exchange; therefore, its surface must be cleaned from
dust and deposits. Remove all impurities from the surface.
Using an air pressure gun, clean the aluminum surface of the
battery. Be careful to direct the air in the opposite direction of
the fan air movement.
Hold the gun parallel to the fins to avoid damages. As an
alternative, an aspirator can be used to suck impurities from
the air input side.
Verify that the aluminum fins are not bent or damaged. In the
event of damages, contact the authorized assistance center
and get the battery “ironed out” in order to restore the initial
condition for an optimal air flow
44
8 - MAINTENANCE
SPARE PARTS SIZES 21 - 31 - 41
45
8 - MAINTENANCE
Ref. Components
1 Mono-phase compressor
2 Reversing cycle valve
3 Electronic thermostatic valve (Solenoid + Body)
4 Internal plate exchanger
5 External finned exchanger
6 Circulator
EC circulator (High efficiency)
7 (*) Mono-phase electrical panel
Mono-phase electrical panel of EC circulator
8 Mono-phase Inverter
9 Water Kit
10 Flow switch
11 Rear panel
12 Right panel
13 Roof
14 Flow nozzle
15 Fan grid
16 Fan
17 Grid for the coil protection
18 Tray
19 Base
20 Supervisory control for the keypad protection
Tray electric heater
(*) Components installed inside each electrical panel
SB655/C CONTROL MODULE
XVD420 DRIVER MODULE FOR ELECTR. VALVE
230/12+12+24V MONO-PHASE TRANSFORMER
CONTROL MODULE OF THE CONDENSING FANS
420V 30.000h/CLASS A CONDENSER
CONDENSING AIR TEMP. PROBE
REFRIGERANT CIRCUIT GAS TEMP. PROBE
WATER TEMPERATURE PROBE
46
8 - MAINTENANCE
SPARE PARTS SIZES 51 - 71
47
8 - MAINTENANCE
Rif Components
1 Three-phase compressor
2 Reversing cycle valve
3 Electronic thermostatic valve (Solenoid + Body)
4 Internal plate exchanger
5 External finned exchanger
6 Circulator
EC circulator (High efficiency)
7 (*) Mono-phase electrical panel
Mono-phase electrical panel of EC circulator
Three-phase electrical panel
Three-phase electrical panel of EC circulator
8 Mono-phase Inverter
Three-phase Inverter
9 Water Kit
10 Flow switch
11 Rear panel
12 Right panel
13 Roof
14 Flow nozzle
15 Fan grid
16 Fan
17 Grid for the coil protection
18 Tray
19 Base
20 Supervisory control for the keypad protection
Tray electric heater
(*) Components installed inside each electrical panel
SB655/C CONTROL MODULE
XVD420 DRIVER MODULE FOR ELECTR. VALVE
230/12+12+24V MONO-PHASE TRANSFORMER
CONTROL MODULE OF THE CONDENSING FANS
420V 30.000h/CLASS A CONDENSER
CONDENSING AIR TEMP. PROBE
REFRIGERANT CIRCUIT GAS TEMP. PROBE
WATER TEMPERATURE PROBE
48
9 - TECHINICAL INFORMATION
378
412166
942
99
2
1
1
1
1
2 2
3
4
56
7
912 15152
033
420
150
100500
143
372
65
67 A
DETTAGLIO A
60
8
9
9
9
895
(1) HOLES TO HANG ANTIVIBRATION MOUNTS (2) LIFTING HOLES (3) ELECTRICAL PANEL (4) ELECTRICAL POWER INPUT (5) CONTROL KEYBOARD (6) INTERNAL EXCHANGER WATER INLET (1" GAS) (7) INTERNAL EXCHANGER WATER OUTLET (1" GAS) (8) CONDENSATE DISCHARGE (9) CLEARANCE ACCESS RECOMMENDED
WW
W W
SIZE 21 31 41
Length mm 895 895
Depth mm 378 378
Height mm 992 992
W1 kg 37 38
W2 kg 17 18
W3 kg 39 40
W4 kg 19 20 Operating weight kg 112 116 Shipping weight kg 110 114
895
378
992
40
20
42
22 124 122
9.1 DIMENSIONALI
49
9 - TECHINICAL INFORMATION
9.1 DIMENSIONALI
20
36
52
0
15 1057 15
148
1087440
12
34
1
1
1
1
2 2
3
45
6
7
5001
50
100
119
568
70
73
410
A
DETTAGLIO A
60
8
9
9
9
1038
(1) HOLES TO HANG ANTIVIBRATION MOUNTS (2) LIFTING HOLES (3) ELECTRICAL PANEL (4) ELECTRICAL POWER INPUT (5) CONTROL KEYBOARD (6) INTERNAL EXCHANGER WATER INLET (1" GAS) (7) INTERNAL EXCHANGER WATER OUTLET (1" GAS) (8) CONDENSATE DISCHARGE (9) CLEARANCE ACCESS RECOMMENDED
WW
W W
SIZE 51 71
Length mm 1038 1038
Depth mm 410 410
Height mm 1234 1234
W1 kg 51 53
W2 kg 32 33
W3 kg 53 55
W4 kg 34 34
Operating weight kg 170 175
Shipping weight kg 168 173
50
9 - TECHINICAL INFORMATION
9.2 GENERAL TECHNICAL DATA
RADIANT PANELS HEATING Heating capacity 1 kW 5,49 6,91 8,80 12,0 14,5 Total power input 2 kW 1,33 1,70 2,17 2,96 3,57 COP (EUROVENT) 3 4,13 4,07 4,06 4,06 4,06
COP (EN 14511:2008) 4 3,90 3,90 3,90 3,93 3,92
COOLING
Cooling capacity 7 kW 4,17 6,24 7,96 10,2 12,9 Total power input 2 kW 1,10 1,70 2,12 2,78 3,49 EER (EUROVENT) 8 3,79 3,67 3,75 3,67 3,70
EER (EN 14511:2008) 9 3,60 3,60 3,65 3,61 3,67
ESEER 10 5,90 5,73 6,84 6,49 6,52
Water flow 7 l/s 0,20 0,30 0,42 0,57 0,69 Useful pump discharge head 7 kPa 52 43 52 47 54
SIZE 21 31 41 51 71
ELFOROOM AND ELFOSPACE TERMINAL UNITS HEATING Heating capacity 5 kW 5,28 6,64 8,35 11,6 14,0
Total power input 2 kW 1,64 2,07 2,61 3,61 4,38
COP (EUROVENT) 3 3,22 3,21 3,20 3,21 3,20
COOLING Cooling capacity 11 kW 3,81 5,15 6,01 8,71 11,5 Total power input 2 kW 1,48 2,00 2,28 3,32 4,37 EER (EUROVENT) 8 2,58 2,57 2,64 2,62 2,63 ESEER (EUROVENT) 12 3,99 3,77 4,32 4,17 4,63 Water flow 11 l/s 0,18 0,25 0,29 0,42 0,55 Useful pump discharge head 11 kPa 53 48 58 53 65
HEATING Heating capacity 6 kW 5.14 6.49 8.13 11.2 13.5 Total power input 2 kW 1.90 2.49 3.20 4.41 5.34
COP (EUROVENT) 3 2.71 2.61 2.54 2.54 2.53
Water flow 6 l/s 0.12 0.16 0.19 0.27 0.32
Useful pump discharge head 6 kPa 58 54 65 64 94
COMPRESSOR Type of compressors ROTARY INVERTER DC SCROLL INVERTER DC
No. of Compressors Nr 1 1 1 1 1
Oil charge l 0,35 0,35 0,87 1,7 1,7
Refrigerant circuits Nr 1 1 1 1 1
UTILITY SIDE EXCHANGER Type of internal exchanger 13 PHE PHE PHE PHE PHE
Water content l 0,56 0,64 0,64 1,14 1,80
No. of exchanger Nr 1 1 1 1 1
Standard supply 230/1/50 230/1/50 230/1/50 400/3/50+N 400/3/50+N
HYDRAULIC CIRCUIT Max water side pressure kPa 550 550 550 550 550
Safety valve calibration kPa 600 600 600 600 600 Min. installation water content l 17 20 25 33 40
(1) In/out water temperature utility side 30/35 °C, external exchanger air intake 7 °C (U.R. = 85%)
(2) The total absorbed power is obtained adding the compressor absorbed power + the fans absorbed power + the power absorbed by the auxiliary electric circuit.
(3)COP EUROVENT: heating performance coefficient. Ratio between heating power delivery and power absorption in compliance with EUROVENT. The power absorbed is the sum of the power absorbed by the compressor + the fans absorbed power + the power absorbed by the auxiliary electric circuit.
(4) COP (EN 14511:2008) heating performance coefficient. Ratio between heating power delivery and power absorption per EN 14511:2008. The power absorption is the sum of the power absorbed by the compressor + the power absorbed by the fans + the power absorbed by the auxiliary electric circuit + pump to overcome internal pressure drops.
(5) In/out water temperature utility side 40/45 °C, external exchanger air intake 7 °C (U.R. = 85%)
(6) In/out water temperature utility side 45/55 °C, external exchanger air intake 7 °C (U.R. = 85%)
(7) In/out water temperature utility side 23/18 °C, aria external exchanger air intake 35 °C
(8) EER EUROVENT: cooling performance coefficient. Ratio between cooling capacity and power absorbed in compliance with EUROVENT. The power absorption is the sum of the power absorbed by the compressor + the power absorbed by the fans + the power absorbed by the auxiliary electric circuit.
(9) EER (EN 14511:2008) cooling performance coefficient. Ratio between cooling capacity and power absorption per EN 14511:2008. The power absorption is the sum of the power absorbed by the compressor+ + the power absorbed by the fans + la the power absorbed by the auxiliary electric circuit + pump to overcome internal pressure drops.
(10) ESEER calculated by Clivet, for radiant installations with water produced to 18 °C, have been considered the conditions of water source load and temperature defined by Eurovent for water produced at 7 °C.
(11) In/out water temperature utility side 12/7 °C, external exchanger air intake 35 °C (12) ESEER calculated according to Eurovent, for terminal unit water produced at 7 °C. (13) PHE = plate exchanger (14) AX = axial-flow fan
EXTERNAL SECTION FANS Type of fans 14 AX AX AX AX AX
Number of fans Nr 1 1 1 2 2
Standard air flow l/s 2350 3700 3700 7400 7150 Installed unit power kW 0,12 0,15 0,15 0,15 0,15
RADIATORS
SUPPLY
51
9 - TECHINICAL INFORMATION
9.4 SOUND LEVELS
9.3 OPERATING LIMITS
COOLING
Twu [°C] = exchanger water outlet temperature Tae [°C] = external exchanger input air temperature (1) Normal operating range (2) Operation with fans in modulation (3) Range of operation where the use of ethylene glycol is mandatory, depending on the temperature of the water delivered by the source side heat exchanger. (4) Operation with compressor in modulation
Twu [°C] = exchanger water outlet temperature Tae [°C] = external exchanger input air temperature (1) Normal operating range (2) Operation with compressor in modulation (3) Operation with fans and compressor in modulation
ELFOEnergy Extended Inverter 21 - 31 - 41 ELFOEnergy Extended Inverter 51 - 71
-10
-5
0
5
10
15
20
0 5 10 15 20 25 30 35 40 45 50
Twu[
°C]
Tae[°C]
12 4
3
-10
-5
0
5
10
15
20
0 5 10 15 20 25 30 35 40 45 50
Twu[
°C]
Tae[°C]
3
12 4
20
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40
Twu[
°C]
Tae [°C]
2 3
HEATING
20
25
30
35
40
45
50
55
60
65
-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45
Twu[
°C]
Tae [°C]
2 31 31
ELFOEnergy Extended Inverter 21 - 31 - 41 ELFOEnergy Extended Inverter 51 - 71
SIZE 21 31 41 51 71
Sound Power Level 62 62 63 64 67
dB(A)
Noise levels are determined using the tensiometric method (UNI EN ISO 9614-2) Data referred to the following conditions: − Internal exchanger water = 12/7°C; − External air temperature 35°C
52
9 - TECHINICAL INFORMATION
DP[KPA] = Useful static pressure Q[L/S] = WATER FLOW The heads are intended as available at the unit connections
10
20
30
40
50
60
70
80
90
100
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
DP
(kP
a)
Q (l/s)
5141 7121-31
SIZE 21 31 41 51 71
Qmin [l/s] 0.15 0.18 0.18 0.23 0.34
Qmax [l/s] 0.9 0.9 0.9 1.1 1.5
Minimum (Qmin) and maximum (Qmax) admissible water flow for the unit to operate correctly.
10
20
30
40
50
60
70
80
90
100
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
DP
(kP
a)
Q (l/s)
21 31-41
51
71
EXCHANGER PRESSURE DROP LIMIT. WARNING: DON'T USE OVER THIS LIMIT
EXCHAMGER PRESSURE DROP LIMIT. WARNING: DON'T USE BELOW THIS LIMIT.
DP = PRESSURE DROP Q = WATER FLOW RATE
THE HEADS ARE INTENDED AS AVAILABLE AT THE UNIT CONNECTIONS Q [L/S] = WATER FLOW RATE DP [KPA] = AVAILABLE HEAD
10
20
30
40
50
60
70
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
DP
(kP
a)
Q (l/s)
31-41 51 71210,00
0,02
0,04
0,06
0,08
0,10
0,12
0,14
0,16
0,18
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2
Pci
rc (
kW)
Q (l/s)
51 - 71
21 - 31 - 41
Available pressure curves with high efficiency circulator High efficiency circulator absorption curve
Q [L/S] = WATER FLOW RATE PAC[KW] = PUMP POWER INPUT
9.5 ADMISSIBLE WATER FLOW
9.6 UNIT WITHOUT HYDRONIC SYSTEM - OPTION
Exchanger pressure drops
9.7 UNIT WITH HYDRONIC SYSTEM - OPTION
Available pressure curves
9.7 UNIT WITH EC HIGH EFFICIENCY CIRCULATING GROUP - OPTIONAL
53
10 - DECOMMISSIONING
THE UNIT MUST ALWAYS BE SENT TO AUTHORISED
CENTRES FOR DISMANTLING AND DISPOSAL.
When dismantling the unit, the fan, the motor and the coil, if
operating, may be recovered by the specialist centres for
reuse.
All the materials must be recovered or disposed of in
compliance with the corresponding national standards in
force.
For further information on the decommissioning of the unit,
contact the manufacturer.
9.1 DISCONNECTING
Only authorised personnel must disconnect the unit.
• Avoid leak or spills into the environment .
• Before disconnecting the unit, the following must be recovered, if present:
- refrigerant gas - Anti-freeze solutions in the hydraulic circuit
• Awaiting dismantling and disposal, the unit can also be
stored outdoors, as bad weather and rapid changes in
temperature will not cause damage to the environment, if
electric, cooling and hydraulic circuits of the unit are
integral and closed.
The units covered by the legislation in question are marked
with the symbol on the side.
With the aim of protecting the environment, all of our units are
produced in compliance with Directive EC on waste electrical
and electronic equipment (WEEE).
The potential effects on the environment and on human health
due to the presence of hazardous substances are shown in the
use and maintenance manual in the section on residual risks.
Information in addition to that indicated below, if required, can
be obtained from the manufacturer/distributor/importer, who
are responsible for the collection/handling of waste originating
from equipment covered by EC - WEEE. This information is
also available from the retailer who sold this appliance or from
the local authorities who handle waste.
Directive EC - WEEE requires disposal and recycling of
electrical and electronic equipment as described therein to be
handled through appropriate collection, in suitable centres,
separate from collection for the disposal of mixed urban waste.
The user must not dispose of the unit at the end of its life cycle
as urban waste. It must instead be handed over to appropriate
collection centres as set forth by current standards or as
instructed by the distributor.
If disposal takes places at the same time as delivery of a new
electrical or electronic equipment for the same family, the
product may be collected directly by the distributor.
9.3 CE RAEE CE DIRECTIVE
9.2 DISMANTLING AND DISPOSAL
54
11 - RESIDUAL RISKS
Smell of burning, smoke or other signals of serious anomalies may indicate a situation which could cause damage to people, things or the unit itself.
Electrically isolate the unit (yellow-red isolator).
Contact the authorised service centre to identify and resolve the problem at the source of the anomaly.
Accidental contact with exchange batteries, compressors, air
delivery tubes or other components may cause injuries and/or burns.
Always wear suitable clothing including protective gloves to work inside the danger zone.
Maintenance and repair operations carried out by non-qualified personnel may cause damge to persons, things or the unit itself.
Always contact the qualified assistance centre.
Failing to close the unit panels or failure to check the correct tightening of all of the panelling fixing screws may cause damage to persons, things or the unit itself.
Periodically check that all of the panels are correctly closed and fixed.
If there is a fire the temperature of the refrigerant could reach values that increase the pressure to beyond the safety valve with the consequent possible projection of the refrigerant itself or explosion of the circuit parts that remain isolated by the closure of the tap.
Do not remain in the vicinity of the safety valve and never
leave the refrigerating system taps closed.
11.1 GENERAL
11.2 DANGER ZONE
11.3 HANDLING
11.4 INSTALLATION
11.5 GENERAL RISKS
11.6 ELECTRICS PARTS
In this section the most common situations are signalled. As these cannot be controlled by the manufacturer these could be a source of risk situations for people or things
This is an area in which only an authorised operator may work.
The danger zone is the area inside the unit which is accessible only with the deliberate removal of protections or parts thereof
The handling operations, if implemented without all of the protection necesssary and without due caution, may cause the fall or the tipping of the unit with the consequent damage, even serious, to persons, things or the unit itself.
Handle the unit following the instructions provided in the pre-sent manual regarding the packaging and in compliance with the local regulations in force.
Should the gas refrigerant leak please refer to the refrigerant "Safety sheet".
An incorrect installation of the unit could cause water leaks, condensate accumulation, leaking of the refrigerant, electric shock, bad functioning or damage to the unit itself.
Check that the installation has been implemented by qualified technical personnel only and that the instructions contained in the present manual and the local regulations in force have been adhered to.
The installation of the unit in a place where even infrequent leaks of inflammable gas and the accumulation of this gas in the area surrounding the area occur could cause explosions or fires.
Carefully check the positioning of the unit.
The installation of the unit in a place unsuited to support its weight and/or guarantee adequate anchorage may cause the fall or the tipping of the unit with the consequent damage to things, people or the unit itself.
Carefully check the positioning and the anchoring of the unit.
Easy access to the unit by children, unauthorised persons or animals may be the source of accidents, some serious.
Install the unit in areas which are only accessible to authori-sed person and/or provide protection against intrusion into the danger zone .
An incomplete attachment line to the electric network or with incorrectly sized cables and/or unsuitable protective devices can cause electric shocks, intoxication, damage to the unit or fires.
Carry out all of the work on the electric system referring to the electric layout and the present manual ensuring the use of a system thereto dedicated.
An incorrect fixing of the electric components cover may favour the entry of dust, water etc inside and may consequently can electric shocks, damage to the unit or fires.
Always fix the unit cover properly.
When the metallic mass of the unit is under voltage and is not correctly connected to the earthing system it may be as source of electric shock and electrocution.
Always pay particular attention to the implementation of the earthing system connections.
Contact with parts under voltage accessible inside the unit after the removal of the guards can cause electric shocks, burns and electrocution.
Open and padlock the general isolator prior to removing the guards and signal work in progress with the appropriate shield.
Contact with parts that could be under voltage due to the start up of the unit may cause electric shocks, burns and electrocution.
When voltage is necessary for the circuit open the isolator on the attachment line of the unit itself, padlock it and display the appropriate warning shield.
55
NOTES
www.clivet.com
I d
ati
con
tenu
ti ne
l pre
sen
te m
an
uale
no
n so
no
imp
egn
ativ
i e p
oss
ono
ve
nire
cam
bia
ti da
l co
stru
ttore
sen
za o
bb
ligo
di p
rea
vvis
o.
R
ipro
du
zio
ne
an
che
pa
rzia
le V
IET
AT
A ©
Cop
yrig
ht -
CL
IVE
T S
.p.A
. - F
eltr
e (
BL
) -
Italia
CLIVET SPA Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - [email protected] CLIVET UK LTD 4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - [email protected] CLIVET ESPAÑA S.A. Parque Empresarial Villapark, Avda. Quitapesares 50 - 28670, Villaviciosa de Odón, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - [email protected] CLIVET GmbH Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - [email protected] CLIVET NEDERLAND B.V. Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - [email protected] CLIVET RUSSIA Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - [email protected] CLIVET MIDEAST FZCO Rep Office: PO Box 28178 - Light industrial unit 10 -Dubai Silicon Oasis - Dubai, UAE Tel. + 97 14 3208499 - Fax + 97 14 3208216 - [email protected] CLIVET AIRCONDITIONING SYSTEMS (P) LTD 3C3, Gundecha Onclave, Kherani Road, Saki Naka, Andheri (East), Mumbai 400 072 (INDIA) Tel. + 91 - 22 - 6193 7000 - Fax + 91 - 22 - 6193 7001 - [email protected] 150311