air conditionning systems.pdf

Embed Size (px)

Citation preview

  • 7/22/2019 air conditionning systems.pdf

    1/253

    Thermal exchange guide

    Air conditioning systems

  • 7/22/2019 air conditionning systems.pdf

    2/253

    Themal exchange guide

    Air conditioning systems

    Chapter 1 : Definitions

    Chapter 2 : All-air systems

    Chapter 3 : All-water systems

    Chapter 4 : Air-water systems

    Chapter 5 : Direct-expansion systems

    Chapter 6 : Computer room systems

    Chapter 7 : Energy storage

  • 7/22/2019 air conditionning systems.pdf

    3/253

    21July 2006

    Page 1/1

    Thermal exchange guideVersion 1.0

    Preamble

    Having been informed of the type of problem to be solved and after analysis of the consequences,the designer will try to outline the type of installation which will guarantee the best results.

    In order to carry out the air handling installation, the designer has at his disposal some basic

    elements to be used alone or in association with others.

    However the choice or implementation of these various elements will take into account the

    following factors :

    Nature of the enquiry :

    room cooling,

    comfort air conditioning,

    precision air conditioning

    . Nature and use of spaces to be treated :

    new or existing,

    number and respective locations

    Presence or absence of equipments which could be used :

    Heating generator,

    Cooling generator,

    Distribution networks

    Summer-winter thermal reports concerning spaces to be treated.

    This appraisal determines the choice of a system.

  • 7/22/2019 air conditionning systems.pdf

    4/253

    21July 2006

    Air conditioning systems Page 1/37 Definitions

    Air conditioning systemsVersion 1.0

    CCChhhaaapppttteeerrr111:::DDDeeefffiiinnniiitttiiiooonnnsss

  • 7/22/2019 air conditionning systems.pdf

    5/253

    21July 2006

    Air conditioning systems Page 2/37 Definitions

    Air conditioning systemsVersion 1.0

    Contents

    Introduction............................................................................................................... 3

    Space cooling ........................................................................................................... 4

    Definition..................................................................................................................... 4

    Aim ............................................................................................................................. 4

    Parameters taken into account ................................................................................... 4

    Fields of application.................................................................................................... 4

    Comment .................................................................................................................... 4

    Comfort air conditioning.......................................................................................... 5

    Definition..................................................................................................................... 5Aim ............................................................................................................................. 5

    Parameters taken into account ................................................................................... 5

    Fields of application.................................................................................................... 5

    Air conditioning ........................................................................................................ 6

    Definition..................................................................................................................... 6

    Aim ............................................................................................................................. 6

    Parameters taken into account ................................................................................... 6

    Fields of application.................................................................................................... 7

    Systems..................................................................................................................... 8Definition..................................................................................................................... 8

    Potential system components..................................................................................... 9

    System identification................................................................................................. 10

    Method 1: Local systems .......................................................................................... 11

    Method 1: Central systems ....................................................................................... 12

    Heating and refrigeration equipment .................................................................... 13

    Definition................................................................................................................... 13

    Heating equipment.................................................................................................... 13

    Refrigeration equipment............................................................................................ 16

    Fresh-air conditioning............................................................................................ 21

    Definition................................................................................................................... 21

    Heat recovery units................................................................................................... 26

  • 7/22/2019 air conditionning systems.pdf

    6/253

    21July 2006

    Air conditioning systems Page 3/37 Definitions

    Air conditioning systemsVersion 1.0

    Introduction

    This chapter defines the various terms used in the industry to address the field of

    air handling: space cooling,

    comfort air conditioning,

    air conditioning.

    It also defines what is meant by a system and its components, and identifies the

    criteria for categorising systems.

    The types of heating and refrigeration equipment are also redefined.

    Last but not least, it discusses fresh-air conditioning and examines the energy

    savings afforded by various aspects of heat recovery.

  • 7/22/2019 air conditionning systems.pdf

    7/253

    21July 2006

    Air conditioning systems Page 4/37 Definitions

    Air conditioning systemsVersion 1.0

    Space cooling

    Definition Cooling is the simplified conditioning of ambient air in order to lower the

    temperature by a few degrees.

    Aim Provide a feeling of coolness in the summer.

    Parameters takeninto account

    Only temperature is taken into account. The system must maintain it two or

    three degrees lower than the outdoor air (for calculations at least).

    Note:

    Relative humidity is not taken into account. Occupants may therefore

    occasionally experience a feeling of discomfort.

    Fields ofapplication

    They remain rather varied in cases where cost outweighs technical aspects.

    Comment This conditioning method must be used with precaution. It is not suitable forsites where significant amounts of moisture are released.

  • 7/22/2019 air conditionning systems.pdf

    8/253

    21July 2006

    Air conditioning systems Page 5/37 Definitions

    Air conditioning systemsVersion 1.0

    Comfort air conditioning

    Definition The term comfort air conditioning encompasses all the conditioning processes

    applied to ambient air to obtain an indoor environment that is comfortableinterms of temperature and relative humidity.

    Aim Obtain, all year round, conditions that are favourable to occupants, their healthand well-being or even improve their conditions.

    Comfort can mean two things:

    In homes, comfort targets the well-being of occupants,

    In businesses, it targets:

    improved worker productivity,

    increased customer satisfaction.

    Parameters takeninto account

    Air conditioning takes into account the following parameters:

    temperature,

    relative humidity,

    air cleanliness (impurities, odours),

    noise level,

    quality of diffusion (air motion, velocity).

    Fields ofapplication

    Comfort air conditioning applies to:

    single-family and multi-family housing,

    businesses (shops, offices, public buildings).

  • 7/22/2019 air conditionning systems.pdf

    9/253

    21July 2006

    Air conditioning systems Page 6/37 Definitions

    Air conditioning systemsVersion 1.0

    Air conditioning

    Definition Air conditioning encompasses all the processes applied to the air in a space to

    obtain specific temperature and humidity levelsfor: an activity,

    a process,

    product storage conditions.

    Aim Obtain specific, constantand reliable conditionsall year round for the activityor process being carried out in the space.

    Example:

    Abattoir cutting room:

    temperature of +12C, dew point temperature: +4C to prevent moisture forming on carcasses

    taken out of coolers at +4/+5C,

    Operating theatre:

    highly efficient filtration (HEPA filter), no return air,

    temperatures of +20C to +22C (or even 18C),

    relative humidity greater than 50% (static electricity).

    Parameters takeninto account

    The parameters vary by activity:

    air cleanliness (impurities, odours),

    temperature,

    relative or absolute humidity,

    drying (or dehumidification) capacity.

    In most cases, more or less stringent requirements must be met to maintain these

    parameters:

    result accuracy:

    temperature C C (e.g. 25C 1C),

    humidity % % (50% RH 10%),

    result stability:

    over time,

    in the space,

    controlled atmosphere:

    cleanrooms.

  • 7/22/2019 air conditionning systems.pdf

    10/253

    21July 2006

    Air conditioning systems Page 7/37 Definitions

    Air conditioning systemsVersion 1.0

    Air conditioning (continued)

    Fields of

    application

    Air conditioning is used in:

    industries: microelectronics,

    avionics,

    optics,

    clockmaking,

    micromechanics,

    automotive,

    paints,

    biology:

    food processing: beverages, dairy products, meat products, pharmaceuticals and cosmetics,

    biotechnology: research laboratories,

    hospitals: operating theatres, sterile rooms,

    high-tech industries:

    fine chemicals,

    space (miniaturisation),

    packaging,

    glassware,

    plastics.

  • 7/22/2019 air conditionning systems.pdf

    11/253

    21July 2006

    Air conditioning systems Page 8/37 Definitions

    Air conditioning systemsVersion 1.0

    Systems

    Definition Whether used for comfort or process applications, the air conditioning system

    is the backbone or flow chart connecting all the basic components used tosolve the problem at hand.

    The components listed in detail on the following page are divided into four main

    categories:

    energy production,

    air conditioning,

    coolant supply (air, water, refrigerant),

    air diffusion.

    waterchiller

    recycling

    fan

    chilled watercoil

    filter

    filter

    energy recoverydevice

    heating coilhot watergenerator

    CIATCOOLERI T OOLER

    humidifier

    fan

    In the example opposite:

    Cooling and heating energy is generated by awater chiller and a water boiler,

    Air, distributed by a system of ducts, is used asthe coolant,

    The air is conditioned in an air handling unit(filter, recovery unit, cooling coil, heating coil,

    humidifier, forced-draught fan),

    The air flows out of ceiling registers,

    And is drawn out of the space by the exhaust fan.

  • 7/22/2019 air conditionning systems.pdf

    12/253

    21July 2006

    Air conditioning systems Page 9/37 Definitions

    Air conditioning systemsVersion 1.0

    Systems (continued)

    Potential system

    components

    The potential components of a system are the basic elements:

    hot water production: independent boiler,

    exchanger (from a distribution system),

    heat pump,

    heat transfer cooling unit (heat recovery condenser),

    chilled water production:

    independent chiller,

    exchanger (from a distribution system),

    direct-expansion refrigeration:

    packaged, split,

    multisplit,

    air conditioning:

    air handling unit,

    terminal units,

    ductwork:

    distribution,

    return,

    supply of fresh air,

    removal of stale air,

    air diffusion equipment:

    supply registers,

    return grilles.

  • 7/22/2019 air conditionning systems.pdf

    13/253

    21July 2006

    Air conditioning systems Page 10/37 Definitions

    Air conditioning systemsVersion 1.0

    Systems (continued)

    System

    identification

    Depending on the criteria used, there are two methods of categorising air

    conditioningsystems (see note): Method 1:

    The cooling of one or more spaces is the main criterion. It does not take into

    account the type of system:

    individual air conditioning, or local system,

    shared air conditioning, or central system,

    Method 2:

    The main coolant is the main criterion.

    If Then

    the system is an all-AIR system air is the coolant

    the system is an all-WATER system water is the coolant

    the system is an AIR-WATER system both water and air are used

    the system is a DIRECT EXPANSION system the refrigerant is the coolant

    Note:

    These two categorisation methods are the most common.

  • 7/22/2019 air conditionning systems.pdf

    14/253

    21July 2006

    Air conditioning systems Page 11/37 Definitions

    Air conditioning systemsVersion 1.0

    Systems (continued)

    Method 1:

    Local systems

    Definition Each space is served by self-contained equipment containing:

    a refrigeration and/or heating unit,

    air conditioning and diffusion components.

    Generally, the equipment is either packagedor split, low or medium capacity,

    and direct expansion.

    INDOOR UNIT

    HEAT EXCHANGER

    REFRIGERANT/INDOOR AIR

    EXPANSION VALVE

    REFRIGERANT LINE

    OUTDOOR UNIT

    COMPRESSOR

    HEAT EXCHANGER

    REFRIGERANT/OUTDOOR AIR OR WATER

    Use Local systems are generally used in existing single-family homes and smallbusinesses.

  • 7/22/2019 air conditionning systems.pdf

    15/253

    21July 2006

    Air conditioning systems Page 12/37 Definitions

    Air conditioning systemsVersion 1.0

    Systems (continued)

    Method 1: Central

    systems

    Definition Each space is supplied with airconditioned in a central unit containing:

    an air handling unit (AHU),

    heating equipment (+),

    refrigerationequipment (-),

    the necessary ductwork

    Exhaust air

    Fresh air

    Hotwater

    Chilledwater

    Supply

    Return

    A H U

    DuctworkAir handling unit

    Water boiler

    Water chiller

    Use As old buildings were not designed with air conditioning in mind, this type ofsystem is found more often in new or recent buildings. A buildings design takes

    into account the entire system, i.e. mechanical room and duct runs.

  • 7/22/2019 air conditionning systems.pdf

    16/253

    21July 2006

    Air conditioning systems Page 13/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment

    Definition The following equipment is needed in order for air to be conditioned:

    water (coolant, humidifier),

    electricity (to power the motors),

    heating equipment,

    refrigeration equipment.

    This section will discuss local heating and refrigeration equipment.

    Heatingequipment

    The term encompasses a number of items of equipment:

    boiler,

    heat exchanger, heat pump,

    transfer unit.

    Boiler A self-contained vessel used to heat water. Electricity, gas or fuel oil may beused as a heating source. The temperature of the hot water can vary from 50 to

    80C.

    SUPPLY

    BOILER

    RETURN

    SUPPLY

    RETURN

  • 7/22/2019 air conditionning systems.pdf

    17/253

    21July 2006

    Air conditioning systems Page 14/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Heating

    equipment(continued)

    Heat exchanger Actual production is centralised (district heating or the boiler room in a factoryor for a group of buildings),

    A heat exchanger is used locally to raise the hot fluid to the desired temperature.

    The operating temperature can vary from 50 to 80C.

    EXCHANGER

    SUPPLY

    RETURN

    DISTRICT HEATING

  • 7/22/2019 air conditionning systems.pdf

    18/253

    21July 2006

    Air conditioning systems Page 15/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Heating

    equipment(continued)

    Heat pump Heat pumps draw heat from a cold source and transmit it to a heat source.

    The cold source may be:

    Water: ground water, river, lake, sea, process cooling water,

    Air: outside air, exhaust air (buildings, processes).

    The temperature of the hot water (heat source) is between 40 and 55C.

    SUPPLYRETURN

    WATER - WATER

    DISCHARGE

    HEAT PUMP

    SUPPLYRETURN

    AIR - WATER

    air

    Transfer unit Transfer units are found on cooling systems that operate all year long (processcooling).

    The refrigeration circuit may be equipped with an additional water-cooled

    condenser known as a heat recovery condenser.

    No heat is produced unless refrigeration is also produced.The temperature of

    the hot water is between 40 and 50C.

    SUPPLYRETURN

    WATER-cooled heatrecovery condenser AIR-cooledcondenser

    Evaporator

  • 7/22/2019 air conditionning systems.pdf

    19/253

    21July 2006

    Air conditioning systems Page 16/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Refrigeration

    equipment

    The term covers a number of items of equipment:

    water chiller,

    direct-expansion refrigeration unit,

    heat exchanger,

    cooling tower,

    drycooler.

    Water chiller A water chiller is a machine that cools water, which is used as a refrigerant.

    Temperature of the chilled water:

    5 to 12C depending on the operating conditions,

    mean inlet/outlet temperature difference: 5C,

    Freezing temperatures:

    An antifreeze such as glycol or similar is added to the water.

  • 7/22/2019 air conditionning systems.pdf

    20/253

    21July 2006

    Air conditioning systems Page 17/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Refrigeration

    equipment(continued)

    Direct-expansion

    refrigerationunit

    The evaporator is removed from the central system and placed inside the air

    handling unit, where it cools the air that will be supplied to each space.

    Direct expansion coil

    Thermostaticexpansion valve

    Air flow

    Water-cooled condenser(or air-cooled)

    Motor compressor

    Heat exchanger Actual production is centralised (district cooling or factory system).

    More and more large cities are turning to chilled water district cooling systems.

    In industry, heat exchangers are used in applications requiring water at

    temperatures different from that in the distribution system.

    EXCHANGER

    SUPPLY

    RETURN

    DISTRICT HEATING

  • 7/22/2019 air conditionning systems.pdf

    21/253

    21July 2006

    Air conditioning systems Page 18/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Refrigeration

    equipment(continued)

    Cooling tower A cooling tower is a specific type of cooling device. It uses humidified ambientair to produce chilled water. The air is cooled to its wet bulb temperature.

    Example: Air at a temperature of 30C with 40% RH is cooled to its wet bulb

    temperature of +20C. It serves as a refrigerant.

    There are two types of cooling tower:

    Closed-circuittowers, in which heat is exchanged between air and water by asprayed heat exchange coil. The air and the water in the condenser circuit

    do not enter into contact.

  • 7/22/2019 air conditionning systems.pdf

    22/253

    21July 2006

    Air conditioning systems Page 19/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Refrigeration

    equipment(continued)

    Cooling tower(continued)

    Open-circuit towers, in which air and water come into direct contact. Dropsof water run along a distribution panover which air flows. The water in the

    condenser circuit and the air are in direct contact with each other.

    The diagram below shows a water chiller operating on an open-circuit cooling

    tower.

    Fan

    Spray nozzle

    Air inlet

    Drain pan

    Wet deck

    Gutter

    Droplet separator

    Cleaning tap

    Makeupwater

    Bypassvalve

    pump

    Treated makeup water inlet

    Overflow

    Screen filter

    Drain

    Water-cooled condenser

  • 7/22/2019 air conditionning systems.pdf

    23/253

    21July 2006

    Air conditioning systems Page 20/37 Definitions

    Air conditioning systemsVersion 1.0

    Heating and refrigeration equipment (continued)

    Refrigeration

    equipment(continued)

    Drycooler A drycooler is a type of cooling device that uses dry air as a refrigerant.

    Example: When the air temperature is 30C with 40% RH, the temperature taken

    into account is +30C (not +20C, as in the case of the cooling tower). Heat is

    transferred from water to air by a dry heat exchanger.

    As with a closed-circuit cooling tower, the water in the condenser circuit of a

    drycooler never enters into contact with the air.

    This eliminates the risk of spreading Legionellosis.

  • 7/22/2019 air conditionning systems.pdf

    24/253

    21July 2006

    Air conditioning systems Page 21/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning

    Definition Before discussing the subject of fresh-air handling, one should understand what

    is meant by the following terms: pollution,

    removal of stale air,

    supply of fresh air,

    fresh-air handling,

    heat recovery units.

    Pollution People, their health and activities, as well as processes are all sources ofpollution:

    dust,

    germs,

    water vapour,

    carbon dioxide, etc.

    The concentration of contaminants that can endanger health and adversely affect

    processes rises quickly in enclosed rooms.

    Removal ofstale air

    The concentration of contaminants must be reduced to a safe level. This is

    accomplished by extracting all or part of the stale air.

    Supply of freshair

    The extracted air is replaced with air from the outside. This air is often referred

    to as fresh air. This outside air is assumed to be of better quality than the

    extracted air. This is not always the case however. This is why fresh air must be

    conditioned before it is introduced into a space.

  • 7/22/2019 air conditionning systems.pdf

    25/253

    21July 2006

    Air conditioning systems Page 22/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Definition

    (continued)

    Fresh-airconditioning

    Fresh air is conditioned in a number of ways:

    It is filtered to ensure the right level of cleanliness,

    It is heated or cooled to ensure the right temperature,

    It is either humidified or dehumidified to ensure the correct level of humidity.

    These processes are energy consuming.

    Fresh air

    +32C

    Stale air

    discharge

    Forced-draught fan

    -10C

    +20Cor

    +25C

    ExtractionfanFilters

    Preheating or precooling coil

    or both if need be

    to

    Winter : ambient +20Cair supply +30C

    Summer : ambient +25Cair supply +15C

    ENERGY-

    CONSUMING

    SYSTEM

    Fresh air can be conditioned:

    For specific environmental conditions. In this case it is not used to heat orcool the space,

    For specific air flow conditions in a space. In this case a portion is usedfor heating and cooling. As the volume of fresh air is small, it is simply

    an addition.

  • 7/22/2019 air conditionning systems.pdf

    26/253

    21July 2006

    Air conditioning systems Page 23/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Definition

    (continued)

    Heat recoveryunits

    The phenomenon is most flagrant in winter. Fresh air drawn in from outdoors is

    at low temperature (e.g. -10C) and stale air discharged outdoors is at high

    temperature (+20C at comfort levels).

    A heat recovery unit is a device used to transfer heat without any direct contact

    between both types of air. More specifically, a portion of the heat in the exhaust

    air is transferred to the supply air. This exchange of heat results in lower energy

    consumption.

    Exhaustair

    Freshair

    Outdoors

    -10C/90%32C/40%

    Air-conditionedspace

    20C/50% (winter)25C/50% (summer)

    Energy recoverysystem

    A H U

  • 7/22/2019 air conditionning systems.pdf

    27/253

    21July 2006

    Air conditioning systems Page 24/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Air purification:

    the No concept

    The No concept is based on the combination of an adsorbent such as

    activated carbon and photocatalysis.

    Polluted air

    mineralization byphotocatalysis

    Contaminant retention Purified air

    NEO operation principle

    Contaminant removal

    ACTIVATED

    carbon

    ULTRAVIOLETradiation

    desorptionabsorption

  • 7/22/2019 air conditionning systems.pdf

    28/253

    21July 2006

    Air conditioning systems Page 25/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Air purification:

    the No concept(continued)

    The activated carbon [Navarri et al., 2001] absorbs large quantities of

    contaminants along its surface (it has a specific surface area ofapprox. 1000 m/g). These contaminants are trapped by low-intensity

    electrostatic forces, called van der Waals bonds, with interaction energies of

    5 to 40 kJ/mol. The main drawback of this kind of filter is the saturation

    point of activated carbon. Known as the breakthrough point, this threshold

    is very difficult to predict in cases where concentrations and flow rates vary.

    Once this point is reached, the filter can no longer achieve the desired

    concentration efficiency. Titanium dioxide (TiO2) photocatalysis in the gas

    phase [Nguyen, 2001] is a heterogeneous catalysis process in which the

    solid catalyst is activated only by ultraviolet radiation. Under certain

    conditions, the heterogeneous photocatalysis process is capable of

    mineralising pollutants completely. It is split into five phases:

    transfer of gaseous reagents to the photocatalytic surface,

    adsorption of the gaseous reagents on the photocatalytic surface,

    photochemical reaction between the adsorbed gaseous reagents and thephotocatalytic surface; mineralisation of organic compounds,

    desorption of gaseous photocatalytic reaction products,

    diffusion of the gaseous products off the photocatalytic surface.

    The main drawback of photocatalysis used on its own is the low adsorption

    capacity of the catalyst (titanium dioxide) which prevents it driving down

    high pollution levels. Pollutants are thus only partially mineralised when

    concentrations and/or flow rates are high. Combining a filter containing anadsorbent such as activated carbon with a photocatalysis system eliminates

    the drawbacks inherent to each process and also significantly cuts down on

    maintenance.

  • 7/22/2019 air conditionning systems.pdf

    29/253

    21July 2006

    Air conditioning systems Page 26/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units

    The term heat recovery unit, or HRU, covers various types of equipment:

    dual-coil recovery units,

    plate heat exchangers,

    heat pipes,

    heat recovery wheel.

    Dual-coilrecovery units

    As is implied by its name, a dual-coil recovery unit consists of two standard

    finned coils connected by a circuit through which refrigerant (antifreeze if

    necessary) is circulated by a circulator pump.

    One coil is placed in the exhaust air circuit and the other in the supply air circuit.

    The air and water circuits are arranged for counter-current circulation.

    Safety valve

    HEAT

    RECOVERY

    COIL

    HEAT

    RECOVERY

    COIL

    Circulator

    +20C

    50%

    -10C90% Drain

    Circuit

    filling

    Preheate

    d

    freshair

    Exhausta

    ir

    Expansionvessel

    Freshair

    Cooled

    exhaust

    air

    Drain valve

  • 7/22/2019 air conditionning systems.pdf

    30/253

    21July 2006

    Air conditioning systems Page 27/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Dual-coilrecovery units

    (continued)

    This system allows for much flexibility, and the coils can be integrated inside the

    air handling unit.

    Water

    Exhaustair

    Freshair

    Outdoors

    AHU+/-

    +/-

    Return air

    Supplyair

    Air-conditionedspace

    In more complex cases where an air extraction system cannot be installed in the

    same space as a fresh-air conditioning system, both can be connected

    hydraulically.

    Forced-draughtfan

    Extractionfan

    Conditionedsupply air

    Pump

    Glycol/water heat transfer circuit

    Airextrait

    Freshair

    Exhaustair

    Water

  • 7/22/2019 air conditionning systems.pdf

    31/253

    21July 2006

    Air conditioning systems Page 28/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Heat pipe A heat pipe is a metal tube usually with fins on its outside and containing a fluidin the form of two balanced phases:

    a liquid phase,

    a gas phase.

    It transfers heat through a cycle of evaporation and condensation.

    1. The fluid evaporates in the hot end (evaporator).

    2. The vapour thus formed condenses on the cold end (condenser).

    3. The fluid from the cold end returns to the hot end:

    By gravity, in which case the condenser section must be above theevaporator section,

    Via a capillary (or wick) structure lining the inside wall of the tube. Theheat pipe can also operate horizontally in this case; a slight angle of 7-8

    will promote movement.

    HORIZONTAL HEAT PIPE

    Liquid

    Vapor

    Liquid

    Evaporation section Condensation section

    Capillary

    structure

    Extracted warmair enters

    Warmed

    air exits

    Cooled airexits

    Cool freshair enters(cold source)

    Partition

    Heat transfer

    (hot source)

    Heat

    recovery

  • 7/22/2019 air conditionning systems.pdf

    32/253

    21July 2006

    Air conditioning systems Page 29/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Heat pipe(continued)

    Condensed

    liquid

    Heat transfer

    (hot source)

    Heat

    recovery

    Vapour

    Capillary

    structure

    Extracted

    warm air

    enters

    Cooled air

    exits

    Warmed

    air exits

    Cool fresh

    air enters(cold source)

    The pipes are arranged in arrays split into two by a sealed partition separating the

    two streams of air.

    The evaporation and condensation temperatures are highly similar and the

    operation is virtually isothermal. The transfer occurs only through the latent heat

    of the change in state.

    gravity causes liquidto flow back down

    condensation

    vaporisation

    vapour

    Warmedair exists

    Liquid

    Extracted warmedair enters

    C

    ondensation

    section

    Evaporation

    section

    Heat

    recovery

    Cooledair exits

    Cool freshair enters

    (cold source)

    Heat transfer

    (hot source)

    VERTICAL HEAT PIPE

    Vapor

  • 7/22/2019 air conditionning systems.pdf

    33/253

    21July 2006

    Air conditioning systems Page 30/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Heat pipe(continued)

    partitionheat pipe

    coolai

    r

    warm

    air

    warmedair

    cooled

    air

    The figure below illustrates a constant-flow model of a ClimaCIAT dual-flow

    AHU with heat pipes:

    Exhaust air

    Fresh air-10C

    Exhaust air+20C

    Air supply

    The figure below illustrates a ClimaCIAT dual-flow AHU with variable-flow

    heat pipes and a mixing box:

    Freshair

    -10C

    Exhaustair

    +20CExhaust

    air

    Airsupply

  • 7/22/2019 air conditionning systems.pdf

    34/253

    21July 2006

    Air conditioning systems Page 31/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Plate heatexchanger

    In this type of heat exchanger, horizontal and vertical streams of air flow

    between thin plates stacked in parallel:

    The exhaust air transfers its heat to the air flowing between the plates.

    There are two types of flow arrangement:

    cross-flow,

    counter-flow.

  • 7/22/2019 air conditionning systems.pdf

    35/253

    21July 2006

    Air conditioning systems Page 32/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)Plate heat

    exchanger (continued)

    Cross-flowexchanger

    Counter-flowexchanger

    Exhaustair

    Fresh air

    Exhaustair

    Cooledexhaust

    air

    Inside

    Outside

    Fresh air

    Preheatedfresh air

    Platethickness

    Gap

    This figure illustrates a ClimaCIAT dual-flow AHU with a plate heat exchanger

    but no mixing box:

    constant flow of exhaust air,

    constant flow of fresh air.

    Fresh air-10C

    Exhaustair

    +20C

    Exhaust air

    Air supply

  • 7/22/2019 air conditionning systems.pdf

    36/253

    21July 2006

    Air conditioning systems Page 33/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Plate heatexchanger

    (continued)

    The figure below illustrates a ClimaCIAT dual-flow AHU with a plate heat

    exchanger and a mixing box. The flow of air over the plate heat exchanger can

    be adjusted.

    exhaust air+20C

    exhaust air

    fresh air-10C

    supply air

    Example of an air handling process: fresh air in with recovery of heat from

    exhaust air by a plate exchanger.

    Dual-flow AHU

    exhaustair

    AIR-TO-AIRheat exchanger

    frost protection dampers freshair

    supply

    air

    exhaust

    air

    R

  • 7/22/2019 air conditionning systems.pdf

    37/253

    21July 2006

    Air conditioning systems Page 34/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Heat recoverywheel

    A heat recovery wheel is a low-speed wheel (10-20 rpm) with many small

    channels through which air passes. A little less than half the front surface is

    connected to the exhaust air circuit. A little less than half the surface is

    connected to the supply air circuit. A small surface is used as the purge sector.

    As the wheel rotates, the section heated by the warm air gives up its heat to the

    stream of cool air flowing through it.

    The two air streams thus flow through the channels alternately.

    motor

    fresh

    air

    exh

    aust

    air

    purge sector

    drive belt

  • 7/22/2019 air conditionning systems.pdf

    38/253

    21July 2006

    Air conditioning systems Page 35/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Heat recoverywheel

    (continued)

    Apurge sectoris usually built over the wheel to minimise carryover from the

    exhaust air. To facilitate this, the pressure of the exhaust air must be lower than

    that of the supply air.

    direction of

    rotation

    purge sector

    P4

    P1

    P1>P4 exhaust air

    fresh air

    duct exhaust air

    exhaust air

    supply air fresh air

    seal

    purge sector

    purge stream

    whell

    direction ofrotation

  • 7/22/2019 air conditionning systems.pdf

    39/253

    21July 2006

    Air conditioning systems Page 36/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    units (continued)

    Heat recoverywheel

    (continued)

    The figure below illustrates a ClimaCIAT dual-flow AHU with a rotary heat

    exchanger without amixing boxbypass:

    constant flow of exhaust air,

    constant flow of fresh air.

    fresh air-10C

    exhaustair

    exhaust air+20C

    supplyair

    The figure below illustrates a ClimaCIAT dual-flow AHU with a rotary heat

    exchanger, mixing box and adjustable air flow:

    fresh air-10C

    supply air

    exhaust air+20C

    exhaust air

  • 7/22/2019 air conditionning systems.pdf

    40/253

    21July 2006

    Air conditioning systems Page 37/37 Definitions

    Air conditioning systemsVersion 1.0

    Fresh-air conditioning (continued)

    Heat recovery

    (continued)

    Importantinformation

    Choosing the right fresh-air conditioning method is part of the design process.

    It depends on the type of air handling equipment that will be used:

    When the air in a large number of spaces is to be handled by standardterminal units (e.g. fan coil units), fresh air should be handled completely by

    one central unit,

    When the air in a space is handled by an AHU, a single or double mixing boxmay be added to help to condition fresh air.

  • 7/22/2019 air conditionning systems.pdf

    41/253

    21 July 2006

    Air conditioning systems Page 1/29 All-air systems

    Air conditioning systemsVersion 1.0

    CCChhhaaapppttteeerrr222:::AAAllllll---aaaiiirrrsssyyysssttteeemmmsss

  • 7/22/2019 air conditionning systems.pdf

    42/253

    21 July 2006

    Air conditioning systems Page 2/29 All-air systems

    Air conditioning systemsVersion 1.0

    Contents

    Contents .................................................................................................................... 2

    Basic concept ........................................................................................................... 3

    Definition..................................................................................................................... 3

    Air handling unit .......................................................................................................... 5

    Possible solutions....................................................................................................... 6

    Local air handling unit.............................................................................................. 7

    Concept ...................................................................................................................... 7

    Operation.................................................................................................................... 8

    Mollier chart ................................................................................................................ 9

    Single-zone air handling unit................................................................................. 10Concept .................................................................................................................... 10

    Operation.................................................................................................................. 11

    Mollier chart .............................................................................................................. 13

    Field of application.................................................................................................... 14

    Dual-duct AHU ........................................................................................................ 15

    Concept .................................................................................................................... 15

    Operation.................................................................................................................. 16

    Mollier chart .............................................................................................................. 17

    Field of application.................................................................................................... 17

    Multizone unit.......................................................................................................... 18

    Concept .................................................................................................................... 18

    Operation.................................................................................................................. 19

    Mollier chart .............................................................................................................. 21

    Field of application.................................................................................................... 21

    Air handling unit with variable-volume diffusion boxes for each space ........... 22

    Concept .................................................................................................................... 22

    Operation.................................................................................................................. 23

    Field of application.................................................................................................... 25

    Impulsair ................................................................................................................... 25

  • 7/22/2019 air conditionning systems.pdf

    43/253

    21 July 2006

    Air conditioning systems Page 3/29 All-air systems

    Air conditioning systemsVersion 1.0

    Basic concept

    Definition Air is preconditioned by an air handling unit then supplied to a space via a duct.

    All the heatneeded to cool a space is carried by air:

    Air conditioning is generally centralised,

    The mechanical room contains:

    refrigeration equipment,

    heating equipment,

    an air handling unit in which air, including fresh air, is conditioned,

    The ductwork contains:

    return ducts running from each space,

    stale air exhaust ducts,

    fresh air supply ducts, supply ducts running to each space.

  • 7/22/2019 air conditionning systems.pdf

    44/253

    21 July 2006

    Air conditioning systems Page 4/29 All-air systems

    Air conditioning systemsVersion 1.0

    Basic concept (continued)

    Definition

    (continued)

    The drawing below illustrates the basic design of an all-air system.

    exhaust air

    fresh air

    hotwater

    chilledwater

    supplyair

    retrurnair

    A.H.U.

    ductworkair handling unit

    water boiler

    water chiller

  • 7/22/2019 air conditionning systems.pdf

    45/253

    21 July 2006

    Air conditioning systems Page 5/29 All-air systems

    Air conditioning systemsVersion 1.0

    Basic concept (continued)

    Air handling unit The flow of the air handled by the unit is determined by:

    thermal loads,

    the acceptable t between the supply and return air (see comfort airconditioning and air handling).

    For obvious reasons of economy, the supply of fresh air is limited (unless

    required otherwise for safety) to minimum healthy levels set out by regulations.

    The type of handling needed is defined by the influencer, who then buildsthe air

    handling unit to fit the needs of the space.

    For example, the AHU below contains the following equipment:

    1 return air fan,

    2 exhaust air/recirculated air mixing

    dampers,

    3 prefilter,

    4 cooling coil and heating coil,

    5 humidifier,

    6 forced-draught fan,

    7 f inal filter.

    exhaust air

    return air

    fresh air

    1

    2

    3

    supply air

    45

    6

    7

    In some cases (such as cleanrooms; see our document on filtration) the final filter

    may be placed at the entrance to a space instead of inside the AHU to allow

    for potential pollution from ductwork.

  • 7/22/2019 air conditionning systems.pdf

    46/253

    21 July 2006

    Air conditioning systems Page 6/29 All-air systems

    Air conditioning systemsVersion 1.0

    Basic concept (continued)

    Air handling unit

    (continued)

    The drawing below shows an air handling system with a heat recovery unit

    installed on the fresh air/exhaust air circuits.

    heat recovery unit on exhaust air circuit

    exhaust

    air

    return air from

    served spaces

    supply airfresh

    air

    128

    43 5 6 7

    mixes exhaust air and

    recirculated air

    Possible solutions The solutions depend on the type of space and changes in loads, as well as

    investment possibilities and the requirements for each space.

    The most common solutions include:

    individual space equipment: a separate AHU and ducts for each space,

    multispace equipment: a unit with ducts for a series of spaces,

    a single unit connected to two ducts, one for hot air and the other for cool air.A mixing box ensures the adequate mix of air for each space,

    a multizone AHU with separate ducts for each space,

    basic equipment (air handling unit) with, for each space, a variable-volume

    air diffusion box.

  • 7/22/2019 air conditionning systems.pdf

    47/253

    21 July 2006

    Air conditioning systems Page 7/29 All-air systems

    Air conditioning systemsVersion 1.0

    Local air handling unit

    Concept Each space is supplied with conditioned air by its own specific unit:

    constant flow of air,

    fresh air (suction) is usually conditioned in the AHU which also extracts staleair,

    the components (filter, cooling and heating coils, humidifier) are determinedbased on the requirements of each space.

    Heating and refrigeration equipment is with the unit in the mechanical room or

    outside (cooling system with air-cooled condenser).

    exhaustair

    Example of a unit with electric heating coil and chilled-water

    cooling coil with temperature control only

    freshair

    volume = constantT = f (space requirement)

    R

  • 7/22/2019 air conditionning systems.pdf

    48/253

    21 July 2006

    Air conditioning systems Page 8/29 All-air systems

    Air conditioning systemsVersion 1.0

    Local air handling unit (continued)

    Operation The unit adjusts conditions based on the space loads. It:

    regulates the temperature (summer and winter),

    regulates the humidity (winter),

    and, in certain cases, dehumidifies the air (summer).

    In the drawing below, regulation occurs with the following sequences:

    Sensors Effect on

    Temperature cooling coil (chilled water) (1)

    heating coil (hot water) (2)

    Relative humidity cooling coil (chilled water) (1)

    humidifier (3)

    Occupancy fresh air damper

    Outdoor temperature free cooling (energy savings)

    room

    supply air

    A

    exhaustair

    extraction air

    T : Temperature sensorH : Humidiy sensorO : Occupancy meter

    O

    T

    T

    S

    EFM C

    H

    freshair

    (1) and (2) 2-way or 3-way modulating or on/off valve(3) 2-way on/off valve

    (1) (2) (3)

    R

  • 7/22/2019 air conditionning systems.pdf

    49/253

    21 July 2006

    Air conditioning systems Page 9/29 All-air systems

    Air conditioning systemsVersion 1.0

    Local air handling unit (continued)

    Mollier chart Changes in air temperature and humidity are plotted in the following manner on

    what is called aMollier chart.

    O

    M

    t

    wq'

    HM

    space linesegment

    summer operation

    O : outdoor airI : indoor environmentM : mixing

    S : supply airC : supply from cooling coil

    H : supply from heating coil Ssummer line segment

    Hwinter line segment

    winter operation

    S

    I

    I

    SS

    W

    C

    100%

    O

    H

    Field ofapplication

    This type of system is generally used for:

    large-volume spaces,

    low-tolerance environmental controls,

    spaces with heavy load conditions that vary,

    meeting rooms,

    theatres and concert halls.

  • 7/22/2019 air conditionning systems.pdf

    50/253

    21 July 2006

    Air conditioning systems Page 10/29 All-air systems

    Air conditioning systemsVersion 1.0

    Single-zone air handling unit

    Concept Air is supplied to several spaces by a single air handling unit:

    the air flow for each individual space is constant and calculated based on itsmaximum heat load,

    fresh air (suction/extraction) is generally conditioned in the AHU beforebeing supplied to all the spaces,

    the components (filter, cooling and heating coils, humidifier, etc.) aredetermined based on the needs of each space,

    heating and refrigeration equipment is generally located in the mechanicalroom,

    detection devices (temperature and humidity sensors) are arranged in acontrol room.

    exhaust air

    fresh air

    hot

    water

    chille

    dwater

    supp

    lyair

    retur

    nair

    A.H.U.

    ductworkair handlingunit

    water boiler

    water chiller

    This type of system is also called a simplified all-air system.

  • 7/22/2019 air conditionning systems.pdf

    51/253

    21 July 2006

    Air conditioning systems Page 11/29 All-air systems

    Air conditioning systemsVersion 1.0

    Single-zone air handling unit (continued)

    Operation This system is used for spaces where the following loads are identical:

    distribution of sensible heat and latent heat, changes and variations in the same direction and proportions,

    The properties of the air supplied to each space are the same,

    Fresh air is distributed based on the total load, not on the density of occupantsin the space.

    The control devices and temperature and humidity sensors may be installed:

    In a control room (e.g.

    A1)

    The other spaces (A2, A3etc.) are governed by the A1

    law.

    In the main return airsection

    All the spaces (A1, A2, A3etc.) are governed by thelaw of averages.

    Space conditions cannot be adjusted to personal preferences,

    As a matter of fact, spaces rarely experience the same changes in heat.Deviations occur in environment parameters on account of the fact that the air

    supply conditions are the same for all spaces. The system would not be an

    adequate choice for precision air conditioning.

  • 7/22/2019 air conditionning systems.pdf

    52/253

    21 July 2006

    Air conditioning systems Page 12/29 All-air systems

    Air conditioning systemsVersion 1.0

    Single-zone air handling unit (continued)

    Operation

    (continued)

    The figure below shows an installed single-zone air handling unit.

    SA3

    A2

    A1

    S

    (1) and (2) 2-way or 3-way modulating or on/off valve(3) 2-way on/off valve

    S

    (1)(2)(3)

    T

    T H

    exhaustair

    fresh

    air

    R

  • 7/22/2019 air conditionning systems.pdf

    53/253

    21 July 2006

    Air conditioning systems Page 13/29 All-air systems

    Air conditioning systemsVersion 1.0

    Single-zone air handling unit (continued)

    Mollier chart Changes in the air supplied to the spaces are plotted on the Mollier chart.

    S

    2

    A3

    A1=A

    A2

    3

    1

    t

    wq'

    This diagram does not show the various handling/conditioning processes the air

    undergoes in the unit. It shows changes in the air in each space based onsensible and latent heat.

    1, 2, and 3 are the line segments. A is the space setpoint. When the same

    amount of air S is distributed to all the spaces, it is clear that the space

    conditions A cannot be controlled when their loads are different,

    the space line segments 1, 2, 3 are rarely completely identical,

    all pass by the same supply air point.

    The indoor environment A1, A2, A3, should have the same value A, but as the

    loads are not really identical, the value of A is controlled only for the space

    where the sensors are installed (i.e. space A1for which A1will equal A).

  • 7/22/2019 air conditionning systems.pdf

    54/253

    21 July 2006

    Air conditioning systems Page 14/29 All-air systems

    Air conditioning systemsVersion 1.0

    Single-zone air handling unit (continued)

    Mollier chart

    (continued)

    To sum up:

    The simplified all-air system is adequate only if the thermal loads in each zoneare identical and vary in the same direction and proportions,

    The balance and stability of the air flows are deceptive for branched orlengthy systems.

    fresh air

    zone 1 zone 2 zone 3 zone 4

    return air

    duct

    supply air

    duct

    no means ofregulation

    supply air conditions are

    the same for every zone

    Field ofapplication

    Because it is economic, the system may be used for spaces with identical thermal

    loads and where conditions do not need to be adjusted to personal preferences.

  • 7/22/2019 air conditionning systems.pdf

    55/253

    21 July 2006

    Air conditioning systems Page 15/29 All-air systems

    Air conditioning systemsVersion 1.0

    Dual-duct AHU

    Concept This system offers the following features:

    A singleair handling unit that is simplified for air preconditioning. It is madeup of:

    a mixing box,

    a preheating coil for winter,

    The supply air duct leaving the AHU is split in two:

    warm air duct with preheating coil and humidifier,

    cool air duct with cooling coil,

    Three ducts are routed to and from spaces:

    cool air supply duct,

    warm air supply duct,

    extraction duct.

    The unit is generally operated at high speed (V >6 m/s) for reasons of space.

    Each space contains a motorised mixing box controlled by the space sensor.

    The supply air is delivered at a constant rate but the proportions of cool and

    warm air vary.

    C

    F

    S

    spacesensor

  • 7/22/2019 air conditionning systems.pdf

    56/253

    21 July 2006

    Air conditioning systems Page 16/29 All-air systems

    Air conditioning systemsVersion 1.0

    Dual-duct AHU (continued)

    Operation Contrary to what might be thought, the system is not particularly energy

    consuming: Most often (in spring and autumn, amongst other periods) only one of the

    ducts (heating or cooling) is supplied with air that has been conditioned

    simply by mixing the outdoor air with the recirculated air,

    When both ducts are needed, the hot water is delivered by the condenser in thewater chiller unit (the condenser then becomes a heat transfer unit).

    Fresh air is introduced when the outdoor temperature drops below room

    temperature and cooling is needed.

    A3

    S3

    A2

    A1

    T

    T

    exhaustair

    freshair

    S2

    T

    S1

    T

    (1) and (2) 2-way modulating or on/off valve

    (3) 2-way on/off valve

    (2) (2)(1)(3) R

  • 7/22/2019 air conditionning systems.pdf

    57/253

    21 July 2006

    Air conditioning systems Page 17/29 All-air systems

    Air conditioning systemsVersion 1.0

    Dual-duct AHU (continued)

    Mollier chart Changes in air temperature and humidity are plotted on the Mollier chart.

    O

    M

    H

    C

    t

    w

    q'

    C

    M

    I

    I

    SS

    W

    C

    E

    S

    O : outdoor airI : indoor air

    M : mixingH : warm air stream properties

    S : supply airC : cool air stream properties

    Ssummer line segment Wwinter line segment

    Field of

    application

    This system is advantageous for handling the air in spaces with heavy load

    conditions that vary.

    It is often used with laminar-flow ceilings:

    business spaces,

    exhibition halls,

    upscale spaces: large glazed surfaces subject to varying loads.

  • 7/22/2019 air conditionning systems.pdf

    58/253

    21 July 2006

    Air conditioning systems Page 18/29 All-air systems

    Air conditioning systemsVersion 1.0

    Multizone unit

    Concept This system offers the following features:

    The conditions of the supply air are adjusted by mixing the cool and warm air,

    Both air types are mixed inside the unit and occupants in each space (or zone)choose the level they want,

    Each space has its own separate supply air duct:

    constant air flow,

    variable supply air temperature,

    The return air ducts may be shared.

    The AHU has a different design.

    recirculatedair

    filter fan

    thermostat

    heating

    coil

    cooling coil

    freshair

    warm air

    cool air

    zone 3 (H)zone 2 (H)

    zone 1 (H)

    zone 3 (C)zone 2 (C)

    zone 1 (C)

    R

    (1) and (2) 2-way or 3-way modulating or on/off valve

    (1)

    (2)outdoor sensor

    R

    R

    outdoor sensor

    The heating and cooling coils are installed in parallel (not in series) on the aircircuit. This creates a stream of warm air and a stream of cool air,

    The fan is installed upline and blows air on the coils,

    Two rows of dampers downline of the coils (one on the warm stream, theother on the cool stream) are used to mix warm air and cool air,

    Vertical barrier walls are used to divide the free areas (i.e. volumes of air) andcreate zones inside the unit. The air flows at work are a function of the thermal

    balances. A unit is typically split into no more than four or five zones.

  • 7/22/2019 air conditionning systems.pdf

    59/253

    21 July 2006

    Air conditioning systems Page 19/29 All-air systems

    Air conditioning systemsVersion 1.0

    Multizone unit (continued)

    Operation The figure below shows a multizone unit.

    recirculated air

    return air A

    freshair

    limit swich for : 3 rooms 3 zones 3 air supply ducts the return air duct may be shared

    A3A2A1

    T1

    T2

    T3

    S1 S2 S3

    T

    exhaustair

    M3

    M2

    M1

    M3M2

    M1

    C

    F

    The sets of dampers are used to mix air in all types of proportions possible for each zone :Warmed air (H) mixed with conditioned air (M) by the mixing box in winterCooled air (C) mixed with conditioned air (M) by the mixing box in summer

    M

    (2)

    (1)

    (1) and (2) 2-way or 3-way modulating or on/off valve

    R

  • 7/22/2019 air conditionning systems.pdf

    60/253

    21 July 2006

    Air conditioning systems Page 20/29 All-air systems

    Air conditioning systemsVersion 1.0

    Multizone unit (continued)

    Operation

    (continued)

    the coils ensure constant cool-air and warm-air temperatures,

    servomotors controlled by the space thermostat adjust the dampers foradequate air mixing:

    a detection unit measures the outdoor air temperature and controls themixing box servomotor (free cooling),

    limit switches (servomotors zone) also participate in regulating air flows.Closing all the zones during heating will cause the heating coil supply to

    close.

    Note:

    as stated previously, the energy-efficient operation described below isfrequently observed:

    only one coil (cooling C or heating H) is supplied and the air delivered bythe mixing box (M = mix of fresh air and recirculated air) is divided

    between the supplied coil and the unsupplied one.

    this gives a new mix:

    C + M or H + M depending on the need,

    when adjusted correctly, this type of system is relatively energy efficient,

    by using refrigeration equipment such as a heat transfer unit, heat from thecondenser can be used in cases where both cooling and heating are necessary.

  • 7/22/2019 air conditionning systems.pdf

    61/253

    21 July 2006

    Air conditioning systems Page 21/29 All-air systems

    Air conditioning systemsVersion 1.0

    Multizone unit (continued)

    Mollier chart Changes in the air supplied to a given space are plotted on the Mollier chart.

    O

    O

    MH

    M

    C

    t

    w

    q'

    CC

    S

    W

    S1

    I1

    S1

    I1

    O : outdoor airI : indoor airM : mixingH : supply from heating coilS : supply airC : supply from cooling coil

    Ssummer line segment Hwinter line segment

    Field ofapplication

    The systems advantage lies in its quick responsiveness and the ability to adjust

    spaces to individual needs:

    Groups of spaces with load conditions that vary quickly,

    Series of spaces, each with occupancy loads that are never the same or varyfrom zone to zone (this makes it possible to lower the total installed capacity).

    It is therefore well-suited to spaces such as:

    company canteens, dining halls, homes (day zone, night zone).

  • 7/22/2019 air conditionning systems.pdf

    62/253

    21 July 2006

    Air conditioning systems Page 22/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling unit with variable-volume diffusion boxes for eachspace

    Concept This system offers the following features:

    variations in thermal loads are handled by adjusting the flow of conditionedairsupplied to each space,

    a single air handling unit for all spaces,

    the AHU may be equipped with a flow control system (suction deflectors orspeed control),

    it may be constant volume; if so, each space is equipped with a bypass.

    variable-volumebox

    variable-speedforced-draught fan

    variable-speedreturn air fan

    air handlingunit

    return air

    exhaust air fresh air

    air outlet

    return airgrille

    System with variable volumes of air per zoneUnit equipped with a flow controller

  • 7/22/2019 air conditionning systems.pdf

    63/253

    21 July 2006

    Air conditioning systems Page 23/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Operation How the system operates:

    air is regulated in the air handling unit to ensure a constant supply airtemperature. The AHU operates in either heating or cooling mode; differing

    needs cannot be met,

    the flow of supply air to each space is modulated by the space sensor based onthe heat load.

    In the example below:

    Air is delivered to Type A spaces by the variable air volume system; the returnair flows along passageways (halls),

    Type B spaces are equipped with their own individual units. Stale air is drawnout by a separate extraction unit.

    AB

    T

    T

    exhaust air

    return air

    discharge

    outside outsidehall

    distribution ofconditioned air bypass

    fresh air

    T

    (1) and (2) 2-way or 3-way modulating or on/off valve(3) 2-way on/off valve

    (1)(2)(3)

    window

    fan coil unit with fresh air inlet

    Constant-volume unit with

    space bypasses

    H

    R

  • 7/22/2019 air conditionning systems.pdf

    64/253

    21 July 2006

    Air conditioning systems Page 24/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Mollier chart Changes in the air in the AHU are plotted as follows on the Mollier chart.

    O :outdoor airI : indoor airM : mixingS : supply air

    Ssummer linesegment

    O

    M

    t

    w

    q'

    S S I

    Air is conditioned in the conventional manner inside the unit. The regulation

    system ensures that the temperature and humidity of the supply air are at

    particular levels. However, the amount of air delivered to each space is adjusted

    as needed.

    Issues andprecautions foruse

    Variations in flow in a given space should not disrupt the balance of the wholeor the flows delivered to the other spaces.

    A system is needed to control and maintain the pressure in the distributioncircuits.

    High variations and significant drops in flow rates may cause the geometry ofthe air stream introduced and its range to create uncomfortable conditions for

    occupants.

    As regards air change, a number of problems may arise:

    The fresh air is conditioned entirely inside the unit.

    Each space receives the required amount of fresh air under full load

    conditions.

    Losses (e.g. insulation) may cause heat load variations in the spacewhereas the occupant density (i.e. the need for fresh air) stays even. The

    modulation of the flow of supply air in turn modulates the amount of fresh

    air introduced.

    Adjustingflow and pressure may be tricky; an adjusting device may need tobe installed to maintain the pressure inside the ducts at a constant level.

    Installing ceiling registers specially designed to keep air streams horizontal isrecommended.

  • 7/22/2019 air conditionning systems.pdf

    65/253

    21 July 2006

    Air conditioning systems Page 25/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Field ofapplication

    This system, quite rate in France, may be used in:

    office buildings,

    hotels.

    Impulsair The impulsair is a variable-air-volume adjustment system used in the 1970s.

    The Coandaeffect

    The operation of the impulsair is based on a well-known aerodynamic

    phenomenon known as the Coanda effect, or the extremely odd tendency of air

    to adhere to the surface along which it is flowing.

    Henri Coanda discovered this phenomenon in 1928 when he noticed that hot

    gases from his experimental jet-propelled aircraft hugged the sides of the

    fuselage, damaging the tail unit.

    On closer look at this phenomenon, it can be seen that a fluid will stay attached

    to a surface, even a convex one, as is moves along it.

    Coanda effect

    stream of fluid

  • 7/22/2019 air conditionning systems.pdf

    66/253

    21 July 2006

    Air conditioning systems Page 26/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Impulsair(continued)

    Concept A stream of air directed towards a Y-duct can be deflected to either branch if twolateral openings A and B are placed just before the Y-duct.

    Opening A and closing B will direct all the air to the right branch. Conversely,

    closing A and opening B will direct all the air to the left branch.

    A B A B

    Variable-volume impulsair systems have the following main features:

    constant supply air velocity resulting in even space temperature,

    air flows are adjusted without the means of moving components such asdampers or motors (zero breakdowns or servicing),

    constant volume in the air handling units, air is supplied to spaces intermittently. The supply time, not the volume

    supplied, is modulated.

  • 7/22/2019 air conditionning systems.pdf

    67/253

    21 July 2006

    Air conditioning systems Page 27/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Impulsair(continued)

    Concept(continued)

    If Then

    Space cooling under full load is

    required.

    The control damper is maintained in a position set by the

    thermostat while the main damper directs the entire volume of air

    to the space.

    The temperature in the space

    decreases, as does the need for cool

    air.

    The thermostat controls the impulsair. The air from the unit is

    directed to either the space or the recirculation duct. At the start,

    the supply time is longer than the recycling time.

    Cooling requirements continue to

    decrease.

    The impulsair responds by gradually shortening the supply time

    and extends the recycling time.

    suspended ceiling

    diffuser

    damper

    damper

    damper

    return air

    supply air

    return air grille

    ceiling

    T

    impulsair

    Operation Note:

    Although it is theoretically conceivable that the entire volume of air be

    recycled and that no more air be directed to the space, this possibility should be

    excluded in a well-designed system. Firstly, lighting and people are a basic

    cooling load. By carefully selecting the supply air temperature, however, a high

    rate of air can be obtained even if the heat gain is minimal.

    What occurs between 100% supply air and 100% recycling is depicted in the

    figure on the following page. The surfaces at the top show the air flows

    delivered to the space. The surfaces at the bottom show the flow rates of

    recirculated air.

  • 7/22/2019 air conditionning systems.pdf

    68/253

    21 July 2006

    Air conditioning systems Page 28/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Impulsair(continued)

    Operation(continued)

    100% constant-volume air stream

    time in seconds

    spaces100

    100

    returnpercentageofveloc

    ity

    spaces100

    250

    100

    return

    p

    ercentageofflow

    2 HZ (max.frequency)

    2 54 565248 504642 444036 3834323026 282420 221814 16128 10640

    AIR VELOCITY

    AIR FLOW

  • 7/22/2019 air conditionning systems.pdf

    69/253

    21 July 2006

    Air conditioning systems Page 29/29 All-air systems

    Air conditioning systemsVersion 1.0

    Air handling with variable-volume diffusion boxes for eachspace (continued)

    Impulsair(continued)

    Operation(continued)

    The figure below shows an installed system with impulsair units.

    return air grille

    impulsair

    diffuser

    diffuser

    forced-draught fan

    return air fan

    airhan

    dlingunit

  • 7/22/2019 air conditionning systems.pdf

    70/253

    21 July 2006

    Air conditioning systems Page 1/33 All-water systems

    Air conditioning systemsVersion 1.0

    CCChhhaaapppttteeerrr333:::AAAllllll---wwwaaattteeerrrsssyyysssttteeemmmsss

  • 7/22/2019 air conditionning systems.pdf

    71/253

    21 July 2006

    Air conditioning systems Page 2/33 All-water systems

    Air conditioning systemsVersion 1.0

    Contents

    Contents .................................................................................................................... 2

    Basic concept ........................................................................................................... 3

    Definition of an all-water system ................................................................................................ 3

    Possible solutions........................................................................................................................ 4

    Fan coil units............................................................................................................. 5

    Basic concept ............................................................................................................................... 5

    Two-pipe fan coil unit .................................................................................................................. 7

    Four-pipe fan coil unit.................................................................................................................. 9

    Two-pipe, two-wire fan coil unit................................................................................................ 11

    Air-change fan coil unit.............................................................................................................. 13Non self-contained air-handling terminal units.................................................... 15

    Basic concept ............................................................................................................................. 15

    Equipment type .......................................................................................................................... 15

    Fan coil units .............................................................................................................................. 15

    Mini air handling units ............................................................................................................... 20

    Individual water-loop heat pumps......................................................................... 29

    Basic concept ............................................................................................................................. 29

    Advantages................................................................................................................................. 29

    Heating and refrigeration equipment........................................................................................ 30

    Heat pumps................................................................................................................................. 32

    Field of application..................................................................................................................... 33

  • 7/22/2019 air conditionning systems.pdf

    72/253

    21 July 2006

    Air conditioning systems Page 3/33 All-water systems

    Air conditioning systemsVersion 1.0

    Basic concept

    Definition of an

    all-water system

    An all-water system offers the following features:

    The space is equipped with a terminal unitsupplied with hot and/or coldwater by pipes (water loop).

    The pipes transfer energy between the central plant(refrigeration andheating equipment) and the terminals.

    All the energy needed to cool a space is carried by water.

    Note: With this type of system, fresh air may be conditioned inside the terminal

    unit or introduced directly in the space without being conditioned (see fan coil

    unit, air change).

  • 7/22/2019 air conditionning systems.pdf

    73/253

    21 July 2006

    Air conditioning systems Page 4/33 All-water systems

    Air conditioning systemsVersion 1.0

    Basic concept (continued)

    Possible solutions The solutions generally depend on the type of space, as well as investment

    possibilities and the requirements for each space.The most common solutions include:

    A fan coil unit that can also be used in a number of versions (two-pipe,four-pipe, two-pipe/two-wire).

    Cassette or mini non self-contained air-handling terminal units.

    Individual water-loop heat pumps.

    Each of these solutions will be discussed in detail in this chapter.

  • 7/22/2019 air conditionning systems.pdf

    74/253

    21 July 2006

    Air conditioning systems Page 5/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units

    Basic concept A fan coil unit is a terminal unit with:

    a heat exchange coil,

    a fan motor,

    a filter,

    a condensate drain pan.

    Fan coil units can be in cased or uncased configurations, vertical or horizontal,

    and withor withoutfresh air inlet.

    Ceiling-mounted

    horizontaluncased fan

    coil unit

    Fresh air inlet with mixing dampers fitted in a suspended ceiling.

  • 7/22/2019 air conditionning systems.pdf

    75/253

    21 July 2006

    Air conditioning systems Page 6/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Basic concept

    (continued)

    Vertical casedfan coil unit

    with fresh airinlet

    Fresh air inlet with mixing dampers attached to a partition wall.

    Horizontalcased fan coil

    unit

    An horizontal cased fan coil unit is also called a ceiling unit.

  • 7/22/2019 air conditionning systems.pdf

    76/253

    21 July 2006

    Air conditioning systems Page 7/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Two-pipe fan coil

    unit

    Operation The unit has just one coil supplied by two pipes (supply and return).

    The coil operates as follows:

    The circuit is supplied with warm water for winter heating,

    And with chilled water for summer cooling.

    The term changeoverrefers to the changing from heating to cooling and vice

    versa.

    The output power is adjusted by: Turning the fan on and off on ultra-simple systems (for economical reasons).

    Opening or closing an electric on/off valve on the water circuit.

    Modulating valve that varies progressively the rate of water supplied to thecoil.

  • 7/22/2019 air conditionning systems.pdf

    77/253

    21 July 2006

    Air conditioning systems Page 8/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Two-pipe fan coil

    unit (continued)

    Operation(continued)

    Two-pipe fan coil units

    coil :air/water

    exchanger

    fan

    filter

    central plant :hot water / cold water

    Principle

    Energyproduction

    Heating and cooling energy is produced in a central plant consisting of:

    water heating equipment (e.g. furnace or exchanger),

    water chilling equipment (water chiller).

    An air-to-water or water-to-water heat pump can also be used to produce hot

    or chilled water depending on the season.

    Field ofapplication

    This system is used for divided spaces, such as offices and hotels, where needs

    fluctuate but are of the same type.

    It does not satisfy simultaneous heating and cooling needs; heating is provided

    in the winter, and cooling in the summer.

  • 7/22/2019 air conditionning systems.pdf

    78/253

    21 July 2006

    Air conditioning systems Page 9/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Four-pipe fan coil

    unit

    Operation The unit consists of two coils, one connected to a hot water loop, the other to acold water loop.

    Both water loops are necessary. The flow of water is usually regulated by valves

    (on/off or modulating) on each water circuit.

    Energyproduction

    Energy may be provided by a:

    Water boiler and a water chiller.

    Heat pump providing hot and cold water simultaneously. Transfer unit that recovers heat from the condenser during cooling.

  • 7/22/2019 air conditionning systems.pdf

    79/253

    21 July 2006

    Air conditioning systems Page 10/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Four-pipe fan coil

    unit (continued)

    Field ofapplication

    This system is used for offices, hotels and other spaces with significant heating

    and cooling needs that fluctuate and are not of the same type.

    It delivers heating and cooling at the same time.

    or

    Four-pipe fan coil units

    heatingcoil

    filter

    coolingcoil

    fan

    Principle

  • 7/22/2019 air conditionning systems.pdf

    80/253

    21 July 2006

    Air conditioning systems Page 11/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Fan coil units

    Two-pipe, two-wirefan coil unit

    Operation The unit has two coils: a two-pipe water coil and a two-wire electric heater.

    Under conventional operation, the water coil is connected to the chilled water

    circuit to provide cooling. There is no hot water circuit; the electric heater

    serves as a heating battery.

  • 7/22/2019 air conditionning systems.pdf

    81/253

    21 July 2006

    Air conditioning systems Page 12/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Fan coil units

    Two-pipe,two-wire fan coilunit (continued)

    Energyproduction

    A water chiller is located in the mechanical room.

    A reversible water chiller could be installed in order to have chilled water in the

    summer and hot water in the winter. In this case the unit serves as a

    low-temperature hot water coil and back-up electric heater in the winter, when

    no cooling is needed.

    or

    Two-pipe, two-wire fan coil units

    electricheater

    filter

    cooling orheating

    coil

    fan

    Principle

    Field ofapplication

    This system is advantageous for heavily insulated modern buildings, such as

    offices and hotels, where heating needs are reduced.

  • 7/22/2019 air conditionning systems.pdf

    82/253

    21 July 2006

    Air conditioning systems Page 13/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Air-change fan coil

    unit

    Concept Although there are fan coil units with fresh air inlets, in most cases the air inspaces is changed by independent, central equipment:

    single-flow ventilation,

    dual-flow ventilation.

    Single-flowventilation

    Single-flow ventilation generally consists of using a roof ventilator (T) to expel a

    portion of the air from a building with passageways and spaces containing

    specific pollutants. Fresh air is introduced via inlets along the exterior walls.

    Although inexpensive, this type of ventilation has the drawback of being unable

    to adequately control air change in each separate room. Nothing guarantees that

    fresh air will actually enter through the inlets and in the expected proportions. As

    a result, some spaces could be under-ventilated while draughts could be created

    in others.

    Furthermore, the inlets along the outer walls also allow outside noise to enter

    indoor spaces. This technique is therefore to be avoided in noisy environments.

    It should also be avoidedin polluted environments.

  • 7/22/2019 air conditionning systems.pdf

    83/253

    21 July 2006

    Air conditioning systems Page 14/33 All-water systems

    Air conditioning systemsVersion 1.0

    Fan coil units (continued)

    Air-change fan

    coil unit(continued)

    Dual-flowventilation

    Dual-flow ventilation makes it possible to avoid these risks:

    The desired amount of fresh air is filtered (and warmed in the winter) by an airhandling unit before being introduced into each space. This conditioned fresh

    air is carried through ducts:

    Directly to served spaces.

    Or to the return air section of terminal units . This solution makes itpossible to limit the risks of occupants being bothered by air draughts. It

    also allows fresh air to be warmed at lower temperatures (energy savings in

    spring and autumn). On the other hand, the fans in the terminal units mustbe left on occupancy periods.

    Stale indoor air is expelled outside by an exhaust fan.

    Fresh air conditioning and air extraction may be accomplished inside a single

    dual-flow air handling unit. A heat recovery unit, or HRU, can also be installed

    to recover heat from exhaust air.

    Comment: A chilled water coil can be added to cool incoming fresh air slightly

    in the summer. The aim here is not to chill the indoor air, but rather to avoid

    supplying fresh air at too high of a temperature in the summer (this is not a true

    chilled dual-ventilation system, which is much more elaborate).

  • 7/22/2019 air conditionning systems.pdf

    84/253

    21 July 2006

    Air conditioning systems Page 15/33 All-water systems

    Air conditioning systemsVersion 1.0

    Non self-contained air-handling terminal units

    Basic concept These units have the same components as conventional fan coil units (heat

    exchange coil, fan motor, filter, condensate drain pan), but are designedspecifically for installation in ceilings, suspended ceilings and raised floors.

    Equipment type There are two types of such terminal units: fan coil units and mini air handlingunits.

    Fan coil unitsare designed for installation in suspended ceilings. They bothsupply air to and recirculate the air in spaces directly. They have no available

    pressure and cannot be connected to ductwork.

    Mini air handling unitscan be installed in false ceilings or raised floors(uncased models) or directly in spaces (cased ceiling or vertical models).

    They can be connected to a mini-duct system (available static pressure).

    Fan coil units There are two models of cassette type fan coil unit:

    Melody fan coil units, designed specifically for installation in the centre of aspace, far from walls.

    Coadis fan coil units, designed for easy installation near walls.

  • 7/22/2019 air conditionning systems.pdf

    85/253

    21 July 2006

    Air conditioning systems Page 16/33 All-water systems

    Air conditioning systemsVersion 1.0

    Non self-contained air-handling terminal units (continued)

    Fan coil units

    (continued)

    Melody type fancoil units

    The composite drawing below shows the components of a cassette type fan coil

    unit:

    6 5 111

    7 3 2 14

    A Melody cassette type fan coil unit discharges air la