Air Balancing - Ag

  • Upload
    hai-le

  • View
    224

  • Download
    0

Embed Size (px)

Citation preview

  • 8/11/2019 Air Balancing - Ag

    1/8

    AG-AB-00Issue1, March 2004

    Air Balancing Application Guide

    TitusAir Distribution Technologies

    Plano, Texas 75074972. 212. 4800

    www.titus-hvac.com

    605 ShilohRoad

  • 8/11/2019 Air Balancing - Ag

    2/8

    Titus, the Titus Spiral, and The Leader in Air Management are trademarks of Titus.

    All other trademarks, noted or not, are the property of their respective owners.

  • 8/11/2019 Air Balancing - Ag

    3/8

    AirBalancing Application Guide AG-AB-00Issue 1,March2004

    Page 1

    C ontents Page

    General .............................................................. 1

    Foreword ........................................................... 1

    Introduction ...................................................... 1

    Methodology ..................................................... 1

    Flow and Pressure Requirements .................. 1Example Air Volume ................................ 1

    Example Air Pressure ............................. 2Example Fan Total Pressure ................. . .2

    Example Fan Volume .............................. 2

    De itions ......................................................... 2

    Anemometer ................................................... 2Area Factor .................................................. . . .2Velocity........................................................... 2Velometer ....................................................... 2

    Instrumentation ................................................ 3

    Preliminary Balancing Steps .......................... . 3

    Proportional Balancing Steps ......................... 3

    Grille Free Area ................................................ 4

    Cross Reference ............................................... 5

    S ystem Balancing Worksheet ......................... 6

    GeneralThis document provides general inform ationnecessary to balance Titu s HVACequipment.Use thisdo cument along with the specproduct factors to balance air distributionequipment.

    Additional information may be found at the Tituswebsite, its address is www.titus-hvac.com.

    ForewordThe intention of an air conditioning engineer is todesign an air distribution system to deliver therequired air volume to satisfy the space load.The duct system components are sized todeliver ai r without excessive balancing. Underideal conditions, the pressure loss from the fanto the supply outlets should be ent toovercome the pressure loss through the supply

    outlet and distribute the air to the space. Thisideal system woul d require no further aiadjustments. However,in reality this condition isusually not met. Therefore, the system andcomponent balancing is required to achi eve theengineers design criteria.

    IntroductionWhen fans operate at a constant speed theyhave such characteristics that for a given air

    rate a certain pressure will be developed at thefan discharge. If the pressure requirementchanges, the quantity of air delivered will alsochange. It is important to note that eachdownstream damper adjustment the fanpressure and An in dividual outlet cannotbe adjusted without ng the rest of the

    system.Therefore the system must be balancedin accordance with some systematic procedure.The objective of the manual is to provide a basicunderstanding of air conditioning systembalancing. The balancing method presentedwithin this manual uses a velometer positionedby hand at each grille. The method is generallyreferred to as the Chicago ProportionalBalancing method.

    MethodologyFigure 1 shows a typical example of a fan and

    duct system pressure characteristic. The ductsystemhas f our supply outlets with a damper ineach outlet s branch line. Therei s also a damperin the main duct between t he fan and the branch takeoff. Eachpart of the system hasthecharacteristic that the pressurerequired toovercome the resistance of that section of thesystem varies as the square of the volume of air

    through it. CurveA shows the pressurecharacterist ic of the last section of the duct fromstation 0 to 1, curve B represents the systemincluding the last two supply outlets and so on.The following numerical examples illustrate therelationship between the volume of air owingthrough a section of the system andthe requiredpressure to overcome the resistance of thatsection.

    Flow and Pressure

    RequirementsThe following are examples of and pressurerequirements occurring in an air dist ributionsystem.

    Example Air Volume

    At the a on the A curve; the req uired pressureis 1 for 8 unit s of air volum e per unit time.When the is in creased from 8 units at a ato 16 units at b then,

    16 units8 units

    = 2 and (2)2= 4

    Therefore,the required pressureat point b is

    1 pressure un it x 4 = 4 pressureunits

    http://www.titus-hvac.com/http://www.titus-hvac.com/
  • 8/11/2019 Air Balancing - Ag

    4/8

    AG- AB-00Issue1,March 2004

    Air Balancing ApplicationGuide

    Page 2

    Example Fan VolumeAnother useful basic fan law is as follows:

    (Fan RPMFan Vol. Flow 2)2= Fan Vol. Flo w1 x

    (Fan RPM1)

    Such that a10 percent increase in fan volume

    requires a 10 percent increase in fan speed.

    AnemometerInstrument used for determining the force orspeed of air. Two anemometertypes are asfollows:

    Vane. Used to measure sidewalls,grill es,registers,and ceiling sers.The vaneanemometers are commonly depicted withbalancing Titus air system equipment.

    Rotating vane. Used to measurelinear feetof air passing through it. Generally used formeasuring air velocity through supply, returnand exhaust air grilles, registers,oropenings. Do not use a rotating vaneanemometer as an averaging instrument.

    Figure1. Fan and System Characteristics

    AreaFactorExample Air Pressure

    The area factor, A K, is the area of theoutlet at the point of outlet velocity, the VKmeasurement is su ch that the volume w isequal to A Ktimes VK.

    At the C on the B curve, the required pressureis 2 for 8 units of Whenthe is

    increased from 8 units at c to 12 units at dthen,

    The area factors are based on equali zedin the outlet neck.12 unit s

    8 units= 1.5 and (1.5)

    2= 2.25

    Note: Severe damper throttling or takewithout air turning devices or control gridscan ct the indicated airflow accuracy ofthese factors dramatically.

    Therefore,the requi red pressure at point d is

    2 pressure units x 2.25 = 4.5 pressure units

    Example Fan Total Pressure VelocityThe followi ng general equation may be used to

    perform fan pressure calculations.

    The measurement of air speed as it exits the

    grille, register,or r. Velocity is averagedby number of readings taken at grille, register, or

    ser. Velocity is measured with instrumentsand depending on application, the velocity beingmeasured can be either supply or return air.

    Vol. Flow 2Fan TotalPressur e2

    =Fan TotalPressur e1

    x ( Vol. Flow 1 )

    Therefore,based upon this basic fan law, a 20percent in crease in fan volume requires Velometer

    Instrument used for HVAC balancing, staticpressure mea surements, e nergy au dits.

    (1 + 0.2)2= 1.44or 44% higher fan total pressure

  • 8/11/2019 Air Balancing - Ag

    5/8

    Air Balancing Application Guide AG- AB-00Issue 1,March2004

    Page 3

    InstrumentationWe recommend all system balancinginstruments calibrated annually with themanufacturers furnished calibration curve. Also,it is strongly recommended these instruments beused within their sp d accuracy range. The

    appropriate usage and accurate instrumentcalibration ensures ongoing credibility andaccuracy for the air balancing technician.

    For return grille balancing, the position of thevelometer probe must be as shown in thediagrams for each r shown. Based on thevane anemometer use, the attachment of thetubing to the anemometer requires a reversingmovement on the instrument. Alternativemethods may use a hood in a similarmanner. Consult organizations such as NEBBand AADCfor more information on those

    methods that use the w hood to measurevolume direc tly.

    Figure 2. Schematic Diagram of the DuctSystem

    Preliminary Balancing Steps Proportional BalancingSteps

    Use the follo wing information to balan cingpreparation.

    The following balancing information is c tolow pressure ventilating and air conditioningsystems.

    1. Open all system air valvesand dampers inboth supply and return ducts.

    2. Set all other dampers to normal operatingposition.

    3. Check all and coils to ensure theyare clear of dirt and debris.

    4. Start all fans.

    5. Check rotation of all fans a nd ensure thedirection is correct.

    6. Copy the balancing worksheet provid ed inthis manual to record readings .

    7. Number the o utlets on the worksheet.

    Note: The furthest branch and thefurthest outlet on the branch away fromthe fan will be outlet one on the branchnumber one. The outlets are numbered

    consecutively working back toward thefan. Figure 2 shows the numberingarrangement.

    It is very important the outlets benumbered, tested, and adjusted in thedescribed sequence. If the sequence is notfollowed, the procedure wil l not be valid.

    8. Spot-check outlets along the branch todetermine if enough air is being deliveredto give measurable readings.

    1. Measure velocities at Outlet 1, the furthestoutlet on the bran ch.

    2 Determine the average velocity and usethe System Balancing Worksheet to recordthe value in the column VM(measuredvelocity) under Adju stments I heading. Thisindicates the reading of that outlet.

    3. Determine the ratio of V D(measure todesign velocity) and record R (ratio ) under

    Adjustment I and 1B.Use the followingequation to determine ratios.

    Measured Velocity VMR =AK w factor)

    =

    VD

    4. Proceed to the second outlet. Determinethe average velocity (V M) and ratio (R) andrecord these values under Adjustment Iand 2A.

    5. Compare R values from 1B and 2A underAdjustment I. If the R values are not equal,adjust Outlet 2 so R2 will approach R1.

    Do not adjust Outlet 1.

    6. After adjustment, record V Mand R valu esfor Outlet 2 u nder II and 2 A.

  • 8/11/2019 Air Balancing - Ag

    6/8

    AG- AB- 00Issue 1,March 2004

    Air Balancing ApplicationGuide

    Page 4

    7. Go back to Outlet 1 and measureVM.Record VMand R values under AdjustmentII, 1B. If R values shown under adjustmentII, 1B and 2A vary more than 0.1,they arenot proportionally balanced one to anotherand further adjustment to Outlet 2 isrequired. After each adju stment of outletnumber, record the new VMand R valuesunder 1B and 2A in each successiveadjustment column. Once the prescribedlimits are achieved, proceed to the nextstep.

    8. After Outlets 1 and 2 are satisfactorilybalanced one to another, theadjustment values of R and VMfrom row2A should be rewritten under column

    Adjustment I, row 2B.

    9. Proceed to Outlet 3 and measure VMandrecord VMand R values under Adjustment

    I, 3A.10. Compare 3A and 2B readings under

    Adjustment I. If necessary adjust Outlet 3to achieve the same R values as shown fornumber 2.

    Note : Do not adjust Outlets 2 or 1.

    Any adjustments to Outlet 3 will change thethrough Outlets 2 an d 1; however, as

    long as Outlet 2 or 1 are adjusted they willremain proportionally balanced to eachother. The R value determined for Outlets 2and 3 will also apply to Outlet 1 and theywill be proportionally balanced to eachother.

    11. Adjust Out let 4 so its R value matchesOutlet 3s R value. Proceed in samemanner to each outlet in the branch untilout outlets are balanced proportionally toeach other.

    It is essential that once an outlet isproportionally balanced with the precedingoutlet, no further adjustments be made tothat or a preceding outlet.

    12. Balance each branch in a similar manner.

    13. Measure ow at a selected outlet in eachof the two branches farthest from the fan.

    Adjust branch dampers until the R valuesfor the selected outlets are equal. The twobranch ducts are not proportionallybalanced.

    14. Adjust each branch to balance itproportionally with the preceding branch inthe same manner that the outlets werebalanced.

    15. Check total at the fan and adjust fanspeed to obtain the correct totalthrough the system.

    Grille Free AreaGrille free area (AF/AC) is the area free ofobstruction in a grille face . The more free space,the more unobstructed ai ow. The followingtable provides the average percentage of freegrille area, de degree , and grille modelnumber

    Table 1. Grille Free Area (A F/AC)

    Modeln

    (Degrees)Free A rea (%)

    3F 45 52%

    4F 45 62%

    13R 0 86%

    15R 0 83%

    23R 45 44%

    25R 30 62%

    30R 0 75%

    33R 38 61%

    50F N/A 90%

    60 F L 0 42%

    63 F L 30 38%

    111R & 112 0 88%

    0 82%

    45 63%271 & 27 2

    22.5 76%300 see 27 1 & 272

    350 35 58%

    355 35 46%

    355 Z RL 0 80%

    1700 N/A 68%

    CT -480 N/A 47%

    CT -481 N/A 42%

    CT -540 N/A 56%

    CT -541 N/A 51%

    CT -580 N/A 69%

    CT -581 N/A 65%

    CT -700 N/A 56%

    T-700 N/A 56%

  • 8/11/2019 Air Balancing - Ag

    7/8

    Air Balancing Application Guide AG- AB-00Issue 1,March2004

    Page 5

    Cross ReferenceTable 2 provides a listing of products and their respective factor document.

    Table 2. Product Cross Reference of Flow Factors

    Product See Flow Factor Product See Flow Factor

    30 272-FF CT-580 CT-FF

    111 272-FF CT-581 CT-FF

    112 272-FF CT-700 T700-FF

    121 272-FF CT-700 Core 272-FF

    122 272-FF DL DL-FF

    131 272-FF FlowBar FB-FF

    132 272-FF FR-1, -2, -3, -4 FR-FF

    271 272-FF LL-1 LL1-FF

    272 272-FF LL-2 LL2-FF

    1700 1700-FF ML-37 ML-FF

    23 - Core 272-FF ML-38 ML-FF

    25 - Core 272-FF ML-39 ML-FF

    250 1-way 250-FF N-1 N1-FF

    250 2-way 250-FF N-1-DR N1DR-FF

    250 3-way 250-FF OMNI OMNI-FF

    250 4-way 250-FF PAR PAR-FF

    3 - Core 272-FF PAS PAS-FF

    30 - Core 272-FF PDR PAR-FF

    300FL 272-FF PDS PAS-FF

    300FS 272-FF PFR PFS-FF

    300HD 300HD-FF PFS PFS-FF

    300RL 272-FF PSS PSS-FF

    300RS 272-FF R-OMNI R-OMNI- FF

    301FL 272-FF SG-SD SGSD-FF

    301FS 272-FF T700 T700-F

    301RL 272-FF T700 - Core 272-FF

    301RS 272-FF TBD-10 TBD-10-F

    33 - Core 272-FF TBD-30 TBD-30-FF

    34 - Core 272-FF TBD-80 TBD-80-FF

    350FL Core 272-FF TBDI-10 TBD-10-F

    350FS Core 272-FF TBDI-30 TBD-30-FF

    350RL Core 272-FF TBDI-80 TBD-80-FF

    350RS Core 272-FF TDC TDC-FF

    355 272-FF TBF TBF-FF

    4 - Core 272-FF TLF TLF-FF

    50 - Core 272-FF TMR TMR-FF

    50F 50-FF TMRA TMRA-FF

    8 - Core 272-FF TMR-AA TMR-FF

    CT-480 CT-FF TMRA-AA TMRA-FF

    CT-481 CT-FF TMS TMS-FF

    CT-540 CT-FF TMSA TMSA-FF

    CT-541 CT-FF XC-310 XC310-FF

  • 8/11/2019 Air Balancing - Ag

    8/8

    AG-AB- 00Issue 1,March 2004

    Air Balancing ApplicationGuide

    Page 6

    System Balancing Worksheet

    Outlet Product Information Adjustments

    Outlet Design I II III IVOutlet

    No. Type Size

    K-factor

    CFM VD VM R VM R VM R VM R

    1 1B

    2A2

    2B

    3A3

    3B

    4A4

    4B

    5A5

    5B

    6A6

    6B

    7A7

    7B

    8A8

    8B

    9A9

    9B

    10A10

    10B

    11A11

    11B

    12A12

    12B

    13A13

    13B

    14A14

    14B

    15A15

    15B

    VM Measured velocit yVD Velocity at design conditionR = V M/VDMeasured to design velocity ratio