    AIR-COOLED AND WATER-COOLED SCROLL CHILLERS

    Voltas is the pioneer and a leading provider of integrated end-to-end solutions in the field of electro-mechanical and

    refrigeration. We are committed to provide customers with technology that suits their needs. We have introduced a wide

    variety of air-cooled and water-cooled scroll chillers with R22 and R407C refrigerant options.

    With ISO:9001 cer tified factories, Voltas possesses total capability in the manufacture of scroll chill er s.

    These chillers are available in a wide range of capacities from 12 TR to 111 TR. They are easy to in st al l

    and commission, and can handle various cooling requirements, aided by multiple compressor con figurations.

    Voltas scroll chillers are an ideal choice for various air-conditioning applications, including office spaces, banks,

    hotels, hospitals, shopping malls, multiplexes, commercial complexes and process cooling.

    MODEL NOMENCLATURE:

    AC WC D S D M N 2044

    AIR-COOLED

    WATER-COOLED

    DX CHILLER

    SCROLL

    COMPRESSOR

    NOM. CAPACITY

    048 = 48 TR

    NO. OF COMPRESSORS PER CIRCUIT(FOR TANDEM MODEL)

    NO. OF REF. CIRCUITS(FOR TANDEM MODEL)

    N - STANDARD PANELA - ADVANCED BMS

    MICROPROCESSOR-BASEDCONTROL PANEL

    C - COPELAND COMPRESSOR

    D - DANFOSS COMPRESSOR - R22

    DP - DANFOSS COMPRESSOR - R407C

    X 2

    KEY FEATURES INCLUDE:

    1) Scroll Compressor with R22 and R407C Refrigerant Options

    2) Energy Efficiency

    3) Modular Design

    4) Application Flexibility

    5) Low Noise and Compact Design

    6) Easy-to-use Microprocessor Panel and Controls

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    3/10

    ACDS

    077DPMN2X2

    ACDS

    096DPMN2X2

    77 96

    4 4

    100/75/50/25 100/75/50/25

    DX DX

    1 1

    205 256

    5" nps 5" nps

    2 3

    4 6

    2625 3710

    2236 2236

    2590 2615

    2562 2872

    ACDS

    011DPMN1X1

    UNIT MODEL

    *Nominal Capacity - TR

    ACDS

    022DPMN2X1

    ACDS

    034DPMN3X1

    ACDS

    045DPMN2X2

    CACDS

    066DPMN3X2

    11 22 34 45 66

    Compressor Qty.

    Unit Capacity ReductionSteps in %

    1 2 3 4 6

    100/50 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/33.3/

    16.7

    Evaporator Type

    Evaporator Qty.

    Evap. Water Flow RateGPM (US)

    Evap. Water NozzleSize**

    DX DX DX DX DX

    1 1 1 1 1

    29 59 90 120 176

    2-1/2" nps 3" nps 3" nps 4" nps 5" nps

    Condenser Module Qty. 1 1 1 2 2

    2 2 2 4 4

    LENGTH (MM)

    WIDTH (MM)

    HEIGHT (MM)

    Shipping Wt. Kg.

    2500 2535 2535 2850 2625

    650 1270 1270 2235 2236

    1400 2310 2410 2590 2690

    631 1033 1349 1961 2633

    Note 1:* Capacity rated for evap. inlet water temp. 12 C leaving water temp. 7 C and at design ambient of 35 C Evap.

    water side fouling factor of 0.000018 m2 C/W. Power and control supply voltage ranges are 360 -440 V and 210-240 V

    respectively, and frequency 50Hz.

    Note 2:** Siz ing of water piping to be done at site, based on operating tonnage and available pump head.

    Note 3:For higher ambient applications, please contact us.

    AIR-COOLED SCROLL CHILLERS R407C

    TECHNICAL DATA

    COMPRESSOR

    EVAPORATOR

    CONDENSER

    No. of Fans

    CHILLER PACKAGE PHYSICAL DATA

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    4/10

    OBEROI HOTEL, DELHIIISC, BANGALOREBHUSHAN STEEL LTD., KOLKATA

    MICROPROCESSOR-BASED LCD CONTROLLER:

    Three Modes of Operation:

    Auto Mode: Auto start-and-stop, programmable for the entire year. Hence there is no need for any operator interface.

    Auto Mode facilitates auto restart on power restoration after load shedding or grid supply failure.

    Semi-auto Mode: Manual, single button start-and-stop, since further sequence is pr og rammed .

    Manual (Test) Mode: Facilitates testing under supervision.

    Equalization of Compressor Runtime

    The Microprocessor Controller ensures equal running of compressors in multiple compressor units.

    This ensures longer life of compressors.

    All chillers are equipped with microprocessor controls that provide the following benefits:

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    5/10

    Controls and Interlocks

    The chilled water pump is interlocked with compressors.

    The safety controls are preset at factory while operating controls are field adjustable, depending on actual operating

    requirements.

    Optional Features

    Communication port RS485 for remote connectivity, status and fault indication.

    Advanced BMS with ASCII or RTU MODBUS protocol can be linked to Integrated Building

    Management System (IBMS).

    Limited hardware BMS for remote control operation.

    Dual-mode chillers for thermal storage system.

    Safety and Protection

    Microcomputer Motor Protection Device (uMPD) and Microcomputer Voltage Protection Device (uVPD) protect chillers from phase

    unbalance, phase loss, treversal, overload,under / over voltage and supply failure.

    Programmed safety features available using sensitive and accurate temperature which protects the

    system from:

    Freezing Low Pressure Anti-recycle Low Chilled Water Temperature High Pressure

    Inlet and Outlet Temperature for Chiller Sensor Error Low Water Flow in Condenser, Chiller

    User-friendly Operation

    Interface with keypad and 32 character LCD display.

    Gives visual annunciation for safety trips.

    Self-diagnosis Function

    Digital display of all vital parameters such as:

    Outlet temperature for Chillers Current Voltage Compressor run hours

    Diagnose mode for easy trouble shooting shows alarm history for the last 5 trips with date, time and cause of failure.

    EMAMI, KOLKATAHONDA R&D, DELHITATA POWER, MUMBAI

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    6/10

    R22

    R407C

    R407C

    R410A

    R410A

    R22

    EIGHT POWERFUL FEATURES:

    Voltas chil lers are available in a wide range of models, with R407C and R22 re fr ig er an ts .

    Higher Energy Efficiency - Tandem Compressor ModelsScroll chillers from 48 TR to 111 TR use compres sors operating in tandem. This improves the oper at in g

    efficiency during part load period s, since the ent ire condenser area is utilized for hea t r ejec tion , e ven

    though only one compressor may be in operation.

    Capacity ModulationMultiple compressors are used in most of the models, with independent refrigerant circuits . The micropro cess or

    contro l le r ensures that only the required number of compressors operate during part load conditions, thereby

    saving power.

    Operating ReliabilityThe compressor is a no-contact scroll design with the motor, cooled by the suction gas. Higher capaci ty sc ro ll

    ch il le rs use tandem compressors with suction gas distribution restrictor, which allows balanced op er ati on of

    compressor. The chillers are charged and tested in the factory prior to dispatch, thus enhancing operating

    reliability.

    Energy EfficiencyA range of sophisticated components such as highly energy-efficient, imported compressor, superior design of

    wa te r- co ol ed condenser and chiller, internally grooved, cross-hatched copper tube coil with matched circuitry,

    and a microprocessor controller, results in low power consumption.

    Quiet Operation

    The chillers use ultra-quiet, high efficiency scroll compressors. The condenser fans are designed for low noise levels.

    Easy to Install

    The chillers are pre-wired, fully charged and run-tested at the factory, saving installation and start-up time.

    Voltas Countrywide After-Sales Service

    A nationwide service network backs every unit. After the initial warranty period, Voltas offers annual se rv ic eschemes. More than 90% of the customers have opted for these schemes. You cannot get better insurance.

    SCROLL CHILLERS

    AIR-COOLED CHILLERS

    WATER-COOLED CHILLERS

    13 TR 26 TR 39 TR 52 TR 78 TR 111 TR

    13 TR 26 TR 39 TR 52 TR 77 TR

    Will be available shortly

    11 TR 22 TR 34 TR 45 TR 66 TR 77 TR 96 TR

    12 TR 24 TR 36 TR 48 TR 72 TR 83 TR 100 TR

    Will be available shortly

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    7/10

    AIR-COOLED SCROLL CHILLERS R22

    ACDS012DMN

    UNIT MODEL

    *Nominal Capacity - TR 12 24 36 48 72 83 100

    COMPRESSOR

    EVAPORATOR

    CONDENSER

    Compressor Qty.

    Unit Capacity ReductionSteps in %

    1 2 3 4 6 4 4

    100/50 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/33.3/

    16.7100/75/50/25 100/75/50/25

    Evaporator Type

    Evaporator Qty.

    Evap. Water Flow RateGPM (US)

    Evap. Water NozzleSize**

    DX DX DX DX DX DX DX

    1 1 1 1 1 1 1

    32 64 96 128 192 221 266

    2-1/2" nps 3" nps 3" nps 4" nps 5" nps 5" nps 6" nps

    Condenser Module Qty.

    No. of Fans

    1 1 1 2 2 2 3

    2 2 2 4 4 4 6

    UNIT DIMENSION & WEIGHTS

    LENGTH (MM)

    WIDTH (MM)

    HEIGHT (MM)

    Shipping Wt. Kg.

    2500 2535 2535 2850 2625 2625 3900

    650 1270 1270 2235 2236 2236 2236

    1400 2310 2310 2690 2690 2690 2590

    631 1034 1300 1961 2634 2515 2868

    ACDS024DMN

    ACDS036DMN

    ACDS048DMN2X2

    CACDS072DMN3X2

    ACDS083DMN2X2

    ACDS100DMN2X2

    Note 1:* Capacity rated for evap. inlet water temp. 12 C leaving water temp. 7 C and at design ambient of 35 C Evap.

    water side fouling factor of 0.000018 m2 C/W. Power and control supply voltage ranges a re 360-440 V and 210-240 V

    respectively, and frequency 50Hz.

    Note 2:** S izing o f water piping to be done at site, based on operating tonnage and available pump head.

    Note 3:For higher ambient applications, please contact us.

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    8/10

    UNIT MODEL

    *Nominal Capacity - TR

    WATER-COOLED SCROLL CHILLERS R22

    COMPRESSOR

    Compressor Qty.

    Unit Capacity ReductionSteps in %

    Evaporator Type

    Evaporator Qty / Unit

    Evap. Water Flow RateGPM (US)

    Evap. Water NozzleSize**

    Condenser Qty / Unit

    Condenser Water FlowRate GPM (US)

    UNIT DIMENSION & WEIGHTS

    WCDS013DMN

    WCDS026DMN

    WCDS039DMN

    WCDS052DMN2X2

    WCDS078DMN3X2

    WCDS111DMN2X2

    13 26 39 52 78 111

    Cond. Water Nozzle

    Size**

    LENGTH (MM)

    WIDTH (MM)

    HEIGHT (MM)

    Shipping Wt. Kg.

    1 1/4" nps 1 1/4" nps 1 1/4" nps 2-1/2" nps

    2000 2000 2500 2500 2500 3000

    1300 1400

    2100 19001700

    950950

    15351450

    850850

    1050

    540 824 2345 267015451150

    1 2 3 4

    100 100/50 100/66.7/33.3 100/75/50/25

    DX DX DX

    1 1 1

    35 69 104

    2-1/2" nps 3" nps 3" nps

    1 2 3 2

    43 85 128 171

    EVAPORATOR

    DX DX

    1 1

    207 295

    5" nps 6" nps

    100/83.3/66.7/50/

    33.3/16.7

    100/83.3/66.7/50/

    33.3/16.8

    CONDENSER

    DX

    6 4

    1

    138

    4" nps

    2-1/2" nps 6" nps

    3 1

    256 365

    Note 1:* Capacity rated for evap. inlet water temp. 12 C, leaving water temp. 7 C,Evap. water side fouling factor

    of 0.000018 m2 C/W and condenser water side fouling factor of 0.000044 m2 C/W. Power and control supply vol tag e ra ng es ar e

    360-440 V and 210-240 V respectively and frequency 50Hz.

    Note 2:** Sizing o f water piping to be done at site, based on operating tonnage and availab le pump head.

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    9/10

    Note 1:* Capacity rated for evap. inlet water t emp . 12 C, leaving water temp. 7 C,Evap. water side fouling factor

    of 0.000018 m2 C/W and condenser water side fouling factor of 0.000044 m2 C/W. Power and control supply volt ag e ra ng es ar e

    360-440 V and 210-240 V respectively, and frequency 50Hz.

    Note 2:** Siz ing of water piping to be done at site, based on operating tonnage and available pump head.

    *Nominal Capacity - TR

    Compressor Qty.

    Unit Capacity ReductionSteps in %

    Evaporator Type

    Evaporator Qty.

    Evap. Water Flow RateGPM (US)

    Evap. Water NozzleSize**

    Condenser Qty / Unit

    Condenser Water FlowRate GPM (US)

    ACWCDS013DPMN1X1

    ACWCDS039DPMN3X1

    ACWCDS052DPMN2X2

    ACWCDS077DPMN3X2

    13 26 39 52 77

    Cond. Water Nozzle

    Size**

    LENGTH (MM)

    WIDTH (MM)

    HEIGHT (MM)

    Shipping Wt. Kg.

    1 1/4" nps 1 1/4" nps 1 1/4" nps 2" nps 2" nps

    2350 2400 2500 2500 2500

    1350

    21501800

    10001100

    13001450

    850850

    1050

    552 846 240415881196

    1 2 3 4 6

    100 100/50 100/66.7/33.3 100/75/50/25100/83.3/66.7/50/

    33.3/16.7

    DX DX DX DX DX

    1 1 1 1 1

    35 69 104 138 205

    2-1/2" nps 3" nps 3" nps 4" nps 5" nps

    1 2 3 2 3

    43 86 128 171 253

    UNIT MODELACWCDS

    026DPMN2X1

    COMPRESSOR

    EVAPORATOR

    CONDENSER

    CHILLER PACKAGE PHYSICAL DATA

    WATER-COOLED SCROLL CHILLERS R407C

  • 7/25/2019 Air and Water Cooled Scroll Chillers

    10/10

    NORTH ZONE:DELHI(011) 66505550 / 66505657 / 66505680 / 66505683 / 66505684 CHANDIGARH(0172) 6610124 / 6610135

    JAIPUR(0141) 6451756 / 6541011 LUCKNOW(0522) 237869 / 6546629 EAST ZONE: KOLKATA(033) 66266280

    66266264 / 662 66 26 8 BHUBANESHWAR(0674) 6574044 JAMSHEDPUR(0657) 2427642 PATNA (0612) 2500786

    WEST ZONE:MUMBAI(022) 66656754 / 66656756 / 66656757 / 66656760 GOA 09860976942 NAGPUR(0712) 64 64 69 2

    PUNE(020) 66046607 / 6604 6447 AURANGABAD(020) 66046607 AHMEDABAD (079) 66301107 / 663 01 10 2

    INDORE (0731) 2498616 SOUTH ZONE: HYDERABAD (040)66743007 / 66743033 VIJAYAWADA (0866) 2431507

    VOLTAS LIMITED

    EM&R Business Group Sales Headquarters

    Voltas House 'B', 3rd Floor, T.B. Kadam Marg, Chinchpokli, Mumbai - 400 033

    Tel: +91 22 66656666 / 66656552 Fax: +91 22 66656930

    Email: [email protected] | www.voltas.com

    ENERGY EFFICIENT

    WATER-COOLED SCREW CHILLER

    AIR-COOLED RECIPROCATING

    CHILLER

    WATER-COOLED RECIPROCATING

    CHILLER

    PRODUCT RANGE

    VARIABLE REFRIGERANT FLOW (VRF)

    SYSTEM

    COGENERATION VAM

    IAQ & ENERGY REDUCTION

    SYSTEM

    COILOTRON (UV FOR AHU COILS)

    AIR-HANDLING UNIT

    ENERGY EFFICIENT

    AIR-COOLED SCREW CHILLER

    DOUBLE EFFECT VAM

    GERMITRON (DUCT MOUNTED UV)

    KITCHEN EA DEODOURISATION SYSTEMSTP EA ODOUR / H2S REMOVAL SYSTEM

    PACKAGED & DUCTABLE SPLIT UNIT