88
RS232C/RS485 Communication Module Technical Specifications RS232C/RS485 Communication Module ACGM0181END V1.0 11/1999 Matsushita Electric Works (Europe) AG is a global brand name of Matsushita Electric Works.

ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

  • Upload
    lecong

  • View
    221

  • Download
    3

Embed Size (px)

Citation preview

Page 1: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485

Communication ModuleTechnical Specifications

RS

232C/R

S485 C

om

mu

nicatio

n M

od

ule

AC

GM

0181EN

D V

1.0 11/1999M

atsushita Electric W

orks (Europe) A

G

is a global brand name of Matsushita Electric Works.

Page 2: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Matsushita Electric Works (Europe) AG a

Copyright

This manual and everything described in it are copyrighted. You may not copy thismanual, in whole or part, without written consent of Matsushita Electric Works(Europe) AG.Matsushita Electric Works (Europe) AG pursues a policy of continuous improvementof the design and performance of its products, therefore, we reserve the right tochange the manual/product without notice. In no event will Matsushita ElectricWorks (Europe) AG be liable for direct, special, incidental, or consequential damageresulting from any defect in the product or its documentation, even if advised of thepossibility of such damages.

Labelling

NameplateNAiS RS232C/RS485 communication modules are clearly identified by theindications on the nameplate.

ManufacturerMatsushita Electric Works (Europe) AG; Rudolf–Diesel–Ring 2, 83607 Holzkirchen,Germany

Intended Use

RS232C/RS485 Communication Module:

• Operate the communication module only under the conditions prescribedin these Technical Specifications.

• The communication module is an additional module and can beoptionally attached to the NAiS VF–C inverter series. TheRS232C/RS485 communication module links these NAiS inverters tosuperimposed hosts (PLC or PC) using LECOM A/B field busses.

• The communication module must be attached and electrically connectedso that it complies with its function and does not cause any hazardswhen attached and operated as instructed. Ensure by appropriatemeasures that neither personal injury nor damage to property may occurin the event of malfunction of the communication module.

• Observe all information given in the section “Safety information”.

• Please observe all information given in these Technical Specifications.This means:– Read these Technical Specifications carefully before you start to work

with the system.– These Technical Specifications must always be available during

operation of the communication module.

Any other use shall be deemed inappropriate!

Page 3: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

b

Matsushita Electric Works (Europe) AG

Liability

• The information, data, and notes in these Technical Specifications metthe state of the art at the time of printing. Claims referring toinverters/communication modules, which have already been supplied,cannot be derived from the information, illustrations, and descriptionsgiven in these Technical Specifications.

• The processing notes and circuit sections shown in these TechnicalSpecifications are proposals which cannot be transferred to otherapplications without being tested and checked. Matsushita ElectricWorks (Europe) AG does not take responsibility for the suitability of theprocess and circuit proposals.

• The indications given in these Technical Specifications describe thefeatures of the product without warranting them.

• Matsushita Electric Works (Europe) AG does not accept any liability fordamage and operating interference caused by:– disregarding the Technical Specifications– unauthorized modifications to the inverter– improper working on and with the communication module– operating errors

Warranty

• Warranty conditions: see Sales and Delivery Conditions of MatsushitaElectric Works (Europe) AG

• Warranty claims must be made to Matsushita Electric Works (Europe)AG immediately after detecting defects or faults.

• The warranty is void in all cases where liability cannot also beestablished.

Disposal

Material recycle disposeMetal � –

Plastic � –

Printed–board assemblies – �

Technical Specifications �

Page 4: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Matsushita Electric Works (Europe) AG c

Safety information

Persons responsible for the safety

Operator

• An operator is any natural or legal person who uses the drivesystem or on behalf of whom the drive system is used.

• The operator or his safety personnel is obliged

– to ensure the compliance with all relevant regulations, instructionsand legislation.

– to ensure that only skilled personnel works on and with the drivesystem.

– to ensure that the personnel has the Technical Specificationsavailable for all corresponding works.

– to ensure that all unqualified personnel are prohibited from working onand with the drive system.

Qualified personnelQualified personnel are persons who – because of their education, experience,instructions, and knowledge about corresponding standards and regulations, rulesfor the prevention of accidents, and operating conditions – are authorized by theperson responsible for the safety of the plant to perform the required actions andwho are able to recognize potential hazards.(Definition for qualified personnel according to VDE 105 or IEC 364)

Page 5: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

d

Matsushita Electric Works (Europe) AG

General Safety Information

• These safety notes do not claim to be complete. In case ofquestions and problems please contact your representative ofMatsushita Electric Works (Europe) AG.

• At the time of delivery the communication module meets the stateof the art and ensures basically safe operation.

• The indications given in these Technical Specifications refer to thestated hardware and software versions of the communicationmodules.

• The communication module is hazardous if:

– unqualified personnel works on and with the communication module.– the communication module is used inappropriately.

• The processing notes and circuit sections shown in these TechnicalSpecifications are proposals which cannot be transferred to otherapplications without being tested and checked.

• Ensure by appropriate measures that neither personal injury nordamage to property may occur in the event of failure of thecommunication module.

• The drive system must only be operated when no faults occur.

• Retrofittings, modifications, or redesigns are basically prohibited.Matsushita Electric Works (Europe) AG must be contacted in allcases.

• The communication module is electrical equipment intended for usein industrial high–power plants. The communication module mustbe tightly screwed to the corresponding inverter during operation.In addition, all measures described in the Operating Instructions ofthe inverter used must be taken. Example: Fasten covers to ensureprotection against contact.

Page 6: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Matsushita Electric Works (Europe) AG e

Important Symbols

The following symbols are used in this manual:

Whenever the warning triangle is used, especially importantsafety instructions are given. If they are not adhered to, theresults could be:

�personal injury and/or• significant damage to instruments or their contents,

e.g. data

�Note

Contains important additional information or indicates that youshould proceed with caution.

� Example:

Contains an illustrative example of the previous text section.

� next pageIndicates that the text will be continued on the next page.

!

Page 7: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

f

Matsushita Electric Works (Europe) AG

Page 8: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Matsushita Electric Works (Europe) AG Preface – 1

Preface

How to use these Operating Instructions

• These Technical Specifications are intended for safety–relevantoperations on and with the RS232C/RS485 communication moduleBFVC 9503. They contain safety information which must be observed.

• All personnel working on and with the RS232C/RS485 communicationmodule must have these Technical Specifications available and observethe information and notes relevant for them.

• The Technical Specifications must always be complete and perfectlyreadable.

These Technical Specifications contain most important technical data and describethe installation of the RS232C/RS485 communication module. Only valid with theoperating manual belonging to the inverter.

Terminology used

Cxxx/y subcode y of code Cxxx (e.g. C0410/3 = subcode 3 of code C0410)

L–Cxxx/y code location of VF–C

Xt/y Terminal block Xt/Terminal y (e. g. X3/28 = terminal 28 on terminal block X3)

(� xx – yy) cross reference (chapter – page number)

Items supplied

• 1 RS232C/RS485 communication module BFVC 9503 with housing(enclosure IP20)

• 1 M3 fixing screw

• 1 Two–pole male connector for voltage supply

• 1 Instruction sheet

ImportantAfter the delivery has been received, check immediately whether the items suppliedmatch the accompanying papers. Matsushita Electric Works (Europe) AG does notaccept any liability for deficiencies claimed subsequently.

Claim

• visible transport damage immediately to the forwarder

• visible deficiencies/incompleteness immediately to your representative ofMatsushita Electric Works (Europe) AG.

Page 9: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module

Preface – 2

Matsushita Electric Works (Europe) AG

Page 10: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

iMatsushita Electric Works (Europe) AG

Table of Contents

Preface

Chapter 1 Technical Data

1.1 Features 1 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 General Data and Application Conditions 1 – 4. . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Rated Data 1 – 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Dimensions 1 – 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Communication Times 1 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 2 Installation

2.1 Connections of the Communication Module 2 – 3. . . . . . . . . . . . . . . . . . . . . . . . . 2.1.1 Overview 2 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.1.2 Female Plug for 9–Pole SubD Plug (LECOM–A/B) 2 – 3. . . . . . . . . . . 2.1.3 Plug–in Terminal for 4–Pole Male Plug (LECOM–B) 2 – 4. . . . . . . . . . . 2.1.4 Plug–in Terminal for 2–Pole Male Plug (External Voltage

Supply) 2 – 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Mechanical Installation 2 – 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Electrical Installation 2 – 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Wiring to a Host 2 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.1 Wiring via RS232C (LECOM–A) 2 – 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2.4.2 Wiring via RS485 (LECOM–B) 2 – 10. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 3 Commissioning

3.1 Before Switching On 3 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 4 Parameter Setting

4.1 Overview 4 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2 Parameter Sets 4 – 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Meaning of Individual Parameters 4 – 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.1 Operating Mode 4 – 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.3.2 LECOM Unit Address (C0009) 4 – 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 11: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Table of Contents RS232C/RS485 Communication Module

ii

Matsushita Electric Works (Europe) AG

4.4 Special Features 4 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.1 Start with Inv. Inhibit Instead of QSP 4 – 7. . . . . . . . . . . . . . . . . . . . . . . . 4.4.2 Reduction of the Response Time of the Interface 4 – 7. . . . . . . . . . . . . 4.4.3 Communication Monitoring 4 – 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.4.4 Relative Setpoint Selection C0141 (Parameter Channel) 4 – 8. . . . . .

Chapter 5 Troubleshooting and Fault Elimination

5.1 Troubleshooting and Fault Elimination 5 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix A Accessories

A.1 Accessoires for RS232C (LECOM–A) A – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.2 Accessories for RS485 (LECOM–B) A – 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix B Code Table

B.1 Code Table B – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix C LECOM–A/B Protocol

C.1 LECOM–A/B Protocol C – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C.1.1 General C – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C.1.2 RECEIVE C – 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C.1.3 SEND C – 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C.1.4 BROADCAST/MULTICAST C – 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C.1.5 Monitoring of the Slave Response C – 14. . . . . . . . . . . . . . . . . . . . . . . . . C.1.6 Transmission Faults C – 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix D List of Abbreviations

D.1 List of Abbreviations D – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix E Glossary

E.1 Glossary E – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Index

Page 12: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

FiguresRS232C/RS485 Communication Module

iiiMatsushita Electric Works (Europe) AG

FiguresFigure 1: Dimensions of the RS232C/RS485 communication module 1 – 6. . . . . . . . . . . . . . . . Figure 2: Inverter VF–C 2 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 3: RS232C/RS485 communication module 2 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 4: Jumper positions for external and internal power supply 2 – 6. . . . . . . . . . . . . . . . . . . Figure 5: Wiring for RS232C (LECOM–A) 2 – 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 6: Wiring for RS485 (LECOM–B) 2 – 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 7: Connection between two inverters and to the C–Net adapter 2 – 11. . . . . . . . . . . . . . Figure 8: LEDs on the communication module 5 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 13: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Figures RS232C/RS485 Communication Module

iv

Matsushita Electric Works (Europe) AG

Page 14: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Chapter 1

Technical Data

1.1 Features 1 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 General Data and Application Conditions 1 – 4. . . . . . . . . . .

1.3 Rated Data 1 – 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Dimensions 1 – 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Communication Times 1 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 15: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleTechnical Data

1 – 2

Matsushita Electric Works (Europe) AG

Page 16: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Technical Data

1 – 3Matsushita Electric Works (Europe) AG

1.1 Features

1.1 Features

The RS232C/RS485 communication module has the following features:

• Different communication media:

– RS232C (LECOM–A)

– RS485 (LECOM–B)

• LECOM protocol V2.0

• The baud rate can be set to 1200, 2400, 4800 9600 or 19200 baud(bit/s).

• Parameter setting via inverter code numbers

• 3 diagnostic LEDs

• Electrical isolation between control stage and power stage

• Electrical isolation of the I/O terminals

• Easy installation

Page 17: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleTechnical Data

1 – 4

Matsushita Electric Works (Europe) AG

1.2 General Data and Application Conditions

1.2 General Data and Application Conditions

Field ValuesCommunicationmedia

RS232C (LECOM–A): copper conductor RS485 (LECOM–B): copper conductor

Protocol LECOM–A/B V2.0

Characterformat

7 bit ASCII 1 Stop bit 1 Start bit 1 Parity bit (even)

Baud rate [bits/s] 1200, 2400, 4800, 9600, 19200

Ambienttemperature

During operation: 0 to +50 °C Transport: –25 to +70 °C Storage: –25 to +55 °C

Permissiblemoisture

Humidity class 3K3 according to EN50178 without condensation(average relative humidity 85%)

24 V DC powersupply

Internal or external supply

Page 18: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Technical Data

1 – 5Matsushita Electric Works (Europe) AG

1.3 Rated Data

1.3 Rated Data

RS232C/RS485 Communication ModuleCommunicationmedia

RS232 (LECOM–A)RS485 (LECOM–B)

Currentconsumption

80 mA

External supply(terminals 39/59)

V = 24 V DC Vrms = 15 to 30 V DC; w = 5 % Vrms = 20 to 25 V DC; w = 48 %; Vss � 35 V

Insulation voltages:

to PE 50 V AC

for external supply(terminal 39/59)

0 V AC (no electrical isolation)

to power stage VF–CE: 270 V AC (double basic insulation)

to the controlterminals

for internal supply:0 V AC (no electrical isolation)

for external supply:100 V AC (single basic insulation)

Degree of pollution VDE 0110 part 2, pollution degree 2

Page 19: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleTechnical Data

1 – 6

Matsushita Electric Works (Europe) AG

1.4 Dimensions

1.4 Dimensions

all dimensions in [mm]

BFVC 9503

Figure 1: Dimensions of the RS232C/RS485 communication module

Page 20: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Technical Data

1 – 7Matsushita Electric Works (Europe) AG

1.5 Communication Times

1.5 Communication Times

The time required for communication with the drive can be displayed as a sequence ofprocessing steps (with corresponding times).

Step Explanationt0 Application program in host: Starts request to the inverter

t1 Software driver in host: Converts the requirement data to the LECOM–A– A/B protocol V2.0 and starts thetransmission

t2 Communication (= serial transmission) to the inverter (message time)

t3 Inverter: Processing of request and starting of response

t4 Communication response is transmitted (message time)

t5 Software driver in host: Evaluates response

t6 Application program in host: gets the result

The times t2, t3, and t4 are described in more detail below.Message time (t2 + t4)The message time comprises the serial communication from the host to the inverter andthe corresponding response from the inverter. The time depends on the message typeand the baud rate set under C0125.

Baud rate [bits/s] (C0125)

1200 2400 4800 9600 19200Single character transmission time [ms] 1 character = 10 bits; � section 1.2

8.4 4.2 2.1 1 0.52

Message type SEND (send data to drive):

Baud rate [bits/s] (C0125)

1200 2400 4800 9600 19200Standard [= t2] (Parameter value = 9 characters) [ms]

150 75 37.5 18.8 9.4

Addition for extended addressing [ms] 41.6 20.8 10.4 5.2 2.6

Message type RECEIVE (read data from drive):

Baud rate [bits/s]

1200 2400 4800 9600 19200Standard [= t4] (Parameter value = 9 characters) [ms]

166.7 83.3 41.7 20.8 10.4

Addition for extended addressing [ms] 83.3 41.7 20.8 10.4 5.2

If more or fewer than 9 characters are transmitted as message data, take thecorresponding character–transmission times into account.

Processing time in the inverter (t3)The processing time in the inverter depends on the inverter type and the code numbers.This is shown in the following table:

� next page

Page 21: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleTechnical Data

1 – 8

Matsushita Electric Works (Europe) AG

1.5 Communication Times

Code numbers Processing time (communicationmodule + inverter) [ms]

C0046, C0135 20

C0050, C0150 20

C0068 30

Write other code numbers 201)

Read other code numbers 20

1) For immediately following write–access procedures, the response times may be up to 50ms.

Page 22: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Chapter 2

Installation

2.1 Connections of the Communication Module 2 – 3. . . . . . .

2.1.1 Overview 2 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.2 Female Plug for 9–Pole SubD Plug(LECOM–A/B) 2 – 3. . . . . . . . . . . . . . . . . . . . . . . . .

2.1.3 Plug–in Terminal for 4–Pole Male Plug(LECOM–B) 2 – 4. . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1.4 Plug–in Terminal for 2–Pole Male Plug (External Voltage Supply) 2 – 4. . . . . . . . . . . . . . .

2.2 Mechanical Installation 2 – 5. . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Electrical Installation 2 – 6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Wiring to a Host 2 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.1 Wiring via RS232C (LECOM–A) 2 – 8. . . . . . . . . .

2.4.2 Wiring via RS485 (LECOM–B) 2 – 10. . . . . . . . . .

Page 23: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleInstallation

2 – 2

Matsushita Electric Works (Europe) AG

Page 24: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Installation

2 – 3Matsushita Electric Works (Europe) AG

2.1 Connections of the Communication Module

2.1 Connections of the Communication Module

2.1.1 Overview

1 32 Pos. Name/Meaning

BFVC 9503BFVC 9503

24V DC RS485

1 3

6

7

2� Green Vcc–LED for voltage supply:

ON = communication module and inverter are supplied with voltage.

BLINKING = communication module is supplied with voltage but the inverter is switched off or not connected

–+ 71 72 88 896

58 � Yellow RxD–LED for receival signal:

BLINKING = Drive units receives messageRS232C

9

4 � Yellow TxD–LED for transmission signal:BLINKING = Drive unit transmits response9

� 9–pole SubD female plug for the RS232C/RS485interface

Figure 3: RS232C/RS485 � Fixing screwcommunication module

� Clamp–plug connection for the RS485 interface

Figure 2: � Display of the operating state of the inverterInverterVF–C � connection for external power supply (24V DC �

10%)

PE connection (not used)

2.1.2 Female Plug for 9–Pole SubD Plug (LECOM–A/B)

Pin Name Input/output Explanation1 – – Not assigned

2 RxD Input Data receiving wire RS232C3 TxD Output Data transmitting wire RS232C

4 DTR Output Transmission control RS232C

5 GND – Reference potential6 DSR Input Not assigned RS232C

7 T/R(A) Input/output RS485

8 T/R(B) Input/output RS485

9 Vcc5 Output Supply +5 V / 10 mA

Page 25: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleInstallation

2 – 4

Matsushita Electric Works (Europe) AG

2.1 Connections of the Communication Module

2.1.3 Plug–in Terminal for 4–Pole Male Plug (LECOM–B)

Pin Name Input/output Explanation71 T/R(B) Input/output RS48572 T/R(A) Input/output RS485

88 S–C – Capacitive screening to PE

89 S – Direct screening to PE

2.1.4 Plug–in Terminal for 2–Pole Male Plug (External Voltage Supply)

Pin Name Input/output Explanation39/� GND24 – Reference potential for external supply

59/� Vcc24 Input External supply 15 to 30 V DC (see chapter 1.3 )

Page 26: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Installation

2 – 5Matsushita Electric Works (Europe) AG

2.2 Mechanical Installation

2.2 Mechanical Installation

Procedure:

1. If there is an operating unit at the front of the inverter,remove it.

2. Mount the RS232C/RS485 communication module to thefront of the inverter using the fixing screws (� figure 3,pos. �).

Tighten the fixing screw to ensure adequate PE connection ofthe communication module.

!

Page 27: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleInstallation

2 – 6

Matsushita Electric Works (Europe) AG

2.3 Electrical Installation

2.3 Electrical Installation

If the RS232C/RS485 communication module is no longersupplied with voltage due to a fault, the bus system willcontinue operation.The connected inverter can however no longer be accessedfrom the host.

The polarity of the voltage supply must not be reversed,otherwise, the communication module will be destroyed!

Voltage supply:

• external 24 V (15 to 30 V) via plug–in connectors 39 (–)/59 (+)or

• internal via the inverter (connection by plugging it on).

Inverters with an extended AIF interface port (front of VF–C inverter) can have aninternal power supply. The greyed area in the diagram below shows the corres–ponding jumper position.

By default, external power supply is set. For internal power supply, you need toposistion the jumper as indicated below.

Tip

Default setting(Only external power supply possible)

Internal power supply

Figure 4: Jumper positions for external and internal power supply

!

Page 28: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Installation

2 – 7Matsushita Electric Works (Europe) AG

2.4 Wiring to a Host

2.4 Wiring to a Host

This chapter informs about networking the communication module using the bussystems RS232C (LECOM–A) or RS485 (LECOM–B). The required accessories aredescribed in appendix A.1.

Warning!

� An additional electrical isolation is required if

– an inverter is connected to a host and

– a safe electrical isolation (double basicinsulation) according to VDE is required.

� Depending on the field bus used, observe thefollowing:

– RS232C: The electrical isolation of the RS232Cinterface (LECOM–A) can be achieved by twolevel converters (e.g. NAiS C–Net Adapter) oranother RS232C electrical isolation.

– RS485: With RS485 (LECOM–B), the NAiS C–Netlevel converter should be installed to thehost if it is not equipped with anappropriately isolated interface.

� For wiring, the electrical isolation of the supplyvoltage must be taken into account.

!

Page 29: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleInstallation

2 – 8

Matsushita Electric Works (Europe) AG

2.4 Wiring to a Host

2.4.1 Wiring via RS232C (LECOM–A)

The following figure shows schematically the connection to a host (here: PC) viaRS232C (LECOM–A).

PC cable

BFVC 9503

Figure 5: Wiring for RS232C (LECOM–A)

Wiring features for RS232C (LECOM–A):

Communication media RS232C

Network topology Point–to–point

Possible number of inverters 1

Maximum cable length 15 mMaximum baud rate 19200 bit/s

Notes

• We recommend the use of Matsushita PC and PLC cables forwiring (� appendix A.1).

• Use metallic SubD connector shells.

• Connect both ends of the screen to the connector shells.

Page 30: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Installation

2 – 9Matsushita Electric Works (Europe) AG

2.4 Wiring to a Host

Wiring the PC cable

Pin No.

1 –

2 RxD

3 TxD

4 DTR

5 GND

6 DSR

7 T/R(A)

8 T/R(B)

9 Vcc5

Shield

Pin No.

1 CD

2 RD

3 SD

4 ER

5 SG

6 DR

7 RS

8 CS

9 RI

Shield

BFVC 9503RS232C connectorSubD 9–pin male

PC–ATSubD 9–pin female

+

Standard adapter9 to 25 pin

Wiring the PLC cable

Pin No. Pin No.

1 FG

2 SD

3 RD

4 RS

5 CS

6 –

7 SG

8 –

9 ER

Shield

BFVC 9503RS232C connectorSubD 9–pin male

Matsushita PLC RS232C COM–PortFP1/M/2/10SH, SDU FP2/3/CSubD 9–pin male

1 –

2 RxD

3 TxD

4 DTR

5 GND

6 DSR

7 T/R(A)

8 T/R(B)

9 Vcc5

Shield

Page 31: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleInstallation

2 – 10

Matsushita Electric Works (Europe) AG

2.4 Wiring to a Host

2.4.2 Wiring via RS485 (LECOM–B)

The following figure shows schematically the connection to a host (PC or PLC) viaRS485 (LECOM–B).

1 1 1

2a

PC

NAiS C–Netadapter

FP2PLC

2b

Figure 6: Wiring for RS485 (LECOM–B)� Interface cable RS485� Optional host connection

a) PLC connection RS232Cb) PC connection RS232C

We recommend the use of appropriate accessories (� ap-pendix A.2).

Only use screened cables twisted in pairs for wiring RS485interface cables.

Tip

Wiring features for RS485 (LECOM–B):

Communication media RS485 (2 wires)

Network topology Line

Possible number of inverters 31

Maximum cable length 1200 m

Maximum baud rate 19200 bit/s

Page 32: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Installation

2 – 11Matsushita Electric Works (Europe) AG

2.4 Wiring to a Host

Connection between two inverters:

• Connect the cable screen to terminal 89 (direct PE) of onecommunication module and to terminal 88 (capacitive PE) of theother communication module (� Fig. 7). This method preventscurrents flowing through the cable screens.

• Connect the terminals 71 and 72 between the communicationmodules via paired cables (e. g. green and yellow).

Connection to the C–Net adapter:

• Connect the cable screen to terminal 89 (direct PE) of the lastinverter and to FG of the C–Net adapter (� Fig. 7). This methodprevents current flows through the cable screens.

71 72 88 89 71 72 88 89

C–Net adapter

Inverter 1 Inverter 2

BFVC9503

BFVC9503

RxD

TxD

FG

Figure 7: Connection between two inverters and to the C–Net adapter

Page 33: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleInstallation

2 – 12

Matsushita Electric Works (Europe) AG

2.4 Wiring to a Host

Page 34: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Chapter 3

Commissioning

3.1 Before Switching On 3 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 35: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleCommissioning

3 – 2

Matsushita Electric Works (Europe) AG

Page 36: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Commissioning

3 – 3Matsushita Electric Works (Europe) AG

3.1 Before Switching On

3.1 Before Switching On

Check the wiring for completeness, short circuit and earthfault before the inverter is connected to the mains.

Procedure: Observe the following switch–on sequence:

1. Switch on the inverter and – if required – the externalsupply of the communication module.The operating status display for the inverter (� figure 3 on page 2 – 3, Pos. �) must be on or blinking.

The green LED (� figure 3 on page 2 – 3, pos. �) must be on. If thisis not the case, � chapter 5.

2. The transmission speed or LECOM baud rate (C0125) isfactory set to 9600 baud. If a different value is required,adjust it via the operating unit.

3. Set the LECOM unit address (C0009) via the operatingunit or via the host (factory setting: 1).If several inverters are interconnected in a network, it must bepossible for the host to address each inverter uniquely. Every invertermust therefore have a different LECOM inverter address (C0009). Thevalues 00, 10, 20, 30, ..., 90 must not be set since they are reservedfor group addressing.

The code numbers C0009 (LECOM inverter address) and C0125(LECOM baud rate) can also be input via LECOM. Please observethat the parameters for the host must be adapted. If C0125 ischanged, the host will not recognize the response because theinverter has already transmitted it using the new baud rate.

Tip

� next page

!

Page 37: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleCommissioning

3 – 4

Matsushita Electric Works (Europe) AG

3.1 Before Switching On

Next steps:1. It is now possible to communicate with every inverter,

i. e. all code numbers can be read and all writeablecodes, except C046 (frequency setpoint) and C0135(control word) can also be changed.If codes C0046 and C0135 are to be changed as well, setC0003=3.

2. If the inverter is switched on while the operating modeC0001 = 3 is active and the speed setpoint is set to 0,QSP (quick stop) is active. Thus, the drive cannot start inan uncontrolled way. The QSP function can bedeactivated by setting bit 3 from C0135 to 0.

Page 38: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Chapter 4

Parameter Setting

4.1 Overview 4 – 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2 Parameter Sets 4 – 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Meaning of Individual Parameters 4 – 5. . . . . . . . . . . . . . . .

4.3.1 Operating Mode 4 – 5. . . . . . . . . . . . . . . . . . . . . . . .

4.3.2 LECOM Unit Address (C0009) 4 – 5. . . . . . . . . . .

4.4 Special Features 4 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Start with Inv. Inhibit Instead of QSP 4 – 7. . . . . .

4.4.2 Reduction of the Response Time ofthe Interface 4 – 7. . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 Communication Monitoring 4 – 8. . . . . . . . . . . . . .

4.4.4 Relative Setpoint Selection C0141 (Parameter Channel) 4 – 8. . . . . . . . . . . . . . . . . . .

Page 39: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleParameter Setting

4 – 2

Matsushita Electric Works (Europe) AG

Page 40: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Parameter Setting

4 – 3Matsushita Electric Works (Europe) AG

4.1 Overview

4.1 Overview

The parameter setting for the communication module comprises:

• Inverter parameters which can also be set with the BFVC 904Ckeypad.

• Communication parameters, which can only be accessed via thecommunication module.

Only the inverter parameters are permanently saved in the corresponding inverter.

In the following and in the code table (� appendix B), only the parameters importantfor serial communication are listed. For further information about the parameter settingsee the Manual or the Operating Instructions of the inverters.

Page 41: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleParameter Setting

4 – 4

Matsushita Electric Works (Europe) AG

4.2 Parameter Sets

4.2 Parameter Sets

The VF–C inverter is equipped with 4 addressable parameter sets. They are addressedby means of a code–digit offset:

• Offset 0 addresses parameter set 1 with the codes C0000 toC1999.

• Offset 2000 addresses parameter set 2 with the codes C2000 toC3999.

• Offset 4000 addresses parameter set 1 with the codes C4000 toC5999.

• Offset 6000 addresses parameter set 2 with the codes C6000 toC7999.

If a parameter is only available once (see VF–CE Operating Instructions), use thecode–digit offset 0.

� Example:

C011 = maximum field frequencyC011 in parameter set 1: code number = 11C011 in parameter set 2: code number = 2011C011 in parameter set 3; code number = 4011C011 in parameter set 4; code number = 6011

Changes of the parameters are automatically saved in the inverter (see VF–CEOperating Instructions). Process data, for instance control words or setpoints, areexcluded.

Page 42: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Parameter Setting

4 – 5Matsushita Electric Works (Europe) AG

4.3 Meaning of Individual Parameters

4.3 Meaning of Individual Parameters

4.3.1 Operating Mode

Code C0001 (operating mode) determines the source (terminal, keypad, LECOM)which writes the frequency setpoint (C0046) and the control word (C0135).

Independently of the selected operating mode C0001, the inverter can be inhibitedunder C0040 via LECOM.

Please note that the operating mode C0001 is available in bothparameter sets. Thus, C0001 must be set identically in both para-meter sets. LECOM control (C0001 = 3) is subject to the operating mode inparameter set1. Terminal control (C0001 <> 3) is subject to theoperating mode in parameters set 1 and parameter set 2.

Tip

4.3.2 LECOM Unit Address (C0009)

The LECOM–A/B protocol uses the LECOM unit address to address the inverter. TheLECOM unit address is set under code C0009 at the inverter. The address must onlybe used once. Thus, each inverter must get its own LECOM unit address. Do not setthe values 00, 10, 20, 30, ..., 90 because they are reserved for group addressing.

The LECOM–A/B protocol enables inverter groups. This allows a write request to beissued to several drives at the same time, e.g. to select new setpoints or enable or inhibitthe inverter. They are selected through the following reserved LECOM unit address:

LECOM unit addressC0009 for group drives

LECOM unit addresses of the addressed inverters

00 all10 11 to 19

20 21 to 29

30 31 to 3940 41 to 49

50 51 to 59

60 61 to 69

70 71 to 7980 81 to 89

90 91 to 99

� next page

Page 43: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleParameter Setting

4 – 6

Matsushita Electric Works (Europe) AG

4.3 Meaning of Individual Parameters

Please note that with LECOM inverter addresseswhich end with a 0, the inverter does not return anacknowledgement, i.e. the host does not recognizewhether the inverter received the data correctly ornot.

Tip

Page 44: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Parameter Setting

4 – 7Matsushita Electric Works (Europe) AG

4.4 Special Features

4.4 Special Features

4.4.1 Start with Inv. Inhibit Instead of QSP

• After mains connection with the operating mode C0001 = 3, thedrive is in the status QSP.

• With C1920 = 1 the switch–on status is always Inv. inhibit, so thatthe drive can be enabled by writing C0040 = 1.

Code Name Note

C1920 Start status

(communication mo-

dule)

0 QSP 1 Inverter inhibit

LECOM format: VD

4.4.2 Reduction of the Response Time of the Interface

• With active reduced response time, write messages (send) are onlychecked for transmission errors:

– If the message is fault–free, a positive acknowledgement(ACK) is sent, otherwise it is a negative acknowledgement(NAK).

– Only then the value to be written is transmitted to theinverter.

• The module can be re–addressed approximately after 50 ms.

The acceptance of the value by the inverter cannot beguaranteed.

Code Name Note

C1921 Shortened response time

(communication module)

0 Not active 1 active

LECOM format: VD

!

Page 45: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleParameter Setting

4 – 8

Matsushita Electric Works (Europe) AG

4.4 Special Features

4.4.3 Communication Monitoring

• The communication module can monitor the communicationconnection to the host.

• If the host does not send a message to the communication modulewithin the monitoring time set under C1923, the action set underC1922 will be carried out.

Code Name Note

C1922 Monitoring selectioncode

(communication module)

0 Not active 1 Inverter inhibit2 QSP (quick stop)

LECOM format: VD

C1923 Monitoring time

(communication module)

50 to 65535 ms

LECOM format: VD

4.4.4 Relative Setpoint Selection C0141 (Parameter Channel)

• Enter a relative setpoint which refers to C0011 under C0141.

• Independently of the currently set parameter, C0011 of parameterset 1 is always taken as reference value.

• The automatic adaptation of the relative setpoint in the event of aC0011 change is not considered because C0011 can only bechanged when the inverter is inhibited.

Code Name Note

C0141 Frequency setpoint

(communication module)

0 to 100 %

LECOM format: VD

�Note

The digital and analog input and output signals are freelyconfigurable (� VF–CE Operating Instructions; codes C0410,C0412, C0417 and C0421).

Page 46: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Chapter 5

Troubleshooting and Fault Elimination

5.1 Troubleshooting and Fault Elimination 5 – 3. . . . . . . . . . . . .

Page 47: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleTroubleshooting and Fault Elimination

5 – 2

Matsushita Electric Works (Europe) AG

Page 48: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Troubleshooting and Fault Elimination

5 – 3Matsushita Electric Works (Europe) AG

5.1 Troubleshooting and Fault Elimination

5.1 Troubleshooting and Fault Elimination

LED yellow (TxD)LED green (Vcc)

LED yellow (RxD)

Operating status display of the inverter

Figure 8: LEDs on the communication module (� figure 3, page 2 – 3)

Fault Cause RemedyCommunica-tion with theinverter failed

Inverter is switched off.Display:� none of the operating–state displays is lit–upand/or� green Vcc–LED is blinking

Supply inverter with voltage (� VF–CE Operating Instructions)

The communication module is not supplied withvoltageDisplay: green Vcc–LED is not flashing or blinking.

� With internal supply from the inverter, checkthe connection to the inverter.

� With external supply, check the voltage atterminals 39 and 59. A voltage between 15 and30 V must be applied (�section 2.3 )

The communication module has not been initiali-zed with the inverterDisplay: green Vcc–LED is blinking.

� Supply inverter with voltage (� VF–CEOperating Instructions)

� Check the connection to the inverter.

The inverter does not receive messages.For a test, let the host send messages cyclically.The yellow RxD–LED must blink when the hostsends a message.

If the yellow RxD–LED does not blink:� Check the wiring (� section 2.4)and� Test whether the host sends messages and

uses the appropriate interface.

The inverter does not send messages.For a test, let the host send message cyclically.The yellow TxD–LED must blink when the hostsends a message to the inverter.

1.Yellow TxD–LED is not blinking:Parameter for LECOM unit address (C0009) andLECOM baud rate (C0125) must be the same atthe inverter and the host. Check the parametersC0009 and C0125 at both units and set them tothe same value if necessary.(Inverter–addressparameters 00, 10, …, 90 must not be used.)

2.Yellow TxD–LED is blinking:� The LECOM unit addresses (C0009) must be

different at all connected inverters. Correctpossibly occuring double addressing.

� Check the wiring to your host.� With self–developed LECOM–A/B software

drivers and RS485 operation, observe thetransmission control. After transmitting signals,the host must return to receive mode afterapprox. 1 ms.

� next page

Page 49: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleTroubleshooting and Fault Elimination

5 – 4

Matsushita Electric Works (Europe) AG

5.1 Troubleshooting and Fault Elimination

Fault Cause RemedyInverter doesnot execute

1.Inverter sends negative acknowledgement (NAK response):

� Set parameter 3 for operating mode C0001.� In general, write command not possible.

write com-mand

� The operating mode C0001 is set incorrectlyfor write access to codes C0046 and C0135.

� The code is defined so that it can only be read.2.Inverter sends positive acknowledgement

(ACK response):� Inverter works with a different parameter set

� Activate inverter inhibit� Change parameter set, the parameter change

will become active now.

Page 50: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Appendix A

Accessories

A.1 Accessoires for RS232C (LECOM–A) A – 3. . . . . . . . . . . . . .

A.2 Accessories for RS485 (LECOM–B) A – 4. . . . . . . . . . . . . . .

Page 51: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleAccessories

A – 2

Matsushita Electric Works (Europe) AG

Page 52: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Accessories

A – 3Matsushita Electric Works (Europe) AG

A.1 Accessoires for RS232C (LECOM–A)

A.1 Accessoires for RS232C (LECOM–A)

In the following you will find accessory components for RS232C (LECOM–A):

Bezeichnung Order no. ExplanationPC cable BFVC9503PCAT between communication module and PC

(9pole socket, with 9–25 pin adpater)

PLC cable BFVC9503PLC between communication module and PLC (9pole plug)

Specification for RS232C interface cablesCable type LIYCY 4 x 0.25 mm2 shielded

Cable resistance � 100 �/km

Capacitance per unit length � 140 nF/km

Length � 15 m

Page 53: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleAccessories

A – 4

Matsushita Electric Works (Europe) AG

A.2 Accessories for RS485 (LECOM–B)

A.2 Accessories for RS485 (LECOM–B)

In the following you will find accessory components for RS485 (LECOM–B):

Name Order no. ExplanationC–Net adapter AFP8536CE Level converter between RS232C/RS422 and RS485 with electrical

isolation; power supply 230 V AC, e. g. for PC–AT

C–Net adapterS1 type

AFP15401CE Level converter between RS232C and RS485 with electrical isolation, forMatsushita FP1 and FP3 PLCs; power supply 5 V DC over RS422 cablefrom PLC

C–Net adapterS2 type

AFP15402CE Level converter between RS232 and RS485 with electrical isolation, forMatsushita FP0, FP–M, FPC, and FP2 PLCs; power supply 5 V DC overRS232C cable from PLC

Specification for RS485–interface cable

with a length of up to 300 m:

Cable type LIYCY 1 x 2 x 0.5 mm2 shielded

Cable resistance � 40 �/km

Capacitance per unit length � 130 nF/km

Length � 300 m

with a length of up to 1200 m:

Cable type CYPIMF 1 x 2 x 0.5 mm2 shielded

Cable resistance � 40 �/km

Capacitance per unit length � 60 nF/km

Length � 1200 m

Page 54: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Appendix B

Code Table

Page 55: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleCode Table

B – 2

Matsushita Electric Works (Europe) AG

Page 56: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Code Table

B – 3Matsushita Electric Works (Europe) AG

B.1 Code Table

B.1 Code Table

How to read the code table:

Code Code number of the parameter.Leading zeros may be omitted. Code numbers marked with * are only in parameter set 1.

Name Parameter name. Brackets indicate whether the code is available in the communication module or the inverter.

Communicationmodule: Parameters in the RS232C/RS485 communication module BFVC 9503VF–C: Parameters in the BFVCX0xxxA VF–CE inverter

The parameters can also be set using the BFVC 904C keypad.

Para–meters

Contents or meaning of the parameter values.Parameters printed in bold are factory settings.

Code Name NoteC0001 Operating mode

for VF–CE� Operating Instructions VF–CE

C0009* LECOM inverteraddress

1 1 to 99

Inverter address for unique address in a LECOM–A/B network.Do not set the values 00, 10, ..., 90, since they are reserved for group addressing.

LECOM format: VD

C0040* Inverter inhibit

(Communication

module)

0 Inverter inhibited1 Inverter enabled

Parameter C0040 is independent of the operating mode C0001.The inverter can also be enabled with the control word C0135.

LECOM format: VD

C0043* TRIP reset forVF–CE

(Communication

module)

0 No current fault; reset the fault by writing value 01 Current fault

Parameter C0043 is independent of the operating mode C0001.TRIP can also be resetwith the control word C0135.

LECOM format: VD

C0046* Frequencysetpoint forVF–CE

(Communication

module)

0 to 480 Hz

The value can be changed by the display factor C500/C501.

LECOM format: VD

C0046* Frequencysetpoint forVF–CE

0 to 480 Hz

The value can be changed by the display factor C500/C501.

LECOM format: VD

Page 57: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleCode Table

B – 4

Matsushita Electric Works (Europe) AG

B.1 Code Table

Code Name NoteC0068* Operating status

for VF–CE

(Communication

module)

Bit Meaning

0 to 3 Operating fault (TRIP) The 10th digit of the LECOM fault number (see C0161 to C0164) is displayed.Example: TRIP OH = 5 (LECOM no. = 50)

4 to 7 Last communication error0 = No error1 = Check sum error 2 = Protocol frame error3 = Reserved 4 = Invalid code number5 = Invalid variable6 = Unauthorised access7 = Message processing interrupted by

a new message15 = General fault

8 Inv. enable0 = No inv. enable1 = Inv. enable

9 FREE; display of C0150 Bit 5Factory setting: Qmin (fd � fdQmin)

0 = Qmin not active1 = Qmin active

10 Reserved11 FREE; display of C0150 Bit 1

Factory setting: IMP (pulse inhibit)0 = Pulses to power stages inhibited1 = Pulses to power stages enabled

12 Reserved13 FREE; display of C0150 Bit 2

Factory setting: Imax (current limit reached)0 = Current limit not reached1 = Current limit reached

14 FREE; display of C0150 Bit 4RFG on = RFG off(Ramp–function generator input = ramp–function generator output)

0 = RFG on <> RFG off1 = RFG on � RFG off

15 TRIP (fault) 0 = No fault 1 = Fault occured

LECOM format: VH

C0125* LECOM baud rate 0 9600 baud (Factory setting)1 4800 baud 2 2400 baud 3 1200 baud 4 19200 baud

Transmission rate for LECOM–A/B in bit/s (= baud).

LECOM format: VD

C0127 Frequencysetpoint selectionformat

(Communication

module)

0 Absolute setpoint selection1 Normalized setpoint selection

LECOM format: VD

Page 58: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Code Table

B – 5Matsushita Electric Works (Europe) AG

B.1 Code Table

Code Name NoteC0135* Control word for

VF–CE

(Communication

module)

Bit Meaning

0, 1 JOG1, JOG2, JOG3 (C0046)0 = C0046 active 1 = JOG1 (C0037) active 2 = JOG2 (C0038) active 3 = JOG3 (C0039) active

2 CW/CCW (CW rotation/CCW rotation)0 = CW rotation1 = CCW rotation

3 QSP (quick stop) 0 = QSP not active1 = QSP active

4 RFG stop (stop of the ramp–function generator)0 = RFG stop not active1 = RFG stop active

5 RFG zero (deceleration along the Tif ramp C0013) 0 = RFG zero not active1 = RFG zero active

6 UP function for motor potentiometer 0 = UP not active

1 = UP active7 DOWN function for motor potentiometer

0 = DOWN not active1 = UP active

8 Reserved 9 Inv. inhibit (inverter inhibit)

0 = No inverter inhibit1 = Inverter inhibit

10 Reserved 11 TRIP reset

0⇒1Signal from 0 to 1 resets TRIP

12 PAR (parameter–set changeover)0�1 = parameter set 2 1�0 = parameter set 1

13 Reserved 14 DC brake (DC injection brake)

0 = DC brake not active 1 = DC brake active

15 Reserved

The control word is used for inverter control. It includes the control commands in acompressed bit format.

LECOM format: VH

C0141 Setpoint Signal configuration Signal Meaningaccording toselected

1xx1 NSET–N Speed setpoint in % of nmax(Speed control)

configuration4xx1 MCTRL–M–ADD Torque setpoint in %(Torque control)

5xx1 NSET–N Speed setpoint in % of nmax(Master frequency)

6xx1 NSET–N Speed setpoint in % of nmax(Master frequency – slave bus)

7xx1 NSET–N Speed setpoint in % of nmax(Master frequency – slave cascade)

Page 59: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleCode Table

B – 6

Matsushita Electric Works (Europe) AG

B.1 Code Table

Code Name NoteC0150* Status word for

VF–CE

(Communication

module)

Free configuration with C0417 (� Operating Instructions VF–CE)

Bit Meaning

0 FREE 0: = freely combinable1 IMP (pulse inhibit)

0 = Pulses to power stages enabled1 = Pulses to power stages inhibited

2 FREE2: = freely combinable3 FREE 3: = freely combinable4 FREE 4: = freely combinable5 FREE 5: = freely combinable6 fd = 0 (act. frequency = 0)

0 = fd <> 0 1 = fd = 0

7 Inv. inhibit (inverter inhibit)0 = No inverter inhibit1 = Inverter inhibit

8–11 Unit status0 = Unit initialisation1 = Switch–on inhibit3 = Operation inhibited (inverter inhibit)6 = Operation enabled7 = Message active8 = Active fault 9 = Power off

12 Warning 0 = No warning1 = Warning

13 Message 0 = No message1 = Message

14 FREE 14: = freely combinable15 FREE 15: = freely combinable

The status word contains the most important status information in compressed form.

LECOM format: VH

Page 60: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Code Table

B – 7Matsushita Electric Works (Europe) AG

B.1 Code Table

Code Name NoteC0249* LECOM code

bank

(Communication

module)

Code bank Code number

0 0 to 255 (Factory setting)1 250 to 505 2 500 to 755 3 750 to 1005 4 1000 to 1255 5 1250 to 1505 6 1500 to 1755 7 1750 to 2005 8 2000 to 2255 9 2250 to 2505 10 2500 to 2755 11 2750 to 3005 12 3000 to 3255 13 3250 to 3505 14 3500 to 3755 15 3750 to 4005

The LECOM code bank ensures the compatibility with the master–system driversaccording to the LECOM–A/B specification V1.0. The maximum code number is 255.With the code bank, an offset of 250 is added to the code number.

The code bank addressing is not effective with extended code addressing(LECOM–A/B specification).

The parameter value is always set to 0 when switching on.

LECOM format: VD

C1810* SW labelling

(Communication

module)

33S2102I_xy000

Software labelling of the RS232C/RS485 communication modulex = main SW version y = SW subversion

LECOM format: VS

C1811* SW generation

(Communication

module)

Software generation of the RS232C/RS485 communication module

LECOM format: VS

C1920 Start status

(Communication

module)

0 QSP 1 Inverter inhibit

LECOM format: VD

C1922 Monitoringselection code

(Communication

module)

0 Not active 1 Inverter inhibit2 QSP (quick stop)

LECOM format: VD

C1921 Shortenedresponse time

(Communication

module)

0 Not active 1 active

LECOM format: VD

C1923 Monitoring time

(Communication

module)

50 to 65535ms

LECOM format: VD

C1962 Extended codeNo.

� fault table, page B – 8

Page 61: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleCode Table

B – 8

Matsushita Electric Works (Europe) AG

B.1 Code Table

The following list indicates the fault numbers which can be read under C1962:

Faultno.

Meaning Classification

0 No error

1 Invalid service designation Internal fault

2 Invalid call recognition Internal fault

3 Invalid data type Application error in the host

4 Invalid subcode number Application error in the host

5 Invalid code number Application error in the host

6 Invalid general parameter Application error in the host

7 Access error: operating status, e.g. inverterinhibit

Access error

8 Access error: because operating mode C0001 Access error

9 Access error: parameter only readable Access error

10 Access error: general Access error

11 Data block too long Limit value exceeded

12 Collision with other parameter values Limit value exceeded

13 Leave value range Limit value exceeded

14 General limit value exceeding Limit value exceeded

17 General internal fault Internal fault

32 General Communication fault communication module inverter

33 Time limit exceeded Communication fault communication module inverter

34 Frame error Communication fault communication module inverter

35 Parity error Communication fault communication module inverter

36 Overflow Communication fault communication module inverter

37 Handshake Communication fault communication module inverter

38 Block memory overflow Communication fault communication module inverter

208 Frame error Communication fault inverter communication module

209 Overflow error Communication fault inverter communication module

210 Check–sum fault in the BFVC 9503communication module detected

Communication fault inverter communication module

211 Message interruption Communication fault inverter communication module

212 Invalid data Communication fault inverter communication module

213 Invalid service Communication fault inverter communication module

214 Parity error Communication fault inverter communication module

Page 62: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Appendix C

LECOM–A/B Protocol

Page 63: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 2

Matsushita Electric Works (Europe) AG

Page 64: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module LECOM–A/B Protocol

C – 3Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

C.1 LECOM–A/B Protocol

The LECOM–A/B protocol is used to exchange data between NAiS inverters and a host.The LECOM–A/B protocol is based on DIN 66019, ISO 1745 and ANSI X3.28 (category2.5 and A2, A4). These standards are similar to each other and describe the controlmode of a transmission section of a transmission system.

The host, which is the master, can communicate with a NAiS VF–CE frequency inverter(slave) in three modes:

• RECEIVE (� C – 10)

• SEND (� C – 12)

• BROADCAST/MULTICAST (� C – 13)

C.1.1 General

The units communicate by means of the ASCII code:

0 1 2 3 4 5 6 7 8 9 O 6.5 C D E F0 NUL SOH STX ETX EOT ENQ ACK BEL BS HT LF VT jFF CR SO SI

1 DLE DC1 DC2 DC3 DC4 NAK SYN ETB CAN EM SUB ESC FS GS RS US

2 ‘ ’ ‘!’ ‘”’ ‘#’ ‘$’ ‘%’ ‘&’ ‘’’ ‘(’ ‘)’ ‘*’ ‘+’ ‘,’ ‘–’ ‘.’ ‘/’

3 ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’ ‘8’ ‘9’ ‘:’ ‘;’ ‘<’ ‘=’ ‘>’ ‘?’

4 ‘@’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ ‘G’ ‘H’ ‘I’ ‘J’ ‘K’ ‘L’ ‘M’ ‘N’ ‘O’

5 ‘P’ ‘Q’ ‘R’ ‘S’ ‘T’ ‘U’ ‘V’ ‘W’ ‘X’ ‘Y’ ‘Z’ ‘[’ ‘\’ ‘]’ ‘^’ ‘_’

6 ‘‘’ ‘a’ ‘b’ ‘c’ ‘d’ ‘e’ ‘f’ ‘g’ ‘h’ ‘i’ ‘j’ ‘k’ ‘l’ ‘m’ ‘n’ ‘o’

7 ‘p’ ‘q’ ‘r’ ‘s’ ‘t’ ‘u’ ‘v’ ‘w’ ‘x’ ‘y’ ‘z’ ‘{’ ‘|’ ‘}’ ‘~’

� Example: “EOT” character = 02hex = 2dec

“1” character = 31hex = 49dec

Code number (C1, C2)

Standard addressing

The meaning of the code numbers and the assigned parameters can be obtained fromthe code table (see appendix B). When transmitting data, the code number is coded asfollows:

The following calculation determines the two ASCII digits (value range: 48dec … 127dec)from the code number (value range: 0 … 6229):

C1 = INTEGER((REMAINDER(code number/790))/10)+48dec

� next page

Page 65: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 4

Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

C2 = REMAINDER(REMAINDER(code number/790)/10) +INTEGER(code number/790) x 10 + 48dec

The INTEGER is the digit before the comma, the REMAINDER is an integer.

� Example 1: 1/5 = 2 remainder 3

INTEGER(13/5) = 2 REMAINDER(13/5) = 3

� Example 2: Convert code number 1002 in ASCII code C1 and C2:

C1 ASCII = INTEGER((REMAINDER(1002/790))/10) + 48 = INTEGER(212/10) + 48 = 21 + 48 = 69 = 45hex = “E”ASCII

C2 ASCII = REMAINDER(REMAINDER(1002/790)/10) +INTEGER(1002/790) x 10 + 48 = REMAINDER(212/10) + 1 x 10 + 48 = 2 + 10 + 48 = 60 = 3Chex = “<”ASCII

The code number C1002 is converted into the ASCII string “E<”, if it is transmitted to theinverter by a host.

Addressing via code bank

With previous LECOM–A/B drivers, only code numbers in the range from 0 to 255 couldhave been addressed, since these drivers used only one byte as code number. Toachieve the addressing of the wider code–number range with these drivers, use codebanking. The code–number range 0 … 255 is displayed as a window over the wholecode–number range. This is controlled via the code C0249 (code bank). Code C0249can always be accessed via number 249, no matter which code bank has currently beenset.

The following assignments exist:

Code bank Code offset Code–number range0 0 0 … 255

1 250 250 … 505

2 500 500 … 755

3 750 750 … 1005

4 1000 1000 … 1255

5 1250 1250 … 1505

6 1500 1500 … 1755

7 1750 1750 … 2005

Page 66: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module LECOM–A/B Protocol

C – 5Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

�Note

Codebanking is only active when the standard addressing isbeing used. If the selected code numbers are higher than 255,the code–number range increases correspondingly. Only thecorresponding code–number offset is selected by means ofthe code bank.

� Example:

Set the codebank INTEGER (1002/250) = 4 in C0249 to addressthe code number 1002. C1002 is then accessed via the codenumber C02.

Addressing via input selection

Simple LECOM–A/B drivers, which only use the standard addressing, cannot addresssubcodes. The input selection C0248 has been developed to offer the possibility ofaddressing the subcodes. When using the standard addressing, the value entered inC0248 is always considered as subcode. The code C0248 can always be accessed vianumber 248, no matter which code bank has currently been set.

� Example:

Enter value 1 in C0248 to address the JOG value 1 in C0039subcode 1. Now subelement 1 is always addressed whenaccessing C39.

After a subelement has been accessed through C0248,C0248 should be reset to 0 to avoid accidentally addressinga subelement when accessing a code.

Tip

Extended addressing

Another possibility is the direct addressing of parameters by means of extendedaddressing.

! CH1 CH2 CH3 CH4 SC1 SC2

� next page

Page 67: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 6

Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

The abbreviations have the following meanings:

! The ASCII character “!” = 21hex = 33dec shows that the expandedaddressing is used.

CH1 to CH4 Code number in hexadecimal code: each character correspondsto a nibble of the code numbers (CH1 is the highest, CH4 is thelowest nibble).

SC1, SC2 Subcode number in hexadecimal code: Each character corres–ponds to a nibble of the code number word (SC1 is the highestand SC2 the lowest nibble).

The following characters can be displayed in the ASCII code:

ASCII 0 1 2 3 4 5 6 7 8 9 O 6.5 C D I F

dec 48 49 50 51 52 53 54 55 56 57 65 66 67 68 69 70

hex 30 31 32 33 34 35 36 37 38 39 41 42 43 44 45 46

A code number range from 0 to 65535 can be addressed by means of these characters.A maximum of 255 subelements (field elements) can be accessed via one subcodenumber of each code.

� Example: 1002 = “!03EA00”

Parameter value (V1 to Vn)

Parameter values can be transmitted in four different formats with the followingstructures:

• ASCII decimal format (VD)

– VK1 VK2 VK3 VK4 VK5 VK6 . NK1 NK2 NK3 NK4

• ASCII hexadecimal format (VH)

H VH1 VH2 VH3 VH4 VH5 VH6 VH7 VH8

• String format (VS)

S VS1 VS2 VS3 VS4 VS5 VS6 ... VS240

• Octet string format for data blocks (VO)

O VO1 VO2 VO3 VO4 VO5 VO6 ... VO240

Page 68: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module LECOM–A/B Protocol

C – 7Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

The abbreviations have the following meanings:

VK1 to VK6 Integers; decimal point (if required)

NK1 to NK4 Decimal codes (if required)

“H” (48hex) Character [H], transfer of parameter values in the ASCII hexadeci-mal format

VH1 to VH8 1 to 8 hexadecimal characters each [0 to 9; A to F]

“S” (53hex) Character [S], transfer of parameter values in the string format

VS1 to VS240 1 to 12 visible ASCII characters each (no control characters)

“O” (4Fhex) Character [O], transfer of parameter values in the octet stringformat

VO1 to VO240 Data block in hexadecimal code; each character corresponds to anibble of the data block

Parameter value in the ASCII decimal format (VD)

The ASCII decimal format (VD) is most often used. The values consist of the following:

1 leading negative sign(if required) 6 digits before the comma (VK1 to VK6) 1 decimal point (if required) 4 digits after the comma (NK1 to NK4) (if required)

Values from –214748.3648 to 214748.3647 can be displayed.

In the ASCII decimal format (VD), the decimal point mustnot be transmitted if the value does not have digits after thecomma.

Tip

Parameter value in ASCII hexadecimal format (VH)

The LECOM–A/B protocol supports the tranmission of hexadecimal parameter valueswith a length of:

• 2 characters (byte value)

• 4 characters (wort/integer value)

• 8 characters (double word/long integer)

In the ASCII hexadecimal format, VH1 is the highest and VH8 the lowest hexadecimalcharacter.

Page 69: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 8

Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

Parameter value in the string format (VS)

By means of the string format (VS) of the protocol it is possible to transmit strings withmax. 20 characters in both directions. The NAiS inverter can only send the string parameters (e. g. C200).

Parameter values in the octet string format (VO)

The LECOM–A/B protocol includes the octet string format (VO) with which it is possibleto transfer data blocks.The character sequence correspond to the filing in the memory (ascending order), i. e.the character transmitted first is the data block nibble with the lowest address. The datastructure of the data block corresponds to the Intel–memory format with the followingdifinition:

BYTE: 1. High nibble

2. Low nibble WORD: 1. High BYTE

2. Low BYTE DWORD: 1. High WORD

2. Low WORD

Unit address (AD1, AD2)

One or more bus participants (slaves) can be selected by means of the unit addresswhich is 2 bytes (AD1, AD2) long. The LECOM–A/B protocol supports the broadcastmessages, i.e. a message is sent to a group or all other bus participants. For this, unitaddresses are reserved (see BROADCAST, page 13). A unit address has the followingstructure:

AD1 AD2

The abbreviations have the following meanings:

AD1 ASCII ten–digit code of the slave address (0 … 9; 30 … 39hex)

AD2 ASCII one digit code of the slave address (0 … 9; 30 … 39hex)

Page 70: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module LECOM–A/B Protocol

C – 9Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

Block–check character (BCC)

The block–check character (BCC) is used to store the transmitted data and is generatedaccording to DIN 66219 (chapter 3).

Because of the program, the block–check character is generated by a XOR link from thefollowing digits of the SEND message:

• it starts with the character directly after the STX control character

• it ends directly after the ETX control character

– BCC can accept the value 00 … FFhex.

EOT AD1 AD2 STX C1 C2 V1 ... Vn ETX BCC

<——————— BCC ———————>

or with expanded addressing:

STX ”!” CH1 CH2 ... SC2 ETX BCC

<—————————— BCC —————————>

Message response

The NAiS inverter must return an acknowledgement to the host. The only exception isthe broadcast message.This message does not require an acknowledgement.

The NAiS inverter sends two types of acknowledgements:

• Positive acknowledgement (ACK = 06hex), if:

– no faults occur during the block storage (longitudinal andlateral parity),

– a valid command (variable address) has been recognized,

– the variable value is within the permissible range,

– the variable value could have been changed.

• negative acknowlegdement (NAK = 15hex), if:

– one of the above listed conditions cannot be met.

• No acknowledgement, if:

– a broadcast message is send,

– the unit address is not correct.

Page 71: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 10

Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

C.1.2 RECEIVE

The command RECEIVE is to request parameter values of the NAiS inverters. The codenumbers of the requested parameter are transmitted with the RECEIVE message usingthe following structure:

EOT AD1 AD2 C1 C2 ENQ

The abbreviations have the following meanings:

EOT (04hex) End of the (previous) transmission

AD1, AD2 Logic unit address of the slave to be addressed

C1, C2 Code number (two ASCII characters) or extended addressing

ENQ (05hex) Station request

Structure and meaning of the code numbers (C1, C2) and the unit address (AD1, AD2)are described in the corresponding paragraphs of the chapter on SEND (� C – 12).

Message response

The NAiS inverter addressed via a RECEIVE message generates one of the followingresponses:

• The inverter could decode the request and is now sending therequested parameter value to the host.

STX C1 C2 V1 ... Vn ETX BCC

• The inverter could decode the request, however, a check–sum fault(parity fault) occured during transmission.

STX C1 C2 ? ETX BCC

• The inverter could not process the request because the codenumber does not exist.

STX C1 C2 EOT

The abbreviations have the following meanings:

STX (02hex) Start of text

C1, C2 Code number (two ASCII characters) or extendedaddressing

ETX (03hex) End of text

BCC Block–check character (00 ... FFhex)

? (3Fhex) ASCII character “?”

EOT (04hex) End of the (previous) transmission

Page 72: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module LECOM–A/B Protocol

C – 11Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

Structure and meaning of the block–check character (BCC) are described in thecorresponding paragraph of the chapter on SEND (� C – 9).

Examples for a RECEIVE message

� Example 1:

The current speed setpoint (code number C46) is to be read with the bus address 01 atthe inverter.

The host sends the following message:

EOT 0 1 4 6 ENQ

The inverter can response in three different ways:

STX 4 6 3 5 . 4 ETX BCC

Valid request: The current value of the parameter C46 is 35.4 (Hz)

or

STX 4 6 ? ETX BCC

Invalid request: A check–sum fault (parity fault) occured during data transmission

or

STX 4 6 EOT

Invalid request: The parameter C46 does not exist in this inverter.

� Example 2:

The current operating status (code number C68) is to be read with the bus address 25for the inverter. The operating status is bit–coded and transmitted in the hexadecimalformat.

The host sends the following message:

EOT 2 5 6 8 ENQ

The inverter responds:

STX 6 8 H 0 9 0 0 ETX BCC

Valid request: The current value of the parameter C68 is “0900”. This means:

� next page

Page 73: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 12

Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

TRIP status not active

Maximumcurrent

not reached

Quick stop not active

Pulse inhibitstatus

free

Display of thedirection ofrotation

CW rotation

Qmin status not active

Inverter enable enabled

Operating fault did not occur

Communicationerror

did not occur

C.1.3 SEND

The command SEND is to transmit data from the master to the slave. The master sendsa message with the following structure:

EOT AD1 AD2 STX C1 C2 V1 ... Vn ETX BCC

The abbreviations have the following meanings:

EOT (04hex) End of the (previous) transmission

AD1, AD2 Logic unit address of the slave to be addressed

STX (02hex) Start of text

C1, C2 Code number (two ASCII characters)

V1 to Vn Parameter value (n ASCII characters)

ETX (03hex) End of text

BCC Block–check character (00 ... FFhex)

In the text section of the message, which is embedded between the control charactersSTX and ETX, the code number (C1, C2) and the corresponding parameter value (V1to Vn) are transmitted to the slave.

� Example: SEND message

The maximum speed (code number C11) is to be set to the value 95.2 Hz via the busaddress 34 at the inverter.

The host must send the following SEND message:

EOT 3 4 STX 1 1 9 5 . 2 ETX BCC

Page 74: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module LECOM–A/B Protocol

C – 13Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

The inverter can respond with two different acknowledgements:

ACK

The command could not be processed correctly. The current value of the parameter C11is 95.2 Hz

or

NAK

The request could not been processed correctly. The parameter value was not changed.

C.1.4 BROADCAST/MULTICAST

In a bus network, the command BROADCAST is to address all participants or a groupof participants (multicast) at the same time. The structure of the BROADCAST messageis similar to the structure of the SEND message. The only exception is that it does notreturn an acknowledgement.

The participants can be selected via their unit addresses. The following unit addressesare reserved for a BROADCAST message:

Unit addresses Unit address of ASCII character(reserved) groups AD1 AD2

00 all “0” “0”

10 11 to 19 “1” “0”

20 21 to 29 “2” “0”

30 31 to 39 “3” “0”

40 41 to 49 “4” “0”

50 51 to 59 “5” “0”

60 61 to 69 “6” “0”

70 71 to 79 “7” “0”

80 81 to 89 “8” “0”

90 91 to 99 “9” “0”

� Example: BROADCAST message

All inverters are to be stopped when setting inverter enable (code number C40 = 0).

The host sends the following BROADCAST message:

EOT 0 0 STX 4 0 0 ETX BCC

The inverters do not return an acknowledgement.

Page 75: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleLECOM–A/B Protocol

C – 14

Matsushita Electric Works (Europe) AG

C.1 LECOM–A/B Protocol

C.1.5 Monitoring of the Slave Response

The master monitors the selected slave. The slave must return a response within adefined time.Under the following circumstances the slave does not return a response tothe master (time out):

• The unit address could not be recognized

• A fault (e.g. parity fault) had been detected in one or severalcharacters, including the character ”ENQ”

• The transmission path is faulty

• A BROADCAST message had been sent

• The hardware does not work properly

If the master does not receive a response within a defined period of time, thetransmission is tried again. The number of repetitions is limited.

The monitoring time of the master should be approx. twice as long as the maximumrespond time.

C.1.6 Transmission Faults

After a transmission fault, the master can read C0068 and evaluate the communicationerror in bit 4…7 .

Page 76: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Appendix D

List of Abbreviations

Page 77: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleList of Abbreviations

D – 2

Matsushita Electric Works (Europe) AG

Page 78: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module List of Abbreviations

D – 3Matsushita Electric Works (Europe) AG

D.1 List of Abbreviations

D.1 List of Abbreviations

Abbreviation Meaning

ACK Response for positive acknowledgement of the inverter

ASCII American Standard Code for Information Interchange: 7 bit code with one free parity bit

Inv. inhibit Inverter inhibit

Inv. enable Inverter enable

DC brake DC–injection brake

EMC Electromagnetic compatibility

fdmin; fdmax Minimum/maximum field frequency

Imax Current limit

IMP Pulse inhibit

JOG (JOG1, JOG2,JOG3)

Fixed speed or input for activation of the fixed speed

LECOM VF–CE communication

LECOM–A Communication medium via RS232C interface and LECOM protocol

LECOM–B Communication medium via RS485 interface and LECOM protocol

NAK Response for negative acknowledgement of the inverter

PAR Parameter set changeover

PC Personal computer

PLC Programmable logic inverter, e. g. Matsushita NAiS FP0

Qmin Frequency threshold

QSP Quick stop

RFG Ramp–function generator; setpoint integrator

RS232 Interface standard

RS485 Interface standard

RxD Pin name LED (receive display)

SW Software

TRIP Operation fault

TxD Pin name LED (transmission display)

VD LECOM format

VGmax DC–bus overvoltage

VH LECOM format

VS LECOM format

Page 79: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleList of Abbreviations

D – 4

Matsushita Electric Works (Europe) AG

D.1 List of Abbreviations

Page 80: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Appendix E

Glossary

Page 81: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleGlossary

E – 2

Matsushita Electric Works (Europe) AG

Page 82: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Glossary

E – 3Matsushita Electric Works (Europe) AG

E.1 Glossary

E.1 Glossary

Technical term Meaning

Baud rate Transmission speed of data in bit/s

Broadcast Message to all inverters

Code For input and display (access) of parameter values.

Code number Addressing of variables according to the format “code–subcode” (Cxxxx–xx). All variablescan be accessed via the code names.

Fieldbus For data exchange between superimposed controls and positioning controls.

Host PC or PLC

Icon Sign or symbol with an unambiguous message.

Interface converter(C–Net)

Additional module to adapt data transmissions via RS232C/RS422 interface cables toRS485 (and vice versa)

Multicast Message to certain inverter groups

Nibble One byte consists of two nibbles:� LOW nibble (bit 0 to 3)� HIGH nibble (bit 4 to 7)

Protocol LECOM–A/B protocol

Pulse inhibit The output of the power stage is inhibited because the inverter is inhibited, the faultmessage TRIP is displayed or an overvoltage or undervoltage is applied.

Remaining hazards Hazards which cannot be eliminated by design

Subcode Defines the table position of a code

Table position Some variables may consist of more than one value. If this is the case, the values areentered subsequently. They are accessed via the subcode using the same code.

Page 83: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication ModuleGlossary

E – 4

Matsushita Electric Works (Europe) AG

E.1 Glossary

Page 84: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

I – 1Matsushita Electric Works (Europe) AG

Index

A

Accessoriesfor RS232 (LECOM–A), A – 3for RS485 (LECOM–B), A – 4

Acknowledgement, C – 9Negative, 4 – 4Positive, 4 – 4

AddressingCode bank addressing, C – 4Extended addressing, C – 5Standard addressing, C – 3via input selection, C – 5

Application conditions, 1 – 4

B

Basic insulation, 2 – 7

Baud rate, 1 – 4, 3 – 3

BCC. See Block–check character

Block–check character, C – 9

BROADCAST, C – 13Example, C – 13

C

C–Net adapter, A – 4

Character format, 1 – 4

Code bank, B – 7, C – 4

Code table, B – 3

Commissioning, 3 – 1

Communication media, 1 – 4, 1 – 5

Communication module, Labelling, a

Communication monitoring, 4 – 8

Communication times, 1 – 7

Connection9–pole SubD female plug, 2 – 3Connections of the communication

module, 2 – 3

Plug–in terminal (2–pole), 2 – 4Plug–in terminal (4–pole), 2 – 4

Control word, 4 – 5, B – 5

Current consumption, 1 – 5

D

Dimensions, 1 – 6

Disposal, b

E

Electrical data. See Rated data

Electrical installation, 2 – 6

Electrical isolation, 2 – 7

Extended addressing, C – 5

F

Fault elimination, 4 – 1

Fault numbers, B – 8

Frequency setpoint, 4 – 5, B – 3

G

Glossary, E – 3

Group formation, of inverters, 4 – 5

Page 85: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Index RS232C/RS485 Communication Module

Matsushita Electric Works (Europe) AGI – 2

I

Initial switch–on. See Installation

Input selection, C – 5

Installation, 2 – 1Electrical, 2 – 6Mechanical, 2 – 5Wiring to a host, 2 – 7Wiring via RS232C (LECOM–A), 2 – 8Wiring via RS485 (LECOM–B), 2 – 10

Intended use, a

Interface, Shorten response time, 4 – 7

Inverter, Group drives, 4 – 5

Inverter address, 3 – 3, B – 3

Inverter enable, B – 3

Inverter inhibit, 4 – 5

Items supplied, Preface – 1

L

LECOM, Protocol, C – 3

LECOM baud rate. See Baud rate

LECOM code bank. See Code bank

LECOM inverter address. See Inverteraddress

LECOM–A/B protocol, 4 – 5, C – 3

Liability, b

ListAbbreviations, D – 3Technical terms. See Glossary

List of abbreviations, D – 3

List of technical terms. See Glossary

M

Manufacturer, a

Message response, C – 9

Message time, 1 – 7

Monitoring of the slave response, C – 14

MULTICAST, C – 13

N

Network topologyLine, 2 – 10Point–to–point, 2 – 8

O

Operating mode, 4 – 5, B – 3

Operating status, B – 4

Operator, c

P

Parameter, Name, B – 3

Parameter sets, 4 – 4

Parameter setting, 4 – 1

Parameter value, C – 6in the ASCII decimal format, C – 7in the ASCII hexadecimal format, C –

7in the octet string format, C – 8in the string format, C – 8

ParametersControl word (C0135), 4 – 5Frequency setpoint (C0046), 4 – 5Individual, 4 – 5Inverter inhibit (C040), 4 – 5Operating mode (C0001), 4 – 5Unit address (C0009), 4 – 5

PC cable, A – 3

PLC cable, A – 3

Personnel, Qualified, c

Plug–in terminal for external supply,Connections, 2 – 4

Plug–in terminal for LECOM–B,Connections, 2 – 4

Processing time, 1 – 7

Protocol, C – 3See also LECOM–A/B protocolCode numbers, C – 3

Page 86: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

RS232C/RS485 Communication Module Index

I – 3Matsushita Electric Works (Europe) AG

Q

Quick stop, 3 – 4

R

Rated data, 1 – 5

RECEIVE, C – 10Examples, C – 11Message response, C – 10

RS232C (LECOM–A), Features, 2 – 8

RS232C/RS485 communication moduleConnections, 2 – 3Technical data, 1 – 1

RS485 (LECOM–B), Features, 2 – 10

RxD–LED, 2 – 3

S

Safety information, c

SEND, C – 12Example, C – 12

Slave response, C – 14

Standard addressing, C – 3

Status word, B – 6

SubD male plug (9–pole), Connections, 2– 3

Supply voltageExternal, 1 – 5, 2 – 6Internal, 2 – 6

T

Technical data, 1 – 1Dimensions, 1 – 6General data and application

conditions, 1 – 4Module features, 1 – 3Rated data, 1 – 5

Terminology, Preface – 1

Transmission faults, C – 14

Transmission speed. See Baud rate

TRIP reset, B – 3

Troubleshooting, 4 – 1

TxD–LED, 2 – 3

U

Unit address, 4 – 5, C – 8

V

Vcc–LED, 2 – 3

W

Warranty, b

Wiringto a host, 2 – 7via RS232C (LECOM–A), 2 – 8via RS485 (LECOM–B), 2 – 10

Page 87: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

Index RS232C/RS485 Communication Module

Matsushita Electric Works (Europe) AGI – 4

Page 88: ACGM0181END Communication Module - powerwarelit.powerware.com/ll_download.asp?file=XACG-M181end.pdf · optionally attached to the NAiS VF–C inverter series. The RS232C/RS485 communication

COPYRIGHT � 2000 All Rights Reserved ARCT1F0000ABC V1.x 12/99

Specifications are subject to change without notice. Printed in Europe

� Austria Matsushita Electric Works Austria GmbHStojanstraße 12, 2344 Maria Enzersdorf, Austria, Tel. (02236) 2 68 46, Fax (02236) 46133, http://www.matsushita.at

� Benelux Matsushita Electric Works Benelux B. V.De Rijn 4, (Postbus 211), 5684 PJ Best, (5680 AE Best), Netherlands, Tel. (0499) 37 2727, Fax (0499) 372185, http://www.matsushita.nl

� France Matsushita Electric Works France S.A.R.L.B.P. 44, 91371 Verrières le Buisson CEDEX, France, Tel. 01 60 13 57 57, Fax 01 60 13 57 58, http://www.matsushita–france.fr

� Germany Matsushita Electric Works Deutschland GmbHRudolf–Diesel–Ring 2, 83607 Holzkirchen, Germany, Tel. (08024) 648–0, Fax (08024) 648–555, http://www.matsushita.de

� Ireland Matsushita Electric Works Ltd., Irish Branch OfficeWaverley, Old Naas Road, Bluebell, Dublin 12, Republic of Ireland, Tel. (01) 460 09 69, Fax (01) 460 11 31

� Italy Matsushita Electric Works Italia s.r.l.Via del Commercio 3–5 (Z.I. Ferlina), 37012 Bussolengo (VR), Italy, Tel. (045) 675 27 11, Fax (045) 670 04 44, http://www.matsushita.it

� Portugal Matsushita Electric Works Portugal, Portuguese Branch OfficeAvda 25 de Abril, Edificio Alvorada 5º E, 2750 Cascais, Portugal, Tel. (351) 1482 82 66, Fax (351) 1482 74 21

� Scandinavia Matsushita Electric Works Scandinavia ABSjöängsvägen 10, 19272 Sollentuna, Sweden, Tel. +46 8 59 47 66 80, Fax (+46) 8 59 47 66 90, http://www.mac–europe.com

� Spain Matsushita Electric Works España S.A.Parque Empresarial Barajas, San Severo, 20, 28042 Madrid, Spain, Tel. (91) 329 38 75, Fax (91) 329 29 76

� Switzerland Matsushita Electric Works Schweiz AGGrundstrasse 8, 6343 Rotkreuz, Switzerland, Tel. (041) 799 70 50, Fax (041) 799 70 55, http://www.matsushita.ch

� United Kingdom Matsushita Electric Works UK Ltd.Sunrise Parkway, Linford Wood East, Milton Keynes, MK14 6LF, England, Tel. (01908) 231 555, Fax (01908) 231 599, http://www.matsushita.co.uk

�������������

� USA Aromat Corporation Head Office USA629 Central Avenue, New Providence, N.J. 07974, USA, Tel. 1–908–464–3550, Fax 1–908–464–8513, http://www.aromat.com

� China Matsushita Electric Works, Ltd. China Office2013, Beijing Fortune, Building 5, Dong San Huan Bei Lu, Chaoyang District, Beijing, China, Tel. 86–10–6590–8646, Fax 86–10–6590–8647

� Hong Kong Matsushita Electric Works Ltd. Hong KongRm1601, 16/F, Tower 2, The Gateway, 25 Canton Road, Tsimshatsui, Kowloon, Hong Kong, Tel. (852) 2956–3118, Fax (852) 2956–0398

� Japan Matsushita Electric Works Ltd. Automation Controls Group1048 Kadoma, Kadoma–shi, Osaka 571–8686, Japan, Tel. 06–6908–1050, Fax 06–6908–5781, http://www.mew.co.jp/e–acg/

� Singapore Matsushita Electric Works Pte. Ltd. (Asia Pacific)101 Thomson Road, #25–03/05, United Square, Singapore 307591,Tel. (65) 255–5473, Fax (65) 253–5689

Europe

North & South America

Asia

North America Europe Asia Pacific China JapanMatsushita Electric Works (Asia Pacific)

Matsushita Electric Works Group

Matsushita Electric Works

Matsushita Electric Works Ltd. Automation ControlsGroup

AromatCorporation