DESIGN OF FOOTINGS
As per ACI 318-02
FOOTING F-1
column size (in) 135 x 135
Fy (K) (unfactored) 1281.00
M (K.ft) (unfactored) 10972.00
factored Fy: (K) fc' (psi): 3,000 P= 1281 k
Mu: (K-ft) fy (psi): 60,000 M= 10972 k-ft
ew=M/P (in) 102.8 O.K A= 1369 sft
Z= 8442.17 ft3
q net 2865.2 psf q induced= 2235 psf
Area 'A' reqd (for axial load): 447 sft -21.98 %
Footing area 'A' selected 1369 sft
footing size (ft x ft): 37 x 37 calculations for punching shear
(short side, 'a') (long side,'b') let d: 8.75
qu induced 0.00 ksf force causing (K) force resisting (K)
h' 11.25 in - 827
let 'h' 15 in (Fy fact-qu xAº) (Φ.4√fc'.bºd)
d' (punch shear criteria) 12.5 in
pressure check for selected area against (axial force+bending)
% increment in "q"=
One-way shear check:
Vub (K): 0 Shear cap (K): 456
(Φ.2√fc'.a.d) O.K
Vua (K): 0 Shear cap (K): 456
(Φ.2√fc'.a.d) O.K
Reinforcement:
Longer side: Shorter side
Mub (k-ft): (qu*(a/2-col/2)^2/2) 0.00 Mua (k-ft): 0.00
steel ratio:ρ=(Mu/φbd^2*fy) - steel ratio: -
min steel ratio:ρmin=(200/fy) 0.0033 min steel ratio: 0.0033
selected value:ρ sel= 0.0033 selected value: 0.0033
As (sq.in/ft)=(ρbd) 0.50 As (sq.in/ft) 0.50
As shown on drawings As shown on drawings