Air Circuit Breakers
Motors | Energy | Automation | Coatings
www.weg.net
Air Circuit Breaker ABW2
ABW Air Circuit Breaker
Designed for the protection of high power electrical circuits, the ABW Air Circuit Breakers are state of the art in terms of technology and design.The characteristics that make this line stand out, include:
Modular design, with only 3 frames:
ABW16 ABW20...32
ABW40...50
Wide range of current adjustment:
High short circuit interruption capacity, with Ics = 100% Icu in all the line
Icu=Ics @ 480V
ABW16 65 kA
ABW20...32 85 kA
ABW40...50
Available in two installation versions: FIXED and WITHDRAWABLE
Full line of accessories
ABW16 384...1600A
ABW20 480...2000A
ABW25 600...2500A
ABW32 768...3200A
ABW40 480...4000A
ABW50 600...5000A
Microprocessed electronic protection units, with LSI(G)1 functions and the possibility of network communication.
100 kA
1) Further details on page 13.
www.weg.net
Air Circuit Breaker ABW 3
ABW Air Circuit Breaker
Withdrawable Rack(withdrawable
version only)
Arc extinction chambersControl Terminals
Suspension slots
Protection Unit
Spring loading lever
OffButton
On Button
Status IndicatorOn / Off
Spring Charge Indicator – Charged / Not charged
Opening for withdrawing bar (withdrawable version only)Position locked by padlock (withdrawable version only)
Position Indicator – Inserted / Test / Withdrawn (withdrawable version only)
OperationsCounter
Withdrawing rail (withdrawable version only)
Constructive Characteristics
www.weg.net
Air Circuit Breaker ABW4
Applications
ABW16 ABW20 ABW25 ABW32 ABW40 ABW50
Max. Rated Current - In max. (A) (40°C) 1600 2000 2500 3200 4000 5000
Rated Operating Voltage - Ue (V) 690
Rated Insulation Voltage - Ui (V) 1000
Impulse Voltage - Uimp (kV) 8
Frequency (Hz) 50 / 60
Number of poles 3
Versions Fixed and Withdrawable
Protection Units Electronic
Rated ultimate short-circuit breaking capacity
220/380/415V 65 85 100
440V 65 85 100
500V 65 85 100
600V 50 65 85
690V 50 50 50
Rated service short-circuit breaking capacity
220/380/415V 65 85 100
440V 65 85 100
500V 65 85 100
600V 50 65 85
690V 50 50 50
Short circuit supportability - Icw (kA)
1s 65 65 85
2s 60 60 65
3s 50 60 65
Short circuit establishment capacity (peak values) - Icm (kA)
220/380/415V 143 187 220
440V 143 187 220
500V 143 187 220
600V 105 143 187
690V 105 105 105
Use category B
Operating time (ms)Opening ≤ 40
Closing ≤ 80
Mechanical life (nº of operations) 12000 10000
Electrical life (nº of operations) 3000
Altitude (m) ≤ 2000 (1)
Ambient temperatureOperation -5...40°C (2)
Storage -20...60°C
Thermal power dissipation at rated current (W) 52 160 250 410 960 1500
Weight (kg)Withdrawable (3) 64 92 93 95 240 240
Fixed 41 60 61 63 115 115
Connection terminalsWithdrawable Horizontal Vertical
Fixed Horizontal Horizontal
Dimensions Withdrawable 339x435x379 474x435x379 961x459x379
W x H x D (mm) Fixed 315x410x295 450x410x295 840x410x295
(1) For installation above 2000m from sea level, please consider derating factors on page 20.(2) For ambient temperature above 40°C, check maximum rated current values in the table on page 20.(3) Include withdrawable rack.
www.weg.net
Air Circuit Breaker ABW 5
ABW16D3F-022-A-116-0000
WEG Air Circuit Breaker
Max. Rated Current
16 – 1600A20 – 2000A25 – 2500A32 – 3200A40 – 4000A50 – 5000A
Motorized Operation0 – Without Mot. Operation1 – 110...120 Vac/dc2 – 220...240 Vac/dc3 – 125 Vdc
TypeD – Cir. Breaker I – Interruptor
N° of Poles3 – 3 Poles
VersionF – FixedE – Withdrawable
Auxiliary Contacts
A – 5NO+5NC
Opening Coil2 – 110...240 Vac/dc
Closing Coil2 – 110...240 Vac/dc
Protection UnitStandard Units:116 – LSI (60Hz) for ABW16...32216 – LSIG (60Hz) for ABW40...50
Optional Units:115 – LSI (50Hz) for ABW16...32215 – LSIG (50Hz) for ABW40...50316 – LSIG (60Hz) + communica-tion for ABW16...50315 – LSIG (50Hz) + communica-tion for ABW16...50000 – Without Protection Unit
Accessories supplied as standard for all line: Accessories supplied as optionals:
g Motorized Operation
g Under Voltage Coil
g Capacitive trigger unit
g Key lock
g Key interlock
g Door Frame
g Transparent Cover
g Mechanical Interlock
g Door Interlock
g Position Auxiliary Contacts
g Vertical Terminals
Under Voltage Coil00 -Without Under Voltage Coil11 - 110 Vac, instantaneous12 - 220 Vac, instantaneous13 - 380 Vac, instantaneous14 - 460 Vac, instantaneous51 - 110 Vac, timed (3s)52 - 220 Vac, timed (3s)53 - 380 Vac, timed (3s)54 - 460 Vac, timed (3s)
Key lock0 - Without key lock1- Key lock(for 1 circuit breaker)3- Key interlock (for 3 circuit breakers)
Mechanical Interlock0 - Without Mechanical Interlock1- Mechanical Interlock for 2 circuit breakers2- Door interlock
g Auxiliary Contacts (5NO+5NC)
g Alarm Contacts
g Opening Coil 110...240 Vac/dc
g Closing Coil 110...240 Vac/dc
g Operations Counter
g Insulating Plates
g Position Locking with Padlock
(padlock not included) – withdrawable version only
g Position Indicator (Inserted /Test/ Withdrawn) –
withdrawable version only
Codification
www.weg.net
Air Circuit Breaker ABW6
Operating System
ABW air circuit breakers operate through a spring system, which can be manually charged through a front lever, or electrically through a motor (supplied as an accessory).
With the springs charged, situation in which the charge indicador shows “CHARGED”, the circuit breaker can be operated locally using the On and Off buttons.
OFF BUTTON
ON / OFFINDICATOR
SPRING CHARGE INDICATOR
CHARGE LEVERON BUTTON
In relation to the installation version, the circuit breakers can be installed as fixed or as withdrawable. The withdrawable version is indicated for applications where eventual replacement or maintenance must be done in the shortest time possible.These curcuit breakers can be positioned at three distinct points in the withdrawable rack:
Inserted: in this position both the power and control circuits are connected. The position indicator shows “CONNECTED”.
Test: position in which the control circuits are connected. The indicator shows “TEST”.
Withdrawn: both circuits are disconnected. The indicator shows “DISCONNECTED”.
Position Indicator
Remote operation is also possible through the closing and opening coils installed inside the circuit breaker. The closing coil is equipped with an “anti-pumping” electronic circuit, which prevents successive re-connections in a single command.
Another feature of the circuit breaker is the indicator on the front showing the status of the product: ON or OFF.
www.weg.net
Air Circuit Breaker ABW 7
These coils allow remote closing of the circuit breaker through electrical control. This remote control is valid only if the springs of the operating mechanism are charged.Supplied as standard in all circuit breakers.
Auxiliary Contacts
Show circuit breaker status – On or Off.Supplied as standard in all circuit breakers.
Configuration 5NO + 5NC
Switch capacity (A)
Operating Voltage Resistive load Inductive load
125 Vac 10 10
250 Vac 10 10
460 Vac 5 2
30 Vdc 10 6
125 Vdc 0.6 0.6
250 Vdc 0.3 0.3
These contacts are incorporated into the protection units and indicate trigger occurrence for any of the protection functions.
0.85...1.1 x Un
Consumption (A)
Operating voltage Energization Nominal Operation
110...120 Vac/dc 2 1
220...240 Vac/dc 3 1.3
125 Vdc 2.3 1
Closing time (ms) ≤ 80
“Anti-pumping” characteristic Yes, through electronic circuit
Minimum supply time for operation (ms) 100
Supply Voltage Reference
110...220 Vac/dc ABW-CC 110/220V
Configuration 2NO (generic) + 4NO (individual)
Switch capacity (A)
Operating Voltage Switch Capacity
250 Vac 5
380 Vac 3
30 Vdc 5
125 Vdc 1
Minimum application levels 5 Vdc / 10 mA
Alarm Contacts
Closing coil
Accessories
www.weg.net
Air Circuit Breaker ABW8
Opening Coil
These coils allow remote opening of the circuit breaker through electric control.Supplied as standard in all circuit breakers.
0,70...1,1 x Un
Consumption (A) 2
Operating Voltage Energization Nominal Operation
110...120 Vac/dc 2 1
220...240 Vac/dc 3 1.3
125 Vdc 2.3 1
Closing time (ms) ≤ 40
Supply Voltage Reference
110...220 Vac/dc ABW-ST 110/220V
Motorized Operation
Motorized operation is used for automatic charging of the circuit breaker springs operating mechanism. Its operation begins immediately after curcuit breaker opening and at the end of this process an auxiliary contact indicates that the springs are charged.Even with the motorized operation installed, it is still possible to charge the springs manually through the front rod.
0.85...1.1 x Un
Consumption (A) 2
Operating Voltage Energization Nominal Operation
110...120 Vac/dc 7 3.5
220...240 Vac/dc 7 3.5
125 Vdc 7 3.5
Operating time (to charge springs) (s) ≤ 5
Charged Spring Auxiliary Contact
Supplied incorporated into the motorized operation.
Supply Voltage Reference
110 Vac/dc ABW-M 110V
220 Vac/dc ABW-M 220V
125 Vdc ABW-M 125VDC
Operating Voltage Resistive load Inductive load
Switch capacity (A)
120...125 Vac 10 10
240...250 Vac 10 10
460 Vac 5 .,5
30 Vdc 10 10
125 Vdc 10 6
250 Vdc 3 1.5
Accessories
www.weg.net
Air Circuit Breaker ABW 9
Under Voltage Module
Power Supply
Trip Button C NO NC
Auxiliary Contacts
Circuit Breaker
Under Voltage Coil
Under Voltage CoilAutomatically disconnects the circuit breaker in cases of undervoltage or phase loss in control circuit. It consists of a coil and a control module, available in two versions: instantaneous trip or delayed.
Coil ABW-UVT COIL
Supply VoltageReferences
(instantaneous performance)References
(delayed performance)
Module 110 Vac ABW-UVT1 110VAC ABW-UVT5 110VAC
Module 220 Vac ABW-UVT1 220VAC ABW-UVT5 220VAC
Module 380 Vac ABW-UVT1 380VAC ABW-UVT5 380VAC
Module 460 Vac ABW-UVT1 460VAC ABW-UVT5 460VAC
Pick-up voltage 0.85...1.1 x Un
Drop-out voltage 0.3...0.7 x Un
Performance time (instantaneous) ≤200ms
Operation time (with delay) 3s
Connection diagram - Instantaneous version
Connection diagram - Delayed version
Accessories
UC+ UC-
Under Voltage Module
Power Supply
Trip Button
Circuit Breaker
Under Voltage Coil
www.weg.net
Air Circuit Breaker ABW10
Position Auxiliary Contacts
Enables remote indication of circuit breaker position inside withdrawable rack.
Key interlock
Circuit Breakers Reference
ABW 16...50 (withdrawable) ABW-PS4
Configuration2NO for INSERTED position
1NO for TEST position1NO for WITHDRAWN position
Resistive load Inductive load
Switch capacity (A)
125 Vac 10 10
250 Vac 10 10
460 Vac 5 2.5
30 Vdc 10 10
125 Vdc 10 6
250 Vdc 3 1.5
Used to interlock 3 circuit breakers in the following configuration:
Circuit Breakers Reference
ABW 16...50 ABW-KI
ABW1 ABW2 ABW3
On Off On
On On Off
Off On On
Vertical Terminals
Used to convert the circuit breaker terminals to the vertical position. They are supplied in individual pieces.
Circuit breakers Terminals References
ABW16 Upper/Lower ABW-VT16
ABW20,25,40,50 Upper ABW-VT25S
ABW20,25,40,50 Lower ABW-VT25I
ABW32 Upper ABW-VT32S
ABW32 Lower ABW-VT32I
Accessories
www.weg.net
Air Circuit Breaker ABW 11
AccessoriesCapacitive Trigger Unit
This device provides the possibility of turning off the circuit breaker in case of control voltage loss. It acts through the discharge of a capacitor over the opening coil, and the stand-alone running period is indicated in the table below. It comes with a capacitor charge signal light and a button to discharge it. Panel door installation.
Supply Voltage References
100...110 Vac ABW-CTD 100-110VAC
200...220 Vac ABW-CTD 200-220VAC
Operating voltage 0.85...1.1 x Un
Capacitor charging time (s) ≤ 5
Stand-alone Running period (minutes)3 (ABW-CTD 100-110VAC)
2 (ABW-CTD 200-220VAC)
Connection diagram
Capacitive trigger unit
AC (input)
OFF Button
Circuit Breaker
Opening Coil
SW1To discharge the capacitor
DC (Output)
www.weg.net
Air Circuit Breaker ABW12
Circuit Breakers References
ABW16 ABW-DF16
ABW20...50 ABW-DF32
Protection Degree IP 3x
Key lock
Circuit breaker locked in off position.
Circuit Breakers Reference
ABW16...50 ABW-KL
Door frame
Finish frame for panel door.
Transparent cover
Curcuit breaker can be viewed without having to open the panel door.
Circuit Breakers References
ABW16 ABW-DC16
ABW20...50 ABW-DC32
Protection Degree IP 5x
Mechanical Interlock
Enables two circuit breakers to be connected simultaneously through flexilbe cables.
Door Interlock
Prevents panel door from being opened when circuit breaker is on.
Circuit Breakers Reference
ABW16...50 ABW-DI
Cable length (m) 1.6
Accessories
Circuit Breakers Reference
ABW16...50 ABW-MI1
Cable length (m) 1.6
www.weg.net
Air Circuit Breaker ABW 13
Accessories
On ABW air circuit breakers, protection against over currents is performed through the ABW-OCR electronic protection units. The ABW-OCR116 is supplied as standard for the ABW16...32 circuit breakers and offers protection against overload (L), timed short circuit (S) and instantaneous short circuit (I), adjusted through selectors on the front. The ABW-OCR216 unit is supplied as standard for ABW40...50 circuit breakers and beside the protections listed above, provides protection against Ground loss (G). Supplied as an option, the ABW-OCR316 unit further enables network communication.
ABW-OCR116 ABW-OCR115 ABW-OCR216 ABW-OCR215 ABW-OCR316 ABW-OCR315
For circuit breakers ABW16...32 ABW40...50 ABW16...50
Supply voltage 110...220 Vac/dc 110...220 Vac/dc 110...220 Vac/dc
Consumption 5 VA 5 VA 5 VA
Supply frequency 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz
Protection functions
L - Overload
S - Short circuit (timed)
I - Short circuit (instantaneous)
G - Ground loss -
Trigger pre-alarm
Discrimination / Indication of trigger cause
Events record (losses)
Nº of storage records 10 10 10
Events sequence -
Loss current value information
Performance time information
Parameterization
Front adjustment knobs - -
Display+navigation keys -
Parameterization password -
Instantaneous current by phase indication
Self-diagnosis function
Test function (trigger, auxiliary contacts and LEDs)
Network communication - -
Door - - RS485
Protocol - - DNP 3.0
Transmission rate - - 9600 bps
(4) Except for protection function I (instantaneous short circuit).(5) The display enables the adjusted values to be viewed on the SETTING menu.
ProtectionUnits
(4) (4) (4)
(5)
www.weg.net
Air Circuit Breaker ABW14
Technical Characteristics
UABW-OCR116
The characteristics of the ABW-OCR116 protection unit meet all requirements for most systems and applications. This unit offers the main protections (L, S and I) and has a wide current and trigger time adjustment range. It is standard supplied for ABW16...32. circuit breakers
Display
Its initial screen displays the instantaneous currents by phase. Other information can also be accessed through other menus.
Signalling LEDs
Indicates general status of circuit breaker.
LED FUNCTION
RUN Indicates circuit breaker on
LTD Indicates trigger by overload (L)
STD Indicates trigger by timed short circuit (S)
INST Indicates trigger by instantaneous short circuit (I)
PAL Indicates pre-alarm
PICK UP Indicates start of trigger timing
Navigation keys
Selector switches for protection functions
Parameters Function / Adjustment Ranges
InRated Current (0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0) x In max.
IcTrigger current by overload (protection function L) (0.6 - 0.7 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0) x In
LTDCurrent delay time Ic(15 - 30 - 60 - 120 - 240 - 480)s @ 1.5 x Ic [Tolerance: ±10%]
Is
Trigger current by timed short circuit (Protection function S)(2 - 3 - 4 - 6 - 8 - 10 - OFF) x In [Tolerance: ±15%]
STDCurrent delay time Is(0.05 - 0.1 - 0.2 - 0.3 - 0.4 - 0.5)s @ 10 x In [Tolerance: ±15%]
li
Trigger current by instantaneous short circuit (protection function I)(4 - 6 - 8 - 10 - 12 - 16 - OFF) x In [Tolerance: ±20%]
lpPre-alarm current(0.7 - 0.8 - 0.9 - 0.95 - 1.0 - OFF) x Ic [Tolerance: ±10%]
Used for navigating among the available menus.
www.weg.net
Air Circuit Breaker ABW 15
Protection Units
Characteristic Curves - ABW-OCR116
Current (%)
Per
form
ance
Tim
e (%
)
Pre-alarm current Ip
Time LTD (s)
Current Is
Current Is
Current Is
Time STD (s)
Current Ii
www.weg.net
Air Circuit Breaker ABW16
Connection Diagram - ABW-OCR116
Protection Units
T0~T
5 A
larm
Con
tact
s (in
divi
dual
s)R
+ R
2-P
rote
ctio
n U
nit P
ower
Sup
ply
M+
M-
Mot
oriz
ed O
pera
tion
T0C
omm
onA
l1+
Al1
-A
larm
con
tact
s (g
ener
ics)
TS+
TS
-C
harg
ed S
prin
gs A
uxilia
ry C
onta
cts
T1-
Func
tion
L (o
verlo
ad)
Al2
+ A
l2-
B6~
B10
Aux
iliary
Con
tact
s (N
C)
T2-
Func
tion
S (t
imed
sho
rt-ci
rcui
t)U
+ U
-U
nder
Vol
tage
Coi
l (*)
A1~
A5
Aux
iliary
Con
tact
s (N
O)
T3Fu
nctio
n I (
inst
anta
neou
s sh
ort-
circ
uit)
S+
S-
Ope
ning
Coi
lC
LP
ositi
on A
uxilia
ry C
onta
cts
(with
draw
able
C
ircui
t Bre
aker
onl
y)
T5P
re-a
larm
CC
+ C
C-
Clo
sing
Coi
l
(*) C
onne
ct o
n un
derv
olta
ge m
odul
e -
see
page
9
PR
OTE
CTI
ON
UN
IT
www.weg.net
Air Circuit Breaker ABW 17
ABW-OCR216 / 316
Protection Units
These units were developed to meet the demands of appplications and electrical systems with high technical requirements.In addition to the main protection functions (L, S and I), they offer protection against Ground loss (G) and have a greater trigger current and time adjustment range.The ABW-OCR316 model is further equipped with a RS485 communication door which, through DNP3.0 communication protocol, enables the monitoring of instantaneous currents, circuit breaker status and the occurrence of events.The ABW-OCR216 unit is supplied as standard for the ABW40...50 circuit breakers, while the ABW-OCR316 unit is supplied as an option for the entire line.
Technical Characteristics
Display
Its initial screen displays the instantaneous currents by phase. Other information can also be accessed through other menus.
Navigation keys
Used for navigating among the available menus and protection function adjustment.
Parameter Function / Adjustment Range
InRated current (0.2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0) x In max.
Ic
Trigger current by overload(protection function L) (0.6 - 0.65 - 0.7 - 0.75 - 0.8 - 0.85 - 0.9 - 0.95 - 1.0) x In
LTDCurrent delay time Ic(15 - 20 - 25 - 30 ... 465 - 470 - 475 - 480 - NO)s @ 1.5 x Ic [Tolerance: ±10%]
Is
Trigger current by timed short circuit (Protection function S)(1.5 - 2 - 2.5 - 3.0 ... 8.5 - 9 - 9.5- 10 - NO) x In [Tolerance: ±15%]
STD
Current delay time Is(0,05 - 0,06 - 0,07 ... 0,48 - 0,49 - 0,5)s @ IO x In [Tolerance: ±15%]
li
Trigger current by instantaneous short circuit (protection function I)ABW16...40: (2 - 3 - 4 ... 14 - 15 - 16 - NO) x In [Tolerance: ±15%]ABW50: (2 - 3 - 4 ... 10 - 11 - 12 - NO) x In [Tolerance: ±15%]
lpPre-alarm current(0.7 - 0.8 - 0.9 - 1.0) x Ic [Tolerance: ±10%]
Ig
Ground loss current(0,2 - 0.3 - 0.4 - 0.5 - 0.6 - 0.7 - 0.8 - 0.9 - 1.0 - NO) x .n max. [Tolerance: ±20%]
GTD Current delay time Ig(0.1 - 0.2 - 0.3 ... 2.8 - 2.9 - 3.0)s [Tolerance: ±20%]
LED FUNCTION
RUN Indicates circuit breaker on
PICK UP Indicates start of trigger timing
FAULT Indicates trigger
Signalling LEDs
Indicates general status of circuit breaker.
www.weg.net
Air Circuit Breaker ABW18
Protection Units
Characteristic Curves - ABW - OCR 216/316
Current (%)
Per
form
ance
tim
e (%
)
Pre-alarm current Ip Time LTD (s)
Time GTD (s) Current Is
Current Ig
Time STD (s)
Current Ii
www.weg.net
Air Circuit Breaker ABW 19
Connection diagram - ABW-OCR216/316
Protection Units
T0~T
5 A
larm
Con
tact
s (in
divi
dual
s)R
+ R
2-P
rote
ctio
n U
nit P
ower
Sup
ply
M+
M-
Mot
oriz
ed O
pera
tion
T0C
omm
onA
l1+
Al1
-A
larm
con
tact
s (g
ener
ics)
TS+
TS
-C
harg
ed S
prin
gs A
uxilia
ry C
onta
cts
T2Fu
nctio
n L
(ove
rload
)A
l2+
Al2
-B
6~B
10A
uxilia
ry C
onta
cts
(NC
)
Func
tion
S (t
imed
sho
rt-ci
rcui
t)U
+ U
-U
nder
Vol
tage
Coi
l (*)
A1~
A5
Aux
iliary
Con
tact
s (N
O)
T3Fu
nctio
n I (
inst
anta
neou
s sh
ort-
circ
uit)
S+
S-
Ope
ning
Coi
lC
LP
ositi
on A
uxilia
ry C
onta
cts
(with
draw
able
C
ircui
t Bre
aker
onl
y)
T4Fu
nctio
n G
(Gro
und
Loss
)C
C+
CC
-C
losi
ng C
oil
485+
485
-C
omm
unic
atio
n (D
NP
3.0
)
T5P
re-a
larm
(*) C
onne
ct o
n un
derv
olta
ge m
odul
e -
see
page
9
PR
OTE
CTI
ON
UN
IT
COMMUNICATION
www.weg.net
Air Circuit Breaker ABW20
Protection Units
For ABW circuit breaker application in environments with temperatures exceeding 40°C, refer to the maximum rated current values shown in the following table.
Maximum Rated Current (A)
Ambient Temperature ABW16 ABW20 ABW25 ABW32 ABW40 ABW5040°C 1600 2000 2500 3200 4000 5000
45°C 1600 2000 2500 3200 4000 5000
50°C 1600 2000 2500 3200 4000 5000
55°C 1550 2000 2450 3000 3900 4850
60°C 1500 2000 2350 2900 3750 4700
Altitude Influence
For ABW circuit breaker application in altitudes exceeding 2000m, refer to the rated voltage and current reduction factors presented in the following table.
Altitude - hRated Voltage
Reduction FactorRated current Reduction Factor
h ≤ 2000m 1.00 1.00
2000 < h ≤ 2600m 0.95 0.99
2600 < h ≤ 3900m 0.80 0.96
Temperature Influence
www.weg.net
Air Circuit Breaker ABW 21
Dimensions (mm)
ABW16 – Fixed Version
Door seat for ABW16...50 (Fixed) (without frame)
ABW16 (Fixed) - Front View
Reference Line of theCircuit Breaker
ABW16 (Fixed)
ABW16 (Fixed) - Side View ABW16 (Fixed) - Rear View
Reference Line of theCircuit Breaker
Mounting Points
Module
Undervoltage
www.weg.net
Air Circuit Breaker ABW22
Dimensions (mm)
ABW16 – Withdrawable version
ABW 16 (Withdrawable) Side View ABW 16 (Withdrawable)
Rear View
ABW 16 (Withdrawable)Front View
ABW 16 (Withdrawable) Horizontal Terminals
Door seat ABW 16...32 (Withdrawable) (without frame)
Reference Line of the Circuit Breaker
Mounting Points
Mounting Points
Pos. Disconnected
Position Auxiliary Contacts
Insulating Plates
Pos. TestPos. Connected
under voltage module
15
www.weg.net
Air Circuit Breaker ABW 23
Dimensions (mm)
ABW20...32 – Fixed Version
20
ABW20...32 (Fixed)Front View
Door seat for ABW16...50 (fixed) (without frame)
ABW20...32 (Fixed) Side View
ABW20...32 (Fixed) Rear View
ABW20...32 (Fixed) Horizontal Terminals
Reference Line of theCircuit Breaker
Undervoltage module
Reference Line of theCircuit Breaker
Mounting Points
www.weg.net
Air Circuit Breaker ABW24
Dimensions (mm)ABW20...32 – Withdrawable version
ABW20...32 (Withdrawable) Front view
Door seat ABW 16...32 (Withdrawable) (without frame)
Door seat for ABW 20 (Withdrawable) Horizontal Terminals
Door seat ABW 20...32 (Withdrawable)
Door seat ABW 20 (Withdrawable) Horizontal Terminals
Reference Line of theCircuit Breaker
Reference Line of theCircuit Breaker
Mounting Points
Mounting Points
Undervoltage module
Pos. Disconnected Pos. Test
Pos. ConnectedPosition Auxiliary Contacts
* Applicable for circuit breaker ABW32
* Applicable for circuit breaker ABW32
Insulating Plates
20 (2
5)*
20 (2
5)*
www.weg.net
Air Circuit Breaker ABW 25
Dimensions (mm)ABW40...50 – Fixed Version
ABW40...50 (Fixed) Horizontal Terminals
ABW40...50 (Fixed) - Side View ABW40...50 (Fixed) - Rear View
ABW40...50 (Fixed) - Front View
Door seat forABW 16...50 (Fixed) (without frame)
Reference Line of theCircuit Breaker
Mounting Points
Reference Line of theCircuit Breaker
Undervoltage module
www.weg.net
Air Circuit Breaker ABW26
Dimensions (mm)
ABW40...50 – Withdrawable Version
14
14
ABW40...50 (Withdrawable) - Front View Door seat ABW40...50 (Withdrawable) (without frame)
ABW40...50 (Withdrawable) - Side View ABW40...50 (Withdrawable) - Rear View
ABW40...50 (Withdrawable) Vertical Terminals
Reference Line of theCircuit Breaker
Reference Line of theCircuit Breaker
Reference Line of theCircuit Breaker
Mounting Points
Mounting Points
Undervoltage module
Projection of the base plate
Pos. DisconnectedPos. Test
Pos. ConnectedPosition Auxiliary Contacts
Insulating Plates
www.weg.net
Air Circuit Breaker ABW 27
Dimensions (mm)
ABW-DF16
ABW-DF32
ABW-CTD Installation – Free Space
ABW-CTD
ABW-DF32 - Front / Side View ABW-DF32 - Door seat
ABW-DF16 - Door seatABW-DF16 - Front / Side View
* Applicable for circuit breaker ABW40 and ABW50
(withdrawable)
1005
.00/
0420
09 -
Sub
ject
to a
ltera
tions
with
out p
rior
notic
e.
The
info
rmat
ion
cont
aine
d is
for
refe
renc
e on
ly.
WEG Worldwide Operations
ARGENTINAWEG EQUIPAMIENTOS ELECTRICOS S.A.(Headquarters San Francisco-Cordoba)Sgo. Pampiglione 4849Parque Industrial San Francisco2400 - San FranciscoPhone(s): +54 (3564) 421484Fax: +54 (3564) [email protected]/ar
AUSTRALIAWEG AUSTRALIA PTY. LTD.3 Dalmore DriveCarribean Park Industrial EstateScoresby VIC 3179 - MelbournePhone(s): 61 (3) 9765 4600Fax: 61 (3) 9753 [email protected]/au
BELGIUM WEG BENELUX S.A.Rue de l’Industrie 30 D, 1400 NivellesPhone(s): + 32 (67) 88-8420Fax: + 32 (67) 84-1748 [email protected]/be
CHILEWEG CHILE S.A.Los Canteros 8600 La Reina - SantiagoPhone(s): (56-2) 784 8900Fax: (56-2) 784 [email protected]/cl
CHINAWEG (NANTONG) ELECTRIC MOTOR MANUFACTURING Co., Ltd.No. 128 - Xinkai Nan Road,Nantong Economic and Technological Development AreaJiangsu Province, China PC226010 Phone(s): 86 513 8598 9329Fax: 86 513 8592 [email protected]/cn
COLOMBIAWEG COLOMBIA LTDACalle 46A N82 - 54Portería II - Bodega 7 - San Cayetano II - BogotáPhone(s): (57 1) 416 0166Fax: (57 1) 416 [email protected]/co
WEG Equipamentos Elétricos S.A.International Division Av. Prefeito Waldemar Grubba, 3000 89256-900 - Jaraguá do Sul - SC - Brazil Phone: 55 (47) 3276-4002 Fax: 55 (47) 3276-4060 www.weg.net
FRANCEWEG FRANCE SASZI de Chenes – Le Loup13 Rue du Morellon – BP 73838297 Saint Quentin FallavierPhone(s): +33 (0) 4 74 99 11 35Fax: +33 (0) 4 74 99 11 [email protected]/fr
GERMANYWEG GERMANY GmbHAlfred-Nobel-Str. 7-9D-50226 FrechenPhone(s): +49 (2234) 9 5353-0Fax: +49 (2234) 9 [email protected]/de
INDIAWEG Electric (India) Pvt. Ltd.#38, Ground Floor, 1st Main Road, Lower Palace Orchards,Bangalore – 560 003Phone(s): +91-80-4128 2007 +91-80-4128 2006 Fax: +91-80-2336 7624 [email protected]/in
ITALYWEG ITALIA S.R.L.V.le Brianza 20 - 20092 - Cinisello Balsamo - MilanoPhone(s): (39) 02 6129-3535Fax: (39) 02 [email protected]/it
JAPANWEG ELECTRIC MOTORSJAPAN CO., LTD.Matsumoto Bldg. 2F, 3-23-7 Kamata, Ohta-ku,Tokyo, Japan 144-0052Phone(s): (81) 3 3736-2998Fax: (81) 3 [email protected]/jp
MEXICOWEG MEXICO, S.A. DE C.V.Carretera Jorobas-Tula Km. 3.5, Manzana 5, Lote 1 Fraccionamiento Parque Industrial - Huehuetoca, Estado de México - C.P. 54680Phone(s): + 52 (55) 5321 4275Fax: + 52 (55) 5321 [email protected]/mx
NETHERLANDSWEG NETHERLANDS Sales Office of WEG Benelux S.A.Keulenstraat 4E 7418 ET DeventerPhone(s): +31 (0) 570-620550Fax: +31 (0) [email protected]/nl
PORTUGALWEG EURO - INDÚSTRIA ELÉCTRICA, S.A.Rua Eng. Frederico UlrichApartado 6074 4476-908 - MaiaPhone(s): +351 229 477 705Fax: +351 229 477 [email protected]/pt
RUSSIAWEG RUSSIA Pochainskaya Str. 17 Nizhny Novgorod 603001 - Russia Phone(s): +7-831-2780425 Fax: [email protected] www.weg.net/ru
SPAINWEG IBERIA S.L. Avenida de la Industria,2528823 Coslada - MadridPhone(s) : (34) 916 553 008Fax : (34) 916 553 [email protected]/es
SINGAPOREWEG SINGAPORE PTE LTD159, Kampong Ampat, #06-02A KA PLACE. Singapore 368328.Phone(s): +65 6858 9081Fax: +65 6858 [email protected]/sg
SWEDENWEG SCANDINAVIA ABBox 10196Verkstadgatan 9434 22 KungsbackaPhone(s): (46) 300 73400Fax: (46) 300 [email protected]/se
UKWEG ELECTRIC MOTORS (U.K.) LTD.28/29 Walkers RoadManorside Industrial EstateNorth Moons Moat - RedditchWorcestershire B98 9HEPhone(s): 44 (0)1527 596-748Fax: 44 (0)1527 [email protected]/uk
UNITED ARAB EMIRATESWEG MIDDLE EAST FZEJAFZA – JEBEL ALI FREE ZONETower 18, 19th Floor, Office LB181905Dubai – United Arab [email protected]/ae
USAWEG ELECTRIC CORP1327 Northbrook Parkway, Suite 490Suwanee 30024Phone(s): 1-770-338-5656Fax: [email protected] www.weg.net/us
VENEZUELAWEG INDUSTRIAS VENEZUELA C.A.Parcela T-4-A Transversal 9 Urb. Industrial Carabobo Catastral 79-101 Edf. ELIMECA Loc. ELI-MECA, Zona Postal 2003, Va-lencia, Edo. CaraboboPhone(s): (58) 241 838 9239Fax: (58) 241 838 [email protected]/ve