ABB GridShield

Embed Size (px)

Citation preview

  • 7/27/2019 ABB GridShield

    1/24

    GridShield

    15/27/38 kV three-phase vacuum recloser

  • 7/27/2019 ABB GridShield

    2/242 GridShield | Descriptive bulletin

    Table of contents

    Introduction ............................................................................................................................................................................. 3

    Recloser design ....................................................................................................................................................................... 4

    Magnetic actuators .............................................................................................................................................................. 4

    Position switch .................................................................................................................................................................... 4

    Vacuum interrupters .... .... ..... .... ..... ..... .... ..... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... .... 4

    Pole assembly ..................................................................................................................................................................... 4

    HCEP insulating material ...................................................................................................................................................... 5

    GridShield 15/38 kV dimensions ........................................................................................................................................... 6

    Recloser control ...................................................................................................................................................................... 8

    RER620 overview................................................................................................................................................................. 8

    PCM600 .............................................................................................................................................................................10

    Web HMI ............................................................................................................................................................................11

    Protection functions ............................................................................................................................................................12

    Technical data.........................................................................................................................................................................14Ordering guide ........................................................................................................................................................................15

    Accessories ...... .... ..... .... ..... ..... .... ..... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ...18

    Additional ABB devices ...... ..... .... ..... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ...20

    Service & support ...................................................................................................................................................................21

    Notes ......................................................................................................................................................................................22

  • 7/27/2019 ABB GridShield

    3/24Descriptive bulletin | GridShield

    IntroductionGridshield: Making distribution networks more reliable

    ABBs dr ive to produce more advanced feeder automation

    equipment and to exceed their users expectations has led

    to the development of the new GridShield recloser. Paired

    with the industrys most intelligent control device - the

    RER620 - the GridShield recloser is a product of extensive

    international research and testing, creating the most reliable

    and technically adept recloser on the market. Whether

    performing three- or single-phase tripping connecting

    distributed generation to the grid or communicating via IEC

    61850 utilizing GOOSE messaging, the GridShield recloser

    is ready for any challenge.

    Features

    Abi lity to perform as a recloser, sectionalizer or automated

    load break switch

    Proven design rated for 10,000 full load operations

    Hydrophobic Cycloaliphatic Epoxy (HCEP) insulation provide

    industry leading reliability

    Stainless steel construction for durability in any environmen

    Air insulat ion for an environmental ly friendly design

    Minimal maintenance required for the high voltage unit

    Two control cabinet options to f it any appl icat ion

    All electronics located inside control cabinet for quick and

    safe access, reducing maintenance costs

    DNP3 Level 2+, IEC 60870-5-101 and 104, IEC61850, and

    MODBUS communication protocols come standard Web Human Machine Interface (web HMI) software for field

    configuration

    Technical ly advanced RER620 control with ful ly customizabl

    settings

    Powerful PCM600 tool suite

    Single-phase tripping option for improved system reliability

    1 Standard control cabinet, open | 2 Standard control cabinet, closed | 3 15/27 kV GridShield recloser

    2 31

  • 7/27/2019 ABB GridShield

    4/244 GridShield | Descriptive bulletin

    Magnetic actuators

    Industry proven design

    No lubrication, maintenance, or adjustments

    Bi-stable technology means no power required to maintain

    open or closed position

    Stainless steel shaft and corrosion resistant construction

    3 independent actuators fitted in the cabinet to allow single

    phase tripping

    Position switch

    Double break, galvanically separate contacts

    Self-cleaning contacts

    Transparent housing allows for contact position and mecha-nism viewing

    Vacuum interrupters

    Superior contact wear ensuring maximum reliability

    Environmentally friendly

    Built by ABB in Ratingen, Germany since 1980s

    Pole assembly

    Modular assembly for easy replacement in the field

    UV protected for environmental durability

    Molded design reduces risk of tampering

    Few moving parts

    10,000 full load operations without maintenance

    Single molded design guarantees the longest creepage dis-

    tance in the industry

    1 Magnetic actuators add durability and safety | 2 Single molded poles for superior creepage | 3 ABB vacuum interrupter clean room

    2 31

    Recloser designHigh voltage unit technology

  • 7/27/2019 ABB GridShield

    5/24Descriptive bulletin | GridShield

    HCEP insulating material

    The pole insulating material is Hydrophobic Cycloa liphatic

    Epoxy (HCEP). the next generation of Cycloaliphatic Epoxy

    (CEP).

    Hydrophobicity provides water resistance, preventing water

    from developing completely wetted, resistively conductive

    surfaces on outdoor insulation. As a result, leakage currents

    are reduced which increases reliability by minimizing the

    risk of insulation flashover. Furthermore, reducing discharge

    activity translates into decreased insulator erosion and

    increased insulator l ife expectancy.

    Advantages

    Improved water beading and runoff

    Lower leakage currents and less discharge activity

    Reduced flash-over probability

    Less erosion of insulation

    Improved performance in heavily polluted areas

    Improved weatherability and outdoor aging

    Prolonged life expectancy

    Exceptional mechanical strength attributed to epoxy-

    based design

    Contamination performanceDetermined by creepage/leakage distance available on a

    recloser bushing (pole), contamination performance is a very

    important factor when considering the reclosers operat-

    ing environment. ABB uses the HCEP insulation to not only

    offer a product that far exceeds the creep required by ANSI

    standards, but also to produce results that go beyond IEC

    Level IV requirements for environments with very heavy pol-

    lution.

    IEC pollution levels

    Pollution level Required Creep ratio

    I - Light 0.63 in/kV (16 mm/kV)

    II - Medium 0.79 in/kV (20 mm/kV)

    III - Heavy 0.98 in/kV (25 mm/kV)IV - Very Heavy 1.22 in/kV (31 mm/kV)

    HCEP does not become resistively conductive when exposed to moisture

    Required Creep vs OVR Creep (Phase to Ground)

    Pollution

    Level

    Rated Maximum Voltage

    15 kV 27 kV 38 kV

    Required Creep

    in (mm)

    ABB Standard

    Creep in (mm)

    Required Creep

    in (mm)

    ABB Standard

    creep in (mm)

    Required Creep

    in (mm)

    ABB Standard

    Creep in (mm)

    I - Light 9.8 (248) N/A 17.0 (432) N/A 23.9 (608) N/A

    II - Medium 12.2 (310) N/A 21.3 (540) N/A 30.0 (760) N/A

    III - Heavy 15.3 (388) N/A 26.6 (675) N/A 37.4 (950) N/A

    IV - Very Heavy 18.9 (481) 38.0 (960) 33.0 (837) 38.0 (960) 46.4 (1178) 50.7 (1288)

  • 7/27/2019 ABB GridShield

    6/246 GridShield | Descriptive bulletin

    GridShield 15/27/38 kV dimensions

    Pole mounting frame

    C C

    N

    O

    36.0

    Adjustment holes locatedat 3.0 in increments

    D

    R

    P

    Q

    M- Max heightL- As shown

    B

    67.5

    20.1

    30.34

    14.40

    16.63

    C

    B

    C

    A

    G

    F

    D E

    H

    Substation mounting frame

    Rating Units A B C D E F G H L M N O P Q R

    15/27 kV in 49.8 41.75 15.5 13 30 39 25.3 15.5 65.6 95.8 48 52.4 22 29.1 27.9

    15/27 kV mm 1265.5 1060.5 393.7 330 763 989.6 642.6 393.7 1666 2433.3 1219.2 1330.5 558.8 738.2 708.6

    38 kV in 49.8 41.8 15.5 13.3 30 45.2 30.1 15.5 71.5 101.5 48 52.4 22 29.1 34.1

    38 kV mm 1265.5 1060.5 393.7 339 763 1146.9 763.9 393.7 1816 2578 1219.2 1330.5 558.8 738.2 866

  • 7/27/2019 ABB GridShield

    7/24Descriptive bulletin | GridShield

    36.00 914.40

    18.19 461.95

    2.24 56.92

    20.12 511.00

    2X 10.06 255.502.82 71.74

    39.17 994.89

    1.34 34.149-59 FT.

    .88 22.23 X 2.38 60.33 SLOT

    .50 12.70

    13.84 351.61

    15.34 389.71

    PAD LOCK

    HOLE

    GROUNDING LUG

    1/2-13 THD

    Large control cabinet - standard

    Small control cabinet low profile option

    9.074

    [230.48]

    27.500

    [698.50]24.000

    [609.59] 0.249

    [6.33]

    18.000

    [457.20]

    0.875

    [22.23]

    30.000

    [762.00]

    1.500

    [38.10]

    17.540

    [445.52]

  • 7/27/2019 ABB GridShield

    8/248 GridShield | Descriptive bulletin

    RER620 overview

    The RER620, part of the Relion family of ABB controls, is a

    dedicated IED perfectly aligned for the protection, control, mea-

    surement and supervision of utility substations and industrial

    power systems including radial, looped and meshed distribu-

    tion networks with or without distributed power generation. The

    RER620 IED is characterized by its compactness and withdraw-

    able unit design.

    Engineered from the ground up, the RER620 has been designed

    to unleash the full potential of the IEC 61850 standard for com-

    munication and interoperability. The RER620 provides main

    protection for overhead lines and cable feeders in distribution

    networks.

    RER620 Introduction

    Part of Relion family of ABB controls

    Drawout design for quick and easy maintenance

    Environmentally friendly design with RoHS compliance

    Capable of having up to 20 binary inputs and 14 binary out-

    puts

    Easy integration into Ethernet or serial-based communica-

    tion networks with standard: DNP3, IEC 60870-5-101, IEC

    60870-5-104, Modbus, IEC 61850

    Use of GOOSE messaging (peer-to-peer) for high-speed pro-

    tection, transfer switching, fault isolation and service restora-tion

    Interact via easy to read local HMI or remotely

    Six setting groups for protection scheme flexibility

    High Impedance (HIZ) fault detection creates more safety for

    life around power lines

    Embedded In-rush detection for added reliability connecting

    distributed generation networks

    Integrated loop control as standard offering

    There are two loop control schemes that come with the Grid-

    Shield recloser:

    The traditional loop control scheme is based on voltage, over-

    current and reclosing sequence.

    Additional ly, there is the advanced 61850 (peer-to-peer) loop

    control scheme for fault detection, isolation and restoration.

    With the quick response from GOOSE messaging, the reclosers

    can communicate with each other and determine where thefault is, preventing unnecessary reclosing.

    Self-diagnostics

    - Built-in self-diagnostics continuously monitors

    the RER620 electronics and the operation of the

    relay software

    - Any fault or malfunction will raise an alert

    Recloser controlThe future of Intelligent Electronic Devices (IEDs)

    RER620 relay located inside padlockable control cabinet

    Substation

    CircuitBreaker

    Source 1

    Substation

    CircuitBreaker

    Source 1

    B

    A D

    C

    T

    Sectionalizing

    Recloser

    NormallyClosed

    SectionalizingRecloser

    NormallyClosed

    MidpointRecloser

    Normally

    Closed

    MidpointRecloser

    NormallyClosed

    Tie Point

    Recloser

    Normally

    Open

    F1 F2 F31 PT

    3 PT

    1 PT1 PT

    1 PT

    3 PT

    Substation

    CircuitBreaker

    Source 1

    Substation

    CircuitBreaker

    Source 1

    B

    A D

    C

    T

    Sectionalizing

    Recloser

    NormallyClosed

    SectionalizingRecloser

    NormallyClosed

    MidpointRecloser

    Normally

    Closed

    MidpointRecloser

    NormallyClosed

    Tie Point

    Recloser

    NormallyOpen

    Interlocking data

    GOOSE

    RER620REF615

    RER620

    RER620

    Interlocking data

    GOOSE

    Interlocking data

    GOOSE

    F1 F2 F31 PT

    3 PT

    1 PT1 PT

    1 PT

    3 PT

  • 7/27/2019 ABB GridShield

    9/24Descriptive bulletin | GridShield

    RER620 hardware features

    Drawout case

    ABBs innovat ive design for the RER620 includes a standard

    drawout case, allowing for quick access to relay cards for easy

    field maintenance. Also included is an automatic function that

    shorts CT connections to the relay when removed from the

    case, making maintenance safer for the user.

    Local HMI

    Large, 13x14 pixel, LCD screen displays ten rows, each

    capable of displaying 20 characters

    Simple controls for navigation and recloser open/close

    operation Normal, Pickup and Trip protection indicators for state

    identification

    Recloser open/close buttons let the user know current

    position

    11 programmable alarm LEDs - great for loss of phase and

    lockout indication

    14 programmable push-buttons for user customization

    Customizable labeling for programmable buttons and alarms

    Front RJ-45 communication port for quick laptop connection

    Communication

    Ethernet network communication via RJ-45 or LC fiber optic

    connectors

    Serial communications via RS-232, RS-485, or ST fiber opt

    connection

    DNP 3.0 Level 2+ over TCP/IP or serial with redundant phys

    cal channel support

    IEC 60870-5-101and IEC 60870-5-104

    Modbus RTU/ASCII over serial and TCP/IP modes supporte

    IEC 61850, with GOOSE messaging

    PG&E 2179

    The event generation subsystem prov ides consistent t imestping across all protocols

    Simultaneously report events to five IEC 61850 clients

    Input and output ports

    Capable of up to 20 binary inputs and 14 binary outputs

    when fully configured

    6 VT inputs for voltage sensing

    4 CT inputs

    1 RER620 relay and drawout case | 2 IED can be controlled via a clean and easy to use HMI | 3 A variety of communication ports and I/Os to fit the users

    needs

    2 31

  • 7/27/2019 ABB GridShield

    10/2410 GridShield | Descriptive bulletin

    PCM600

    PCM600 offers extensive relay configuration functions such as

    relay signal configuration and IEC61850 communication con-

    figuration with GOOSE horizontal relay-to-relay messaging.

    Advantages

    Tool suite with numerous tools at hand, useable with and

    without connection to RER620

    Easy to navigate menu follows local HMI menu layout

    Tab structure for easy management of open tools

    Create settings ahead of time and load onto an RER620 via

    RJ-45 connection

    Save setting profiles and load onto other relays

    Customize recloser, sectionalizer, and automated load breakswitch modes with application configuration tool

    Integrated documentation for quick referencing of technical

    information and communication point lists

    Import and export GOOSE messages for advanced commu-

    nication schemes

    Graphical display editor

    Visuall y display power system objects and their status

    Integrate on-line measurement in the IED HMI

    Set node attributes like name, name position and sort index

    Extensive ANSI and IEC symbol library included

    Application conf iguration tool

    Function block-based programming for easy customization

    Search feature and quick jump function allows for easy

    navigation

    View existing logic for clear understanding of recloser func-

    tions

    Adapt pre-configured applications

    Broken up into I/O, Measurements, Control, and Protection

    tabs for progamming organization

    Insertable text boxes for tracking changes

    Debugging for operation assurance

    Disturbance handling

    Records up to 12 analog channels and 64 binary channels Can be triggered by analog/binary channels or manual/peri-

    odic commands

    Selectable sampling rate, 32/16/8 samples per cycle

    Events stored following COMTRADE standard

    Export and view using ABBs WaveWin32 software or any

    other COMTRADE compliant software

    Records include current, voltage and angle values, and

    pickup times of the protection elements

    Time stamps provide useful record for analyzing in what order

    events occurred

    ACT tool for logic programming Change HMI screen with the Graphical Display

    Editor

    Disturbance handling capabilities include signal

    charts for reviewing faults

  • 7/27/2019 ABB GridShield

    11/24Descriptive bulletin | GridShield

    Web HMI

    The web HMI enables the user to access the RER620 via a web

    browser. This method of connecting to the RER620 requires

    no additional software and can connect locally by connecting

    a computer to the RER620 via the front communication port

    or remotely over LAN/WAN. With a menu tree structure similar

    to the one on the local HMI, the user does not need to spend

    time relearning where every setting is located. With this useful

    tool, the user has a quick means for programming most of the

    recloser settings.

    Overview

    Local and remote access

    User access level authentication On-line Help menu

    Runs with Internet Explorer 7.0 or later

    Features

    View alarm LEDs, event lists, and measurements

    Monitor signals

    Read and download disturbance records

    Review phasor/tabular diagrams with various representation

    Phase currents

    Sequence currents

    Phase voltages

    Sequence voltages

    Zoom in phasor/tabular diagrams

    Freeze current and voltage measurements to obtain a snap

    shot view during testing

    Set parameters

    Save event lists Print settings

    All sett ings can be opened and saved in CSV format

    Quickly view disturbance records Choose from various phasor diagram options Make quick parameter setting changes

  • 7/27/2019 ABB GridShield

    12/2412 GridShield | Descriptive bulletin

    Protection functions

    The RER620 IED offers the most extensive and adaptive set of

    protective functions in the industry.

    High Impedance (HIZ) fault detection

    High impedance faults have small current magnitudes that are

    difficult to detect by standard protection. While small fault cur-

    rents do not pose danger to power equipment, a high imped-

    ance fault poses a deadly threat to humans and animals.

    How has ABB addressed HIZ?

    7 years of dedicated research and extensive field tests to

    develop best solution

    Created HIZ (PHIZ1) function in protection schemes

    Utilize ground/earth fault current signatures in HIZ algorithm

    Embedded In-rush energy detectionIn situations where distributed generation is first connected to

    a main network, there is a large current pull from transformers,

    which will cause a relay to trip the recloser on the line. The

    traditional solution is to use communication to inform the relay

    of the situation and prevent the trip. With the RER620, there is

    no need for communication because of the embedded In-rush

    energy detection.

    Current protection

    Single-Phase overcurrent protection [51P, 50P-1, 50P-2,

    50P-3; 3I>(1), 3I>(2), 3I>(3)]

    Overcurrent ground-fault protection [51N, 50N-1, 50N-2,50N-3; lo>(2), lo>(3), lo>>(3), lo>>>(2)]

    Sensitive earth-fault protection [50SEF; lo>(3)]

    Negative sequence overcurrent protection [46-1, 46-2;I2>(1),

    I2>(2)]

    Phase discontinuity protection [46PD; I2/I1>]

    Three-phase inrush detector [INR; 3I2f>]

    Directional protection

    Single-phase overcurrent protection [67/51P-1, 67/51P-2;

    3I>->(1), 3I>->(2)]

    Ground-fault protection [67/51N-1, 67/51N-2; lo>->(1),

    lo>->(1)]

    Cold load timers

    Cold load timer phase A [62CLD-1, 62CLD-2; TPS(1),

    TPM(1)]

    Cold load timer phase B [63CLD-3, 63CLD-4; TPS(2),

    TPM(2)]

    Cold load timer phase C [63CLD-5, 63CLD-6; TPS(3),

    TPM(3)]

    Voltage protection

    Three-phase overvoltage [59-1, 59-2, 59-3; 3U>(1), 3U>(2),3U>(3)]

    Three-phase undervoltage [27-1, 27-2, 27-3; 3U(1), U2>(2)]

    Zero sequence overvoltage [59N-1, 59N-2; Uo>(1), Uo>(2)]

    Frequency protection

    Underfrequency, Overfrequency, Frequency rate of change

    [81-1, 81-2; f,df/dt(1), f,df/dt(2)]

    Load shed & restoration [81S-1, 81S-2; UFLS/R(1),UFLS/R(2)]

    HIZ effects on gravel HIZ effects on grass

  • 7/27/2019 ABB GridShield

    13/24Descriptive bulletin | GridShield

    Control

    Autoreclosing, 1ph and/or 3ph [79; O->I]

    Synchro-check/voltage check [25; SYNC]

    Circuit breaker 1 (3 state inputs / 3 control outputs)

    [52; IO CB]

    Loop control

    Supervision monitoring

    CB condition monitoring [52CM; CBCM]

    Fuse failure supervision [60, FUSE]

    Measurement

    Three-phase current [ IA, IB, IC; 3I]

    Demand metering, Max/Min metering

    Sequence current [I1, I2, I0; I1, I2, I0]

    Ground current [IG; lo]

    Three-phase voltage, source [VA, VB, VC; 3U] Three-phase voltage, load [VA, VB, VC(2); 3U(B) ]

    Sequence voltages, source [V1, V2, V0; U1, U2, U0]

    Sequence voltages, load [V1, V2, V0(2); U1, U2, U0(B)]

    Three and single -phase power and energy [P, E]

    Frequency [f]

    Power factor [pf]

    Recorders

    Digital fault recorder (DFR) [DFR]

    Sequence of events (SER) [SER]

    Fault recorder [FLTMSTA]

    Fault locator (FLOC) [FLO]

    Other functions

    High impedance fault detector [HIZ; PHIZ1]

    Recloser failure protection [50BFT; 3I>/lo>BF]

    Recloser close failure protection [50BFC; SCCBRBCF1]

    Directional positive sequence power protection [32P; P>->]

    Directional negative/zero sequence power protection

    [32N; Q>->]

    Battery voltage, current, battery test [UPS]

    Programmable buttons (16 buttons) [FKEYGGIO1]

    Move function block (8 outputs) [MVGAPC1]

    Move function block (8 outputs) [MVGAPC2] Pulse timer (8 timers) [PTGAPC1]

    Pulse timer (8 timers) [PTGAPC2]

    Generic control points (16 outputs) [SPCGGIO1]

    Generic control points (16 ouputs) [SPCGGIO2]

    Set reset flip flops (8 outputs) [SRGAPC1]

    Set reset flip flops (8 outputs) [SRGAPC2]

    Time de lay off timers (8 timers) [TOFGAPC1]

    Time de lay off timers (8 timers) [TOFGAPC2]

    Time de lay on t imers (8 timers) [TONGAPC1]

    Time de lay on t imers (8 timers) [TONGAPC2]

    All traditional recloser, ANSI and IEC curves are also avai lable

    RER620

    1Io selectable by setting, Io calculated as default

    52

    or

    Va,

    Vb,

    Vc

    3

    51P3I> 50P-13I> 50P-23I>> 50P-33I>>>

    6846PD 3I2f>I2/I1I2>50BF3I>BF 46I2>

    67P3I>->

    51NI0>50N-1I0>50N-2I0>>50N-3I0>>>

    32PP>-> 32NQ>->

    50SEFI0> HIZPHIZ1 67N1I0>->

    Ia, Ib, Ic4

    27P3U< 59P3U> 81f 81SUFLS/R2

    2Under-frequcny and df /dt based load shedding function

    59PSV1> 59NV0>

    60FUSEF

    27P3U< 59P3U>

    47NSV2>

    47NSV2> V1> 59PS

    59NV0>

    2SYNC

    0 791 LCMLCM

    3In the case of ABB GridShield recloser, t hese are embedded Capacitor Voltage

    Divider (CVD) with 10,000:1 ratio4

    In the case of ABB GridShield recloser, these are embedded Current Transformer

    (CT) with 600:1 ratio

    RER620 protection diagram

  • 7/27/2019 ABB GridShield

    14/2414 GridShield | Descriptive bulletin

    Nom. operating voltage: 2.4-14.4 24.9 34.5 kV

    Rated max. voltage: 15.5 27 38 kV

    Rated power frequency: 50/60 50/60 50/60 Hz

    Rated continuous current: 800/1000/1250 800/1000/1250 800/1000/1250 A

    Rated symmetrical interrupting current: 12.5/16 12.5/16 12.5/16 kA

    Rated lightning impulse withstand (BIL): 110/125 125/150 150/170 kV

    Dry withstand 60 Hz 1 Min.: 50 60 70 kV

    Wet withstand 60 Hz 10 Sec.: 45 50 60 kV

    Phase spacing 15.50 (394) 15.50 (394) 15.50 (394) inches (mm)

    External creep distance, H2-ground: 38.00 (960) 38.00 (960) 50.70 (1288) inches (mm)

    External creep distance, H1-H2: 45.00 (1160) 45.00 (1160) 49.80 (1260) inches (mm)

    Min. external strike distance: 9.50 (240) 9.50 (240) 14.40 (367) inches (mm)

    Min. interrupting time: 0.050 0.050 0.050 sec max

    Max. closing time: 0.055 0.055 0.055 sec max

    High voltage unit weight: 333 (150) 333 (150) 430 (195) lbs (kg)

    Small control cabinet weight: 138 (63) 138 (63) 138 (63) lbs (kg)

    Large control cabinet weight: 182 (83) 182 (83) 182 (83) lbs (kg)

    Rated standard operating duty: O 0.2s CO 2s CO 5s CO lockout

    Operating temperature: -40C to +60C (-40 F to +140F)

    Control voltage:

    - 120 VAC UPS: 90-140 VAC / 109 - 144 VDC

    - 240 VAC UPS: 180 - 285 VAC / 220 - 285 VDC

    Materials: Vacuum interrupter encapsulated in hydrophobic cycloaliphatic epoxy with stainless steel construction

    Current sensors: One per phase encapsulated into the pole

    Battery:

    - 48 VDC, 12 AH battery bank- Sealed lead acid rechargeable battery pack

    - Monitor locally and remotely

    - Easy access in low voltage control cabinet

    - Capable of up to 38 hours of carryover and multiple operations upon loss of power

    GridShield Testing:

    ANSI : Meets al l app licable recloser s tandards (Dual logo standard IEC 62271-111/IEEE C37.60 2005-11, IEEE, and IEC)

    IP54 rated for water and dust intrusion

    Life Test: 10,000 mechanical operations without degradation

    Technical data

  • 7/27/2019 ABB GridShield

    15/24Descriptive bulletin | GridShield

    Ordering guide

    Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17-1

    S 1 1 8 1 C D E 1 2 E 1 4 4 S A 00

    1) Recloser

    Ratings

    S: GridShield Recloser S: GridShield

    Recloser

    2) Voltage 1: 15 kV 1: 15 kV

    2: 27 kV

    3: 38kV

    3) BIL 1: 110 kV 1: 110 kV

    2: 125 kV

    5: 150 kV

    7: 170 kV

    4) Continuous

    Current

    8: 800 A 8: 800 A

    1: 1000 A

    2: 1250 A

    5) Interrupting

    Rating

    1: 12.5 kA 1: 12.5 kA

    2: 16 kA

    6) Mounting

    Frame

    C: Pole w/ 6 Arrester

    brackets & 3 PT

    C- Channel Mtg Bra-

    ckets, Assembled

    A: Pole w/ 6 Arrester brackets , Assembled

    B: Pole w/ 6 Arrester brackets,

    Unassembled

    C: Pole w/ 6 Arrester brackets & 3 PT C-

    Channel Mtg Brackets, Assembled

    D: Pole w/ 6 Arrester brackets & 3 PT C-

    Channel Mtg Brackets, Unassembled

    H: Pole w/ 6 Arrester brackets & Flat PT

    Mtg Bracket, Assembled

    R: Pole w/ 6 Arrester brackets & Flat PTMtg Bracket, Unassembled

    G: Pole w/ 6 Arrester brackets & 6 PT Mtg

    Brackets, Hrztl Construction, Galvanized,

    Assembled

    I: Pole w/ 6 Arrester brackets & 6 PT Mtg

    Brackets, Hrztl Construction, Stainless

    Steel, Assembled

    K: Pole w/6 Arrester brackets & 6 PT Mtg

    Brackets, Vertical Construction, Galva-

    nized, Assembled

    M: Pole w/6 Arrester brackets & 6 PT Mtg

    Brackets, Vertical Construction, StainlessSteel, Assembled

    V: Substation Frame, Assembled

    W: Substation Frame, Unassembled

    X: Substat ion Frame w/ 3 PT Mtg Bra-

    ckets, Assembled

    Y: Substation Frame w/ 3 PT Mtg Bra-

    ckets, Unassembled

    Z: Custom Frame

    N: None

  • 7/27/2019 ABB GridShield

    16/2416 GridShield | Descriptive bulletin

    Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17-18

    S 1 1 8 1 C D E 1 2 E 1 4 4 S A 00

    7) 24-pin Control

    Cable

    D: 40 f ee t [12 m] A: 10 f eet [3 m]

    B: 20 feet [6 m]

    C: 30 feet [9 m]

    D: 40 feet [12 m]

    E: 50 feet [15.24 m]

    F: 60 feet [18.29 m]

    Z: Customized (Max. length 200 ft)

    N: None

    8) Cable Options

    for Control

    Power and PT

    Input

    E: (1) 2 pin connector

    with 45 ft cable and

    (1) 5 pin connector

    with 45 ft cable & 3

    internal voltage inputs

    directly into relay

    A: (1 ) 2 p in connector wi th 20 ft cable

    B: (1) 2 pin connector with 45 ft cable

    C: (1) 5 pin connector with 45 ft cable & 3 internal

    voltage inputs directly into relay

    D: (2) 5 pin connector with 45 ft cable & 3 internal

    voltage inputs directly into relay

    E: (1) 2 pin connector with 45 ft cable and (1) 5 pin

    connector with 45 ft cable & 3 internal voltage inputs

    directly into relay

    Z: Custom cable option

    N: None

    9) Control Power

    Supply11: UPS (Input

    Voltage :100V-200V)

    DC/AC with 120VAC

    Heater

    1. UPS (90-140 VAC) with 120 VAC heater

    2. UPS (90-140 VAC) with 240 VAC heater (aux power

    needed for heater)

    3. UPS (180-285 VAC) with 240 VAC heater

    10) Binary I/O 2: 12 BI (Binary Input)

    + 10 BO (Binary

    Output)

    1: 4 BI (Binary Input) + 6 BO (Binary Output)

    2: 12 BI (Binary Input) + 10 BO (Binary Output)

    3: 20 BI (Binary Input) + 14 BO (Binary Output)

    11) Control &

    Faceplate

    Options

    E: ANSI Standard

    RER620

    E: ANSI Standard RER620

    F: ANSI Standard RER620 with Single Phase Tripping

    G: ANSI Standard RER620 with Single Phase Tripping + PG&E 2179

    D: IEC Standard RER620 (comes with IEC Indicating Cup)

    C: IEC Standard RER620 with Single Phase Tripipng (comes with IEC

    Indicating Cup)12) Language 1: English 1: English

    2: English and Spanish

    13) Communica-

    tion Ports and

    Protocol2

    4: Three ports:

    Ethernet 10/100BaseT

    (RJ45) + configura-

    ble RS232/RS485 +

    [RS485 or serial glass

    fiber (ST) ]

    1: Ethernet RJ-45 only (COMB01A)

    2: Ethernet 100FX fiber optic with LC connector (COMB02A)

    3: Ethernet RJ-45 + RS485/IRIG-B (COMB11A)

    4: Ethernet RJ-45 + RS485/IRIG-B + RS232 + serial fiber optic with ST

    connector (COMB23A)

    14) Bushing Ter-

    minal Connectors

    4: NEMA 4-Hole Pad S: Stud terminal

    2: NEMA 2-Hole Pad

    4: NEMA 4-Hole Pad

    C: Clamp15) LV Cabinet

    Option

    S: Small S: Small - Low profile cabinet

    L : Large - Standard cabinet

    16) Standard

    Dynamic

    Accessories

    A: 69 Switch Close

    Block function from

    yellow handle

    A: 69 Switch Close Block function from yellow handle

    N: No accessories required

  • 7/27/2019 ABB GridShield

    17/24Descriptive bulletin | GridShield

    Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17-1

    S 1 1 8 1 C D E 1 2 E 1 4 4 S A 00

    17-18) Dynamic

    Accessories-

    Specific to unit

    will change last

    two digits of

    style number3

    00

    Radio Package

    (1) PT mounted and wired on recloser frame

    (3) PT mounted and wired on recloser frame

    (6) PT mounted and wired on recloser frame

    PT animal guard with push pins (set of 3)

    Anima l Guard (S traight) ( set o f 3)

    Anima l Guard (L -shaped) (set of 3)

    (1) 7200/12470 GY VOG-11 PT (Style Number: E-7525A95G01)

    (1) 7620/13200 GY VOG-11 PT (Style Number: E-7525A95G02)

    (1) 8400/14560 GY VOG-11 PT (Style Number: E-7525A95G03)

    (1) 14400/24940 GY VOG-12 PT (Style Number: E7525A97G02)

    (1) 11547/200000 GY VOG-12 PT (Style Number: E-7525A97G04)

    (1) 20125/34500 GY VOY-20G PT (Style Number: E-75265A55G01)

    Cable Animal Guard with straight pins

    10 feet Armored on the control cable (this armor will be on the control cable for the first 10 feet after

    LV cabinet)

    Ground Connector

    IEC Cups (set of 3)

    Transfer switch to transfer contro l power from primary to secondary source (PTs must be ava ilab le

    on line and load side )

    (1) Potential test switch & (1) Current test switch (available only in large Cabinet)

    (1) FT test switch 6 current 4 potential

    38 kV Animal Guard (Straight) (set of 3)

    Custom option

    1. A separate power source, 120/240VAC, is needed for the heater if input voltage is DC. If other power supply required, please contact ABB sales representative.

    2. SNTP is available for time-sync with all E thernet options. IRIG-B is available for time-sync with all RS-485 options.

    3. 00 for Standard - Style numbering will change for specials & dynamic accessories.

    Note: When selecting ANSI f aceplating, IEC61850, DNP3.0 Level 2 and Modbus communication protocols are automatically selected for the RER620.

    An IEC facepla te sel ection will result in a selec tion for IEC61850 IEC101 and IEC104 communica tion pro tocols for the RER620.

  • 7/27/2019 ABB GridShield

    18/2418 GridShield | Descriptive bulletin

    Accessories

    Recloser simulator assembly

    Test relay schemes or verify your protection settings with an

    ABB Recloser Simulator Card without having the high voltage

    unit connected to it. This is ideal for protection engineers to

    verify the relay performance at their convenience.

    Easy, cost effective method for testing relay schemes and

    the operational health of an RER620, without operating the

    recloser

    Simulate fault conditions inject secondary currents up to

    1 A (to simulate primary currents up to 600 A)

    Software can collect oscillographic records of fault

    simulations

    Comes with wiring harness and power adapter for RER620 Compatible with PCM600 software

    Flexitest switch

    Perform secondary current and voltage injection directly into

    the RER620 (ABB FT-1 option allows easy access for testing

    using secondary current injection and voltage with virtually

    any type of test equipment)

    Use the FT-1 to test the health of the recloser PTs and CTs

    No need to disconnect the 24 pin cable or phoenix plugs

    Use the FT-1 to test the GridShield contacts and program-

    mable I/O

    Transfer switch

    Quickly transfer control power between the load and source

    sides of a GridShield recloser. Potential transformers (PTs) must

    be connected on both the load and source sides of a GridShieldrecloser.

    1 Recloser simulator card (separate harness included in kit) | 2 Flexitest switch | 3 Transfer switch

    2 31

  • 7/27/2019 ABB GridShield

    19/24Descriptive bulletin | GridShield

    Animal guards

    GridShield animal guards provide easy-to-install protection that

    reduces on animal related interruptions.

    Bushing terminal accessories

    All GridShield reclosers come standard with a 1- inch (25.4 mm)

    diameter stud (12 threads) on all source and load terminals.

    Bushing Terminal Options

    NEMA Connectors Clamp Connector

    2-Hole Pad 4-Hole Pad #6-800 MCM (kcmil)

    Part # 12A00199H02 Part # 12A00198H02 Part # 12A00897H01

    6 included 6 included 6 included

    1 Straight bushing guard for 15 kV - 27 kV applications | 2 Straight bushing guard for 38 kV applications | | 3 L-shape bushing guard 15 kV - 27 kV applicatio

    | 4 Cable guard for 15 kV - 38 kV applications (36 long 1 dia.) | 5 Standard terminal | 6 NEMA connector 2-hole pad | 7 NEMA connector 4-hole pad |8 Clamp connector

    1

    5

    2

    6

    3

    7

    4

    8

  • 7/27/2019 ABB GridShield

    20/2420 GridShield | Descriptive bulletin

    Additional ABB devicesDesigned for improved reliability and feeder performance

    Single phase by-pass switch

    Provides a means for bypassing and disconnecting reclosers

    or voltage regulators, allowing maintenance on equipment

    without service interruption

    Porcelain or silicone insulators

    Mounting configurations: vertical, underhung, pole mount, or

    crossarm

    Avai lable ratings:

    15-38 kV

    600/900 A

    40 kA Momentary rating

    110-150 kV BIL

    AutoLink single-phase electronic sect ionalizer Works as sectionalizer in conjunction with an upstream re-

    closer or circuit breaker

    Prevents unnecessary supply outages

    Reduces replacement of fuses

    Both actuating current and count can be reset as many times

    as needed, making it unmatched in the industry

    Detects inrush current

    Compatible with ABB, S&C and AB Chance interchangeable

    cutout bodies

    Ideal for lateral feeders

    COM600

    The stat ion automation device of ABB, COM600 is an all-in-

    one communication gateway, providing connectivity between

    substation IEDs and network-level control and management

    systems. Additionally it is capable of automatic fault isolation

    and restoration.

    The COM600 adds distributed inte lligence to the feeders, and

    it is ideal for automation of rural li nes or whenever the user

    has SCADA IDMS limitations. It is a total configurable solution

    capable of providing all logic for fault detection isolation and

    restoration.

    1 Single-phase by-pass switch | 2 AutoLink single-phase electronic sectionalizer | 3 COM6001

    32

  • 7/27/2019 ABB GridShield

    21/24Descriptive bulletin | GridShield

    Service & support

    Recloser customer support

    Free 24/7 technical support line 1-800-929-7947 ext. 5 or

    outside the U.S. +1 407-732-2000 ext. 2510, e-mail

    [email protected]

    Feeder Automation users website featuring news, FAQs,

    discussion board, technical information, product brochures,

    software downloads, contact information, instruction manu-

    als, programming shortcuts, drawings:

    www.abb.com/fa-users

    Standard three year warranty

    Training

    Factory based training: three-day training designed for partici-

    pants to become proficient application, installation, operation,maintenance, testing, and commissioning of RER620 relays and

    GridShield reclosers

    Advanced training

    The advanced 3 day training is available upon request. It intro-

    duces IEC61850 architecture and IEC61850 communications.

    The participant learns the IET600 tool and how to configure

    peer-to-peer IEC61850 GOOSE communications.

    Day 1 topics

    Introduction

    GridShield with RER620 relay overview

    GridShield high voltage (HV) unit overview, troubleshooting &

    maintenance

    GridShield control cabinet overview, troubleshooting & main

    tenance, and introduction to RER620 relay

    Introduction to the WebHMI interface

    Introduction to Protection and Control IED Manager, PCM60

    tool

    Day 2 topics

    Using the Graphical Display Editor, Parameter Setting Tool,

    and Application Configuration Tool Setting the auto-recloser sequence for di fferent applications

    Day 3 topics

    DNP3 and Configuration Management tool for point remap-

    ping

    DNP3 objects, classes, events, deadbands and variation

    explained

  • 7/27/2019 ABB GridShield

    22/2422 GridShield | Descriptive bulletin

    Notes

  • 7/27/2019 ABB GridShield

    23/24Descriptive bulletin | GridShield

    Notes

  • 7/27/2019 ABB GridShield

    24/24

    Contact us

    ABB Inc.

    655 Century Point

    Lake Mary, FL 32746

    Phone: +1 407 732 2000

    Customer service: +1 800 929 7947 ext. 5

    +1 407 732 2000 ext. 2510

    E-Mail: [email protected]

    www.abb.com/mediumvoltage

    For more information about our Feeder Automation

    products, news, downloads, and Feeder Automation UsersGroup website registration, please contact:

    [email protected].

    All sales are s ubjec t to ABB Inc.

    General Terms and Conditions of Sale.

    While every effort has been made to assure accuracy, the

    information in this document is subject to change without

    notice.

    Copyright 2011, 2012 ABB Inc. All rights reserved.