GridShield
15/27/38 kV three-phase vacuum recloser
7/27/2019 ABB GridShield
2/242 GridShield | Descriptive bulletin
Table of contents
Introduction ............................................................................................................................................................................. 3
Recloser design ....................................................................................................................................................................... 4
Magnetic actuators .............................................................................................................................................................. 4
Position switch .................................................................................................................................................................... 4
Vacuum interrupters .... .... ..... .... ..... ..... .... ..... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... .... 4
Pole assembly ..................................................................................................................................................................... 4
HCEP insulating material ...................................................................................................................................................... 5
GridShield 15/38 kV dimensions ........................................................................................................................................... 6
Recloser control ...................................................................................................................................................................... 8
RER620 overview................................................................................................................................................................. 8
PCM600 .............................................................................................................................................................................10
Web HMI ............................................................................................................................................................................11
Protection functions ............................................................................................................................................................12
Technical data.........................................................................................................................................................................14Ordering guide ........................................................................................................................................................................15
Accessories ...... .... ..... .... ..... ..... .... ..... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ...18
Additional ABB devices ...... ..... .... ..... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ..... .... ..... ...20
Service & support ...................................................................................................................................................................21
Notes ......................................................................................................................................................................................22
7/27/2019 ABB GridShield
3/24Descriptive bulletin | GridShield
IntroductionGridshield: Making distribution networks more reliable
ABBs dr ive to produce more advanced feeder automation
equipment and to exceed their users expectations has led
to the development of the new GridShield recloser. Paired
with the industrys most intelligent control device - the
RER620 - the GridShield recloser is a product of extensive
international research and testing, creating the most reliable
and technically adept recloser on the market. Whether
performing three- or single-phase tripping connecting
distributed generation to the grid or communicating via IEC
61850 utilizing GOOSE messaging, the GridShield recloser
is ready for any challenge.
Features
Abi lity to perform as a recloser, sectionalizer or automated
load break switch
Proven design rated for 10,000 full load operations
Hydrophobic Cycloaliphatic Epoxy (HCEP) insulation provide
industry leading reliability
Stainless steel construction for durability in any environmen
Air insulat ion for an environmental ly friendly design
Minimal maintenance required for the high voltage unit
Two control cabinet options to f it any appl icat ion
All electronics located inside control cabinet for quick and
safe access, reducing maintenance costs
DNP3 Level 2+, IEC 60870-5-101 and 104, IEC61850, and
MODBUS communication protocols come standard Web Human Machine Interface (web HMI) software for field
configuration
Technical ly advanced RER620 control with ful ly customizabl
settings
Powerful PCM600 tool suite
Single-phase tripping option for improved system reliability
1 Standard control cabinet, open | 2 Standard control cabinet, closed | 3 15/27 kV GridShield recloser
2 31
7/27/2019 ABB GridShield
4/244 GridShield | Descriptive bulletin
Magnetic actuators
Industry proven design
No lubrication, maintenance, or adjustments
Bi-stable technology means no power required to maintain
open or closed position
Stainless steel shaft and corrosion resistant construction
3 independent actuators fitted in the cabinet to allow single
phase tripping
Position switch
Double break, galvanically separate contacts
Self-cleaning contacts
Transparent housing allows for contact position and mecha-nism viewing
Vacuum interrupters
Superior contact wear ensuring maximum reliability
Environmentally friendly
Built by ABB in Ratingen, Germany since 1980s
Pole assembly
Modular assembly for easy replacement in the field
UV protected for environmental durability
Molded design reduces risk of tampering
Few moving parts
10,000 full load operations without maintenance
Single molded design guarantees the longest creepage dis-
tance in the industry
1 Magnetic actuators add durability and safety | 2 Single molded poles for superior creepage | 3 ABB vacuum interrupter clean room
2 31
Recloser designHigh voltage unit technology
7/27/2019 ABB GridShield
5/24Descriptive bulletin | GridShield
HCEP insulating material
The pole insulating material is Hydrophobic Cycloa liphatic
Epoxy (HCEP). the next generation of Cycloaliphatic Epoxy
(CEP).
Hydrophobicity provides water resistance, preventing water
from developing completely wetted, resistively conductive
surfaces on outdoor insulation. As a result, leakage currents
are reduced which increases reliability by minimizing the
risk of insulation flashover. Furthermore, reducing discharge
activity translates into decreased insulator erosion and
increased insulator l ife expectancy.
Advantages
Improved water beading and runoff
Lower leakage currents and less discharge activity
Reduced flash-over probability
Less erosion of insulation
Improved performance in heavily polluted areas
Improved weatherability and outdoor aging
Prolonged life expectancy
Exceptional mechanical strength attributed to epoxy-
based design
Contamination performanceDetermined by creepage/leakage distance available on a
recloser bushing (pole), contamination performance is a very
important factor when considering the reclosers operat-
ing environment. ABB uses the HCEP insulation to not only
offer a product that far exceeds the creep required by ANSI
standards, but also to produce results that go beyond IEC
Level IV requirements for environments with very heavy pol-
lution.
IEC pollution levels
Pollution level Required Creep ratio
I - Light 0.63 in/kV (16 mm/kV)
II - Medium 0.79 in/kV (20 mm/kV)
III - Heavy 0.98 in/kV (25 mm/kV)IV - Very Heavy 1.22 in/kV (31 mm/kV)
HCEP does not become resistively conductive when exposed to moisture
Required Creep vs OVR Creep (Phase to Ground)
Pollution
Level
Rated Maximum Voltage
15 kV 27 kV 38 kV
Required Creep
in (mm)
ABB Standard
Creep in (mm)
Required Creep
in (mm)
ABB Standard
creep in (mm)
Required Creep
in (mm)
ABB Standard
Creep in (mm)
I - Light 9.8 (248) N/A 17.0 (432) N/A 23.9 (608) N/A
II - Medium 12.2 (310) N/A 21.3 (540) N/A 30.0 (760) N/A
III - Heavy 15.3 (388) N/A 26.6 (675) N/A 37.4 (950) N/A
IV - Very Heavy 18.9 (481) 38.0 (960) 33.0 (837) 38.0 (960) 46.4 (1178) 50.7 (1288)
7/27/2019 ABB GridShield
6/246 GridShield | Descriptive bulletin
GridShield 15/27/38 kV dimensions
Pole mounting frame
C C
N
O
36.0
Adjustment holes locatedat 3.0 in increments
D
R
P
Q
M- Max heightL- As shown
B
67.5
20.1
30.34
14.40
16.63
C
B
C
A
G
F
D E
H
Substation mounting frame
Rating Units A B C D E F G H L M N O P Q R
15/27 kV in 49.8 41.75 15.5 13 30 39 25.3 15.5 65.6 95.8 48 52.4 22 29.1 27.9
15/27 kV mm 1265.5 1060.5 393.7 330 763 989.6 642.6 393.7 1666 2433.3 1219.2 1330.5 558.8 738.2 708.6
38 kV in 49.8 41.8 15.5 13.3 30 45.2 30.1 15.5 71.5 101.5 48 52.4 22 29.1 34.1
38 kV mm 1265.5 1060.5 393.7 339 763 1146.9 763.9 393.7 1816 2578 1219.2 1330.5 558.8 738.2 866
7/27/2019 ABB GridShield
7/24Descriptive bulletin | GridShield
36.00 914.40
18.19 461.95
2.24 56.92
20.12 511.00
2X 10.06 255.502.82 71.74
39.17 994.89
1.34 34.149-59 FT.
.88 22.23 X 2.38 60.33 SLOT
.50 12.70
13.84 351.61
15.34 389.71
PAD LOCK
HOLE
GROUNDING LUG
1/2-13 THD
Large control cabinet - standard
Small control cabinet low profile option
9.074
[230.48]
27.500
[698.50]24.000
[609.59] 0.249
[6.33]
18.000
[457.20]
0.875
[22.23]
30.000
[762.00]
1.500
[38.10]
17.540
[445.52]
7/27/2019 ABB GridShield
8/248 GridShield | Descriptive bulletin
RER620 overview
The RER620, part of the Relion family of ABB controls, is a
dedicated IED perfectly aligned for the protection, control, mea-
surement and supervision of utility substations and industrial
power systems including radial, looped and meshed distribu-
tion networks with or without distributed power generation. The
RER620 IED is characterized by its compactness and withdraw-
able unit design.
Engineered from the ground up, the RER620 has been designed
to unleash the full potential of the IEC 61850 standard for com-
munication and interoperability. The RER620 provides main
protection for overhead lines and cable feeders in distribution
networks.
RER620 Introduction
Part of Relion family of ABB controls
Drawout design for quick and easy maintenance
Environmentally friendly design with RoHS compliance
Capable of having up to 20 binary inputs and 14 binary out-
puts
Easy integration into Ethernet or serial-based communica-
tion networks with standard: DNP3, IEC 60870-5-101, IEC
60870-5-104, Modbus, IEC 61850
Use of GOOSE messaging (peer-to-peer) for high-speed pro-
tection, transfer switching, fault isolation and service restora-tion
Interact via easy to read local HMI or remotely
Six setting groups for protection scheme flexibility
High Impedance (HIZ) fault detection creates more safety for
life around power lines
Embedded In-rush detection for added reliability connecting
distributed generation networks
Integrated loop control as standard offering
There are two loop control schemes that come with the Grid-
Shield recloser:
The traditional loop control scheme is based on voltage, over-
current and reclosing sequence.
Additional ly, there is the advanced 61850 (peer-to-peer) loop
control scheme for fault detection, isolation and restoration.
With the quick response from GOOSE messaging, the reclosers
can communicate with each other and determine where thefault is, preventing unnecessary reclosing.
Self-diagnostics
- Built-in self-diagnostics continuously monitors
the RER620 electronics and the operation of the
relay software
- Any fault or malfunction will raise an alert
Recloser controlThe future of Intelligent Electronic Devices (IEDs)
RER620 relay located inside padlockable control cabinet
Substation
CircuitBreaker
Source 1
Substation
CircuitBreaker
Source 1
B
A D
C
T
Sectionalizing
Recloser
NormallyClosed
SectionalizingRecloser
NormallyClosed
MidpointRecloser
Normally
Closed
MidpointRecloser
NormallyClosed
Tie Point
Recloser
Normally
Open
F1 F2 F31 PT
3 PT
1 PT1 PT
1 PT
3 PT
Substation
CircuitBreaker
Source 1
Substation
CircuitBreaker
Source 1
B
A D
C
T
Sectionalizing
Recloser
NormallyClosed
SectionalizingRecloser
NormallyClosed
MidpointRecloser
Normally
Closed
MidpointRecloser
NormallyClosed
Tie Point
Recloser
NormallyOpen
Interlocking data
GOOSE
RER620REF615
RER620
RER620
Interlocking data
GOOSE
Interlocking data
GOOSE
F1 F2 F31 PT
3 PT
1 PT1 PT
1 PT
3 PT
7/27/2019 ABB GridShield
9/24Descriptive bulletin | GridShield
RER620 hardware features
Drawout case
ABBs innovat ive design for the RER620 includes a standard
drawout case, allowing for quick access to relay cards for easy
field maintenance. Also included is an automatic function that
shorts CT connections to the relay when removed from the
case, making maintenance safer for the user.
Local HMI
Large, 13x14 pixel, LCD screen displays ten rows, each
capable of displaying 20 characters
Simple controls for navigation and recloser open/close
operation Normal, Pickup and Trip protection indicators for state
identification
Recloser open/close buttons let the user know current
position
11 programmable alarm LEDs - great for loss of phase and
lockout indication
14 programmable push-buttons for user customization
Customizable labeling for programmable buttons and alarms
Front RJ-45 communication port for quick laptop connection
Communication
Ethernet network communication via RJ-45 or LC fiber optic
connectors
Serial communications via RS-232, RS-485, or ST fiber opt
connection
DNP 3.0 Level 2+ over TCP/IP or serial with redundant phys
cal channel support
IEC 60870-5-101and IEC 60870-5-104
Modbus RTU/ASCII over serial and TCP/IP modes supporte
IEC 61850, with GOOSE messaging
PG&E 2179
The event generation subsystem prov ides consistent t imestping across all protocols
Simultaneously report events to five IEC 61850 clients
Input and output ports
Capable of up to 20 binary inputs and 14 binary outputs
when fully configured
6 VT inputs for voltage sensing
4 CT inputs
1 RER620 relay and drawout case | 2 IED can be controlled via a clean and easy to use HMI | 3 A variety of communication ports and I/Os to fit the users
needs
2 31
7/27/2019 ABB GridShield
10/2410 GridShield | Descriptive bulletin
PCM600
PCM600 offers extensive relay configuration functions such as
relay signal configuration and IEC61850 communication con-
figuration with GOOSE horizontal relay-to-relay messaging.
Advantages
Tool suite with numerous tools at hand, useable with and
without connection to RER620
Easy to navigate menu follows local HMI menu layout
Tab structure for easy management of open tools
Create settings ahead of time and load onto an RER620 via
RJ-45 connection
Save setting profiles and load onto other relays
Customize recloser, sectionalizer, and automated load breakswitch modes with application configuration tool
Integrated documentation for quick referencing of technical
information and communication point lists
Import and export GOOSE messages for advanced commu-
nication schemes
Graphical display editor
Visuall y display power system objects and their status
Integrate on-line measurement in the IED HMI
Set node attributes like name, name position and sort index
Extensive ANSI and IEC symbol library included
Application conf iguration tool
Function block-based programming for easy customization
Search feature and quick jump function allows for easy
navigation
View existing logic for clear understanding of recloser func-
tions
Adapt pre-configured applications
Broken up into I/O, Measurements, Control, and Protection
tabs for progamming organization
Insertable text boxes for tracking changes
Debugging for operation assurance
Disturbance handling
Records up to 12 analog channels and 64 binary channels Can be triggered by analog/binary channels or manual/peri-
odic commands
Selectable sampling rate, 32/16/8 samples per cycle
Events stored following COMTRADE standard
Export and view using ABBs WaveWin32 software or any
other COMTRADE compliant software
Records include current, voltage and angle values, and
pickup times of the protection elements
Time stamps provide useful record for analyzing in what order
events occurred
ACT tool for logic programming Change HMI screen with the Graphical Display
Editor
Disturbance handling capabilities include signal
charts for reviewing faults
7/27/2019 ABB GridShield
11/24Descriptive bulletin | GridShield
Web HMI
The web HMI enables the user to access the RER620 via a web
browser. This method of connecting to the RER620 requires
no additional software and can connect locally by connecting
a computer to the RER620 via the front communication port
or remotely over LAN/WAN. With a menu tree structure similar
to the one on the local HMI, the user does not need to spend
time relearning where every setting is located. With this useful
tool, the user has a quick means for programming most of the
recloser settings.
Overview
Local and remote access
User access level authentication On-line Help menu
Runs with Internet Explorer 7.0 or later
Features
View alarm LEDs, event lists, and measurements
Monitor signals
Read and download disturbance records
Review phasor/tabular diagrams with various representation
Phase currents
Sequence currents
Phase voltages
Sequence voltages
Zoom in phasor/tabular diagrams
Freeze current and voltage measurements to obtain a snap
shot view during testing
Set parameters
Save event lists Print settings
All sett ings can be opened and saved in CSV format
Quickly view disturbance records Choose from various phasor diagram options Make quick parameter setting changes
7/27/2019 ABB GridShield
12/2412 GridShield | Descriptive bulletin
Protection functions
The RER620 IED offers the most extensive and adaptive set of
protective functions in the industry.
High Impedance (HIZ) fault detection
High impedance faults have small current magnitudes that are
difficult to detect by standard protection. While small fault cur-
rents do not pose danger to power equipment, a high imped-
ance fault poses a deadly threat to humans and animals.
How has ABB addressed HIZ?
7 years of dedicated research and extensive field tests to
develop best solution
Created HIZ (PHIZ1) function in protection schemes
Utilize ground/earth fault current signatures in HIZ algorithm
Embedded In-rush energy detectionIn situations where distributed generation is first connected to
a main network, there is a large current pull from transformers,
which will cause a relay to trip the recloser on the line. The
traditional solution is to use communication to inform the relay
of the situation and prevent the trip. With the RER620, there is
no need for communication because of the embedded In-rush
energy detection.
Current protection
Single-Phase overcurrent protection [51P, 50P-1, 50P-2,
50P-3; 3I>(1), 3I>(2), 3I>(3)]
Overcurrent ground-fault protection [51N, 50N-1, 50N-2,50N-3; lo>(2), lo>(3), lo>>(3), lo>>>(2)]
Sensitive earth-fault protection [50SEF; lo>(3)]
Negative sequence overcurrent protection [46-1, 46-2;I2>(1),
I2>(2)]
Phase discontinuity protection [46PD; I2/I1>]
Three-phase inrush detector [INR; 3I2f>]
Directional protection
Single-phase overcurrent protection [67/51P-1, 67/51P-2;
3I>->(1), 3I>->(2)]
Ground-fault protection [67/51N-1, 67/51N-2; lo>->(1),
lo>->(1)]
Cold load timers
Cold load timer phase A [62CLD-1, 62CLD-2; TPS(1),
TPM(1)]
Cold load timer phase B [63CLD-3, 63CLD-4; TPS(2),
TPM(2)]
Cold load timer phase C [63CLD-5, 63CLD-6; TPS(3),
TPM(3)]
Voltage protection
Three-phase overvoltage [59-1, 59-2, 59-3; 3U>(1), 3U>(2),3U>(3)]
Three-phase undervoltage [27-1, 27-2, 27-3; 3U(1), U2>(2)]
Zero sequence overvoltage [59N-1, 59N-2; Uo>(1), Uo>(2)]
Frequency protection
Underfrequency, Overfrequency, Frequency rate of change
[81-1, 81-2; f,df/dt(1), f,df/dt(2)]
Load shed & restoration [81S-1, 81S-2; UFLS/R(1),UFLS/R(2)]
HIZ effects on gravel HIZ effects on grass
7/27/2019 ABB GridShield
13/24Descriptive bulletin | GridShield
Control
Autoreclosing, 1ph and/or 3ph [79; O->I]
Synchro-check/voltage check [25; SYNC]
Circuit breaker 1 (3 state inputs / 3 control outputs)
[52; IO CB]
Loop control
Supervision monitoring
CB condition monitoring [52CM; CBCM]
Fuse failure supervision [60, FUSE]
Measurement
Three-phase current [ IA, IB, IC; 3I]
Demand metering, Max/Min metering
Sequence current [I1, I2, I0; I1, I2, I0]
Ground current [IG; lo]
Three-phase voltage, source [VA, VB, VC; 3U] Three-phase voltage, load [VA, VB, VC(2); 3U(B) ]
Sequence voltages, source [V1, V2, V0; U1, U2, U0]
Sequence voltages, load [V1, V2, V0(2); U1, U2, U0(B)]
Three and single -phase power and energy [P, E]
Frequency [f]
Power factor [pf]
Recorders
Digital fault recorder (DFR) [DFR]
Sequence of events (SER) [SER]
Fault recorder [FLTMSTA]
Fault locator (FLOC) [FLO]
Other functions
High impedance fault detector [HIZ; PHIZ1]
Recloser failure protection [50BFT; 3I>/lo>BF]
Recloser close failure protection [50BFC; SCCBRBCF1]
Directional positive sequence power protection [32P; P>->]
Directional negative/zero sequence power protection
[32N; Q>->]
Battery voltage, current, battery test [UPS]
Programmable buttons (16 buttons) [FKEYGGIO1]
Move function block (8 outputs) [MVGAPC1]
Move function block (8 outputs) [MVGAPC2] Pulse timer (8 timers) [PTGAPC1]
Pulse timer (8 timers) [PTGAPC2]
Generic control points (16 outputs) [SPCGGIO1]
Generic control points (16 ouputs) [SPCGGIO2]
Set reset flip flops (8 outputs) [SRGAPC1]
Set reset flip flops (8 outputs) [SRGAPC2]
Time de lay off timers (8 timers) [TOFGAPC1]
Time de lay off timers (8 timers) [TOFGAPC2]
Time de lay on t imers (8 timers) [TONGAPC1]
Time de lay on t imers (8 timers) [TONGAPC2]
All traditional recloser, ANSI and IEC curves are also avai lable
RER620
1Io selectable by setting, Io calculated as default
52
or
Va,
Vb,
Vc
3
51P3I> 50P-13I> 50P-23I>> 50P-33I>>>
6846PD 3I2f>I2/I1I2>50BF3I>BF 46I2>
67P3I>->
51NI0>50N-1I0>50N-2I0>>50N-3I0>>>
32PP>-> 32NQ>->
50SEFI0> HIZPHIZ1 67N1I0>->
Ia, Ib, Ic4
27P3U< 59P3U> 81f 81SUFLS/R2
2Under-frequcny and df /dt based load shedding function
59PSV1> 59NV0>
60FUSEF
27P3U< 59P3U>
47NSV2>
47NSV2> V1> 59PS
59NV0>
2SYNC
0 791 LCMLCM
3In the case of ABB GridShield recloser, t hese are embedded Capacitor Voltage
Divider (CVD) with 10,000:1 ratio4
In the case of ABB GridShield recloser, these are embedded Current Transformer
(CT) with 600:1 ratio
RER620 protection diagram
7/27/2019 ABB GridShield
14/2414 GridShield | Descriptive bulletin
Nom. operating voltage: 2.4-14.4 24.9 34.5 kV
Rated max. voltage: 15.5 27 38 kV
Rated power frequency: 50/60 50/60 50/60 Hz
Rated continuous current: 800/1000/1250 800/1000/1250 800/1000/1250 A
Rated symmetrical interrupting current: 12.5/16 12.5/16 12.5/16 kA
Rated lightning impulse withstand (BIL): 110/125 125/150 150/170 kV
Dry withstand 60 Hz 1 Min.: 50 60 70 kV
Wet withstand 60 Hz 10 Sec.: 45 50 60 kV
Phase spacing 15.50 (394) 15.50 (394) 15.50 (394) inches (mm)
External creep distance, H2-ground: 38.00 (960) 38.00 (960) 50.70 (1288) inches (mm)
External creep distance, H1-H2: 45.00 (1160) 45.00 (1160) 49.80 (1260) inches (mm)
Min. external strike distance: 9.50 (240) 9.50 (240) 14.40 (367) inches (mm)
Min. interrupting time: 0.050 0.050 0.050 sec max
Max. closing time: 0.055 0.055 0.055 sec max
High voltage unit weight: 333 (150) 333 (150) 430 (195) lbs (kg)
Small control cabinet weight: 138 (63) 138 (63) 138 (63) lbs (kg)
Large control cabinet weight: 182 (83) 182 (83) 182 (83) lbs (kg)
Rated standard operating duty: O 0.2s CO 2s CO 5s CO lockout
Operating temperature: -40C to +60C (-40 F to +140F)
Control voltage:
- 120 VAC UPS: 90-140 VAC / 109 - 144 VDC
- 240 VAC UPS: 180 - 285 VAC / 220 - 285 VDC
Materials: Vacuum interrupter encapsulated in hydrophobic cycloaliphatic epoxy with stainless steel construction
Current sensors: One per phase encapsulated into the pole
Battery:
- 48 VDC, 12 AH battery bank- Sealed lead acid rechargeable battery pack
- Monitor locally and remotely
- Easy access in low voltage control cabinet
- Capable of up to 38 hours of carryover and multiple operations upon loss of power
GridShield Testing:
ANSI : Meets al l app licable recloser s tandards (Dual logo standard IEC 62271-111/IEEE C37.60 2005-11, IEEE, and IEC)
IP54 rated for water and dust intrusion
Life Test: 10,000 mechanical operations without degradation
Technical data
7/27/2019 ABB GridShield
15/24Descriptive bulletin | GridShield
Ordering guide
Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17-1
S 1 1 8 1 C D E 1 2 E 1 4 4 S A 00
1) Recloser
Ratings
S: GridShield Recloser S: GridShield
Recloser
2) Voltage 1: 15 kV 1: 15 kV
2: 27 kV
3: 38kV
3) BIL 1: 110 kV 1: 110 kV
2: 125 kV
5: 150 kV
7: 170 kV
4) Continuous
Current
8: 800 A 8: 800 A
1: 1000 A
2: 1250 A
5) Interrupting
Rating
1: 12.5 kA 1: 12.5 kA
2: 16 kA
6) Mounting
Frame
C: Pole w/ 6 Arrester
brackets & 3 PT
C- Channel Mtg Bra-
ckets, Assembled
A: Pole w/ 6 Arrester brackets , Assembled
B: Pole w/ 6 Arrester brackets,
Unassembled
C: Pole w/ 6 Arrester brackets & 3 PT C-
Channel Mtg Brackets, Assembled
D: Pole w/ 6 Arrester brackets & 3 PT C-
Channel Mtg Brackets, Unassembled
H: Pole w/ 6 Arrester brackets & Flat PT
Mtg Bracket, Assembled
R: Pole w/ 6 Arrester brackets & Flat PTMtg Bracket, Unassembled
G: Pole w/ 6 Arrester brackets & 6 PT Mtg
Brackets, Hrztl Construction, Galvanized,
Assembled
I: Pole w/ 6 Arrester brackets & 6 PT Mtg
Brackets, Hrztl Construction, Stainless
Steel, Assembled
K: Pole w/6 Arrester brackets & 6 PT Mtg
Brackets, Vertical Construction, Galva-
nized, Assembled
M: Pole w/6 Arrester brackets & 6 PT Mtg
Brackets, Vertical Construction, StainlessSteel, Assembled
V: Substation Frame, Assembled
W: Substation Frame, Unassembled
X: Substat ion Frame w/ 3 PT Mtg Bra-
ckets, Assembled
Y: Substation Frame w/ 3 PT Mtg Bra-
ckets, Unassembled
Z: Custom Frame
N: None
7/27/2019 ABB GridShield
16/2416 GridShield | Descriptive bulletin
Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17-18
S 1 1 8 1 C D E 1 2 E 1 4 4 S A 00
7) 24-pin Control
Cable
D: 40 f ee t [12 m] A: 10 f eet [3 m]
B: 20 feet [6 m]
C: 30 feet [9 m]
D: 40 feet [12 m]
E: 50 feet [15.24 m]
F: 60 feet [18.29 m]
Z: Customized (Max. length 200 ft)
N: None
8) Cable Options
for Control
Power and PT
Input
E: (1) 2 pin connector
with 45 ft cable and
(1) 5 pin connector
with 45 ft cable & 3
internal voltage inputs
directly into relay
A: (1 ) 2 p in connector wi th 20 ft cable
B: (1) 2 pin connector with 45 ft cable
C: (1) 5 pin connector with 45 ft cable & 3 internal
voltage inputs directly into relay
D: (2) 5 pin connector with 45 ft cable & 3 internal
voltage inputs directly into relay
E: (1) 2 pin connector with 45 ft cable and (1) 5 pin
connector with 45 ft cable & 3 internal voltage inputs
directly into relay
Z: Custom cable option
N: None
9) Control Power
Supply11: UPS (Input
Voltage :100V-200V)
DC/AC with 120VAC
Heater
1. UPS (90-140 VAC) with 120 VAC heater
2. UPS (90-140 VAC) with 240 VAC heater (aux power
needed for heater)
3. UPS (180-285 VAC) with 240 VAC heater
10) Binary I/O 2: 12 BI (Binary Input)
+ 10 BO (Binary
Output)
1: 4 BI (Binary Input) + 6 BO (Binary Output)
2: 12 BI (Binary Input) + 10 BO (Binary Output)
3: 20 BI (Binary Input) + 14 BO (Binary Output)
11) Control &
Faceplate
Options
E: ANSI Standard
RER620
E: ANSI Standard RER620
F: ANSI Standard RER620 with Single Phase Tripping
G: ANSI Standard RER620 with Single Phase Tripping + PG&E 2179
D: IEC Standard RER620 (comes with IEC Indicating Cup)
C: IEC Standard RER620 with Single Phase Tripipng (comes with IEC
Indicating Cup)12) Language 1: English 1: English
2: English and Spanish
13) Communica-
tion Ports and
Protocol2
4: Three ports:
Ethernet 10/100BaseT
(RJ45) + configura-
ble RS232/RS485 +
[RS485 or serial glass
fiber (ST) ]
1: Ethernet RJ-45 only (COMB01A)
2: Ethernet 100FX fiber optic with LC connector (COMB02A)
3: Ethernet RJ-45 + RS485/IRIG-B (COMB11A)
4: Ethernet RJ-45 + RS485/IRIG-B + RS232 + serial fiber optic with ST
connector (COMB23A)
14) Bushing Ter-
minal Connectors
4: NEMA 4-Hole Pad S: Stud terminal
2: NEMA 2-Hole Pad
4: NEMA 4-Hole Pad
C: Clamp15) LV Cabinet
Option
S: Small S: Small - Low profile cabinet
L : Large - Standard cabinet
16) Standard
Dynamic
Accessories
A: 69 Switch Close
Block function from
yellow handle
A: 69 Switch Close Block function from yellow handle
N: No accessories required
7/27/2019 ABB GridShield
17/24Descriptive bulletin | GridShield
Digit 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17-1
S 1 1 8 1 C D E 1 2 E 1 4 4 S A 00
17-18) Dynamic
Accessories-
Specific to unit
will change last
two digits of
style number3
00
Radio Package
(1) PT mounted and wired on recloser frame
(3) PT mounted and wired on recloser frame
(6) PT mounted and wired on recloser frame
PT animal guard with push pins (set of 3)
Anima l Guard (S traight) ( set o f 3)
Anima l Guard (L -shaped) (set of 3)
(1) 7200/12470 GY VOG-11 PT (Style Number: E-7525A95G01)
(1) 7620/13200 GY VOG-11 PT (Style Number: E-7525A95G02)
(1) 8400/14560 GY VOG-11 PT (Style Number: E-7525A95G03)
(1) 14400/24940 GY VOG-12 PT (Style Number: E7525A97G02)
(1) 11547/200000 GY VOG-12 PT (Style Number: E-7525A97G04)
(1) 20125/34500 GY VOY-20G PT (Style Number: E-75265A55G01)
Cable Animal Guard with straight pins
10 feet Armored on the control cable (this armor will be on the control cable for the first 10 feet after
LV cabinet)
Ground Connector
IEC Cups (set of 3)
Transfer switch to transfer contro l power from primary to secondary source (PTs must be ava ilab le
on line and load side )
(1) Potential test switch & (1) Current test switch (available only in large Cabinet)
(1) FT test switch 6 current 4 potential
38 kV Animal Guard (Straight) (set of 3)
Custom option
1. A separate power source, 120/240VAC, is needed for the heater if input voltage is DC. If other power supply required, please contact ABB sales representative.
2. SNTP is available for time-sync with all E thernet options. IRIG-B is available for time-sync with all RS-485 options.
3. 00 for Standard - Style numbering will change for specials & dynamic accessories.
Note: When selecting ANSI f aceplating, IEC61850, DNP3.0 Level 2 and Modbus communication protocols are automatically selected for the RER620.
An IEC facepla te sel ection will result in a selec tion for IEC61850 IEC101 and IEC104 communica tion pro tocols for the RER620.
7/27/2019 ABB GridShield
18/2418 GridShield | Descriptive bulletin
Accessories
Recloser simulator assembly
Test relay schemes or verify your protection settings with an
ABB Recloser Simulator Card without having the high voltage
unit connected to it. This is ideal for protection engineers to
verify the relay performance at their convenience.
Easy, cost effective method for testing relay schemes and
the operational health of an RER620, without operating the
recloser
Simulate fault conditions inject secondary currents up to
1 A (to simulate primary currents up to 600 A)
Software can collect oscillographic records of fault
simulations
Comes with wiring harness and power adapter for RER620 Compatible with PCM600 software
Flexitest switch
Perform secondary current and voltage injection directly into
the RER620 (ABB FT-1 option allows easy access for testing
using secondary current injection and voltage with virtually
any type of test equipment)
Use the FT-1 to test the health of the recloser PTs and CTs
No need to disconnect the 24 pin cable or phoenix plugs
Use the FT-1 to test the GridShield contacts and program-
mable I/O
Transfer switch
Quickly transfer control power between the load and source
sides of a GridShield recloser. Potential transformers (PTs) must
be connected on both the load and source sides of a GridShieldrecloser.
1 Recloser simulator card (separate harness included in kit) | 2 Flexitest switch | 3 Transfer switch
2 31
7/27/2019 ABB GridShield
19/24Descriptive bulletin | GridShield
Animal guards
GridShield animal guards provide easy-to-install protection that
reduces on animal related interruptions.
Bushing terminal accessories
All GridShield reclosers come standard with a 1- inch (25.4 mm)
diameter stud (12 threads) on all source and load terminals.
Bushing Terminal Options
NEMA Connectors Clamp Connector
2-Hole Pad 4-Hole Pad #6-800 MCM (kcmil)
Part # 12A00199H02 Part # 12A00198H02 Part # 12A00897H01
6 included 6 included 6 included
1 Straight bushing guard for 15 kV - 27 kV applications | 2 Straight bushing guard for 38 kV applications | | 3 L-shape bushing guard 15 kV - 27 kV applicatio
| 4 Cable guard for 15 kV - 38 kV applications (36 long 1 dia.) | 5 Standard terminal | 6 NEMA connector 2-hole pad | 7 NEMA connector 4-hole pad |8 Clamp connector
1
5
2
6
3
7
4
8
7/27/2019 ABB GridShield
20/2420 GridShield | Descriptive bulletin
Additional ABB devicesDesigned for improved reliability and feeder performance
Single phase by-pass switch
Provides a means for bypassing and disconnecting reclosers
or voltage regulators, allowing maintenance on equipment
without service interruption
Porcelain or silicone insulators
Mounting configurations: vertical, underhung, pole mount, or
crossarm
Avai lable ratings:
15-38 kV
600/900 A
40 kA Momentary rating
110-150 kV BIL
AutoLink single-phase electronic sect ionalizer Works as sectionalizer in conjunction with an upstream re-
closer or circuit breaker
Prevents unnecessary supply outages
Reduces replacement of fuses
Both actuating current and count can be reset as many times
as needed, making it unmatched in the industry
Detects inrush current
Compatible with ABB, S&C and AB Chance interchangeable
cutout bodies
Ideal for lateral feeders
COM600
The stat ion automation device of ABB, COM600 is an all-in-
one communication gateway, providing connectivity between
substation IEDs and network-level control and management
systems. Additionally it is capable of automatic fault isolation
and restoration.
The COM600 adds distributed inte lligence to the feeders, and
it is ideal for automation of rural li nes or whenever the user
has SCADA IDMS limitations. It is a total configurable solution
capable of providing all logic for fault detection isolation and
restoration.
1 Single-phase by-pass switch | 2 AutoLink single-phase electronic sectionalizer | 3 COM6001
32
7/27/2019 ABB GridShield
21/24Descriptive bulletin | GridShield
Service & support
Recloser customer support
Free 24/7 technical support line 1-800-929-7947 ext. 5 or
outside the U.S. +1 407-732-2000 ext. 2510, e-mail
Feeder Automation users website featuring news, FAQs,
discussion board, technical information, product brochures,
software downloads, contact information, instruction manu-
als, programming shortcuts, drawings:
www.abb.com/fa-users
Standard three year warranty
Training
Factory based training: three-day training designed for partici-
pants to become proficient application, installation, operation,maintenance, testing, and commissioning of RER620 relays and
GridShield reclosers
Advanced training
The advanced 3 day training is available upon request. It intro-
duces IEC61850 architecture and IEC61850 communications.
The participant learns the IET600 tool and how to configure
peer-to-peer IEC61850 GOOSE communications.
Day 1 topics
Introduction
GridShield with RER620 relay overview
GridShield high voltage (HV) unit overview, troubleshooting &
maintenance
GridShield control cabinet overview, troubleshooting & main
tenance, and introduction to RER620 relay
Introduction to the WebHMI interface
Introduction to Protection and Control IED Manager, PCM60
tool
Day 2 topics
Using the Graphical Display Editor, Parameter Setting Tool,
and Application Configuration Tool Setting the auto-recloser sequence for di fferent applications
Day 3 topics
DNP3 and Configuration Management tool for point remap-
ping
DNP3 objects, classes, events, deadbands and variation
explained
7/27/2019 ABB GridShield
22/2422 GridShield | Descriptive bulletin
Notes
7/27/2019 ABB GridShield
23/24Descriptive bulletin | GridShield
Notes
7/27/2019 ABB GridShield
24/24
Contact us
ABB Inc.
655 Century Point
Lake Mary, FL 32746
Phone: +1 407 732 2000
Customer service: +1 800 929 7947 ext. 5
+1 407 732 2000 ext. 2510
E-Mail: [email protected]
www.abb.com/mediumvoltage
For more information about our Feeder Automation
products, news, downloads, and Feeder Automation UsersGroup website registration, please contact:
All sales are s ubjec t to ABB Inc.
General Terms and Conditions of Sale.
While every effort has been made to assure accuracy, the
information in this document is subject to change without
notice.
Copyright 2011, 2012 ABB Inc. All rights reserved.