Air System Sizing Summary for AHU-GF-02Project Name: 2014-09-18 Cyberjaya Skypark09/25/2014Prepared by: PECE05:59PMHourly Analysis Program v.4.4Page1of1Air System InformationAir System NameAHU-GF-02Equipment ClassCW AHUAir System TypeSZCAV Number of zones1Floor Area623.2mLocationKuala Lumpur, Malaysia

Sizing Calculation InformationZone and Space Sizing Method:Zone L/sSum of space airflow ratesSpace L/sIndividual peak space loads Calculation MonthsJan to DecSizing DataCalculated

Central Cooling Coil Sizing DataTotal coil load100.9kWSensible coil load81.0kWCoil L/s at Aug 16006237L/sMax block L/s6237L/sSum of peak zone L/s6237L/sSensible heat ratio0.803m/kW6.2W/m161.8Water flow @ 8.9 K rise2.71L/s Load occurs atAug 1600OA DB / WB34.2 / 25.5CEntering DB / WB26.0 / 19.2CLeaving DB / WB15.2 / 14.6CCoil ADP14.0CBypass Factor0.100Resulting RH51%Design supply temp.14.4CZone T-stat Check1 of 1OKMax zone temperature deviation0.0K

Supply Fan Sizing DataActual max L/s6237L/sStandard L/s6221L/sActual max L/(s-m)10.01L/(s-m) Fan motor BHP0.00BHPFan motor kW0.00kWFan static0Pa

Outdoor Ventilation Air DataDesign airflow L/s729L/sL/(s-m)1.17L/(s-m) L/s/person7.80L/s/person