    100 Series

    Low-Profle Plug-inSmoke Detectors

    System Sensor 100 Series Plug-in Smoke Detectors oer

    superb perormance and reliability in a profle which is

    just 2 (5.1 cm) deep.

    Features

    Sleek,low-profiledesign

    Compatiblewith400Seriesproduct

    TwoLEDsblinkinstandby,providing360visibility

    Broadrangeofadapterbasesavailablewithbuilt-inshortingspring

    Hand-heldsensitivityreaderavailable

    Model 2151(photoelectricsensor)andmodel2151T(photoelectric

    sensorwiththermal)canbeusedwithavarietyofadapterbasesin

    severalwiringcongurationsandvoltages.Otherfeaturesinclude:

    lowcurrentdraw,stableperformanceinhighairvelocities,built-in

    tamperresistantbasedesign,remoteLEDoption,removablecover

    andbuilt-intestswitch.

    The100seriesisdesignedtomeettheperformancecriteria

    designatedbyUL. Thesensingchamberissealedagainstback

    pressureairow. Thechambertopiscoveredbyaonepiece

    moldedscreenwhichminimizestheentryofdirtandinsects. Thisscreencanberemovedforcleaning. Additionalkeyfeaturesinclude

    avarietyofmountingbasesandafulllineofaccessories.

    All100Seriesphotoelectricsmokedetectorscontainaunique

    opticalsensingchamberdesignedtosensesmokeparticles

    producedbyawiderangeofcombustionsources.Acustom

    integratedcircuitincorporatessignalprocessingtoreducefalse

    alarms.

    Model2151photoelectricdetectorsuniqueopticalsensingchamber

    isengineeredtosensesmokebyawiderangeofcombustion

    sources.Dualelectronicthermistorsadd135Fxedtemperature

    thermalsensingonmodel2151T.

    CS308 7272-1653:0122 21803025009S911

  • 7/31/2019 a05 0182system Sensor

    2/2

    3825OhioAvenueSt.Charles,IL60174

    Phone:800-SENSOR2Fax:630-377-6495

    2011SystemSensor.

    Productspecicationssubjecttochangewithoutnotice.Visitsystemsensor.comfor

    currentproductinformation,includingthelatestversionofthisdatasheet.

    A05-0182-01511/11#2709

    100 Series Plug-in Smoke Detector SpeciicationsOperating Voltage/Alarm Current SeeAdapterBaseSelectionGuidefollowing

    Standby Current 120AStandby(whenmountedinaB110LPbase)

    Sensitivity 13.18%/ft.

    Height 2.0inB401

    Diameter 4.1installedinB401;6.2installedinB110LP

    Shipping Weight 5.2oz

    Construction Flameretardantthermoplastic

    Temperature Photo:32Fto120F(0to49C);Photo/thermal:32Fto100F(0to38C)

    UL Listed Velocity Range Photo:03000fpm(015.2m/s)

    Humidity Range 10%93%RHnon-condensing

    Smoke Detector Spacing Onsmoothceilings(asdenedinNFPA72),spacingof30feet(900sq.ft.)maybeusedasaguide.Otherspacingmay

    beuseddependingonceilingheight,highairmovements,andotherconditionsorresponserequirements.

    Adapter Base Selection Guide

    Base Model Number Loop Type Current Limit Resistor Contact Type Nominal Voltage Current Draw on

    Alarm (mA)

    B110LP 2-wire* No 12/24VDC 10130

    B110RLP 2-wire* Yes 24VDC 1062

    B112LP 4-wire Yes FormA&C 24VDC 1736

    B114LP 4-wire Yes FormA&C+ASupervisory 120VAC 75mAACMax

    B116LP 2-wire* No FormC 24VDC 20100

    B401 2-wire* No 12/24VDC 10130

    *FunctionalitycontingentonpanelcompatibilityMustbelimitedbycontrolpanelFlangelessbase

    RelayContactRatings: ResistiveorInductive(60%powerfactor)load.

    FormA: 2.0Aat30VAC/DC

    FormC: 0.6Aat110VDC,2.0Aat30VDC

    1.0Aat125VAC,2.0Aat30VAC

    Ordering InormationPart No. Description

    2151 Low-prolephotoelectricdetector.MustbemountedtooneoftheB100SeriesorB400SeriesbaseslistedintheAdapterBaseSelectionGuide.

    2151T Low-profilephotoelectricdetectorwiththermal.MustbemountedtooneoftheB100SeriesorB400SeriesbaseslistedintheAdapterBase

    SelectionGuide.

    Accessories

    F110 AccessoryFlangeRingfor6Base

    RA100Z Remoteannunciatorfor2or4wiresystems,332V.Fitsstandardsinglegangelectricalbox.

    SENS-RDR Hand-heldsensitivityreader.

    SMB600 Surfacemountingkit(anged)

    EOLR-1 Endoflinerelayforpowersupervision,12/24VDCsystems.

    M02-04-01 Testmagnet.

    M02-09-00 Testmagnetwith32telescopinghandle.

    XR-2B Detectorremovaltool.Allowsinstallationand/orremovalof100SeriesdetectorheadsfrombaseinhighceilinginstallationswhenusedwithXP-4.

    XP-4 ExtensionpoleforXR-2B.Comesinthree5ft.sections.

    C58-227-01 Replacementdustcoverfor100Seriessmokedetectors.

    Junction Box Selection Guide*

    Base Model Number Single Gang 3Octagon 4Octagon 4Square 50 mm 60 mm 75 mm

    B401 No No No No Yes Yes No

    B110LP/RLP Yes Yes Yes Yes No No No

    B112LP/B116LP Yes Yes Yes Yes Yes Yes Yes

    B114LP No No Yes Yes No No No

    *Boxdepthcontingentonbaseandwiresize.RefertoNationalElectricalCodeorlocalapplicablecodesforappropriaterecommendations.