ABB Power Technologies AB 2006-04-20 Carl Öhlén © Slide 1 Rio de Janeiro April 23-25, 2006 A modular and future proof IED concept Carl Öhlén

A modular and future proof IED · PDF fileA modular and future proof IED concept ... REL670 = Lines and cables ... Extensive interoperability testing with Areva, Siemens and Omicron

Embed Size (px)

Citation preview

AB

B P

ower

Tec

hnol

ogie

s A

B

2006-04-20 Carl Öhlén

©

Slide 1

Rio de JaneiroApril 23-25, 2006

A modular and future proof IED concept

Carl Öhlén

©AB

B G

roup

-2

-20

-Apr

-06

A global activityGlobal Center HV SA Products

Västerås, Sweden (IEDs & Cx)Vaasa, Finland (MicroSCADA)Mannheim, Germany (RTU)

Global Center MV SA ProductsVasa, Finland (DA)

Global Center SA SystemBaden Switzerland

Local centersAllentown, U.S. (ANSI)Coral Springs, U.S. (EM)India, China, Russia (LP)Local Engineering Centers

Local Sales, Service & Support

©AB

B G

roup

-3

-20

-Apr

-06

A modular & future proof IED concept

Why do we need protection and controlIntroducing the ABB application of IEC 61850Advantages for an open and modular concept

Reliable - Improving the grid reliabilityEfficient - More than just a relayFlexible - Exactly what you needUser friendly - Easy to select, set, install and useInformative - Designed to communicateForever young - Futurproof migration

©AB

B G

roup

-4

-20

-Apr

-06

Imagine a world without electricity

©AB

B G

roup

-5

-20

-Apr

-06

Hot summer blackouts 2003…2004…

…continued in 2005

Dubai

Moscow

©AB

B G

roup

-6

-20

-Apr

-06

Why do we need reliable protection & control?

To rapidly detect and clear all faults with minimum effect to the grid operationTo inform about all abnormaloperating conditions and initiate necessary actionsTo rapidly facilitate the automatic and/or manual restoration to normal operationTo provide overview, information and control for efficient operation, maintenance & asset management

©AB

B G

roup

-7

-20

-Apr

-06

To detect all types of faults

ESA SBA B

ZsA ZsB

Z<

p*ZL 1-p*ZL

Rf

Z<

IAIA IBWeak End Infeed FaultsHigh Current & Faults with large DC component

IL

Faults during high load (IL)

3- phase faults

2- phase faults

High Resistance Faults

Evolving faults

1- phase faults

©AB

B G

roup

-8

-20

-Apr

-06

To operate correctly independent of transients

Primary Transientse.g.Transformer Inrushcurrent and Power Swings

Secondary Transientse.g. CT saturation and CVT transients

currentin pu

time in ms

iL1

iL2

iL3

10.0

0 20 40 60 80 100

5.0

0.0

-5.0

phase L3 current

phase L1 current

CBcloses

currentin pu

time in ms

iL1

iL2

iL3

10.0

0 20 40 60 80 100

5.0

0.0

-5.0

phase L3 current

phase L1 current

CBcloses

Advanced filtering:• Compensation for 2º, 3º and 5º harmonics• Detection of CT saturation• Detection of CT remanence• Compensation for transients

©AB

B G

roup

-9

-20

-Apr

-06

Correct information to act correctly

Repair and Maintenance

Customer Service

StationAutomation

Customer

Asset Management Engineering

Sales

Accounting

Control Centerand Office

©AB

B G

roup

-10

-20

-Apr

-06

But why do we need so many protocols?

IEC60870-6 (TASE2)IEC61970 (CIM)

Control Center Control Center

StationAutomation

StationAutomation

SPA, LON, DNP 3.0, MODBUS, UCA 2, Profibus, IEC60 870-5-103, K-Bus, ZZZ

SCADAIEC60870-5-101IEC60870-5-104DNP 3.0ELCOM 90RP570/571XXX

Metering & BillingIEC61107IEC62056IEC60870-5-102YYY

WindfarmsIEC51400-25

IEC G703IEEE C37.94WWW

IEC 61850

IEC 61850= IEC 61850

©AB

B G

roup

-11

-20

-Apr

-06

What? Where? When? Who? Which?- then How?

IED HMI

Station HSI

Control Center Office Home Anywhere(On line) (On request)

Information and control access

Substation(Automatic)

©AB

B G

roup

-12

-20

-Apr

-06Protect your assets and personnel & ensure reliable

power supplyAIS industrial and utility substations High Voltage Power Systems

The objective is always The objective is always protection & control withprotection & control withmaximum reliability & availabilitymaximum reliability & availability

Power GenerationGIS industrial and utility substations

©AB

B G

roup

-13

-20

-Apr

-06

A modular & future proof IED concept

Why do we need protection and controlIntroducing the ABB application of IEC 61850Advantages for an open and modular concept

Reliable - Improving the grid reliabilityEfficient - More than just a relayFlexible - Exactly what you needUser friendly - Easy to select, set, install and useInformative - Designed to communicateForever young - Futurproof migration

©AB

B G

roup

-14

-20

-Apr

-06

The next step in technology for ABBProducts for protection, monitoring and control of distribution and transmission networks & electrical processes in industries and power plants

Today’s protection and control products are an evolution from more than 100 years of experience of relays and more than 20 years experience of numerical protection, digital communication & substation automation

ABB has delivered more than 10 millions relays and 500 000 IEDs to more than 100 countries on all continents

We now introduce a unique and open concept based on the new standard = IEC 61850IED 670, PCM 600 e MicroSCADA Pro

IED = Intelligent Electronic Device

©AB

B G

roup

-15

-20

-Apr

-06

The next step in our IED evolution

100 – series200 – series300 – series500 – series

+ Further enhanced algorithms+ Further increased functionality+ Further improved tools+ New user friendly HMI+ Full IEC 61850 implementation= Introducing IED 670ONE powerful and open IEDfor ALL transmission applications

©AB

B G

roup

-16

-20

-Apr

-06

One Future proof IED for ALL applications

©AB

B G

roup

-17

-20

-Apr

-06A major leap in Substation Automation

IED = Intelligent Electronic DeviceIED 670 for ALL protection and control of

transmission applications

REL670 = Lines and cablesRET670 = Transformers and Multple objects

RED670 = Multi terminal networksREC670 = Control for one or several bays

REB670 = Bus & BreakerPCM 600 = Configuration & Monitoring

MicroSCADA Pro, Gateway & RTU

ABB introduce the first open concept

for protection and control of transmission

applications designed for the new

IEC 61850 standard

©AB

B G

roup

-18

-20

-Apr

-06

Introducing IEC 61850 for protection and control

The ability for IED’s from one or severalmanufacturers to exchange information and use

the information for their own functions

The standard shall support different architecture and allow a free allocation of

functions. E.g. it must work equally well for centralized or decentralized systems.

The standard shall be future proof, i.e. it must be able to follow thed progress in

communication technology as well as evolvingsystem requirements

©AB

B G

roup

-19

-20

-Apr

-06

What is 61850 Open Communication?Basics:

Ethernet 100 MBpsStation Bus 61850 8-1 Process Bus 61850 9-2 Bay-to-bay communication (Goose)Common Object Modeling (logical nodes) and Configuration Language (SCL)

Much more than a protocol:Modularization and structuring of dataStandardized Logical NodesAllocation of functions to any IEDStructured engineering & services

A reliable, simple and fast wayto build YOUR future proof

Substation Automation

“Combining the best properties in a new way...”

©AB

B G

roup

-20

-20

-Apr

-06

ABB's Experience and Status> 20 years experience of EMS, SCADA, SA and DA solutions

ABB is global leader in automationFirst Ethernet SA system & SPA 1984First LON SA system 1994

Driving force in standardization committees

13 permanent members in TC57 !

Extensive interoperability testing with Areva, Siemens and Omicron

IEC61850 References First High Voltage IEC61850 multi-vendor installation in service> 50 stations on order> 200 project proposals

Part 6Substation Configuration Language (SCL)Communication model Parts 7-1 to 7-4

Communication requirements Part 5

System and Project management Part 4

Glossary Part 2

Introduction and overview Part 1

General requirements Part 3

Part 10Conformance testing

Part 9Part 9-1

Part 9-2

Part 8-1 : Mapping for MMS-TCP/IP-Ethernet

Part 8-x : for Future Use

100 Mbit/s redundant switched Ethernet ring

Bay Level

Station Level/ Gateway

IEC101

GPS

Kema Simulator

KemaAnalyser

380kV Laufenburg

©AB

B G

roup

-21

-20

-Apr

-06

Interoperability demo (June 2005 Brazil)

©AB

B G

roup

-22

-20

-Apr

-06

Now are we ready

©AB

B G

roup

-23

-20

-Apr

-06

Substation Automation designed for IEC 61850Remote control (NCC) Office

Bay Level

Station Level

Station or interbay bus (LAN)Optical EthernetIEC61850-8-1

Station ComputerHSI

StationGatewayor RTU

REB 670 REC 670REL 670RED 670 RET 670

SMS & PCMTCP/IP LAN

Station or interbay bus (LAN)Optical LON

Optional IEC 870-5-103 or SPA

Process bus (LAN)IEC61850-9-2

Remote binary and analoguesignal transfer

©AB

B G

roup

-24

-20

-Apr

-06

GOOSE - Horizontal communication for ALL IEDs

GOOSE = Generic Object Oriented System-wide Events

Data to be sent to other IEDs are defined in the engineering tool

GOOSE

Peer to peer communication

An IED sends information by multicasting

Only IEDs which are defined to listen (subscribers) receive this message

ProtectionControlProtectionControl Control &Protection

©AB

B G

roup

-25

-20

-Apr

-06

Modular I/O in different “boxes” and HMI

1/1 Case

Option 1:•1TRM = 12 AI•< 14 I/O modules

Option 2:•2TRM = 24 AI•< 11 I/O modules

BIM(max 11/14)

16 binary inputs

The same I/O modules as in the REx5xx series

BOM(max 4)

24 binary outputs

IOM(max 6)

6 Transducer inputs,setting range + 20 mA

MIM(max 4)

12 binary outputsand 8 binary inputs

©AB

B G

roup

-26

-20

-Apr

-06

Hardware independent function libraryB24PDIF 87B Bus differential protection 24 baysL6CPDIF 87L Line differential protection 6 x 3 inputsT3WPDIF 87T Transformer differential protection 3 x 2 x 3 inputsREFPDIF 87N Low impedance differential protectionHZ PDIF 87 High impedance differential protection

ZMQPDIS 21 Distance protection5 or 2 x 2 zonesFull scheme

PH4POCM 51/67 Overcurrent protection 4 steps x 6EF4PEFM 51N/67N Overcurrent protection 4 steps x 6POVM 27/59 Overcvoltage protectionPTUF 81 Under frequency protectionPTOF 81 Over frequency protectionPVPH 24 Over excitation protectionLPTTR 26 Overload protectionPGPF XXX Programmable general current/voltage function CustomizedCRBRF 50BF Breaker failure protectionRSYN 25 Synchro checkRREC 79 Auto reclosingCSWI Control 6 bays / 30 objectsRFLO Fault locatorRADR Disturbance reporting 100 x 40MMXU MeasurementMMTR Pulse counter

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR49

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27PGPF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

This is an example of functions included in the library. For full details please consult the buyer’s guide.

©AB

B G

roup

-27

-20

-Apr

-06

Flexible allocation of functions to any IED

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR49

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27PGPF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

PDIS21

RREC79

MMTR

PDIS21

POCM51/67

RBRF50BF

RREC79

RSYN25

MMXUMMTRCSWI

PDIF87L

PDIS21

PDIFHZ

POCM51/67

RBRF50BF

RREC79

RSYN25

MMXUMMTRCSWI

PDIF87T

PGPF

PVPH24

B24PDIF 87B Bus differential protection 24 baysL6CPDIF 87L Line differential protection 6 x 3 inputsT3WPDIF 87T Transformer differential protection 3 x 2 x 3 inputsREFPDIF 87N Low impedance differential protectionHZ PDIF 87 High impedance differential protection

ZMQPDIS 21 Distance protection5 or 2 x 2 zonesFull scheme

PH4POCM 51/67 Overcurrent protection 4 steps x 6EF4PEFM 51N/67N Overcurrent protection 4 steps x 6POVM 27/59 Overcvoltage protectionPTUF 81 Under frequency protectionPTOF 81 Over frequency protectionPVPH 24 Over excitation protectionLPTTR 26 Overload protectionPGPF XXX Programmable general current/voltage function CustomizedCRBRF 50BF Breaker failure protectionRSYN 25 Synchro checkRREC 79 Auto reclosingCSWI Control 6 bays / 30 objectsRFLO Fault locatorRADR Disturbance reporting 100 x 40MMXU MeasurementMMTR Pulse counter

This is an example of functions included in the library. For full details please consult the buyer’s guide.

©AB

B G

roup

-28

-20

-Apr

-06

Configure your “best” IED from the libraryG

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR49

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27

RBRF50BF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

RET 670

REB 670

REL 670

RED 670

REB 670

RET 670

RED 670

You can even configure ONE IED for transformer protection, line protection, bus protection and control at the same time

You can upgrade and change the IED atany time (even on-line over LAN/Ethernet)

©AB

B G

roup

-29

-20

-Apr

-06

Configure your “best” IED from the library

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR26

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27PGPF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

PDIS21

PDIFHZ

POCM51/67

PEFM51/67N

RREC79

RSYN25

MMTR MMXU

PDIS21

PDIFHZ

POCM51/67

PEFM51/67N

RREC79

RSYN25

MMTR MMXU

PDIF87L

RBRF50BF

RBRF50BF

POVM59

PDIS21

PDIFHZ

POCM51/67

PEFM51/67N

RREC79

RSYN25

MMTR MMXU

RBRF50BF

RBRF50BF

POVM59

PDIF87T

RBRF50BF

RBRF50BF

CSWI

CSWI

CSWI

CSWI

PVPH24

PTTR26

REL 670

RED 670

RET 670

©AB

B G

roup

-30

-20

-Apr

-06

Bus 1A

CB 1

Line 1A

Line 1B

CB 2

Transformer 1A

Transformer 1B

T- connection

CB 3

Bus 2 A

Bus 1B

Bus 1B

Control 1

Control 3

Optimize with free allocation of functions to any IED

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR26

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27

RBRF50BF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

Control 3

©AB

B G

roup

-31

-20

-Apr

-06

Bus 1A

CB 1

Line 1A

Line 1B

CB 2

Transformer 1A

Transformer 1B

T- connection

CB 3

Bus 2 A

Bus 1B

Control 1

Control 3

Control 3

Optimize with free allocation of functions to any IED

PDIS21

PDIF87L

RBRF50BF

RBRF50BF

RBRF50BF

PDIF87B

PDIF87B

PDIF87B

PDIFHZ

PDIF87B

PDIS21

CSWI

CSWI

CSWI

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR26

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27

RBRF50BF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

©AB

B G

roup

-32

-20

-Apr

-06

Bus 1A

CB 1

Line 1A

Line 1B

CB 2

Transformer 1A

Transformer 1B

T- connection

CB 3

Bus 2 A

Bus 1B

Control 1

Control 3

Control 3

E.g. RBRF (50BF) andPIOC (50) in all IEDs

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR26

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27

RBRF50BF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

©AB

B G

roup

-33

-20

-Apr

-06

Bus 1A

CB 1

Line 1A

Line 1B

CB 2

Transformer 1A

Transformer 1B

T- connection

CB 3

Bus 2 A

Bus 1B

Functional integration in any IEDPDIF87B

PDIF87B

PDIS21

PDIF87L

PDIS21

PEFM51/67N

RBRF50BF

RBRF50BF

RREC79

RREC79

MMXU

MMTRCSWi

PDIF87T

PDIFHZ

RBRF50BF

PDIS21

PDIFHZ

PDIFHZ

REB 670

REL 670

RED 670

REC 670

RET 670

REL 670

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR26

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27

RBRF50BF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

©AB

B G

roup

-34

-20

-Apr

-06

Bus 1A

CB 1

Line 1A

Line 1B

CB 2

Transformer 1A

Transformer 1B

T- connection

CB 3

Bus 2 A

Bus 1B

You can move, change and upgrade at any timePDIF87B

PDIF87B

PDIS21

PDIF87L

PDIS21

PEFM51/67N

RBRF50BF

RBRF50BF

RREC79

RREC79

MMXU

MMTRCSWi

PDIF87T

PDIFHZ

RBRF50BF

PDIS21

PDIFHZ

PDIFHZ

REB 670

REL 670

RED 670

REC 670

RET 670

REL 670

POVM59

PVPH24

RBRF50BF

RREC79

MMXUMMTR

RSYN25

CSWI

PTUF81

PTOF81

PSCHPTTR26

POVM59

PVPH24

POCM51/67

PIOC50N

PUVM27

RBRF50BF

PIOC50

PEFM51/67N

PDIFREF

PDIFHZ

PDIF87T

PDIF87L

PDIS21

PDIF87B

©AB

B G

roup

-35

-20

-Apr

-06

The old way with many “Boxes”Different hardwareDifferent softwareDifferent protocol convertersDifferent spare partsDifferent toolsDifferent maintenanceA lot to learn and manage

©AB

B G

roup

-36

-20

-Apr

-06

ABB introduces the first IED concept for protection & control of transmission grids fully designed for IEC 61850open standard

ONE common IED of transmission class for all protection & control applications

ONE common Application Function Library with high performing algorithmswhich is hardware independentONE common concept for ALL transmission applications

A major leap in Substation Automation

©AB

B G

roup

-37

-20

-Apr

-06

ONE IED 670 for ALL TransmissionREL 670 (Lines & Cables)RED 670 (Multi terminal Networks)RET 670 (Transformers & Multi objects) REB 670 (Bus & Breakers)REC 670 (Switchgear Bays)

ONE PCM 600 IED toolConfiguration & SettingMonitoring & Disturbance upload

ONE MicroSCADA ProSubstation Automation & HSIIntegrated or separate Gateway

ONE SA concept designed forthe IEC 61850 open standard

The first SA concept designed for IEC 61850

©AB

B G

roup

-38

-20

-Apr

-06

We can deliver what you wantThe same old Protection & Control design..

Separate primary and secondary protection

Separate control in RTU or bay controller

..but with improved selectivity & functionalityParallel algorithms (E.g. 87T, 87, 21, 4x 51/ 67)

Up to 6 x 3 Restrained Inputs (87T, 87L)

Integrated Protection & ControlAll bay protection & control in one IED 670

Connected to metering & protection cores

Optimized Protection & Control Functionality requirements

Redundancy & service requirement,

HMI requirement

©AB

B G

roup

-39

-20

-Apr

-06

A modular & future proof IED concept

Why do we need protection and control

Introducing the ABB application of IEC 61850

Advantages for an open and modular conceptReliable - Improving the grid reliability

Efficient - More than just a relay

Flexible - Exactly what you need

User friendly - Easy to select, set, install and use

Informative - Designed to communicate

Forever young - Futurproof migration

©AB

B G

roup

-40

-20

-Apr

-06

Unique modular solution provider with ONE extensive function library & ONE expandible I/O for protection and control

Hardware independent modular concept for ALL applications in Power Transmission SystemsIED670 is fully designed for IEC 61850, TCP/IP and high speed EthernetCan handle multiple objects and algorithms in parallel

Provides efficient substation automation solutions for any high voltage application

It is efficient

Presenting the magic IED

©AB

B G

roup

-41

-20

-Apr

-06

The most powerful “relay” ever designed

©AB

B G

roup

-42

-20

-Apr

-06

The most powerful “relay” ever designed

A/D5 kHz

~~~

~~~

Fundamental 50/60 Hz2nd, 3rd, 5th

Memory, HMI, IEC 61850, IEC 60870-5-103, SPA, LON, TCP/IP etc.

Protection communication (E.g. Transfer trip, differential current )

PSCHRREC

RDREMMTR

RSYN

RFLO

PDISPTOF

RDIFPGPF

PTUF

PFRC

PTOCRBRF

POVMPUVM

PTTR

RPLD

PSOFRPSB

PEFMPOCM

PDIS

PIOS Logic

Trip&

SignalMatrix

PTRC

GGIO

I/O

Up to 24 analog inputs(E.g. 12 I & 12 V)

Disturbance recorder forUp to 40 channels and100 disturbances

600 MHz CPU withall functions mapped

as IEC 61850

600 MHz CPU withall functions mapped

as IEC 61850

Up to 14 I/O modules(E.g. 96 BO + 160 BI)

©AB

B G

roup

-43

-20

-Apr

-06

ONE open IED designed for IEC 61850State-of-the-art 600 MHz CPU

Fast and accurate execution of high performance algoritms

Possibility to run several high performing algorithms in parallel

Up to 24 Analog InputsCan handle multi breaker, multi feeder

and multi winding inputsCan be connected to both protection

and metering cores

Multi page HMI & scalable I/OCan handle up to 6 bays/6 pagesCan handle up to 250 BI/BOCan integrate both protection and

control

©AB

B G

roup

-44

-20

-Apr

-06

Select from the Application Function LibraryFor any application!

©AB

B G

roup

-45

-20

-Apr

-06

Unique high performance concept for ALL transmission applications in ONE IED

Global power system & substation know how “Made in ABB” ensures reliable algorithmsPowerful Transmission Standard IED/CPU gives faster and more accurate operationUnique multiple & adaptive algorithms ensures maximum dependability andsecurity with speed and selectivity.Evolution from the well proven 316 & 500 series ensures quality

Ensures grid reliability through innovation, experience and commitment - Made in ABB

It is reliable

Introducing the most reliable IED ever designed

©AB

B G

roup

-46

-20

-Apr

-06

Based on Power System Know-how and experienceReliability = Dependability + SecurityDependability = Speed + SenstivitySecurity = Selectivity + Stability

REB 670 RTDS simulation10 ms operating time

©AB

B G

roup

-47

-20

-Apr

-06

Optimizing the protection of your network

½ Cycle for Bus & Transformer Faults

1 Cycle for Line faultsand ½ cycle for close-in faults

Inter turn faultsand CT saturation

Single-pole, high loadhigh resistance

Parallel algorithms

©AB

B G

roup

-48

-20

-Apr

-06

Unique open system which can be configured for integrated or distributed protection & control architecture

Pre configured for all protection and control applications.......or freedom to distribute all functions & logical nodes in any IEDUnique library of optimized algorithms + “customizer” to solve special functions

You can tailor the protection & control of your substation for the performance, redundancy and cost you want to have

It is flexible

Exactly what you want

©AB

B G

roup

-49

-20

-Apr

-06

Select your perfect hardware

©AB

B G

roup

-50

-20

-Apr

-06

As pre-configured or open configuration

©AB

B G

roup

-51

-20

-Apr

-06

Select your prefered architechtureIntegration, Redundancy etc.

Establish type & number of IEDsREL, RED, RET, REC, REB

Decide IED functionalityIdentify the need for I/OSelect the size (½ , ¾, 1/1 ) Select type of HMI

Select communicationDownload your configurationSet I/O input to you primary circuitsAdjust setting & commission

Ready to operate but you canchange and update at any time

ONE modular concept for ALL applications

©AB

B G

roup

-52

-20

-Apr

-06

Unique information management of data, disturbances and events with seamless integration to TCP/IP, MicroSCADA Pro and via ABB powerful gateway concept

Monitoring communication for up to 40 analog channels and 100 disturbances per IEDProtection communication with built in analog and binary remote communication (transfer trip + Id)Control communication with built in optical Ethernet ports (2 + 2) for IEC 61850

Improved availability and asset management through right information, in right time, to the right user, for right decisions

com municate

It is informative

Right information in right time for right actions

©AB

B G

roup

-53

-20

-Apr

-06

NCC

Separate Gateway/RTUCOM 500, COM 610,

COM 581 or RTU 560

IEC 61850-8-1

TCP/IP

Operators workstationMicroSCADA Pro

SYS 600 (with GW)

Remote SMS workplacewith PCM 600

Remote Binaryand Analog

communication

Optional SPA/LON

IEC 870-5-103

IEC 61850 Made in ABB

©AB

B G

roup

-54

-20

-Apr

-06

MicroSCADA Pro with new graphics

©AB

B G

roup

-55

-20

-Apr

-06

Example of ABB SA solution

©AB

B G

roup

-56

-20

-Apr

-06

IED 670 Communcation options

©AB

B G

roup

-57

-20

-Apr

-06

IED 670 Control options

©AB

B G

roup

-58

-20

-Apr

-06

Unique, simple and fast interaction via built in multi page HMI, Ethernet connection & LAN TCP/IP with different user access

Ready to use & fast to deliver products with simple setting and signal matrix tool

ONE common Protection & Control IED Manager (PCM 600) and one common MicroSCADA Pro

ONE IED to learn, ONE IED to apply, ONE IED to operate , ONE IED to maintain

Simple to manage for all users

It is user friendly

IED 670 is designed for YOU

©AB

B G

roup

-59

-20

-Apr

-06

Local HMI and local/remote PC access

©AB

B G

roup

-60

-20

-Apr

-06

Protection & Control IED Manager PCM 600Project Manager

Application Configuration (CAP)

SCL file export/import

Parameter Setting (PST)

Signal Matrix (SMT)

Graphical Display Editor (GDE)

Disturbance Handling (DH)

Task Scheduler (Scheduler)

Monitoring (MON)

Event Viewer (EV)

©AB

B G

roup

-61

-20

-Apr

-06

Protection & Control IED Manager PCM 600

©AB

B G

roup

-62

-20

-Apr

-06

Protection & Control IED Manager PCM 600

©AB

B G

roup

-63

-20

-Apr

-06

PCM 600 Disturbance Handling ToolRecordings List

Report Tool

Open recordings for evaluation

Recording management

Manual trig of IED

Read from IED

Import/Export in COMTRADE format

Delete

Recordings List layout

Default template

e-mail-list

Template Editor

©AB

B G

roup

-64

-20

-Apr

-06

REL670 – Line/Cable1 or 2 CB – 1 or 3 phase

RED670 – Multi terminal1 or 2 CB – 1 or 3 phase

3 or 5 line ends

RET670 – Transformer2 Winding - 1 or 2 CB/w

3 Winding – 1 or 2 CB/w

REC670 – Bay 1 or 2 Breaker

1 ½ Breaker

REB670 - Bus3-phase for 8 feeders

1-phase for 24 feeders

Summation for 24 feeders

IED 670 pre-configured for transmission

©AB

B G

roup

-65

-20

-Apr

-06

A unique & open concept with ONE IED, ONE library, ONE MicroSCADA Pro and ONE common tool fully designed for IEC 61850 open standard

Designed for 61850 from the start –and not an after thoughtUnique application function library independent of hardware & mapped in IEC61850 allows future upgrades Clear migrartion path for IEDs and MicroSCADA Pro with SPA, LON, IEC 60850-5-103, OPC, TCP/IP

Adds value to your investment for the total life cycle

It is forever young

State-of-the art IED “Made in ABB”

©AB

B G

roup

-66

-20

-Apr

-06

Comparing communication protocols

©AB

B G

roup

-67

-20

-Apr

-06

KEMA Certificate and inter operability

©AB

B G

roup

-68

-20

-Apr

-06

ABB System Verification Center

©AB

B G

roup

-69

-20

-Apr

-06

LON

TCP/IP

Optional SPAIEC 870-5-103

Migration Made in ABB with LON

©AB

B G

roup

-70

-20

-Apr

-06

IEC 61850-8-1

TCP/IP

Optional SPA/LONIEC 870-5-103

Migration Made in ABB with IEC 61850

©AB

B G

roup

-71

-20

-Apr

-06

IEC 61850-8-1

TCP/IP

Optional SPA/LONIEC 870-5-103

Interoperability Made in ABB

Third party IED

Other protocol (IEC 870-5-103, DNP 3.0 etc.)

Omicron test planwith Goose

©AB

B G

roup

-72

-20

-Apr

-06

IED 670 deliveries and FAT

Brazil: IED 670, MicroSCADA Pro and LON India: IED 670, MicroSCADA Pro and IEC 61850

©AB

B G

roup

-73

-20

-Apr

-06

IED 670 deliveries and FATNorway RED 670 installation Finland REB 670 FAT

Jordal

RED670

Matre

Seim

Padöy

RED670

RED670 Internet

40 km 30 km

30 km

©AB

B G

roup

-74

-20

-Apr

-06

Two Gold medals

©AB

B G

roup

-75

-20

-Apr

-06

Selected ABB IEC 61850 References