Protection 01 VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications: Vamp 300 IED features a modular design that allows user-defined conventional protection and arc flash protection solutions both in new and existing power distribution systems. 2. New improved integrated arc protection: New arc option modules with either two, four or six point sensors or one fibre and four point sensors together with high speed outputs provides faster operation time if an arc fault occurs. 3. Local push buttons for object control: New password protected and easy to use control buttons for breaker controlling. The Vamp 300 IED is modular and fully supervised unit that can be adapted for a wide range of applications. Free-of-charge Vampset relay management software ensures easy commissioning, configuration and system maintenance. The Vamp 300 series IED is based on the proven technology of Vamp protection relays and arc flash protection systems. Its modular design also allows you to add functionalities to existing systems, thus extending the investment life. Optional fibre or point sensor interface enable less than 2 ms operation time for arc protection. The modularity of the VAMP 300 IED also allows a wide selection of communication protocols, including IEC 61850, Profibus DP, Modbus TCP, Modbus RTU, DNP 3.0, DeviceNet, IEC 60870-5-101, 60870-5-103, DNP TCP, IEC 60870-5-101 TCP and SPA-Bus. Vamp - pioneer in arc flash protection

VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

Protection 01

VAMP 300 SeriesModular IED > design your own protection relay

BENEFITS OF MODULAR DESIGN

1.AmodularIEDfordifferentapplications:Vamp300IEDfeaturesamodulardesignthatallowsuser-definedconventionalprotectionandarcflashprotectionsolutionsbothinnewandexistingpowerdistributionsystems.

2.Newimprovedintegratedarcprotection:Newarcoptionmoduleswitheithertwo,fourorsixpointsensorsoronefibreandfourpointsensorstogetherwithhighspeedoutputsprovidesfasteroperationtimeifanarcfaultoccurs.

3.Localpushbuttonsforobjectcontrol:Newpasswordprotectedandeasytousecontrolbuttonsforbreakercontrolling.

The Vamp 300 IED is modular and fully supervised unit that can be adapted for a wide range of applications. Free-of-charge Vampset relay management software ensures easy commissioning, configuration and system maintenance.

The Vamp 300 series IED is based on the proven technology of Vamp protection relays and arc flash protection systems. Its modular design also allows you to add functionalities to existing systems, thus extending the investment life. Optional fibre or point sensor interface enable less than 2 ms operation time for arc protection.

The modularity of the VAMP 300 IED also allows a wide selection of communication protocols, including IEC 61850, Profibus DP, Modbus TCP, Modbus RTU, DNP 3.0, DeviceNet, IEC 60870-5-101, 60870-5-103, DNP TCP, IEC 60870-5-101 TCP and SPA-Bus.

Vamp - pioneer in arc flash protection

Page 2: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

02Protection VAMP 300 Series

Build your own protection IED suitable to your applicationUser may decide the hardware and software of the unit with the order code. Various I/O modules and communication options bring more flexibility to the protection application.

QUICK SELECTION TABLE

Inputs and outputs

Modularity ensures a wide range of DI / DO combination as per customer demand.

The table shows number of DI / DO for few optional module combinations. Maximum amount of DI can be 40 pcs and DO 22 pcs but not at a same time.

Protection functions

Coming now, feeder and motor protection include necessary protection functions and modern control features for basic and demanding applications.

Protection A= 3L + U + Io (5/1A)

B = 3L+4U+Io (5/1A) C = 3L+4U+2Io (5+1A) D = 3L+4U+2Io (1+0.2A)

Feeder Motor Feeder MotorArc protection (option) Phase overcurrent (50/51) Directional phase overcurrent (67) Cold load pick-up Thermal overload (49) Earth fault (50N/51N) Directional earth fault (67N) Intermittent earth fault (67N-IEF) Undervoltage (27) Overvoltage (59) Neutral voltage (59N) Phase undercurrent (37) Unbalance (46) Phase sequence (47) Directional power (32) E cessive starts (48) Successive starts (66) Magnetising inrush (68F2) Frequency (81H/81L) Synchrocheck (25) Rate of change of frequency (81R) Recloser (79) Breaker failure (50BF) Programmable stage 1-8 (99)

Inputs and outputs combination examplesDI (pcs) 31 30 26 22 18 16 12DO (pcs) 14 10 10 14 18 10 14

EXTENSION SLOTS

The optional integrated arc protection provides new dimension to protection scheme.

Inputs and outputs combination examplesDO (pcs) 6 10 14 18DI (pcs) 36 30 16 10

1 2 3 4 5 8

6

9

= single phase

Page 3: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

03Protection VAMP 300 Series

Application F = Feeder (Slot 8: HW = A, B, C or D) Vamp 300 feeder IEDM = Motor (Slot 8: HW = A, B, C or D) Vamp 300 motor IED

Supply voltage [V] C = Power C 110 - 240 (80 .. 265 Vac/dc, 5 x DO heavy duty, A1, SF)D = Power D 24 - 48 (18 .. 60Vdc, 5 x DO heavy duty, A1, SF)

I/O Card I A = None B = 3BIO+2Arc (3 x BI/BO, 2 x Arc sensor, T2, T3, T4) C = F2BIO+1Arc (Fibre 2 x BI/BO, 1 x Arc loop sensor, T2, T3, T4)G = 6DI+4DO (6 x DI, 4 x DO) I = 10DI (10 x DI)

I/O Card II A = None G = 6DI+4DO (6 x DI, 4 x DO) I = 10DI (10 x DI)

I/O Card III A = None G = 6DI+4DO (6 x DI, 4 x DO) I = 10DI (10 x DI)

I/O Card IV A = None G = 6DI+4DO (6 x DI, 4 x DO) I = 10DI (10 x DI)

Option card I A = None D = 4Arc (4 x Arc sensor)

Future option A = None

Analog measurement card (See application) A = 3L+U+Io (5/1 A) B = 3L+4U+Io (5/1 A) C = 3L+4U+2Io (5+1 A)D = 3L+4U+2Io (1+0.2 A)

Communication interface I A = None B = RS232 C = RS232+RJ (RS232 + Ethernet RJ-45 100 Mbs)D = RS232+LC (RS232 + Ethernet LC 100 Mbs)

Future option A = None

Display typeA = 128 x 64 LCD matrix

DI treshold voltage1 = 24 VDC / 110 VAC2 = 110 VDC / 220 VAC3 = 220 VDC

V300- - - A A -

SLOT NUMBERS

1 2 3 4 5 6 7 8 9 10

Order Codes

C = RS232+RJ (RS232 + Ethernet RJ-45 100 Mbs)

B = 3BIO+2Arc (3 x BI/BO, 2 x Arc sensor, T2, T3, T4)

G = 6DI+4DO (6 x DI, 4 x DO)

D = RS232+LC (RS232 + Ethernet LC 100 Mbs)

Page 4: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

Protection VAMP 300 Series 04

ACCESSORIES

The VAMPSET software is future-proof, supporting future updates and new VAMP products.

Order code Description NoteVX052-3 USB programming cable (Vampset) Cable length 3mVX067 VAMP 300/321 split cable for COM1-2 and COM 3-4 ports Cable length 3m

VSE001PP Fiber optic Interface Module (plastic - plastic) Max. distance 1 kmVSE001GG Fiber optic Interface Module (glass - glass) Max. distance 1 kmVSE001GP Fiber optic Interface Module (glass - plastic) Max. distance 1 kmVSE001PG Fiber optic Interface Module (plastic - glass) Max. distance 1 kmVSE002 RS485 ModuleVSE009 DeviceNet module

VPA3CG Profibus DP fieldbus option boardVX072 VAMP 300/321 profibus cable Cable length 3m

3P014 MOXA TCF-90 Max. distance 40 kmVX048 RS232 converter cable for MOXA TCF-90 Cable length 3 m3P022 MOXA TCF-142-S-ST Max. distance 40 kmVX062 RS232 converter cable for MOXA TCF-142-S-ST Cable length 3 m

VA 1 DA-6 Arc Sensor Cable length 6 mVA 1 DA-20 Arc Sensor Cable length 20 mVA 1 DA-6s Arc Sensor, shielded Cable length 6 mVA 1 DA-20s Arc Sensor, shielded Cable length 20 mVA 1 EH-6 Arc Sensor (Pipe type) Cable length 6 mVA 1 EH-20 Arc Sensor (Pipe type) Cable length 20 mARC SLm-x Fibre sensor, 8 000 lx x = fibre lenght (1

VIO 12 AB RTD Module, 12pcs RTD inputs, RS 485 Communication (24-230 Vac/dc)

VIO 12 AC RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (24 Vdc)

VIO 12 AD RTD/mA Module, 12pcs RTD inputs, PTC, mA inputs/outputs, RS232, RS485 and Optical Tx/Rx Communication (48-230 Vac/dc)

VYX695 Projection for 300-serie Height 45 mm

Note 1. Fibre lengths 1, 5, 10, 15, 20, 25, 30, 35, 40, 50, 60 or 70 m

VAMPSET setting and configuration tool VAMPSET is a user-friendly, free-of-charge relay management software for setting parameters and configuring VAMP relays. Via the VAMPSET software, relay parameters, configurations and recorded data can be exchanged between PC and VAMP relays. Supporting the COMTRADE format, VAMPSET also incorporates tools for analysing relay events, waveforms and trends from data recorded by the relays, e.g. during a network fault situation.

Using a standard USB communication cable the PC running VAMPSET connects to the front port of the VAMP relays. The VAMPSET software also supports TCP/IP communication via an optional port. Featuring true multi-language support the software runs on Windows 7 / Vista / XP / 2000 / NT and Windows 98 / 95 without any need for configuration of the PC.

Page 5: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

Protection VAMP 300 Series 05

CommunicationVAMP is a communication expert with a wide experience in interfacing with different system integrators’ and SCADA suppliers’ RTUs, PLCs, gateways etc. using many different protocols. Flexible adaptation of the communication protocols together with powerful and easy to use software tools are the key of successful integration.

VAMP 300 IED and the VAMPSET tool provide access to practically any power system information you may need.

DeviceN

et

External I/O: M

odbus

IEC-101

IEC-103

ModBus

Profibus DP

SpaBus

Ethernet IP

IEC-61850

ModBus TCP

None

DN

P 3.0

GetSet

RS-485

Profibus

Ethernet

Devive Net

Profibus

RS-232

Serial fiber

RS-485

Exte

rnal

mod

ules

COMMUNICATION MATRIX

Check which physical interface matches with certain protocols. It is possible to expand RS-232 interface with external hardware modules

NATIVE IEC 61850

The IEC 61850 protocol can be used to read or write static data or to receive events sent spontaneously from the relay. In addition, the interface allows peer-to-peer communication between the relays, called GOOSE communication. The IEC 61850 interface is confi gured with familiar, user-friendly VAMPSET software.

The IEC 61850 datamodel, data-sets, report control blocks and the GOOSE communication are configured according to the requirements of the system configuration. VAMPSET is also used to produce ICD files, which may be needed for the substation RTU configuration

The VAMP 300 IED contains native implementation, which means that the IEC 61850 functionality is embedded in the software.

Arc flash protectionVAMP relays measure fault current and with optional arc protection, also measure light via arc sensor channels, which provide monitoring for the whole switchgear. Should an arc fault occur in the switch-gear the arc protection system provides extremely fast tripping of the circuit breaker. The fault will be prevented from spreading and quickly isolated, which may save valuable assets.

Cable

CB

BB

Cable

L> (CB, BB)

L> (CB, BB)

CB CB

Cable

Page 6: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

06Protection VAMP 300 Series

ConnectionsVOLTAGE CONNECTION MODE

The slot 8 can accommodate four different analogue measurement cards. Model A has only one voltage input where as models B, C and D have four voltage measurement channels.

A = 3L+U+Io (5/1 A)

B = 3L+4U+Io (5/1 A)

C = 3L+4U+2Io (5+1 A)

D = 3L+4U+2Io (1+0.2 A)

Correlation between voltage measuring mode, physical voltage input and available voltages in Terminal 8/B/1 and 8/B/2. Note that terminals for voltage channel (U4) in slot 8/B/1 are 10 and 11.

Correlation between voltage measuring mode, physical voltage input and available voltages in terminal 8/C/1 (8/D/1) and 8/C/2 (8/D/2). Note that terminals for voltage channel (U4) in slot 8/C/1 (8/D/1) are 11 and 12.

The B module, terminal 1 has 11 pins

The C and D, terminal 1 have 12 pins

Terminal8/B/2 8/B/1

1 2 3 4 5 6 10 11

Voltage channel U1 U2 U3 U4

Mode / Used voltage

3LN

UL1 UL2 UL3

Not in use

3LN+U0 Uo

3LN+LLy LLy

3LN+LNy LNy

2LL+U0

U12U23

Uo

Not in use

2LL+U0+LLy LLy

2LL+U0+LNy LNy

LL+U0+LLy+LLz U12y L12z

LN+U0+LNy+LNz UL12 U11y UL1z

Terminal8/C/2 and 8/D/2

8/C/1 and 8/D/1

1 2 3 4 5 6 10 11

Voltage channel U1 U2 U3 U4

Mode / Used voltage

3LN

UL1 UL2 UL3

Not in use

3LN+U0 Uo

3LN+LLy LLy

3LN+LNy LNy

2LL+U0

U12U23

Uo

Not in use

2LL+U0+LLy LLy

2LL+U0+LNy LNy

LL+U0+LLy+LLz U12y L12z

LN+U0+LNy+LNz UL12 U11y UL1z

Page 7: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

07Protection VAMP 300 Series

Connection examples

3LN_Uo

123456789101112

IL1IL1IL2IL2IL3IL3I01I01I02I02U4U4

(S1)(S2)(S1)(S2)(S1)(S2)(S1)(S2)(S1)(S2)Uo (da)Uo (dn)

Slot 88/C1 : 1...128/D1 : 1...12

8C2 : 1...68D2 : 1...6

123456

UL1 (a)UL1 (n)UL2 (a)UL2 (n)UL3 (a)UL3 (n)

3LN_LNy

123456789101112

IL1IL1IL2IL2IL3IL3I01I01I02I02U4U4

(S1)(S2)(S1)(S2)(S1)(S2)

UL1 (a)UL1 (n)

8C2 : 1...68D2 : 1...6

123456

Slot 88/C1 : 1...128/D1 : 1...12

UL1 (a)UL1 (n)UL2 (a)UL2 (n)UL3 (a)UL3 (n)

(S1)(S2)(S1)(S2)

Voltage measuring mode: 3LN + UoVoltages measured by VTs

UL1, UL2, UL3, Uo

Values calculated UL12, UL23, UL31, U1, U2, U2/U1, f

Measurements available All

Protection functions available

All

Voltage measuring mode: 3LN Voltages measured by VTs

UL1, UL2, UL3

Values calculated UL12, UL23, UL31, U1, U2, U2/U1, f, Uo

Measurements available All

Protection functions available

All

Voltage measuring mode: 3LN+LNyVoltages measured by VTs

UL1, UL2, UL3, UL1y

Values calculated UL12, UL23, UL31, Uo, U1, U2, U2/U1, f

Measurements available All

Protection functions available

All

Above measuring modes are typically used for feeder and motor protection schemes.

3LN connection is similar to 3LN+Uo. Open delta connection is missing in this mode but Uo is calculated.

This connection is typically used for feeder protection scheme where line-to-neutral voltage is required for synchrocheck application.

Page 8: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

08Protection VAMP 300 Series

V 2LL + Uo

123456

UL12UL12UL23UL23UoUo

8/C/2 : 1...68/D/2 : 1...6

UL2

UL3

UL1

(a)(b)(a)(b)(da)(dn)

V 2LL + Uo + LLy

1112

123456

UL12UL12UL23UL23UoUo

8/C/1 : 11...128/D/1 : 11...12

8/C/2 : 1...68/D/2 : 1...6

UL2

UL3

UL1

UL12UL12

(a)(b)

(a)(b)(a)(b)(da)(dn)

Voltage measuring mode: 2LL + UoVoltages measured by VTs

UL12, UL23, Uo

Values calculated UL31, UL1, UL2, UL3, U1, U2, U2/U1, f

Measurements available All

Protection functions available

All

Voltage measuring mode: 2LL+Uo+LLyVoltages measured by VTs

UL12, UL23, Uo, UL12y

Values calculated UL31, UL1, UL2, UL3, U1, U2, U2/U1, f

Measurements available All

Protection functions available

All

V 3LN + LLy

1112

UL12 (a)UL12 (b)

123456

UL1 (a)UL1 (n)UL2 (a)UL2 (n)UL3 (a)UL3 (n)

8/C/1 : 11...128/D/1 : 11...12

8/C/2 : 1...68/D/2 : 1...6

UL2

UL3

UL1Voltage measuring mode: 3LN + LLyVoltages measured by VTs

UL1, UL2, UL3, UL12y

Values calculated UL12, UL23, UL31, Uo, U1, U2, U2/U1, f

Measurements available All

Protection functions available

All

Connection of voltage transformers for synchrocheck application. The other side of the CB has line-to-line connection for reference voltage.

Connection of two line-to-line and residual voltage measurement scheme.

Connection of two line-to-line and residual voltage scheme. Line-to-line reference voltage is taken from other side of the CB for synchrocheck scheme.

Page 9: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

09Protection VAMP 300 Series

V 2LL + Uo + LNy

1112

123456

UL12UL12UL23UL23UoUo

UL1 (a)UL1 (b)

8/C/1 : 11...128/D/1 : 11...12

8/C/2 : 1...68/D/2 : 1...6

UL2

UL3

UL1

(a)(b)(a)(b)(da)(dn)

V LL + Uo + LLy + LLz

1112

123456

UL12UL12UL12UL12UoUo

UL12 (a)UL12 (b)

8/C/1 : 11...128/D/1 : 11...12

8/C/2 : 1...68/D/2 : 1...6

UL2

UL3

UL1

(a)(b)(a)(b)(da)(dn)

V NL + Uo + LNy + LNz

1112

8/C/1 : 11...128/D/1 : 11...12

123456

UL1UL1UL1UL1UoUo

8/C/2 : 1...68/D/2 : 1...6

UL1 (a)UL1 (n)

UL2

UL3

UL1

(a)(n)(a)(n)(da)(dn)

Voltage measuring mode: 2LL+Uo+LNyVoltages measured by VTs

UL12, UL23, Uo, UL1y

Values calculated UL31, UL1, UL2, UL3, U1, U2, U2/U1, f

Measurements available All

Protection functions available

All

Voltage measuring mode: LL+Uo+LLy+LLzVoltages measured by VTs

UL12, Uo, UL12y, UL12z

Values calculated UL1, UL2, UL3, f

Measurements available

Protection functions available

Single phase voltage protection

Voltage measuring mode: LN+Uo+LNy+LNzVoltages measured by VTs

UL1, Uo, UL1y, UL1z

Values calculated UL12, UL23, UL31, f

Measurements available

Protection functions available

Single phase voltage protection

Connection of two line-to-line and residual voltage scheme. The other side of the CB has phase-to-neutral connection for synchrocheck.

This scheme has two CBs to be synchronized. Left side of the bus bar has line-to-line and right side line-to-line connection for synchrocheck's reference voltages. In the middle system voltages are measured by phase-to-neutral and open delta connection.

This scheme has two CBs to be synchronized. Left and right sides of the bus bar have line-to-neutral connections for synchrocheck's reference voltages. In the middle system voltages are measured by phase-to-neutral and open delta connection.

Page 10: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

Protection VAMP 300 Series 10

Dimensional drawings

PANEL MOUNTING

PROJECTION MOUNTING

2

ON

F1

F2

OK

Vamp 300

OI

3b

ON

OK

Vamp 300

F1 F2OI

1.0-600.04-2.36

225 8.86

152 5.98

1

4

27010.63

150 5.91

2309.05183

7.20

2.5Nm22 lb.in

3c

3Nm27 lb.in

mmin

mmin

T max. 1.2Nm10.6 lb.in

T max. 0.5...0.6Nm4.4...5.3 lb.in

ON

F1

F2

OK

Vamp 300

OI

269 10.59

152 5.98

172 6.77

224 8.82

45 1.77

3

3a

3a

CLICK !

1766.93

ON

F1

F2

OK

Vamp 300

OI

1375.39

ON

F1

F2

OK

Vamp 321

vamp

ON

F1

F2

OK

Vamp 321

vamp

ON

F1

F2

OK

Vamp 321

vamp

ON

OK

Vamp 321

F1 F2

vamp

VYX 695

Page 11: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

Protection VAMP 300 Series 11

Disturbance tests Standard & Test class / level Test value

Emission- Conducted - Emitted

EN 61000-6-4 / IEC 60255-26EN 55011, Class A / IEC 60255-25 EN 55011, Class A / IEC 60255-25 / CISPR 11

0.15 - 30 MHz30 - 1 000 MHz

Immunity- 1Mhz damped oscillatory wave- Static discharge (ESD) - Emitted HF field- Fast transients (EFT)- Surge

- Conducted HF field- Power-frequency magnetic field- Pulse magnetic field- Voltage interruptions- Voltage alternative component- Voltage dips and short interruptions

EN 61000-6-2 / IEC 60255-26IEC 60255-22-1EN 61000-4-2 Level 4 / IEC 60255-22-2 Class 4 EN 61000-4-3 Level 3 / IEC 60255-22-3EN 61000-4-4 Level 4 / IEC 60255-22-4 Class AEN 61000-4-5 Level 4 / IEC 60255-22-5

EN 61000-4-6 Level 3 / IEC 60255-22-6EN 61000-4-8EN 61000-4-9 Level 5EN 61000-4-29 / IEC 60255-11EN 61000-4-17 / IEC 60255-11EN 61000-4-11

± 2.5 kVp CM, ± 2.5 kVp DM± 8 kV contact, ± 15 kV air 80 - 2700 MHz, 10 V/m± 4 kV 5/50 ns, 5 kHz± 4 kV, 1.2/50 µs, CM2 kV, 1.2/50 µs, DM0.15 - 80 MHz, 10 Vemf300 A/m (continuous), 1000 A / m 1-3 s1000 A/m, 1.2 / 50 µs30 % / 1 s, 60 % / 0.1 s, 100 % / 0.05 s12 % of operating voltage (DC) / 10 min30 % / 10 ms, 100 % / 10 ms, 60 %/100 ms, >95 % / 5000 ms

Electrical safety tests- Impulse voltage withstand- Dielectric test- Insulation resistance- Protective bonding resistance- Power supply burden

EN 60255-5, Class IIIEN 60255-5, Class IIIEN 60255-5EN 60255-27IEC 60255-1

5 kV, 1.2/50 µs2 kV, 50 Hz

Mechanical testsDevice in operation- Vibrations- ShocksDevice de-energized- Vibrations- Shocks- Bump

IEC 60255-21-1, Class II / IEC 60068-2-6, FcIEC 60255-21-2, Class II / IEC 60068-2-27, Ea

IEC 60255-21-1, Class II / IEC 60068-2-6, FcIEC 60255-21-2, Class II / IEC 60068-2-27, EaIEC 60255-21-2, Class II / IEC 60068-2-27, Ea

1Gn, 10Hz – 150 HZ10Gn / 11 ms

2Gn, 10 Hz – 150 HZ30Gn / 11ms20Gn / 16ms

Environmental testsDevice in operation- Dry heat- Cold- Damp heat, cyclic- Damp heat, staticDevice in storage- Dry heat- Cold

EN / IEC 60068-2-2, Bd EN / IEC 60068-2-1, AdEN / IEC 60068-2-30, DbEN / IEC 60068-2-78, Cab

EN / IEC 60068-2-2, BbEN / IEC 60068-2-1, Ab

+70°C- 40°CFrom +25°C to +55°C, From 93% RH to 98% RH, 6 days+40°C, 93% RH, 10 days

+70°C- 40°C

Environmental conditionsAmbient temperature, in-service Ambient temperature, storage Relative humidityMaximum operating altitude Degree of protection (IEC 60529)WeightDimension (W x H x D)

-25…+60°C -40…+70 °C < 95%, no condensation allowed 2000 m IP54 (from front when panel mounted) 3.2 kg or higher (depends of options) 270 x 176 x 230 mm

PackageDimensions (W x H x D)Weight (IED, Package and Manual)

270 x 176 x 230 mm 4.2 kg or higher (depends of options)

Tests and environmental

Page 12: VAMP 300 Series - Allectro · 2016-07-04 · VAMP 300 Series Modular IED > design your own protection relay BENEFITS OF MODULAR DESIGN 1. A modular IED for different applications:

12Protection VAMP 300 Series

12-2013

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Design: Schneider Electric Industries SAS - WILMAPhotos: Schneider Electric Industries SAS Printed in Finland

35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France)Tel.: +33 (0) 1 41 29 70 00RCS Nanterre 954 503 439 Capital social 896 313 776 €www.schneider-electric.com/energy-automation

DEVICE TRACK RECORD

•SchneiderElectric’sVAMPRangespecialisesinprotectionprotectionrelays,arcflashprotectionandmeasuringandmonitoringunitsforpowersystems.

•VAMP’smedium-voltageandsub-transmissionprotectionrelaysareusedinnumerousapplications,fromoverheadlinefeedersandsubstationstopowerplantsandindustrialpowersystem.TheiruniqueintegratedarcflashfaultprotectionfunctionalityenhancesthesafetyofbothpeopleandpropertyandhasmadeVAMPaleadingmanufacturerinarcflashprotectionworldwide.AllVAMPproductsmeetthelatestinternationalstandardsandregulations.