REG - D™
REG - D™ Operating Manual
Operating ManualREG-D™ Relay for Voltage Control
& Transformer Monitoring
Issue 12.02.2009/03a
Issue GB
Version 02.2009
Software Version
8/20/2019 A-Abrel Redg- D Operating Manual 2009
2/3032
REG - D™
REG - D™ Operating Manual
REG-D™ Relay for Voltage Control &
Transformer Monitoring
Operating Manual
Issue 12.02.2009
Copyright 2009 by A. Eberle GmbH & Co. KG.
All rights reserved.
Published by:
A. Eberle GmbH & Co. KG
Frankenstraße 160
90461 Nuremberg, Germany
Tel: +49 (0) 911 / 62 81 08 - 0
Fax No.: +49 (0) 911 / 62 81 08 -96
e-mail: [email protected]
Internet: www.a-eberle.de, www.regsys.de
The company A. Eberle GmbH & Co. KG cannot be held liable for
any damages or losses resulting from printing errors or changes
in this operating manual.
Furthermore, A. Eberle GmbH & Co. KG does not assume
responsibility for any damages and losses resulting from
defective devices or from devices altered by the user.
8/20/2019 A-Abrel Redg- D Operating Manual 2009
3/3033
REG - D™
REG - D™ Operating Manual
Table of Contents
1 Warnings and Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 Scope of Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.1 Plug-in modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203.4.1 Block diagram of socket connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.4.2 Socket connector 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.4.3 Socket connector 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4.4 Socket connector 3; (Measuring voltage, auxiliary voltage) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.4.5 Socket connector 4; (measuring current input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.4.6 Socket connector 5; (tap changing via feature T1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.4.7 Socket connector 6; (analogue inputs / outputs; interfaces) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.4.8 Interface COM 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.5 Installation in the mounting rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6 Wall-mounted housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.1 Wall-mounted housing, type 30 MW, feature B02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373.6.2 Wall-mounted housing, type 30 MW, feature B03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.3 Control panel mounting enclosure, type 30 MW, feature B05. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6.4 Control panel mounting enclosure, type 49 MW, feature B06. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.6.5 Wall-mounted housing, type 49 MW, feature B07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.5.1 19” mounting rack, feature B92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.7 Pin assignment for types B05, B06 and B07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
4 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.1 The front panel operator interface of the REG-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
4.1.1 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444.1.2 Function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
4.1.3 Plug connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.2 Operating principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
4.3 Selecting the display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
4.4 Lamp check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4.5 Resetting fault signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.6 Operating the Recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8/20/2019 A-Abrel Redg- D Operating Manual 2009
4/3034
REG - D™
REG - D™ Operating Manual
5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
5.2 Transducer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 625.3 Recorder mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
5.4 Statistics mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
5.5 Paragramer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
5.6 Choosing the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.7 Setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
5.8 Permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
5.9 Time behaviour. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
5.10 Backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.11 Tap-changer running time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.12 Knx transformer mounting ratios and transformer connection . . . . . . . . . . . . . . . . . . . . . . . . . 75
5.13 Setting the nominal current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
5.14 Inhibit low limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
5.15 Triggering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
5.16 Short description of the individual limit values, the setpoint values and the permissible regulative
deviation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
6 Basic Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 876.1.2 Station name. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88
6.1.3 Setting the time/date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
6.1.4 LCD contrast (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89
6.1.5 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90
6.1.6 Deleting recorder data (resetting the measured value memory). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
6.1.7 Deleting tap-change sums (resetting the tap-counter to zero). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91
6.1.8 Actual value correction of the measuring voltage UE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
6.1.9 Actual value correction of the measuring current IE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
6.2 RS-232 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 936.2.1 COM 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
6.2.2 COM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
6.3 E-LAN (Energy-Local Area Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
6.4 PAN-D voltage monitoring unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6.5 Status (actual ID data of the REG-D Relay for Voltage Control & Transformer Monitoring). . . . . . 99
8/20/2019 A-Abrel Redg- D Operating Manual 2009
5/3035
REG - D™
REG - D™ Operating Manual
7 Parameterisation of the REG-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
7.1 Permissible regulative deviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2 Time behaviour (regulation behaviour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1037.2.1 Time factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
7.2.2 Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.2.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
7.3 Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1057.3.1 1st setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
7.3.2 Further setpoint values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
7.4 Programs (parameters for parallel transformer regulation). . . . . . . . . . . . . . . . . . . . . . . . . . . 1077.4.1 Selection of the parallel programs (regulation programs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
7.4.2 Parameters for the parallel program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
7.2.2 Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1047.4.3 Current influence (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
7.4.4 LDC parameter R (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
7.4.5 LDC parameter X (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
7.5 Gradient (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
7.6 Limitation (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
7.7 < U Undervoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
7.8 > U Overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
7.9 > I, < Limit (upper and lower current limits). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1127.10 Trigger inhibit high (highest limit value of the voltage). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
7.11 High-speed switching during undervoltage/overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1147.11.1 High-speed switching when undervoltage occurs (RAISE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
7.11.2 High-speed switching when overvoltage occurs (LOWER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
7.12 Relay for Voltage Control & Transformer Monitoring inhibit low when undervoltage occurs . . . 115
7.13 Time delays (limit signals). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1157.13.1 Time Delay > U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
7.13.2 Time delay < U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
7.13.3 Time delay > I, < I limit value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1167.13.4 Time delay trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
7.13.5 Time delay forward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7.13.6 Time delay backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7.13.7 Time delay inhibit low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
8/20/2019 A-Abrel Redg- D Operating Manual 2009
6/3036
REG - D™
REG - D™ Operating Manual
7.14 Add-Ons (Relay behaviour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1187.14.1 Overview of the Add-Ons menus numbers 1 to 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118
7.14.2 Maximum time TC in operation (motor drive running time) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120
7.14.3 Manual/Automatic. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1217.14.4 Tap-changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122
7.14.5 Self-Conduction of the operation mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
7.14.6 Current Display (of the Transformer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123
7.14.7 LCD saver (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
7.14.8 Regulator mode: large display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
7.14.9 Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125
7.14.10 Parallel Program Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
7.14.11 Up/down relay on time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126
7.14.12 AUTO(MATIC) LOCK in the event of an E-LAN error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
7.14.13 Setpoint adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127
7.14.14 Creeping net breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128
7.14.15 Limit base (reference value) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129
7.14.16 Setting the Relay to inhibit low if I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
7.14.17 Maximum tap difference (monitoring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130
7.14.18 PARAGRAMER activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131
7.15 Transformer configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1317.15.1 Transformer configuration voltage (conductor connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132
7.15.2 Transformer mounting ratio for the voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
7.15.3 Transformer mounting current (conductor connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
7.15.4 Transformer mounting current (conversion 1 A / 5 A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135
7.15.5 Transformer mounting ratio for the current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137
7.16 Input assignments (binary inputs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
7.17 Relay assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
7.18 LED assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
8 Measurement Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
8.1 Setting the simulated voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
8.2 Setting the simulated current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
8.3 Setting the simulated phase angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1458.4 Setting the simulated tap-change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
9 Parallel Operation of Transformers with REG-D™ . . . . . . . . . . . . . . . . . . . . . . 147
9.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
9.2 Programs for parallel operation and their prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1519.2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151
9.2.2 Preparing manual activation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153
9.2.3 Preparing automatic activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .160
9.3 Parallel operation using the “Master-Slave-Independent (MSI)” procedure . . . . . . . . . . . . . . . 1709.3.1 Trouble-shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181
8/20/2019 A-Abrel Redg- D Operating Manual 2009
7/3037
REG - D™
REG - D™ Operating Manual
10 Resistance Measuring Equipment for Tap-Changers with Resistance-Coded Tap-
Change Signalling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
10.1 Error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18510.2 Level detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
10.3 Connection options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
11 mA inputs, mA outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
11.1 Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188
11.2 Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
12 Updating the Operating Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
12.1 Preparing the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21012.1.1 Windows NT/2000/XP operating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210
12.2 Starting the bootstrap loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211
13 Updating Analogue Inputs, Outputs, Tap-Change Potentiometer Input. . . . . . . . . . 215
14 Maintenance and Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
14.1 Cleaning information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
14.2 Changing fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
14.3 Changing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
14.4 REG-D current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
15 Storage Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
16 Background Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
16.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221
16.2 Command variable W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22216.2.1 Fixed command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
16.2.2 Variable command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
16.2.3 Current-dependent setpoint value increment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22616.3 Summary and Examples for Current Influencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
16.4 Regulative deviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23316.4.1 Regulative deviation Xw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
16.4.2 Permissible regulative deviation Xwz. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
16.4.3 Displaying the permissible regulative deviation Xw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
16.4.4 Setting the permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
16.5 Monitoring extreme operation values (faults) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23516.5.1 Limit signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
8/20/2019 A-Abrel Redg- D Operating Manual 2009
8/3038
REG - D™
REG - D™ Operating Manual
16.6 Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24016.6.1 High-speed switching Add-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .240
16.6.2 Relay inhibit low function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .241
16.6.3 Measuring the “Creeping Net Breakdown” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24216.6.4 Add-On: monitoring the “maximum tap-change difference” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .244
16.6.5 Add-On: monitoring the tap-changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .244
16.7 Time behaviour of the Relay when a control command is output . . . . . . . . . . . . . . . . . . . . . . 24516.7.1 Determining the reaction delay tv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .247
16.7.2 Integrated time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250
16.7.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .251
16.7.4 “Const” time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .252
16.7.5 Setting the time factor Ft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .257
16.8 E-LAN (Energy Local Area Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
16.9 Voltage regulation with parallel-switched transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26216.9.1 Regulation programs for transformers switched in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .263
16.9.2 Functional principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .264
16.9.3 Influence of the circulating current regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .264
16.9.4 Activation of the regulation program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .265
16.9.5 Description of the regulation programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .266
16.10 Nominal transformation of the measuring transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281
16.11 Self-conduct. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
16.12 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28216.12.1 LCD contrast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282
16.12.2 LCD saver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282
16.12.3 Background illumination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282
17 Definition of the Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
18 Symbols and their Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
19 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
20 Notes on the Interpreter Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
21 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
22 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303
8/20/2019 A-Abrel Redg- D Operating Manual 2009
9/3039
REG - D™
REG - D™ Operating Manual
1 Warnings and Information
The REG-D Relay for Voltage Control & Transformer Monitoring
is exclusively designed for implementation in systems and
equipment incorporating electrical energy technology on which
only trained experts are permitted to carry out all required work.
Experts are persons who are familiar with the installation,
mounting, commissioning and operation of these types of
products. Furthermore, experts have qualifications which
comply with their field of work.
The REG-D Relay for Voltage Control & Transformer Monitoringhas been designed and tested in accordance with all important
electrical safety regulations and left the factory in perfect
condition. To maintain this condition and to ensure safe
operation, the following instructions and warnings in this
operating manual must be observed.
❑ The REG-D Relay for Voltage Control & Transformer
Monitoring has been designed to comply with IEC 10110/
EN61010 (DIN VDE 0411), degree of protection I and was
tested according to this standard before delivery.
❑ The REG-D Relay for Voltage Control & Transformer
Monitoring must be earthed via a protective earth
conductor. This condition is fulfilled when the Relay for
Voltage Control & Transformer Monitoring is connected to
an auxiliary voltage with a protective earth conductor
(European power supply system). If the auxiliary voltage
power supply system does not have a protective earth
conductor, an additional connection must be established
from the protective earth conductor terminal to earth.
❑ The upper limit of the permissible auxiliary voltage U AUX may
not be exceeded, neither permanently nor for a short period
of time.
❑ Before changing the fuse, separate the REG-D Relay for
Voltage Control & Transformer Monitoring completely from
the auxiliary voltage U AUX .
The use of fuses other than those of the indicated type and
rated current is prohibited.
❑ A REG-D Relay for Voltage Control & TransformerMonitoring which displays visible damage or clear
malfunctioning must not be used and has to be secured
against unintentionally being switched on.
8/20/2019 A-Abrel Redg- D Operating Manual 2009
10/30310
REG - D™
REG - D™ Operating Manual
❑ Maintenance and repair work on an opened REG-D Relay
for Voltage Control & Transformer Monitoring may only be
carried out by authorised experts.
Warning signs
Please familiarise yourself with the nominal insulation voltage of
the Relay for Voltage Control & Transformer Monitoring before
connecting the device.
Ensure that the voltages are connected via a disconnecting
mechanism, and that the current path can be short circuited ifthere is a device fault to enable problem-free device
replacement.
This is only required if the device, including the device housing/
mounting rack, has to be disassembled. If the plug-in modules
alone are removed, the short circuit plug prevents the circuits
from being used whilst open.
When wiring, please ensure that the conductors are either
bound short or kept sufficiently short, so that they can neither
come into contact with the connecting elements (plugs,terminals etc.) nor the stripped conductor ends of circuits with
a low nominal insulation voltage. If this is not ensured, a self-
feeding voltage may form when an error occur, turning the
originally safe low voltage circuits (e.g. mA outputs) into ones
that are dangerous if touched.
!
8/20/2019 A-Abrel Redg- D Operating Manual 2009
11/30311
REG - D™
REG - D™ Operating Manual
2 Scope of Delivery
1 REG-D Relay for Voltage Control & Transformer Monitoring
1 short-form operating manual in English
1 operating manual in English
1 WinREG programming and parameterisation software
1 cable
1 replacement fuse
8/20/2019 A-Abrel Redg- D Operating Manual 2009
12/30312
REG - D™
REG - D™ Operating Manual
3 Technical Data
3.1 Plug-in modules
Front panel Plastic film on aluminium support
RAL 7035 light grey
Height 3 U (128.5 mm)
Width 28 T (142.2 mm)
Weight ≤ 1.5 kg
Degree of protection
Plug-in modules IP00
Socket connector IP00
Configuration according to DIN 41494 Part 5
Plug-in connector DIN 41612
Dimensions
28 MW
8/20/2019 A-Abrel Redg- D Operating Manual 2009
13/30313
REG - D™
REG - D™ Operating Manual
Location of
blade connectors
Location of
socket connectors
1
2
3
4
5
6
Analogue module
optional
123456
8/20/2019 A-Abrel Redg- D Operating Manual 2009
14/30314
REG - D™
REG - D™ Operating Manual
3.2 Connection diagram
Contact load R1, R2: AC 250 V, 5 A, cosϕ = 1,DC 250 V, 150 W
REG-D
* Please observe the contact load at R1 and
R2 (see below)!
** The connections for I and U can be freely
assigned via the menu.
110 V DC 230 V AC
20 A Switch on 5 A @ cosϕ = 1
5 A Hold 3 A @ cosϕ = 0.4
0.4 A Switch off
8/20/2019 A-Abrel Redg- D Operating Manual 2009
15/30315
REG - D™
REG - D™ Operating Manual
3.3 Overview of features
REG-D is a highly variable product.
The operating manual must take this factor into account andprovide different descriptions for the for the various
specifications.
Because the features ... M2, S1... D2 ... are noted on the name
plate of the device, but the relation to the function which it
stands for is not always given, the complete structure of the
device's features is listed here.
Feature Code
REG-D™ Relay for Voltage Control & Transformer
Monitoring, 28TE, 3HE plug-in module
Standard version, with double E-LAN interface, COM
1, COM 2,
16 binary inputs, 10 relay outputs plus status relays
and
WinREG parameterisation and programming soft-
ware incl. connection cable
REG-D™
Design19” plug-in module
Wall-mounting housing (30TE) - without wiring
Wall-mounting housing (30TE) - with wiring
(Terminals compatible with REG 5A)
Panel-mounting housing (30TE) with wiring
Panel-mounting housing (49TE) with wiring
Wall-mounting housing (49TE) with wiring
Wall-mounting or panel-mounting housing (30/49TE)
on request
19” mounting rack according on request
B01
B02
B03
B05
B06
B07
B91
B92
Power supply
From monitoring network AC 80V ... 110V ... 185V
AC 85V ... 110V ... 264V / DC 88V ... 220V ... 280V
DC 18V ... 60V ... 72V
H0
H1
H2
Input current
IEN 1A
IEN 5A
F1
F2
8/20/2019 A-Abrel Redg- D Operating Manual 2009
16/30316
REG - D™
REG - D™ Operating Manual
Measurement transducer display functions for net-
work quantities Three-phase current with equal load
Three-phase current with unequal load
U measurement for overvoltage, U and I measure-
ments for undervoltage
Other uses of the transformer ( 2 x I, 2 x U, e.g. triple-
wound transformer)
M1
M2
M3
M9
Recorder functions for network quantities
Incl. evaluation software
WithoutWith S0S1
Parallel operation
without firmware for parallel operation
with firmware for parallel operation
K0
K1
Feature Code
8/20/2019 A-Abrel Redg- D Operating Manual 2009
17/30317
REG - D™
REG - D™ Operating Manual
Analogue inputs and outputs
withoutwith 2 inputs
with 4 inputs
with 6 inputs
with 2 outputs
with 4 outputs
with 6 outputs
with 2 inputs and 2 outputs
with 2 inputs and 4 outputs
with 4 inputs and 2 outputs
Any combination on requesteach with 2 analogue inputs and outputs
PT 100 direct input
Tap-change potentiometer input
Note:
Please specify the scale if known!:
Example:
Channel 1:-100 ... 0 ... +100 MW
-20 ... 0 ... +20 mA
Channel 2:0 ... 80 ... 100 V
4 ... 16 ... 20 mA
Channel 3:1 ... 19 Stufen
0 ... 20 mA
Note:
A total of 3 modules may be used. Pay attention
to the TMM particularly with use of the
transformer monitoring module!
E00E91
E92
E93
E94
E95
E96
E97
E98
E99
E900
Binary inputs (freely programmable)
E1...E8: AC/DC48..250V, E9...E16: AC/DC 10 ...
50V (can also be used as a BCD input)
E1...E16: AC/DC 48 ...250V (can also be used as a
BCD input)
E1...E16: AC/DC 10 ...50V (can also be used as a
BCD input)
D1
D2
D3
RS485 interface (COM 3)
withoutwith
Note:
COM 3 is only required for ANA-D and BIN-D!
R0R1
Feature Code
8/20/2019 A-Abrel Redg- D Operating Manual 2009
18/30318
REG - D™
REG - D™ Operating Manual
Control system connection: Internal or external:
without (more in Feature Group “Y”))with integrated connection (more in Feature Group
“XL”)
with ext. connection (REG-P/PE/PM) more in Feature
Group “Y”)
XW0 XW1
XW9
Integrated protocol interface card
for control connection of REG-D™ system
for control connection of multiple systems
Note: XL9 can only be combined with XZ15..XZ19
and XZ91
XL1
XL9
Type of connection:
Copper RS 232
RS 485 only for 2-wire operation
Note:
XV13 .. XV 19 can only be selected in combination
with B02…B92.
In all other case, select the appropriate fibre optic
cable module!
Fibre optic cable with FSMA connection
Glass fibre
(wavelength 800...900 nm, range 2000 m)
Plastic
(wavelength 620...680 nm, range 50 m)
Fibre optic cable with ST connection
Glass fibre
(wavelength 800...900 nm, range 2000 m)
Plastic(wavelength 620...680 nm, range 50 m)
XV10
XV11
XV13
XV15
XV17
XV19
Feature Code
8/20/2019 A-Abrel Redg- D Operating Manual 2009
19/30319
REG - D™
REG - D™ Operating Manual
Log
IEC60870-5-103 for ABB
IEC60870-5-103 for Areva
IEC60870-5-103 for SAT
IEC60870-5-103 for Siemens (LSA/SAS)
IEC60870-5-103 for Sprecher Automation
IEC60870-5-103 for andere
IEC60870-5-101 for ABB
IEC60870-5-101 for IDS
IEC60870-5-101 for SAT
IEC60870-5-101 for Siemens (LSA/SAS)
IEC60870-5-101 for others
DNP 3.00
LONMark
SPABUS
MODBUS RTU
XZ10
XZ11
XZ12
XZ13
XZ14
XZ90
XZ15
XZ17
XZ18
XZ19
XZ91
XZ20
XZ21
XZ22
XZ23
Local/remote switching using the keyboardwithout
with
Y0
Y1
Status output
closes during fault
opens during fault
U0
U1
Operating manual
German
English
FrenchSpanish
Italian
Russian
G1
G2
G3G4
G5
G8
Display text
Same as operating manual
German
English
French
Spanish
ItalianDutch
Czech
Russian
A0
A1
A2
A3
A4
A5 A6
A7
A8
Feature Code
8/20/2019 A-Abrel Redg- D Operating Manual 2009
20/30320
REG - D™
REG - D™ Operating Manual
3.4 Block diagram
3.4.1 Block diagram of socket connectors
Feature ... D1 ...
8/20/2019 A-Abrel Redg- D Operating Manual 2009
21/30321
REG - D™
REG - D™ Operating Manual
Feature ... D2 ...