Upload
malini72
View
215
Download
0
Embed Size (px)
Citation preview
8/10/2019 88307a.ppt
1/48
Topic 7: Pulse Width Modulation
Techniques for Voltage-Fed
Inverters
Spring 2004
ECE 8830 - Electric Dr
ives
8/10/2019 88307a.ppt
2/48
Introduction
While the 36-step inverter offers simplecontrol and low switching loss, lower order
harmonics are relatively high leading tohigh distortion of the current wave (unlesssignificant filtering is performed).
PWM inverter offers better harmonic controlof the output than 6-step inverter.
8/10/2019 88307a.ppt
3/48
PWM Principle
The dc input to the inverter is choppedby switching devices in the inverter. Theamplitude and harmonic content of the acwaveform is controlled by the duty cycleof the switches. The fundamental voltagev1has max. amplitude = 4Vd/for a
square wave output but by creatingnotches, the amplitude of v1is reduced(see next slide).
8/10/2019 88307a.ppt
4/48
PWM Principle (contd)
8/10/2019 88307a.ppt
5/48
PWM Techniques
Various PWM techniques, include:
Sinusoidal PWM (most common)
Selected Harmonic Elimination (SHE)PWM
Space-Vector PWM
Instantaneous current control PWM
Hysteresis band current control PWM
Sigma-delta modulation
8/10/2019 88307a.ppt
6/48
Sinusoidal PWM
The most common PWM approach issinusoidal PWM. In this method a
triangular wave is compared to asinusoidal wave of the desiredfrequency and the relative levels of thetwo waves is used to control the
switching of devices in each phase legof the inverter.
8/10/2019 88307a.ppt
7/48
Sinusoidal PWM (contd)
Single-Phase (Half-Bridge) Inverter
Implementation
8/10/2019 88307a.ppt
8/48
Sinusoidal PWM (contd)
when va0> vTT+on; T-off; va0= Vd
va0< vTT-on; T+off; va0= -Vd
8/10/2019 88307a.ppt
9/48
Sinusoidal PWM (contd)
8/10/2019 88307a.ppt
10/48
Sinusoidal PWM (contd)
Definition of terms:
Triangle waveform switching freq. = fc(alsocalled carrier freq.)
Control signal freq. = f (also called modulationfreq.)
Amplitude modulation ratio, m = Vp
VT
Frequency modulation ratio,
mf(P)= fc/ f
Peak amplitude
of control signal
Peak amplitude
of triangle wave
8/10/2019 88307a.ppt
11/48
Sinusoidal PWM (contd)
Harmonics
Note: Nearly independent of mf (P)for mf9.
8/10/2019 88307a.ppt
12/48
Sinusoidal PWM (contd)
Harmonics (contd)
8/10/2019 88307a.ppt
13/48
Sinusoidal PWM (contd)
At high fcthe nominal leakage inductanceof the machine will effectively filter outthe inverter line current harmonics at
high switching frequencies. High fcleadsto higher switch lossesbut lower machineharmonic loss.
Choose mf (P) = odd integer it eliminateseven harmonics.
8/10/2019 88307a.ppt
14/48
Sinusoidal PWM (contd)
At m=1, the max. value of fundamentalpeak voltage =0.5Vd= 0.7855 . Vpk
sq.wave
(=4Vd/2). This max. value can be
increased to 0.907Vpksq.waveby injecting3rd order harmonics- this is a commonmode voltage and does not affect torqueproduction.
8/10/2019 88307a.ppt
15/48
Sinusoidal PWM (contd)
Overmodulation (m > 1.0)
Gives non-linear control and increases
harmonics but results in greater output.
Vd < ( VA0)1< 4 Vd for m >1.
2 2
(see text)
8/10/2019 88307a.ppt
16/48
Sinusoidal PWM (contd)
Two regions of operation - constant torqueand constant power.
For constant power, max. voltage obtainedby operating inverter in square wave mode.
For constant torque, voltage can be
controlled by PWM principle.
8/10/2019 88307a.ppt
17/48
8/10/2019 88307a.ppt
18/48
Single Phase Half-Bridge Inverter
C+, C- large and equal => voltage dividesexactly between capacitors at all times.
The current i0must flow through parallelcombination of C+and C-=> i0has no dc
component in steady state.
8/10/2019 88307a.ppt
19/48
Single Phase Full-Bridge Inverter
Essentially two one-leg inverters with the
same dc input voltage.Max. output voltage = 2 x max. output
voltage of -bridge. => output current is half
(useful at high powers since it means lessparalleling of devices.)
8/10/2019 88307a.ppt
20/48
Square Wave Inverter
V01 = 4 Vd
No pulse width control . Frequencycontrol is possible. Amplitude control is
possible if Vdis varied.
v0Vd
-Vd
full
bridge
V01
8/10/2019 88307a.ppt
21/48
Bipolar PWM Switching
8/10/2019 88307a.ppt
22/48
Bipolar PWM Switching (contd)
Switch pairs: (TA+,TB- ) and (TB+, TA-)
Output of leg B is negativeof leg A
output => vB0(t) = -vA0(t)=>v0(t)=2vA0(t)
Peak of fundamentalfrequency
component, V01= maVd (ma< 1.0)
Vd< V01< 4 Vd (ma> 1.0)
8/10/2019 88307a.ppt
23/48
Dead Time Effect
Because of finite turn-on time and turn-off time of switches, you wait a blankingtime, tdafter switching one switch off in
a leg before switching on the otherswitch in the same leg. The blankingtime will increaseor decreasethe outputslightly depending on the directionof the
load current.
Also, additional high frequencies appearin the output waveform.
8/10/2019 88307a.ppt
24/48
Dead Time Effect (contd)
8/10/2019 88307a.ppt
25/48
8/10/2019 88307a.ppt
26/48
Selective Harmonic Elimination
By placing notchesin the output waveformat proper locations, certain harmonics canbe eliminated. This allows lower switchingfrequencies to be used -> lower losses,higher efficiency.
8/10/2019 88307a.ppt
27/48
Selective Harmonic Elimination
(contd)
General Fourier series of wave is given by:
where
and
1
( ) ( cos sin )n nn
v t a n t b n t
2
0
1( ) cos( ) ( )na v t n t d t
2
0
1( ) sin( ) ( )nb v t n t d t
8/10/2019 88307a.ppt
28/48
Selective Harmonic Elimination
(contd)
For a waveform with quarter-cyclesymmetry, only the odd harmonics withsine components will appear, i.e. an=0
and
where
1
( ) sinnn
v t b n t
2
0
4 ( ) sin( ) ( )nb v t n t d t
8/10/2019 88307a.ppt
29/48
Selective Harmonic Elimination
(contd)
It can be shown (see text forderivation) that
Thus we have K variables (i.e. 1, 2,3, ... K) and we need K simultaneous
equations to solve for their values.WithK angles, K-1 harmonics can beeliminated.
1
41 2 ( 1) cos
KK
n KK
b nn
8/10/2019 88307a.ppt
30/48
Selective Harmonic Elimination
(contd)
Consider the 5th and 7th harmonics (the3rd order harmonics can be ignored if themachine has an isolated neutral). ThusK=3 and the equations can be written as:
Fundamental:
5th Harmonic:
7th Harmonic:
1 1 2 3
4(1 2 cos 2 cos 2 cos )b
5 1 2 3
4(1 2 cos 5 2 cos 5 2 cos 5 ) 0
5b
7 1 2 3
4(1 2 cos 7 2 cos 7 2 cos 7 ) 07b
8/10/2019 88307a.ppt
31/48
Selective Harmonic Elimination
(contd)
These transcendental equations can besolved numerically for the notch angles1, 2, and3for a specified fundamental
amplitude. For example, if thefundamental voltage is 50% (i.e. b1=0.5)the values are:
1=20.9,
2=35.8, and
3=51.2
This approach can easily be implementedin a microcomputer using a lookup tablefor notch angles (see text).
8/10/2019 88307a.ppt
32/48
Selective Harmonic Elimination
(contd)
8/10/2019 88307a.ppt
33/48
Space-Vector PWM
Space vector PWMis an advanced,computationally intensive technique thatoffers superior performance in variable-
speed drives. This technique has theadvantage of taking account of interactionamong the phases when the load neutralis isolated from the center tap of the dc
supply. Space vector PWM can be used tominimize harmonic content of the three-phase isolated neutral load.
This approach is discussed in detail in the
textbook.
8/10/2019 88307a.ppt
34/48
Current Regulated PWM
The flux and torque output of an ac motoris directly controlled by the current inputto the motor. Thus having current control
on the output of a voltage-fed converterwith voltage control PWM is important. Afeedback current loop is used to controlthe machine current.
Two PWM techniques for current controlwill be considered:
1. Instantaneous Current Control
2. Hysteresis Band Current Control
8/10/2019 88307a.ppt
35/48
Instantaneous Current Control
The below figure shows an instantaneouscurrent control scheme with sinusoidal PWMin the inner control loop.
8/10/2019 88307a.ppt
36/48
Instantaneous Current Control
(contd)
Actual current i is compared to commandedcurrent i* and the error fed to a proportional-integral (P-I) controller. The rest of the
circuit is the standard PWM topology. For a3inverter, three such controllers are used.
Although the control approach is simple, thismethod produces significant phase lag athigh frequencies which are very harmful tohigh-performance drives.
8/10/2019 88307a.ppt
37/48
Hysteresis-Band Current Control
In hysteresis-band current control theactual current tracks the command currentwithin a hysteresis band.
In this approach a sine reference currentwave is compared to the actual phasecurrent wave. As the current exceeds aprescribed hysteresis band, the upperswitch in the half-bridge is turned off andthe lower switch is turned on. As thecurrent goes below the hysteresis band,
the opposite switching takes place.
8/10/2019 88307a.ppt
38/48
Hysteresis-Band Control (contd)
8/10/2019 88307a.ppt
39/48
Hysteresis-Band Control (contd)
With upper switch closed, the positivecurrent slope is given by:
where 0.5Vdis the applied dc voltage,
Vcmsinet is the opposing load counter EMF,and L = effective load inductance.
Similarly, with the lower switch closed, thenegative current slope is given by:
0.5 sind cm eV V tdi
dt L
(0.5 sin )d cm e
V V tdi
dt L
8/10/2019 88307a.ppt
40/48
Hysteresis-Band Control (contd)
Pk-to-pk current ripple and switching freq.are related to width of hysteresis band.Select width of hysteresis band to
optimally balance harmonic ripple andinverter switching loss.
Current control tracking is easy at low
speed but at high speeds, when counterEMF is high, current tracking can be moredifficult.
8/10/2019 88307a.ppt
41/48
Hysteresis-Band Control (contd)
A simple control block diagram forimplementing hysteresis band PWM isshown below:
8/10/2019 88307a.ppt
42/48
Hysteresis-Band Control (contd)
The error in the control loop is input to aSchmitt trigger ckt. The width of thehysteresis band HB is given by:
Upper switch on: (i*
-i) >HBLower switch on: (i*-i)
8/10/2019 88307a.ppt
43/48
Hysteresis-Band Control (contd)
This approach is very popular because ofsimple implementation, fast transientresponse, direct limiting of device pk.current, and practical insensitivity to dclink voltage ripple (=> small filtercapacitor).
However, PWM freq. is not const. which
leads to non-optimal harmonic ripple inmachine current. Can be overcome byadaptive hysteresis band. Also, significantphase lag at high freqs. is a drawback of
this method for high-performance drives.
8/10/2019 88307a.ppt
44/48
Sigma Delta Modulation
Sigma-delta modulation is a usefultechnique for high frequencylink converter
systems - uses integral half-cycle pulses togenerate variable freq., variable voltagesinusoidal waves.
8/10/2019 88307a.ppt
45/48
Sigma Delta Modulation (contd)
Principle is as follows:
Modulator receives command phasevoltage va0
*at variable freq./mag. And is
compared to actual discrete phase voltagepulses. The error (deltaoperation) isintegrated (sigmaoperation) to generatean integral error function e:
Polarity of e is used to select either a
positive pulse or negative pulse.
*
0 0a ae v dt v dt
8/10/2019 88307a.ppt
46/48
Sigma Delta Modulation (contd)
8/10/2019 88307a.ppt
47/48
Output Ripple
The output ripple may be defined as thedifference between the instantaneousvalue of the current/voltage compared tothe value of the fundamental frequencycomponent.
Consider the load to be an ac motor.
v0= v01+ vripple ; i0= i01+ iripple
Single -Phase
Inverter
+ -i0
+v0
-
L
vL= vL1+ vripple
+e0 = 2E0sint-
8/10/2019 88307a.ppt
48/48
Output Ripple (contd)
Using superposition:
vripple(t) = v0(t) - v01(t)
Note: The ripple is independentof the
power being transferred to the load.
kdvL
tit
rippleripple )(1
)(0
constant