76678 HK 13 IE08 278 285:IE · HA360 HA362 HA364 Auxiliary contact for HA352 to HA364 HZ023 2 changeover In 16 A - 250 V~ cos ϕ = 0,8 mechanical life span: 107 switches Rotary Drive

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • Sw

    itch

    gea

    r

    Switchgear

    280 Isolating Switches281 HRC Fuse Carriers282 Isolators 40A-160A283 Isolators up to 1600A284 Switch Disconnectors

    286 Technical Data

  • 280

    Isolating Switches

    4 x 16A 400V~ 2 1 SB 416 SB 416F4 x 25A 400V~ 2 1 SB 425 SB 425F4 x 32A 400V~ 2 1 SB 432 SB 432F4 x 40A 400V~ 4 1 SB 440 SB 440F4 x 63A 400V~ 4 1 SB 463 SB 463F4 x 80A 400V~ 4 1 SB 480 SB 480F4 x 100A 400V~ 4 1 SB 499 SB 499F

    Four pole

    Descriptionfor use as a switchdisconnector in all types ofcircuit.

    Complies with :- IEC 60947-3 (In 16 to 100A)- EN 669.1 (In 16 to 63A)

    Technical dataIn : 16, 25, 32AAC 21A duty specificationconnection capacity:10▫ rigid cables6▫ flexible cablesIn : 40, 63, 80A (1 pole)AC 22B duty specificationconnection capacity:25▫ rigid cables16▫ flexible cables

    In : 80A (2 to 4 poles), 100AAC 22B duty specificationconnection capacity:50▫ rigid cables 35▫ flexible cables

    Designation Characteristics Width in I Pack Cat. 17.5mm qty. ref.

    Single pole 1 x 16A 250V~ 1 12 SB 1161 x 16A 250V~ 1 1 SB 116Vwith pilot light1 x 25A 250V~ 1 12 SB 1251 x 25A 250V~ 1 1 SB 125Vwith pilot light1 x 32A 250V~ 1 1 SB 1321 x 32A 250V~ 1 1 SB 132Vwith pilot light1 x 40A 250V~ 1 1 SB 1401 x 63A 250V~ 1 1 SB 1631 x 80A 250V~ 1 12 SB 1801 x 100A 250V~ 1 1 SB 199

    Double pole 2 x 16A 250V~ 1 1 SB 2162 x 16A 250V~ 1 1 SB 216Vwith pilot light2 x 25A 250V~ 1 12 SB 2252 x 25A 250V~ 1 1 SB 225Vwith pilot light2 x 32A 250V~ 1 1 SB 2322 x 32A 250V~ 1 1 SB 232Vwith pilot light2 x 40A 250V~ 1 1 SB 2402 x 63A 250V~ 1 6 SB 2632 x 80A 250V~ 1 1 SB 2802 x 100A 250V~ 1 1 SB 299

    Triple pole 3 x 16A 400V~ 2 1 SB 3163 x 25A 400V~ 2 1 SB 3253 x 32A 400V~ 2 1 SB 3323 x 32A 400V~ 3 1 SB 332Qlarge terminals3 x 40A 400V~ 3 1 SB 3403 x 63A 400V~ 3 1 SB 3633 x 80A 400V~ 3 1 SB 3803 x 100A 400V~ 3 1 SB 399

    Designation Characteristics Width in I Pack Cat. ref. Cat. ref. 17.5mm qty. neutral neutral

    right left

    SB 140

    SB 232

    SB 240

    SB 399

  • 281

    HRC fuse carrier range - L58

    Sw

    itch

    gea

    r

    DescriptionProtection and control ofcircuits against overloads andshort-circuits in commercial andindustrial distribution systems.

    Technical dataFor cylindrical fuses22 x 58mm125A- 690V AC50-60 Hz

    Complies with IEC947-3

    Fuse carriers type LS 7xx can beequipped with followingaccessories :- indicating light : for indication

    of the fuse status.- auxiliary switch : for indication

    of fuse blown condition

    LR type will not acceptaccessories

    Connection capacity :50▫ rigid cables35▫ flexible cables

    � For technical details see page 286

    Four pole carrier 3 phases+neutral link 8 1 LR 704 LS 704

    Auxiliary switch 5A - 250V ~1 c/o contact

    for fuses 22 x 58 single pole 1 LS 770with striker pinsfor fuses 22 x 58 three pole 1 LS 771with striker pins

    Indicating light 230V ~ 1 LS 672indication of blownor missing fuse link

    Adaptor for assymetric 20 L 065rails for series L51 and L58

    Three pole carrier 3 phases 6 1 LR 703 LS 703

    Single pole carrier 1 phase 2 1 LR 701 LS 701

    Designation Description Width in I Pack LR 7xx LS 7xx17.5mm qty. cat.ref. cat.ref.

    Two pole carrier 2 phases 4 1 LR 702 LS 702

    1 phase+ neutral link 4 1 LR 712 LS 712

    LS 701

    LS 703

    LS 770

    LS 672

    L 065

  • 282

    Isolators 40 A to 160 A HA Range

    3 Pole isolator with In 40 A 36 2 1 HA302visible disconnection Insulation VoltageAC 22 - 690 V~ Ui: 800 V~

    In 63 A 54 3 1 HA303Insulation VoltageUi: 800 V~

    Handle for mounting for In 40 A to 63 A 1 HZ001on the cabinet door Included in delivery:

    - Axial extension, 200 mm- Handle with frame for door

    mounting

    Auxialliary switch In 10 A - 690 V~ 1 HZ0211 open, 1 close for isolator

    40 to 63 A

    3 Pole Isolator with In 80 A 108 6 1 HA304visible disconnection Insulation VoltageAC 22 - 400 V~ Ui: 690 V~

    In 100 A 108 6 1 HA305Insulation VoltageUi: 690 V~

    In 125 A 108 6 1 HA306Insulation VoltageUi: 690 V~

    In 160 A 142 8,5 1 HA307

    Insulation VoltageUi: 750 V~

    Cage terminals for HA307 1 Set = 3 pcs. 1 HZ072solid/flexible with cable lugsfrom 10–95 mm2

    Terminal covers for HA307 1 HZ062

    • Modular Isolators for DIN Railor mounting plate

    • Handle directly on the device,lockable when OFF

    • In: 40 to 160 A• IP Rating: IP 20• certified to turn OFF and ON

    under load and has a safetyfunction in all electrical surgecircuits

    Characteristics:• double disconnection per

    phase• 40, 63 A with visible status

    display• 80 bis 160 A visible

    disconnectionApplication:in all Hager boards and cabinetsAccessories:- Handle on cabinet door- Auxilliary switch

    Norm:EN 60 947-3 / DIN VDE 0660 Part 107 Copy of documents on requestConnection:Cage Terminals40 A: max. 16 mm2

    63 A: max. 35 mm2

    80 to 125 A: max. 50 mm2

    massivConnection with lugs for HA307 (160A) Cage Terminals HZ072 in accessories for max. 70 mm2 massiv

    For further technical details, see page 288

    Description Characteristics Width Modular Pack Cat. ref.in mm spaces qty.

    Rotary drive for assembly for In 80 A to 160 A 1 HZ002on cabinet door Included in delivery:

    - Axial extension, 200 mm- Handle with frame for door

    mounting

    Auxiliary contact In 5 A - 250 V~ 1 HZ0221 open, 1 close für Lasttrennschalter

    80 bis 160 A

    HA302

    HA305

    HZ021

    HZ001

    HZ022

    HZ062

  • 283

    Isolators up to 1600 A HA Range

    Sw

    itch

    gea

    r

    • Isolators ready for fitting into Univers N system (see Univers Chapter)

    • Rotary drive directly on device • In: 160 ti 1600 A• certified to switch on and

    disconnect under load and asafety disconnection functionfor all low voltage circuits

    complies with norm:EN 60947-3 / DIN VDE 0660 Part 107Documentation on request

    Application:fitting into Univers N kit systemPack quantity 1

    for technical details see page 292

    Description Characteristics In/A Cat. ref. Cat. ref.3-pole 4-pole

    Description In/A Connection Cat. ref.cross sectionsolid [mm2]

    Isolator Insulation voltage Ui: 160manually used 750 V~ für HA352, HA354

    800 V~ für HA357 2501000 V~ für HA358

    AC 23 - 400 V~3 pole or 4 pole 1 Lockable handle, 400HA357, AC 22 - 400 V~ fastening screws Screw connection: and nuts, 630In 160 A: 95 mm

    2 max.In 250 A: 150 mm

    2 max. Assembly in univers 800In 400 A: 240 mm

    2 max. kits:In 630 A: 2 x 150 mm

    2 min. HA352 in UK21R1 12502 x 300 mm2 max. HA354/357 in UK21S1

    HA358 in UK42T1 1600

    HA452

    HA454

    HA457

    HA458

    HA352

    HA354

    HA357

    HA358

    HA360

    HA362

    HA364

    Auxiliary contact for HA352 to HA364 HZ0232 changeover In 16 A - 250 V~

    cos ϕ = 0,8mechanical life span:107 switches

    Rotary Drive for cabinet door for HA352 - HA358, 20 mm HZ003univers N for HA360 - HA364 HZ004

    longer shaft for HZ003, 320 mm HZ013longer shaft for HZ004, 320 mm HZ014

    Cage terminals 160 16 - 95 HZ0733 pole 250 16 - 185 HZ074meant for Al and Cu 400 50 - 240 HZ075

    630 70 - 300 HZ076

    Terminal Covers HA352 topto protect the conections bottom(IP2X), HA354, HA357 topfor top and bottom bottom

    HA358 topbottom

    HZ063

    HZ064

    HZ065

    HZ053HZ053BHZ054HZ054BHZ055HZ055B

    Double terminal set 160 16 - 95 HZ183makes connection of 2 cage 250 16 - 185 HZ184terminals per pole possible 400 50 - 300 HZ185

    630 70 - 300 HZ186

    HA358

    HZ003

    HZ033

    HZ053

    HZ074

    HZ184

    HZ023

    Protective cover - HA352for range of HA switchesfor top and bottom - HA354, HA357

    - HA358

    - HA360

    - HA362, HA364

    HZ043

    HZ044

    HZ045

    HZ046

    HZ047

    HZ033

    HZ034

    HZ035

    HZ036

    HZ037

  • 284

    Switch Disconnectors including handle HFD Range

    Functions:The HFD Series of Hager isolators are manually operatedmultipolar fuse combinationswitches. They break or switchoff on load and provide safetyisolation and protection againstover current for any low voltageelectrical circuit.

    • Double break by phase (topand bottom of fuse)

    • Protection against overcurrentby fuse circuit-breakers withhigh breaking capacity (100 kA eff.)

    • IP2 protection with terminalshrouds

    • Compact• TEST position for testing

    control circuits without powerusing U type auxiliary contacts.

    Complies with standards:• IEC 60947-3• IEC 60269-1• IEC 60269-2• EN 60947-3• DIN 43620• VDE 0636-10• VDE 0660 Part 107

    Description No. poles In/A Fuse Length Modules Cat. ref.sizes in mm 17.5mm

    3 pole 3 63 000 120 min. 24 HFD306

    3 125 00 120 min. 24 HFD312

    34 160 000 120 min. 24 HFD316

    3 250 1 120 min. 72 HFD325

    3 400 2 120 min. 72 HFD340

    3 630 3 120 min. 96 HFD363

    4 pole 4 63 000 120 min. 24 HFD406

    4 125 00 120 min. 24 HFD412

    4 160 00 120 min. 24 HFD416

    4 250 1 120 min. 72 HFD425

    4 400 2 120 min. 72 HFD440

    4 630 3 120 min. 96 HFD463

    HFD312

  • 285

    Sw

    itch

    gea

    r

    Accessories for switch disconnectors HFD Range

    HZC001

    HZC002

    L73H

    Shaft extension 200 mm - 63 to 400 A HZC101

    320 mm - 63 to 400 A HZC102

    200 mm - 630 A HZF102

    Interlocked handle 63 A black HZC001

    100 to 400 A black HZC002

    630 A black HZF001

    Description Details Cat.ref.

    Description Switch type Colour Cat.ref.

    Auxiliary contacts NO HZF301

    suitable for switches NC HZF30263 to 630A

    Description Type Cat.ref.

    Set of IP20 Terminal Shrouds 3 100 to 160 A HZF202top or bottom 4 HZF203

    3 250 to 400 A HZF2044 HZF205

    3 630 A HZF2064 HZF207

    Neutral Link 63 A HZF501

    125 A / 160 A HZF502

    250 A HZF503

    400 A HZF504

    630 A HZF505

    Description No. poles In/A Cat.ref.

    Neozed switch fuses

    Description Technical data Module Pack Cat.ref.spaces qty.

    Neozed Switch fuse 1 x 63 A 1.5 1 L71Hsealable 3 x 63 A 4.5 1 L73Hwith switch lock and screw capup to 35 mm2 max.

  • 286

    HRC fuse carriers

    Auxiliary changeover contactIdentical mounting on L 51 and L 58 - SP and multipole type LS

    Function of auxiliary contact

    - possible to disconnect the supply to the motor by wiring theauxiliary to the coil of the contactor.

    - remote indication of the fuse blown status by wiring the auxiliaryto an indicating lamp

    Note : to use the auxiliary for remote indication it is necessary to use fuselinks with striker pins.

    2 A

    L 633NONC

    C

    m3 �

    Clic !

    Correction chart for admissable currentA - ambient temperature effect.B - mutual temperature effect.

    In conditions where both conditions are combined(ambient temperature > 20°C and 3 juxtaposed phasessimultaneously on load) both coefficients A and B are applicable.

    Type L 31fuse size 8.5x31.5

    L 3810,3 x 38

    L 5114 x 51

    L 5822 x 58

    In for Un 400 V� 20A 32 A 50 A 125 A

    In for Un 500 V� 16A 20 A 40 A 80 A

    20° 1 1 1 1

    A 30° 0.95 0.95 0.95 0.95

    40° 0.9 0.90 0.90 0.90

    50° 0.8 0.80 0.80 0.80

    1 to 3 Ph 1 1 1 1

    B 4 to 6 Ph 0.8 0.8 0.8 0.8

    7 to 9 Ph 0.7 0.7 0.7 0.7Application drawing

    Isolation and padlocking in open position

    Indicating lightmounting on L 51 and L 58

    1

    2

    ø 4.5 mm

    > 10 Ph 0.6 0.6 0.6 0.6

    connection by5 mm push onterminals

  • 287

    Isolators HA Range

    Sw

    itch

    gea

    r

    Accessories for HA302 and HA303• Auxiliary contact HZ021, 1 open, 1 closed• A 3 pole earthing device can be fitted on each side of the auxi-

    liary contact HZ021

    Fitting example� 3 Pole earthing device� Auxiliary contact 1 open, 1 closed

    Dimensional picture of rotary drive HZ001 for door mounting

    H≥ 80 mm

    10...14 mm

    32,5 mm

    L = H-30 mm

    ∅ 6

    2 m

    m

    74

    22

    13 36 13

    L1

    ON

    OFF

    I

    O

    L2 L3

    T1 T2 T3

    IP Rating remains at IP54 with fitting of rotary driveH min = 80 mmH max = 230 mm

    OFF position lockable by:• lockable direct frontal drive (with a 5mm lock) • lockable door drive (with up to three 8mm locks)

    Door locking in Position 1 with handle; in Position 0 the handleis separated from the shaft

  • 288

    Isolators HA Range

    Standard IEC 947-3 Cat. ref.HA302 HA303

    Thermal current Ith, 40°C 40 A 63 A

    Rated Insulation voltage Ui 800 V 800 V

    Withstand Voltage 50 Hz 1 min 3 kV 3 kV

    Rated impulse withstand voltage Uimp 8 kV 8 kV

    400 VAC 21 A - AC 22 A

    AC 23 A40 A32 A

    63 A63 A

    500 VAC 21 A - AC 22 A

    AC 23 A40 A32 A

    63 A50 A

    690 VAC 21 A - AC 22 A

    AC 23 A40 A20 A

    63 A50 A

    Surge protection

    Fuse size gL- gG 40 A 63 A

    Rated short circuit capacity gL-gG 50 kA 50 kA

    Rated short time current capacity 1 s - Icw 1260 A 1500 A

    Switching on and off details

    Breaking capacity 400 V AC 23 A 320 A 630 A

    Making capacity 400 V AC 23 A 256 A 504 A

    Life span

    Mechanical (number of switching cycles) 100000 30000

    Electrical (number of switching cycles) 1500 1500

    Connection

    Min. and max. cross section copper cable by Ith 6/16 mm2 10/50 mm2

    Weight 0.13 kg 0.25 kg

    Rated operating current Ie (1)

    Isolator 40 to 63A with rotary drive HAIsolator HA302/HA303

    1

    0

    ON

    OFF

    D

    45B

    CA

    Dimensionsin mm

    Cat. ref.HA302 HA303

    In 40 A 63 A

    A 36 52

    B 65 77

    C 39 44

    D 74.5 74.5

    500 V AC - AC 23 A 18,5 kW 30 kW

    400 V AC - AC 23 A 18,5 kW 30 kW

    690 V AC - AC 3 11 kW 18.5 kW

    500 V AC - AC 3 15 kW 18.5 kW

    400 V AC - AC 3 11 kW 18.5 kW

    Power output (2)

    690 V AC - AC 23 A 15 kW 45 kW

  • 289

    Isolators HA Range

    Sw

    itch

    gea

    r

    Isolators 80 to 160A with rotary drive HAIsolators HA304 / HA305 / HA306 / HA307

    Cat. ref. In

    HA304 80 A

    HA304, HA305, HA306

    HA307

    Cover (accessories)

    HA305 100 A

    HA306 125 A

    HA307 160 A

  • 290

    Isolators HA Range

    Accessories for HA304 to HA307 � direct frontal drive (incl. in delivery)� Door drive HZ002� and � auxiliary contact HZ022, max. 2 auxiliaries can be fitted� IP 2-Terminal covers HZ062 for HA307� Cage terminals HZ072 for HA307

    (Accessories for switches HA304, HA305, HA306 incl.)� Can be fitted onto mounting plates or DIN Rail

    ➁➅

    Lockable in OFF Position:• lockable direct frontal drive (with a 5mm lock) • lockable door drive (with up to three 8mm locks)

    – Door locking in Position 1 with handle; in Position 0 thehandle is separated from the shaft

    Auxiliary contact HZ022• 1 open, 1 closed, 5 A, 250 V~• advanced• max. connection cross section: 2 x 1.5 mm2

    • gilded contact surface• min. contact current: 1 mA with 4 V DC

    Dimensional picture of rotary drive for door mounting –Indirect door drive Door drill holes for indirect rotary drive

    IP rating IP54 maintained when drive is fitted

    46.5

    63

    L

    X

    90°

    I

    O

    50

    50

    31

    4.54

    HA304 - HA306 HA307

    X min.X max.

    118 mm286 mm

    103 mm254 mm

    Shaft length X - 49 mm

    Fit with screws

  • 291

    Isolators HA Range

    Sw

    itch

    gea

    r

    Standards IEC 947-3 VDE 0660 Part 107 HA304 HA305 HA306 HA307

    Thermal current Ith (40°C) 80 A 100 A 125 A 160 A

    Rated insulation voltage Ui 690 V 690 V 690 V 750 V

    Withstand voltage 50 Hz 1 min 4 kV 4 kV 4 kV 4 kV

    Rated impulse withstand voltage Uimp 8 kV 8 kV 8 kV 8 kV

    Rated operating current A / B A / B A / B A / B

    400 V AC AC 21 A / AC 21 BAC 22 A / AC 22 BAC 23 A / AC 23 B

    80 / 80 A80 / 80 A63 / 63 A

    100 / 100 A100 / 100 A

    63 / 63 A

    125 / 125 A125 / 125 A

    63 / 63 A

    160 / 160 A160 / 160 A160 / 160 A

    Power output (3)

    400 V AC without advanced auxiliary 30 / 30 kW 30 / 30 kW 30 / 30 kW 90 / 90 kW

    500 V AC AC 21 A / AC 21 BAC 22 A / AC 22 BAC 23 A / AC 23 B

    80 / 80 A80 / 80 A50 / 50 A

    100 / 100 A100 / 100 A

    50 / 50 A

    125 / 125 A100 / 100 A

    50 / 50 A

    160 / 160 A160 / 160 A160 / 160 A

    690 V AC AC 20AC 21 A / AC 21 BAC 22 A / AC 22 BAC 23 A / AC 23 B

    80 / 80 A80 / 80 A40 / 40 A25 / 25 A

    100 / 100 A80 / 80 A40 / 40 A25 / 25 A

    125 / 125 A80 / 80 A40 / 40 A25 / 25 A

    160 / 160 A160 / 160 A160 / 160 A

    63 / 80 A

    260 V DC DC 20DC 21 A / DC 21 B (2)DC 22 A / DC 22 B (2)

    DC 23 A / DC 23 B (2)

    80 / 80 A80 / 80 A80 / 80 A63 / 63 A

    100 / 100 A100 / 100 A100 / 100 A

    63 / 63 A

    125 / 125 A125 / 125 A100 / 100 A

    63 / 63 A

    160 / 160 A160 / 160 A160 / 160 A160 / 160 A

    400 V DC DC 20DC 21 A / DC 21 B (2)DC 22 A / DC 22 B (2)

    DC 23 A / DC 23 B (2)

    80 / 80 A40 / 40 A32 / 32 A-

    100 / 100 A40 / 40 A32 / 32 A

    -

    125 / 125 A40 / 40 A32 / 32 A

    -

    160 / 160 A160 / 160 A100 / 100 A

    63 / 63 A

    690 V AC without advanced auxiliary 22 / 22 kW 22 / 22 kW 22 / 22 kW 55 / 75 kW

    400 V AC without advanced auxiliary 37 / 37 kW 55 / 55 kW 55 / 55 kW 90 / 90 kW

    690 V AC without advanced auxiliary 37 / 37 kW 37 / 37 kW 37 / 37 kW 132 / 132 kW

    Surge protection

    Rated short circuit capacity with fuses gL - gG 100 kA eff 100 kA eff 50 kA eff 50 kA eff

    Fuse size 80 A 100 A 125 A 160 A

    Dynamic current capacity 12 kA 12 kA 12 kA 16 kA

    Rated short circuit capacity (1 s) Icw 2.5 kA eff 2.5 kA eff 2.5 kA eff 5 kA eff

    Short circuit making capacity Icm (uninfluenced peak value) 10 kA eff 10 kA eff 10 kA eff 13 kA eff

    Switching data

    Breaking capacity 400 V AC AC23 504 A 504 A 504 A 1280 A

    Making capacity 400 V AC AC23 630 A 630 A 630 A 1600 A

    Life Span

    Mechanical (number of switch cycles) 20000 20000 20000 10000

    Electrical (number of switch cycles) (1) 1500 / 300 1500 / 300 1000 / 200 1000 / 200

    Operation power 3 Nm 3 Nm 3 Nm 6 Nm

    Connection (copper cable)

    Min. wire cross section 4 mm2 4 mm2 4 mm2 10 mm2

    max. wire cross section, (multi wire) 35 mm2 35 mm2 35 mm2 95 mm2 (4)(5)

    max. wire cross section (single wire) 50 mm2 50 mm2 50 mm2 95 mm2 (5)

    Max. rail cross section - - - 20 mm2

    Weight

    3-Pole 0.6 kg 0.7 kg 0.7 kg 0.9 kg

    4-Pole 0.7 kg 0.8 kg 0.8 kg 1 kg

    (1) A: frequent use B: occasional use

    (2) 2 pole in range per pole(3) Power output: the height of current is different between dif-

    ferent manufacturers

    (4) with cable lugs(5) with additional cage terminal HZ072

  • 292

    Isolators HA Range

    0 I

    0

    A

    K

    J J J

    H

    N

    G

    M

    C

    L

    D

    E

    B

    F

    Isolators HA352, HA354, HA357, HA358, HA360, HA362, HA364

    Auxiliary contact HZ023, 2 changeover contactsTechnical Data:• Rated current 16 A 250 V~ cos ϕ = 0.8

    250 V~ cos ϕ = 0,35 In = 12 A400 V~ cos ϕ = 0,35 In = 8 A

    • Operational temperature -20°C + 125°C• Connection with Fast on contact pin

    6.35mm• Life span (electrical) 30000 switch cycles• IP Rating IP 20

    Dimensions switches 160 bis 630 A

    Dim. Cat. ref.in mm HA352 HA354 HA357 HA358 HA360 HA362 HA364

    In/A 160 A 250 A 400 A 630 A 800 A 1250 A 1600 A

    A 140 180 180 230 280 372 372

    B 135 160 170 260 320 330 360

    C 65 75 75 110 140 140 140

    D 35 39 39 65 86 86 86

    E 120 130 130 165 234 234 234

    F 148 150 150 170 330 330 330

    G 120 160 160 210 255 347 347

    H 65 80 80 140 175 175 175

    J 36 50 50 65 80 120 120

    K 20 25 35 40 50 63 80

    L 20.5 22.5 22.5 36.5 47 47 51

    M 174 210 210 420 460 460 460

    N 45 55 55 130 130 130 130

    Door drill holes HA352-358

    L 70

    126.

    5

    Isolator HA352 / 354 / 357 HZ358 HA360-64

    Rotary drive HZ003 HZ003 + HZ003 HZ003 + HZ004HZ013 HZ013

    Lmin 109 103 138 138 212

    Lmax 246 366 280 400 262

    212 ± 1 without shaft extension

    Minimum length with shaft extension: 262 ± 1

    81

    50 A

    ø 31

    4 ø 4.5

    26

    24

    45º

    3.5

    28 = = ø 25

    70

    4 ø 6

    50

    Fron

    t p

    late

    65 x

    65

    A

    90°

    I

    O

    50

    50

    31

    4.54

    HA360-64

    HA360-64

    Door drill holes HA352-358

  • 293

    Isolators HA Range

    Sw

    itch

    gea

    r

    Accessories for HA352, HA354, HA357, HA358, HA360, HA362, HA364Operation types:- direct: the lockable handle is fixed to the switch

    - indirect: the lockable handle is fixed frontally on the door. The indirect frontal drive can be separated from theoperating shaft in position 0, in Position 1 it allows forthe locking of the door (an "out of order" of the lockingis possible)

    Terminal coverIP 20from 160 to 630 A

    lockable handle HZ003 (3 locks) HA352 - HA358HZ004 (3 locks) HA360 - HA364

    protective coverHZ033 for HA352HZ034 for HA354, HA357HZ035 for HA358HZ036 for HA360HZ037 for HA362, 64

    connection terminalsHZ073…076

    IP 20auxiliary HZ023

    shaft(∅ to 18 mm)

    lockable handle

    Connection cage terminals up to 630 A Cage terminal with extension terminal up to 630 A

    • designed for direct connection of copper and aluminium wires(without cable lugs))

    • can be integrated in cover

    In / A Cable connection flexible rgid Flex rails width Blank on

    160A 16 to 95 mm2 16 to 95 mm2 13 mm 22 mm

    250A 16 to 185 mm2 16 to 185 mm2 18 mm 27 mm

    400A 50 to 240 mm2 50 to 300 mm2 20 mm 34 mm

    630A

    800A

    1250A

    1600A

    70 to 300 mm2 70 to 300 mm2 24 mm 34 mm

    2 x 300 mm2 63 mm

    4 x 185 mm2 100 mm

    6 x 240 mm2 100 mm

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages false /GrayImageMinResolution 150 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 72 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages false /MonoImageMinResolution 300 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects true /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /False

    /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > > /FormElements true /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MarksOffset 6 /MarksWeight 0.250000 /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PageMarksFile /RomanDefault /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice