Sw
itch
gea
r
Switchgear
280 Isolating Switches281 HRC Fuse Carriers282 Isolators 40A-160A283 Isolators up to 1600A284 Switch Disconnectors
286 Technical Data
280
Isolating Switches
4 x 16A 400V~ 2 1 SB 416 SB 416F4 x 25A 400V~ 2 1 SB 425 SB 425F4 x 32A 400V~ 2 1 SB 432 SB 432F4 x 40A 400V~ 4 1 SB 440 SB 440F4 x 63A 400V~ 4 1 SB 463 SB 463F4 x 80A 400V~ 4 1 SB 480 SB 480F4 x 100A 400V~ 4 1 SB 499 SB 499F
Four pole
Descriptionfor use as a switchdisconnector in all types ofcircuit.
Complies with :- IEC 60947-3 (In 16 to 100A)- EN 669.1 (In 16 to 63A)
Technical dataIn : 16, 25, 32AAC 21A duty specificationconnection capacity:10▫ rigid cables6▫ flexible cablesIn : 40, 63, 80A (1 pole)AC 22B duty specificationconnection capacity:25▫ rigid cables16▫ flexible cables
In : 80A (2 to 4 poles), 100AAC 22B duty specificationconnection capacity:50▫ rigid cables 35▫ flexible cables
Designation Characteristics Width in I Pack Cat. 17.5mm qty. ref.
Single pole 1 x 16A 250V~ 1 12 SB 1161 x 16A 250V~ 1 1 SB 116Vwith pilot light1 x 25A 250V~ 1 12 SB 1251 x 25A 250V~ 1 1 SB 125Vwith pilot light1 x 32A 250V~ 1 1 SB 1321 x 32A 250V~ 1 1 SB 132Vwith pilot light1 x 40A 250V~ 1 1 SB 1401 x 63A 250V~ 1 1 SB 1631 x 80A 250V~ 1 12 SB 1801 x 100A 250V~ 1 1 SB 199
Double pole 2 x 16A 250V~ 1 1 SB 2162 x 16A 250V~ 1 1 SB 216Vwith pilot light2 x 25A 250V~ 1 12 SB 2252 x 25A 250V~ 1 1 SB 225Vwith pilot light2 x 32A 250V~ 1 1 SB 2322 x 32A 250V~ 1 1 SB 232Vwith pilot light2 x 40A 250V~ 1 1 SB 2402 x 63A 250V~ 1 6 SB 2632 x 80A 250V~ 1 1 SB 2802 x 100A 250V~ 1 1 SB 299
Triple pole 3 x 16A 400V~ 2 1 SB 3163 x 25A 400V~ 2 1 SB 3253 x 32A 400V~ 2 1 SB 3323 x 32A 400V~ 3 1 SB 332Qlarge terminals3 x 40A 400V~ 3 1 SB 3403 x 63A 400V~ 3 1 SB 3633 x 80A 400V~ 3 1 SB 3803 x 100A 400V~ 3 1 SB 399
Designation Characteristics Width in I Pack Cat. ref. Cat. ref. 17.5mm qty. neutral neutral
right left
SB 140
SB 232
SB 240
SB 399
281
HRC fuse carrier range - L58
Sw
itch
gea
r
DescriptionProtection and control ofcircuits against overloads andshort-circuits in commercial andindustrial distribution systems.
Technical dataFor cylindrical fuses22 x 58mm125A- 690V AC50-60 Hz
Complies with IEC947-3
Fuse carriers type LS 7xx can beequipped with followingaccessories :- indicating light : for indication
of the fuse status.- auxiliary switch : for indication
of fuse blown condition
LR type will not acceptaccessories
Connection capacity :50▫ rigid cables35▫ flexible cables
� For technical details see page 286
Four pole carrier 3 phases+neutral link 8 1 LR 704 LS 704
Auxiliary switch 5A - 250V ~1 c/o contact
for fuses 22 x 58 single pole 1 LS 770with striker pinsfor fuses 22 x 58 three pole 1 LS 771with striker pins
Indicating light 230V ~ 1 LS 672indication of blownor missing fuse link
Adaptor for assymetric 20 L 065rails for series L51 and L58
Three pole carrier 3 phases 6 1 LR 703 LS 703
Single pole carrier 1 phase 2 1 LR 701 LS 701
Designation Description Width in I Pack LR 7xx LS 7xx17.5mm qty. cat.ref. cat.ref.
Two pole carrier 2 phases 4 1 LR 702 LS 702
1 phase+ neutral link 4 1 LR 712 LS 712
LS 701
LS 703
LS 770
LS 672
L 065
282
Isolators 40 A to 160 A HA Range
3 Pole isolator with In 40 A 36 2 1 HA302visible disconnection Insulation VoltageAC 22 - 690 V~ Ui: 800 V~
In 63 A 54 3 1 HA303Insulation VoltageUi: 800 V~
Handle for mounting for In 40 A to 63 A 1 HZ001on the cabinet door Included in delivery:
- Axial extension, 200 mm- Handle with frame for door
mounting
Auxialliary switch In 10 A - 690 V~ 1 HZ0211 open, 1 close for isolator
40 to 63 A
3 Pole Isolator with In 80 A 108 6 1 HA304visible disconnection Insulation VoltageAC 22 - 400 V~ Ui: 690 V~
In 100 A 108 6 1 HA305Insulation VoltageUi: 690 V~
In 125 A 108 6 1 HA306Insulation VoltageUi: 690 V~
In 160 A 142 8,5 1 HA307
Insulation VoltageUi: 750 V~
Cage terminals for HA307 1 Set = 3 pcs. 1 HZ072solid/flexible with cable lugsfrom 10–95 mm2
Terminal covers for HA307 1 HZ062
• Modular Isolators for DIN Railor mounting plate
• Handle directly on the device,lockable when OFF
• In: 40 to 160 A• IP Rating: IP 20• certified to turn OFF and ON
under load and has a safetyfunction in all electrical surgecircuits
Characteristics:• double disconnection per
phase• 40, 63 A with visible status
display• 80 bis 160 A visible
disconnectionApplication:in all Hager boards and cabinetsAccessories:- Handle on cabinet door- Auxilliary switch
Norm:EN 60 947-3 / DIN VDE 0660 Part 107 Copy of documents on requestConnection:Cage Terminals40 A: max. 16 mm2
63 A: max. 35 mm2
80 to 125 A: max. 50 mm2
massivConnection with lugs for HA307 (160A) Cage Terminals HZ072 in accessories for max. 70 mm2 massiv
For further technical details, see page 288
Description Characteristics Width Modular Pack Cat. ref.in mm spaces qty.
Rotary drive for assembly for In 80 A to 160 A 1 HZ002on cabinet door Included in delivery:
- Axial extension, 200 mm- Handle with frame for door
mounting
Auxiliary contact In 5 A - 250 V~ 1 HZ0221 open, 1 close für Lasttrennschalter
80 bis 160 A
HA302
HA305
HZ021
HZ001
HZ022
HZ062
283
Isolators up to 1600 A HA Range
Sw
itch
gea
r
• Isolators ready for fitting into Univers N system (see Univers Chapter)
• Rotary drive directly on device • In: 160 ti 1600 A• certified to switch on and
disconnect under load and asafety disconnection functionfor all low voltage circuits
complies with norm:EN 60947-3 / DIN VDE 0660 Part 107Documentation on request
Application:fitting into Univers N kit systemPack quantity 1
for technical details see page 292
Description Characteristics In/A Cat. ref. Cat. ref.3-pole 4-pole
Description In/A Connection Cat. ref.cross sectionsolid [mm2]
Isolator Insulation voltage Ui: 160manually used 750 V~ für HA352, HA354
800 V~ für HA357 2501000 V~ für HA358
AC 23 - 400 V~3 pole or 4 pole 1 Lockable handle, 400HA357, AC 22 - 400 V~ fastening screws Screw connection: and nuts, 630In 160 A: 95 mm
2 max.In 250 A: 150 mm
2 max. Assembly in univers 800In 400 A: 240 mm
2 max. kits:In 630 A: 2 x 150 mm
2 min. HA352 in UK21R1 12502 x 300 mm2 max. HA354/357 in UK21S1
HA358 in UK42T1 1600
HA452
HA454
HA457
HA458
HA352
HA354
HA357
HA358
HA360
HA362
HA364
Auxiliary contact for HA352 to HA364 HZ0232 changeover In 16 A - 250 V~
cos ϕ = 0,8mechanical life span:107 switches
Rotary Drive for cabinet door for HA352 - HA358, 20 mm HZ003univers N for HA360 - HA364 HZ004
longer shaft for HZ003, 320 mm HZ013longer shaft for HZ004, 320 mm HZ014
Cage terminals 160 16 - 95 HZ0733 pole 250 16 - 185 HZ074meant for Al and Cu 400 50 - 240 HZ075
630 70 - 300 HZ076
Terminal Covers HA352 topto protect the conections bottom(IP2X), HA354, HA357 topfor top and bottom bottom
HA358 topbottom
HZ063
HZ064
HZ065
HZ053HZ053BHZ054HZ054BHZ055HZ055B
Double terminal set 160 16 - 95 HZ183makes connection of 2 cage 250 16 - 185 HZ184terminals per pole possible 400 50 - 300 HZ185
630 70 - 300 HZ186
HA358
HZ003
HZ033
HZ053
HZ074
HZ184
HZ023
Protective cover - HA352for range of HA switchesfor top and bottom - HA354, HA357
- HA358
- HA360
- HA362, HA364
HZ043
HZ044
HZ045
HZ046
HZ047
HZ033
HZ034
HZ035
HZ036
HZ037
284
Switch Disconnectors including handle HFD Range
Functions:The HFD Series of Hager isolators are manually operatedmultipolar fuse combinationswitches. They break or switchoff on load and provide safetyisolation and protection againstover current for any low voltageelectrical circuit.
• Double break by phase (topand bottom of fuse)
• Protection against overcurrentby fuse circuit-breakers withhigh breaking capacity (100 kA eff.)
• IP2 protection with terminalshrouds
• Compact• TEST position for testing
control circuits without powerusing U type auxiliary contacts.
Complies with standards:• IEC 60947-3• IEC 60269-1• IEC 60269-2• EN 60947-3• DIN 43620• VDE 0636-10• VDE 0660 Part 107
Description No. poles In/A Fuse Length Modules Cat. ref.sizes in mm 17.5mm
3 pole 3 63 000 120 min. 24 HFD306
3 125 00 120 min. 24 HFD312
34 160 000 120 min. 24 HFD316
3 250 1 120 min. 72 HFD325
3 400 2 120 min. 72 HFD340
3 630 3 120 min. 96 HFD363
4 pole 4 63 000 120 min. 24 HFD406
4 125 00 120 min. 24 HFD412
4 160 00 120 min. 24 HFD416
4 250 1 120 min. 72 HFD425
4 400 2 120 min. 72 HFD440
4 630 3 120 min. 96 HFD463
HFD312
285
Sw
itch
gea
r
Accessories for switch disconnectors HFD Range
HZC001
HZC002
L73H
Shaft extension 200 mm - 63 to 400 A HZC101
320 mm - 63 to 400 A HZC102
200 mm - 630 A HZF102
Interlocked handle 63 A black HZC001
100 to 400 A black HZC002
630 A black HZF001
Description Details Cat.ref.
Description Switch type Colour Cat.ref.
Auxiliary contacts NO HZF301
suitable for switches NC HZF30263 to 630A
Description Type Cat.ref.
Set of IP20 Terminal Shrouds 3 100 to 160 A HZF202top or bottom 4 HZF203
3 250 to 400 A HZF2044 HZF205
3 630 A HZF2064 HZF207
Neutral Link 63 A HZF501
125 A / 160 A HZF502
250 A HZF503
400 A HZF504
630 A HZF505
Description No. poles In/A Cat.ref.
Neozed switch fuses
Description Technical data Module Pack Cat.ref.spaces qty.
Neozed Switch fuse 1 x 63 A 1.5 1 L71Hsealable 3 x 63 A 4.5 1 L73Hwith switch lock and screw capup to 35 mm2 max.
286
HRC fuse carriers
Auxiliary changeover contactIdentical mounting on L 51 and L 58 - SP and multipole type LS
Function of auxiliary contact
- possible to disconnect the supply to the motor by wiring theauxiliary to the coil of the contactor.
- remote indication of the fuse blown status by wiring the auxiliaryto an indicating lamp
Note : to use the auxiliary for remote indication it is necessary to use fuselinks with striker pins.
2 A
L 633NONC
C
m3 �
Clic !
Correction chart for admissable currentA - ambient temperature effect.B - mutual temperature effect.
In conditions where both conditions are combined(ambient temperature > 20°C and 3 juxtaposed phasessimultaneously on load) both coefficients A and B are applicable.
Type L 31fuse size 8.5x31.5
L 3810,3 x 38
L 5114 x 51
L 5822 x 58
In for Un 400 V� 20A 32 A 50 A 125 A
In for Un 500 V� 16A 20 A 40 A 80 A
20° 1 1 1 1
A 30° 0.95 0.95 0.95 0.95
40° 0.9 0.90 0.90 0.90
50° 0.8 0.80 0.80 0.80
1 to 3 Ph 1 1 1 1
B 4 to 6 Ph 0.8 0.8 0.8 0.8
7 to 9 Ph 0.7 0.7 0.7 0.7Application drawing
Isolation and padlocking in open position
Indicating lightmounting on L 51 and L 58
1
2
ø 4.5 mm
> 10 Ph 0.6 0.6 0.6 0.6
connection by5 mm push onterminals
287
Isolators HA Range
Sw
itch
gea
r
Accessories for HA302 and HA303• Auxiliary contact HZ021, 1 open, 1 closed• A 3 pole earthing device can be fitted on each side of the auxi-
liary contact HZ021
Fitting example� 3 Pole earthing device� Auxiliary contact 1 open, 1 closed
Dimensional picture of rotary drive HZ001 for door mounting
�
�
H≥ 80 mm
10...14 mm
32,5 mm
L = H-30 mm
∅ 6
2 m
m
74
22
13 36 13
L1
ON
OFF
I
O
L2 L3
T1 T2 T3
IP Rating remains at IP54 with fitting of rotary driveH min = 80 mmH max = 230 mm
OFF position lockable by:• lockable direct frontal drive (with a 5mm lock) • lockable door drive (with up to three 8mm locks)
Door locking in Position 1 with handle; in Position 0 the handleis separated from the shaft
288
Isolators HA Range
Standard IEC 947-3 Cat. ref.HA302 HA303
Thermal current Ith, 40°C 40 A 63 A
Rated Insulation voltage Ui 800 V 800 V
Withstand Voltage 50 Hz 1 min 3 kV 3 kV
Rated impulse withstand voltage Uimp 8 kV 8 kV
400 VAC 21 A - AC 22 A
AC 23 A40 A32 A
63 A63 A
500 VAC 21 A - AC 22 A
AC 23 A40 A32 A
63 A50 A
690 VAC 21 A - AC 22 A
AC 23 A40 A20 A
63 A50 A
Surge protection
Fuse size gL- gG 40 A 63 A
Rated short circuit capacity gL-gG 50 kA 50 kA
Rated short time current capacity 1 s - Icw 1260 A 1500 A
Switching on and off details
Breaking capacity 400 V AC 23 A 320 A 630 A
Making capacity 400 V AC 23 A 256 A 504 A
Life span
Mechanical (number of switching cycles) 100000 30000
Electrical (number of switching cycles) 1500 1500
Connection
Min. and max. cross section copper cable by Ith 6/16 mm2 10/50 mm2
Weight 0.13 kg 0.25 kg
Rated operating current Ie (1)
Isolator 40 to 63A with rotary drive HAIsolator HA302/HA303
1
0
ON
OFF
D
45B
CA
Dimensionsin mm
Cat. ref.HA302 HA303
In 40 A 63 A
A 36 52
B 65 77
C 39 44
D 74.5 74.5
500 V AC - AC 23 A 18,5 kW 30 kW
400 V AC - AC 23 A 18,5 kW 30 kW
690 V AC - AC 3 11 kW 18.5 kW
500 V AC - AC 3 15 kW 18.5 kW
400 V AC - AC 3 11 kW 18.5 kW
Power output (2)
690 V AC - AC 23 A 15 kW 45 kW
289
Isolators HA Range
Sw
itch
gea
r
Isolators 80 to 160A with rotary drive HAIsolators HA304 / HA305 / HA306 / HA307
Cat. ref. In
HA304 80 A
HA304, HA305, HA306
HA307
Cover (accessories)
HA305 100 A
HA306 125 A
HA307 160 A
290
Isolators HA Range
Accessories for HA304 to HA307 � direct frontal drive (incl. in delivery)� Door drive HZ002� and � auxiliary contact HZ022, max. 2 auxiliaries can be fitted� IP 2-Terminal covers HZ062 for HA307� Cage terminals HZ072 for HA307
(Accessories for switches HA304, HA305, HA306 incl.)� Can be fitted onto mounting plates or DIN Rail
➆
➄
➂
➃
➅
➁➅
➀
Lockable in OFF Position:• lockable direct frontal drive (with a 5mm lock) • lockable door drive (with up to three 8mm locks)
– Door locking in Position 1 with handle; in Position 0 thehandle is separated from the shaft
Auxiliary contact HZ022• 1 open, 1 closed, 5 A, 250 V~• advanced• max. connection cross section: 2 x 1.5 mm2
• gilded contact surface• min. contact current: 1 mA with 4 V DC
Dimensional picture of rotary drive for door mounting –Indirect door drive Door drill holes for indirect rotary drive
IP rating IP54 maintained when drive is fitted
46.5
63
L
X
90°
I
O
50
50
31
4.54
HA304 - HA306 HA307
X min.X max.
118 mm286 mm
103 mm254 mm
Shaft length X - 49 mm
Fit with screws
291
Isolators HA Range
Sw
itch
gea
r
Standards IEC 947-3 VDE 0660 Part 107 HA304 HA305 HA306 HA307
Thermal current Ith (40°C) 80 A 100 A 125 A 160 A
Rated insulation voltage Ui 690 V 690 V 690 V 750 V
Withstand voltage 50 Hz 1 min 4 kV 4 kV 4 kV 4 kV
Rated impulse withstand voltage Uimp 8 kV 8 kV 8 kV 8 kV
Rated operating current A / B A / B A / B A / B
400 V AC AC 21 A / AC 21 BAC 22 A / AC 22 BAC 23 A / AC 23 B
80 / 80 A80 / 80 A63 / 63 A
100 / 100 A100 / 100 A
63 / 63 A
125 / 125 A125 / 125 A
63 / 63 A
160 / 160 A160 / 160 A160 / 160 A
Power output (3)
400 V AC without advanced auxiliary 30 / 30 kW 30 / 30 kW 30 / 30 kW 90 / 90 kW
500 V AC AC 21 A / AC 21 BAC 22 A / AC 22 BAC 23 A / AC 23 B
80 / 80 A80 / 80 A50 / 50 A
100 / 100 A100 / 100 A
50 / 50 A
125 / 125 A100 / 100 A
50 / 50 A
160 / 160 A160 / 160 A160 / 160 A
690 V AC AC 20AC 21 A / AC 21 BAC 22 A / AC 22 BAC 23 A / AC 23 B
80 / 80 A80 / 80 A40 / 40 A25 / 25 A
100 / 100 A80 / 80 A40 / 40 A25 / 25 A
125 / 125 A80 / 80 A40 / 40 A25 / 25 A
160 / 160 A160 / 160 A160 / 160 A
63 / 80 A
260 V DC DC 20DC 21 A / DC 21 B (2)DC 22 A / DC 22 B (2)
DC 23 A / DC 23 B (2)
80 / 80 A80 / 80 A80 / 80 A63 / 63 A
100 / 100 A100 / 100 A100 / 100 A
63 / 63 A
125 / 125 A125 / 125 A100 / 100 A
63 / 63 A
160 / 160 A160 / 160 A160 / 160 A160 / 160 A
400 V DC DC 20DC 21 A / DC 21 B (2)DC 22 A / DC 22 B (2)
DC 23 A / DC 23 B (2)
80 / 80 A40 / 40 A32 / 32 A-
100 / 100 A40 / 40 A32 / 32 A
-
125 / 125 A40 / 40 A32 / 32 A
-
160 / 160 A160 / 160 A100 / 100 A
63 / 63 A
690 V AC without advanced auxiliary 22 / 22 kW 22 / 22 kW 22 / 22 kW 55 / 75 kW
400 V AC without advanced auxiliary 37 / 37 kW 55 / 55 kW 55 / 55 kW 90 / 90 kW
690 V AC without advanced auxiliary 37 / 37 kW 37 / 37 kW 37 / 37 kW 132 / 132 kW
Surge protection
Rated short circuit capacity with fuses gL - gG 100 kA eff 100 kA eff 50 kA eff 50 kA eff
Fuse size 80 A 100 A 125 A 160 A
Dynamic current capacity 12 kA 12 kA 12 kA 16 kA
Rated short circuit capacity (1 s) Icw 2.5 kA eff 2.5 kA eff 2.5 kA eff 5 kA eff
Short circuit making capacity Icm (uninfluenced peak value) 10 kA eff 10 kA eff 10 kA eff 13 kA eff
Switching data
Breaking capacity 400 V AC AC23 504 A 504 A 504 A 1280 A
Making capacity 400 V AC AC23 630 A 630 A 630 A 1600 A
Life Span
Mechanical (number of switch cycles) 20000 20000 20000 10000
Electrical (number of switch cycles) (1) 1500 / 300 1500 / 300 1000 / 200 1000 / 200
Operation power 3 Nm 3 Nm 3 Nm 6 Nm
Connection (copper cable)
Min. wire cross section 4 mm2 4 mm2 4 mm2 10 mm2
max. wire cross section, (multi wire) 35 mm2 35 mm2 35 mm2 95 mm2 (4)(5)
max. wire cross section (single wire) 50 mm2 50 mm2 50 mm2 95 mm2 (5)
Max. rail cross section - - - 20 mm2
Weight
3-Pole 0.6 kg 0.7 kg 0.7 kg 0.9 kg
4-Pole 0.7 kg 0.8 kg 0.8 kg 1 kg
(1) A: frequent use B: occasional use
(2) 2 pole in range per pole(3) Power output: the height of current is different between dif-
ferent manufacturers
(4) with cable lugs(5) with additional cage terminal HZ072
292
Isolators HA Range
0 I
0
A
K
J J J
H
N
G
M
C
L
D
E
B
F
Isolators HA352, HA354, HA357, HA358, HA360, HA362, HA364
Auxiliary contact HZ023, 2 changeover contactsTechnical Data:• Rated current 16 A 250 V~ cos ϕ = 0.8
250 V~ cos ϕ = 0,35 In = 12 A400 V~ cos ϕ = 0,35 In = 8 A
• Operational temperature -20°C + 125°C• Connection with Fast on contact pin
6.35mm• Life span (electrical) 30000 switch cycles• IP Rating IP 20
Dimensions switches 160 bis 630 A
Dim. Cat. ref.in mm HA352 HA354 HA357 HA358 HA360 HA362 HA364
In/A 160 A 250 A 400 A 630 A 800 A 1250 A 1600 A
A 140 180 180 230 280 372 372
B 135 160 170 260 320 330 360
C 65 75 75 110 140 140 140
D 35 39 39 65 86 86 86
E 120 130 130 165 234 234 234
F 148 150 150 170 330 330 330
G 120 160 160 210 255 347 347
H 65 80 80 140 175 175 175
J 36 50 50 65 80 120 120
K 20 25 35 40 50 63 80
L 20.5 22.5 22.5 36.5 47 47 51
M 174 210 210 420 460 460 460
N 45 55 55 130 130 130 130
Door drill holes HA352-358
L 70
126.
5
Isolator HA352 / 354 / 357 HZ358 HA360-64
Rotary drive HZ003 HZ003 + HZ003 HZ003 + HZ004HZ013 HZ013
Lmin 109 103 138 138 212
Lmax 246 366 280 400 262
212 ± 1 without shaft extension
Minimum length with shaft extension: 262 ± 1
81
50 A
ø 31
4 ø 4.5
26
24
45º
3.5
28 = = ø 25
70
4 ø 6
50
Fron
t p
late
65 x
65
A
90°
I
O
50
50
31
4.54
HA360-64
HA360-64
Door drill holes HA352-358
293
Isolators HA Range
Sw
itch
gea
r
Accessories for HA352, HA354, HA357, HA358, HA360, HA362, HA364Operation types:- direct: the lockable handle is fixed to the switch
- indirect: the lockable handle is fixed frontally on the door. The indirect frontal drive can be separated from theoperating shaft in position 0, in Position 1 it allows forthe locking of the door (an "out of order" of the lockingis possible)
Terminal coverIP 20from 160 to 630 A
lockable handle HZ003 (3 locks) HA352 - HA358HZ004 (3 locks) HA360 - HA364
protective coverHZ033 for HA352HZ034 for HA354, HA357HZ035 for HA358HZ036 for HA360HZ037 for HA362, 64
connection terminalsHZ073…076
IP 20auxiliary HZ023
shaft(∅ to 18 mm)
lockable handle
Connection cage terminals up to 630 A Cage terminal with extension terminal up to 630 A
• designed for direct connection of copper and aluminium wires(without cable lugs))
• can be integrated in cover
In / A Cable connection flexible rgid Flex rails width Blank on
160A 16 to 95 mm2 16 to 95 mm2 13 mm 22 mm
250A 16 to 185 mm2 16 to 185 mm2 18 mm 27 mm
400A 50 to 240 mm2 50 to 300 mm2 20 mm 34 mm
630A
800A
1250A
1600A
70 to 300 mm2 70 to 300 mm2 24 mm 34 mm
2 x 300 mm2 63 mm
4 x 185 mm2 100 mm
6 x 240 mm2 100 mm
/ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages false /GrayImageMinResolution 150 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Bicubic /GrayImageResolution 72 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 1.50000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages true /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages false /MonoImageMinResolution 300 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Bicubic /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects true /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile () /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName (http://www.color.org) /PDFXTrapped /False
/Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > > /FormElements true /GenerateStructure false /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MarksOffset 6 /MarksWeight 0.250000 /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /DocumentCMYK /PageMarksFile /RomanDefault /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice