Upload
tamann2004
View
217
Download
0
Embed Size (px)
Citation preview
8/17/2019 7117171-A-New-Method-for-Power-Factor-Correction-and-Harmonic-Elimination-in-Power-Systems.pdf
1/6
810
-
A
New Method for Power Factor orrection and Harmonic Elimination
in Power Systems
I. Kasikci, MIEEE, VDE
University
of
Applied
Sciences
of
Mannheim,
Germany
TeVFax: +49-620
1
I 82301, E-mail: I m a i l .~ ~ s i ~ c i i u r h ~ i n i i i ~ i n . ~ ~. i n i l
Abstract : The influence of power electronics-based
technology, which is increasingly used, has disadvantageous
effect on the quality of electric power supply. Pure sinuso idal
voltage supply does not exist anymore. Low and medium
voltage power systems are polluted to an increasing extent
by
harmonic currents and voltages, voltage fluctuation, voltage
unbalance, voltage sags, voltage swells and flicker This paper
presents an new configuration for power factor co rrection and
harmonic current elimination in electrical power systems. A
single-phasecontrol concept is discussed for simplicity. It also
presents a brief discussion of the main problems in the
distribution power systems.
Keywords: Reactive power compensation, Harmonics, Active
Filters, Control
,
EM1
I.
INTRODUCTION
The increased use of non-linear devices cause voltage
distortion in the network. This leads to malfunctions of
the electric facilities and to costly interruptions of
production.
The filter circuit parameters are analysed and described.
This filter configuration provides an alternative
approach to the existing one. According to the test
results, the proposed approach can achieve a complete
elimination of harmonics.
The sw itched-capacitor active filter was first presented
in 19 82 by C.C. Marouchos
[ I ]
and
is
fundamentally
different fiom the inverter configuration. T he switched-
capacitor configuration removes the requirement for a
large current or voltage source, which leads, not only to
a reduction in cost but also in physical size [2,3].
Another configuration of shunt active filter was
developed in [4]. The major drawback of these circuit is
that the control algorithm is very complicated, time
consuming and produces itself resonances.
As
described in [5] a sampling control is used and a load
is applied to the inverter which requires only the control
of the fundamental current for power factor correction.
In this paper, it is shown that the circuit is capable of
correcting not only the power factor of the
fundamentals but also of eliminating the harmonics and
ver easy to control. In recent years the proliferation of
non-linear loads has lead to the development
of
active
filters designed to eliminate current harmonics from the
power supply network.
0-
78C3-
49 ?-6:00:$18. O 20901EEE
This paper examines shunt active filter inverter and
passive filter, highlighting the co mplexity of the control.
Two different approaches are investigated, with the aim
of
reducing the computational requirements associated
with the control technique and hence increase the
applicability of the propos ed system.
A significant simplification is presented which eases the
somewhat laborious, but never the less unavoidable
computational requirements. A new control unit is also
developed providing
an
alternative to the dominated
computer controlled very complicated techniques.
The main characteristics of a non-linear supply are the
voltage interruptions, harmonic pre-distortions and
unbalance in the three phase systems. O n the other side,
the main characteristics of a non-linear loads are the
harmonics, hndamental reactive current, unsymmetrical
parts and the stochastic fluctuations called flicker.
There is a strong coupling between reactive power
balance and of a power system and the voltages. Today,
many techniques are used to compensate the reactive
power. Shunt and series com pensation is widely used in
the industry.
Two possible loads can be discussed in this point of
view. The non-linear supply voltage which influences
the loads behaviour and non-linear loads which cause
voltage distortions in other supply feedings.
Fig.1 represents the proposed active power filter
configuration. The proposed new control block diagram
shows nine main sections constituting the power active
filter structure. The harm onic cu rrent generated by non-
linear load is detected and fed back to the reference
current estimator, in conjunction with the other system
variables. The resulting reference signal drives the
overall system controller, which, in turn, generates the
control effort necessary for the switching pattern.
The resulting filter current is also detected and fed back
to the controller. The power and filter circuit is then
connected to the PCC. Shunt active filter is connected to
the main power circuit as shown in the single-line
diagram of Fig.2.
I t
is mainly aim ed towards cancelling
the load current harmonic as it has the ability of
controlling the amount of current flowing in the circuit.
It can also contribute to reactive power compensation
and balancing of three-phase currents, transients and
flicker.
8/17/2019 7117171-A-New-Method-for-Power-Factor-Correction-and-Harmonic-Elimination-in-Power-Systems.pdf
2/6
PCC Measurements
-
r l
ilter elements
..................... .............. ................................................................................ t r
I
_.................. .... .........
Switching Overall
i Controller
Strategy System
.............................................
Detector I
%. " .......-
. .
.
Reference
current
Estimator
1 1
Actual current
.... . .................. ............
........... ........
Fig.1 Complete Control Diagram
for
the proposed System
v cy
C D C
...................
VSI
s
s
r
........................... ...................................... .....-.....
c
lComp
V F
AC-Passive F ilter
T-Network
PCC
ion-linear Load Supply Voltage
N LL
Non-
linear
Load
Current C ontroller
i
Actual current , Reference current, Switch condi tions, P W nd H ysterisis controller, Supply
voltage, Load current)
L
..
................
.....................................................................................................
Fig.2: S ingle-phase
Full
Bridge Inverter-Filter Scheme
- 8 1 1
8/17/2019 7117171-A-New-Method-for-Power-Factor-Correction-and-Harmonic-Elimination-in-Power-Systems.pdf
3/6
- 812 11. ANALYSIS OF
THE
FILTER
The problem relating to current harmonics is very
important in lo w and medium power applications. It is the
value of the current and its waveform that determines many
of the power system design criteria Fig. 3 . Due
to
the
non-linear nature of the load, the load current
iL
, consists
of a fundamental component i as well as harmonic
components ihormwhich in the absence of the active filter
are present within the supply current i s , polluting the
power system. Therefore if i = i,, then is = i where
i, contains only the fundam ental component.
Most active filters designed for this purpose are voltage or
current fed inverter configurations, using various switching
techniques to control the compensation signal. The inverter
configuration relies on the availability of a constant dc
voltage
or
current source in order to generate the required
compensation signal. This is accomplished by the use of
large reservoir capacitors or inductors, which are not only
expensive but are also physically very large.
Network
m
Fig.3: Basic structure of shunt-active power-
filter configurations
The parallel connected active filter generates a
compensation signal i, ,which then supplies the harmonic
components required by the load, shown below:
(1 )
. . .
is
= i L
- 1 ,
= i i, -i
The energy required to maintain this constant dc level is
obtained from the supply via the inverter, this limits the
performance of the filter.
Using Fig. 4 as an example, the rate of change of current
within the inverter inductor
L,
is controlled
as
follows:
tr. 11
t
t
Fig.4: PW M-hysterisis switching technique
For the top boundary
For the bottom boundary
.
Idv
-
= 2 Ts
+T,)
3)
To achieve a hysteresis control band w idth
1
the current,
which is controlled, can be calculated fiom:
4)
To
avoid the harmonics in the main power current and
supply voltage a filter is designed and applied to a single
VSI.
The filter resistance R is inserted to restrain the
oscillation of the capacitor of the network and inverter
inductance.
A
lower value
of R ,
gives the best results of
the smoothing of the network current and supply voltage.
On the other hand, the filter capacitor C Fm us t be large
enough to absorb the current and vo ltage ripples. In order
to limit the failure current the following equation gives:
8/17/2019 7117171-A-New-Method-for-Power-Factor-Correction-and-Harmonic-Elimination-in-Power-Systems.pdf
4/6
813
-
The resonance frequency is:
fr -
8/17/2019 7117171-A-New-Method-for-Power-Factor-Correction-and-Harmonic-Elimination-in-Power-Systems.pdf
5/6
814
25,
23-
15-
10-
:C111..:0 20 3 4
5
Fig.
6 :
Current harmonic spectrum before comp ensation
2
l
e 10
20 30 40
5
Fig.
7:
Current harmonic spectrum after compensation
4,682"
. .
: 10A
_ I
......................
...
. . .
. ?
......................
. . +-++A
. . . . . . . .
. . . .
.
,:
.
.:
....
x _: .....
x . ....... 3 ......:vi.. ..
Fig. 8: Load Current waveform
226,Ou::
ms 22911-2 ~ ~ :RX
in
SO ,OH ~
'gqo ?
.-. ;R.
...
$?
...... I 2. . . . . . . . . :%........
;
. ;
? ' .
I
::
:
0.
i
i 1 ::. :
: : : : : : i
.... : :....>,.,I
.......:... ... ..5,..:..
\ :
%
S J
: .t
. .
; i
. -
a) Inverter Current
2.1 572
b) Compensated C urrent
1 4 lb
10.2 P
4995
HZ
2140 C
995
Xr
00
2.154
7
13 K
4
4 13 17 21 25 29 33 37 41 45 49
c) Harmonic Spectrum
Fig.9: Loading condition
8/17/2019 7117171-A-New-Method-for-Power-Factor-Correction-and-Harmonic-Elimination-in-Power-Systems.pdf
6/6
IV.
EMC COMPATIBILITY
Th e EM1 generated by the proposed system was m easured
when employing both hysterisis and PWM techniques.
Permissible level of electromagnetic emissions of the
switching power devices is given in Fig.
10,
in conjunction
with the emitted harmonics. These indicate that the passive
filter and the proposed switching technique meet the EM1
regulations.
The emitted interference is decreased about 30 dBN. The
passive filter designed traps the high fkequency harmonics
as shown in the Bode plots of Fig.
11.
It stops these
harmonics ffom penetrating into the supply and hence
hr the r reduces the EM1 generated by the system.
. lr
Fig. 10: Permissible level of the electromagnetic emissions
I I
Fig. 1 1 : Bode
diagram
of the transfer hnc tion
successfu lly filters unwan ted harmon ics generated by a
non-linear load.
8
15
-
By using PWM and hysterisis control method outlined
above the switching patterns required to control the filter
can rapidly be determined, and therefore the filter can
respond to varying load.
The main advantage of this technique is that it does not
require very complicated computer algorithms and
microprocessors. Simulation and experimental results show
that this new method can eliminate a wide range of
harmonics currents, flicker and transients. Power factor
correction is also possible.
Further, the response time
of
the controller much faster
comparing to the existing comm ercial power conditioner.
VI. REFERENCES
[1] Marouchos C.C., “Switched Capacitor Circuits For Reactive
Power Generation”, PhD Thesis, 1982.
[2] Mehta P., Darwish
M.,
Thomson T., “Switched Capacitor
Filters”, IEEE trans on Power Electronics, Vo1.5, No.3, July
1990
Koozehkani Z.D., Mehta P., Darwish M.K.,”An active filter
for retrofit applications”, in PEVD-96, Nottingham, UK.
El-Habrouk M., Mehta P., Darwish M.K., ‘‘ A new active
filter for power sytem applications”; I N P O W E R 9 8 ,
October 1998
Masaaki Ohshima, Eisuke Masada: Novel error tracking
mode ac current waveform control method and ac filter
design procedure, Sevilla EPE 95 , page 2.472-2.477.
[3]
[4]
[5]
VII. BIOGRAPHY
Ismail Kasikci was bom in Turkey, on September
1,
1952. He
received two Dipl.-Ing. degrees from the University of Applied
Sciences of Darmstadt in Germany and the MPhil and PhD
degree from Brunel University London. He has been working in
the industry more than 15 years as a Chief Design Engineer. He
is responsible for design and development of electrical power
including power distribution networks, transformer stations,
protection and control of electrical systems. He is also a Lecturer
at University of Applied Sciences of Mannheim Germany and
VDE in Berlin. His special fields of interest is reactive power
compensation and harmonics, design, protection and control of
electrical power systems, VDE and IEC regulations. He is an
author
of
tree books in electrical engineering being published
in
2000 in German and another tree books in Turkish. He is a
member
of
VDE and IEEE.
V.
CONCLUSIONS
The results presented show that the shunt active power
filter configuration combined with a passive filter