2
203.743.6741 • 203.798.7313 www.preferred-mfg.com Instruments & Controls Catalog 25 Instruments & Controls 228 5004-M-110 QUANTA-FLAME PRIMARY CONTROL System Overview The Quanta-Flame 5004-M-110 controller is a state-of- the-art microcomputer based Burner Management System designed for a single burner boiler or process heat application. An LCD display provides real-time diagnostic and status messages for the operator. Unlike other flame safeguard controllers that require a variety of modules to make a complete system (programmers, flame amplifiers, displays, etc.) the Preferred Quanta-Flame 5004-M-110 has just one processor with a built-in universal amplifier that accepts UV, IR and Flame Rod inputs. Service technicians can carry this one processor on their trucks and be equipped to replace a large number of existing flame safeguard controller combinations. The 5004-M-110 replaces the following Fireye E110 combinations: E110 Flame monitor consisting of EB700 Chassis and EC600 Dust cover E110 Compatibility: Any of these Amplifiers Any of these Programmers EUV1-Standard UV EP160 E1R1-Infrared EP161 E1R2-Infrared EP170 E1R3-Infrared EPD160 ERT1-Flame Rectification EPD161 EPD170 Quanta-Flame Primary Control Quanta-Flame Primary Control Dimensions The 5004-M-110 mounts directly into an existing 60- 1466-2 or 60-1386-2 wiring sub-base. The 5004-M-110 interfaces to the annunciator QA 5004- 85 when additional annunciation is required. Existing flame sensors and scanners can be reused. An auxiliary connector is used for interface with Modbus communication or to provide a remote reset function.

5004-M-110 QUANTA-FLAME PRIMARY CONTROL System ......The 5004-M-110 replaces the following Fireye E110 combinations: E110 Flame monitor consisting of EB700 Chassis and EC600 Dust cover

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: 5004-M-110 QUANTA-FLAME PRIMARY CONTROL System ......The 5004-M-110 replaces the following Fireye E110 combinations: E110 Flame monitor consisting of EB700 Chassis and EC600 Dust cover

203.743.6741 • 203.798.7313www.preferred-mfg.com

Instruments & Controls

Catalog 25

Inst

rum

ents

& C

ontro

ls

228

5004-M-110 QUANTA-FLAME PRIMARY CONTROL SystemOverview

TheQuanta-Flame5004-M-110controllerisastate-of-the-artmicrocomputerbasedBurnerManagementSystemdesignedforasingleburnerboilerorprocessheatapplication.AnLCDdisplayprovidesreal-timediagnosticandstatusmessagesfortheoperator.

Unlikeotherflamesafeguardcontrollersthatrequireavarietyofmodulestomakeacompletesystem(programmers,flameamplifiers,displays,etc.)thePreferredQuanta-Flame5004-M-110hasjustoneprocessorwithabuilt-inuniversalamplifierthatacceptsUV,IRandFlameRodinputs.

Servicetechnicianscancarrythisoneprocessorontheirtrucksandbeequippedtoreplacealargenumberofexistingflamesafeguardcontrollercombinations.

The5004-M-110replacesthefollowingFireyeE110combinations:E110FlamemonitorconsistingofEB700ChassisandEC600Dustcover

E110Compatibility:

AnyoftheseAmplifiers AnyoftheseProgrammersEUV1-StandardUV EP160

E1R1-Infrared EP161E1R2-Infrared EP170E1R3-Infrared EPD160

ERT1-FlameRectification EPD161EPD170

Quanta-Flame Primary Control

Quanta-Flame Primary Control Dimensions

The5004-M-110mountsdirectlyintoanexisting60-1466-2or60-1386-2wiringsub-base.The5004-M-110interfacestotheannunciatorQA5004-85whenadditionalannunciationisrequired.Existingflamesensorsandscannerscanbereused.AnauxiliaryconnectorisusedforinterfacewithModbuscommunicationortoprovidearemoteresetfunction.

Page 2: 5004-M-110 QUANTA-FLAME PRIMARY CONTROL System ......The 5004-M-110 replaces the following Fireye E110 combinations: E110 Flame monitor consisting of EB700 Chassis and EC600 Dust cover

203.743.6741 • 203.798.7313www.preferred-mfg.com

Instruments & Controls

Catalog 25

Instruments &

Controls

229

5004-M-110 QUANTA-FLAME PRIMARY CONTROL SystemOverview

Quanta-Flame Primary Control Wiring Diagram