5004-M-110 QUANTA-FLAME PRIMARY CONTROL SystemOverview
TheQuanta-Flame5004-M-110controllerisastate-of-the-artmicrocomputerbasedBurnerManagementSystemdesignedforasingleburnerboilerorprocessheatapplication.AnLCDdisplayprovidesreal-timediagnosticandstatusmessagesfortheoperator.
Unlikeotherflamesafeguardcontrollersthatrequireavarietyofmodulestomakeacompletesystem(programmers,flameamplifiers,displays,etc.)thePreferredQuanta-Flame5004-M-110hasjustoneprocessorwithabuilt-inuniversalamplifierthatacceptsUV,IRandFlameRodinputs.
Servicetechnicianscancarrythisoneprocessorontheirtrucksandbeequippedtoreplacealargenumberofexistingflamesafeguardcontrollercombinations.
The5004-M-110replacesthefollowingFireyeE110combinations:E110FlamemonitorconsistingofEB700ChassisandEC600Dustcover
E110Compatibility:
AnyoftheseAmplifiers AnyoftheseProgrammersEUV1-StandardUV EP160
E1R1-Infrared EP161E1R2-Infrared EP170E1R3-Infrared EPD160
ERT1-FlameRectification EPD161EPD170
Quanta-Flame Primary Control
Quanta-Flame Primary Control Dimensions
The5004-M-110mountsdirectlyintoanexisting60-1466-2or60-1386-2wiringsub-base.The5004-M-110interfacestotheannunciatorQA5004-85whenadditionalannunciationisrequired.Existingflamesensorsandscannerscanbereused.AnauxiliaryconnectorisusedforinterfacewithModbuscommunicationortoprovidearemoteresetfunction.