475 project

Embed Size (px)

Citation preview

  • 8/7/2019 475 project

    1/22

    American University of Beirut

    Department of Electrical and Computer Engineering

    EECE 475 Industrial Electrification

    Design Project 6

    Fall 2010 2011

  • 8/7/2019 475 project

    2/22

    Presented to

    Prof. Chahine

    Prepared by

    Tarik Ibrahim

    Jad Karaa

    Sabine Khalil

    Rand Kassamany

  • 8/7/2019 475 project

    3/22

    1.Power Factor Correction1.1Power Factor

    Power factor corrections are supposed to reduce electricity consumption of a firm. Othersdispute that and argue it reduces only electricity costs in case the power utility is offering a

    tariff where a reactive power demand charge are part of the monthly electricity bill. In

    discussing the nature or phenomena of reactive power experts use incomprehensive equations

    or explanations.

    The vector combination of these two power components (active and reactive) is termed as

    Apparent Power (measured in kVA), the value of which varies considerably for the same

    active power depending upon the reactive power drawn by the equipment. The ratio of the

    active power (kW) of the load to the apparent power (kVA) of the load is known as the

    power factor of the load.

    Power Factor = __Active Power (kW) __

    Apparent Power (kVA)

    Thus when the nature of the load is purely resistive the kVAr or the reactive component will

    be nil and thus the angle will be equal to 0 degrees and the power factor will be equal to

    unity. For a purely inductive load the power factor will be lagging and for a purely capacitive

    load the power factor will be leading.

    Thus, it is evident from above that, more the power factor departs from unity the more will

    be the kVA demand for the same kW load. Since most of the HT tariffs include kVA

    Demand charges along with the Energy Charges, the more the kVA demand for the same kW

    load the more shall be the electricity bill of the consumer. To say it otherwise, the customers

    with a low power factor will pay more for their useful electrical power. (The Billing demand

    for the month is generally taken to be the actual maximum kVA demand of the consumer

    during the month or a fixed percentage of the contract demand or a fixed kVA value,

    whichever is higher, based on the type of the consumer and the tariff structure of the utility.)

  • 8/7/2019 475 project

    4/22

    1.2 Disadvantages of low power factor

    The disadvantages of a low power factor are:

    y The load draws greater current for the same value of the useful power.

    Current (I1) = __Power (kW)_

    Volts (V) * PF

    If the power factor of the motor is increased the current drawn by the motor will decrease

    Thus, as the power factor decreases the current required for the same value of active, or

    useful, power increases. The result is that the sizes of the equipment, like the switchgear,

    cables, transformers, etc., will have to be increased to cater the higher current in the

    circuit. All this adds to the cost. Further, the greater current causes increased power loss

    or I2

    R losses in the circuits. Also due to higher current, the conductor temperature rises

    and hence the life of the insulation is reduced.

    y Also, with the increased current the voltage drop increases, thereby the voltage at thesupply point is reduced. For different loads it causes voltage drop resulting in :

    - Lower output of the illumination system.- Less current is drawn by the heating devices so that the operating temperature drops.

    This results in increased consumption for the same rise of temperature.- The induction motors slow down and therefore draw more current to produce a fixed

    torque for the loads., and more consumption for the same torque.

    In the transmission and distribution of the current itself, from the generating station to the

    consumer, heating losses will be greater at low power factor (varying in proportion to the

    square of the current) and the voltage drop will be in accordance with relation I*Z (where

    Z is the impedance, combination of resistance and reactance) . Since the losses in the

    electricity system due to low power factor will incur additional cost, it is evident that

    these will have to be reflected to some extent in the charges to the consumers. This is

    implemented by metering the maximum demand in kVA or by applying a low power

    factor penalty component in the tariffs.

  • 8/7/2019 475 project

    5/22

    1.3Advantages of power factor correctionHigher power factors result in:

    - Reduced system losses, and the losses in the cables, lines, and feeder circuits andhence lower sizes could be opted.

    - Improved system voltages, thus enable maintaining rated voltage to motors, pumpsand other equipment. The voltage drop in supply conductors is a resistive loss, and

    wastes power heating the conductors. A 5% drop in voltage means that 5% of your

    power is wasted as heat before it even reaches the motor. Improving the power factor,

    especially at the motor terminals, can improve your efficiency by reducing the line

    current and the line losses.

    - Improved voltage regulation.- Increased system capacity, by release of kVA capacity of transformers and cables for

    the same kW , thus permitting additional loading without immediate augmentation.

    The figure below shows the amount of capacity released for various amounts of

    correction. For the example given previously, the dotted lines indicate the system

    capacity released is 0.13 times the kilowatt load, which in this case is 10.4 kVA.

    - Reduced power costs (depending on the electric utility tariff schedule) due to reducedkVA demand charges and so also by reduced power factor charges.

  • 8/7/2019 475 project

    6/22

    1.4Cost saving due to Power Factor improvementTaking the Tariff as below:

    1. Demand charges Rs. 144/kVA/month

    2. Energy Charges Rs. 4.11 / Unit

    3. PF surcharge for each 1% below 90% 1% of (Demand charges + Energy Charges)

    As we already know, by improving the power factor there will be a reduction in the kVA

    demand of the load. Thus , in this case the kVA MD will drop from 400 kVA (at 79.7%) to

    327.78 kVA (at 90%):

    Load 1:

    SL1 = 100 kVA p.f. = 0.85 = 1

    PL1 = SL1 1 = 100 0.85 = 85 kW

    Load 2:

    SL2 = 300 kVA p.f. = 0.7 = 2

    PL2 = SL2 2 = 300 0.7 = 210 kW

    PTotal = PL1 + PL2 = 85 + 210 = 295 kW

    p.f. = 0.797

    S1 = 400 kVA

    S2= PTotal /0.9=327.78KVA

    Therefore reduction in energy bill due to reduction in maximum demand due to improved power

    factor from 0.797 to 0.9 shall be:

    Rs. 144.00 * (400-327.78)= Rs. 10399.68 per month

    In addition, by increasing the power factor from 79.7% to 90% , there shall be no power factor

    penalty/surcharge on account of low power factor. Thus the savings due to avoidance of the PF

    surcharge per month would be as below:

  • 8/7/2019 475 project

    7/22

    Rs. ((400-327.78)*144*(90-79.7))*1/100= Rs. 1071.16

    Thus the total monthly reduction in bill due to P.F improvement from 0.797 to 0.9 would be:

    Rs. 10399.68 + 1071.16 = Rs. 11470.84 per month.

    Net reduction per annum = 11470.84*12=137650.08 per year

    1.5 Cost of investment for Power Factor improvement:

    QC = Ptotal[ 1)) comp))]

    = Ptotal[ ]

    = 295 ( tan 37.16 - tan 25.84)

    = 80.73kVAR

    QL = S = 400 sin 37.16 = 241.59 kVAR

    Qcomp = QL - QC = 241.59 80.73 = 160.86 kVAR

    IL =

    =

    = 607.737 A

    IC = I =

    =

    = 350.877 A

    C =

    =

    = 2.939 mF

    Size of capacitor required to improve the PF from 0.797 to 0.9

    = kVA1* Sin1 kVA2* Sin2

    =400*sin(37.15) 327.78*Sin(25.84) = 98.70 kVAr

    If we take the cost of capacitor bank per kVAr as Rs. 200/KVAr,

    The cost of the capacitor bank = 98.7*200 = Rs. 19739

    Cost of switching and associated equipment = Rs. 1000 and installation, etc.

    Total cost = Rs. 20739

  • 8/7/2019 475 project

    8/22

  • 8/7/2019 475 project

    9/22

    y Static capacitors which are electrical devices without moving parts that have the ability toprovide magnetizing current to the load. Their efficiency is high since losses are less than

    one-half of 1 percent of their kVAC (or kVAR) rating.

    In the past two other types of equipment were used to supply kVAr to a system: synchronous

    condensers and synchronous converters. Both of these machines have been replaced

    principally by the use of static capacitors.

    Static capacitors are the cheapest and the simplest means for reactive power compensation .

    They are installed by power utilities in the transmission and distribution network and also at

    the consumers premises on to different loads such as motors, transformers, incoming supply,

    etc. In present days automatic switching of the capacitors enables keeping a high power

    factor for heavily fluctuating loads as well.

    1.7 kVAr Compensation or Power Factor Correction

    With the present scenario of power crisis it has become all the more important that whatever

    energy is available, it should be used most optimally. For these reasons proper management

    of the reactive power is all the more significant. In a power system, it is important that the

    power utilities and the consumer both work together for providing the reactive power

    compensation. The power utilities have to provide reactive compensation for the transmissionsystems reactive power requirement, reduction of line losses and improved voltage

    regulation. The consumers have to compensate for the additional reactive power requirement

    by the loads at their installations.

    The power utilities take a number of steps for installation of reactive power compensation

    equipment. These include:

    33 kV series compensation equipment.

    220 kV series compensation equipment.

    Synchronous condensers.

    33 kV shunt capacitors.

  • 8/7/2019 475 project

    10/22

    11 kV and LT shunt capacitors.

    Static VAR compensation equipment.

    Further steps are continuously being taken by the utilities to make their system healthy and

    for providing additional compensation based on the system studies carried out.

    Based on the reactive power requirement at their installations, the consumers have to provide

    for the necessary reactive compensation at their end to achieve the minimum power factor

    level prescribed by the utility (0.9). The most economical and reliable method of reactive

    compensation is the installation of power capacitors. Lagging power factor can be corrected

    by connecting capacitors in parallel with the system. The current in a capacitor produces a

    leading power factor. Current flows in the opposite direction to that of the inductive device.

    When the two circuits are combined, the effect of capacitance tends to cancel that of the

    inductance.

    Most customer loads (particularly motors, but many lighting circuits also) are inductive. A

    low power factor can generally be corrected by connecting appropriate capacitors. This is not

    the case if low power factor is caused by harmonics, in which case the installation of

    capacitors will not help, and may cause a serious problem. In high harmonic situations,

    expert help should be obtained before attempting to correct power factor problems.

    kVAr component before PF correctionResultant kVAr component after correction.

  • 8/7/2019 475 project

    11/22

    Note the smaller resultant with the capacitors added, but real power (kW) does not change. A

    properly chosen capacitance value will neutralize the inductance and produce unity power

    factor. Too little or too much capacitance must be avoided. Too little will not correct to a

    sufficiently high power factor to eliminate a surcharge, and too much will result in leading

    power factor with possible undesirable effects.

    2.Optimum point for Power SupplyFor 400KVA load we need to feed the premise with medium voltage overhead lines with a

    distance of 150 m away from the 300KVA Load.

    The cable cross section used is 2x (3x240) and thus we will be reducing line losses.

    The utility breaker has to be placed according to the electric moment method. Refer to the

    figure in Appendix A.

    2.1 Overhead Lines

    In overhead lines, we have three components:

    y Conductors: cross- section and number of conductors (there is usually five conductors-three phases, 1 neutral and one for the municipality lighting). Conductors could be bare

    copper or aluminum alloy (mostly alloy because Al doesnt have enough mechanical

    strength to withstand the mechanical stresses) or insulated preassembled aerial cable for

    MV.

    y Support:a. Steel: Various types are present:

    i. I- beam: has a lot of weight but takes a very small space for the sameconductors sizes; a higher weight/km is used.

    ii. Lattice: Weight/ Km for the same conductors is smaller but larger basearea is needed.

  • 8/7/2019 475 project

    12/22

    b. Wood: Special types of wood. Classified according to :i. reputing capacity at the top (how much pull I put on the top of the pole to

    break it)

    ii. Length of the poleiii. Diameter of the top/ bottom

    c. Concrete: It must have special forms (rectangular or square form). Steel barsinside them are sized and then molded into concrete slaps.

    On each angle put a wedge, and later install a pole (more stresses).

    Partial distance between two wedges must be marked.

    The larger the angle the stronger is the support required.

    To increase the height of the line above ground, we have to increase either the height of the

    supports or increase their number. As the span increases then higher mechanical stresses

    (stronger support is needed).

    2.2 MV Lines

    MV lines have four basic components:

    y Conductors :Conductors can be copper as per our case or aluminum alloy.

    y Supports:The support can be steel or toughened glass or porcelain.

    y Insulator chains and accessories:Insulation could be suspended or rigid

  • 8/7/2019 475 project

    13/22

    y Base of supportSupport steel is used in lattice form. We will not use I beam because it is very costly and

    we need high Kg of support/ Km.

    The connection is considered from M.V. (B.B.) through a M.V. cubicle and the sealing

    end (Termination) and it is housed normally in a cubicle.

    3.Distribution Sub-StationsAfter the overhead line we need a Distribution Sub-Stations (DSS). We would obviously

    save in cable sizes and hence cost, obtain a better voltage regulation, and thus save losses.

    Its function is to transfer power from MV to LV. It is composed basically of:

    yMV switch gearyLV switch gearyMV/LV transformersyMV busbarsyLV busbarsy

    Accessories

  • 8/7/2019 475 project

    14/22

    The MV switch gear installed on the nearest accessible steel-pole. The pole supports the

    transformer and its accessories, MV feeders, LV feeders & switchgear and panel board.

    Anchoring clamp will have to withstand the tension of the MV feeder as it hooked to the

    pole. It supports the MV feeder. A grip clamp to elongate the live conductors from the

    grounded parts of the DSS. A chain of 3 insulators are used to isolate the anchoring clamp

    from the support. Spark gaps are used for protection of the insulators and the transformer

    from voltage surges; its insulation is lower than that of the chain so that itt can divert the

    surges to ground. Aluminum- Copper joint is used when the line conductors are Aluminum

    alloy and transformer windings are made of copper, to avoid voltaic effect. Transformer is

    composed of tank, cooling /insulating oil, steel core, MV and LV windings., and MV and LV

    brushings (insulators + transversal conductor through it)

    The transformer has a built in hook, casted or welded on its tank. This hook is clamped on a

    steel bar not less than 3.5cm. in diameter, firmly anchored to the support.

    A UPN beam, about 1m long and up to 1ton capacity having a hook on its end to which a

    mobile tray could be anchored.

    LV feeder goes down from LV winding to the panel board. LV switch gear (a CB housed in a

    DSS LV panel board). A minimum of 2 LV feeders to supply the local LV network with 5

    conductors. Concrete platform is used for man oeuvre and repair and exploitation. A 25mm2

    bare copper conductor or steel equivalent is used for the grounding of the pole.

    3.1 Built-in Sub-station

    Built in area or where the transformer is larger than 400 KVA (to give the power

    required). Most important is the one used in Beirut. The built-in area (has to have housing

    i.e needs a room) used to house the DSS is not included in the covered area permitted by

    the municipalities of Beirut or the city planning in the region.

    3.2Housing the TransformerWe need a minimum of 16 m

    2(not included in the covered up area in the city planning) built

    in area for a normal DSS. It is composed of:

    y Medium voltage switch gear with the incoming and outgoing feeders

  • 8/7/2019 475 project

    15/22

    y Transformers with auxiliaryy LV switch gear and feedersy Housing- support

    Termination is the junction between the end of the feeder and the switch gear. This ceiling is

    applied to medium and low voltages. It must be covered (ambient proof cover) to prevent

    entrance of dust, humidity, rats, and to prevent cockroaches to eat the insulation. Joints are

    the potential source of faults, so they are used when necessary only.

    A minimum of 3 cells or cubicles (on the MV side because if we want to do any

    maintenance, it is used to protect personnel) that have the following dimensions

    a.

    90cm widthb. 3m height

    Partitions are made of steel.

    Transformer is installed on a pedestal (hollow seat) where the transformer is fixed- it is an

    opening with a volume several times that of the transformer oil, then it is put on a railed

    beam in order to move/ roll it easily)

    Pedestal has a connection to the sewage system (fill the bottom with material that is

    inflammable and protect against burning oil). They also allow for ventilation.

  • 8/7/2019 475 project

    16/22

    Appendix A:

    Figure 1

  • 8/7/2019 475 project

    17/22

    Figure 2

  • 8/7/2019 475 project

    18/22

    Appendix B:

    Meeting Minutes (1) of EECE 475 Design Project 6Date: O

    ctober 20, 2010

    Location: Professor Chahines Office Bechtel 324A

    Attendees:

    Prof. Chahine, Tarek Ibrahim, Jad Karaa, Rand Kassamany, Sabine Khalil

    Absence:None

    Agenda:

    1. The meeting was called to order on Wednesday, October 20 at 11:30 am byProfessor Chahine.

    2. A primary sketch of the design was drawn and discussed by Prof. Chahine andthe group members.

    3.

    The following questions were raised:y Do we have to leave the loads at their current consumption?y Should we choose an individual or separate power factor correction?y How can we supply the loads and which is the best alternative?y Where are M.V. and L.V. used?

    4. All members agreed upon seeking information from the utility to give us thebasic information about the prices.

    5. The meeting was adjourned by Prof. Chahine at 12:05 pm.

  • 8/7/2019 475 project

    19/22

    Meeting Minutes (2) of EECE 475 Design Project 6Date: October 27, 2010

    Location: Professor Chahines Office Bechtel 324A

    Attendees:

    Prof. Chahine, Tarek Ibrahim, Jad Karaa, Rand Kassamany, Sabine Khalil

    Absence:None

    Agenda:1. The meeting was called to order on Wednesday, October 27 at 11:40 am by

    Professor Chahine.

    2. The minute of Wednesday October 20 were approved unanimously.3. The choice of individual or central compensation was discussed.4. A sketch of the main panel along with the loads and the CB were drawn and

    discussed.

    5. All group members agreed to go to the utility within the coming week to gaininformation about the role of the utility in supplying, whether to use medium

    voltage or low voltage, and whether to use overhead or underground live.

    6. connected capacitors have to be used, but are they connected locally orcentrally?

    7. The meeting was adjourned by Prof. Chahine at 12:05 pm.

  • 8/7/2019 475 project

    20/22

    Meeting Minutes (3) of EECE 475 Design Project 6Date: November 10, 2010

    Location: Professor Chahines Office Bechtel 324A

    Attendees:

    Prof. Chahine, Jad Karaa, Rand Kassamany, Sabine Khalil

    Absence:Tarek Ibrahim

    Agenda:8. The meeting was called to order on Wednesday, November 10 at 11:30 am by

    Professor Chahine.

    9. The minute of Wednesday October 27 were approved unanimously.10.A discussion of the line losses was held. It has to be taken into consideration

    while compensating the power factor.

    11.If the power factor has to be taken centrally, where shall the capacitor bankbe placed?

    12.The following points are to be discussed in the utility:y Where will the utility give us, centrally or individually?y Where to put the panel board and how to feed the loads?y The types of cables used and how to lay the cables?y The voltage drop?

    13.The members agreed that the power factor correction will reduce the powerlosses and the cables used will be of smaller cross-section hence losses are

    reduced.

    14.The meeting was adjourned by Prof. Chahine at 11:50 am.

  • 8/7/2019 475 project

    21/22

    Meeting Minutes (4) of EECE 475 Design Project 6Date: November 10, 2010

    Location: Professor Chahines Office Bechtel 324A

    Attendees:

    Prof. Chahine, Tarek Ibrahim, Jad Karaa, Rand Kassamany, Sabine Khalil

    Absence:None

    Agenda:

    15.The meeting was called to order on Monday, November 29 at 11:00 am byProfessor Chahine.

    16.The minute of Wednesday November 10 were approved unanimously.17.A discussion of the utility findings was held.18.It depends on us where to place the room of electricity, and what is placed

    inside the premises would be on our expense.

    19.We have to use a MV source; it has to be overhead and not underground. Thefirst 200m is on the utility.

    20.We have to take the rules that govern the utility into consideration and how itapplies on private property with the right of way.

    21.The electric moment was done:300x = 100(60-x) 300x = 6000 100x

    x = 15m22.A discussion of the cables was held. If we chose underground, the the cost

    would roughly be 10 times that of overhead.

    23.While calculating the power factor, the losses on the 60m has to beconsidered.

    24.The meeting was adjourned by Prof. Chahine at 11:30 am.

  • 8/7/2019 475 project

    22/22

    Appendix C:

    References:

    [1] Grondzik, Kwok, Stein, & Reynolds. Mechanical and Electrical Equipment for Buildings.11

    thEdition.

    [2] EECE 475 Draft

    [3] EDL