400 kv swyd FOR DOJ

  • Upload
    sam

  • View
    225

  • Download
    1

Embed Size (px)

Citation preview

  • 7/31/2019 400 kv swyd FOR DOJ

    1/49

  • 7/31/2019 400 kv swyd FOR DOJ

    2/49

    Understanding basics of switchyard

    Switchyard equipments and schemes

    Functions of various equipments

    Brief description of modes of transmission

  • 7/31/2019 400 kv swyd FOR DOJ

    3/49

    What is a Switchyard ?What is a Switchyard ?It is a switching station which has the following credits :It is a switching station which has the following credits :

    (i) Main link between Generating plant and(i) Main link between Generating plant and

    Transmission system, which has a large influence onTransmission system, which has a large influence on

    the security of the supply.the security of the supply.

    (ii) Step-up and/or Step-down the voltage(ii) Step-up and/or Step-down the voltage

    levels depending upon the Network Node.levels depending upon the Network Node.

    (iii) Switching ON/OFF Reactive Power Control(iii) Switching ON/OFF Reactive Power Control

    devices, which has effect on Quality of power.devices, which has effect on Quality of power.

  • 7/31/2019 400 kv swyd FOR DOJ

    4/49

    Power evacuation from switchyardPower evacuation from switchyard

    400 KV LINES400 KV LINES

    VINDHYACHAL-JABALPUR # 1VINDHYACHAL-JABALPUR # 1 VINDHYACHAL-JABALPUR # 2VINDHYACHAL-JABALPUR # 2

    VINDHYACHAL-JABALPUR # 3VINDHYACHAL-JABALPUR # 3 VINDHYACHAL-JABALPUR # 4VINDHYACHAL-JABALPUR # 4 VINDHYACHAL- SATNA # 1VINDHYACHAL- SATNA # 1 VINDHYACHAL- SATNA # 2VINDHYACHAL- SATNA # 2

    VINDHYACHAL- SATNA # 3VINDHYACHAL- SATNA # 3 VINDHYACHAL- SATNA # 4VINDHYACHAL- SATNA # 4 VINDHYACHAL- KORBA # 1VINDHYACHAL- KORBA # 1 VINDHYACHAL- KORBA # 2VINDHYACHAL- KORBA # 2

  • 7/31/2019 400 kv swyd FOR DOJ

    5/49

    POWER ALLOCATIONPOWER ALLOCATION

    Stage I & II Stage IIIStage I & II Stage III

    Gujrat 23.6% 23.9%Gujrat 23.6% 23.9% MH 36.1% 31.9%MH 36.1% 31.9%

    MP 29.5% 23.1%MP 29.5% 23.1%

    CG 3.4% 4.2%CG 3.4% 4.2% Goa, daman, dadar 7.4% 1.9%Goa, daman, dadar 7.4% 1.9%

    & nagar haweli& nagar haweli

  • 7/31/2019 400 kv swyd FOR DOJ

    6/49

    Type of

    Clearance

    400 KV

    Phase toEarth

    clearance

    3800mm

    Phase to

    Phase

    clearance

    4000 mm

    Section

    clearance

    6500 mm

    The minimum clearances for 400 KV switchyard are as follows:

    Clearances

  • 7/31/2019 400 kv swyd FOR DOJ

    7/49

    400 KV

    Highest System Voltage 420 KV RMS

    Lightning Impulse Voltage 1425 KVp

    Switching Impulse Voltage 1050 KVp

    Power Freq withstand

    voltage for 1 minute

    630 KV RMS

    MaximumFault Level (for1 second) 40 KA

    Minimum Creepage dist 10500 mm

    parameters

  • 7/31/2019 400 kv swyd FOR DOJ

    8/49

  • 7/31/2019 400 kv swyd FOR DOJ

    9/49

    OUTGOING LINE

  • 7/31/2019 400 kv swyd FOR DOJ

    10/49

  • 7/31/2019 400 kv swyd FOR DOJ

    11/49

    PICTORIAL VIEW OF 400KV SWITCHYARD AT

    VSTPS

    http://var/www/apps/conversion/current/tmp/scratch17457/sld%20of%20all%20stages%20switchyard.pdfhttp://var/www/apps/conversion/current/tmp/scratch17457/sld%20of%20all%20stages%20switchyard.pdf
  • 7/31/2019 400 kv swyd FOR DOJ

    12/49

    Bay DetailsBay DetailsThere are 38 nos. of 400 KV bays in VSTPSThere are 38 nos. of 400 KV bays in VSTPS

    switchyard.switchyard.

    1) 10 Nos. of 400 KV, GT Bay1) 10 Nos. of 400 KV, GT Bay2) 3 Nos. of 400/132 KV, 200 MVA ICT Bay2) 3 Nos. of 400/132 KV, 200 MVA ICT Bay

    3) 10 Nos. of 400 KV Line Bay3) 10 Nos. of 400 KV Line Bay

    4) 4 Nos. of 400 KV Bus Sections4) 4 Nos. of 400 KV Bus Sections

    5) 3 Nos. of Bus Coupler Bay5) 3 Nos. of Bus Coupler Bay6) 3 Nos. of Transfer Bus Coupler6) 3 Nos. of Transfer Bus Coupler7) 2 Nos. of HVDC bay7) 2 Nos. of HVDC bay

  • 7/31/2019 400 kv swyd FOR DOJ

    13/49

    Equipments commonly found in switchyard :Equipments commonly found in switchyard :

    Circuit breakerCircuit breaker IsolatorIsolator Instrument transformerInstrument transformer

    Surge arrestorSurge arrestor Shunt reactorShunt reactor Wave trapWave trap Inter connecting transformerInter connecting transformer Neutral grounding reactorNeutral grounding reactor Post insulatorPost insulator DC systemDC system EarthingEarthing

  • 7/31/2019 400 kv swyd FOR DOJ

    14/49

    Functions of various equipments :Functions of various equipments :

    Circuit breakers :Circuit breakers :

    -- Makes or automatically breaks the electrical circuits underMakes or automatically breaks the electrical circuits underLoaded condition.Loaded condition.

    Isolators :Isolators :

    -- Opens or closes the electrical circuits under No-loadOpens or closes the electrical circuits under No-loadconditions.conditions.

    Instrument transformers :Instrument transformers :-- For stepping-down the electrical parameter (Voltage orFor stepping-down the electrical parameter (Voltage or

    Current) to a lower and safe value for Metering andCurrent) to a lower and safe value for Metering andProtection logics.Protection logics.

    Lightning arrestorsLightning arrestors

    -- Safe guards the equipment by discharging the high currentsSafe guards the equipment by discharging the high currentsdue to Lightning.due to Lightning.

    Earth switch :Earth switch :

    -- Used to connect the charged body to ground to dischargeUsed to connect the charged body to ground to dischargethe trapped charge to have a safe maintenance zone.the trapped charge to have a safe maintenance zone.

  • 7/31/2019 400 kv swyd FOR DOJ

    15/49

    Post insulatorPost insulator::

    -- used for supporting bus bars, CTs, PTs, CBs etc.used for supporting bus bars, CTs, PTs, CBs etc.

    ICTICT::-- used to interconnect two grids/system operating at twoused to interconnect two grids/system operating at twodifferent voltages.different voltages.

    NGRNGR::

    -- used for low impedance grounding of high voltage systemused for low impedance grounding of high voltage systemto limit the line to ground fault current under system faultto limit the line to ground fault current under system faultconditions.conditions.

    DC systemDC system::

    -- required for control and protection supply for switchgear,required for control and protection supply for switchgear,

    indications, annunciation system and also for emergencyindications, annunciation system and also for emergencylighting.lighting.

  • 7/31/2019 400 kv swyd FOR DOJ

    16/49

    Overhead earth wireOverhead earth wire ::

    -- Protects the O/H transmission line from Lightning strokes.Protects the O/H transmission line from Lightning strokes.

    Bus barBus bar ::

    -- Conductors to which a number of circuits are connected.Conductors to which a number of circuits are connected.

    Wave Traps/Line trapsWave Traps/Line traps ::

    -- Used in PLCC circuits for Communication and telemetering.Used in PLCC circuits for Communication and telemetering.

    Reactive Power control devicesReactive Power control devices ::

    -- Controls the reactive power imbalance in the grid byControls the reactive power imbalance in the grid by

    switching ON/OFF the Shunt Reactors, Shunt Capacitors etc.switching ON/OFF the Shunt Reactors, Shunt Capacitors etc.

    Current Limiting ReactorsCurrent Limiting Reactors ::

    -- Limits the Short circuit currents in case of fault.Limits the Short circuit currents in case of fault.

  • 7/31/2019 400 kv swyd FOR DOJ

    17/49

    Can break or make the circuit on load and even on faults.

    SF6gas is used for arc quenching medium since it has outstanding arc-

    quenching properties and very good dielectric strength .

    Each pole of breaker consists of 2 interrupter unit, a bell crank

    mechanism with grading capacitors & PIR.

    Bell Crank Mechanism converts the vertical movement of operating

    rod into linear horizontal movement of moving parts of interrupter &

    PIR.

    Grading Capacitor ensures uniform voltage distribution in open

  • 7/31/2019 400 kv swyd FOR DOJ

    18/49

  • 7/31/2019 400 kv swyd FOR DOJ

    19/49

  • 7/31/2019 400 kv swyd FOR DOJ

    20/49

  • 7/31/2019 400 kv swyd FOR DOJ

    21/49

    400 KV Circuit Breaker parameters

    Rated Voltage 420 kV (rms)

    Rated continuous current minimum 2000A/3150A

    Rated short ckt breaking current 40 kA

    Rated short ckt making current 2.5 x 40 kA

    Rated short ckt current duration 3 sec

    Closing time 100 ms (max)

    Opening time 22 ms (max)

  • 7/31/2019 400 kv swyd FOR DOJ

    22/49

    Operates on no load.It is not meant for breaking load currents. It merely acts as a

    disconnecting switch for isolation of equipments from live parts

    when required for maintenance purpose.

    It can be opened only when Circuit Breaker is in open position.

    Types of Isolators:-

    Horizontal Centre Break isolator

    Pantograph Isolator

  • 7/31/2019 400 kv swyd FOR DOJ

    23/49

  • 7/31/2019 400 kv swyd FOR DOJ

    24/49

    Pantograph Isolator:-

    TECHNICAL PARAMETERS

  • 7/31/2019 400 kv swyd FOR DOJ

    25/49

    TECHNICAL PARAMETERS

    400KV ISOLATOR

    Rated voltage 420 kV (rms)

    Rated continuous current 2000 A/3150 A

    Rated insulation level

    1) Rated one minute power frequency withstand voltage

    520 KVrms (between live terminals and earth)

    610 KVrms (across isolating distance)

    2) Rated lightning impulse withstand voltage1425 KV

    P(between line terminals and earth)

    1425 KVP

    impulse on one terminal and 240 KVP

    power

    frequency voltage of opposite polarity on other terminals.

  • 7/31/2019 400 kv swyd FOR DOJ

    26/49

    Instrument transformers are used for measurement and

    protection purposes.Types :-

    1) Current Transformer:-

    Steps downs current from high to low value.

    Connected in series with the main circuit

    2) Capacitor Voltage Transformer:-

    Capacitor voltage divider type with electromagnetic unit

    (EMU). EMU comprises of compensating reactor,

    intermediate transformer, protective and damping devices.

  • 7/31/2019 400 kv swyd FOR DOJ

    27/49

    400KV CLASS CT

  • 7/31/2019 400 kv swyd FOR DOJ

    28/49

    400KV CLASS CVT

  • 7/31/2019 400 kv swyd FOR DOJ

    29/49

    ECHNICAL PARAMETERS

    00KV CT (OIL FILLED TYPE)

    Rated current 2000A(peak)

    Number of cores 5(Four for protection

    & one for metering)

    Rated frequency 50 Hz

    System neutral earthing effectively earthed

    Rated system voltage 420 kV (rms)

  • 7/31/2019 400 kv swyd FOR DOJ

    30/49

    CAPACITOR VOLTAGE TRANSFORMER (CVT)

    PARAMETERS 400kV

    Rated frequency 50 Hz

    System neutral earthing effectively earthed

    Rated voltage 420 kV (rms)

    Rated total thermal burden 750 VA

    Number of cores 5(five)

    Installation outdoor Rated insulation level

    1) 1.2/50 microsecond impulse 1425 kVP

  • 7/31/2019 400 kv swyd FOR DOJ

    31/49

    2.4 SURGE ARRESTOR

    Provides protection against lightning or any surge developing.

    Discharges high frequency over voltages to the ground.

    Non linear characteristics.

    TECHNICAL PARAMETERS

  • 7/31/2019 400 kv swyd FOR DOJ

    32/49

    TECHNICAL PARAMETERS

    Particular 400 kV

    Rated system voltage 420 kV

    Rated arrestor voltage 390 kV

    Minimum discharge capability 8 kJ/kV corresponding to minimum

    discharge characteristic

    Switching surge residual voltage (1kA) 730 kVP- minimum

    780 kVP maximumOne minute power frequency withstand

    voltage of arrestor housing

    630 kV(rms)

    Impulse withstand voltage of arrestor 1425 kVP

    Maximum residual voltage at

    1) 10 kA nominal discharge current

    2) 20 kA "

    900 kVP

    975 kVP

  • 7/31/2019 400 kv swyd FOR DOJ

    33/49

    2.5 SHUNT REACTOR

    Provided at sending & receiving end of long transmission line Switched on when the line is to be charged or line is on low load to

    avoid Ferranti Effect by neutralizing shunt capacitance of such lines.

    TECHNICAL PARAMETERS

    Rated voltage 420 kV Rated MVAR 50 at rated voltage Number of phases 3 System fault level 40 kA

    Connection with neutral through load

  • 7/31/2019 400 kv swyd FOR DOJ

    34/49

    Insulation level

    1) Lightning impulse 1.2/50 1300 kV(peak)

    microsecond withstand voltage

    2) Switching surge withstand voltage 1050 kV(peak)

    3) One minute power frequency 630 kV(rms)

    withstand voltage

    Cooling system ONAN

    Ratio of zero sequence reactance

  • 7/31/2019 400 kv swyd FOR DOJ

    35/49

    400KV CLASS SHUNT REACTOR

  • 7/31/2019 400 kv swyd FOR DOJ

    36/49

    2.6 POST INSULATOR

    It is used for supporting bus bars, CTs, PTs, CBs etc. in the

    switchyard. Post type insulator consists of a particular part

    permanently secured in a metal base to be mounted on the

    supporting structure.

  • 7/31/2019 400 kv swyd FOR DOJ

    37/49

    2.7 WAVE TRAP

    Wave trap is inserted into high voltage transmission line to prevent

    undue loss of carrier signal for all power system conditions.

    Its impedance is negligible at power frequency so as not to disturb

    power transmission but is relatively high over the frequency band of

    carrier .

    TECHNICAL PARAMETERS

    Rated power frequency 50 Hz

    Rated system voltage 400 kV

    Rated continuous current 2000 A/3150 A

    Type of tuning Broad band

  • 7/31/2019 400 kv swyd FOR DOJ

    38/49

  • 7/31/2019 400 kv swyd FOR DOJ

    39/49

    2.8 INTERCONNECTING TRANSFORMER:-

    Are normally autotransformer

    Used to interconnect two grids/system operating at two differentsystem voltages (ie.400/132 KV).

    Characterized by wide tapping range & an additional tertiary

    winding which may be loaded or unloaded. Unloaded tertiary

    winding acts a stabilizing winding by providing a path for the thirdharmonic currents.

    TECHNICAL PARAMETRS:-

    MVA Rating 200/120/80

    Voltage Ratio 400/132/33 KV

  • 7/31/2019 400 kv swyd FOR DOJ

    40/49

    Insulation level:

    HV winding-

    1. Lightning impulse withstand voltage 1425 KVp

    2.CW Impulse withstand voltage 1570 KVp

    LV winding-

    1.Lightning impulse withstand voltage 250 KVp

    2.CW Impulse withstand voltage 90 KVrms

    MV winding-

    1. Lightning withstand voltage 650 KVp

    2. Magnetizing inrush current (Amps) 4 times the rated

    current

  • 7/31/2019 400 kv swyd FOR DOJ

    41/49

    ICT

  • 7/31/2019 400 kv swyd FOR DOJ

    42/49

    2.9 NEUTRAL GROUND REACTOR(NGR):-

    Neutral grounding reactors are used for lowimpedance grounding of high voltage systems.

    They limit the line to ground fault current undersystem fault conditions by providing additionalreactance which neutralizes the capacitive currents.

    RatingUnder balanced operating conditions, there isessentially no continuous current flowing through theneutral grounding reactor. Therefore, the rated

    current of this reactor is considered to be the thermalshort time current under fault conditions . Theduration of the short time rating is time dependent,and is specified as 10 sec or 1minute

  • 7/31/2019 400 kv swyd FOR DOJ

    43/49

  • 7/31/2019 400 kv swyd FOR DOJ

    44/49

    2.10 DC SYSTEM

    DC is required for control and protection supply forswitchgear, indications, annunciation system, communication

    system etc. DC supply is also required for emergency lighting.

    The commonly used voltage levels are 220 V for motors, for

    controls & protection schemes and 48 V for communication.

  • 7/31/2019 400 kv swyd FOR DOJ

    45/49

    Modes

    of

    Transmission

  • 7/31/2019 400 kv swyd FOR DOJ

    46/49

    -- Power can be generated at high voltages.Power can be generated at high voltages.

    - Step-up/Step-down is possible.- Step-up/Step-down is possible.

    -- Requires more copper.Requires more copper.- Due to Skin effect, the effective- Due to Skin effect, the effectiveresistanceresistance is increasedis increased

    - Continuous loss of power due to charging current even- Continuous loss of power due to charging current even

    when the line is open.when the line is open.

    - Requirement of Transposition of conductors.- Requirement of Transposition of conductors.

  • 7/31/2019 400 kv swyd FOR DOJ

    47/49

    -- Low cost due to less copper requirementLow cost due to less copper requirement

    - No Stability and synchronizing problems.- No Stability and synchronizing problems.

    - Asynchronous lines (Interregional ties)- Asynchronous lines (Interregional ties)

    - No increase in Fault level if interconnected.- No increase in Fault level if interconnected.- Less Corona and RI.- Less Corona and RI.

    - Better Voltage regulation due to absence of- Better Voltage regulation due to absence ofInductance.Inductance.

    - Requires less insulation as the potential stress is less.- Requires less insulation as the potential stress is less.

    -- Higher generation is not possible due toHigher generation is not possible due tocommutationcommutation

    - Step-up/Step-down is not possible.- Step-up/Step-down is not possible.

  • 7/31/2019 400 kv swyd FOR DOJ

    48/49

    km

    Cost

    100 300 1100500 700 900

    Break Even distance

    HVDC Preferred

    EHVAC Preferred

    Cost of

    Substation

    HVDC

    Line

    EHVAC

    Line

  • 7/31/2019 400 kv swyd FOR DOJ

    49/49