     Power. Passion. Partnership.

    A TOGNUM GROUP BRAND

    Sales ProgramGendriveDiesel Engines Edition 1/15

      valid from 01/2015

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    2/55

    2 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 3

    04  A customer-oriented technological leader

    06 MTU Gendrive rating definition

    12 General specifications

    13  Engine designation

    14  New products

      Gendrive engines - 50 Hz22  3D - Diesel engines for standby power

    28  3E - Diesel engines for standby power with overload

    30  3F - Diesel engines for data center continuous power

    32  3H - Diesel engines for mission critical power

    34  3C - Diesel engines for NPP standby power

    36  3B - Diesel engines for prime power

    42  3G - Diesel engines for grid stability power

    44  3C - Diesel engines for prime power limited

    46  3A - Diesel engines for continuous power

      Gendrive engines - 60 Hz

    48  3D - Diesel engines for standby power

    52  3F - Diesel engines for data center continuous power54  3H - Diesel engines for mission critical power

    56  3C - Diesel engines for NPP standby power

    58  3B - Diesel engines for prime power

    62  3G - Diesel engines for grid stability power

    64  3A - Diesel engines for continuous power

      Gendrive engines (switchable) - 50 / 60 Hz

    66  3D - Diesel engines for standby power (switchable)

    68  3B - Diesel engines for prime power (switchable)

    70  3A - Diesel engines for continuous power (switchable)

    72  Technical engine data

      Cylinder data; dimensions and masses

    82 Explanation emission optimization (TA-Luft)

    Exhaust emissions

    83  Stationary Power Plants

    94 Nonroad Mobile Machinery 

    102 MTU ValueCare

    104 Service network

    107  Conversion table

    Contents   G  e  n  e  r  a   l

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    3/55

    4 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 5

    A customer-orientedtechnology leader.

    MTU is the core brand of Rolls-Royce Power Systems AG, which is

    a world-leading provider of high- and medium-speed diesel and

    gas engines, complete drive systems, distributed energy systems

    and fuel injection systems for the most demanding requirements.

    The product range of MTU is one of the widest and most modern

    in the sector. We offer comprehensive, powerful and reliable

    engine solutions for yachts, commercial ships and naval vessels,construction and industrial vehicles, agricultural machinery,

    mining, rail and military vehicles as well as for the oil and gas

    industry. We also provide a full line of service products to help

    you maximize uptime and performance.

    For over 100 years, MTU has been known for cutting-edge

    innovation and technological leadership. That same spirit of

    innovation inspires our sustainability efforts. Today and in the

    future, our focus is on developing and implementing system

    solutions to maximize efficiency and meet emissions standards.

    MTU supplies its customers with technologically-

    advanced products that are proven in the field.

    MTU’s range of products and services for

    off-highway applications is extensive and includes

    both standard and customized solutions.

       G  e  n  e  r  a   l

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    4/55

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    5/55

    8 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 9

    MTU Gendriverating definition

    NPP Standy Power (3C)

    NPP Standby Power ratings apply

    to installations in thermal power

    stations. At constant or varying

    load, the number of generator

    set operating hours is unlimited.

    Quoted ratings are in accordance

    with ISO 3046 and are capable

    of 10% overload. Products are

    qualified in accordance with IEEE

    and/or KTA requirements.

    Typical applications:

    nuclear thermal power plants or

    nuclear research facilities

    Prime Power (3B)

    Prime Power ratings apply to

    installations where utility power

    is unavailable or unreliable. At

    varying load, the number of

    generator set operating hours is

    unlimited. Quoted ratings are in

    accordance with ISO 3046 and

    are capable of 10% overload.

    Typical applications:

    construction sites, remote areas

    Grid Stability Power (3G)

    Grid Stability Power ratings

    apply to installations operating

    in support of utility networks

    or grids (especially when renew-

    able power sources are used).

    At constant or varying load,

    the number of generator set

    operating hours is limited to

    1000 hours per year. Full

    power output is available for 500

    hours non-stop operation per

    year. Quoted ratings are in

    accordance with ISO 3046 andare capable of 10% overload.

    Typical applications:

    peak shaving, grid stability and

    capacity programs

    Prime Power Limited (3C)

    Prime Power limited ratings apply

    to installations where utility

    power is unavailable or unreliable.

    At varying load, the number of

    generator set operating hours is

    limited to 1000 hours per year.

    Quoted ratings are in accordance

    with ISO 3046 and are capable

    of 10% overload.

    Main usage:

    peak shaving, grid stability

       G  e  n  e  r  a   l

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    6/55

    10 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 11

    MTU Gendriverating definition    G  e

      n  e  r  a   l

    Continous Power (3A)

    Continuous Power ratings apply

    to installations where one or

    several generator sets serve as

    utility. At constant or varying

    load, the number of generator

    set operating hours is unlimited.

    Quoted ratings are in accor-

    dance with ISO 3046 and are

    capable of 10% overload.

    Typical applications:

    power stations

    Overview of values

    Standby Power Standby Power Data Center Mission Critical NPP Standby

      (3D) with Overload (3E) Continuous Power (3F) Power (3H) Power (3C)

     Load variable variable constant & variable variable variable

     Load factor ≤ 85 % ≤ 85 % ≤ 100 % ≤ 85 % acc. to KTA&IEEE regul.

     10 % overload (ICXN) no yes yes 50 HZ: yes / 60 Hz: no yes

     Max. operating hours

    (per year) 500 h 1)  500 h 1)  unlimited 2)  1000 h 1) unlimited 3)

     Rating definition DIN ISO 3046 - IFN DIN ISO 3046 - ICXN DIN ISO 3046 – ICXN 50 Hz: ISO 3046 - ICXN DIN ISO 3046 – ICXN

      60 Hz: ISO 3046 - IFN

      Prime Power Grid Stability Prime Power Continuous

      (3B) Power (3G) Limited (3C) Power (3A)

     Load variable constant & variable variable constant & variable

     Load factor ≤ 75 % ≤ 100 % ≤ 75 % ≤ 100 %

     10 % overload (ICXN) yes yes yes yes

     Max. operating hours

    (per year) unlimited 1000 h 4)  1000 h  unlimited

     Rating definition DIN ISO 3046 - ICXN DIN ISO 3046 – ICXN DIN ISO 3046 - ICXN DIN ISO 3046 – ICXN

    1) or for the duration of an emergency

    2) in data center application where a reliable utility is present

    3) where a reliable utility is present

    4) 500h with 100% load without interruption

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    7/55

    12 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 13

    Diesel engines for power generation with constant speed

    > Four-stroke, direct-injection

    > Water- and air cooled

    > V or In-line configuration

    Power Definition

    Rated power of diesel engines in this Sales Program

    corresponds to ISO 3046

    ICFN = ISO standard (continuous) fuel stop power

    ICXN = ISO standard (continuous) power exceedable by 10 %

    IFN = ISO standard fuel stop power

    (ratings also apply to SAE J1995 and J1349 standard conditions)

    Standard conditions for diesel engines:

    Barometric pressure: 1000 mbar;

    Site altitude above sea level: 100 m

    Ambient air temperature: 25°C

    Charge-air coolant temp.:

    Series 956 50°C

    Series 2000 55°C for fuel consumption or for

    TA-Luft optimized,

    45°C for for emission optimized

    Series 4000 55°C for fuel consumption or

    TA-Luft optimizied,

    45°C for emission optimized

    Series 4000 Ex3 45°C

    Unless otherwice stated rated power available up to:

    Site altitude above sea level: 400 m

    Ambient air temperature: 40°C

    Power ratings for cogeneration plants and special applications

    on request.

    Please note, specifications are subject to change without further notice.

    All dimensions are approximate, more detailed information is included

    within installation drawings.

    General

    specifications

    Explanation ofthe engine designation

    Series 956

    Example:

    20 V 956 TB 34Design index

    Application segment

    Turbocharged/Charge-air cooling

    Series

    Cylinder-configuration: V = V-engine

    No. of cylinders

    Series 1600 / 2000 / 4000

    Example:

    12 V 4000 G 63 LAdditional engine features

    Design index

    Application segment

    Application

    Series

    Cylinder-configuration: V = V-engine

    R = Inline

    No. of cylinders

    Series 1600/2000/4000/956

    Cooling variants

    Water-to-air charge air cooling (W2A) 2000/4000/956

    Air-to-air charge air cooling (A2A) 1600/2000

    For more information about MTU gendrive diesel engines please visit:

    www.mtu-online.com

       G  e  n  e  r  a   l

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    8/55

    14 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 15

    New products

    Series 4000 Gx3 – 50 Hz & 60 Hz –

    water-to-air charge air cooled (W2A)

    Page 28 / 29: Standby Power with Overload (3E)

    Page 30 / 31: Data Center Continuous Power (3F)

    Page 32 / 33: Mission Critical Power (3H)

    Page 34 / 35: NPP Standby Power (3C)Page 42 / 43: Grid Stability Power (3G)

    The product portfolio of series 4000 Gx3 has been extended by the

    following application groups:

    Series 2000 Gx6 – 50 Hz –

    air-to-air charge air cooled (A2A)

    Page 24 / 25: Standby Power (3D)

    Page 38 / 39: Prime Power (3B)

    The new Series 2000 Gx6 air-to-air charge air cooled gendrive

    engine with common rail injection system is certified to variousemission levels. It serves the power range 665 to 1102 kWm Prime

    Power and up to 1235 kWm in Standby Power.

      Series 2000 Gx6 - 50 Hz

    Frequency: 50 Hz

    Cylinder version: 12V / 16V / 18V

    Power range: 665 - 1235 kWm

    Application groups: Prime Power (3B)

      Standby Power (3D)

    Emissions: Fuel consumption optimized,

    Exhaust emission optimized (TA-Luft)*,

      US EPA Nonroad Tier 2 compliant,

    NEA Singapore for Off Road Diesel Engines

    (ORDE), compliant EPA Tier 2

      Series 4000 Gx3 - 50 Hz

    Frequency: 50 Hz

    Cylinder version: 12V / 16V / 20V

    Application groups: Grid Stability Power (3G)

      Standby Power with Overload (3E)

      Data Center Continuous Power (3F)

      Mission Critical Power (3H)

      NPP Standby Power (3C)

      Series 4000 Gx3 - 60 Hz

    Frequency: 60 Hz

    Cylinder version: 12V / 16V / 20V

    Application groups: Grid Stability Power (3G)

      Data Center Continuous Power (3F)

      Mission Critical Power (3H)

      NPP Standby Power (3C)

    * Explanation see page 82Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

       N  e  w   P  r  o  u  c   t  s

       G  e  n  e  r  a   l

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    9/55

    16 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 17

    New products

    Seris 2000 Gx6 – 50 Hz –

    water-to-air charge air cooled (W2A)

    Page 38 / 39: Prime Power (3B)

    The new Series 2000 Gx6 water-to-air charge air cooled gendrive

    engine with EGR (exhaust gas recirculation) system and common

    rail injection system is certified to India CPCB (ARAI) Stage II andTA-Luft emissions. It serves the power range 665 to 709 kWm.

    Series 2000 Gx6 - 50 Hz

    Frequency: 50 Hz

    Cylinder version: 12V

    Power range: 665 / 709 kWm

    Application groups: Prime Power (3B)

    Emissions: India CPCB (ARAI) Stage II,

      Exhaust emission optimized (TA-Luft)*

       N  e  w   P  r  o  u  c   t  s

       G  e  n  e  r  a   l

    Series 2000 Gx6 – 60 Hz –

    air-to-air charge a ir cooled (A2A)

    Page 48 / 49: Standby Power (3D)

    The new 18V 2000 Gx6 air-to-air charge air cooled gendrive engine

    with common rail injection system is certified to US EPA Nonroad

    Tier 2 Stationary.

    Series 2000 Gx6 - 60 Hz

    Frequency: 60 Hz

    Cylinder version: 18V

    Power range: 1371 kWm

    Application groups: Standby Power (3D)

    Emissions: Fuel consumption optimized,

      US EPA Nonroad Tier 2 compliant,

      US EPA Nonroad Tier 2 Stationary (40 CFR 60)

    * Explanation see page 82Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    10/55

    18 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 19

    Series 2000 Bx6 – 50 Hz / 60 Hz –

    switchable – air-to-air charge air cooled (A2A)

    Page 68 / 69: Prime Power (3B)

    The new Series 2000 Bx6 air-to-air charge air cooled gendrive

    engines feature 50 or 60 Hz frequency selection. They are available

    as 12V, 16V and 18V models.

      Series 2000 Bx6 - 50 Hz / 60 Hz

    Frequency: 50 Hz / 60 Hz

    Cylinder version: 12V / 16V / 18V

    Power range: 709 - 1097 kWm

    Application groups: Prime Power (3B)

    Emissions: Fuel consumption optimized,

    Exhaust emission optimized (TA-Luft)*,

      US EPA Nonroad Tier 2 compliant,

    NEA Singapore for Off Road Diesel Engines

    (ORDE), compliant EPA Tier 2

    * Explanation see page 82Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

       G  e  n  e  r  a   lNew products

    16V 4000 G83L – 60 Hz –

    water-to-air charge air cooled (W2A)

    Page 50 / 51: Standby Power (3D)

    The 16V 4000 G83L water-to-air charge air cooled gendrive engine

    is designed to serve the 2500 kWe power node and is certified to

    US EPA Nonroad Tier 2 Stationary.

      Series 4000 G83L - 60 Hz

    Frequency: 60 Hz

    Cylinder version: 16V

    Power range: 2740 kWm

    Application groups: Standby Power (3D)

    Emissions: Fuel-consumption optimized,

      US EPA Nonroad Tier 2 compliant,

      US EPA Nonroad Tier 2 Stationary (40 CFR 60)

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    11/55

    20 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 21

    New products

    Series 956 TB34

    Page 34 / 35: NNP Standby Power (3C)

    Mission critical standby, grid stability / peak shaving services with

    variable load. The engine family is available with NPP – standby

    service specific qualifications such as KTA 3702 or IEEE.

    Series 956 TB34 - 50 Hz

    Frequency: 50 Hz

    Cylinder Version: 12V / 16V / 20V

    Power range: 3900 – 6500 kWm

    Application groups: NPP Standby Power (3C)

    Emissions: Fuel-consumption optimized

          G    e    n    e    r    a      l

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    12/55

    22 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 23

    kVA kWe kWm bhp

     

    300 240 274 367 x x x x x A2A x 6R 1600 G70F

    330 264 301 404 x x x x x A2A x 6R 1600 G80F

    400 320 358 480 x x x x x A2A x 8V 1600 G70F

    440 352 394 528 x x x x x A2A x 8V 1600 G80F

    500 400 448 601 x x x x x A2A x 10V 1600 G70F

    550 440 493 661 x x x x A2A x 10V 1600 G80F

    650 520 576 772 x x x A2A x 12V 1600 G70F

    715 572 634 850 x x x A2A x 12V 1600 G80F

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    274 kWm - 634 kWmGendrive enginesStandby Power (3D)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is appliedfor calculation and serves as guideline only.

    reference to emission level in price list

    (2) Explanation see page 82

    24 22 251981

    22 25    S   t  a  n   d   b  y   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    13/55

    24 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 25

    kVA kWe kWm bhp

     

    715 572 635 852 x x A2A x 12V 2000 G25

    715 572 635 852 x W2A 12V 2000 G25

    825 660 732 982 x x x A2A x 12V 2000 G76F

    860 688 765 1026 x x A2A x 12V 2000 G65

    860 688 765 1026 x W2A 12V 2000 G65

    1000 800 887 1189 x A2A x 12V 2000 G86F

    1000 800 890 1194 x A2A x 16V 2000 G25

    1000 800 890 1194 x W2A 16V 2000 G25

    1100 880 975 1307 x A2A x 16V 2000 G65

    1100 880 975 1307 x W2A 16V 2000 G65

    1110 888 979 1313 x x x A2A x 16V 2000 G76F

    1250 1000 1100 1475 x A2A x 18V 2000 G65 (3)

    1250 1000 1100 1475 x A2A x 16V 2000 G86F

    1250 1000 1100 1475 x W2A 18V 2000 G65 (3)

    1400 1120 1235 1656 x A2A x 18V 2000 G76F

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    635 kWm - 1235 kWmGendrive enginesStandby Power (3D)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 18V 2000 G65 without power

    reduction available up to 35°C / 400 m

    reference to emission level in price list

    24 22 251981

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25    S   t  a  n   d   b  y   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    14/55

    26 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 27

    kVA kWe kWm bhp

     

    1800 1440 1575 2112 x x W2A 12V 4000 G23

    2000 1600 1750 2347 x x W2A 12V 4000 G63 (4)

    2250 1800 1965 2635 x x W2A 16V 4000 G23

    2500 2000 2185 2930 x x W2A 16V 4000 G63

    2800 2240 2420 3245 x x W2A 20V 4000 G23

    3100 2480 2670 3581 x x W2A 20V 4000 G63 (3)

    3300 2640 2850 3822 x x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    1575 kWm - 2850 kWmGendrive enginesStandby Power (3D)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 20V 4000 G63 without power

    reduction available up to 35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63L

    without power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25    S   t  a  n   d   b  y   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    15/55

    28 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 29

    kVA kWe kWm bhp

     

    1600 1280 1420 1904 x x x W2A 12V 4000 G23

    1800 1440 1575 2112 x x x W2A 12V 4000 G63 (4)

    2100 1680 1798 2411 x x x W2A 16V 4000 G23

    2250 1800 1965 2635 x x x W2A 16V 4000 G63

    2500 2000 2200 2950 x x x W2A 20V 4000 G23

    2800 2240 2420 3245 x x x W2A 20V 4000 G63 (3)

    3000 2400 2590 3473 x x x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    1420 kWm - 2590 kWmGendrive enginesStandby Powerwith Overload (3E)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 20V 4000 G63 without power

    reduction available up to 35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63L

    without power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25

       S   t  a  n   d   b  y   P  o  w  e  r  w   i   t   h   O  v  e  r   l  o  a   d  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    16/55

    30 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 31

    kVA kWe kWm bhp

     

    1600 1280 1420 1904 x x x W2A 12V 4000 G23

    1800 1440 1575 2112 x x x W2A 12V 4000 G63 (4)

    2100 1680 1798 2411 x x x W2A 16V 4000 G23

    2250 1800 1965 2635 x x x W2A 16V 4000 G63

    2500 2000 2200 2950 x x x W2A 20V 4000 G23

    2800 2240 2420 3245 x x x W2A 20V 4000 G63 (3)

    3000 2400 2590 3473 x x x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    1420 kWm - 2590 kWmGendrive enginesData CenterContinuous Power (3F)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 20V 4000 G63 without power

    reduction available up to 35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63L

    without power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25

       D  a   t  a   C  e  n   t  e  r   C  o  n   t   i  n  u  o  u  s   P  o  w  e  r  -   5   0   H

      z241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    17/55

    32 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 33

    kVA kWe kWm bhp

     

    1600 1280 1420 1904 x x x W2A 12V 4000 G23

    1800 1440 1575 2112 x x x W2A 12V 4000 G63 (4)

    2100 1680 1798 2411 x x x W2A 16V 4000 G23

    2250 1800 1965 2635 x x x W2A 16V 4000 G63

    2500 2000 2200 2950 x x x W2A 20V 4000 G23

    2800 2240 2420 3245 x x x W2A 20V 4000 G63 (3)

    3000 2400 2590 3473 x x x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    1420 kWm - 2590 kWmGendrive enginesMission Critical Power (3H)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 20V 4000 G63 without power

    reduction available up to 35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63L

    without power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25

       M   i  s  s   i  o  n   C  r   i   t   i  c  a   l   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    18/55

    34 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 35

    kVA kWe kWm bhp

     

    1800 1440 1560 2092 x W2A 12V 4000 E63 (3) (4)

    2400 1920 2080 2789 x W2A 16V 4000 E63 (3) (4)

    3000 2400 2600 3487 x W2A 20V 4000 E63 (4)

    4400 3520 3900 5230 x W2A 12V 956 TB34 (3)

    5820 4656 5200 6973 x W2A 16V 956 TB34 (3)

    7275 5820 6500 8717 x W2A 20V 956 TB34

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    1560 kWm - 6500 kWm

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25

    Gendrive enginesNPP Standby Power (3C)

       N   P   P   S

       t  a  n   d   b  y   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Available on request

    (4) S4000 E63 with KTA or IEEE

    qualifications

    reference to emission level in price list

    24 22 251981

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    19/55

    36 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 37

    kVA kWe kWm bhp

     

    275 220 249 334 x x x x x x A2A x 6R 1600 G10F

    300 240 274 367 x x x x x x A2A x 6R 1600 G20F

    365 292 325 436 x x x x x x A2A x 8V 1600 G10F

    400 320 358 480 x x x x x x A2A x 8V 1600 G20F

    450 360 407 546 x x x x x x A2A x 10V 1600 G10F

    500 400 448 601 x x x x x x A2A x 10V 1600 G20F

    590 472 524 703 x x x x A2A x 12V 1600 G10F

    650 520 576 772 x x x x A2A x 12V 1600 G20F

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    249 kWm - 576 kWm

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is appliedfor calculation and serves as guideline only.

    reference to emission level in price list

    (2) Explanation see page 82

    24 22 251981

    22 25

    Gendrive enginesPrime Power (3B)

       P  r   i  m  e   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    20/55

    38 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 39

    kVA kWe kWm bhp

     

    650 520 580 778 x x x A2A x 12V 2000 G25

    650 520 580 778 x W2A 12V 2000 G25

    750 600 665 892 x x x x A2A x 12V 2000 G16F

    750 600 665 892 x x W2A 12V 2000 G56F

    780 624 695 932 x x x A2A x 12V 2000 G65

    780 624 695 932 x W2A 12V 2000 G65

    800 640 709 951 x x x x A2A x 12V 2000 G26F

    800 640 709 951 x x W2A 12V 2000 G66F

    910 728 806 1081 x x x x A2A x 16V 2000 G16F

    910 728 810 1086 x x A2A x 16V 2000 G25

    910 728 810 1086 x W2A 16V 2000 G25

    1000 800 890 1194 x x A2A x 16V 2000 G65

    1000 800 890 1194 x x x x A2A x 16V 2000 G26F

    1000 800 890 1194 x W2A 16V 2000 G65

    1135 908 1000 1341 x x A2A x 18V 2000 G65

    (3)

    1135 908 1000 1341 x x x x A2A x 16V 2000 G36F

    1135 908 1000 1341 x W2A 18V 2000 G65 (3)

    1250 1000 1102 1478 x x x x A2A x 18V 2000 G26F

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    Gendrive enginesPrime Power (3B)

    50 Hz – 1500 rpm

    580 kWm - 1102 kWm

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 18V 2000 G65 for fuel

    consumption optimized / without

    power reduction available up to

    35°C / 400 m

    reference to emission level in price list

    24 22 251981

    22 25

       P  r   i  m  e   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    21/55

    40 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 41

    kVA kWe kWm bhp

     

    1365 1092 1205 1616 x x x W2A 12V 4000 G23R

    1600 1280 1420 1904 x x x W2A 12V 4000 G23

    1800 1440 1575 2112 x x x W2A 12V 4000 G63 (4)

    2100 1680 1798 2411 x x x W2A 16V 4000 G23

    2250 1800 1965 2635 x x x W2A 16V 4000 G63

    2500 2000 2200 2950 x x x W2A 20V 4000 G23

    2800 2240 2420 3245 x x x W2A 20V 4000 G63 (3)

    3000 2400 2590 3473 x x x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    Gendrive enginesPrime Power (3B)

    50 Hz – 1500 rpm

    1205 kWm - 2590 kWm

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is appliedfor calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 20V 4000 G63 without power

    reduction available up to 35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63Lwithout power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

    22 25

       P  r   i  m  e   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    22/55

    42 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 43

    kVA kWe kWm bhp

     

    1600 1280 1420 1904 x x x W2A 12V 4000 G23

    1800 1440 1575 2112 x x x W2A 12V 4000 G63 (4)

    2100 1680 1798 2411 x x x W2A 16V 4000 G23

    2250 1800 1965 2635 x x x W2A 16V 4000 G63

    2500 2000 2200 2950 x x x W2A 20V 4000 G23

    2800 2240 2420 3245 x x x W2A 20V 4000 G63 (3)

    3000 2400 2590 3473 x x x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    1420 kWm - 2590 kWmGendrive enginesGrid Stability Power (3G)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 20V 4000 G63 without power

    reduction available up to 35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63L

    without power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25

       G  r   i   d   S   t  a   b   i   l   i   t  y   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    23/55

    44 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 45

    kVA kWe kWm bhp

     

    275 220 249 334 x x x A2A x 6R 1600 G40F

    300 240 274 367 x x x A2A x 6R 1600 G50F

    365 292 325 436 x x x A2A x 8V 1600 G40F

    400 320 358 480 x x x A2A x 8V 1600 G50F

    450 360 407 546 x x x A2A x 10V 1600 G40F

    500 400 448 601 x x x A2A x 10V 1600 G50F

    590 472 524 703 x x A2A x 12V 1600 G40F

    650 520 576 772 x x A2A x 12V 1600 G50F

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    Gendrive enginesPrime Power Limited (3C)

    50 Hz – 1500 rpm

    249 kWm - 576 kWm

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is appliedfor calculation and serves as guideline only.

    reference to emission level in price list

    (2) Explanation see page 82

    24 22 251981

    22 25

       P  r   i  m  e   P  o  w  e  r   L   i  m   i   t  e   d  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    24/55

    46 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 47

    kVA kWe kWm bhp

     

    575 460 515 691 x A2A x 12V 2000 G65

    575 460 515 691 x W2A 12V 2000 G65

    740 592 655 878 x A2A x 16V 2000 G65

    740 592 655 878 x W2A 16V 2000 G65

    750 600 665 892 x A2A x 12V 2000 B26F

    800 640 709 951 x A2A x 16V 2000 B26F

    810 648 720 966 x A2A x 18V 2000 G65 (3)

    810 648 720 966 x W2A 18V 2000 G65 (3)

    1000 800 887 1189 x A2A x 18V 2000 B26F

    1480 1184 1310 1757 x W2A 12V 4000 G63 (4)

    1875 1500 1635 2193 x W2A 16V 4000 G63

    2275 1820 2000 2682 x W2A 20V 4000 G63 (3)

    2500 2000 2200 2950 x W2A 20V 4000 G63L (4)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d

       (   T   A  -   L  u   f   t   )   (   2   )

       E   U   N  o  n  r  o  a   d

       S   t  a  g  e   I   I   I   A

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    50 Hz – 1500 rpm

    515 kWm - 2200 kWm

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    22 25

    Gendrive enginesContinuous Power (3A)

       C  o  n   t   i  n  u  o  u  s   P  o  w  e  r  -   5   0   H  z

    241981

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I

       I  n   d   i  a   C   P   C   B   (   A   R   A   I   )   S   t  a  g  e   I   I

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Series 18V 2000 G65 / 20V 4000 G63

    without power reduction available up to

    35°C / 400 m

    (4) Series 12V 4000 G63 / 20V 4000 G63L

    without power reduction available up to

    30°C / 400 m

    reference to emission level in price list

    24 22 251981

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    25/55

    48 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 49

    60 Hz – 1800 rpm

    312 kWm - 1371 kWmGendrive enginesStandby Power (3D)

    kWe kVA kWm bhp

     

    275 344 312 418 x x A2A x 6R 1600 G70S

    300 375 343 460 x x A2A x 6R 1600 G80S

    365 456 408 547 x x A2A x 8V 1600 G70S

    400 500 448 601 x x A2A x 8V 1600 G80S

    450 563 511 685 x x A2A x 10V 1600 G70S

    500 625 561 752 x x A2A x 10V 1600 G80S

    550 688 613 822 x x A2A x 12V 1600 G70S

    600 750 668 896 x x A2A x 12V 1600 G80S

    710 888 780 1046 x x A2A x 12V 2000 G45

    710 888 780 1046 x x W2A 12V 2000 G45

    800 1000 890 1194 x x A2A x 12V 2000 G85

    800 1000 890 1194 x x W2A 12V 2000 G85

    925 1156 1010 1354 x x A2A x 16V 2000 G45

    925 1156 1010 1354 x x W2A 16V 2000 G45

    1000 1250 1115 1495 x x A2A x 16V 2000 G851000 1250 1115 1495 x x W2A 16V 2000 G85

    1200 1500 1310 1757 x x A2A x 18V 2000 G85

    1200 1500 1310 1757 x x W2A 18V 2000 G85

    1250 1563 1371 1839 x x x A2A x 18V 2000 G76S

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    20 719 3

    reference to emission level in price list

       S   t  a  n   d   b  y   P  o  w  e  r  -   6   0   H  z

    20 719 3

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    26/55

    50 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 51

    60 Hz – 1800 rpm

    1736 kWm - 3490 kWmGendrive enginesStandby Power (3D)

    kWe kVA kWm bhp

     

    1600 2000 1736 2328 x x x W2A 12V 4000 G43

    1750 2188 1910 2561 x x x W2A 12V 4000 G83

    2100 2625 2280 3058 x x x W2A 16V 4000 G43

    2300 2875 2500 3353 x x x W2A 16V 4000 G83

    2550 3188 2740 3674 x x x W2A 16V 4000 G83L

    2550 3188 2740 3674 x x x W2A 20V 4000 G43

    2800 3500 3010 4036 x x x W2A 20V 4000 G83

    3250 4063 3490 4680 x x x W2A 20V 4000 G83L

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is appliedfor calculation and serves as guideline only.

    reference to emission level in price list

       S   t  a  n   d   b  y   P  o  w  e  r  -   6   0   H  z

    20 719 3

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    27/55

    52 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 53

    kWe kVA kWm bhp

     

    1400 1750 1520 2038 x x x W2A 12V 4000 G43

    1600 2000 1736 2328 x x x W2A 12V 4000 G83

    1850 2313 2020 2709 x x x W2A 16V 4000 G43

    2100 2625 2280 3058 x x x W2A 16V 4000 G83

    2300 2875 2490 3339 x x x W2A 20V 4000 G43

    2550 3188 2740 3674 x x x W2A 20V 4000 G83

    2800 3500 3010 4036 x x x W2A 20V 4000 G83L

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    60 Hz – 1800 rpm

    1520 kWm - 3010 kWmGendrive enginesData CenterContinuous Power (3F)

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    reference to emission level in price list

       D  a   t  a   C  e  n   t  e  r   C  o  n   t   i  n  u  o  u  s   P  o  w  e  r  -   6   0   H

      z20 719 3

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    28/55

    54 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 55

    kWe kVA kWm bhp

     

    1600 2000 1736 2328 x x x W2A 12V 4000 G43

    1750 2188 1910 2561 x x x W2A 12V 4000 G83

    2100 2625 2280 3058 x x x W2A 16V 4000 G43

    2300 2875 2500 3353 x x x W2A 16V 4000 G83

    2550 3188 2740 3674 x x x W2A 16V 4000 G83L

    2550 3188 2740 3674 x x x W2A 20V 4000 G43

    2800 3500 3010 4036 x x x W2A 20V 4000 G83

    3250 4063 3490 4680 x x x W2A 20V 4000 G83L

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    60 Hz – 1800 rpm

    1736 kWm - 3490 kWmGendrive enginesMission Critical Power (3H)

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is appliedfor calculation and serves as guideline only.

    reference to emission level in price list

       M   i  s  s   i  o  n   C  r   i   t   i  c  a   l   P  o  w  e  r  -   6   0   H  z

    20 719 3

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    29/55

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    30/55

    58 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 59

    kWe kVA kWm bhp

     

    250 313 284 381 x x A2A x 6R 1600 G10S

    275 344 312 418 x x A2A x 6R 1600 G20S

    330 413 371 498 x x A2A x 8V 1600 G10S

    365 456 408 547 x x A2A x 8V 1600 G20S

    415 519 465 624 x A2A x 10V 1600 G10S

    450 563 511 685 x x A2A x 10V 1600 G20S

    500 625 561 752 x x A2A x 12V 1600 G10S

    550 688 608 815 x x A2A x 12V 1600 G20S

    640 800 710 952 x x A2A x 12V 2000 G45

    640 800 710 952 x x W2A 12V 2000 G45

    735 919 810 1086 x x A2A x 12V 2000 G85 (2)

    735 919 810 1086 x x W2A 12V 2000 G85 (2)

    830 1038 915 1227 x x A2A x 16V 2000 G45

    830 1038 915 1227 x x W2A 16V 2000 G45

    925 1156 1010 1354 x x A2A x 16V 2000 G85925 1156 1010 1354 x x W2A 16V 2000 G85

    1100 1375 1191 1597 x x A2A x 18V 2000 G85

    1100 1375 1191 1597 x x W2A 18V 2000 G85

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    60 Hz – 1800 rpm

    284 kWm - 1191 kWm

    20 719 3

    Gendrive enginesPrime Power (3B)

       P  r   i  m  e   P  o  w  e  r  -   6   0   H  z

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Series 12V 2000 G85 without power

    reduction available up to 30°C / 400 m

    reference to emission level in price list

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    31/55

    60 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 61

    kWe kVA kWm bhp

     

    1000 1250 1105 1482 x W2A 12V 4000 G73 (2)

    1260 1575 1390 1864 x W2A 16V 4000 G73 (2)

    1400 1750 1520 2038 x x x W2A 12V 4000 G43

    1600 2000 1736 2328 x x x W2A 12V 4000 G83

    1850 2313 2020 2709 x x x W2A 16V 4000 G43

    2100 2625 2280 3058 x x x W2A 16V 4000 G83

    2300 2875 2490 3339 x x x W2A 20V 4000 G43

    2550 3188 2740 3674 x x x W2A 20V 4000 G83

    2800 3500 3010 4036 x x x W2A 20V 4000 G83L

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    60 Hz – 1800 rpm

    1105 kWm - 3010 kWm

    20 719 3

    Gendrive enginesPrime Power (3B)

       P  r   i  m  e   P  o  w  e  r  -   6   0   H  z

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    reference to emission level in price list

    (2) 4000 G73 with 1200 rpm

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    32/55

    62 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 63

    kWe kVA kWm bhp

     

    1400 1750 1520 2038 x x x W2A 12V 4000 G43

    1600 2000 1736 2328 x x x W2A 12V 4000 G83

    1850 2313 2020 2709 x x x W2A 16V 4000 G43

    2100 2625 2280 3058 x x x W2A 16V 4000 G83

    2300 2875 2490 3339 x x x W2A 20V 4000 G43

    2550 3188 2740 3674 x x x W2A 20V 4000 G83

    2800 3500 3010 4036 x x x W2A 20V 4000 G83L

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    60 Hz – 1800 rpm

    1520 kWm - 3010 kWm

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    reference to emission level in price list

    20 719 3

    Gendrive enginesGrid Stability Power (3G)

       G  r   i   d   S   t  a   b   i   l   i   t  y   P  o  w  e  r  -   6   0   H  z

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    33/55

    64 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 65

    kWe kVA kWm bhp

     

    525 656 580 778 x A2A x 12V 2000 G45 (2)

    525 656 580 778 x W2A 12V 2000 G45 (2)

    550 688 620 831 x A2A x 12V 2000 G85 (2)

    550 688 620 831 x W2A 12V 2000 G85 (2)

    615 769 685 919 x A2A x 16V 2000 G45 (2)

    615 769 685 919 x W2A 16V 2000 G45 (2)

    715 894 790 1059 x A2A x 16V 2000 G85 (2)

    715 894 790 1059 x W2A x 16V 2000 G85 (2)

    790 988 870 1167 x W2A 12V 4000 G73 (3)

    815 1019 900 1207 x A2A x 18V 2000 G85 (2)

    815 1019 900 1207 x W2A 18V 2000 G85 (2)

    1040 1300 1140 1529 x W2A 16V 4000 G73 (3)

    1100 1375 1190 1596 x W2A 12V 4000 G43

    1300 1625 1420 1904 x W2A 12V 4000 G83

    1500 1875 1680 2253 x W2A 16V 4000 G431775 2219 1950 2615 x W2A 16V 4000 G83

    2050 2563 2230 2990 x W2A 20V 4000 G83

    2300 2875 2490 3339 x W2A 20V 4000 G83L

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Rating Emissions Standard Cooling Engine

    Generator Set

    output (1)

    60 Hz – 1800 rpm

    580 kWm - 2490 kWm

    20 719 3

    Gendrive enginesContinuous Power (3A)

       C  o  n   t   i  n  u  o  u  s   P  o  w  e  r  -   6   0   H  z

    20 719 3Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Available on request

    (3) 4000 G73 with 1200 rpm

    Series 1600: Heavy duty base load ratings

    (3A) on request

    reference to emission level in price list

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    34/55

    66 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 67

    kVA kWe kWe kVA kWm bhp kWm bhp

    50 Hz 50 Hz 60 Hz 60 Hz 50 Hz 50 Hz 60 Hz 60 Hz

     

    1800 1440 1600 2000 1575 2112 1736 2328 x W2A 12V 4000 G23/G43(3)

    2000 1600 1750 2188 1750 2347 1910 2561 x W2A 12V 4000 G63/G83(3)

    2250 1800 2100 2625 1965 2635 2280 3058 x W2A 16V 4000 G23/G43(3)

    2500 2000 2300 2875 2185 2930 2500 3353 x W2A 16V 4000 G63/G83(3)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d   (   T   A  -   L  u   f   t

       )   (   2   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Generator Set Rating Emissions Standard Cooling Engine

    output (1)

    50/60 Hz – 1500/1800 rpm

    1575 kWm – 2500 kWmGendrive engines (switchable)Standby Power (3D)

    20 719 350 Hz 60 Hz 50 Hz 60 Hz

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical

    generator efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Available on request

    reference to emission level in price list

    19 31 20 7 24

    241

       S   t  a  n   d   b  y   P  o  w  e  r  -

       5   0   /   6   0   H  z   (  s  w   i   t  c   h  a   b   l  e   )

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    35/55

    68 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 69

    kVA kWe kWe kVA kWm bhp kWm bhp

    50 Hz 50 Hz 60 Hz 60 Hz 50 Hz 50 Hz 60 Hz 60 Hz

     

    275 220 250 313 249 334 284 381 x A2A x 6R 1600 B30S

    300 240 275 344 274 367 312 418 x A2A x 6R 1600 B40S

    365 292 330 413 325 436 371 498 x A2A x 8V 1600 B30S

    400 320 365 456 358 480 408 547 x A2A x 8V 1600 B40S

    450 360 415 519 448 601 511 685 x A2A x 10V 1600 B40S

    500 400 450 563 524 703 561 752 x A2A x 12V 1600 B30S

    590 472 500 625 576 772 608 815 x A2A x 12V 1600 B40S

    800 640 650 813 709 951 716 960 x (3) x (4) x (4) A2A x 12V 2000 B76

    1000 800 910 1138 890 1194 998 1338 x (3) x (4) x (4) A2A x 16V 2000 B76

    1250 1000 1000 1250 1102 1478 1097 1471 x (3) x (4) x (4) A2A x 18V 2000 B76

    1600 1280 1400 1750 1420 1904 1520 2038 x  x  W2A 12V 4000 G23/G43

    1600 1280 1400 1750 1420 1904 1520 2038 x(3), (5) x(4), (5) W2A 12V 4000 G23/G43

    1800 1440 1600 2000 1575 2112 1736 2328 x(5) x(4), (5) W2A 12V 4000 G63/G83

    2100 1680 1850 2313 1798 2411 2020 2709 x W2A 16V 4000 G23/G43

    2100 1680 1850 2313 1798 2411 2020 2709 x(3), (5) x(4), (5) W2A 16V 4000 G23/G43

    2250 1800 2100 2625 1965 2635 2280 3058 x W2A 16V 4000 G63/G83

    2250 1800 2100 2625 1965 2635 2280 3058 x(3), (5) x(4), (5) W2A 16V 4000 G63/G83

    Cooling Variants 

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical generator

    efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan drive power and generator efficiency is applied

    for calculation and serves as guideline only.

    (2) Explanation see page 82

    (3) Only 60 Hz

    (4) Only 50 Hz

    (5) Available on request

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d   (   T   A  -   L  u   f   t

       )   (   2   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Generator Set Rating Emissions Standard Cooling Engine

    output (1)

    Gendrive engines (switchable)Prime Power (3B)

    50 / 60 Hz – 1500/1800 rpm

    249 kWm – 2280 kWm

    50 Hz 60 Hz 50 Hz 60 Hz 1 20 7 2419 3

    reference to emission level in price list

    19 31 20 7 24

       P  r   i  m  e   P  o  w  e  r  -   5   0   /   6   0   H  z   (  s

      w   i   t  c   h  a   b   l  e   )

  • 8/17/2019 3190171 MTU Gendrive SalesProgram

    36/55

    70 I Gendrive I Sales Program 2015 Sales Program 2015  I Gendrive I 71

    kVA kWe kWe kVA kWm bhp kWm bhp

    50 Hz 50 Hz 60 Hz 60 Hz 50 Hz 50 Hz 60 Hz 60 Hz

     

    1485 1188 1300 1625 1310 1757 1420 1904 x W2A 12V 4000 G63/G83(3)

    1865 1492 1775 2219 1635 2193 1950 2615 x W2A 16V 4000 G63/G83(3)

       F  u  e   l  c  o  n  s  u  m  p   t   i  o  n  o  p   t   i  m   i  z  e   d

       E  x   h  a  u  s   t  e  m   i  s  s   i  o  n  o  p   t   i  m   i  z  e   d   (   T   A  -   L  u   f   t

       )   (   2   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   2

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

      c  o  m  p   l   i  a  n   t

       U   S   E   P   A   N  o  n  r  o  a   d   T   i  e  r   3

       S   t  a   t   i  o  n  a  r  y   (   4   0   C   F   R   6   0   )

       N   E   A   S   i  n  g  a  p  o  r  e   f  o  r   O   R   D   E ,

      c  o  m  p   l   i  a  n   t   E   P   A   T   i  e  r   2

       C  o  o   l   i  n  g  v  a  r   i  a  n   t

       C  o  o   l   i  n  g  p  a  c   k  a  g  e   i  n  c   l  u   d  e   d

       E  n  g   i  n  e  m  o   d  e   l

    Typical Generator Set Rating Emissions Standard Cooling Engine

    output (1)

    50 /60 Hz – 1500/1800 rpm

    1310 kWm – 1950 kWmGendrive engines (switchable)Continuous Power (3A)

    50 Hz 60 Hz 50 Hz 60 Hz

    Cooling Variants

    A2A: air-to-air charge air cooling (TD)

    W2A: water-to-air charge air cooling (TB)

    (1) The quoted typical kVA / kWe ratings are based on typical

    generator efficiencies.

    The kVA figures are calculated with a 0.8 power factor.

    Typical deductions for fan