Upload
roobow
View
19
Download
1
Embed Size (px)
Citation preview
HUAWEI TECHNOLOGIES CO., LTD.
Power1000 V200R003 (MBBS Scenario)
Quick Installation Guide
Document Version: 01
Part Number: 31505046Issued on: 2011-02-28
1
Safety PrecautionsTo ensure safety of humans and the equipment, pay attention to the safety symbols on the equipment and all the safety instructions in this document. The "NOTE", "CAUTION", and "WARNING" marks in other documents do not represent all the
safety instructions. They are only supplements to the safety instructions.When operating Huawei equipment, in addition to following the general precautions in this document, follow the specific safety instructions given by Huawei. Huawei will not be liable for the consequences that are caused by the violation of the
safety operation regulations and design, production, and usage standards.
Local Safety RegulationsWhen operating Huawei equipment, you must follow the local laws and regulations. The safety instructions in this document
are only supplements to the local laws and regulations.
Personnel RequirementsOnly trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment.
Symbols
■
Alerts you to a potentially hazardous situation that could, if not avoided, result in equipment damage, data loss, performance deterioration, or unanticipated results.
Provides additional information to emphasize or supplement important points in the main text.
■
■
■
Precautions
Human SafetyTo prevent electric shock, get tools insulated and wear electrostatic discharge (ESD) gloves when connecting cables.To prevent dust inhalation or contact with the eyes, take adequate preventive measures when drilling holes.
■
Power1000 V200R003 (Power1000 for short) is applicable in various scenarios. This presentation describes the installation procedures in the
following four scenarios: 1. D.G.+DCB; 2. D.G.+D.G.+DCB; 3. D.G.+Mains+DCB; 4. D.G.+D.G.+Mains+DCB. In this document, D.G. stands for
diesel generator, and DCB stands for deep cycle battery.
Installation Tools
Flat-head screwdriver Phillips screwdriver Adjustable wrench Claw hammer Diagonal pliers COAX crimping tool
Wire stripper Hydraulic pliers Fuse extracting unit PVC insulation tape Multimeter Electrician's knife
Hammer drill Heat gun Socket wrench Marker Heat shrink tubing ESD gloves
Cable tie Clamp meter
Copyright Huawei Technologies Co.,Ltd.2011.All rights reserved.
2
Network Diagram
Scenario 1: D.G.+DCB
Installation Procedure
(a1) AC power cable between the
D.G. and the ATS
(a3) AC power cable between
the ATS and the power system
(a4) (Optional) AC power cable
between the AC-powered load
and the ATS
(d1) DC power cable
between the DC-powered
load and the power system
(d2) DC power cable between the
power system and the DCB
(d3) Signal cable for monitoring
the voltage of the –48 V DCB
(d4) DC power cable between
the HPMU and the DCB
(s1) (Optional) Signal cable
between the fuel level sensor
and the SAU
(s2) Signal cable for starting the
D.G.
(s3) Signal cable for monitoring
the voltage of the 12 V storage
battery in the D.G.
(s4) Signal cable for detecting
the charge capacity and
discharge capacity of the DCB
(s5) Signal cable between
the ambient temperature
sensor and the SAU
(s6) Communications cable
between the HPMU and the SAU
(s7) (Optional) Communications
cable between the HPMU (with
the OMU) and the transport
network
(s8) (Optional) Communications
cable between the NetEco and
the transport network
(s10) Signal cable for the
ATS to report its output
voltage to the SAU
(s13) Communications cable
between the intelligent electric
meter and the HPMU
AC power cable (a)
DC power cable (d)
Signal cable (s)
Fuel tank D.G.
NetEco
GPRS/IPnetwork
HPMU
(with the OMU)
SAUAmbienttemperature sensor
Power systemATS
DCB
AC-powered load DC-powered load
D.G. and Battery Hybrid Power System
a1
a4
a3
d1
d2
d3
d4
s1
s2
s3
s4
s5
s6
s7
s8
s9 s10
Current sensor
1. Install the D.G. and Battery Hybrid Power System.
2. Disconnect the power supply of the original storage battery.
3. Install cables.
4. Power on and commission the Power1000.
Intelligent electric meter
s13
3
Concrete pad
1. Installing the D.G. and Battery Hybrid Power System
Method 1: Using a crane
Method 1: Route four steel wire ropes through the four lifting eyes on the top of the cabinet respectively and secure them atthe base of the cabinet, as shown in the following figure. Then hoist the cabinet to the installation place using a crane.Method 2: Move the cabinet to the installation place using a pallet track.
Install expansion bolts in the mounting holes to secure the cabinet.
Steel base
Installing the MBBSa
When hoisting the cabinet, ensure that no friction occurs between the steel wire rope and the cabinet. If the cabinet is scratched during transportation, paint or apply glue to the scratched areas.
Method 2: Using a pallet truck
1
2
3
4
1
2
Four M12x60
expansion bolts
55–60 mm
(2.17–2.36 in.)
Ф16
900
1 2 3 4
Prepare the mini-shelter battery bank system(MBBS) concrete pad.
ATS
concrete
pad
Single-compartment MBBS
d ≤ 5000 mm (196.85 in.)
11
00
mm
(4
3.3
1 in
.)
1100 mm (43.31 in.)
Scenario 1: Single-Compartment MBBS
Concrete pad
4
Concrete pad
Method 1: Using a crane
Method 1: Route four steel wire ropes through the four lifting eyes on the top of the cabinet respectively and secure them atthe base of the cabinet, as shown in the following figure. Then hoist the cabinet to the installation place using a crane.Method 2: Move the cabinet to the installation place using a pallet track.
Install expansion bolts in the mounting holes to secure the cabinet.
Steel base
When hoisting the cabinet, ensure that no friction occurs between the steel wire rope and the cabinet. If the cabinet is scratched during transportation, paint or apply glue to the scratched areas.
Method 2: Using a pallet truck
1
2
3
4
1
2
Four M12x60
expansion bolts
Ф16
90°
1 2 3 4
Prepare the MBBS concrete pad.
ATS concrete
pad
Dual-compartment
MBBS
d ≤ 5000 mm (196.85 in.)
11
00
mm
(4
3.3
1 in
.)
2100 mm (82.68 in.)
Scenario 2: Dual-Compartment MBBS
55–60 mm
(2.17–2.36 in.)
5
Installing the HPMU and SAUb
Scenario 1: Single-Compartment MBBS
Install the HPMU and SAU in the correct subracks.
Install captive nuts in the subracks used for housing the HPMU and SAU.
8pcs
8pcs
1
2
Complete
Scenario 2: Dual-Compartment MBBS
1
2
Install the HPMU and SAU in the correct subracks.
Install captive nuts in the subracks used for housing the HPMU and SAU.
Complete
6
Site ground bar
Installing the DCBc
Scenario 1: Single-Compartment MBBSSwitch the circuit breaker of the battery cabinet to the OFF position, and then ground the MBBS.
1. At least two persons are required to carry one DCB.2. DCBs must be placed in strict accordance with the figure under step 2. Otherwise, you will fail to connect cables to the DCBs or the DCBs will experience short circuits.
3. When connecting cables to DCBs, wear ESD gloves, use insulated tools (such as a wrench with its handle wrapped with PVC insulation tape), and tighten the nuts on all DCBs.
4. Before connecting a cable to a DCB, remove the protective lid from the DCB, and then resume it after connecting the cable.
OFF
Install DCBs. Note that a DCB cannot be connected reversely.
Connect cables between DCBs and between the DCB string and the ground bar of the MBBS.
Install the current sensor.
Ground bolt of the MBBS
1
2
3
To the ground bolt of the MBBS To the ground bar of the MBBS
To the ground bar of the MBBS To the site ground bar
Ground bar of the MBBS
2
3
OFF
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
7
c Scenario 2: Dual-Compartment MBBS
OFF
Install DCBs. Note that a DCB cannot be connected reversely.
Connect cables between DCBs and between the DCB string and the ground bar of the MBBS.
Install the current sensor.
Ground bolt of the MBBS
Switch the circuit breaker of the battery cabinet to the OFF position, and then ground the MBBS.
Site ground bar
Ground bar of the MBBS
To the ground bolt of compartment 1 To the ground bar of the MBBS
To the ground bolt of compartment 2 To the ground bar of the MBBS
To the ground bar of the MBBS To the site ground bar
1
2
3
4Compartment 1
Compartment 2
2
3
4
OFF
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
+ - + - + -
+-+- +-
8
2. Disconnecting the Power Supply of the Original Storage Battery
Switching the Power Supplier to D.G.a
1. When removing and installing storage batteries, ensure that the D.G. supplies power properly.2. When disconnecting cables from storage batteries, wear ESD gloves, use insulated tools (such as a wrench with
its handle wrapped with PVC insulation tape), and tighten the nuts on all DCBs after disconnecting the cables.
Start the D.G. by referring to the user manual of the D.G.
Configure the ATS to work in manual mode by referring to the ATS User Manual.
Switch the power supplier to the D.G. on the ATS by referring to the ATS User Manual.
Disconnecting the Power Supply of the Original Storage Batteryb
Switch the circuit breaker of the original battery cabinet or battery rack to the OFF position.
Disconnect the charging circuit between the power system and the storage battery by referring to the Power System User Manual.
If possible, reuse any cables to storage batteries, including the battery temperature sensor.
Scenario 1: The original battery cabinet or cabinet rack has circuit breakers.
Disconnect the cables between original storage batteries from top to bottom.
Disconnect the cable between the original battery string and the power system.
Scenario 2: The original battery cabinet or cabinet rack has no circuit breakers.
Disconnect the cable between any DCBs.
Disconnect the charging circuit between the power system and the storage battery by referring to the Power System User Manual.
Disconnect the cables between original storage batteries from top to bottom.
Disconnect the cable between the original battery string and the power system.
3. Installing Cables
Prepare terminals as required before installing cables.
Cord end terminal
Ring terminal
Heat shrink tubing
COAX crimping tool
Hydraulic pliers
Flipping the Switch of the SAU to the OFF Positiona
OFF
9
Cables Between the MBBS, the DCB, and the Power Systemb
No. Cable The Other End Cable The Other End
1 Ground cable of the HPMU Ground bolt of the HPMU Ground bar of the MBBS
2 Ground cable of the SAU Ground bolt of the SAU Ground bar of the MBBS
3 Power cable between the power system and the DCB
Battery input terminals of the
power system
Battery cable bar in the MBBS
4 Signal cable for monitoring the voltage of the –48 V DCB
–48V1 ports of PORT1 of the
SAU
Ground and –48V ports of the power distribution bar of
the MBBS
5 Signal cable for detecting the charge capacity and discharge capacity of the
DCB
Current sensor M1, G1, C1+, and C1- ports of PORT4 of the SAU
6 Signal cable between the ambient temperature sensor and the SAU
Battery rack in the MBBS Temp port of PORT4 of the SAU
7 (Optional) Signal cable between the battery temperature sensor and the
HPMU
Battery rack in the MBBS BAT_T port of the HPMU
8 DC power cable between the HPMU and
the DCB
RTN(+) –48V port of the
HPMU
Ground and –48V ports of the power distribution bar of
the MBBS
9-1 Signal cable for transmitting alarms for
fan failures
DI1 port of the HPMU COM_IN port of the fan connection box on the single-
compartment MBBS door or on compartment 1 of the
dual-compartment MBBS
9-2 Signal cable for transmitting alarms for
fan failures
DI3 port of the HPMU COM_IN port of the fan connection box on
compartment 2 of the dual-compartment MBBS
10 Signal cable for detecting the door status DI4 port of the HPMU Door status sensor
Ground bar of
the MBBS
Ground bolt of the HPMU
Ground bolt of the SAU
Power systemTransfer busbar in
the MBBS
Scenario 1: Single-Compartment MBBS
Battery temperature
sensor
Door status sensor
Fan connection box on the MBBS door
Current sensor
+ -
-
-
+
–48V1
+ -
M1 G1 C1+ C1-
DI4
COM_IN
+ -+ -
+ -+ -
GND
–48V
DI1BAT_T
TEMP
+ -
1
2
3 3
4
4
5
6
7
8
9-1
10
Ambient temperature
sensor
M1
G1
C1+
C1-
10
Scenario 2: Dual-Compartment MBBS
Removing the Original Batteries and Battery Cabinetc
Remove baffle plates from top to bottom and take out original storage batteries.
Remove the battery cabinet.
At least two persons are required to carry one storage battery.
2
33
+ -
-
-
+
4
–48V1
+ -
5
Temp
6
7
1
8
COM_IN COM_IN
+ -
9-1
10
9-2
GND
–48V
DI4DI1BAT_T DI3
M1 G1 C1+ C1-
+ -+
+ - + - + -
+ -
Ground bar of
the MBBS
Ground bolt of the
HPMU
Ground bolt of the SAU
Power system
Transfer busbar in
the MBBS
Battery temperature sensor
Door status sensor
COM_IN port on
compartment 1 of
the dual-
compartment MBBS
Ambient
temperature sensor
COM_IN port on
compartment 2 of
the dual-
compartment MBBS
Current sensor
M1
G1
C1+
C1-
11
Enabling the DCB to Supply Powerd
Switch the circuit breaker of the original battery cabinet or battery rack to the OFF position.
Connect the charging circuit between the power system and the DCB by referring to the Power System User Manual.
Stop the D.G. by referring to the user manual of the D.G.
Disconnect the connections between the ATS and both of the D.G. and power system by referring to the ATS User Manual.
Cables Between the MBBS, the D.G., and the ATSe
ATS Output
U
V
W
N1
1
ATS
D.G.
Fuel tank
2
12V1 NC1 COM1
+ -
Fuel1
3
4
4
2 3+ -
1
Communications Cable Between the Intelligent Electric Meter and the HPMUf
Pins to the Intelligent
Electric Meter
Cable Appearance Pins to the COM4 port of
the HPMU
7 R+
T+
8 R-
T-
1. For the D.G. that is started when the dry contact is closed, connect the signal
cable for starting the D.G. to the NC1 and COM1 ports of the SAU. For the D.G.
that is started when the dry contact is open, connect the signal cable for starting
the D.G. to the NO1 and COM1 ports of the SAU.
2. Before connecting the signal cable between the fuel level sensor and the SAU, remove the 2-pin terminal (green part in the following figure) from the cable.
No. Cable The Other End Cable The Other End
1 Signal cable for the ATS to report its
output voltage to the SAU
ATS Output (U port) of the SAU L1 port of the ATS
ATS Output (V port) of the SAU L2 port of the ATS
ATS Output (W port) of the SAU L3 port of the ATS
ATS Output (N1 port) of the SAU N port of the ATS
2 Signal cable for monitoring the voltage of the 12 V storage battery in the D.G.
12V1 port of PORT1 of the SAU Storage battery in the D.G.
3 Signal cable for starting the D.G. NC1 and COM1 ports of PORT2 of the
SAU
Dry contacts for starting the D.G.
4 (Optional) Signal cable between the fuel level sensor and the SAU
Fuel1 port of PORT4 of the SAU Fuel level sensor
If there is only one D.G., connect the fuel level sensor to the Fuel1 port.
12
Installing Communications Cablesg
Connect the communications cable between the northbound serial port of the SAU and the HPMU.
Communications cable between the northbound serial port of the SAU and the HPMU
To the N port (RS485) of the SAU To the COM3 port of the HPMU
N
COM3
Power supply direction
The intelligent electric meter is installed in the same cabinet as the ATS or alternating current distribution box (ACDB). The specific position depends on the actual installation scenario.
N
W
V
U
ACDBATS
220 V
NL
COM4
T+ T- R+ R-
Power supply direction
SIM
Module card
13
IP network
(Optional) Communications cable
between the OMU and the Ethernet To the ETH port of the OMU To the GPRS or IP network
ETH
Scenario 1: Communication over the Ethernet
(Optional) GSM antenna To the RF port of the OMU
Scenario 2: Communication over the GPRS
1 Install the subscriber identity module (SIM) card.
2 Install the Global System for Mobile Communications (GSM) antenna.
GSM antenna
RF
Out-of-Band Communication (over the OMU)
GSM antennainstalled
inside the cabinet base
Installing the SIM card
Removing the module card
14
In-Band Communication (over the HPMU)
Prepare a cable as shown in the following f igure.
View A
T+
1 8
Pin Number of
the RI45
Connector to the
MON Port of the
BTS3900E in the
GBBS12.0
Pin Number of
the Connector to
the COM_OUT
Port of the HPMU
1 T+
2 T-
4 R+
5 R-
T-R+R-
Scenario 1: UMTS13.0 and GBSS12.0 (excluding the BTS3900E)
1
Install the communications cable.2
Scenario 2: GBBS12.0 (pole-mounted BTS3900E)
(Optional) Communications cable between
the UTMS13.0 and the HPMU To the MON1 port of the BBU To the COM_OUT port of the
HPMU
COM_OUT
MON1
BBU
HPMU
T+ T- R+ R-
Prepare a cable as shown in the following f igure.
Core Color Pin Number of the DB15 Connector to the
MON Port of the BTS3900E in the
GBBS12.0
Pin Number of the Connector to the
COM_OUT Port of the HPMU
Red 11 R-
Blue 12 R+
Red 13 T-
Orange 14 T+
1
COM_OUT
15
Checking Cable Connectionsh
No. Check Item
1 All cables are connected correctly.
2 Cables to the MBBS are connected properly.
3 The battery circuit breaker on the MBBS is switched to the ON position, the D.G. output circuit breaker is switched to the OFF
position, and the D.G. works in manual mode.
4 No short circuit occurs between the –48 V power cable and any of the ground bar, positive bus bar, three-phase live wire, neutral
wire, and ground cable. No short circuit occurs between the three-phase live wire, the neutral wire, and the ground cable.
5 Cable holes are blocked by fireproof mud.
Fireproof mud
4. Powering On and Commissioning the Power1000Configure the D.G. and ATS to work in manual mode, and stop the D.G. and the AC output of the ATS. For details, see the ATS User Manual.
Flip the power switches of the SAU and HPMU both to the ON position.
ON
ON
Install the communications cable.2
COM_OUT
MON port of the BTS3900E in the GBBS12.0 on the BBU
HPMU
T+ T- R+ R-
16
A. Out-of-Band Communication (over the OMU)
1
Scenario 1: Communication over the GPRS
1. The following table describes the buttons on the HPMU panel.
Button Function
or Allows you to view menu items and set the value of a menu item.
Cancel Returns to the previous menu without saving the settings of the current menu item.
Enter Enters the main menu from the standby screen, enters a submenu from the main menu, or saves the
settings of a submenu item.
Verify that the LEDs on the PMB01 panel, OMU01 panel, and HCU01 panel are in a normal state.
2. Information on the liquid crystal display (LCD) described in pages 17–22 is for reference only.
Set parameters on the HPMU.
Set parameters on the HPMU.
The initial password is 0.2
Parameter Settings on the HPMU
Parameter Value Parameter Value Parameter Value
Application Set Battery Set NetEcoNum
Number of the SIM card in the short message service (SMS) modem
on the NetEco side
System Type DG&DCB Batt 1 Cap
Set based on actual requirements
User1 to User5 Phone
Num
Set based on actual requirements
System Set Batt 2 Cap
Set based on actual requirements
SMS Test Num
Set based on actual requirements
Zone Set based on actual requirements
Install Date
Set based on actual requirements
APN Name
Obtained from the survey table
APN Number
Obtained from the survey tableDate Set based on
actual requirements
Time Set based on actual requirements
Net Para Set User Name
User name for accessing the GPRS (specified if the APN is used or left
blank if the APN is not used)Server IP
AddressObtained from the element management
system (EMS)
Comm Method
GPRS+SMS (if the SMS modem is configured) User
PasswordPassword for accessing the GPRS (specified if the APN is used or left
blank if the APN is not used)
Server IP Backup
Obtained from the EMS
SMC Num Obtained from the survey table
17
Please SelectSystem Type:
DG&ACB
Please SelectSystem Type:
DG&DCB
or
Step 1: Set application parameters.
a. Initial power-on
b. Non-initial power-on
0#
SettingsDG SetApplication Set
Engineer Set
Application SetSystem Type
DG&ACB
Enter Enter
Enter Enter
Step 2: Set system parameters.
0#EnterEnter
Server IP Addr:0.0.0.0
Server IP Backup:
0.0.0.0
Enter
Step 3: Set battery parameters.
0#
Timing BC:Enable
BC Duration:
30 days
Install Date:2009-01-01
BMU Number:
0 Piece
Batt 1 Cap:490Ah
Batt 2 Cap:
490Ah
Enter Enter
Enter Max Discharge:Disable
Max Disch Time:
24h
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsDG SetApplication Set
Engineer Set
Application SetSystem Type
DG&DCB
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
Local Address: 1Lang: EnglishDisp Contrast:3
Modify User PWD
Server IP Addr:0.0.0.0
Server IP Backup:
0.0.0.0
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsSystem SetAlarm Set
Battery Set
Batt 1 Cap:490Ah
Batt 2 Cap:
490Ah
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
18
Step 4: Set network parameters.
Enter
User1 Phone Num>
SMS Test Num>
APN Name>
APN Number>
User Name>
If both the GPRS and SMS are used in networking, the value of GPRS IP Addr is not 0.0.0.0 and the NetEco has obtained
the correct site information, the dialup service is successful.
3
If only the SMS is used in networking, check the validity of the SMS test number on the LCD and then test the SMS function.
If the number receives 210231***************, the settings related to the SMS are correctly set on the HPMU.
OMU IP Addr:0.0.0.0
GPRS IP Addr:
0.0.0.0
Scenario 2: Communication over the Ethernet
1 Verify that the LEDs on the PMB01 panel, OMU01 panel, and HCU01 panel are in a normal state.
Set parameters on the HPMU. The initial password is 0.2
Parameter Settings on the HPMU
Parameter Value Parameter Value Parameter Value
Application Set System Set Battery Set
System Type
DG&DCB Zone Set based on actual requirements Batt 1 Cap Set based on actual requirements
Net Para Set Date Set based on actual requirements
Time Set based on actual requirements Batt 2 Cap Set based on actual requirementsComm
MethodETH Server IP Address
Back UPObtained from the EMS
Server IP Address Obtained from the EMS Install Date
Set based on actual requirementsOMU IP Set according to the network plan
OMU Mask IP Set according to the network plan
Gateway IP Set according to the network plan
User Password>
Neteco Num
>
SMC Num
>
Comm MethodGPRS+SMSDial Up/Down
Dial up
0#EnterEnter2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsDG SetApplication Set
Engineer Set
SettingsNet Para Set
User2 Phone Num>
User3 Phone Num>
User4 Phone Num>
User5 Phone Num>
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
0#
Caution:Start Sms Test? ENTER:Continue
CANCEL:Quit
Enter Enter Enter
Enter
Before performing the SMS test, ensure that the
SMS test number is valid.
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
MaintenanceFunction TestReset HPMU
Sms Test
MaintenanceFunction TestReset HPMU
Sms Test
19
Step 1: Set the display language and application parameters.
Step 3: Set system parameters.
OMU IP0.0.0.0
OMU Mask IP
0.0.0.0
Please SelectSystem Type:
DG&ACB
Please SelectSystem Type:
DG&DCB
or
a. Initial power-on
b. Non-initial power-on
0#
SettingsDG SetApplication Set
Engineer Set
Application SetSystem Type
DG&ACB
Enter Enter
Enter Enter
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsDG SetApplication Set
Engineer Set
Application SetSystem Type
DG&DCB
0#EnterEnter
Server IP Addr:0.0.0.0
Server IP Backup:
0.0.0.0
Enter
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
Local Address: 1Lang: EnglishDisp Contrast:3
Modify User PWD
Server IP Addr:0.0.0.0
Server IP Backup:
0.0.0.0
OMU IP0.0.0.0
OMU Mask IP
0.0.0.0
Enter Comm MethodGPRS+SMSDial Up/Down
Dial up
0#EnterEnter2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsDG SetApplication Set
Engineer Set
SettingsNet Para Set
Enter Comm MethodETH
Dial Up/Down
Dial up
Step 2: Set network parameters.
Gateway IP0.0.0.0
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
20
In-Band Communication (over the HPMU)
1 Verify that the LEDs on the PMB01 panel, OMU01 panel, and HCU01 panel are in a normal state.
Set parameters on the HPMU.
The initial password is 0.2
Parameter Settings on the HPMU
Parameter Value Parameter Value Parameter Value
Application Set System Set Battery Set
System Type DG&DCB Zone Set based on actual
requirements
Batt 1 Cap Set based on actual
requirements
Date Set based on actual
requirements
Batt 2 Cap Set based on actual
requirements
Time Set based on actual
requirements
Install Date Set based on actual
requirements
Local Address 27
Step 1: Set the display language and application parameters.
Please SelectSystem Type:
DG&ACB
Please SelectSystem Type:
DG&DCB
or
a. Initial power-on
b. Non-initial power-on
0#
SettingsDG SetApplication Set
Engineer Set
Application SetSystem Type
DG&ACB
Enter Enter
Enter Enter
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsDG SetApplication Set
Engineer Set
Application SetSystem Type
DG&DCB
Step 4: Set battery parameters.
0#
Timing BC:Enable
BC Duration:
30 days
Install Date:2009-01-01
BMU Number:
0 Piece
Batt 1 Cap:490Ah
Batt 2 Cap:
490Ah
Enter Enter
Enter Max Discharge:Disable
Max Disch Time:
24h
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsSystem SetAlarm Set
Battery Set
Batt 1 Cap:490Ah
Batt 2 Cap:
490Ah
Verify that the NetEco has obtained the correct site information.3
21
Start the AC input of the power system and AC output of the ATS, and configure the D.G. and ATS to work in automatic mode.
The D.G. starts to charge the DCB. Check whether the data in the SAU system information list and on the HPMU standby screen matches the actual configurations. If yes, proceed to step 6. If no, check cable connections and part configurations.
Button Name Function
ENT Confirmation
button
Displays a submenu or confirms the current operation, or makes a new
setting take effect.
Up arrow key Allows you to view menus of the same level on the previous page or next
page or to change the value option when the value is a numeral on the
parameter setting screen. Down arrow key
Left arrow key Returns to the previous menu without saving the current parameter settings.
Right arrow key Moves the cursor on the parameter setting screen.
The following table describes the buttons on the SAU panel.
Step 3: Set battery parameters.
0#
Timing BC:Enable
BC Duration:
30 days
Install Date:2009-01-01
BMU Number:
0 Piece
Batt 1 Cap:490Ah
Batt 2 Cap:
490Ah
Enter Enter
Enter Max Discharge:Disable
Max Disch Time:
24h
2009-06-16Batt1 Volt:52.3VBatt2 Volt: 50.6V
Supplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
SettingsSystem SetAlarm Set
Battery Set
Batt 1 Cap:490Ah
Batt 2 Cap:
490Ah
Step 2: Set system parameters.
0#EnterEnter
Enter
2009-06-16
Batt1 Volt:52.3V
Batt2 Volt:
50.6VSupplier:DG1
MAIN MENU
StatusMaintenance
Settings
MAIN MENU
StatusMaintenance
Settings
Enter passwordend with #:>#
SettingsSystem SetAlarm Set
Battery Set
Local Address: 27Lang: EnglishDisp Contrast:3
Modify User PWD
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
Date:2009-07-06
Time: 13:27
Zone: GMT+8:00
22
Check whether the values in the system information list are the same as the actual configurations, whether the LEDs on panels of the SAU and HPMU indicate alarms, and whether an alarm message for the SAU or HPMU is displayed after you select Active Alarm. If there is an alarm, rectify the fault. For details, see the maintenance guide.
Switch on the DC-powered load connecting to the power system and the AC-powered load connecting to the ATS.
If no alarm is raised after the system runs for a period of time, close and lock the cabinet doors, and hand the keys over tothe persons in charge.
StatusSys managementParameter Setting
History
ENT
SAU
Remote 10 44 DG1System Bat1 [-----] Volt:0.0V Cur: 0A
System Bat1 [-----] Volt:51.8V Cur: 37A
ENT
Load status:DG1Bat Online :BatteryCH Time :784Min
Bat 1 volt:0.0VBat 2 volt :51.7V
ENT
HPMU
Phase A: 215.7VPhase B: 216.2VPhase C: 215.7V
Ambient: 25°C
2009-06-16Batt1 Volt:52.3VBatt2 Volt: 50.6V
Supplier:DG1
Active AlarmSystemVersion
Alarm HistoryClear Hist Alarm
Active AlarmSystemVersion
Alarm HistoryClear Hist Alarm
0#Reset HPMUSms TestDG Test
BMU&DTS Test
Close all DGPlease wait
Enter Enter
Enter Test open DG 1Please wait
MAIN MENU
Status
MaintenanceSettings
MAIN MENU
Status
MaintenanceSettings
Enter passwordend with #:>#
Enter
Reset HPMUSms TestDG Test
BMU&DTS Test
Caution:Start DG Test?Enter: Continue
CANCEL: Quit
Enter Test close DG 1Please wait
2009-06-16Batt1 Volt:52.3VBatt2 Volt:50.6V
Supplier:DG1
Test ResultMains: OffDG1 test: Pass
DG2 test:NT/Fail
Test open DG 2Please wait
Test close DG 2Please wait
On the standby screen of the HPMU, choose Status > Maintenance > Reset HPMU > DG Test. The HPMU stops the running D.G. After that, the HPMU starts D.G. 1 and then stops it, and starts D.G. 2 and then stops it. The HPMU finally displays DG1 test: Pass DG2 test: NT/Fail.
In scenarios with one D.G., the D.G. must be connected to ports reserved for D.G. 1 on the SAU. Otherwise, the D.G. 1 test fails, and the D.G. 2 test cannot be performed.
23
Network Diagram
Scenario 2: D.G.+D.G.+DCB
Installation Procedure
(a1) AC power cable between D.G.
1 and the ATS
(a3) AC power cable between the ATS
and the power system
(a4) (Optional) Power cable
between the AC-powered load and
the ATS
(a5) AC power cable between D.G. 2 and
the ATS
(d1) Power cable between the DC-
powered load and the power
system
(d2) DC power cable between the power
system and the DCB
(d3) Signal cable for monitoring the
voltage of the –48 V DCB
(d4) DC power cable between the HPMU
and the DCB
(s1) (Optional) Signal cable
between the fuel level sensor and
the SAU
(s2) Signal cable for starting D.G. 1 (s3) Signal cable for monitoring the
voltage of the 12 V storage battery
in D.G. 1
(s4) Signal cable for detecting the charge
capacity and discharge capacity of the DCB
(s5) Signal cable between the
ambient temperature sensor and
the SAU
(s6) Communications cable between the
HPMU and the SAU
(s7) (Optional) Communications
cable between the HPMU (with the
OMU) and the transport network
(s8) (Optional) Communications cable
between the NetEco and the transport
network
(s10) Signal cable for the ATS to
report its output voltage to the SAU
(s11) Signal cable for starting D.G. 2 (s12) Signal cable for monitoring the
voltage of the 12 V storage battery
in D.G. 2
(s13) Communications cable between the
intelligent electric meter and the HPMU
AC power cable (a)
DC power cable (d)
Signal cable (s)
Fuel tank
D.G. 1
NetEco
GPRS/IPnetwork
HPMU
(with the OMU)
SAU
Ambienttemperature sensor
Power systemATS
DCB
AC-powered load DC-powered load
D.G. and Battery Hybrid Power System
a1
a4
a3
d1
d2
d3d4
s1s2
s3
s4
s5
s6
s7
s8
s10
Current sensor
1. Install the D.G. and Battery Hybrid Power System.
2. Disconnect the power supply of the original storage battery.
3. Install cables.
4. Power on and commission the Power1000.
s11s12
a5
D.G. 2
Compared with scenario 1, scenario 2 requires one more D.G. and three more cables, namely, the AC power cable between D.G. 2 and the ATS, signal cable for monitoring the voltage of the 12 V storage battery in D.G. 2, and signal cable for starting D.G. 2.
s13
Intelligent electric meter
24
1. Installing the D.G. and Battery Hybrid Power System
For details, see the steps a–c on pages 3–7. Note that D.G. 1 is installed prior to D.G. 2.
2. Disconnecting the Power Supply of the Original Storage Battery
For details, see section 2 on page 8.
3. Installing Cables
Prepare terminals as required before installing cables.
Cord end terminal
Ring terminal
Heat shrink tubing
COAX crimping tool
Hydraulic pliers
Flipping the Switch of the SAU to the OFF Positiona
For details, see step a under section 3 "Installing Cables" on pages 8–15.
Installing Cables Between the MBBS, the DCB, and the Power Systemb
For details, see step b on pages 9–10.
Removing the Original Batteries and Battery Cabinetc
Enabling the DCB to Supply Powerd
Remove baffle plates from top to bottom and take out original storage batteries.
Remove the battery cabinet.
At least two persons are required to carry one storage battery.
Switch the circuit breaker of the original battery cabinet or battery rack to the OFF position.
Connect the charging circuit between the power system and the DCB by referring to the Power System User Manual.
Stop the D.G. by referring to the user manual of the D.G.
Disconnect the connections between the ATS and both of the D.G. and power system by referring to the ATS User Manual.
25
Cables Between the MBBS, the D.G., and the ATSe
No. Cable The Other End Cable The Other End
1 Signal cable for the ATS to report its
output voltage to the SAU
ATS Output (U port) of the SAU L1 port of the ATS
ATS Output (V port) of the SAU L2 port of the ATS
ATS Output (W port) of the SAU L3 port of the ATS
ATS Output (N1 port) of the SAU N port of the ATS
2 Signal cable for monitoring the voltage of
the 12 V storage battery in D.G. 1 12V1 port of PORT1 of the SAU Storage battery
in D.G. 1
3 Signal cable for starting D.G. 1 NC1 and COM1 ports of PORT2 of the
SAU
Dry contacts for
starting D.G. 1
4 (Optional) Signal cable between the fuel
level sensor and the SAUFuel1 port of PORT4 of the SAU Fuel level sensor
5 Signal cable for monitoring the voltage of
the 12 V storage battery in D.G. 2 12V2 port of PORT1 of the SAU Storage battery
in D.G. 2
6 Signal cable for starting D.G. 2 NC2 and COM2 ports of PORT2 of the
SAU
Dry contacts for
starting D.G. 2
ATS Output
U
V
W
N1 1
ATS
D.G. 1
Fuel tank
2
12V1 NC1 COM1
Fuel1
3
4
4
2 3
+ -
1
Installing Communications CablesgFor details, see step g on pages 12–15.
+ -
12V2
D.G. 2
5
6
5
+ - + -
NC2 COM2
6
Checking Cable ConnectionshFor details, see step h on page 15.
Connecting the Communications Cable Between the Intelligent Electric Meter and the HPMUfFor details, see step f on pages 11–12.
1. For the D.G. that is started when the dry contact is closed, connect the signal cable
for starting the D.G. to the NC1 and COM1 ports or NC2 and COM2 ports of the SAU.
For the D.G. that is started when the dry contact is open, connect the signal cable for
starting the D.G. to the NO1 and COM1 ports or NO2 and COM2 ports of the SAU.
2. Before connecting the signal cable between the fuel level sensor and the SAU, remove the 2-pin terminal (green part in the following figure) from the cable.
If there is only one fuel
level sensor, connect the
sensor to the Fuel1 port.
If there are two fuel level
sensors, connect the
sensor of D.G. 1 to the
Fuel1 port and connect
the sensor of D.G. 2 to
the Fuel2 port.
+ -
26
4. Powering On and Commissioning the Power1000
aConfigure the D.G. and ATS to work in manual mode, and stop the D.G. and the AC output of the ATS. For details, see the ATS User Manual.
Flip the power switches of the SAU and HPMU both to the ON position.
Set parameters on the HPMU.
For details, see step 3 on pages 16–21.
Start the AC input of the power system and AC output of the ATS, and configure the D.G. and ATS to work in automatic mode.
The D.G. starts to charge the DCB. Check whether the data in the SAU system information list and on the HPMU standby screen matches the actual configurations. If yes, proceed to step 6. If no, check cable connections and part configurations.
Check whether the values in the system information list are the same as the actual configurations, whether the LEDs on panels of the SAU and HPMU indicate alarms, and whether an alarm message for the SAU or HPMU is displayed after you select Active Alarm. If there is an alarm, rectify the fault. For details, see the maintenance guide.
Switch on the DC-powered load connecting to the power system and the AC-powered load connecting to the ATS.
If no alarm is raised after the system runs for a period of time, close and lock the cabinet doors, and hand the keys over tothe persons in charge.
For details, see step 2 in section 4 "Powering On and Commissioning the Power1000" on page 15.
For details about how to set parameters on the SAU and HPMU, see step 5 on pages 21–22.
0#Reset HPMUSms TestDG Test
BMU&DTS Test
Close all DGPlease wait
Enter Enter
Enter Test open DG 1Please wait
MAIN MENU
Status
MaintenanceSettings
MAIN MENU
Status
MaintenanceSettings
Enter passwordend with #:>#
Enter
Reset HPMUSms TestDG Test
BMU&DTS Test
Caution:Start DG Test?Enter: Continue
CANCEL: Quit
Enter Test close DG 1Please wait
2009-06-16Batt1 Volt:52.3VBatt2 Volt:50.6V
Supplier:DG1
Test ResultMains: OffDG1 test: Pass
DG2 test: Pass
Test open DG 2Please wait
Test close DG 2Please wait
On the standby screen of the HPMU, choose Status > Maintenance > Reset HPMU > DG Test. The HPMU stops the running D.G. After that, the HPMU starts D.G. 1 and then stops it, and starts D.G. 2 and then stops it. The HPMU finally displays DG1 test: Pass DG2 test: pass.
27
Network Diagram
Scenario 3: D.G.+Mains+DCB
Installation Procedure
(a1) AC power cable between D.G. 1
and the ATS
(a2) AC power cable between the
mains and the ATS
(a3) AC power cable between
the ATS and the power system
(a4) (Optional) Power cable between
the AC-powered load and the ATS
(d1) Power cable between the DC-
powered load and the power system
(d2) DC power cable between the
power system and the DCB
(d3) Signal cable for monitoring
the voltage of the –48 V DCB
(d4) DC power cable between the
HPMU and the DCB
(s1) (Optional) Signal cable between the
fuel level sensor and the SAU
(s2) Signal cable for starting D.G. 1 (s3) Signal cable for monitoring
the voltage of the 12 V storage
battery in D.G. 1
(s4) Signal cable for detecting the
charge capacity and discharge capacity
of the DCB
(s5) Signal cable between the ambient
temperature sensor and the SAU
(s6) Communications cable between
the HPMU and the SAU
(s7) (Optional) Communications
cable between the HPMU (with
the OMU) and the transport
network
(s8) (Optional) Communications cable
between the NetEco and the transport
network
(s9) Signal cable for monitoring the
mains voltage
(s10) Signal cable for the ATS to
report its output voltage to the SAU
(s13) Communications cable
between the intelligent electric
meter and the HPMU
AC power cable (a)
DC power cable (d)
Signal cable (s)
Fuel tank D.G. 1
NetEco
GPRS/IPnetwork
HPMU(with the OMU)
SAU
Ambient temperature sensor
Power systemATS
DCB
AC-powered load DC-powered load
D.G. and Battery Hybrid Power System
a1
a4
a3
d1
d2
d3d4
s1
s2
s3
s4
s5
s6
s7
s8
s9 s10
Current sensor
1. Install the D.G. and Battery Hybrid Power System.
2. Disconnect the power supply of the original storage battery.
3. Install cables.
4. Power on and commission the Power1000.
a2
Mains
Compared with scenario 1, scenario 3 requires the mains and two more cables, namely, the AC power cable between the mains and the ATS as well as the signal cable for monitoring the mains voltage.
s13
Intelligent electric meter
28
1. Installing the D.G. and Battery Hybrid Power System
For details, see steps a–c on pages 3–7.
2. Disconnecting the Power Supply of the Original Storage Battery
3. Installing Cables
Prepare terminals as required before installing cables.
Cord end terminal
Ringterminal
Heat shrink tubing
COAX crimping tool
Hydraulic pliers
Flipping the Switch of the SAU to the OFF Positiona
For details, see step a under section 3 "Installing Cables" on pages 8–15.
Installing Cables Between the MBBS, the DCB, and the Power Systemb
For details, see step b on pages 9–10.
Removing the Original Batteries and Battery Cabinetc
Enabling the DCB to Supply Powerd
Remove baffle plates from top to bottom and take out original storage batteries.
Remove the battery cabinet.
At least two persons are required to carry one storage battery.
Switch the circuit breaker of the original battery cabinet or battery rack to the OFF position.
Connect the charging circuit between the power system and the DCB by referring to the Power System User Manual.
Stop the D.G. by referring to the user manual of the D.G.
Disconnect the connections between the ATS and all of the mains, D.G., and power system by referring to the ATS User Manual.
Switching the Power Supplier to D.G.a
1. When removing and installing storage batteries, ensure that the D.G. supplies power properly.2. When disconnecting cables from storage batteries, wear ESD gloves, use insulated tools (such as a wrench
with its handle wrapped with PVC insulation tape), and tighten the nuts on all DCBs after disconnecting the cables.
Disconnect the main supply and then start the D.G. by referring to the user manual of the D.G.
Configure the ATS to work in manual mode by referring to the ATS User Manual.
Switch the power supplier to the D.G. on the ATS by referring to the ATS User Manual.
Disconnecting the Power Supply of the Original Storage Batteryb
For details, step b under section 2 “Disconnecting the Power Supply of the Original Storage Battery” on page 8.
29
Cables Between the MBBS, the D.G., and the ATSe
No. Cable The Other End Cable The Other End
1 Signal cable for the ATS to report its output
voltage to the SAU
ATS Output (U port) of the SAU L1 port of the ATS
ATS Output (V port) of the SAU L2 port of the ATS
ATS Output (W port) of the SAU L3 port of the ATS
ATS Output (N1 port) of the SAU N port of the ATS
2 Signal cable for monitoring the voltage of
the 12 V storage battery in D.G. 1 12V1 port of PORT1 of the SAU Storage battery in D.G. 1
3 Signal cable for starting D.G. 1 NC1 and COM1 ports of PORT2 of
the SAU
Dry contacts for starting
D.G. 1
4 (Optional) Signal cable between the fuel
level sensor and the SAUFuel1 port of PORT4 of the SAU Fuel level sensor
5 Signal cable for monitoring the mains
voltage
Main Input port of the SAU Mains
ATS Output
U
V
W
N1
1
ATS
D.G. 1
Fuel tank
2
12V1 NC1 COM1
Fuel1
3
4
4
2 3
+ -
1
+ -
Main Input
N2
L3
L2
L1
5
5
1. For the D.G. that is started when the dry contact is closed, connect the signal
cable for starting the D.G. to the NC1 and COM1 ports of the SAU. For the D.G.
that is started when the dry contact is open, connect the signal cable for starting
the D.G. to the NO1 and COM1 ports of the SAU.
2. Before connecting the signal cable between the fuel level sensor and the SAU, remove the 2-pin terminal (green part in the following figure) from the cable.
Installing Communications Cablesg
For details, see step g on pages 12–15.
Connecting the Communications Cable Between the Intelligent Electric Meter and the HPMUfFor details, see step f on pages 11–12.
30
4. Powering On and Commissioning the Power1000
a Configure the D.G. and ATS to work in manual mode, and stop the D.G. and the AC output of the ATS. For details, see the ATS User Manual.
Flip the power switches of the SAU and HPMU both to the ON position.
Set parameters on the HPMU.
For details, see step 3 on pages 16–21.
Start the AC input of the power system and AC output of the ATS, and configure the D.G. and ATS to work in automatic mode.The D.G. starts to charge the DCB. Check whether the data in the SAU system information list and on the HPMU standby screen matches the actual configurations. If yes, proceed to step 6. If no, check cable connections and part configurations.
For details, see step 2 in section 4 "Powering On and Commissioning the Power1000" on page 15.
No. Check Item
1 All cables are connected correctly.
2 Cables to the MBBS are connected properly.
3 The battery circuit breaker on the MBBS is switched to the ON position, the mains input circuit breaker is switched to the OF F
position, the D.G. output circuit breaker is switched to the OFF position, and the D.G. works in manual mode.
4 No short circuit occurs between the –48 V power cable and any of the ground bar, positive bus bar, three-phase live wire, neutral
wire, and ground cable. No short circuit occurs between the three-phase live wire, the neutral wire, and the ground cable.
5 Cable holes are blocked by fireproof mud.
Checking Cable Connectionsh
For details about how to set parameters on the SAU and HPMU, see step 5 on pages 21–22.
0#Reset HPMUSms TestDG Test
BMU&DTS Test
Close all DGPlease wait
Enter Enter
Enter Test open DG 1Please wait
MAIN MENU
Status
MaintenanceSettings
MAIN MENU
Status
MaintenanceSettings
Enter passwordend with #:>#
Enter
Reset HPMUSms TestDG Test
BMU&DTS Test
Caution:Start DG Test?Enter: Continue
CANCEL: Quit
Enter Test close DG 1Please wait
2009-06-16Batt1 Volt:52.3VBatt2 Volt:50.6V
Supplier:DG1
Test ResultMains: OffDG1 test: Pass
DG2 test:NT/Fail
Test open DG 2Please wait
Test close DG 2Please wait
On the standby screen of the HPMU, choose Status > Maintenance > Reset HPMU > DG Test. The HPMU stops the running D.G. After that, the HPMU starts D.G. 1 and then stops it, and starts D.G. 2 and then stops it. The HPMU finally displays DG1 test: Pass DG2 test: NT/Fail.
In scenarios with one D.G., the D.G. must be connected to ports reserved for D.G. 1 on the SAU. Otherwise, the D.G. 1 test fails, and the D.G. 2 test cannot be performed.
31
Check whether the values in the system information list are the same as the actual configurations, whether the LEDs on panels of the SAU and HPMU indicate alarms, and whether an alarm message for the SAU or HPMU is displayed after you select Active Alarm. If there is an alarm, rectify the fault. For details, see the maintenance guide.
Switch on the DC-powered load connecting to the power system and the AC-powered load connecting to the ATS.
If no alarm is raised after the system runs for a period of time, close and lock the cabinet doors, and hand the keys over tothe persons in charge.
Connect the Power1000 to the mains. The ATS starts the AC mains power supply and the D.G. stops after tens of seconds (this duration is configurable).
32
Network Diagram
Scenario 4: D.G.+D.G.+Mains+DCB
Installation Procedure
1. Install the D.G. and Battery Hybrid Power System.
2. Disconnect the power supply of the original storage battery.
3. Install cables.
4. Power on and commission the Power1000.
Compared with scenario 1, scenario 4 requires the mains, one more D.G., and five more cables, namely, the AC power cable between
the mains and the ATS, signal cable for monitoring the mains voltage, AC power cable between D.G. 2 and the ATS, signal cablefor
monitoring the voltage of the 12 V storage battery in D.G. 2, and signal cable for starting D.G. 2.
(a1) AC power cable between
D.G. 1 and the ATS
(a2) AC power cable between the
mains and the ATS
(a3) AC power cable between the
ATS and the power system
(a4) (Optional) Power cable between the AC-
powered load and the ATS
(a5) AC power cable between
D.G. 2 and the ATS
(d1) Power cable between the DC-
powered load and the power
system
(d2) DC power cable between the
power system and the DCB
(d3) Signal cable for monitoring the voltage of
the –48 V DCB
(d4) DC power cable between the
HPMU and the DCB
(s1) (Optional) Signal cable
between the fuel level sensor and
the SAU
(s2) Signal cable for starting D.G.
1
(s3) Signal cable for monitoring the voltage of
the 12 V storage battery in D.G. 1
(s4) Signal cable for detecting the
charge capacity and discharge
capacity of the DCB
(s5) Signal cable between the
ambient temperature sensor and
the SAU
(s6) Communications cable
between the HPMU and the SAU
(s7) (Optional) Communications cable
between the HPMU (with the OMU) and the
transport network
(s8) (Optional) Communications
cable between the NetEco and
the transport network
(s9) Signal cable for monitoring the
mains voltage
(s10) Signal cable for the ATS to
report its output voltage to the
SAU
(s11) Signal cable for starting D.G. 2
(s12) Signal cable for monitoring
the voltage of the 12 V storage
battery in D.G. 2
(s13) Communications cable
between the intelligent electric
meter and the HPMU
AC power cable (a)
DC power cable (d)
Signal cable (s)
Fuel tank D.G. 1
NetEco
GPRS/IPnetwork
HPMU
(with the OMU)
SAU
Power system
ATS
DCB
AC-powered load DC-powered load
D.G. and Battery Hybrid Power System
a1
a4
a3
d1
d2
d3d4
s1s2
s3
s4
s5
s6
s7
s8
s9 s10
Current sensor
s11s12
a5
D.G. 2
a2
Mains
s13
Intelligent electric meter
Ambient temperature sensor
33
1. Installing the D.G. and Battery Hybrid Power System
For details, see the steps a–c on pages 3–7. Note that D.G. 1 is installed prior to D.G. 2.
2. Disconnecting the Power Supply of the Original Storage Battery
3. Installing Cables
Prepare terminals as required before installing cables.
Cord end terminal
Ring terminal
Heat shrink tubing
COAX crimping tool
Hydraulic pliers
Flipping the Switch of the SAU to the OFF Positiona
For details, see step a under section 3 on page 8.
Installing Cables Between the MBBS, the DCB, and the Power Systemb
For details, see step b on pages 9–10.
Removing the Original Batteries and Battery Cabinetc
Enabling the DCB to Supply Powerd
Remove baffle plates from top to bottom and take out original storage batteries.
Remove the battery cabinet.
At least two persons are required to carry one storage battery.
Switch the circuit breaker of the original battery cabinet or battery rack to the OFF position.
Connect the charging circuit between the power system and the DCB by referring to the Power System User Manual.
Stop the D.G. by referring to the user manual of the D.G.
Disconnect the connections between the ATS and all of the mains, D.G., and power system by referring to the ATS User Manual.
Switching the Power Supplier to D.G.a
1. When removing and installing storage batteries, ensure that the D.G. supplies power properly.2. When disconnecting cables from storage batteries, wear ESD gloves, use insulated tools (such as a wrench
with its handle wrapped with PVC insulation tape), and tighten the nuts on all DCBs after disconnecting the cables.
Disconnect the main supply and then start the D.G. by referring to the user manual of the D.G.
Configure the ATS to work in manual mode by referring to the ATS User Manual.
Switch the power supplier to the D.G. on the ATS by referring to the ATS User Manual.
Disconnecting the Power Supply of the Original Storage Batteryb
For details, step b under section 2 “Disconnecting the Power Supply of the Original Storage Battery” on page 8.
34
1
ATS
D.G. 1
Fuel tank
2
12V1 NC1 COM1
Fuel1
3
4
4
2 3
+ -
1
+ -
12V2
D.G. 2
5
6
5
+ - + -
NC2 COM2
6
Cables Between the MBBS, the D.G., and the ATSe
ATS Output
U
V
N1
1
Main Input
N2
L3
L2
L1
7
Mains
No. Cable The Other End Cable The Other End
1 Signal cable for the ATS to report its output voltage
to the SAU
ATS Output (U port) of the SAU L1 port of the ATS
ATS Output (V port) of the SAU L2 port of the ATS
ATS Output (W port) of the SAU L3 port of the ATS
ATS Output (N1 port) of the SAU N port of the ATS
2 Signal cable for monitoring the voltage of the 12 V
storage battery in D.G. 1 12V1 port of PORT1 of the SAU Storage battery in
D.G. 1
3 Signal cable for starting D.G. 1 NC1 and COM1 ports of PORT2
of the SAU
Dry contacts for
starting D.G. 1
4 (Optional) Signal cable between the fuel level
sensor and the SAUFuel1 port of PORT4 of the SAU Fuel level sensor
5 Signal cable for monitoring the voltage of the 12 V
storage battery in D.G. 2 12V2 port of PORT1 of the SAU Storage battery in
D.G. 2
6 Signal cable for starting D.G. 2 NC2 and COM2 ports of PORT2
of the SAU
Dry contacts for
starting D.G. 2
7 Signal cable for monitoring the mains voltage Main Input port of the SAU Mains
7
1. For the D.G. that is started when the dry contact is closed, connect the signal
cable for starting the D.G. to the NC1 and COM1 ports or NC2 and COM2 ports of
the SAU. For the D.G. that is started when the dry contact is open, connect the
signal cable for starting the D.G. to the NO1 and COM1 ports or NO2 and COM2
ports of the SAU.2. Before connecting the signal cable between the fuel level sensor and the SAU,
remove the 2-pin terminal (green part in the following figure) from the cable.
Connecting the Communications Cable Between the Intelligent Electric Meter and the HPMUf
For details, see step f on pages 11–12.
W
+ -
35
4. Powering On and Commissioning the Power1000
aConfigure the D.G. and ATS to work in manual mode, and stop the D.G. and the AC output of the ATS. For details, see the ATS User Manual.Flip the power switches of the SAU and HPMU both to the ON position.
Set parameters on the HPMU.
For details, see step 3 on pages 16–21.
Start the AC input of the power system and AC output of the ATS, and configure the D.G. and ATS to work in automatic mode.The D.G. starts to charge the DCB. Check whether the data in the SAU system information list and on the HPMU standby screen matches the actual configurations. If yes, proceed to step 6. If no, check cable connections and part configurations.
For details, see step 2 in section 4 "Powering On and Commissioning the Power1000" on page 15.
No. Check Item
1 All cables are connected correctly.
2 Cables to the MBBS are connected properly.
3 The battery circuit breaker on the MBBS is switched to the ON position, the mains input circuit breaker is switched to the OF F
position, the D.G. output circuit breaker is switched to the OFF position, and the D.G. works in manual mode.
4 No short circuit occurs between the –48 V power cable and any of the ground bar, positive bus bar, three-phase live wire, neutral
wire, and ground cable. No short circuit occurs between the three-phase live wire, the neutral wire, and the ground cable.
5 Cable holes are blocked by fireproof mud.
Checking Cable Connectionsh
Installing Communications Cablesg
For details, see step g on pages 12–15.
For details about how to set parameters on the SAU and HPMU, see step 5 on pages 21–22.
0#Reset HPMUSms TestDG Test
BMU&DTS Test
Close all DGPlease wait
Enter Enter
Enter Test open DG 1Please wait
MAIN MENU
Status
MaintenanceSettings
MAIN MENU
Status
MaintenanceSettings
Enter passwordend with #:>#
Enter
Reset HPMUSms TestDG Test
BMU&DTS Test
Caution:Start DG Test?Enter: Continue
CANCEL: Quit
Enter Test close DG 1Please wait
2009-06-16Batt1 Volt:52.3VBatt2 Volt:50.6V
Supplier:DG1
Test ResultMains: OffDG1 test: Pass
DG2 test: Pass
Test open DG 2Please wait
Test close DG 2Please wait
On the standby screen of the HPMU, choose Status > Maintenance > Reset HPMU > DG Test. The HPMU stops the running D.G. After that, the HPMU starts D.G. 1 and then stops it, and starts D.G. 2 and then stops it. The HPMU finally displays DG1 test: Pass DG2 test: pass.
36
Check whether the values in the system information list are the same as the actual configurations, whether the LEDs on panels of the SAU and HPMU indicate alarms, and whether an alarm message for the SAU or HPMU is displayed after you select Active Alarm. If there is an alarm, rectify the fault. For details, see the maintenance guide.
Switch on the DC-powered load connecting to the power system and the AC-powered load connecting to the ATS.
If no alarm is raised after the system runs for a period of time, close and lock the cabinet doors, and hand the keys over tothe persons in charge.
Connect the Power1000 to the mains. The ATS starts the AC mains power supply and the D.G. stops after tens of seconds (this duration is configurable).
HUAWEI TECHNOLOGIES CO., LTD.Huawei Industrial Base Bantian Longgang
Shenzhen 518129
www.huawei.com