Upload
sofian-hachid
View
148
Download
25
Embed Size (px)
Citation preview
SHENZHEN HUAWEI AGISSON ELECTRIC CO., LTD.
TP48600B V100R001
Quick Installation Guide
Document Version: 04Part Number: 31504805Issued on: 2011-01-05
Insulating gloves
& ESD gloves
Installation Tools
1
Phillipsscrewdriver(M3, M4: 1 PCS) Adjustable wrench Nylon tie
Electrical knife Torque wrench Wire stripper Crimping tool
Multimeter Claw hammerDiagonal pliers Paint brush
Hydraulic pliers Insulated handleMarker Vacuum cleaner
Socket wrench Insulating tapeHammer drill (with
Ф16 drill bit) Heat gun
Flat-headscrewdriver(M3, M4: 1 PCS)
Inner hexagon wrench
Copyright Huawei Technologies Co.,Ltd.2011.All rights reserved.
The Flat-head screwdriver, Phillips screwdriver, Adjustable wrench, Torque wrench, and Inner hexagon wrench should be use insulating tapeas a wrap..
Cutting pliers
Cabinet Appearance
Positive busbar of the DC output
Negative-pole input of the battery
LLVD fuse
AC input circuit breaker
PMU
Rectif ier module
Ground bar ofthe cabinet
AC surge protector
BLVD circuit breaker
Power monitoringinterface board(under the cover plate)
LLVD switch
BLVD switch
LLVD circuit breaker
N wiring terminal
The pictures are for reference only. The operation must be in accordance with the actual conditions.
2
Cabinet InstallationInstalling the Cabinet on the Ground
3
a Installing the Expansion Bolt Assembly
b Installing Cabinet
M12x60 boltSpring washerFlat washer
Expansion sleeve
Anchor template
Installation hole
Socket wrench
Socket wrench
c Installing PSU
The maximum output current is 30A or 50A per PSU.
Two PSU have installed in the cabinet,please installing the PSU refer to the actual requirement.
Connect to battery Connect to power supply system
Installing Sensor (Optional) 1 Installing indoor temperature and humidity sensor. (Optional)
4
2 Installing battery temperature sensor. (Optional)
Main equipment
Indoor temperature and humidity sensor
Shelter
Indoor temperature and humidity sensor
M4 x 35Expansion Bolt
Humidity and temperature sensor: Install it next to the air inlet of the main equipment and far from the air outlet. Install it at the same height of the air inlet of the main equipment.
Cable Connections
1 Installing the PGND Cable
5
Unlock and open the cabinet door, and then remove the cover plate of the cable window on the top of the cabinet.
Remove battery shutdown and load shutdown fuses using an insulated handle.
Set all circuit breaker to OFF.
Cover plate
Cable window
Type Cable section area
Color Exterior
Ground cable
35mm^2 Olivine Ring terminal
Signal cable
/ / Dry contact cable with cord endterminal Sensor cable with pin socket
Communications cable
/ / RJ45
Type Cable section area
Color Exterior
DC outputcable
Determined by the customer device
/ Ring terminal and Cord endterminal
Battery power cable
120mm^2 Blue, and yellow
Ring terminal
220V three-phase AC inputcable
35mm^2 Black jacket with red, yellow, green, and black cables
Ring terminal and Cord endterminal
When connect cables, please wear insulating gloves or ESD gloves.
6
Lead the PGND cables into the cabinet through the cable window, and then connect the PGND cable to the ground bar.
The cables such as the PGND cable. AC power cable, DC power cable, and signal cable cannot be connected or tied together.
2 Installing the Dry Contact Signal Cables and Communication Cables
1. The use of the dry contact signal cables and communication cables is scenario-specific. Before installation, determine the dry contact signal cables and communication cables to be installed according to actual requirements.2. Functions of dry contacts.
J13, J14, J4-J10 are nine dry contact sockets on the power monitoring interface board. Status, Status1, and Status2 are three circuits for the input of the detection signals of the diesel generator. Ctrl1 and Ctrl2 are two circuits for the output of the control signals of the diesel generator. ALM1-ALM7 are seven circuits for the output of the alarm signals of the diesel generator. Each circle represents the corresponding wiring terminal. The black circles are the common terminals of the constant-enabled ports and constant-disabled ports on the relays. NC represents constant-disabled port and NO represents constant-enabled port.
7
Remove the cover plate on the top of the cabinet. Then, lead dry contact signal cables and communication cables through the cable window to the position above dry contacts.
Press the white contact plates slightly using a f lat-head screwdriver. Then, insert the dry contact signal cable into the ports, and pull out the screwdriver to fasten the signal cable.
Subrack cover plate
1. Lead and bind signal cables along the rear of the column.2. The cables such as the PGND cable. AC power cable, DC power cable, and signal cable cannot be connected or bound together.
Signal core wire
Column Power monitoring interface board
Dry contact
Insert communication cables to RJ45 port on the power monitoring interface board according to actual installation requirements.
Do not connect the power system and the BBU with an Ethernet cable or RJ45 communication cable. If the customer requires in-band NMS management of the power system, the NMS management requires setting of the storage battery capacity. For the details of NMS setting, please see the NMS User Guide.
RJ45
Dry contact
White contact plate
8
Bind dry contact signal cables to the cabling rack.
According to the actual installation requirements, Insert the temperature and humidity sensor signal cable and battery temperature sensor signal cable. (Optional)
Indoor temperature and humidity sensor
Battery temperature sensor
3 Installing DC Output Cables
Loosen the bolt on the top of the load power-of f fuse, connect the -48 V output cable to the bolt, and then tighten the bolt using a torque wrench. The recommended torque is 10 N.m.
1. The torque for tightening the bolt cannot exceed 10 Nm.2. The signal cables must be installed in the f ront of -48 V cables.
a Installing LLVD DC Output CablesInsert -48 V DC output cables into the output ports on the LLVD circuit breaker.
Torque wrench(use insulating tape as a wrap)
Ensure that cables are connected to circuit breaker securely.
9
Ensure that cables are connected to circuit breaker securely.
b Installing BLVD DC Output CablesInsert -48 V DC output cables into the output ports on the BLVD circuit breaker.
Connect the 0 V output cables to the DC positive output busbar.
Bind the DC output cables on the cabling rack.
4 Installing Power Cables of BatteriesIf the circuit breaker for batteries is available,Set the circuit breaker of the battery rack or battery cabinet to OFF.
If the circuit breaker for batteries is not available, disconnect one of the cables between two batteries.
Bind the DC output cables on the cabling rack.
Connect the 0 V output cables to the DC positive output busbar.
Phillips screwdriver(use insulating tape as a wrap)
10
Arrange the output cables, and then bind the cables to the cabling rack using nylon ties.
5 Installing AC Input Cables
ACDB
Inner hexagon wrench
Connecting negative poles of batteries: Loosen the bolt on the top of the base of the battery negative -pole access fuse, connect the -48 V input cables to the bolt, and then tighten the bolt using a torque wrench and a adjustable wrench. The recommended torque is 20 N.m.
1. Ensure that the signal cables are installed above battery negative-pole input cables and that the battery protection circuit breaker is set to OFF.
2. When connecting battery negative-pole input cables, the exposed metal part of the torque cannot contact the fuse terminal and the positive busbar. Otherwise, a short circuit may occur.3. The torque for tightening the bolt cannot exceed 20 Nm.
Connect the positive pole of the battery to the positive DC output wiring busbar.Positive pole of the battery
Torque wrench
Adjustable wrench
Negative pole of the battery
Adjustable wrench
Torque wrench
AC input cables is three-phase:Connect the neutral line to the N-terminal.
Connect the U-phase, V-phase, and W-phase lines to the AC input circuit breaker.
U V W
N
a 220 V AC InputaBefore connect AC input cables, set the circuit breaker of ACDB to OFF.
11
110V AC Inputb
ACDB
ACDB
AC input cables is three-phase: Connect the L1, L2, and L3 lines to the AC input circuit breaker.
AC input cables is single-phase: Connect the L1, L2, lines to the AC input circuit breaker.
912
6 Cabling guide
1. Lead and bind cables along the binding holes.2. The cables such as the PGND cable. AC power cable, DC power cable, and signal cable cannot be connected or bound together.
913
7 Checks After the InstallationEnsure that the cabinet and cables are securely installed.Ensure that the cables are installed properly and that the live line, earth line, and neutral line are not short -circuited using a multimeter. Ensure that the 0 V cable and -48 V cable are not short-circuited.Insert the removed battery fuses into the corresponding positions.
8 Conducting a Power-on Testa Connecting the Battery Branch and Setting PMU Parametersa
1. The position of the CPM01 monitoring module, operating keyboard, and status indicator are shown in the following figure.2. The TP48600B is working properly. When the TP48600B communicates with the main equipment, the ALM indicator on the CPM01 does not light and the RUN indicator blinks slowly. The TP48600B is working properly. When the TP48600B does not communicates with the main equipment, the ALM indicator off and the RUN indicator is on. When the TP48600B is severely faulty, the ALM indicator on the CPM01 is ON and the buzzer sounds. For details of troubleshooting methods, see the TP4848600B Maintenance Guide.3. Press ↓ and Enter when the interface is standby interface to decrease the LCD contrast. Press ↑ and Enter at the same timeto increase the LCD contrast.4. When the menu setting interface is displayed, press ↓ or ↑ to browse the menu and set parameters. Press Enter on the standby interface to access the main menu. Press Enter in the main menu to access the submenu. To set the submenu, press Enter to save the value of the menu bar options. Press Cancel to go back to the above menu without saving the value of the menu bar options.5. The PMU does not generate any alarm. When the current interface is not the main menu, the LCD goes dark five minutes later if you do not press any button, and the main menu is displayed eight minutes later if you do not press any button.6. The System Control menu can operated using the user password, engineer password. The Engineer Advanced Setting menu can be operated using the engineer password. The user password and engineer password are 0# and 11# respectively and can be reset on the menu.
1. Set the battery group number, capacity, temperature alarm thresholds, time, and date according to actual conditions.2. The number of the battery groups can be set to 0, 1, and 2. If one battery group is required, set the battery capacity according to the fuse position. For example, if the battery group is connected to fuse BF1, set the capacity to Battery Capacity 1. If the battery group is connected to fuse BF2, set the capacity to Battery Capacity 2. This guide describes the setting of two battery groups.
Set the system type.
Set temperature alarm parameters.
Set time and date.
Connect the battery branch:If the circuit breaker for batteries is available, set the circuit breaker for the battery rack or battery cabinet to ON.
Then set PMU parameters.
If the circuit breaker for batteries is not available, connect the cables Removed between two batteries.
Set the number, capacity and Install time of battery groups.
14
English中 文
2008-08-0653.6VDC 227VACLoad:0.2ABatt:0.0A
MAIN MENUStatusMaintenanceSettings
SettingsSystem SettingsAlarm SettingsAC Settings
ENT
ENT
ENT
ENT
Address:0Text:EnglishComm Mode: RS232Band:9600
Batt2 Shunt: YesDisp Contrast:3System Type:
TP48300/A
ENT
ENT
English中 文
2008-08-0653.6VDC 227VACLoad:0.2ABatt:0.0A
ENT
ENT
ENT
ENT
Batt SettingsBatt SelectionLVD Settings Charge
ENT
ENT ENT
Batt SelectionBatt String:1Cap 1:400Ah Cap:0Ah
ENT
ENT
ENT
ENT
English中 文
2008-08-0653.6VDC 227VACLoad:0.2ABatt:0.0A
ENT
ENT
ENT
ENT
Batt SettingsBatt TestTemp Coeff
ENT
Temp Comp Basis:Batt 1Temp Comp:80mV/0C
ENT
Low Temp Alarm:00CHigh Temp Alarm:500C
ENT
English中 文
2008-08-0653.6VDC 227VACLoad:0.2ABatt:0.0A
ENT
ENT
ENT
ENT
ENT
Date: 2008-08-08Time:09:10
ENT
MAIN MENUStatusMaintenanceSettings
MAIN MENUStatusMaintenanceSettings
MAIN MENUStatusMaintenanceSettings
SettingsSystem SettingsAlarm SettingsAC Settings
SettingsDC SettingsBatt SettingsAMB. Settings
SettingsDC SettingsBatt SettingsAMB. Settings
Batt2 Shunt: YesDisp Contrast:3System Type:
TP48300/A
Batt2 Shunt: YesDisp Contrast:3System Type:
TP48600B
Batt SelectionBatt String:2Cap 1:400Ah Cap 2:0Ah
Batt SelectionBatt String:2Cap 1:400Ah Cap 2:0Ah
Batt SelectionBatt String:2Cap 1:300Ah Cap 2:0Ah
Batt SelectionBatt String:2Cap 1:300Ah Cap 2:0Ah
Batt SelectionBatt String:2Cap 1:300Ah Cap 2:300Ah
Low Temp Alarm:00CHigh Temp Alarm:500C
Address:0Text:EnglishComm Mode: RS232Band:9600
Date: 2008-08-08Time:09:10
ENT
Batt SelectionInstall Date:2008-08-08
15
a
Set the AC circuit breaker to ON and repeat step 1.
b Power-on Check
Check whether the voltage of the LLVD fuse, battery fuse, and BLVD circuit breaker is proper using a multimeter. The rate voltage is 53.5 V and the range is between 44 V and 58 V. Check whether the panel display of the PMU is functional. If the voltage is improper or the panel display fails, contact professional personnel for troubleshooting or handle the problem by referring to the TP48600B Maintenance Guide.
Set the LLVD and BLVD circuit breaker to ON.
Set the AC input circuit breaker, LLVD circuit breaker, and BLVD circuit breaker according to actual conditions. Cut the cabling holes on the top of the cabinet according to the cabling conditions. Clear up the site, close and lock the cabinet door, and return the key to the administrator.
Insert the removed load power-off fuses into the
corresponding positions. Set the LLVD, BLVD circuit breaker to ON and repeat step 1.
Set the LLVD and BLVD circuit breaker manually to OFF. Then, check the load branches of the LLVD circuit breaker, BLVD circuit breaker, and battery fuse can be disconnected.
The mains supplies power only when the parameters related to the storage battery on the CPMU01 are correctly set. Otherwise, the storage battery may be damaged.
Appendix1. Monitoring Menu Structure
Appendix 1Main menu
Status
Rectifiers
Rectifiers ID
Output Voltage
Status
Major Alarm
End Time
Alarm SN
Alarm Level
Maintenance
Management Mode
Start
Rectifiers1-12
Automatic
Manual
FloatCharge
StandardTest
ON
OFF
Settings
System Settings
Address
Text
Communications Mode
Baud
Date
Time
Batt 2 Shunt
Display Contrast
System Type
IP Address
Subnet Mask
Alarm Level
Alarm Control
Relay Relate
Digital Alarm
Over Voltage
Under Voltage
Appendix 2
Upper limit
Lower limit
High Alarm
Generator Enable
Output Power
Discharge Depth
Temp OFF Enable
Start Temperature
Type
Power
Rectifiers Sleep
Best Efficient Points
Fast Charge
Alarm Type
Level
Audible Alarm
Clear History AlarmAlarm Type
Relate Relay
Active Alarm
History Alarm
Battery Test Result
Version Display
Output Current
Current Limit
Common Alarm
Alarm Name
Generation Time
Alarm SN
Alarm Level
Alarm Name
Generation TimeAlarm SN
Alarm Level
Alarm Name
Generation Time
Short Test
End Test
BoostCharge
AlarmSettings
ACSettings
DCSettings
BatterySettings
AMBSettings
Generator
Air-condition
GatewayEngineer Settings
Over Voltage
Under Voltage
Low Alarm
OFF Temperature
Modify PasswordInitialize Parameter
Rectifiers Mini Number On
Rectifiers Exchange Sleep
Generator Status
16
DI No
Mode
Set DI Name
Appendix 2
Battery Selection
LVD Setting
Charge
Battery Test
Temp Coefficient
Battery String
Capacity 1
Install Date
Float Charge
Current Limit
Auto Test Enable
TEMP Compensate Basis
BatterySettings
LLVD Enable
Boost Charge
Boost Charge Duration
Short Test
TEMP Compensate Factor
Battery High-TEMP Disconnect Enable
Low TEMP Alarm
Upper limit
Low limit
Cycle
Test End Voltage
Duration
Test Delay
Test End Voltage
Auto Test
17
Duration
BLVD Enable
LLVD
BLVD
Battery High-TEMP Disconnect TEMP
High TEMP Alarm
Capacity 2
2. CPM01 Menu ReferenceMain Menu Second-Level
MenuThird-LevelMenu
Fourth-LevelMenu
Parameter Value
Settings System Settings Address 3
Text English
Comm Mode RS232
Band 9600
Date 2001-01-01
Time 00 : 00
Batt2 Shunt Yes
Disp Contrast 3
System Type TP48600B
IP Address 192.168.0.1
Subnet Mask 255.255.254.0
Gateway 10.70.199.1
Eng Setting Modify PWD None
Init Para No
Rect Sleep No
Rect Exch Sleep 7 days
Rect Mini Num On 1 pieces
Best Effi Points 70%
Fast Charge No
Alarm Settings Alarm Level AC ON/OFF Serious
AC Volt Low/High Common
DC Volt Low/High Serious
Load Off Alarm Serious
Batt Off Alarm Serious
Batt Fuse Alarm Serious
Temp 1 Alarm Common
Humidity Alarm Common
Batt Temp Alarm Common
Door Alarm Common
Water Alarm Serious
Smoke Alarm Serious
Rect Fail Serious
Rect Protect Common
18
Main Menu Second-LevelMenu
Third-LevelMenu
Fourth-LevelMenu
Parameter Value
Settings Alarm Settings Alarm Level Rect Comm Fail Common
Charge Curr High Common
Digital 1 Common
Digital 2 Common
AC SPD Alarm Common
DC SPD Alarm Common
Digital 5 Common
Digital 6 Common
Digital 7 Common
Wire Alarm Serious
Generator Fail Serious
Load Fuse Alarm Serious
Digital Alarm DI No: 1 Mode High
Set DI Name Digital 1
DI No: 2 Mode High
Set DI Name Digital 2
DI No: 3 Mode High
Set DI Name AC SPD Alarm
DI No: 4 Mode High
Set DI Name DC SPD Alarm
DI No: 5 Mode High
Set DI Name Digital 5
DI No: 6 Mode High
Set DI Name Digital 6
DI No: 7 Mode High
Set DI Name Digital 7
Alarm Control Audible Alarm No
Cir Hist Alarm No
Relay Relate Alarm AC OFF
Relate Relay 1
AC Settings Over Volt 280 V
Under Volt 180 V
DC Settings Over Volt 58.0 V
Under Volt 45.0 V
19
Main Menu Second-LevelMenu
Third-LevelMenu
Fourth-LevelMenu
Parameter Value
Batt Settings Batt Selection Batt String 1
Cap 1 400Ah
Cap 2 0Ah
Install Date 2001-01-01
LVD Setting LLVD Enable Yes
BLVD Enable Yes
LLVD 44.0V
BLVD 43.0V
Charge Float 53.5V
Boost 56.5V
BC Duration 60 days
Current limit 0.10C10
Batt Test Auto Test Auto Test Enable Disch Test
Cycle 120 days
Test End Volt 1.9V
Duration 10 hours
Test Delay 14 Days
Short Test Test End Volt 45.0V
Duration 60 min
Temp Coeff Temp Comp Basis Batt 1
Temp Comp 80mV/0C
BHTD Enable No
BHTD Temp 530C
Low Temp Alarm 00C
High Temp Alarm 500C
Upper Limit 800C
Lower Limit -200C
AMB Settings Upper Limit 800C
Lower Limit -200C
High Alarm 500C
Low Alarm 00C
Generator Enable No
Output Power 12.5KW
Discharge Depth 30%
20
Main Menu Second-LevelMenu
Third-LevelMenu
Fourth-LevelMenu
Parameter Value
Settings Generator Temp OFF Enable Yes
Start Temp 450C
OFF Temp 290C
Air-condition Type Single-Phase
Power 1.0kW
Status Rectifiers
Active Alarm Major Alarm*
Common Alarm *
History Alarm
Batt Test Result No Record
Version Display V100R**************
Generator Generator 1 Null
Generator 2 Null
Maintenance Mgmt Mode Auto
Manual
Start FC
Std Test
Short Test
End Test
BC
Rect1 Rect1 ON
Rect2
Rect3
Rect4
Rect5
Rect6
Rect7
Rect8
Rect9
Rect10
Rect11
Rect12
21
TP48600B Power System Parameter List
Item Setting Bound Factory Setting 1st Rev Date Sign 2st Rev Date Sign
★Battery String 0~2 1
★Battery Cap1 30~1000 400Ah
★Battery Cap2 30~1000 0Ah
Date 0000-00-00~9999-12-31
2001-01-01
Time 00:00~23:59 00:00
LLVD BLVD~DC Under Volt
44.0V
BLVD 35V~LLVD 43.0V
Battery Float 43.20V~57.6V 53.5V
Battery Boost 43.20V~57.6V 56.5V
Rect Sleep Yes/No No
LLVD Enable Yes/No Yes
BLVD Enable Yes/No Yes
Current Limit Coefficient
0.05~0.25 0.1
Battery High Temp Alarm
-500C~1000C 500C
Environment High Alarm
-500C~1000C 500C
22
Shenzhen Huawei Agisson Electric Co., Ltd.Administration Building, Huawei Technologies Co., Ltd.,
Bantian, Longgang District, Shenzhen, PRCPostal Code: 518129
www.huawei.com