3 - ACU User Guide Rev F

Embed Size (px)

Citation preview

  • 7/24/2019 3 - ACU User Guide Rev F

    1/56

    DESCRIPTION USERS GUIDE

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    1(56)

    ACU for NetSure 201, 501, 701 and 801Power Supply Systems

    Emerson Network Power Energy Systems AB 2008 All rights reserved

  • 7/24/2019 3 - ACU User Guide Rev F

    2/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    2(56)

    The contents of this document are subject to revision without notice dueto continued progress in methodology, design, and manufacturing.

    Emerson Network Power Energy Systems ABSE 141 82 Stockholm

    Sweden

    Tel. +46 8 721 6000 Fax. +46 8 721 7177 www.emersonenergy.com

  • 7/24/2019 3 - ACU User Guide Rev F

    3/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    3(56)

    Contents

    1 General 4

    1.1 Alarms 41.2 Input/output terminals 5

    2

    Software functions 8

    2.1 Control functions 82.2 Supervision functions 182.3 Alarm management 202.4 Site status 212.5 SW Download 212.6 Setting Download 24

    3 Handling the ACU from the LCD screen 27

    3.1 Operation panel 273.2 Menu tree structure 28

    4

    Handling the ACU through the Web interface 35

    4.1 Web interface requirements 354.2 Connection to ACU web server 364.3 Login 404.4 Homepage introduction 414.5 Devices 424.6 Alarms 434.7 Settings 444.8 Maintenance 534.9 Site map 55

    5 Abbreviations used in this document 56

  • 7/24/2019 3 - ACU User Guide Rev F

    4/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    4(56)

    1 General

    ACU is an advanced control unit used in DC power supply systemsNetSure 201, 501, 701 and 801. It communicates with the other units of thepower supply system like rectifiers, LC and SM modules (SM IO, SM BAT and

    SM AC) and manages alarm handling, data processing, voltage control, etc.

    The ACU can monitor the power system locally and from a remote manage-ment system.

    1.1 Alarms

    The control- and the rectifier-units are equipped with LEDs that provide rele-vant information regarding system- and unit-status, and guide the servicetechnician to the right unit in case of trouble.

    The alarm events are classified into different alarm categories. Different alarmcategories have different visual/audible alarms and alarm callback activities.

    Table 1. ACU alarm categories.

    Alarm Category Red LED YellowLED

    AlarmBuzzer

    AlarmCallback

    Remark

    Critical Alarm ON ON Yes Callback func-tion enabled

    Major Alarm ON ON Yes Callback func-tion enabled

    ObservationAlarm

    ON OFF No

    No Alarm OFF OFF OFF No

    The audible alarm is silenced if the user presses any key on ACU, if the faultthat triggers the alarm is cleared or after 10 min (settable). The audible alarmcan be disabled from a menu in the LCD display.

    The alarm LED stops emitting light if all the faults that trigger the alarm are

    cleared.

  • 7/24/2019 3 - ACU User Guide Rev F

    5/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    5(56)

    1.2 Input/output terminals

    RS 232 Port (for EEM)

    Ethernet Port

    RS 485 Port

    RS 232 (console port)

    Input/output terminals

    Figure 1. ACU with connection board.

    Eight configurable digital inputs are provided on the connector board placedabove or beside the ACU. The connections to the connector board are de-scribed in the INSTALLATION INSTRUCTIONS for the respective system.

    Eight potential free relay outputs are provided on the connector board. Thereare both closing and opening contacts on each output.

    Note: When either the ACU or the connection board is disconnected from theback plane board the output terminals have no connection to the relays.

    Three of the relays are default configured and mapped to alarms of the follow-ing alarm severity:

    Relay 1 Opened: critical alarm (Critical) indicating that the power systemscontinued operation may be at risk and that the supply of the priorityloads is, or might soon be affected. Immediate action is required.Closed: normal operation.

    Relay 2 Opened: normal operation.Closed: alarm (Major) indicating a failure that requires action whenconvenient from the point of view of workload.

    Relay 3 Opened: normal operationClosed: alarm (Observation), signalling that the power system doesnot perform to its maximum but that the loads are not affected. No

    action is required.

  • 7/24/2019 3 - ACU User Guide Rev F

    6/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    6(56)

    1.2.1 Communication with SM modules

    The ACU acquires data from SM modules (SM DU, SM IO, SM BAT and SMAC) through an RS485 port on the connection board. See Figure 1.

    1.2.2 Web communication

    The Ethernet port of ACU is used for Web communication via LAN or Internet.It can also be used for direct connection to a PC.

    1.2.3 Remote communication with management systems

    LAN

    PSTN or GSM

    Crossed type

    Ethernet cable Modem

    Regular Ethernet

    cable

    Regular DSUB

    RS232 cable

    ACUManagement

    computer

    Regular Ethernet

    cable

    Management

    computerManagement

    computerManagement

    computer

    Modem

    Figure 2. Remote communication to the ACU.

    The ACU supports the EEM, RSOC and SOC/TPE protocols. These protocolsare used to communicate with a power management system.

    For the communication, an RS232 port is provided at the connector board fordirect connection or via a PSTN modem. This port has two DB9 contacts, oneat the front of and one inside the unit. See Figure 1. Default setting of the port:38400 bps, 8 data bits, 1 stop bit, no parity and no data flow control.

    As an alternative, the Ethernet port can be used for direct or LAN connection.

    1.2.4 SNMP communication

    SNMP communication can be established via LAN.

    Description of SNMP

    SNMP is a technology used for network management. The technology isbased on implementing an information base called MIB (Managed InformationBase). This MIB contains parameters that are interesting from a managementperspective. All LAN connected equipment that support SNMP shall also sup-port a default MIB called MIB-II.

    The SNMP Agent responds to requests received via the SNMP protocol andalso actively sends traps to a specified manager when certain MIB values

  • 7/24/2019 3 - ACU User Guide Rev F

    7/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    7(56)

    change state. This is used to actively inform a manager when an alarm situa-tion is recognised.

    The PCU supports MIB-II and Emersons power MIB, rev B. Contact EmersonEnergy Systems for more information.

    Figure 3. Emerson power MIB layout.

    1.2.5 Console port

    The RS232 console port is for factory use only.

  • 7/24/2019 3 - ACU User Guide Rev F

    8/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    8(56)

    2 Software functions

    2.1 Control functions

    Note: All tables refer to do cum ent Table of set values: 3/1532 BMP 903 050.

    2.1.1 System voltage

    The set voltage of the rectifiers is configurable from the ACU.

    In case temperature compensated battery voltage control is activated, thevoltage will be adjusted in accordance with the battery temperature.

    2.1.2 Temperature compensated battery voltage

    To compensate for some of the negative effects on batteries caused by high

    ambient temperatures, this function can be used. However, it requires connec-tion of a temperature sensor.

    The function adds a correction term related to the temperature of the batteries tothe nominal value of the system voltage. The degree of regulation can be set.

    The maximum influence, delta U of the function, is 2 V from the nominal sys-tem voltage.

    The temperature compensation is disabled if there is a rectifier communicationfailure, DC over/undervoltage or a low voltage disconnection.

    TnomTlower

    Temp comp coeff

    (mV/C/string)

    U (V)

    Batt.Temp(C)

    0

    Tupper

    Unom

    Ulow

    50

    100

    200

    Uhigh

    Umax2 V

    Figure 4. Temperature compensated voltage control.

    Unom: Nominal voltage (value at nominal temperature). See Table 2.

    Uhigh: Upper voltage level where compensation ends, 56.0 V.

    Ulow: Lower voltage level where compensation ends, 47.2 V.

  • 7/24/2019 3 - ACU User Guide Rev F

    9/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    9(56)

    Tnom: Nominal temperature, 20C (no compensation is done at this tem-perature).

    Tupper: Upper temperature where compensation ends, +40C.

    Tlower: Lower temperature where compensation ends, 0C.

    Table 2. Temperature compensated voltage control.

    Table of set valueSetting Description

    Section Index

    Nominal Voltage Float charge voltagelevel.

    2.1.1 3

    Temp Compensation Center Nominal tempera-ture for temperature

    compensation.

    2.1.3 2

    Compensation coefficient Number of mV/degCthat the voltage will

    be changed.

    2.1.3 3

    2.1.3 Battery boost charging

    Boost charging voltage is used to reduce the charging time after a mains fail-ure and to equalise the charge level of the batteries. The charging functioncan be initiated cyclically, automatically or manually.

    The battery manufacturers instructions for boost charging shall be observed.

    Figure 5. Voltage course on mains failure and automatic boost charging.

  • 7/24/2019 3 - ACU User Guide Rev F

    10/56

  • 7/24/2019 3 - ACU User Guide Rev F

    11/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    11(56)

    Table of set valueSetting Description

    Section Index

    Cyclic BC Interval Time between cyclicboost charges.

    2.1.3 48

    Cyclic BC Duration Duration of cyclic boostcharge.

    2.1.3 49

    Battery Current Limit Charge current limita-tion level.

    2.1.3 50

    Current Limit Enable Enabling of batterycharge current limita-

    tion.

    2.1.3 51

    Over current Setpoint Alarm level for batterycharge current.

    2.1.3 52

    2.1.4 Very high battery temperature handling

    If the battery temperature exceeds the very high battery temperature alarm level,the system voltage will be reduced to the defined voltage for this function.

    Table 4. Very high battery temperature handling.

    Table of set valueSetting Description

    Section Index

    Very high temperature limit Alarm level for veryhigh battery tem-

    perature.

    2.1.3 4

    Very high TemperatureVoltage Setpoint

    Voltage level duringvery high battery

    temperature.

    2.1.3 7

    2.1.5 Battery test

    The battery test has four modes, short test (requires two battery shunts), ACfails test (at mains failure), planned time test and stable current test.

    Battery tests can be started either manually or automatically at scheduled in-

    tervals for regular test of battery status.

    For manual battery tests as well as for AC fail tests and cyclic battery tests, thefollowing parameters must be set: End voltage, Test time and Battery capacitydischarge limit.

  • 7/24/2019 3 - ACU User Guide Rev F

    12/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    12(56)

    Figure 6. Battery test diagram.

    The battery tests follow the procedure described below:

    In time test mode, the output voltage of the rectifiers is reduced to the testvoltage so that only the batteries power the load. If the batteries fail, therectifiers will power the load.

    In stable current test mode, the output voltage of the rectifiers is reducedso that the batteries give the preset test current to the load.

    This test will continue until one of the following four situations occurs:

    The preset test time, see Figure 6, expires. The battery has passedthe test.

    The battery voltage drops below the preset end voltage level (Uend)(Figure 6). The battery has notpassed the test and the test is inter-rupted. An alarm Bad battery is issued in the system.

    The battery capacity drops below the preset Test end battery capacity.The battery has not passed the test and the test is interrupted.An alarm Bad battery is issued in the system.

    After the test, the output voltage of the rectifiers will increase again so thatthe rectifiers feed the plant and charge the batteries.

    The ACU will record the battery test start/end time, battery test voltageand battery remaining capacity in the battery test log. 10 groups of batterytest data can be recorded. The user can query the test log from the ACUthrough the Web interface or via EEM.

    If the AC Fail Test is enabled, the test log will also be issued at a mainsfailure. The set values for test time, end voltage and end capacity will bethe same as for Planned test. Should any of these values be exceededduring the mains failure the alarm Bad battery is issued in the system.

    Test Voltage LevelU test

  • 7/24/2019 3 - ACU User Guide Rev F

    13/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    13(56)

    Table 5. Battery test.

    Table of set valueSetting Description

    Section Index

    Nominal Voltage Float charge voltage

    level.

    2.1.1 3

    Planned Test Enabled Enabling of planned(scheduled) battery

    test.

    2.1.3 13

    AC Fail Test Enabled Enabling of batterytest during mains

    fail.

    2.1.3 14

    Test Voltage Level Rectifier voltagelevel during battery

    test.

    2.1.3 15

    Test End Time End time for batterytest.

    2.1.3 16

    Test End Voltage Voltage level foractivating the Bad

    Battery alarm.

    2.1.3 17

    Test End Capacity 2.1.3 18

    Pre-BC Enabled Enabling of a boostcharge before the

    battery test isstarted.

    2.1.3 19

    Constant current test Enabling of constantcurrent test.

    2.1.3 20

    Constant current test current Battery dischargecurrent during bat-

    tery test.

    2.1.3 21

    Number of schedule Test peryear

    Number of plannedtest per year.

    2.1.3 22

    Planned Test1 Month, day andhour (mm-dd hh) ofwhen the planned

    test will be started.

    2.1.3 23

    Planned Test2 See above. 2.1.3 24

    Planned Test3 See above. 2.1.3 25

    Planned Test4 See above. 2.1.3 26

    Planned Test5 See above. 2.1.3 27

    Planned Test6 See above. 2.1.3 28

    Planned Test7 See above. 2.1.3 29

    Planned Test8 See above. 2.1.3 30

    Planned Test9 See above. 2.1.3 31

  • 7/24/2019 3 - ACU User Guide Rev F

    14/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    14(56)

    Table of set valueSetting Description

    Section Index

    Planned Test10 See above. 2.1.3 32

    Planned Test11 See above. 2.1.3 33

    Planned Test12 See above. 2.1.3 34

    Record threshold Voltage level whena new entry in the

    test log will bestored.

    2.1.3 35

    Short Test Enabling of shorttest.

    2.1.3 36

    Short Test Cycle Time between shorttests.

    2.1.3 37

    Max Diff Current For Short

    Test

    Alarm level for short

    test.

    2.1.3 38

    Short Test Duration Time that the shorttest will run.

    2.1.3 39

    2.1.6 Backup control (LVD)

    To prevent serious damage to the batteries during a long mains failure theloads can be disconnected by voltage-, or time-control, if LVD contactors areincluded. The software supports load disconnection in to two steps. Both LVD

    contactors can be set individually to voltage or time disconnect. Load discon-nection can be activated at AC mains failure only.

    Load reconnection is made automatically on the return of AC mains.

    2.1.6.1 Voltage controlled disconnection

    When the set voltage level is reached, the backup batteries are disconnectedfrom the selected loads.

    2.1.6.2 Time controlled disconnection

    When the set time has elapsed, the backup batteries are disconnected fromthe selected loads.

    2.1.6.3 High Temperature Disconnection

    When the High Temperature Disconnection (HTD) point is reached, thebackup batteries are disconnected from the selected loads.

  • 7/24/2019 3 - ACU User Guide Rev F

    15/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    15(56)

    Table 6. LVD.

    Table of set valueSetting Description

    Section Index

    LVD Need AC Fail When set to Yes, none

    of the LVD will be dis-connected before thereis a Mains Failure. Thissetting is only valid in

    voltage mode.

    2.1.5 1

    HTD Point Level for the high tem-perature disconnection.

    2.1.5 2

    HTD Reconnect Point Level for reconnectionafter high temperature

    disconnection.

    2.1.5 3

    HTD Temp Sensor Temperature sensorthat will be used for

    high temperature dis-connection.

    2.1.5 4

    LVD Enabled Enabling of an individ-ual LVD.

    2.1.6 1

    LVD Mode Mode for LVD discon-nection.

    2.1.6 2

    LVD Voltage Voltage level for dis-connection.

    2.1.6 3

    LVD Time Time between mainsfailure and LVD dis-connection.

    2.1.6 4

    LVD reconnect voltage Voltage level for re-connection. This volt-

    age is comparedagainst the rectifier

    output voltage.

    2.1.6 5

    LVD reconnect delay Time between that thereconnection voltage isreached and reconnec-

    tion.

    2.1.6 6

    LVD dependency Dependency betweendifferent LVD. The LVD

    that is depending onanother LVD will not be

    disconnected beforethat LVD.

    2.1.6 7

    High Temp Disconnect Enabling of high tem-perature disconnectionfor an individual LVD.

    2.1.6 8

  • 7/24/2019 3 - ACU User Guide Rev F

    16/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    16(56)

    2.1.7 Energy management

    Energy management is an advanced function, which can save money for cus-tomers. It includes:

    2.1.7.1 Energy saving

    Reduces the mains energy consumption during high tariff periods.

    Can make the power consumption rate lower than a given limit.

    2.1.7.2 Rectifier redundancy

    The rectifier redundancy function maintains a configured redundancy level byswitching on/off rectifiers depending on the actual load on the system.

    Which rectifiers that are switch on/off is cycled periodically.

    The rectifier redundancy is calculated according to the following formula,Redundancy = (((NoOfRectOn * RectCap) Load ) / RectCap) *100.

    NoOfRectOn => Number of rectifiers turned on.RectCap => Rectifier rated capacity.Load => Load current.

    When the Redundancy is below the Min Redundancy setting one rectifier willbe turned on. If Redundancy is very much below the Min Redundancy settingall rectifiers will be turned on.

    When the Redundancy is above the Max Redundancy setting one rectifier willbe turned off.

    Table 7. Rectifier redundancy.

    Table of set valueSetting Description

    Section Index

    Redundancy Enabled Enabling of the rectifierredundancy.

    2.1.2 6

    Pre-Currlmt for Redund Enb Enabling of currentlimitation before a recti-

    fier is turned on.

    2.1.2 7

    Min Redundancy Level for turning onrectifier.

    2.1.2 8

    Max Redundancy Level for turning offrectifier.

    2.1.2 9

    Switch-off Delay Delay between turningon a rectifier and turn-ing off another rectifier.

    2.1.2 10

    Cycle Activation Hour Hour of the day whenthe cycling of rectifiers

    will take place.

    2.1.2 11

    Cycling Period Time between rectifiercycling.

    2.1.2 12

  • 7/24/2019 3 - ACU User Guide Rev F

    17/56

  • 7/24/2019 3 - ACU User Guide Rev F

    18/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    18(56)

    2.2 Supervision functions

    2.2.1 Fuse (circuit breaker) alarms

    If a distribution or battery fuse (circuit breaker) that has a load connected hasblown (tripped) due to overcurrent or short-circuit or has been removed(manually tripped), alarm is initiated.

    2.2.2 Voltage alarms

    Two overvoltage and two undervoltage levels are supervised.

    Table 9. Voltage alarms.

    Table of set valueSetting Description

    Section Index

    Under-voltage 1 Level Level for activation of undervoltage 1 alarm. Deactivation

    level is 0.5V higher.

    2.1.1 4

    Under-voltage 2 Level Level for activation of undervoltage 2 alarm. Deactivation

    level is 0.5V higher.

    2.1.1 5

    Over-voltage 1 Level Level for activation of overvoltage 1 alarm. Deactivation

    level is 0.5V lower.

    2.1.1. 11

    Over-voltage 2 Level Level for activation of over

    voltage 2 alarm. Deactivationlevel is 0.5V lower.

    2.1.1 12

    2.2.3 Battery temperature supervision

    The battery temperature can be supervised by means of a temperature sensormounted on one battery cell.

    Alarms are provided in two steps in case of high temperature.

    There is also an alarm at low battery temperature.

    To activate the alarms the temperature sensor must be enabled.

    Table 10. Battery temperature supervision.

    Table of set valueSetting Description

    Section Index

    Very High Temperature limit Level for activationof very high tem-

    perature alarm. De-activation level is

    1C lower.

    2.1.3 4

  • 7/24/2019 3 - ACU User Guide Rev F

    19/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    19(56)

    Table of set valueSetting Description

    Section Index

    High Temperature limit Level for activationof high temperaturealarm. Deactivation

    level is 1C lower.

    2.1.3 5

    Low temperature limit Level for activationof low temperaturealarm. Deactivationlevel is 1C higher.

    2.1.3 6

    Temp Sensor Enabled Enabling of tem-perature alarms.

    2.1.3 8

    2.2.4 Ambient temperature supervision

    Alarms are provided in case of high or low ambient temperature.

    To activate the alarms the temperature sensor must be enabled.

    Table 11. Ambient temperature supervision.

    Table of set valueSetting Description

    Section Index

    High Ambient TemperatureLimit

    Level for activationof high temperaturealarm. Deactivation

    level is 1C lower.

    2.1.1 8

    Low Ambient TemperatureLimit

    Level for activationof low temperaturealarm. Deactivationlevel is 1C higher.

    2.1.1 9

    Temp Sensor Enabled Enabling of tem-perature alarms.

    2.1.1 10

    2.2.5 Mains supervision

    In case of mains failure from all rectifiers, the ACU interprets it as a generalmains failure. If the rectifier is of a type that is not fed from the DC side, thenthe ACU will consider a communication failure with all rectifiers as a generalmains failure.

    2.2.6 Extended mains supervision via SM-AC

    Detailed supervision of AC supplies from mains and diesel generator can beimplemented with SM-AC units. See documents for the SM-AC unit.

  • 7/24/2019 3 - ACU User Guide Rev F

    20/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    20(56)

    2.2.7 Rectifier supervision

    In case of mains or rectifier failure, alarms are sent to the ACU.

    2.2.8 Periodic maintenance

    The ACU can be configured to give alarm at a preset interval to indicate theneed for system maintenance.

    The maintenance alarm will be deactivated when the alarm time has passedor when deactivated manually.

    Table 12. Periodic maintenance.

    Table of set valueSetting Description

    Section Index

    Maintenance Alarm Time Time until the main-tenance alarm is

    deactivated auto-matically.

    2.1.1 6

    Maintenance Interval Time between acti-vation of the main-

    tenance alarm.

    2.1.1 7

    2.3 Alarm management

    2.3.1 Alarm severityThe severity of all predefined alarms can be set.

    2.3.2 Incoming alarms

    The digital alarm inputs can be configured as to name, severity and polarity.

    2.3.3 Outgoing alarms

    The output alarm terminals can be configured by selecting the alarms withcombinations in between them.

    2.3.4 Security

    All settings of the ACU can be password protected. There are four different levelsof passwords that can be entered via the LCD display and the Web interface.

    New users with their individual authority level can be created by the adminis-trator via the Web interface. The ACU has a default administrator with user IDadmin (not changeable) and the password 1 (changeable via the Web inter-face).

  • 7/24/2019 3 - ACU User Guide Rev F

    21/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    21(56)

    Privilegelevel

    User group User authority

    Level A Browser All users can browse power information without anywriting permission.

    Level B Common

    user

    Set the parameters, control and operate the DC

    Power System

    Level C Engineer Browsing, control, modifying parameter, downloadingconfiguration file, but except updating application anOS and modifying, adding, deleting user information(user name, user level, password).

    Level D Administrator Full access that include updating application an OSand modifying, adding, deleting user information(user name, user level, password)

    2.4 Site status

    The software presents detailed information on measured data, alarms, alarmhistory, equipment data and site inventory.

    2.5 SW Download

    The PC software, ACU SW Download Tool, is needed to run the SW download.

    Before the ACU SW Download Tool is started the PC will need to be con-nected to the ACU, see section 4.2 for details.

    Note! Do not power off the ACU or interrupt the Ethernet connection dur-ing the download.

    Follow these steps to run the ACU SW Download Tool:

  • 7/24/2019 3 - ACU User Guide Rev F

    22/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    22(56)

    1. Start the ACU SW Download Tool by double clicking theACU_SW_Download_R2A.exe file.

    2. Select or enter the IP address of the ACU and click OK.

    3. Select the SW Package to download and click Open.

  • 7/24/2019 3 - ACU User Guide Rev F

    23/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    23(56)

    4. When connection to the ACU is verified click Nextto start the download.

    5. The download process will run automatically until the ACU is up andrunning. This will take about 5-10min.

    6. When the download is finished click the Closebutton to exit the ACUSW Download Tool.

  • 7/24/2019 3 - ACU User Guide Rev F

    24/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    24(56)

    2.6 Setting Download

    The PC software, ACU SW Download Tool, is needed to run the settingdownload.

    Follow these steps to run the ACU SW Download Tool:

    1. Start the ACU SW Download Tool by double clicking theACU_SW_Download_R2A.exe file.

    2. Select or enter the IP address of the ACU and click OK.

  • 7/24/2019 3 - ACU User Guide Rev F

    25/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    25(56)

    3. Change the Files of typeto Parameter and select the SettingParam.runfile.The file must be named SettingParam.run.

    4. Click Open.

  • 7/24/2019 3 - ACU User Guide Rev F

    26/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    26(56)

    5. When connection to the ACU is verified click Nextto start the download.

    6. The download process will run automatically until the ACU is up andrunning. This will take about 5-10min.

    7. When the download is finished click the Closebutton to exit the ACU

    SW Download Tool.

  • 7/24/2019 3 - ACU User Guide Rev F

    27/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    27(56)

    3 Handling the ACU from the LCD screen

    The display is graphical. It provides extensive information regarding systemstatus and allows system parameters and settings to be checked and ad-justed.

    Only a person who is adequately trained and is authorized may change thevalues set in the ACU. The value settings can be made by using the keys andthe display of the ACU.

    3.1 Operation panel

    The ACU has an LCD screen with backlight, function keys and indicator LEDs.For fixing the unit to the cabinet slot there is a handle with a locking latch.

    O p e r a t i o n i n d i c a t o r

    A la rm in d ic a to r

    P r o t e c t i o n i n d i c a t o r

    L C D

    F u n t i o n k e y s

    H a n d le w it h la t c h

    Figure 7. ACU front panel.

    3.1.1 LEDs

    LEDNormalStatus

    AbnormalStatus

    Cause

    Operation Indicator(Green)

    ON OFF No Power Supply

    Protection Indicator(Yellow)

    OFF ONDC Power has an ob-

    servation alarm

    Alarm Indicator(Red)

    OFF ONDC Power has a majoralarm or critical alarm.

  • 7/24/2019 3 - ACU User Guide Rev F

    28/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    28(56)

    3.1.2 Function keys

    The keys are used to move through the display menus.

    KeyName of

    KeyFunctions

    ESCReturn

    Key

    Press this key to back to pre-vious menu or cancel a set-ting of a parameter.

    ENTEnterkey

    Press this key to go to nextmenu, highlight editable areafor parameter setting or vali-date the change made to aparameter setting.

    Press ESC and ENT togetherto reset ACU

    Up

    Down

    Pressorto scroll

    through the menus.

    Left

    Right

    Pressorto change the

    value of a parameter. In Initial

    Screen, pressorto

    adjust the contrast of LCD.

    These four arrow keys can beused to change the value of a

    parameter:Pressor to move

    the cursor to the parameter to

    be changed and pressor

    to change the value of a

    parameter.

    Note: The keypad sound can be set on/off from the display menuParameter Set/System Param/Keypad Sound.

    3.2 Menu tree structure

    3.2.1 ACU initialising screen

    After the ACU starts up its LCD display, the following screen will offer the userto select language. The user can select between English and a local language

    in the screen by pressing and.

    SpanishEnglish

    When pressingENT the default main screen will appear.

    Note: If no key has been pressed for 30 seconds, the default screen willappear automatically.

  • 7/24/2019 3 - ACU User Guide Rev F

    29/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    29(56)

    3.2.2 Default main screen

    2005-08-20

    53.5 V

    Auto No Alarm23 A

    Float Charge

    15:18:25

    53.5 V

    Auto No Alarm

    23 A

    Float Charge

    The screen alters between date and time:

    ESC ENT

    ESC ENT

    Figure 8. Default main screen.

    The information is dependent on the configuration information such as theequipment Type, signal ID and display location.

    Pressorto scroll.

    Pressandand ESC together to log out (The password will be invalid).

    Pressorto change the contrast of the LCD.

    Press ENT and ESC together to reset the ACU.

    Press ENT to enter the main menu.

    Press ESC once to see the ACU serial number and software revision.

    Press first ESC and then ENT twice to see the configuration revision.(For example EMEA_2_R2A)

  • 7/24/2019 3 - ACU User Guide Rev F

    30/56

  • 7/24/2019 3 - ACU User Guide Rev F

    31/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    31(56)

    Figure 10. Main menu tree.

    To reach the Maintain or Parameter Set menu, a password is required.

  • 7/24/2019 3 - ACU User Guide Rev F

    32/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    32(56)

    3.2.4 Running Info menu

    Figure 11. Running Info Menu tree.

    In this menu, equipment status information, active alarms and alarm historycan be selected. There are 50 active alarm information screens in ActiveAlarm Menu and can be displayed. There are 400 History Alarm and can bedisplayed in History Alarm Menu.

  • 7/24/2019 3 - ACU User Guide Rev F

    33/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    33(56)

    Under sub-menu Site Inv the Site Inventory page displays information aboutthe units connected to the ACU. The page is automatically updated when unitsare exchanged or when new units are connected to the system.

    Note: In the site inventory the rectifiers are numbered (1,2,3.) accordingto their order of serial numbers. By moving a rectifier to another placein the subrack its position and order number can be made equal.

    3.2.5 Maintenance menu

    Figure 12. Maintenance Menu tree.

    After entering a password of level B, or higher (see item 2.3.4), the user can

    control the following functions manually:

  • 7/24/2019 3 - ACU User Guide Rev F

    34/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    34(56)

    Note: Some settings can only be reached after setting the ACU System toMan state (Parameter Set/ACU System/Auto-Man State).

    Note: Be careful when using the low voltage disconnect control function(LVD Ctrl) that may disconnect the load!

    3.2.6 Parameter Set menuAfter entering a password of level B, or higher (see item 2.3.4), the user canset parameters according to the document TABLE OF SET VALUES3/1532-BMP 903 050.

    3.2.6.1 Alarm Param

    From these menus it is possible to configure alarm categories. Furthermorethe audible alarm can be blocked and the alarm history can be cleared.

    3.2.6.2 System settings

    System parameters like language, date, time, IP address, subnet mask, de-fault gateway, Reload Config (reset to default) and Keypad Sound are set inthese menus.

  • 7/24/2019 3 - ACU User Guide Rev F

    35/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    35(56)

    4 Handling the ACU through the Web interface

    The ACU is equipped with a web server with a default IP address 192.168.0.1.The ACU web server can be connected to a PC:

    directly by using a crossedtype network cable

    through a LAN

    through a WAN (For safety reasons, it is not recommended to connectthrough the Internet)

    The ACU is accessed through the Ethernet port at the front of the connectingunit. See Figure 13.

    LAN/WAN

    Crossed typeEthernet cable

    Regular Ethernet cable

    ACULaptop or PC wit hMS Internet Explorer

    Regular Ethernetcable

    Laptop or PC with

    MS Internet Explorer

    Figure 13. Remote communication to the ACU.

    4.1 Web interface requirements4.1.1 Hardware

    Computer/processor: 486DX/66 MHz or higher processor.

    Network card.

    Ethernet network cable

    Crossed Ethernet network cable (necessary only when direct connectionis used).

  • 7/24/2019 3 - ACU User Guide Rev F

    36/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    36(56)

    4.1.2 Software

    Web browser Internet Explorer version 5.0 or later.

    If you have an earlier-version web browser installed, download the latest ver-sion from http://www.microsoft.com and follow the instructions to install thenew browser.

    For information about available-memory requirements and hard-drive spacerequirements, see system requirements for the chosen web browser.

    4.2 Connection to ACU web server

    Note: PC settings may differ depending of operative system. The examplesbelow are from Windows 2000.

    4.2.1 Direct connection

    This procedure is highly recommended for installation.

    Connect the computer to the ACU directly if they are placed maximum 15 me-tres from each other. Follow the steps described below to connect them:

    1. Check that your computer is equipped with a network card.

    2. Connect the computer to the ACU by using a crossed type network cable.Connect one cable connector to the network card on your computer.Connect the other cable connector to the Ethernet port placed at the frontof the connecting board.

    3. Check the IP address and the subnet mask of the ACU web server in thedisplay menu Parameter set/System param/IP Address.

    Default settings:IP address: 192.168.0.1Subnet mask: 255.255.255.0

    4. Open the Control Panel/ Network and Dial-up Connectionsof your com-puter.

    Note: In order to return to the original configuration, note down the parame-ter settings before modifying them.

  • 7/24/2019 3 - ACU User Guide Rev F

    37/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    37(56)

    5. Select the network connection and open its Properties under File in thetoolbar to pop up the following screen:

    6. Select the Internet Protocol (TCP/IP) and click Properties.

  • 7/24/2019 3 - ACU User Guide Rev F

    38/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    38(56)

    7. Click the circle Use the following IP address:

    8. Set an IP address of the PC. It should be one number higher orlower than the ACU web servers IP address.The subnet mask should be the same as the ACU.

    Example:

    ACU: IP address is: 192.168.0.1subnet mask is: 225.225.225.0

    The PC should be set to:IP address: 192.168.0.2subnet mask: 225.225.225.0

    It is possible to check and change the ACU web servers IP address and sub-net mask in the display menuParameter set/System param/IP Address.

    9. Click OK in this and the next screen.

    10. Click Back in the screen Network and Up-up Connectionsto return to theControl Panel.

    11. Open Internet Options in theControl Panel.

    12. Select the tab Connections and click the circle Never dial a connection.

    13. Click the button LAN Settings.

    Click here

  • 7/24/2019 3 - ACU User Guide Rev F

    39/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    39(56)

    14. Uncheck the box Use a proxy server for your LAN and click OK to finishthe LAN setting.

    4.2.2 Connecting via LAN or WAN

    Note: For safety reasons, it is not recommended to connect to the ACU web

    server through the Internet (although it is possible).

    1. Connect a standard network cable between the Ethernet port placed at thefront of the connecting board and a LAN outlet.

    2. Check that your computer is equipped with a network card and is con-nected to your LAN and/or WAN (via a standard network cable).

    3. Check that your services, protocols and adapters are correctly installedand configured. If you are not sure how your computer is to be installedand configured, contact your network administrator for advice. The net-work connection to be used is an ordinary TCP/IP (Internet) connection.

    4. Connect to the ACU web server by entering the Web servers IP addressor domain name. Use the settings that were made in the installation.

    5. It is possible to change the web servers IP address in display menuPa-rameter set/System param/IP Address.

    Uncheck

    here

  • 7/24/2019 3 - ACU User Guide Rev F

    40/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    40(56)

    4.3 Login

    Note: The ACU software needs Internet Explorer version 5.0, or later.

    1. To log in the ACU, double-click the icon of Internet Explorer to run the

    software.

    2. Type the IP address of the ACU and press ENT.The following Web interface will pop up for ACU information (includingsoftware and configuration version), selecting the homepage languageand login.

    Figure 14. Login page.

    3. Enter the username (default: admin) and password (default: 1) to log in tothe ACU, and the following homepage screen will show.

    configurationversion

  • 7/24/2019 3 - ACU User Guide Rev F

    41/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    41(56)

    4.4 Homepage introduction

    Figure 15. ACU Home page.

    In the Homepage screen, the left part displays the NetSure type number,the menus of Devices, Alarms, Settings, Maintenance, Query, Sitemap and at the bottom date, and time.

    The top right part displays (by default) the system status. Three buttons forSample, Control and Setting are used to open different sub-pages.

    The alarm survey is displayed in the middle of the screen. It can be hidden byclicking the arrow on top of it and set for automatic popup at an alarm bychecking the Auto popup square.

    A status bar is displayed at the bottom of the screen.

    Click here to hidethe alarm survey

  • 7/24/2019 3 - ACU User Guide Rev F

    42/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    42(56)

    When data for a sub menu is transferred from the ACU, the following screen isdisplayed:

    Figure 16. Loading data indication.

    If the screen is empty and the text Loading data does not appear, there isno data to display from the selected menu.

    4.5 Devices

    As shown in Figure 15, the menu Devices has the sub-menus of equipmentgroups such as ACU System, Rectifier Group, Battery Group, DC Distri-bution, Battery Fuse Group, LVD Group and SM IO1. A user can checkthe sample data of the equipment, set the equipment parameters and controlthe equipment by operating these sub-menus.

    Note: The equipment groups displayed depend on the equipment con-nected to the system.

  • 7/24/2019 3 - ACU User Guide Rev F

    43/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    43(56)

    4.5.1 Device parameter settings

    When browsing the control- and setting-values of the system devices, somesettings are blocked (the set button is grey). The reason is that the setting de-pends on another setting or that the user authority level does not approve achange of the setting.

    Figure 17. Example of blocked setting.

    4.6 Alarms

    In any screen, click the icon located in the middle bottom part of the

    screen to pop up the alarm screen. See Figure 16.

    Figure 18. Alarm screen.

    By clicking the buttons Observation, Major or Critical the respective alarmcategory will be displayed separately.

    Blockedbutton

  • 7/24/2019 3 - ACU User Guide Rev F

    44/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    44(56)

    4.6.1 Alarms history

    To view the alarms history, click the submenu History of Alarms, historyalarm query screen pops up.

    In the screen, first select device (All device, for example).

    Enter the start time and end time of the desired alarms history.

    Click Query.

    The alarms history recorded for the desired period will be displayed.

    Figure 19. Alarms History.

    By clicking Download the list can be stored to the PC as a text file.

    4.7 Settings

    From the sub menu SETTINGS a number of system- and communication-settings can be made.

    4.7.1 Network configuration

    On this page, the IP address, the subnet mask and the default gateway forcommunication over the Ethernet interface are to be set.

    Note: After modifying the IP address, be sure to re-log in the ACU with thenew IP address, since the communication will be broken when chang-ing the IP address.

  • 7/24/2019 3 - ACU User Guide Rev F

    45/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    45(56)

    4.7.2 NMS configure

    On this page, the trap addresses for Simple Network Management Protocolare to be set.

    4.7.3 MC configuration

    The EEM protocol is used for communication between the Main Computer andthe ACU. The Main Computer is the computer superior to the ACU (the clientof the ACU). On this page, all parameters needed for communication with amain EEM computer are to be set.

    4.7.4 User configuration

    On this page, users, their authority and password are configured. For authoritylevels, see item 2.3.4.

    4.7.5 Edit PLC Config

    By combining the equipment analogue signals, parameters and alarms newalarms can be configured from the Programmable Logic Controllers menu.An alarm can then be related to a digital (relay) output of the ACU.

    4.7.5.1 Default Setup

    The default setup of the relays is that:

    Relay1 will be activated when the ACU is fully started and there is no

    critical alarm active.

    Relay2 will be activated when there is any major alarm active.

    Relay3 will be activated when there is any observation alarm active.

    This means that if all the three relays are connected in the same way, then re-lay1 will be inverted.

  • 7/24/2019 3 - ACU User Guide Rev F

    46/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    46(56)

    4.7.5.2 Column Description

    Operator

    The Operator column explains the type of function that will be performed. Thelist of operators is shown in the symbol information table, from line 3 anddown.

    Input 1

    The INPUT 1 column is dived in three sub-columns, which are described be-low.

    EquipName/Register

    This column shows the equipment that the chosen signal is connected to(equipment is not necessarily connected to a physical device. One equipmentcan be connected to several physical devices and vice versa).

    The equipment can be replaced by a register. Every register is given a uniquenumber between 0 and 99. A register works a temporary storage place thatwill be cleared after every run of the PLC function.

    Signal Type

    This column shows of which type the chosen signal is.

    The ACU has four different signal types:

    Sample (measured or calculated values or status)

  • 7/24/2019 3 - ACU User Guide Rev F

    47/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    47(56)

    Control (control of different functions or events)

    Setting (different kind of settings)

    Alarm (alarms, these signals will only be activated if the alarm categoryis set to anything else than NA)

    Signal Name

    This column shows which signal that is chosen.

    Input 2

    See Input 1.

    Param 1

    This column shows if any parameter is used.

    A parameter is just a way to enter a value, which can be used in compares

    with signals.

    Param 2

    See Param 1.

    Output

    The Output column is divided in three sub-columns, which has the same in-formation as for the inputs. See EquipName/Register, Signal Type and SignalName for more info.

    4.7.5.3 Work Flow of The PLC FunctionThe PLC function normally runs every 10sec. It starts by executing the firstline and stores the result in the output signal/register. Then executes the nextline and continues executing line by line until it reaches the end.

    The PLC function will be stopped if the ACU is set to Manual Mode.

    4.7.5.4 Adding a New Line

    Click theAddbutton and the window below is shown.

  • 7/24/2019 3 - ACU User Guide Rev F

    48/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    48(56)

    1. Choose the type of operator. The web page will disable some boxes thatare not applicable for the type of operator chosen.

    2. Select Signal or Register for Input 1.

    3. Enter either the register number or choose the equipment, signal typeand signal name. The format for entering a register is R(x), where x is

    the number of the register.

    4. Setup Input 2 in the same way as Input 1 if its not disabled.

    5. Enter Param 1 and Param 2 if they are not disabled. The format for en-tering a parameter is P(x), where x is the value.

    6. Select Signal or Register for the Output.

    7. Enter either the register number or choose the equipment, signal typeand signal name.

    4.7.5.5 ExamplesConnecting One Alarm To A Relay

    This example will describe how to set up relay 4 so that it will be activatedwhen the High Battery Temperature alarm is active.

    This will be done by using OR operator and chose the High Battery Tempera-ture alarm for both inputs.

  • 7/24/2019 3 - ACU User Guide Rev F

    49/56

  • 7/24/2019 3 - ACU User Guide Rev F

    50/56

  • 7/24/2019 3 - ACU User Guide Rev F

    51/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    51(56)

    5. Set up Input 2. Do step 4a to 4d but for Input 2. The window shall looklike below.

    6. Set up Outputa. In the choice between Signal and Register, select Signal

    b. Choose the equipmentACU System

    c. Choose the signal type Control

  • 7/24/2019 3 - ACU User Guide Rev F

    52/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    52(56)

    d. Choose the signal name DO 4

    7. Click theAddbutton

    8. The following pop-up shall be shown

  • 7/24/2019 3 - ACU User Guide Rev F

    53/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    53(56)

    9. Restart the ACU from the Restore Defaultpage

    4.7.6 Power Split

    On this page the Power Split function can be enabled. And the LVD, BatteryTest and Boost Charging can be set up for control from the master system viadigital inputs. For more settings connected to Power Split see ACU System.

    4.7.7 Time synchronization

    On this page, the system time and date are to be set.Automatic time synchronization from time servers can also be configured.

    4.8 Maintenance

    From the maintenance pages, parameter settings can be uploaded from theACU, some resets can be made and signal names can be configured.

  • 7/24/2019 3 - ACU User Guide Rev F

    54/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    54(56)

    4.8.1 Clear data

    On this page, the system logs can be cleared.

    4.8.2 Restore default

    When clicking the button Restore default on this page, all adjustable parame-ters will be restored to default settings (the values the system had at delivery,or that were stored by the user in a configuration file).

    When clicking the button Reboot ACU the ACU program restarts but no set-tings are changed. Some settings demand a restart to become active.

    4.8.3 Site inventory

    The Site inventory page displays information about the units connected to theACU. The page is automatically updated when units are exchanged or whennew units are connected to the system

    4.8.4 Get setting parameter

    Through this function, current parameter settings can be retrieved from theACU. They can then be downloaded to another ACU via the SW DownloadTool.

    Note: Both ACUs must have the same software and configuration versions for cor-rect function after transferring parameter settings.

    4.8.5 Auto Configuration

    When the Auto configuration function is started the ACU will search for con-nected SM-DU units and SM-AC units. This will take about 5-10min, during thesearch it will not be possible to login to the ACU web pages or the display.

    Before the auto configuration is started the user must set the correct AC Unittype in the AC Group Settings.

    4.8.6 Modify configuration online

    Site specifications, device names, signal names and alarm categories can bemodified from these pages.

  • 7/24/2019 3 - ACU User Guide Rev F

    55/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5/1553-BMP 903 050 Uen Rev F 2008-10-01

    55(56)

    4.9 Site map

    Figure 20. Site map.

    This page displays the headings and underlying pages of the web interface. Clickon the hypertext links to go to the page in question. Some pages are dependenton which units are connected to the ACU.

  • 7/24/2019 3 - ACU User Guide Rev F

    56/56

    USERS GUIDE ACU for NetSure 201, 501, 701 and 801

    5 Abbreviations used in this document

    AC Alternating CurrentACU Advanced Control UnitDC Direct Current

    EEM Emerson EnergyMasterENERGYMASTER is a registered trademark ofEmerson Network Power Energy Systems AB

    ENT EnterESC EscapeESR Energy Supervision ReportGSM Global System for Mobile communicationIO Input OutputIP Internet ProtocolLAN Local Area NetworkLC Local Computer

    LCD Liquid Crystal DisplayLED Light Emitting DiodeLVD Low Voltage DisconnectMIB Managed Information BaseNMS Network Management SystemOS Operating SystemPC Personal ComputerPLC Programmable Logic ControllersPSTN Public Switched Telephony NetworkSM Supervision ModuleSNMP Simple Network Management ProtocolWAN Wide Area Network