Upload
yinder-vega-osorio
View
216
Download
0
Embed Size (px)
Citation preview
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 1/39
Lecture 22
Power System Protection, Transient Stability
Professor Tom Overbye
Department of Electrical and
Computer Engineering
ECE 476
POWER SYSTEM ANALYSIS
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 2/39
1
Announcements
Be reading Chapters 9 and 10
After exam read Chapter 11
HW 9 is 8.4, 8.12, 9.1,9.2 (bus 2), 9.14; do by Nov 10 but
does not need to be turned in.
Start working on Design Project. Firm due date has been
extended to Dec 1 in class
Second exam is on Nov 15 in class. Same format as first
exam, except you can bring two note sheets (e.g., the one
from the first exam and another)
Exam/solution from 2008 will be posted on website shortly
Exam covers through Chapter 10
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 3/39
2
In the News: Boulder municipalization
• Last week Boulder, CO narrowly voted to move
forward with municipalization of their electric grid
• Currently Boulder is in the Xcel Energy electric service
territory (Xcel is a large Investor Owned Utility)• Xcel has recently decided not to continue funding
the Boulder “SmartGridCity” initiative, which has
cost $45 million, triple its original cost.
• Xcel does not wish to sell its electric grid inBoulder, saying it would be extremely expensive
for Boulder to go on their own.Source: NY Times 11/3/11; Thanks to Margaret for pointing out this story
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 4/39
3
Power System Protection
Main idea is to remove faults as quickly as possible
while leaving as much of the system intact as
possible
Fault sequence of events1. Fault occurs somewhere on the system, changing the
system currents and voltages
2. Current transformers (CTs) and potential transformers
(PTs) sensors detect the change in currents/voltages3. Relays use sensor input to determine whether a fault has
occurred
4. If fault occurs relays open circuit breakers to isolate fault
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 5/39
4
Power System Protection
Protection systems must be designed with both
primary protection and backup protection in case
primary protection devices fail
In designing power system protection systemsthere are two main types of systems that need to be
considered:
1. Radial: there is a single source of power, so power
always flows in a single direction; this is the
easiest from a protection point of view
2. Network: power can flow in either direction:
protection is much more involved
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 6/39
5
Radial Power System Protection
Radial systems are primarily used in the lower
voltage distribution systems. Protection actions
usually result in loss of customer load, but the
outages are usually quite local.The figure shows
potential protection
schemes for a
radial system. The
bottom scheme is
preferred since it
results in less lost load
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 7/39
6
Radial Power System Protection
In radial power systems the amount of fault current is
limited by the fault distance from the power source:
faults further done the feeder have less fault current
since the current is limited by feeder impedance Radial power system protection systems usually use
inverse-time overcurrent relays.
Coordination of relay current settings is needed to
open the correct breakers
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 8/39
7
Inverse Time Overcurrent Relays
Inverse time overcurrent relays respond instan-
taneously to a current above their maximum setting
They respond slower to currents below this value
but above the pickup current value
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 9/39
8
Inverse Time Relays, cont'd
The inverse time characteristic provides backup
protection since relays further upstream (closer to
power source) should eventually trip if relays closer
to the fault fail Challenge is to make sure the minimum pickup
current is set low enough to pick up all likely faults,
but high enough not to trip on load current
When outaged feeders are returned to service therecan be a large in-rush current as all the motors try to
simultaneously start; this in-rush current may re-trip
the feeder
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 10/39
9
Inverse Time Overcurrent Relays
Relays have
traditionally been
electromechanical
devices, but are
gradually being
replaced by
digital relays
Current and timesettings are ad-
justed using dials
on the relay
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 11/39
10
Protection of Network Systems
In a networked system there are a number of
difference sources of power. Power flows are
bidirectional
Networked system offer greater reliability, sincethe failure of a single device does not result in a
loss of load
Networked systems are usually used with the
transmission system, and are sometimes used withthe distribution systems, particularly in urban areas
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 12/39
11
Network System Protection
Removing networked elements require the opening
of circuit breakers at both ends of the device
There are several common protection schemes;
multiple overlapping schemes are usually used1. Directional relays with communication between
the device terminals
2. Impedance (distance) relays.
3. Differential protection
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 13/39
12
Directional Relays
Directional relays are commonly used to protect
high voltage transmission lines
Voltage and current measurements are used to
determine direction of current flow (into or out ofline)
Relays on both ends of line communicate and will
only trip the line if excessive current is flowing into
the line from both ends
– line carrier communication is popular in which a high
frequency signal (30 kHz to 300 kHz) is used
– microwave communication is sometimes used
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 14/39
13
Impedance Relays
Impedance (distance) relays measure ratio of
voltage to current to determine if a fault exists on a
particular line
1 1
12 12
Assume Z is the line impedance and x is thenormalized fault location (x 0 at bus 1, x 1 at bus 2)
V V Normally is high; during fault
I I
x Z
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 15/39
14
Impedance Relays Protection Zones
To avoid inadvertent tripping for faults on other
transmission lines, impedance relays usually have
several zones of protection:
– zone 1 may be 80% of line for a 3f fault; trip isinstantaneous
– zone 2 may cover 120% of line but with a delay to prevent
tripping for faults on adjacent lines
– zone 3 went further; most removed due to 8/14/03 events The key problem is that different fault types will
present the relays with different apparent
impedances; adequate protection for a 3f fault gives
very limited protection for LL faults
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 16/39
15
Impedance Relay Trip Characteristics
Source: August 14th 2003 Blackout Final Report, p. 78
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 17/39
16
Differential Relays
Main idea behind differential protection is that
during normal operation the net current into a
device should sum to zero for each phase
– transformer turns ratios must, of course, be considered Differential protection is used with geographically
local devices
– buses
– transformers
– generators
1 2 3 0 for each phase
except during a fault
I I I
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 18/39
17
Other Types of Relays
In addition to providing fault protection, relays are
used to protect the system against operational
problems as well
Being automatic devices, relays can respond muchquicker than a human operator and therefore have
an advantage when time is of the essence
Other common types of relays include
– under-frequency for load: e.g., 10% of system load must
be shed if system frequency falls to 59.3 Hz
– over-frequency on generators
– under-voltage on loads (less common)
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 19/39
18
Sequence of Events Recording
During major system disturbances numerous relays
at a number of substations may operate
Event reconstruction requires time synchronization
between substations to figure out the sequence ofevents
Most utilities now have sequence of events
recording that provide time synchronization of at
least 1 microsecond
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 20/39
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 21/39
20
Power System Transient Stability
In order to operate as an interconnected system all of
the generators (and other synchronous machines)
must remain in synchronism with one another
– synchronism requires that (for two pole machines) therotors turn at exactly the same speed
Loss of synchronism results in a condition in which
no net power can be transferred between the
machines A system is said to be transiently unstable if
following a disturbance one or more of the
generators lose synchronism
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 22/39
21
Generator Transient Stability Models
In order to study the transient response of a power
system we need to develop models for the generator
valid during the transient time frame of several
seconds following a system disturbance We need to develop both electrical and mechanical
models for the generators
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 23/39
22
Example of Transient Behavior
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 24/39
23
Generator Electrical Model
The simplest generator model, known as the
classical model, treats the generator as a voltage
source behind the direct-axis transient reactance;
the voltage magnitude is fixed, but its anglechanges according to the mechanical dynamics
'( ) sinT ae
d
V E P X
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 25/39
24
Generator Mechanical Model
Generator Mechanical Block Diagram
m
D
e
( )
mechanical input torque (N-m)
J moment of inertia of turbine & rotor angular acceleration of turbine & rotor
T damping torque
T ( ) equivalent electrical torque
m m D e
m
T J T T
T
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 26/39
25
Generator Mechanical Model, cont’d
s
s s
s s
In general power = torque angular speed
Hence when a generator is spinning at speed
( )
( ( ))( )
Initially we'll assume no damping (i.e., 0)
Then
m m D e
m m D e m
m m D e
D
m e
T J T T
T J T T P P J T P
T
P P
s( )
is the mechanical power input, which is assumed
to be constant throughout the study time period
m
m
J
P
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 27/39
26
Generator Mechanical Model, cont’d
s
s s
s
s
( )rotor angle
( )
inertia of machine at synchronous speedConvert to per unit by dividing by MVA rating, ,
( ) 2
m e m
m s
mm m s
m m
m e m
B
m e s
B B B
P P J t
d
dt
P P J J
J S
P P J
S S S
2 s
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 28/39
27
Generator Mechanical Model, cont’d
s
2
2
( ) 22
( ) 1(since 2 )
2
Define H per unit inertia constant (sec)2
All values are now converted to per unit
( ) Define
Then ( )
m e s
B B B s
m e s s s
B B s
s
B
m e s s
m e
P P J S S S
P P J f
S S f J
S
H H P P M
f f
P P
M
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 29/39
28
Generator Swing Equation
This equation is known as the generator swing equation ( )
Adding damping we get
( )This equation is analogous to a mass suspended by
a spring
m e
m e
P P M
P P M D
k x gM Mx Dx
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 30/39
29
Single Machine Infinite Bus (SMIB)
To understand the transient stability problem we’ll
first consider the case of a single machine
(generator) connected to a power system bus with a
fixed voltage magnitude and angle (known as aninfinite bus) through a transmission line with
impedance jXL
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 31/39
30
SMIB, cont’d
'
'
( ) sin
sin
ae
d L
a M
d L
E P
X X
E M D P X X
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 32/39
31
SMIB Equilibrium Points
'
Equilibrium points are determined by setting theright-hand side to zero
sina M
d L
E D P
X X
'
'th
1
sin 0
Define X
sin
a M
d L
d L
M th
a
E P
X X
X X
P X
E
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 33/39
32
Transient Stability Analysis
For transient stability analysis we need to consider
three systems
1. Prefault - before the fault occurs the system is
assumed to be at an equilibrium point2. Faulted - the fault changes the system equations,
moving the system away from its equilibrium
point
3. Postfault - after fault is cleared the system
hopefully returns to a new operating point
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 34/39
33
Transient Stability Solution Methods
There are two methods for solving the transient
stability problem
1. Numerical integration
this is by far the most common technique, particularlyfor large systems; during the fault and after the fault the
power system differential equations are solved using
numerical methods
2. Direct or energy methods; for a two bus systemthis method is known as the equal area criteria
mostly used to provide an intuitive insight into the
transient stability problem
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 35/39
34
SMIB Example
Assume a generator is supplying power to aninfinite bus through two parallel transmission lines.
Then a balanced three phase fault occurs at the
terminal of one of the lines. The fault is cleared by
the opening of this line’s circuit breakers.
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 36/39
35
SMIB Example, cont’d
Simplified prefault system
1
The prefault system has two
equilibrium points; the left one
is stable, the right one unstable
sin M th
a
P X
E
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 37/39
36
SMIB Example, Faulted System
During the fault the system changes
The equivalent system during the fault is then
During this fault no power can be transferred
from the generator to
the system
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 38/39
37
SMIB Example, Post Fault System
After the fault the system again changes
The equivalent system after the fault is then
8/10/2019 24_Velez_Power System Protection, Transient Stability_p38
http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 39/39
SMIB Example, Dynamics
eDuring the disturbance the form of P ( ) changes,altering the power system dynamics:
1sina th
M
h
E V P
M X