39
Lecture 22 Power System Protection, Transient Stability Professor Tom Overbye Department of Electrical and Computer Engineering ECE 476 POWER SYSTEM ANALYSIS

24_Velez_Power System Protection, Transient Stability_p38

Embed Size (px)

Citation preview

Page 1: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 1/39

Lecture 22

Power System Protection, Transient Stability

Professor Tom Overbye

Department of Electrical and

Computer Engineering

ECE 476

POWER SYSTEM ANALYSIS

Page 2: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 2/39

1

Announcements

Be reading Chapters 9 and 10

After exam read Chapter 11

HW 9 is 8.4, 8.12, 9.1,9.2 (bus 2), 9.14; do by Nov 10 but

does not need to be turned in.

Start working on Design Project. Firm due date has been

extended to Dec 1 in class

Second exam is on Nov 15 in class. Same format as first

exam, except you can bring two note sheets (e.g., the one

from the first exam and another)

Exam/solution from 2008 will be posted on website shortly

Exam covers through Chapter 10

Page 3: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 3/39

2

In the News: Boulder municipalization

• Last week Boulder, CO narrowly voted to move

forward with municipalization of their electric grid

• Currently Boulder is in the Xcel Energy electric service

territory (Xcel is a large Investor Owned Utility)• Xcel has recently decided not to continue funding

the Boulder “SmartGridCity” initiative, which has

cost $45 million, triple its original cost.

• Xcel does not wish to sell its electric grid inBoulder, saying it would be extremely expensive

for Boulder to go on their own.Source: NY Times 11/3/11; Thanks to Margaret for pointing out this story

Page 4: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 4/39

3

Power System Protection

Main idea is to remove faults as quickly as possible

while leaving as much of the system intact as

 possible

Fault sequence of events1. Fault occurs somewhere on the system, changing the

system currents and voltages

2. Current transformers (CTs) and potential transformers

(PTs) sensors detect the change in currents/voltages3. Relays use sensor input to determine whether a fault has

occurred

4. If fault occurs relays open circuit breakers to isolate fault

Page 5: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 5/39

4

Power System Protection

Protection systems must be designed with both

 primary protection and backup protection in case

 primary protection devices fail

In designing power system protection systemsthere are two main types of systems that need to be

considered:

1. Radial: there is a single source of power, so power

always flows in a single direction; this is the

easiest from a protection point of view

2.  Network: power can flow in either direction:

 protection is much more involved

Page 6: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 6/39

5

Radial Power System Protection

Radial systems are primarily used in the lower

voltage distribution systems. Protection actions

usually result in loss of customer load, but the

outages are usually quite local.The figure shows

 potential protection

schemes for a

radial system. The

 bottom scheme is

 preferred since it

results in less lost load

Page 7: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 7/39

6

Radial Power System Protection

In radial power systems the amount of fault current is

limited by the fault distance from the power source:

faults further done the feeder have less fault current

since the current is limited by feeder impedance Radial power system protection systems usually use

inverse-time overcurrent relays.

 Coordination of relay current settings is needed to

open the correct breakers

Page 8: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 8/39

7

Inverse Time Overcurrent Relays

Inverse time overcurrent relays respond instan-

taneously to a current above their maximum setting

They respond slower to currents below this value

 but above the pickup current value

Page 9: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 9/39

8

Inverse Time Relays, cont'd

The inverse time characteristic provides backup

 protection since relays further upstream (closer to

 power source) should eventually trip if relays closer

to the fault fail Challenge is to make sure the minimum pickup

current is set low enough to pick up all likely faults,

 but high enough not to trip on load current

When outaged feeders are returned to service therecan be a large in-rush current as all the motors try to

simultaneously start; this in-rush current may re-trip

the feeder

Page 10: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 10/39

9

Inverse Time Overcurrent Relays

Relays have

traditionally been

electromechanical

devices, but are

gradually being

replaced by

digital relays

Current and timesettings are ad-

 justed using dials

on the relay

Page 11: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 11/39

10

Protection of Network Systems

In a networked system there are a number of

difference sources of power. Power flows are

 bidirectional

 Networked system offer greater reliability, sincethe failure of a single device does not result in a

loss of load

 Networked systems are usually used with the

transmission system, and are sometimes used withthe distribution systems, particularly in urban areas

Page 12: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 12/39

11

Network System Protection

Removing networked elements require the opening

of circuit breakers at both ends of the device

There are several common protection schemes;

multiple overlapping schemes are usually used1. Directional relays with communication between

the device terminals

2. Impedance (distance) relays.

3. Differential protection

Page 13: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 13/39

12

Directional Relays

Directional relays are commonly used to protect

high voltage transmission lines

Voltage and current measurements are used to

determine direction of current flow (into or out ofline)

Relays on both ends of line communicate and will

only trip the line if excessive current is flowing into

the line from both ends

 –  line carrier communication is popular in which a high

frequency signal (30 kHz to 300 kHz) is used

 –  microwave communication is sometimes used

Page 14: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 14/39

13

Impedance Relays

Impedance (distance) relays measure ratio of

voltage to current to determine if a fault exists on a

 particular line

1 1

12 12

Assume Z is the line impedance and x is thenormalized fault location (x 0 at bus 1, x 1 at bus 2)

V V Normally is high; during fault

I I

 x Z 

Page 15: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 15/39

14

Impedance Relays Protection Zones

To avoid inadvertent tripping for faults on other

transmission lines, impedance relays usually have

several zones of protection:

 –  zone 1 may be 80% of line for a 3f fault; trip isinstantaneous

 –  zone 2 may cover 120% of line but with a delay to prevent

tripping for faults on adjacent lines

 –  zone 3 went further; most removed due to 8/14/03 events The key problem is that different fault types will

 present the relays with different apparent

impedances; adequate protection for a 3f fault gives

very limited protection for LL faults

Page 16: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 16/39

15

Impedance Relay Trip Characteristics

Source: August 14th 2003 Blackout Final Report, p. 78

Page 17: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 17/39

16

Differential Relays

Main idea behind differential protection is that

during normal operation the net current into a

device should sum to zero for each phase

 –  transformer turns ratios must, of course, be considered Differential protection is used with geographically

local devices

 –   buses

 –  transformers

 –  generators

1 2 3 0 for each phase

except during a fault

 I I I 

Page 18: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 18/39

17

Other Types of Relays

In addition to providing fault protection, relays are

used to protect the system against operational

 problems as well

Being automatic devices, relays can respond muchquicker than a human operator and therefore have

an advantage when time is of the essence

Other common types of relays include

 –  under-frequency for load: e.g., 10% of system load must

 be shed if system frequency falls to 59.3 Hz

 –  over-frequency on generators

 –  under-voltage on loads (less common)

Page 19: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 19/39

18

Sequence of Events Recording

During major system disturbances numerous relays

at a number of substations may operate

Event reconstruction requires time synchronization

 between substations to figure out the sequence ofevents

Most utilities now have sequence of events

recording that provide time synchronization of at

least 1 microsecond

Page 20: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 20/39

Page 21: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 21/39

20

Power System Transient Stability

In order to operate as an interconnected system all of

the generators (and other synchronous machines)

must remain in synchronism with one another

 –  synchronism requires that (for two pole machines) therotors turn at exactly the same speed

Loss of synchronism results in a condition in which

no net power can be transferred between the

machines A system is said to be transiently unstable if

following a disturbance one or more of the

generators lose synchronism

Page 22: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 22/39

21

Generator Transient Stability Models

In order to study the transient response of a power

system we need to develop models for the generator

valid during the transient time frame of several

seconds following a system disturbance We need to develop both electrical and mechanical

models for the generators

Page 23: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 23/39

22

Example of Transient Behavior

Page 24: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 24/39

23

Generator Electrical Model

The simplest generator model, known as the

classical model, treats the generator as a voltage

source behind the direct-axis transient reactance;

the voltage magnitude is fixed, but its anglechanges according to the mechanical dynamics

'( ) sinT ae

V E  P   X    

Page 25: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 25/39

24

Generator Mechanical Model

Generator Mechanical Block Diagram

m

D

e

( )

mechanical input torque (N-m)

J moment of inertia of turbine & rotor angular acceleration of turbine & rotor 

T damping torque

T ( ) equivalent electrical torque

m m D e

m

T J T T  

  

 

  

Page 26: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 26/39

25

Generator Mechanical Model, cont’d 

s

s s

s s

In general power = torque angular speed

Hence when a generator is spinning at speed

( )

( ( ))( )

Initially we'll assume no damping (i.e., 0)

Then

m m D e

m m D e m

m m D e

 D

m e

T J T T  

T J T T P   P J T P 

 P P 

 

  

 

   

s( )

 is the mechanical power input, which is assumed

to be constant throughout the study time period

m

m

 J 

 P 

 

Page 27: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 27/39

26

Generator Mechanical Model, cont’d 

s

s s

s

s

( )rotor angle

( )

inertia of machine at synchronous speedConvert to per unit by dividing by MVA rating, ,

( ) 2

m e m

m s

mm m s

m m

m e m

 B

m e s

 B B B

 P P J t 

dt 

 P P J J 

 J S 

 P P J 

S S S 

    

     

  

   

 

 

2  s 

Page 28: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 28/39

27

Generator Mechanical Model, cont’d 

s

2

2

( ) 22

( ) 1(since 2 )

2

Define H per unit inertia constant (sec)2

All values are now converted to per unit

( ) Define

Then ( )

m e s

 B B B s

m e s s s

 B B s

 s

 B

m e s s

m e

 P P J S S S 

 P P J  f  

S S f   J 

 H H  P P M 

 f f  

 P P 

 

 

   

 

 

    

  

  M   

Page 29: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 29/39

28

Generator Swing Equation

This equation is known as the generator swing equation  ( )

Adding damping we get

  ( )This equation is analogous to a mass suspended by

a spring

m e

m e

 P P M 

 P P M D

  

  

k x gM Mx Dx

Page 30: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 30/39

29

Single Machine Infinite Bus (SMIB)

To understand the transient stability problem we’ll

first consider the case of a single machine

(generator) connected to a power system bus with a

fixed voltage magnitude and angle (known as aninfinite bus) through a transmission line with

impedance jXL 

Page 31: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 31/39

30

SMIB, cont’d 

'

'

( ) sin

sin

ae

d L

a M 

d L

 E  P 

 X X 

 E  M D P  X X 

  

  

Page 32: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 32/39

31

SMIB Equilibrium Points

'

Equilibrium points are determined by setting theright-hand side to zero

sina M 

d L

 E  D P 

 X X 

  

'

'th

1

sin 0

Define X

sin

a M 

d L

d L

 M th

a

 E  P 

 X X 

 X X 

 P X 

 E 

  

   

Page 33: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 33/39

32

Transient Stability Analysis

For transient stability analysis we need to consider

three systems

1. Prefault - before the fault occurs the system is

assumed to be at an equilibrium point2. Faulted - the fault changes the system equations,

moving the system away from its equilibrium

 point

3. Postfault - after fault is cleared the system

hopefully returns to a new operating point

Page 34: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 34/39

33

Transient Stability Solution Methods

There are two methods for solving the transient

stability problem

1.  Numerical integration

this is by far the most common technique, particularlyfor large systems; during the fault and after the fault the

 power system differential equations are solved using

numerical methods

2. Direct or energy methods; for a two bus systemthis method is known as the equal area criteria

mostly used to provide an intuitive insight into the

transient stability problem

Page 35: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 35/39

34

SMIB Example

Assume a generator is supplying power to aninfinite bus through two parallel transmission lines.

Then a balanced three phase fault occurs at the

terminal of one of the lines. The fault is cleared by

the opening of this line’s circuit breakers.

Page 36: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 36/39

35

SMIB Example, cont’d 

Simplified prefault system

1

The prefault system has two

equilibrium points; the left one

is stable, the right one unstable

sin   M th

a

 P X 

 E   

   

Page 37: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 37/39

36

SMIB Example, Faulted System

During the fault the system changes

The equivalent system during the fault is then

During this fault no power can be transferred

from the generator to

the system

Page 38: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 38/39

37

SMIB Example, Post Fault System

After the fault the system again changes

The equivalent system after the fault is then

Page 39: 24_Velez_Power System Protection, Transient Stability_p38

8/10/2019 24_Velez_Power System Protection, Transient Stability_p38

http://slidepdf.com/reader/full/24velezpower-system-protection-transient-stabilityp38 39/39

SMIB Example, Dynamics

eDuring the disturbance the form of P ( ) changes,altering the power system dynamics:

1sina th

 M 

h

 E V  P 

M X