18
Report on Proposals 2013 Annual Revision Cycle NOTE: The proposed NFPA documents addressed in this Report on Proposals (ROP) and in a follow-up Report on Comments (ROC) will only be presented for action when proper Amending Motions have been submitted to the NFPA by the deadline of April 5, 2013. The June 2013 NFPA Conference & Expo will be held June 10–13, 2013, at McCormick Place Convention Center, Chicago, IL. During the meeting, the Association Technical Meeting (Tech Session) will be held June 12–13, 2013. Documents that receive no motions will not be presented at the meeting and instead will be forwarded directly to the Standards Council for action on issuance. For more information on the rules and for up-to-date information on schedules and deadlines for processing NFPA documents, check the NFPA website (www.nfpa.org) or contact NFPA Standards Administration. ISSN 1079-5332 Copyright © 2012 All Rights Reserved NFPA and National Fire Protection Association are registered trademarks of the National Fire Protection Association, Quincy, MA 02169. National Fire Protection Association® 1 BATTERYMARCH PARK, QUINCY, MA 02169-7471 A compilation of NFPA ® Technical Committee Reports on Proposals for public review and comment Public Comment Deadline: August 31, 2012

2013 Annual Revision Cycle Report on Proposals

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Report onProposals

2013 Annual Revision Cycle

NOTE: The proposed NFPA documents addressed in this Report on

Proposals (ROP) and in a follow-up Report on Comments (ROC) will

only be presented for action when proper Amending Motions have been

submitted to the NFPA by the deadline of April 5, 2013. The June 2013

NFPA Conference & Expo will be held June 10–13, 2013, at McCormick

Place Convention Center, Chicago, IL. During the meeting, the Association

Technical Meeting (Tech Session) will be held June 12–13, 2013.

Documents that receive no motions will not be presented at the meeting

and instead will be forwarded directly to the Standards Council for action on

issuance. For more information on the rules and for up-to-date information

on schedules and deadlines for processing NFPA documents, check the

NFPA website (www.nfpa.org) or contact NFPA Standards Administration.

ISSN 1079-5332 Copyright © 2012 All Rights Reserved

NFPA and National Fire Protection Association are registered trademarks of the National Fire Protection Association, Quincy, MA 02169.

National Fire Protection Association®1 BATTERYMARCH PARK, QUINCY, MA 02169-7471

A compilation of NFPA® TechnicalCommittee Reports on Proposals for public review and comment

Public Comment Deadline: August 31, 2012

Information on NFPA Codes and Standards Development

I. Applicable Regulations. The primary rules governing the processing of NFPA documents (codes, standards, recommended practices, and guides) are the NFPA Regulations Governing Committee Projects (Regs). Other applicable rules include NFPA Bylaws, NFPA Technical Meeting Convention Rules, NFPA Guide for the Conduct of Participants in the NFPA Standards Development Process, and the NFPA Regulations Governing Petitions to the Board of Directors from Decisions of the Standards Council. Most of these rules and regulations are contained in the NFPA Directory. For copies of the Directory, contact Codes and Standards Administration at NFPA Headquarters; all these documents are also available on the NFPA website at “www.nfpa.org.”

The following is general information on the NFPA process. All participants, however, should refer to the actual rules and regulations for a full understanding of this process and for the criteria that govern participation.

II. Technical Committee Report. The Technical Committee Report is defined as “the Report of the Technical Committee and Technical Correlating Committee (if any) on a document consisting of the ROP and ROC.” A Technical Committee Report consists of the Report on Proposals (ROP), as modified by the Report on Comments (ROC), published by the Association.

III. Step 1: Report on Proposals (ROP). The ROP is defined as “a report to the Association on the actions taken by Technical Committees and/or Technical Correlating Committees, accompanied by a ballot statement and one or more proposals on text for a new document or to amend an existing document.” Any objection to an action in the ROP must be raised through the filing of an appropriate Comment for consideration in the ROC or the objection will be considered resolved.

IV. Step 2: Report on Comments (ROC). The ROC is defined as “a report to the Association on the actions taken by Technical Committees and/or Technical Correlating Committees accompanied by a ballot statement and one or more comments resulting from public review of the Report on Proposals (ROP).” The ROP and the ROC together constitute the Technical Committee Report. Any outstanding objection following the ROC must be raised through an appropriate Amending Motion at the Association Technical Meeting or the objection will be considered resolved.

V. Step 3a: Action at Association Technical Meeting. Following the publication of the ROC, there is a period during which those wishing to make proper Amending Motions on the Technical Committee Reports must signal their intention by submitting a Notice of Intent to Make a Motion. Documents that receive notice of proper Amending Motions (Certified Amending Motions) will be presented for action at the annual June Association Technical Meeting. At the meeting, the NFPA membership can consider and act on these Certified Amending Motions as well as Follow-up Amending Motions, that is, motions that become necessary as a result of a previous successful Amending Motion. (See 4.6.2 through 4.6.9 of Regs for a summary of the available Amending Motions and who may make them.) Any outstanding objection following action at an Association Technical Meeting (and any further Technical Committee consideration following successful Amending Motions, see Regs at 4.7) must be raised through an appeal to the Standards Council or it will be considered to be resolved.

VI. Step 3b: Documents Forwarded Directly to the Council. Where no Notice of Intent to Make a Motion (NITMAM) is received and certified in accordance with the Technical Meeting Convention Rules, the document is forwarded directly to the Standards Council for action on issuance. Objections are deemed to be resolved for these documents.

VII. Step 4a: Council Appeals. Anyone can appeal to the Standards Council concerning procedural or substantive matters related to the development, content, or issuance of any document of the Association or on matters within the purview of the authority of the Council, as established by the Bylaws and as determined by the Board of Directors. Such appeals must be in written form and filed with the Secretary of the Standards Council (see 1.6 of Regs). Time constraints for filing an appeal must be in accordance with 1.6.2 of the Regs. Objections are deemed to be resolved if not pursued at this level.

VIII. Step 4b: Document Issuance. The Standards Council is the issuer of all documents (see Article 8 of Bylaws). The Council acts on the issuance of a document presented for action at an Association Technical Meeting within 75 days from the date of the recommendation from the Association Technical Meeting, unless this period is extended by the Council (see 4.8 of Regs). For documents forwarded directly to the Standards Council, the Council acts on the issuance of the document at its next scheduled meeting, or at such other meeting as the Council may determine (see 4.5.6 and 4.8 of Regs).

IX. Petitions to the Board of Directors. The Standards Council has been delegated the responsibility for the administration of the codes and standards development process and the issuance of documents. However, where extraordinary circumstances requiring the intervention of the Board of Directors exist, the Board of Directors may take any action necessary to fulfill its obligations to preserve the integrity of the codes and standards development process and to protect the interests of the Association. The rules for petitioning the Board of Directors can be found in the Regulations Governing Petitions to the Board of Directors from Decisions of the Standards Council and in 1.7 of the Regs.

X. For More Information. The program for the Association Technical Meeting (as well as the NFPA website as information becomes available) should be consulted for the date on which each report scheduled for consideration at the meeting will be presented. For copies of the ROP and ROC as well as more information on NFPA rules and for up-to-date information on schedules and deadlines for processing NFPA documents, check the NFPA website (www.nfpa.org) or contact NFPA Codes & Standards Administration at (617) 984-7246.

i

2013 Annual Revision Cycle ROP Contents

by NFPA Numerical Designation

Note: Documents appear in numerical order.

NFPA No. Type Action Title Page No.

25 P Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems ............... 25-1 51B P Standard for Fire Prevention During Welding, Cutting, and Other Hot Work ........................................... 51B-1 56(PS) P Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping Systems .......................................................................................................... 56(PS)-1 58 P Liquefied Petroleum Gas Code ....................................................................................................................... 58-1 77 P Recommended Practice on Static Electricity .................................................................................................. 77-1 96 P Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations.......................... 96-1 130 P Standard for Fixed Guideway Transit and Passenger Rail Systems ............................................................. 130-1 306 P Standard for the Control of Gas Hazards on Vessels ................................................................................... 306-1 403 P Standard for Aircraft Rescue and Fire-Fighting Services at Airports .......................................................... 403-1 412 P Standard for Evaluating Aircraft Rescue and Fire-Fighting Foam Equipment ............................................ 412-1

502 P Standard for Road Tunnels, Bridges, and Other Limited Access Highways ............................................... 502-1 610 P Guide for Emergency and Safety Operations at Motorsports Venues ......................................................... 610-1 780 P Standard for the Installation of Lightning Protection Systems..................................................................... 780-1 1002 P Standard for Fire Apparatus Driver/Operator Professional Qualifications ................................................ 1002-1

1021 P Standard for Fire Officer Professional Qualifications ................................................................................ 1021-1

1026 P Standard for Incident Management Personnel Professional Qualifications ............................................... 1026-1 1031 P Standard for Professional Qualifications for Fire Inspector and Plan Examiner ....................................... 1031-1 1033 P Standard for Professional Qualifications for Fire Investigator ................................................................... 1033-1 1123 P Code for Fireworks Display ....................................................................................................................... 1123-1 1143 P Standard for Wildland Fire Management ................................................................................................... 1143-1

TYPES OF ACTION

P Partial Revision N New Document R Reconfirmation W Withdrawal

ii

2013 Annual Revision Cycle ROP Committees Reporting

Type Action Page No. Aircraft Rescue and Fire Fighting 403 Standard for Aircraft Rescue and Fire-Fighting Services at Airport P 403-1 412 Standard for Evaluating Aircraft Rescue and Fire-Fighting Foam Equipment P 412-1 Fixed Guideway Transit and Passenger Rail Systems 130 Standard for Fixed Guideway Transit and Passenger Rail Systems P 130-1 Forest and Rural Fire Protection 1143 Standard for Wildland Fire Management P 1143-1 Gas Hazards 306 Standard for the Control of Gas Hazards on Vessels P 306-1 Gas Process Safety 56(PS) Standard for Fire and Explosion Prevention During Cleaning and Purging of Flammable Gas Piping

Systems

P

56(PS)-1 Hot Work Operations 51B Standard for Fire Prevention During Welding, Cutting, and Other Hot Work P 51B-1 Inspection, Testing, and Maintenance of Water-Based Systems 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems P 25-1 Lightning Protection 780 Standard for the Installation of Lightning Protection Systems P 780-1 Liquefied Petroleum Gases 58 Liquefied Petroleum Gas Code P 58-1 Professional Qualifications Fire Fighter Professional Qualifications 1002 Standard for Fire Apparatus Driver/Operator Professional Qualifications P 1002-1 Fire Officer Professional Qualifications 1021 Standard for Fire Officer Professional Qualifications P 1021-1 Incident Management Professional Qualifications 1026 Standard for Incident Management Personnel Professional Qualifications P 1026-1 Fire Inspector Professional Qualifications 1031 Standard for Professional Qualifications for Fire Inspector and Plan Examiner P 1031-1 1033 Standard for Professional Qualifications for Fire Investigator P 1033-1 Pyrotechnics 1123 Code for Fireworks Display P 1123-1 Road Tunnel and Highway Fire Protection 502 Standard for Road Tunnels, Bridges, and Other Limited Access Highways P 502-1 Static Electricity 77 Recommended Practice on Static Electricity P 77-1 Safety at Motorsports Venues 610 Guide for Emergency and Safety Operations at Motorsports Venues P 610-1 Venting Systems for Cooking Appliances 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations P 96-1

iii

COMMITTEE MEMBER CLASSIFICATIONS1,2,3,4

The following classifications apply to Committee members and represent their principal interest in the activity of the Committee. 1. M Manufacturer: A representative of a maker or marketer of a product, assembly, or system, or portion thereof,

that is affected by the standard. 2. U User: A representative of an entity that is subject to the provisions of the standard or that voluntarily uses the

standard. 3. IM Installer/Maintainer: A representative of an entity that is in the business of installing or maintaining a product,

assembly, or system affected by the standard. 4. L Labor: A labor representative or employee concerned with safety in the workplace. 5. RT Applied Research/Testing Laboratory: A representative of an independent testing laboratory or independent

applied research organization that promulgates and/or enforces standards. 6. E Enforcing Authority: A representative of an agency or an organization that promulgates and/or enforces

standards. 7. I Insurance: A representative of an insurance company, broker, agent, bureau, or inspection agency. 8. C Consumer: A person who is or represents the ultimate purchaser of a product, system, or service affected by the

standard, but who is not included in (2). 9. SE Special Expert: A person not representing (1) through (8) and who has special expertise in the scope of the

standard or portion thereof. NOTE 1: “Standard” connotes code, standard, recommended practice, or guide. NOTE 2: A representative includes an employee. NOTE 3: While these classifications will be used by the Standards Council to achieve a balance for Technical Committees, the Standards Council may determine that new classifications of member or unique interests need representation in order to foster the best possible Committee deliberations on any project. In this connection, the Standards Council may make such appointments as it deems appropriate in the public interest, such as the classification of “Utilities” in the National Electrical Code Committee. NOTE 4: Representatives of subsidiaries of any group are generally considered to have the same classification as the parent organization.

FORM FOR COMMENT ON NFPA REPORT ON PROPOSALS 2013 Annual Revision CYCLE

FINAL DATE FOR RECEIPT OF COMMENTS: 5:00 pm EDST, August 31, 2012

For further information on the standards-making process, please contact the Codes and Standards Administration at 617-984-7249 or visit www.nfpa.org/codes.

For technical assistance, please call NFPA at 1-800-344-3555.

FOR OFFICE USE ONLY

Log #:

Date Rec’d:

Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: If choosing the download option, you must view the ROP/ROC from our website; no copy will be sent to you.)

Date 8/1/200X Name John B. Smith Tel. No. 253-555-1234

Company Email

Street Address 9 Seattle St. City Tacoma State WA Zip 98402

***If you wish to receive a hard copy, a street address MUST be provided. Deliveries cannot be made to PO boxes.

Please indicate organization represented (if any) Fire Marshals Assn. of North America

1. (a) NFPA Document Title National Fire Alarm Code NFPA No. & Year NFPA 72, 200X ed.

(b) Section/Paragraph 4.4.1.1

2. Comment on Proposal No. (from ROP): 72-7

3. Comment Recommends (check one): new text revised text deleted text

4. Comment (include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording).]

Delete exception.

5. Statement of Problem and Substantiation for Comment: (Note: State the problem that would be resolved by your recommendation; give the specific reason for your Comment, including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.)

A properly installed and maintained system should be free of ground faults. The occurrence of one or more ground faults should be required to cause a ‘trouble’ signal because it indicates a condition that could contribute to future malfunction of the system. Ground fault protection has been widely available on these systems for years and its cost is negligible. Requiring it on all systems will promote better installations, maintenance and reliability.

6. Copyright Assignment

(a) I am the author of the text or other material (such as illustrations, graphs) proposed in the Comment.

(b) Some or all of the text or other material proposed in this Comment was not authored by me. Its source is as follows: (please identify which material and provide complete information on its source)

I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this Comment and that I have full power and authority to enter into this assignment.

Signature (Required)

PLEASE USE SEPARATE FORM FOR EACH COMMENT

Mail to: Secretary, Standards Council · National Fire Protection Association 1 Batterymarch Park · Quincy, MA 02169-7471 OR

Fax to: (617) 770-3500 OR Email to: [email protected]

FORM FOR COMMENT ON NFPA REPORT ON PROPOSALS 2013 Annual Revision CYCLE

FINAL DATE FOR RECEIPT OF COMMENTS: 5:00 pm EDST, August 31, 2012

For further information on the standards-making process, please contact the Codes and Standards Administration at 617-984-7249 or visit www.nfpa.org/codes.

For technical assistance, please call NFPA at 1-800-344-3555.

FOR OFFICE USE ONLY

Log #:

Date Rec’d:

Please indicate in which format you wish to receive your ROP/ROC electronic paper download (Note: If choosing the download option, you must view the ROP/ROC from our website; no copy will be sent to you.)

Date Name Tel. No.

Company Email

Street Address City State Zip

***If you wish to receive a hard copy, a street address MUST be provided. Deliveries cannot be made to PO boxes.

Please indicate organization represented (if any)

1. (a) NFPA Document Title NFPA No. & Year

(b) Section/Paragraph

2. Comment on Proposal No. (from ROP):

3. Comment Recommends (check one): new text revised text deleted text

4. Comment (include proposed new or revised wording, or identification of wording to be deleted): [Note: Proposed text should be in legislative format; i.e., use underscore to denote wording to be inserted (inserted wording) and strike-through to denote wording to be deleted (deleted wording).]

5. Statement of Problem and Substantiation for Comment: (Note: State the problem that would be resolved by your recommendation; give the specific reason for your Comment, including copies of tests, research papers, fire experience, etc. If more than 200 words, it may be abstracted for publication.)

6. Copyright Assignment

(a) I am the author of the text or other material (such as illustrations, graphs) proposed in the Comment.

(b) Some or all of the text or other material proposed in this Comment was not authored by me. Its source is as follows: (please identify which material and provide complete information on its source)

I hereby grant and assign to the NFPA all and full rights in copyright in this Comment and understand that I acquire no rights in any publication of NFPA in which this Comment in this or another similar or analogous form is used. Except to the extent that I do not have authority to make an assignment in materials that I have identified in (b) above, I hereby warrant that I am the author of this Comment and that I have full power and authority to enter into this assignment.

Signature (Required)

PLEASE USE SEPARATE FORM FOR EACH COMMENT

Mail to: Secretary, Standards Council · National Fire Protection Association 1 Batterymarch Park · Quincy, MA 02169-7471 OR

Fax to: (617) 770-3500 OR Email to: [email protected] 5/15/2012

Sequence of Events Leading to Issuance of an NFPA Committee Document

Step 1 Call for Proposals

▼ Proposed new document or new edition of an existing document is entered into one of two yearly revision cycles, and a Call for Proposals is published.

Step 2 Report on Proposals (ROP)

▼ Committee meets to act on Proposals, to develop its own Proposals, and to prepare its Report.

▼ Committee votes by written ballot on Proposals. If two-thirds approve, Report goes forward. Lacking two-thirds approval, Report returns to Committee.

▼ Report on Proposals (ROP) is published for public review and comment.

Step 3 Report on Comments (ROC)

▼ Committee meets to act on Public Comments to develop its own Comments, and to prepare its report.

▼ Committee votes by written ballot on Comments. If two-thirds approve, Report goes forward. Lacking two-thirds approval, Report returns to Committee.

▼ Report on Comments (ROC) is published for public review.

Step 4 Association Technical Meeting

▼ “Notices of intent to make a motion” are filed, are reviewed, and valid motions are certified for presentation at the Association Technical Meeting. (“Consent Documents” that have no certified motions bypass the Association Technical Meeting and proceed to the Standards Council for issuance.)

▼ NFPA membership meets each June at the Association Technical Meeting and acts on Technical Committee Reports (ROP and ROC) for documents with “certified amending motions.”

▼ Committee(s) vote on any amendments to Report approved at NFPA Annual Membership Meeting.

Step 5 Standards Council Issuance

▼ Notification of intent to file an appeal to the Standards Council on Association action must be filed within 20 days of the NFPA Annual Membership Meeting.

▼ Standards Council decides, based on all evidence, whether or not to issue document or to take other action, including hearing any appeals.

The Association Technical Meeting

The process of public input and review does not end with the publication of the ROP and ROC. Following the completion of the Proposal and Comment periods, there is yet a further opportunity for debate and discussion through the Association Technical Meeting that takes place at the NFPA Annual Meeting.

The Association Technical Meeting provides an opportunity for the final Technical Committee Report (i.e., the ROP and ROC) on each proposed new or revised code or standard to be presented to the NFPA membership for the debate and consideration of motions to amend the Report. The specific rules for the types of motions that can be made and who can make them are set forth in NFPA’s rules, which should always be consulted by those wishing to bring an issue before the membership at an Association Technical Meeting. The following presents some of the main features of how a Report is handled.

The Filing of a Notice of Intent to Make a Motion. Before making an allowable motion at an Association Technical Meeting, the intended maker of the motion must file, in advance of the session, and within the published deadline, a Notice of Intent to Make a Motion. A Motions Committee appointed by the Standards Council then reviews all notices and certifies all amending motions that are proper. The Motions Committee can also, in consultation with the makers of the motions, clarify the intent of the motions and, in certain circumstances, combine motions that are dependent on each other together so that they can be made in one single motion. A Motions Committee report is then made available in advance of the meeting listing all certified motions. Only these Certified Amending Motions, together with certain allowable Follow-Up Motions (that is, motions that have become necessary as a result of previous successful amending motions) will be allowed at the Association Technical Meeting.

Consent Documents. Often there are codes and standards up for consideration by the membership that will be noncontroversial and no proper Notices of Intent to Make a Motion will be filed. These “Consent Documents” will bypass the Association Technical Meeting and head straight to the Standards Council for issuance. The remaining documents are then forwarded to the Association Technical Meeting for consideration of the NFPA membership.

What Amending Motions Are Allowed. The Technical Committee Reports contain many Proposals and Comments that the Technical Committee has rejected or revised in whole or in part. Actions of the Technical Committee published in the ROP may also eventually be rejected or revised by the Technical Committee during the development of its ROC. The motions allowed by NFPA rules provide the opportunity to propose amendments to the text of a proposed code or standard based on these published Proposals, Comments, and Committee actions. Thus, the list of allowable motions include motions to accept Proposals and Comments in whole or in part as submitted or as modified by a Technical Committee action. Motions are also available to reject an accepted Comment in whole or part. In addition, Motions can be made to return an entire Technical Committee Report or a portion of the Report to the Technical Committee for further study.

The NFPA Annual Meeting, also known as the NFPA Conference & Expo, takes place in June of each year. A second Fall membership meeting was discontinued in 2004, so the NFPA Technical Committee Report Session now runs once each year at the Annual Meeting in June.

Who Can Make Amending Motions. NFPA rules also define those authorized to make amending motions. In many cases, the maker of the motion is limited by NFPA rules to the original submitter of the Proposal or Comment or his or her duly authorized representative. In other cases, such as a Motion to Reject an accepted Comment, or to Return a Technical Committee Report or a portion of a Technical Committee Report for Further Study, anyone can make these motions. For a complete explanation, the NFPA Regs should be consulted.

Action on Motions at the Association Technical Meeting. In order to actually make a Certified Amending Motion at the Association Technical Meeting, the maker of the motion must sign in at least an hour before the session begins. In this way a final list of motions can be set in advance of the session. At the session, each proposed document up for consideration is presented by a motion to adopt the Technical Committee Report on the document. Following each such motion, the presiding officer in charge of the session opens the floor to motions on the document from the final list of Certified Amending Motions followed by any permissible Follow-Up Motions. Debate and voting on each motion proceeds in accordance with NFPA rules. NFPA membership is not required in order to make or speak to a motion, but voting is limited to NFPA members who have joined at least 180 days prior to the Association Technical Meeting and have registered for the meeting. At the close of debate on each motion, voting takes place, and the motion requires a majority vote to carry. In order to amend a Technical Committee Report, successful amending motions must be confirmed by the responsible Technical Committee, which conducts a written ballot on all successful amending motions following the meeting and prior to the document being forwarded to the Standards Council for issuance.

Standards Council Issuance

One of the primary responsibilities of the NFPA Standards Council, as the overseer of the NFPA codes and standards development process, is to act as the official issuer of all NFPA codes and standards. When it convenes to issue NFPA documents, it also hears any appeals related to the document. Appeals are an important part of assuring that all NFPA rules have been followed and that due process and fairness have been upheld throughout the codes and standards development process. The Council considers appeals both in writing and through the conduct of hearings at which all interested parties can participate. It decides appeals based on the entire record of the process as well as all submissions on the appeal. After deciding all appeals related to a document before it, the Council, if appropriate, proceeds to issue the document as an official NFPA code or standard. Subject only to limited review by the NFPA Board of Directors, the decision of the Standards Council is final, and the new NFPA code or standard becomes effective twenty days after Standards Council issuance.

412-1

Report on Proposals A2013 — Copyright, NFPA NFPA 412Report of the Committee on

Aircraft Rescue and Fire Fighting

Robert G. Lindstrom, ChairPro-Tec Fire Services Ltd., OK [U]

Rep. International Association of Fire Chiefs

John W. McDonald, SecretaryUS General Services Administration, VA [E]

Keith W. Bagot, US Federal Aviation Administration, NJ [RT] Peter H. Bordeleau, US Marine Corps, TX [C] Charles Cinquemani, Dallas/Fort Worth International Airport Board, TX [C] Rep. Airports Council International-North America Ralph Colet, JRI Inc., CA [M] Ross A. Davidson, US Department of the Navy, CA [C] Hanh Deniston, Metropolitan Washington Airports Authority, VA [L] Rep. International Association of Fire Fighters Fred B. Goodnight, Amerex Corporation, AL [M] Rep. Fire Equipment Manufacturers’ Association Michael A. Greenup, Los Angeles Fire Department, CA [U] Owen Healey, United Kingdom Civil Aviation Authority, United Kingdom [E] Mark S. Lawler, Omaha Airport Authority, NE [L] Rep. Aircraft Rescue & Fire Fighting Working Group, Inc. Graydon L. Matheson, King County Sheriff’s Office-ARFF Division, WA [U] Robert C. Mathis, The Boeing Company, WA [M] John E. McLoughlin, Fire Research Corporation, MO [M] Paul S. Meyer, Hartsfield Atlanta International Airport, GA [C] Kevin J. Petit, Akron Brass Company, OH [M] Pam L. Phillips, Port Authority of New York & New Jersey, NJ [C] Rep. American Association of Airport Executives Danny M. Pierce, ARFF Solutions, CA [SE] James E. Podolske, Jr., US Department of the Air Force, FL [C] Joseph L. Scheffey, Hughes Associates, Inc., MD [SE] Jason Shively, Oshkosh Corporation, WI [M] Jeremy Souza, Rhode Island Airport Corporation, RI [E] Dirk Steyn, E-One, Inc., FL [M] Marc S. Tonnacliff, US Federal Aviation Administration, DC [E] Pierre Voisine, National Defence Department, Canada, Canada [C]

Alternates

Abdulrahman A. Y. Alsaadi, Department of Civil Aviation, United Arab Emirates [U] (Voting Alt. to Dubai Civil Aviation Dept. Rep.)Alan Black, Dallas/Fort Worth International Airport Board, TX [C] (Alt. to Charles Cinquemani) Edward Bushman, Los Angeles Fire Department, CA [U] (Alt. to Michael A. Greenup) Bradford Colton, American Pacific Corporation, NV [M] (Alt. to Fred B. Goodnight) Robert L. Darwin, Jacobs Technology, VA [C] (Alt. to Ross A. Davidson)Graeme Day, BAA Ltd., United Kingdom [C] (Voting Alt. to BAA Rep.) Richard L. James, III, Hartsfield-Jackson Atlanta International Airport, GA [C] (Alt. to Paul S. Meyer) Ronald E. Jones, E-One, Inc., FL [M] (Alt. to Dirk Steyn) David J. Krajnak, KME Fire Apparatus, PA [M] (Voting Alt. to FAMA Rep.)Randy J. Krause, Port of Seattle Fire Department, WA [U] (Alt. to Robert G. Lindstrom)Douglas C. Mangels, Denver Fire Department, CO [L] (Alt. to Mark S. Lawler) Nicholas M. Subbotin, US Federal Aviation Administration, NJ [RT] (Alt. to Keith W. Bagot)

Nonvoting

L. M. Krasner, Medfield, MA [SE] (Member Emeritus)Thomas J. Lett, Albuquerque Fire & Safety Associates, NM [SE] (Member Emeritus)Francois Villard, Fire Safety Security Crisis Management Training, Switzerland [SE]

Staff Liaison: Kendall Holland

Committee Scope: This Committee shall have primary responsibility for documents on aircraft rescue and fire-fighting services and equipment, for procedures for handling aircraft fire emergencies, and for specialized vehicles used to perform these functions at airports, with particular emphasis on saving lives and reducing injuries coincident with aircraft fires following impact or aircraft ground fires. This Committee also shall have responsibility for documents on aircraft hand fire extinguishers and accident prevention and the saving of lives in future aircraft accidents involving fire.

This list represents the membership at the time the Committee was balloted on the text of this report. Since that time, changes in the membership may have occurred. A key to classifications is found at the front of the document.

The Technical Committee on Aircraft Rescue and Fire Fighting is presenting two Reports for adoption, as follows:

Report I: The Technical Committee proposes for adoption, amendments to NFPA 403, Standard for Aircraft Rescue and Fire-Fighting Services at Airports, 2009 edition. NFPA 403-2009 is published in Volume 9 of the 2012 National Fire Codes and in separate pamphlet form.

The report on NFPA 403 has been submitted to letter ballot of the Technical Committee on Aircraft Rescue and Fire Fighting, which consists of 29 voting members. The results of the balloting, after circulation of any negative votes, can be found in the report.

Report II: The Technical Committee proposes for adoption, amendments to NFPA 412, Standard for Evaluating Aircraft Rescue and Fire-Fighting Foam Equipment, 2009 edition. NFPA 412-2009 is published in Volume 9 of the 2012 National Fire Codes and in separate pamphlet form.

The report on NFPA 412 has been submitted to letter ballot of the Technical Committee on Aircraft Rescue and Fire Fighting, which consists of 29 voting members. The results of the balloting, after circulation of any negative votes, can be found in the report.

412-2

Report on Proposals A2013 — Copyright, NFPA NFPA 412_______________________________________________________________ 412-1 Log #CP1 Final Action: Accept in Principle(Entire Document)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Review entire document to: 1) Update any extracted material by preparing separate proposals to do so, and 2) review and update references to other organizations documents, by preparing proposal(s) as required. Substantiation: To conform to the NFPA Regulations Governing Committee Projects. Committee Meeting Action: Accept in PrincipleCommittee Statement: The committee has reviewed the entire document and has corrected or updated any of the references for extracted material in separate proposals. The committee has also checked and updated cross reference material to ensure that there is consistency between the extracted material in this document and the most current editions of documents from which the material has been extracted. Number Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-2 Log #CP2 Final Action: Accept(1.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:1.1 Scope. This standard establishes test procedures for evaluating the foam fire-fighting equipment installed on aircraft rescue and fire-fighting vehicles designed in accordance with the applicable portions of NFPA 414.Substantiation: These changes were made for document consistency and clarification. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-3 Log #CP29 Final Action: Accept(Chapter 2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 403, Standard for Aircraft Rescue and Fire-Fighting Services at Airports, 2009 edition.NFPA 414, Standard for Aircraft Rescue and Fire-Fighting Vehicles, 201207 edition. 2.4 References for Extracts in Mandatory Sections. NFPA 11, Standard for Low-, Medium-, and High-Expansion Foam, 201005 edition. Substantiation: These changes were made in order to update referenced documents. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-4 Log #1 Final Action: Accept in Principle(3.3.1 Foam)_______________________________________________________________ Submitter: Marcelo M. Hirschler, GBH InternationalRecommendation: Revise definitions to read as follows: 3.3.1* Foam. Fire-fighting foam, within the scope of this standard, is a stable aggregation of small bubbles of lower density than oil or water that exhibits a tenacity for covering horizontal surfaces. Air foam is made by mixing air into a water solution, containing a foam concentrate, by means of suitably designed equipment. It flows freely over a burning liquid surface and forms a tough, air-excluding, continuous blanket that seals volatile combustible vapors from access to air. It resists disruption from wind and draft or heat and flame attack and is capable of resealing in case of mechanical rupture. Firefighting foams retain these properties for relatively long periods of time. 3.3.1.1* Alcohol-Resistant Foam. Used for fighting fires involving water-soluble materials or fuels that are destructive to other types of foams. Some alcohol-resistant foams may be capable of forming a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. 3.3.1.2* Aqueous Film-Forming Foam (AFFF) Concentrate. A concentrated aqueous solution of one or more hydrocarbon or fluorochemical surfactants that forms a foam capable of producing a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. The foam produced from AFFF concentrates is dry-chemical compatible and is therefore suitable for use in combination with that agent. 3.3.1.3* Film-Forming Fluoroprotein (FFFP) Foam Concentrate. A protein-based foam concentrate incorporating fluorinated surfactants that forms a foam capable of producing a vapor-suppressing aqueous film on the surface of

hydrocarbon fuels. This foam may show an acceptable level of compatibility with dry chemicals and may be suitable for use with those agents. A.3.3.1 Foam. Air foam is made by mixing air into a water solution, containing a foam concentrate, by means of suitably designed equipment. It flows freely over a burning liquid surface and forms a tough, air-excluding, continuous blanket that seals volatile combustible vapors from access to air. It resists disruption from wind and draft or heat and flame attack and is capable of resealing in case of mechanical rupture. Firefighting foams retain these properties for relatively long periods of time. A.3.3.1.1 Alcohol-Resistant Foam. Some alcohol-resistant foams may be capable of forming a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. A.3.3.1.2 Aqueous Film-Forming Foam (AFFF) Concentrate. The foam produced from AFFF concentrates is dry-chemical compatible and is therefore suitable for use in combination with that agent. A.3.3.1.3 Film-Forming Fluoroprotein (FFFP) Foam Concentrate. This foam may show an acceptable level of compatibility with dry chemicals and may be suitable for use with those agents.Substantiation: The NFPA Manual of Style requires definitions to be in single sentences and not to contain requirements. The additional sentences of these definitions contain information that should be placed in an annex or elsewhere in the standard. Committee Meeting Action: Accept in PrincipleRevise text to read as follows: 3.3.1 Foam. Fire-fighting foam, within the scope of this standard, is a stable aggregation of small bubbles of lower density than oil or water that exhibits a tenacity for covering horizontal surfaces. Air foam is made by mixing air into a water solution, containing a foam concentrate, by means of suitably designed equipment. It flows freely over a burning liquid surface and forms a tough, air-excluding, continuous blanket that seals volatile combustible vapors from access to air. It resists disruption from wind and draft or heat and flame attack and is capable of resealing in case of mechanical rupture. Fire-fighting foams retain these properties for relatively long periods of time. 3.3.1.1 Alcohol-Resistant Foam. Used for fighting fires involving water-soluble materials or fuels that are destructive to other types of foams. Some alcohol-resistant foams may be capable of forming a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. 3.3.1.2 Aqueous Film-Forming Foam (AFFF) Concentrate. A concentrated aqueous solution of one or more hydrocarbon or fluorochemical surfactants that forms a foam capable of producing a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. The foam produced from AFFF concentrates is dry-chemical compatible and is therefore suitable for use in combination with that agent. 3.3.1.3 Film-Forming Fluoroprotein (FFFP) Foam Concentrate. A protein-based foam concentrate incorporating fluorinated surfactants that forms a foam capable of producing a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. This foam may show an acceptable level of compatibility with dry chemicals and may be suitable for use with those agents.3.3.2* Foam Concentrate. Foam concentrate is a concentrated liquid foaming agent as received from the manufacturer. [11, 201005] For the purpose of this document, “foam concentrate” and “concentrate” are used interchangeably. [11, 2005] A.3.3.2 Foam Concentrate. For the purpose of this document, “foam concentrate” and “concentrate” are used interchangeably. [11, 2010]3.3.1* Foam. A stable aggregation of bubbles of lower density than oil or water. [11,2010]A.3.3.1 Air foam is made by mixing air into a water solution, containing a foam concentrate, by means of suitably designed equipment. It flows freely over a burning liquid surface and forms a tough, air-excluding, continuous blanket that seals volatile combustible vapors from access to air. It resists disruption from wind and draft or heat and flame attack and is capable of resealing in case of mechanical rupture. Fire-fighting foams retain these properties for relatively long periods of time.3.3.1.1* Alcohol-Resistant Foam Concentrate. A concentrate used for fighting fires on water-soluble materials and other fuels destructive to regular, AFFF, or FFFP foams, as well as for fires involving hydrocarbons.[11,2010]A.3.3.1.1 Alcohol-Resistant Foam Concentrate. Some alcohol-resistant foams may be capable of forming a vapor-suppressing aqueous film on the surface of hydrocarbon fuels. 3.3.1.2* Aqueous Film-Forming Foam (AFFF)Concentrate. A concentrate based on fluorinated surfactants plus foam stabilizers to produce a fluid aqueous film for suppressing hydrocarbon fuel vapors and usually diluted with water to a 1 percent, 3 percent, or 6 percent solution. [11,2010]A.3.3.1.2 Aqueous Film-Forming Foam (AFFF) Concentrate. The foam produced from AFFF concentrates is dry-chemical compatible and is therefore suitable for use in combination with that agent. 3.3.1.3* Film-Forming Fluoroprotein (FFFP) Foam Concentrate. A protein-foam concentrate that uses fluorinated surfactants to produce a fluid aqueous film for suppressing hydrocarbon fuel vapors. [11,2010]A.3.3.1.3 Film-Forming Fluoroprotein (FFFP) Foam Concentrate. This foam may show an acceptable level of compatibility with dry chemicals and may be suitable for use with those agents. Committee Statement: The committee agrees with the submitters intent to follow the NFPA MOS, however they have decided to extract the applicable definitions from NFPA 11 as well as add the associated annex materials with those terms.

412-3

Report on Proposals A2013 — Copyright, NFPA NFPA 412Number Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.Comment on Affirmative: DAVIDSON, R.: The committee may wish to reconsider the appropriateness of including alcohol-resistant foam since such foam is not installed in ARFF vehicle foam systems. Additionally, such foam is not defined in NFPA 403 nor is it listed in 403 as an approved ARFF foam agent. DAY, G.: No mention is made of ICAO Level B approved fluorine/organohalogen free fire fighting foam. See 403 3.3.14.6. _______________________________________________________________ 412-5 Log #CP3 Final Action: Accept(Chapter 4)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:Chapter 4 Aircraft Rescue and Fire-Fighting Vehicle Foam Production Performance Testing Substantiation: This change was made for document consistency. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-6 Log #CP4 Final Action: Accept(4.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:4.1 Foam and Foam System Performance Tests.4.1.1 The expansion ratio and 25 percent drainage time are the foam characteristics that shall be determined. Additionally, the foam concentration shall be determined, both as a test of the vehicle proportioning system and to establish the legitimacy of the expansion and drainage data obtained. Foam distribution patterns shall be determined for use in calculating the area of fire that the vehicle is capable of controlling.4.1.1 In addition to manufacturers’ performance testing, ARFF vehicles shall be tested on a schedule set by the AHJ to meet the following criteria; (1) Expansion ratio (2) Drainage 25 percent (3) Proportioning (4) Distribution patternSubstantiation: The committee believes that this text provides the end user with a clearer intent of the requirements. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-7 Log #CP5 Final Action: Accept(4.2.2, 4.2.3, 4.2.4, 4.3, 4.3.1, and 4.3.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Delete the following text:4.2.2 Foam samples shall be obtained by the methods given in 6.3.1.3 of this standard. 4.2.3 Foam samples shall be analyzed for expansion and drainage time using the criteria specified in Section 5.1 of this standard. 4.2.4 Foam samples shall be analyzed for concentration as specified in Section 5.2 of this standard. 4.3 Undertruck Nozzles.4.3.1 The foam distribution pattern shall provide protection for the area beneath the vehicle. 4.3.2 Foam samples shall be collected and analyzed for concentration as specified in Section 5.2 of this standard. Substantiation: The committee has deleted this text as these requirements only led the end user to other parts of the document and are unnecessary and redundant. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-8 Log #CP6 Final Action: Accept(5.1.1, 5.2.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:5.1.1 Foams The foam system shall be tested as specified in 6.3.2 and 6.3.3 of this standard and shall meet at least the performance requirements specified in Table 5.1. 5.2.1 Foam solution concentration shall be tested in accordance with Section 6.2 of this standard.

Substantiation: The committee has made these changes for increased accuracy and for document consistency. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-9 Log #CP7 Final Action: Accept(5.2.4 (New) )_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Add new text to read as follows:5.2.4 For nominal 1 percent concentrates, the concentration shall be between 1.0 percent and 1.3 percent for all nozzles. Substantiation: The committee has added this new requirement to address when this type of foam might be used. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 20 Negative: 6 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.Explanation of Negative: BAGOT, K.: There is not enough supporting documentation to allow the use of 1% foams in ARFF. The original submitter provided a USAF report from the 90’s which only had 3 test fires and no statistical validity. The USAF which sponsored that work did not even take any actions based on the results. BORDELEAU, P.: Per the reference ( P-19 precision metering and one percent AFFF large scale fire performance test Dated April 1992) which was supplied at the committee meeting held in Jan-Feb 2012 concerning 1% Foam. The standard used in the reference stated that the foam concentrate tolerance should be + or - 10% (+ or -.1). the correct concentration for all nozzles should be.9 and 1.1% not 1.0 and 1.3 as listed in the current edition of the revision. MATHESON, G.: The stated allowable foam concentration range of 1.0% to 1.3% seems arbitrary and does not allow for a level slightly below the nominal percent concentration as is done in 5.2.2* & 5.2.3. Also the wording of this proposal does not follow that in 5.2.2* & 5.2.3, as there is no differentiation between the allowable foam concentrations from a turret, hand line, etc. PHILLIPS, P.: Concerns regarding basis for the change. STEYN, D.: Data presented is not current (dates back to April 1992). This issue is not addressed in the MIL specification MIL-F-24385. TONNACLIFF, M.: The information presented at the meeting was not conclusive. The information was based on a report that was more than 20 years old and the data was not current. The data I feel was old and not significant enough to warrant a change in the standard. Also, there is not significant enough use of 1%. Comment on Affirmative: PIERCE, D.: This is in accordance with the ISO 7076-1 requirement. _______________________________________________________________ 412-10 Log #CP8 Final Action: Accept(6.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.1 Preparation for Testing.The following general preparations shall be made prior to conducting concentration, expansion/drainage, and pattern testing: (1) The vehicle water and foam systems shall be verified to be operational. (2) The pressure and flow characteristics of each vehicle outlet shall be verified to be in accordance with NFPA 414. (3) The piping systems shall be flushed. (4)* A sample of foam concentrate from the vehicle concentrate tank shall be obtained to form the baseline for concentration determinations and to determine whether the agent concentrate in the vehicle has been contaminated. This sample shall be compared with a virgin sample of the same concentrate from a new foam container from the same manufacturer.(5) This sample shall be compared with a virgin sample of the same concentrate from a new foam container from the same manufacturer. Substantiation: This change was to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-11 Log #CP9 Final Action: Accept(6.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.2 Foam Solution Concentration Determination. 6.2.1* Foam solution concentration shall be determined using one of the following methods as described in 6.2.2 or 6.2.3. When testing foam concentration from vehicles, the lowest flow rate outlet shall be tested first. One handheld refractometer or one handheld conductivity meter suitable for the foam concentrate being tested shall be used. Method B (in 6.2.3) shall be used only when using a refractometer. Refractive index readings shall be taken by placing a few drops of solution on the refractometer prism, closing the cover

412-4

Report on Proposals A2013 — Copyright, NFPA NFPA 412plate, and observing the scale reading at the dark field intersection. Or, if using conductivity, the probe shall be dipped into the sample and the digital scale read.6.2.1.1 When testing foam concentration from vehicles, the lowest flow rate outlet shall be tested first. 6.2.1.2 One handheld refractometer or one handheld conductivity meter suitable for the foam concentrate being tested shall be used. 6.2.1.3 Method B (in 6.2.3) shall be used only when using a refractometer. 6.2.1.4 Refractive index readings shall be taken by placing a few drops of solution on the refractometer prism, closing the cover plate, and observing the scale reading at the dark field intersection. 6.2.1.5 Or, if using conductivity, the probe shall be dipped into the sample and the digital scale read. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-12 Log #CP10 Final Action: Accept(6.2.2.2.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.2.2.2.2 The graduated cylinders shall then be filled to the 100 mL mark with water. After thoroughly mixing, a refractive index reading shall be taken of each standard. A plot shall be made on graph paper of the scale reading against the known foam solution concentrates and shall serve as a calibration curve for this particular series of foam tests.6.2.2.2.2.1 After thoroughly mixing, a refractive index or conductivity reading shall be taken of each standard. 6.2.2.2.2.2 A plot shall be made of the scale reading against the known foam solution concentrates and shall serve as a calibration curve for this particular series of foam tests. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-13 Log #CP26 Final Action: Accept(6.2.2.2.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Add annex notation to this section. Substantiation: This addition of an annex item to this section was done for document consistency. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-14 Log #CP11 Final Action: Accept(6.2.2.3)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.2.2.3* Test Sample Concentration. Portions of solution drained during the drainage test described in 6.3.2.2 shall be used as a source of test sample for the concentration determination. Refractive index or conductivity readings of the test sample shall be compared to the calibration curve and the corresponding foam solution concentration read from the graph. 6.2.2.3.1 Portions of solution drained during the drainage test described in 6.3.2.2 shall be used as a source of test sample for the concentration determination. 6.2.2.3.2 Refractive index or conductivity readings of the test sample shall be compared to the calibration curve and the corresponding foam solution concentration read from the graph. A.6.2.2.3 Because of the high sensitivity of the conductivity meter, it is necessary to collect a larger sample of drainage before making the determination. This will allow for the variation in conductivity of the drained liquid caused by small changes in the chemical composition of AFFF solution as it drains over a period of time. The equipment used to determine concentration should enable the user to accurately measure whether the foam solution produced by proportioning equipment is within the tolerance specified in 5.2.2 and 5.2.3. Examples include one handheld refractometer— American Optical Co. Model No. 10430 or equivalent — or one handheld conductivity meter — Omega Model CDH-70 or equivalent. ATAGO Co. Ltd. Model No. N10, AO Model No. 10441, or equivalent showing 0–10 on the Brix scale is recommended to enable low readings given by AFFF solutions to be read easily. Conductivity meters should

have an automatic temperature compensation feature, and should measure a conductivity range of 0 - 199.9 µS/cm in a low scale, and 0 - 199.9 mS/cm in a high scale. However, low-range refractometers (e.g., 0–10 Brix) might not be able to provide a 100 percent concentration reading of the foam concentrate when using Method B. This is particularly true when using 1 percent and 3 percent foam concentrates. Substantiation: These changes were made to comply with the NFPA Manual of Style. The committee also removed product specific items from the annex as well as some text that was not in the correct place. The newly added text to the annex was done so to provide the end user with clarity and accuracy. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-15 Log #CP12 Final Action: Accept(6.2.3)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.2.3 Method B (Refractometer Only). A calculation shall be made using the following apparatus and procedure described in 6.2.3.1and 6.2.3.2.6.2.3.1* Apparatus. The concentration determination shall be made using the following apparatus: (1) Three clean plastic or glass containers (2) One dropper or pipette (3) A refractometer with a scale capable of reading the complete refractive index for the samples. A.6.2.3.1 However, low-range refractometers (e.g., 0–10 Brix) might not be able to provide a 100 percent concentration reading of the foam concentrate when using Method B. This is particularly true when using 1 percent and 3 percent foam concentrates. Substantiation: These changes were made in order to comply with the NFPA Manual of Style and to also correct some text that was incorrectly placed in the annex in the current edition. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-16 Log #CP14 Final Action: Accept(6.2.3.3)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.2.3.3 Test Sample Concentration. Determine the foam concentration of the foam solution sample by calculating the following formula using the readings obtained in the steps given in 6.2.3.1(4), 6.2.3.1(6), and 6.2.3.1(8) above:Substantiation: These changes were editorial in nature. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-17 Log #CP13 Final Action: Accept(6.3)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.3 Foam Tests. Foam Expansion and Drainage Determination.6.3.1 General Requirements for Expansion and DrainageMethods.6.3.1.3 Foam samples selected for analysis shall be representative of the foam produced by the nozzle as it would be applied to the fire hazard. This shall be accomplished by placing a foam sample collector in the center of the ground pattern as determined in the nozzle pattern test. 6.3.1.4 This shall be accomplished by placing a foam sample collector in the center of the ground pattern as determined in the nozzle pattern test.6.3.1.5 Apparatus. The expansion and drainage determinations shall be made using the following apparatus, in addition to the specific apparatus required for Method A or Method B: (1) Stopwatch (2) Scale / balance (3) Straightedge Substantiation: These changes were made in order to comply with the NFPA Manual of Style as well as to provide the end user with a detailed list of tools that can be used. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.

412-5

Report on Proposals A2013 — Copyright, NFPA NFPA 412_______________________________________________________________ 412-18 Log #CP17 Final Action: Accept(6.3.2.1.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.3.2.1.2 The foam sample shall be collected in a standard 1000 mL capacity graduated cylinder. The cylinder shall be cut off at the 1000 mL mark to ensure a fixed volume of foam as a sample. The cylinder shall be marked in 10 mL graduations below the 100 mL mark.6.3.2.1.2.1 The cylinder shall be cut off at the 1000 mL mark to ensure a fixed volume of foam as a sample. 6.3.2.1.2.2 The cylinder shall be marked in 10 mL graduations below the 100 mL mark. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-19 Log #CP18 Final Action: Accept(6.3.2.2.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.3.2.2.1 The empty weight of the foam sample container shall be recorded to the nearest gram on a scale/balance having a maximum capacity sufficient to weigh the foam sample container and the foam sample. The foam sample collector shall then be located in the center of the discharge pattern determined in Section 6.5. The foam sample container shall be positioned at the bottom of the foam collector so that the foam hitting the collector flows into the container. The foam nozzle shall be aimed so that the foam deflects off the side of the foam collector, adjusted to its normal operating pressure, and then moved so as to discharge foam onto the foam sample collector. As soon as the foam sample container has been completely filled with foam, the discharge nozzle shall be shut off and the timing of the 25 percent drainage started.6.3.2.2.1.1 The foam sample collector shall then be located in the center of the discharge pattern determined in Section 6.5. 6.3.2.2.1.2 The foam sample container shall be positioned at the bottom of the foam collector so that the foam hitting the collector flows into the container. 6.3.2.2.1.3 The foam nozzle shall be aimed so that the foam deflects off the side of the foam collector, adjusted to its normal operating pressure, and then moved so as to discharge foam onto the foam sample collector. 6.3.2.2.1.4 As soon as the foam sample container has been completely filled with foam, the discharge nozzle shall be shut off and the timing of the 25 percent drainage started.Substantiation: These changes were made in order to comply with the NFPA Manual of Style and to provide the end user with some clarification as to what devices can be used. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-20 Log #2 Final Action: Accept in Principle(6.3.2.2.2, 6.3.2.2.3, and 6.3.2.2.x)_______________________________________________________________ Submitter: Kevin J. Petit, Akron Brass CompanyRecommendation: Revise text to read as follows: 6.3.2.2.2 The foam sample container shall be removed from the base of the foam collector, excess foam struck off the top of the foam container using a straight edge, and any remaining foam wiped from the outside surface of the container. The container shall then be placed on the balance. The total weight of the foam sample and container shall be determined to the nearest gram. The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters. 6.3.2.2.3* The foam sample container shall be placed on a level surface at a convenient height. At 30-second intervals, the level of accumulated solution in the bottom of the cylinder shall be noted and recorded. The drainage shall be recorded until the liquid level reaches 95ml for non-aspirated nozzles, 60 ml for air-aspirated nozzles. The drainage time versus the volume relationship shall be recorded until the 25 percent volume has been exceeded. The 25 percent drainage time shall then be interpolated from the data. Insert new paragraph after 6.3.2.2.3* 6.3.2.2.x The container shall then be placed on the balance. The total weight of the foam sample and container shall be determined to the nearest gram. The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters. The 25 percent drainage time shall then be interpolated from the drainage data collected in 6.3.2.2.3.

Substantiation: As the document is currently written, the recording of the drainage data is delayed until after the foam sample container is dried and weighed. This frequently causes the 30 second and 1 minute readings to be missed. Weighing the foam sample container at the end of the test will not change the results and it will permit the recording of the 30 second and 1 minute drainage readings. The 95 ml and 60 ml values are added to 6.3.2.2.3 to provide guidance as to how long drainage needs to be monitored to capture the ¼ drain time. Committee Meeting Action: Accept in PrincipleRevise text to read as follows:6.3.2.2.2 The foam sample container shall be removed from the base of the foam collector, excess foam struck off the top of the foam container using a straight edge, and any remaining foam wiped from the outside surface of the container. The container shall then be placed on the balance. The total weight of the foam sample and container shall be determined to the nearest gram. The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters. 6.3.2.2.3* The foam sample container shall be placed on a level surface at a convenient height. 6.3.2.2.3.1 At 30-second intervals, the level of accumulated solution in the bottom of the cylinder shall be noted and recorded. 6.3.2.2.3.2 The drainage shall be recorded until the liquid level reaches 95ml for non-aspirated nozzles, 60 ml for air-aspirated nozzles. The drainage time versus the volume relationship shall be recorded until the 25 percent volume has been exceeded. The 25 percent drainage time shall then be interpolated from the data. NEW 6.3.2.2.X The container shall then be placed on the scale/balance. NEW 6.3.2.2.X.1 The total weight of the foam sample and container shall be determined to the nearest gram. NEW 6.3.2.2.X.2 The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. NEW 6.3.2.2.X.3 The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters. NEW 6.3.2.2.X.4 The 25 percent drainage time shall then be interpolated from the drainage data collected in 6.3.2.2.3.1 and 6.3.2.2.3.2Committee Statement: The committee agrees with the submitters intent and proposed changes, however the text needs to comply with the NFPA MOS, which the committee made the appropriate adjustments to ensure MOS compliance and renumbering. Number Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-21 Log #CP19 Final Action: Accept(6.3.3.1.1 and Figure 6.3.3.1.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text and figure title to read as follows:6.3.3.1.1 The object is to obtain a sample of foam that is typical of that to be applied to the burning fuel surface under anticipated fire conditions. The foam collector shall be constructed as specified in Figure 6.3.3.1.1. 6.3.3.1.1.1 The foam collector shall be constructed as specified in Figure 6.3.3.1.1.1 FIGURE 6.3.3.1.1.1 Foam Sample Collector Method BSubstantiation: These changes were made in order to comply with the NFPA Manual of Style and for document consistency. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-22 Log #4 Final Action: Reject(Figure 6.3.3.1.2)_______________________________________________________________ Submitter: Kevin J. Petit, Akron Brass CompanyRecommendation: Revise text to read as follows: 1/16 in. (1.6 mm) 3/32 in. (2.4 mm) inside diameterSubstantiation: The 1/16” (1.6 mm) opening in the valve can lead to misleading foam drainage data. For example, an experiment was conducted where 533 mL of water was placed into the 1600 mL foam sample container. This is the amount of liquid in the container for a foam of 3:1 expansion. The valve on the bottom of the container was opened, and the amount of time for 133 mL of liquid to drain out was recorded. 133 mL was chosen since it is the ¼ volume of 533 mL. The time required for 133 mL to drain out was 54 seconds. The minimum allowable per table 5.1 is 45 seconds. Therefore, it is possible for pure water to meet the ¼ drain requirement of 45 seconds listed in table 5.1 for Method ‘B’. Increasing the opening to 3/32” (2.4 mm) reduces the time required for the same volume to 22 seconds. Using this modification, it is not possible for pure water to pass the ¼ drain requirement of 45 seconds listed in table 5.1 for Method ‘B’.

412-6

Report on Proposals A2013 — Copyright, NFPA NFPA 412Committee Meeting Action: RejectCommittee Statement: The committee rejects this proposal because in order to change the standard the test method should be coordinated with UL. Number Eligible to Vote: 29 Ballot Results: Affirmative: 25 Negative: 1 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.Explanation of Negative: SOUZA, J.: The equipment described in Figure 6.3.3.1.2 was shown by the submitter to allow plain water to be deemed acceptable using the current configuration. The testing equipment should be changed to a configuration that provides valid data as per the submitter’s proposal, irrespective of coordination with other agencies. Comment on Affirmative: STEYN, D.: Note should be added to state that this test method (Method B) may not be accurate under all circumstances. _______________________________________________________________ 412-23 Log #CP20 Final Action: Accept(6.3.3.1.2 and Figure 6.3.3.1.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text and figure title to read as follows:6.3.3.1.2 The foam sample shall be collected in a cylindrical 1600 mL container. The foam sample container shall be constructed as specified in Figure 6.3.3.1.2.6.3.3.1.2.1 The foam sample container shall be constructed as specified in Figure 6.3.3.1.2.1 FIGURE 6.3.3.1.2.1 1600 mL Foam Sample Container.Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-24 Log #3 Final Action: Accept in Principle(6.3.3.1.3, 6.3.3.2.2, 6.3.3.2.3, 6.3.3.2.x, and 6.3.3.2.4)_______________________________________________________________ Submitter: Kevin J. Petit, Akron Brass CompanyRecommendation: Revise text to read as follows:6.3.3.1.3 Foam drainage will be recorded using a 100 mL graduated beaker for foams with expected expansion ratios above 5:1, and a 250 mL graduated cylinder for foams with expected expansion ratios of 5:1 or below. The weight of the appropriate empty graduated cylinder shall be recorded before the test. 6.3.3.2.2 The foam sample container shall be removed from the base of the foam collector, excess foam struck off the top of the foam container using a straight edge, and any remaining foam wiped from the outside surface of the container. The container shall then be placed on the balance. The total weight of the foam sample and container shall be determined to the nearest gram. The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in millileters.6.3.3.2.3 The foam sample container shall then be placed on a suitable support and a graduated cylinder placed below the drain spout. At 30-second intervals, the accumulated solution in the bottom of the foam sample container shall be drawn off into the graduated cylinder and the amount recorded. If the expected expansion ration is more than 5:1, then a 100 ml graduated cylinder shall be used to collect the drainage; if the expected expansion ratio is 5:1 or less, then a 250 ml graduated cylinder shall be used. The drainage shall be recorded until the liquid level reaches 150 mL for non-aspirated nozzles, 95 mL for air-aspirated nozzles. Insert new paragraph after 6.3.3.2.3: 6.3.3.2.x The foam sample container complete with any remaining foam will then be weighed to the nearest gram. The graduated cylinder used to record the drainage and the collected foam will then be weighed in the same manner. The net weight of the foam sample is determined by adding these two weights together and subtracting the weight of the empty foam sample container and the empty graduated cylinder. The net weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters 6.3.3.2.4* Foam samples shall be weighed to the nearest gram. The expansion of the foam shall be calculated by the following equation: Expansion=1600/(full weight)-(empty weight in grams) net weight of foam sample in gramsSubstantiation: As the document is currently written, the recording of the drainage data is delayed until after the foam sample container is dried and weighed. This frequently causes the 30 second and 1 minute readings to be missed. Weighing the foam sample container at the end of the test will not change the results and it will permit the recording of the 30 second and 1 minute drainage readings. The 150 mL and 95 mL values are added to 6.3.3.2.3 to provide guidance as to how long drainage needs to be monitored to capture the ¼ drain time. Committee Meeting Action: Accept in PrincipleRevise text to read as follows:6.3.3.1.3 Foam drainage will be recorded using a 100 mL graduated beaker for

foams with expected expansion ratios above 5:1, and a 250 mL graduated cylinder for foams with expected expansion ratios of 5:1 or below. 6.3.3.1.4 The weight of the appropriate empty graduated cylinder shall be recorded before the test. 6.3.3.2.2 The foam sample container shall be removed from the base of the foam collector, excess foam struck off the top of the foam container using a straight edge, and any remaining foam wiped from the outside surface of the container. The container shall then be placed on the balance. The total weight of the foam sample and container shall be determined to the nearest gram. The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in millileters.6.3.3.2.3 The foam sample container shall then be placed on a suitable support and a graduated cylinder placed below the drain spout. 6.3.3.2.3.1 At 30-second intervals, the accumulated solution in the bottom of the foam sample container shall be drawn off into the graduated cylinder and the amount recorded. If the expected expansion ration is more than 5:1, then a 100 ml graduated cylinder shall be used to collect the drainage; if the expected expansion ratio is 5:1 or less, then a 250 ml graduated cylinder shall be used. 6.3.3.2.3.2 The drainage shall be recorded until the liquid level reaches 150 mL for non-aspirated nozzles, 95 mL for air-aspirated nozzles. 6.3.3.2.4 The foam sample container complete with any remaining foam will then be weighed to the nearest gram. 6.3.3.2.4.1 The graduated cylinder used to record the drainage and the collected foam will then be weighed in the same manner. 6.3.3.2.4.2 The net weight of the foam sample is determined by adding these two weights together and subtracting the weight of the empty foam sample container and the empty graduated cylinder. 6.3.3.2.4.3 The net weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters 6.3.3.2.54* Foam samples shall be weighed to the nearest gram. The expansion of the foam shall be calculated by the following equation: Expansion=1600/(full weight)-(empty weight in grams) net weight of foam sample in gramsCommittee Statement: The committee agrees with the submitters intent and proposed changes, however the text needs to comply with the NFPA MOS, which the committee made the appropriate adjustments to ensure MOS compliance and renumbering. Number Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-25 Log #CP21 Final Action: Accept(6.3.3.2.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.3.3.2.1 The empty weight of the foam sample container shall be recorded to the nearest gram on a scale/balance having a maximum capacity sufficient to weigh the foam sample container, on a suitable support, and the foam sample. The foam sample collector shall then be located in the center of the discharge pattern determined in Section 6.5 of this standard. The foam sample container shall be positioned at the bottom of the foam collector so that the foam hitting the collector will flow into the container. The foam nozzle shall be aimed so that the foam deflects off the side of the foam collector, adjusted to its normal operating pressure, and then moved so as to discharge foam onto the foam sample collector. As soon as the foam sample container has been completely filled with foam, the discharge nozzle shall be shut off and the timing of the 25 percent drainage started. 6.3.3.2.1.1 The foam sample collector shall then be located in the center of the discharge pattern determined in Section 6.5 of this standard. 6.3.3.2.1.2 The foam sample container shall be positioned at the bottom of the foam collector so that the foam hitting the collector will flow into the container. 6.3.3.2.1.3 The foam nozzle shall be aimed so that the foam deflects off the side of the foam collector, adjusted to its normal operating pressure, and then moved so as to discharge foam onto the foam sample collector. 6.3.3.2.1.4 As soon as the foam sample container has been completely filled with foam, the discharge nozzle shall be shut off and the timing of the 25 percent drainage started. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-26 Log #CP22 Final Action: Accept(6.3.3.2.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows: 6.3.3.2.2 The foam sample container shall be removed from the base of the foam collector, excess foam struck off the top of the foam container using a straight edge, and any remaining foam wiped from the outside surface of the

412-7

Report on Proposals A2013 — Copyright, NFPA NFPA 412container. The container shall then be placed on the balance. The total weight of the foam sample and container shall be determined to the nearest gram. The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters. 6.3.3.2.2.1 The container shall then be placed on the scale/balance. 6.3.3.2.2.2 The total weight of the foam sample and container shall be determined to the nearest gram. 6.3.3.2.2.3 The weight of the foam sample in the container shall be determined by subtracting the weight of the empty container from the weight of the container filled with the foam. 6.3.3.2.2.4 The weight of the foam sample in grams shall be divided by 4 to obtain the equivalent 25 percent drainage volume in milliliters. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-27 Log #CP23 Final Action: Accept(6.5)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.5 Turret Ground Pattern Test.6.5.1 Prior to the start of the test, the water tank shall be full, the foam concentrate tank shall be full with the type of foam concentrate to be used during actual emergencies, and the proportioner shall be set for normal fire-fighting operation. For premixed systems, the tank shall be full with the premixed solution in the correct proportion for normal fire-fighting operations. 6.5.1.1 For premixed systems, the tank shall be full with the premixed solution in the correct proportion for normal fire-fighting operations. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-28 Log #CP24 Final Action: Accept(6.5.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.5.2* Discharge tests shall be conducted to establish the fire-fighting foam discharge patterns produced and the maximum range attainable by the turret nozzle. The test shall be conducted under wind conditions of 5 mph (8 km/h) or less. To determine maximum discharge range, the turret nozzles shall be tilted upward to form a 30-degree angle with the horizontal.6.5.2.1 The test shall be conducted under wind conditions of 5 mph (8 km/h) or less. 6.5.2.2 To determine maximum discharge range, the turret nozzles shall be tilted upward to form a 30-degree angle with the horizontal. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.Comment on Affirmative: DAVIDSON, R.: The committee may wish to consider whether a 30 degree turret discharge angle provides maximum range. Theoretically under ideal conditions (no air resistance and zero wind) 45 degrees provides maximum range. Prior testing with turrets in real life air resistance and varying wind conditions, shows that max range is usually with turret elevation of 35-40 degrees. _______________________________________________________________ 412-29 Log #CP25 Final Action: Accept(6.5.3)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:6.5.3 Foam shall be discharged onto a paved surface for a period of 30 seconds at the specified pressure, in both the straight stream and fully dispersed nozzle settings. Immediately after foam discharge has stopped, markers shall be placed around the outside perimeter to preserve the identity of the foam pattern as it fell on the ground. For purposes of defining the edge of the pattern, any foam less than ½ in. (12.7 mm) in depth shall be disregarded. Distances between markers shall be plotted on graph paper. The vertical axis shall show the reach, and the horizontal axis shall show the pattern width, for each nozzle setting. The distance from the nozzle to the end of the effective foam pattern shall be measured and plotted on the graph paper.

6.5.3.1 Immediately after foam discharge has stopped, markers shall be placed around the outside perimeter to preserve the identity of the foam pattern as it fell on the ground. 6.5.3.2 For purposes of defining the edge of the pattern, any foam less than ½ in. (12.7 mm) in depth shall be disregarded. 6.5.3.3 Distances between markers shall be plotted on graph paper. 6.5.3.4 The vertical axis shall show the reach, and the horizontal axis shall show the pattern width, for each nozzle setting. 6.5.3.5 The distance from the nozzle to the end of the effective foam pattern shall be measured and plotted on the graph paper. Substantiation: These changes were made in order to comply with the NFPA Manual of Style. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-30 Log #CP15 Final Action: Accept(A.6.3.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows and delete annex notation from the main body of the document: A.6.2.2.2.2 6.3.2 Method A procedures are used to provide a reference line on which the reading of the solution tested is plotted to determine its exact concentration. Figure A.6.2.2.2.2 3.2(a) shows a typical graph using 6 percent AFFF solution and Figure A.6.2.2.2.2 3.2(b) shows a typical graph using a 6 percent FFFP solution. Substantiation: This annex item has been moved and added to as another annex item as it was incorrectly placed in this edition. The re-numbering has occurred for document consistency. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-31 Log #CP16 Final Action: Accept(Figure A.6.3.2(a), Figure A.6.3.2(b), and Figure 6.3.2.1.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise figure numbering and text to read as follows:FIGURE A.6.2.2.2.2 3.2(a) Typical Graph Using AFFF (6%).FIGURE A.6.2.2.2.2 3.2(b) Typical Graph Using FFFP (6%).FIGURE 6.3.2.1.1 AFFF Foam Sample Collector, Method A.Substantiation: These changes were editorial in nature and for document consistency. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P._______________________________________________________________ 412-32 Log #CP27 Final Action: Accept(B.1.1 and B.1.3.1)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Revise text to read as follows:B.1.1 Basic Extinguishing Capability. The following is a suggested method for evaluating the basic extinguishing capability of the foam fire-fighting system. This method can be used to determine fire fighting capability of systems that do not meet the requirements listed in NFPA 414. B.1.3.1 The resistance of the foam blanket to the fire is important. Wind plays a big role in the determination of this property and repeat results are difficult to obtain with an outdoor test. Another factor, but one easier to control, is the size of the fire area at the start of re-ignition. To standardize this, a short section of stovepipe 12 in. (30.5 cm) in diameter is dropped into the foam blanket like a cookie cutter. The foam is removed from the inside, and the fuel surface is ignited and allowed to burn for 1 minute before the stovepipe is removed. The rate of enlargement of the fire is then observed. A long period of confinement is desired. The delay period after end of foam application and start of re ignition can be varied, but for comparative tests, it must be kept constant. Burnback performance requirements can be referenced using Underwriters Laboratories Inc. Standard UL 162, Standard for Foam Equipment and Liquid Concentrates or U.S. Military Specification MIL-F-24385, Fire Extinguishing Agent, Aqueous Film-Forming Foam (AFFF), Liquid Concentrate for Fresh and Sea Water.Substantiation: The committee has made these changes in order to provide better direction and use of this standard for the end user. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.

412-8

Report on Proposals A2013 — Copyright, NFPA NFPA 412_______________________________________________________________ 412-33 Log #CP28 Final Action: Accept(C.1.2)_______________________________________________________________ Submitter: Technical Committee on Aircraft Rescue and Fire Fighting, Recommendation: Add new text to read as follows:C.1.2 Other Publications. Standard UL 162, Standard for Foam Equipment and Liquid Concentrates.U.S. Military Specification MIL-F-24385, Fire Extinguishing Agent, Aqueous Film-Forming Foam (AFFF), Liquid Concentrate for Fresh and Sea Water.Substantiation: The committee has added these references to the document as an added resource for the end user. Committee Meeting Action: AcceptNumber Eligible to Vote: 29 Ballot Results: Affirmative: 26 Ballot Not Returned: 3 Deniston, H., Greenup, M., Voisine, P.