2. Moist Air Properties and Air Conditioning Processes

Embed Size (px)

Citation preview

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    1/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Chapter 2.Moist Air Properties and Air-Conditioning Processes

    2.1 Moist Air and Its Properties2.2 Methods of Measurements and Analysis2.3 Typical Air Conditioning Processes2.4 Characteristics of Real Systems2.5 Psychrometric Analysis of Complete Systems

    Readings: McQuiston & Parker (M&P) Ch 3 Texts on moist air in most thermodynamics books

    2.1 Moist Air and Its Properties

    2.1.1 Air Composition (two components)

    Dry air composition (volume fraction):

    Nitrogen 78.084% Minor gases 0.003%Oxygen 20.948% Water VaporArgon 0.934% Dust, Fog, MicrobeCarbon dioxide 0.031%

    2.1.2 Ideal Gas Law

    For dry air

    ==== R)lbf)/(lbm53.352(ft965.28

    32.1545

    a

    ua M

    R R

    For water vapor

    ==== R)lbf/(lbm85.78ft02.18

    32.1545v

    uv M

    R R

    The following data for US STANDARD ATSMOPHERE are from ASHARE Handbook ofFundamentals (Chapter6). Several assumptions are introduced such as:

    The atmosphere consists of dry air that behaves as an ideal gas.(see pg.50 in thetextbook)

    1

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    2/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Reference p and T are functions of altitude. Formula for p as function of elevation Z: p[psi] = 14.696 (1-6.8753 10 -6 Z[ft]) 5.2559 p[bar] = 1.013 (1-2.256 10 -6 Z[m]) 5.2559

    2

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    3/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Example

    Sea level: p=14.696 psi, T=59 oF

    3.1.3 Fundamental Parameters

    (1) Pressure

    The air layer above the earth forms atmospheric pressure. Atmospheric pressure: sea level 14.692 psi elevation of 6600 ft, 11.513 psi

    (note: pressure inch mercury)a,b ---Table 3-2 in M&P

    Partial pressure (Daltons Law)

    Component/partial pressure: p p p p= + + +1 2 3 ... Gibbs Daltons Law for Moist air:

    pa dry air component (constant) pv vapor component (change with moisture content)

    Note: When applying ideal gas law to each component of a mixture (e.g., moist air), should use partial pressure for the component.

    For component i: P ivi=R iT i

    Where P i is partial pressure for component i.

    Example

    One lbm H 2O vapor in 100 lbm dry air at standard pressure.(a) What is p v vapor pressure? (b) What is saturation T at this p v?

    3

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    4/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    (a) ,

    (b) Saturation: State of maximum concentration for mixture components.

    (2) Temperature

    Temperature is the macro results of molecular kinetics.

    0th law of thermodynamicsT T T T T T a b b c a= = c

    Table 2.1 Relationship between Different Temperature Scales

    Relationshipbetween

    Kelvin (K) Celsius ( C) Fahrenheit( F)

    Rankine (R)

    Kelvin ( K)--

    K C = +o 27315. K R= 59

    Celsius ( C) o C K = 27315.--

    o o

    C F = 59

    32( )

    o

    C R= 59

    27315.

    Fahrenheit

    ( F)o o

    F C = +95

    32 --

    oF = R-459.67

    Rankine (R) R K = 9

    5 --

    ExampleTemperature in Celsius Kelvin Fahrenheit RankineWater Boiling 100C 373.15K 212F 617.67 R

    Ice Point 0C 273.15K 32F 491.67 RAbsolute Zero -273.15 C 0 K -459.67 F 0R

    4

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    5/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    (3) Humidity Ratio, W

    Definition: W mm

    Kg Kg va

    drry air = ( / )

    P

    i.e. 1 kg dry air + w kg water vapor = (1+W) kg moist air

    where P is the atmospheric pressure. Because , thus W p pv > T at sgas

    P

    vapor

    T > T sat superheated vapor

    P

    T = T sat saturated

    liquid

    P

    vapor

    T = T sat saturated vapor

    P

    vapor

    T = T sat quality vapor

    liquid

    P

    T < T sat subcooled

    liquid

    P

    5

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    6/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    = = = p p

    p p

    p pvv s

    v

    sv s s

    ,,100% 100%

    pv = partial pressure of the water vapor in the air p s = partial pressure of the water vapor in a saturated mixture under the same temperature

    Dry air: =0% Saturated air: =100%Difference between W and :

    Moist air: W p

    P pv

    v

    =

    0622.

    Saturated air: W p

    P p s s

    s

    =

    0622.

    =

    =

    =

    W W

    p p

    P p P p

    P p P p

    W W

    P p P p

    s

    v

    s

    s

    v

    s

    v

    s

    v

    s

    100%

    Since P>> p v and P >>p s

    Further

    Example

    Determine the humidity ratio of moist air at a temperature of 24 C and a relative humidity of50% at a standard pressure 1atm

    Given: T, Find: W

    Solution:

    (5) Dewpoint Temperature, T d

    Td the saturated temperature of a given mixture at the same pressure and humidity ratio.

    6

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    7/37

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    8/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.2 Methods of Measurement and Analysis

    2.2.1 Measurement of air temperature

    Liquid-in-glass thermometers Thermocouples

    2.2.2 Measurement of pressure

    Absolute pressure (vacuum tube with mercury) Differential pressure

    ManometersPressure transducer

    2.2.3 Measurement of other parameters of moist air

    To determine state of moist air, one property in addition to the pressure and temperaturemust be known. It can be v, I, , or W. However, none of them can be directly measured. As analternative, we seek an indirect measuring technique. In this section, the method used todetermine air humidity will be introduced.

    Adiabatic saturation device

    First we look at a special process:

    Adiabatic saturation devicewater

    ia,1W 1 iv,1 T 1

    ia,2W 2 iv,2 T 2

    The equation that describes above process is:

    1st

    Law

    The process is adiabatic, and only flow work is present.:

    where , , and form mass balanceaa mW mm &&& 11 += aa mW mm &&& 22 +=

    8

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    9/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    The equation that describe above process becomes:

    )()()()()( out out added inin

    vapor water air dryadded vapor water vapor water air dry +=++

    so we have

    where i fg is enthalpy difference between liquid water and saturated vapor at the temperature T 2

    W p P p

    v

    v2

    2

    2

    0622=

    . ,

    ,

    Then the state of moist are can be determined.

    T2 is called wet-bulb temperature .

    Example

    Find W and of the above adiabatic saturation device.

    Given: P=1.01325 105

    Pa, T 1=30C, T 2=26 CFind: W 1 , 1

    Solution:

    Since the state 2 is in saturation, from the Table A-1b (McQuiston & Paker, p587), we can find:

    for T 2 = 26 C, pv,2 = ps = 0.03363 105 ( =100%), ifg = 2439.1 kJ/kg, i w= 109.07 kJ/kgfor T 1 = 30 C, iv,1 = 2555.3 kJ/kg

    1) Find W 1

    9

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    10/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2) Find 1

    %1001

    1, = s

    v

    p

    p

    pv,1 can be found via

    From Table A-1b

    The Psychrometer

    Psychrometer T WB used in place of T 2 for practical humidity measurement.

    TWB

    TTdry In wet-bulb, heat transfer from air bulb

    p+T DB+T WB =>Moist air state

    Key issues to measure T WB

    Wet bulb unshielded Wet bulb well ventilated (V>100 fpm)

    For thermocouples V could be lower.Then the accuracy is in order of 0.27 oC (0.5 oF).

    10

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    11/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.2.4 The psychrometric chart

    (1) Selection of the Coordinates

    Horizontal coordinate Enthalpy (155 )Vertical coordinate Humidity Ratio

    (2) Dry Bulb Temperature

    )86.13.2501(01.1 T W T i ++= (SI Unit)W iconst T =

    Isothermal lines are not parallel.

    (3) Relative Humidity

    %100622.0,

    ,

    == sv

    s sv

    sv

    p P p P

    W W

    p P

    pW

    Under a certain P , W )()( ,, T f p p f sv sv == From P587 Table A-1b. find W-T relationship

    Approximately W W s

    100% (equal division)

    11

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    12/37

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    13/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    i = (C p,a + W C p,v) T wet + W x 2501 when T wet = const, linear relationship

    i = (C p,a + W C p,v) T wet + W x 2501 + W i w when 100%

    (6) Sensible Heat /Total Heat

    Enthalpy/Humidity ratioSee figure: Primary moist air parameter on the psychrometric chart.

    For specific pressure:

    Repeat the previous problem by using the psychrometric chart.

    Given: T C T C dry wet = =30 26o o

    ,

    W = 0.01971 74%i = 81kJ / Kg v = 0.885 m3 / Kg T dewpo int = 24.7

    o C

    T DB W, T DP

    Find: Primary moist air parameter on psychrometric chart

    Solution:

    From the psychrometric chart (SI Unit)i, T WB

    v

    13

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    14/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Example

    Repeat the previous problem by using the psychrometric chart.

    Given : T C T dry wet = =30 26o o

    , C

    Find: Primary moist air parameter on psychrometric chart

    Solution:

    14

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    15/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.3 Typical Air-Conditioning Process

    Typical Air-Conditioning processes are:

    Sensible Heating / Cooling Cooling and dehumidification Heating and humidification Adiabatic Humidification Adiabatic Mixing of Air

    Governing equations:

    STATE is a point, and PROCESS (sequence of states) is a line on the Chart.

    Process may involve: Sensible Heat (change T DB, constant W) Latent Heat (constant T DB , change W) Both

    2.3.1 Sensible heating and coolingQ&

    am&

    W 1 T1 i1

    On the psychrometric chart

    cooling12

    1 2

    heating

    i Energy conservation (1 st

    Law))( 1212 T T C iiq p == .

    W1 = W 2

    15

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    16/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Example

    Determine the energy (heat flux) required for sensible heating of air at 15 C and 50% RH to32C. Also find 2.

    Given: State 1: 15 C, RH=50%, State 2: 32 CFind : , q& 2

    Solution:

    Heat Flux:

    Relative humidity:

    From the psychrometric chart (the process is a horizontal line):

    Heat flux is

    Relative humidity:

    How to check if W is constant, i.e. no latent heat?

    16

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    17/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.3.2 Cooling and dehumidification

    am&

    Q&

    wm&

    W 1T1 i1

    iw

    Moisture is removed as saturated liquid.

    A 1

    coolin

    B2

    where i w water enthalpy

    W a iW W m )( 21 & is normally small

    Sensible heat:)( 12 T T C q p sensible =&

    Latent heat fg latent iW W q )( 12 =&

    17

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    18/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Example

    Air at 60% RH, T dry =30C, Cooled to 18 C. Determine new , qsensible , qlatent

    Solution:

    new=100%, from the psychrometric chart, we can find

    By using the formula

    Sensible Heat Factor (SHF) isQ

    QS &

    &

    Defines process slope on the chart. Use protractor (semicircular scale) in the upper left hand

    corner to read the sensible heat factor.

    18

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    19/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.3.3 Heating and humidification

    am&

    mw, iw

    W 1T1 i1

    Q

    A

    2

    1

    ratiohumidityenthalpy

    -> Look at the semicircular scale in the psychrometric chart.

    Defines the process slope.

    For adiabatic humidification, then

    Q& = 0i2 - i1 = W iw

    W2 - W 1 = W

    Since iw of the water is rather small, i i 2 1

    19

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    20/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Example

    In Phoenix, it is possible to use evaporative cooling in summer. In a room of 50 m 3, the airtemperature is 45 oC and relative humidity is 20%. Comfort standard allows the relative humidityto be increased to 60% by evaporative cooling. Determine the dry bulb temperature and water

    needed if there is no internal heat source and no air infiltration. Assume local pressure is 101325Pa.

    Solution:

    This is an adiabatic humidification process. The air process in a psychrometric chart is iso-enthalpy. For the psychrometric chart, we can determine the starting humidity ratio and endinghumidity ratio as

    2.3.4 Other Humidity Process

    Steam

    Adiabatic

    Hot water

    Super-heated steam

    20

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    21/37

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    22/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.3.5 Adiabatic Mixing of Air

    m& 1 i1 W 1

    m& 2 i2 W 2

    32

    1

    m& 3i3 W 3

    Eliminate , We obtain3m&

    )()(

    )()(

    232311

    232311

    W W mW W m

    iimiim

    ==

    &&

    &&

    so

    31

    23

    31

    23

    2

    1

    W W W W

    iiii

    mm

    =

    =

    &

    &

    Example

    Return air at 25 C, 50% relative humidity and flowing at a rate of 5 m 3/s is mixed with outsideair at 35 C and 60% relative humidity and flowing at a rate of 1.25 m 3/s. Determine the mixedair condition and flow rate.

    Given: T 1,T 2, 1, 2, Q1(V1), Q 2(V2)Find: T 3, 3, W 3, m 3

    22

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    23/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Solution:

    From the psychrometric chart ( ASHRAE PSYCHROMETRIC CHART NO.1[sea level] , chart 1 b), we candetermine the point 1 and 2

    Return Air Outdoor Airi1 (kJ/kg ) 50.8 90.5W 1 (kg water/kg dry air ) 0.010 0.0215v1 (m3 /kg dry air ) 0.858 0.902

    then we find the mass flow rates:

    and the enthalpy, etc.:

    23

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    24/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.4 Characteristics of Real Systems

    2.4.1 Design conditions

    The processes described in the previous chapter are used to condition moist air in a real air-conditioning systems. The AC system is used to remove both sensible and latent heat from aspace. Relationship between sensible and latent heat is defined as SHF (sensible heat factor).

    Sensible loads:

    Latent loads:

    Sensible and Latent loads:

    Example

    Dishwasher (100 dishes/h): sensible 167 W (570 Btu/h), and latent 65 W (220 Btu/h)Person (male, moderate office work): sensible 70 W (250 Btu/h), and latent 30 W (105 Btu/h)Light bulb: sensible 100 W = 341 Btu/h

    AC system provides airflow: at certain T to meet sensible loads at certain W to meet latent loads

    where T and W must give sensible and latent conditioning proportional to the loads.supply supply

    Condition line represents line in the psychrometric chart through space conditions with theslope defined by SHF. This line contains all feasible supply air states.

    Supply farther from space condition => Smaller mass flow required

    Design condition is defined by: dry bulb temperature, humidity and pressure.

    Design condition + SHF + T => Fix mass flow and supply air conditionsupplyExample

    24

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    25/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Space design condition is 72 oF and 50% RH. The total cooling load is 1,200,000 Btu/hr(100ton), and the sensible cooling load is 720,000 Btu/hr (60 ton). Compare flow rates for (a) T= 10 oF and (b) T = 20 oF. )( supplyspace T T T =

    1ton=12,000 Btu/h

    Solution:

    Construct condition line by using the protractor.

    Btu/hr 000,200,1

    Btu/hr 000,720

    ==

    total

    sensible

    Q

    Q&

    &

    am&

    am&

    2

    1

    TDB=72 oF

    = 50%

    25

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    26/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.4.2 Analysis of the single zone system

    CC Q&

    8.0SHF

    /102.1 6

    == h BtuQ&

    CoolingCoil

    SAMAOA

    RA

    TDB=72 oF = 50%

    Example

    Cooling design conditions for OA are 16,262 cfm and 90 oF db/72 oF wb.

    Design space cooling load is 1,200,000 Btu/h (80% sensible). Supply air temperature is 55oF.

    Determine (a) supply airflow rate and (b) cooling coil load.

    Solution:

    Plot known state on psych chart: OA, SA, and RA.

    Assumption of perfect mixing => RA is equal to room air conditions => i RA=26.4 Btu/lbmOA: i A=35.6 Btu/lbm, v OA=14.1 ft 3/lbmSA: i SA=21.2 Btu/lbm, v SA=13.1 ft 3/lbm

    (a) Flow rate

    26

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    27/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    (b) Cooling coil load

    27

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    28/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    2.4.3 Component characteristics

    Fan Heat Gain

    Due to irreversibility, i.e. friction, fan contributes to sensible heat gain, and increases

    temperature of moist air.

    am&am&

    PFan

    ToutT in

    Fan

    where , therefore Fan P W &

    pa

    Faninout cm

    P T T

    &+=

    Example

    A 1.5 kW fan moves 1m 3/s of dry air entering at 15 oC. What is T out?

    Solution:

    Duct and Plenum Heat Gain

    Plenum heat gains: lights; hot pipes.

    Ducted supply/return: convection in hot spaces; sweating on cool duct surfaces.

    28

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    29/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Example

    Space conditioning(conditioning line)

    Return fanFan & supply duct Return plenum

    Cooling Coils

    Cooling coil are indirect contact heat exchangers. Different types: Air-to-Water Air-to-Refrigerants

    Air is outside, and liquid is inside the tubes.

    Air-side --- fins promote heat transfer (larger area)

    Water-side --- shape promotes heat transfer (higher turbulence)

    For an ideal coil : T DB = T coil, mean = 100%

    For a real coil : T DB > T coil, mean < 100%

    29

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    30/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Approximate methods for rough estimate of cooling coil condition:

    fixed relative humidity (assume coil leaving RH, say 90%) bypass factor b (assume fraction of flow bypasses the coil, reminder in perfectcontact with coil)

    where LA-air leaving the coil, EA - air entering coil, ADP - coil (apparatus) dew point

    Example:

    A chilled water coil with 8 oC entering water conditions air from 26 oC db/ 19 oC wb to 15 oC db/14oC wb . What are T ADP , b, and leaving relative humidity?

    Solution:

    30

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    31/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Evaporative Cooling

    If sufficiently dry air is available, an evaporative process can be used to cool the air stream.Direct evaporative coolers (see Figure) add moisture to air adiabatically. The evaporation usesair sensible heat => T air drops.

    Direct Evaporative Cooler

    Direct evaporative cooling effectives:

    where e varies with air flow rate and media thickness. Range is 60-95%. Typical value is 80%.

    Unassisted Direct Evaporative Cooling

    Applicable if the wet bulb temperature is less than 24 oC (75 oF). Regional applicability is limitedin U.S.:

    the western U.S. the north central states the northeastern U.S.

    May require large supply airflow rates. May give high space humidity at times.

    31

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    32/37

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    33/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Humidification types: wetted media, heated pan, atomizer and steam.

    2.4.3 Off-Design Conditions

    In operation, the cooling or heating loads are only a part of the design loads. HVAC systemneeds to respond to this lower demand, and some of the strategies are:

    CAV-RH (Constant Air Volume) VAV-RH (Variable Air Volume) Face and bypass coil Economizer Variable T for the heat exchangers

    Analyze these processes by the same methods as design conditions.Problems for cooling systems: thermostat controls T DB , and therefore humidity correct only atdesign (in general). As a result, space humidity varies with loads, and may need to iterate tospace conditions. This is not a problem for heating conditions.CAV-RH

    33

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    34/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    same flow rate and W as design conditions, variable T DB good control at part loads

    VAV-RH lower flow rate in proportion to the sensible loads same coil dewpoint temperature => less dehumidification

    Face and bypass coil bypass fraction is proportional to sensible loads no dehumidification of bypassed air => supply humidity is proportional to bypass fract.

    Face and Bypass Coil

    Economizer used in spring or fall supplies outdoor air without operating a cooling coil; potential humidity problems limit is 100% outdoor air; control humidity rise with reheat

    EnthalpyEconomizer

    Return AirTemperatureEconomizer

    RA

    C

    BD

    A

    Roomenthalpy

    line

    C: RA Economizer is off => lost cooling opportunityD: RA Economizer is on => energy penalty results

    No reliable, durable and inexpensive enthalpy sensor for the enthalpy economizer.2.5 Psychrometric Analysis of Complete Systems

    34

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    35/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Space Heating and Cooling Loads

    Heating Load the maximum probable net rate of heat loss from a conditioned spacewhich would have to be made up by addition of heat from the heating system to maintain

    some desired temperature and humidity conditions in the spaceCooling Load for cooling

    Example:

    Cooling and heating load of a classroom at PSU with 10 occupants are estimated as follows:

    Sensible Cooling (W) Heating (W)Walls 1000 2000Window (conduction) 1000 2000Window (radiation) 1000 -People: 70 W/person 700 -Lighting 300 -

    Latent Cooling (W) Heating (W)People 30 W/person 300 -Plants 700

    Outdoor Design ConditionsT 31 oC -14 oCTwet 23 oC -

    Indoor Design ConditionsT 25 oC 22 oC 50% 50%

    Minimum Outdoor AirFresh air: 8 L/s person 80 L/s 80 L/s

    Air Supply TemperaturesMaximum 60 oCMinimum 15 oCDesign the air-conditioning system.

    35

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    36/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Solution (Summer cooling conditions):

    25C

    50%

    15C

    0.80

    31C

    OM

    RI

    C

    Q+Q-R

    M C IO

    Determine the enthalpy at all the status. We use the psych chart in sea level, p = 101325 Pa.

    Outdoor (O): T o = 31 oC, T o,wet = 23 oCFrom Table A-1b, p s,wet = 2815 PaWo,wet = 0.622 p s,wet /(p - p s,wet )

    = 0.622 x 2815/(101325 - 2815) =0.0178 kg v/kg a

    962558

    24470178.0)3123(01.1)( ,,

    +=

    +=

    wo

    fg wet oowet o p

    o ii

    iW T T C W =0.0144 kg v/kg a

    io = 1.01T o + W o(2501 + 1.86T o)= 1.01 kJ/(kg a oC) x 31 oC+ 0.0144 kg v/kg a(2501 kJ/kg v+ 1.86 kJ/(kg v oC) x 31 oC)= 68.15 kJ/kg a

    Room (R): T R = 25 oC, =50%From Table A-1B, p s,R = 3174 PaWR = 0.622 ps,R /(p - p s,R )= 0.622 x 0.5 x 3174 /(101325 -3174)= 0.01 kg v/kg a iR = 1.01T R + W R (2501 + 1.86T R )= 1.01 kJ/(kg a oC) x 25 oC+ 0.01 kg v/kg a(2501 kJ/kg v+ 1.86 kJ/(kg v oC) x 25 oC)= 50.72 kJ/kg a

    36

  • 8/13/2019 2. Moist Air Properties and Air Conditioning Processes

    37/37

    AE 310 Fundamentals of Heating, Ventilating, and Air-Conditioning Chapter2

    Mixture (M): ma =Q sensible

    C p (T R T I )= 4000 W

    1.01 x1000 3 J / kg a (25o C 15o C )

    = 0.396 kg / s

    mo = 80 L/s = 80x10 -3 m3/s x 1.2 kg a/m3 = 0.096 kg a/smR = m a - m o = 0.396 - 0.096 = 0.3 kg a/s

    i M

    = mo io+m R i R

    mo +m R= 0.096 68.15 +0.3 50.72

    0.096 +0.3=54.95 kJ / kg

    Supply air at the inlet (I): T I = 15 oCW = m a(W R - W I) = Q latent /ifg W I = W R - Q latent /(i fg ma )== 0.01kg v/kg a - 1 kW /(2454 kJ/kg v x 0.396 kg a/s ) = 0.009 kg v/kg a iI = 1.01T I + W I(2501 + 1.86T I)= 1.01 x 15 + 0.009(2501 + 1.86 x 15)= 37.91 kJ/kg a

    Cooling coil (C): = 90%Wc = W I = 0.009 kg v/kg a

    W C = 0.622 pC

    p pC

    0.009 = 0.622 pC 101325 pC

    pC= 1447.5 Pa p s,C = p C / = 1447.5 / 0.9= 1608 PaFrom Table A1-b, T C = 14 oCiC = 1.01T C + W C(2501 + 1.86T C)= 1.01 x 14 + 0.009 (2501 + 1.86 x 14)= 36.88 kJ/kg a

    Fan: = v = 0.396 kg/s x 0.84 mV& am&3/kg = 0.332 m 3/s = 1200 m 3/hr

    Cooling coil: Q cooling = (iam& M - i C) = 0.396 kg a/s (54.95 kJ/kg a - 36.88 kJ/kg a)= 7.156 kW

    Heating coil: Q heating = (iam& I - i C) = 0.396 kg a/s (37.91 kJ/kg a - 36.88 kJ/kg a)= 0.4 kW

    The capacity of the heating coil will be larger in winter. Therefore, the final size of theequipment should be the greater of the summer and winter capacities. In many cases,economizers are used to recover energy. Then re-heat in the present design becomesunnecessary.