1KHW001508be Upgrade From ETL500 to ETL600

Embed Size (px)

Citation preview

  • ABB Switzerland Ltd 1KHW001508-EN Archive No.: Rev. Date: Upgrade from ETL500 to ETL600 - B 2007-02-14

    Responsible Department: Prepared: Approved: Distribution: Lang.: Page:

    PSND 2006-02-14 B. Busslinger 2007-02-14 H. Benninger - EN 1/5 Valid for: Derived from: Replaces: Classification-No.: File:

    - - - 1KHW001508be Upgrade from ETL500 to ETL600.doc

    We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd

    Power Line Carrier Equipment: Series ETL600

    Upgrade from ETL500 to ETL600

    Contents

    1 Purpose of document 2 2 General 2 3 Upgrade procedure for a nominal carrier frequency bandwidth BN of 8 kHz or 4 kHz 2

    3.1 General description 2 3.2 Hardware required for upgrading 2 3.3 Procedure 3

    4 Upgrade procedure for a nominal carrier frequency bandwidth BN greater than 8 kHz 4 4.1 General description 4 4.2 Hardware required for upgrading 4 4.3 Procedure 4

    5 Manual Firmware upgrade using MMI500 5

    List of equipment:

    PC with Windows 2000 or XP MMI500 software HMI600 software ETL600 firmware download files PC P4LT/P4LU cable (1:1 serial RS-232) Operational ETL500 terminal Replacement board for P4LQ: P4LT or P4LU Optional E5TX, P4RX, P3LE for bandwidth > 8 kHz Optional P3LG and second E5TX for 80 W and bandwidth > 8 kHz Set of additional connecting cables, if required

    Note:

    Please refer 1KHW001490 for compatibility between software HMI600, firmware and hardware of ETL600.

  • Revision: Language: Page:

    B EN 2/5 1KHW001508-EN

    1 Purpose of document This document describes the upgrade process from the equipment ETL500 Rel.3 to ETL600.

    2 General The new ETL600 boards are designed in a way that they could be inserted in an operational ETL500 Rel.3 system in order to upgrade the ETL500 into an ETL600 by replacing a minimal amount of cards. For ETL500 to ETL600 upgrade system with a nominal carrier frequency bandwidth BN of 8 kHz or 4 kHz, the central processor card P4LQ has to be replaced either by a P4LT or a P4LU. The existing Tx-filter, Rx-filter and RF-hybrid may be reused. This is also valid for the 80 W option. For ETL500 to ETL600 upgrade system with a nominal carrier frequency bandwidth BN of more than 8 kHz, the central processor card P4LQ has to be replaced either by a P4LT or a P4LU. Additionally the Tx filter E5LA/E5LB has to be replaced by E5TX, the Rx filter P4LR by P4RX, the RF-hybrid P3LB/P3DA by P3LE. If an ETL580 (80 W) is upgraded to an ETL600 with a nominal carrier frequency bandwidth BN of more than 8 kHz, the second Tx filter E5LA/E5LB has to be replaced by E5TX and the combiner P3LC/P3LD by P3LG. NSK5 modules in the ETL600 rack are no longer supported and have to be removed. The NSK600 modems integrated on P4LT/P4LU may be used instead.

    ESD protection

    Caution The modules in this equipment contain devices, which can be damaged by electrostatic discharges. Appropriate measures must be taken before unpacking modules or withdrawing them from equipment racks. Essential precautions to prevent ESD damage when handling or working on modules are grounding straps for technical personnel and the provision of anti-static workbenches. Modules may only be shipped either in their original packing or installed in equipment racks.

    ESD

    Insertion and removal of plug-in modules

    Neither removing nor inserting of modules is permitted during power-up of the equipment. Preceding to plug in and out of modules the power supply of the equipment has to be switched OFF. An exception to this is the Rx filter P4RX, which has to be removed and inserted while the equipment remains powered when performing the Rx level adjustment procedure.

    Caution

    3 Upgrade procedure for a nominal carrier frequency bandwidth BN of 8 kHz or 4 kHz

    3.1 General description The existing Tx- and Rx filters and the RF hybrid shall be re-used, i.e. the nominal carrier frequency bandwidth BN is limited to 4 or 8 kHz, and the nominal carrier frequency range remains the same as for the existing RF filter set. This is also valid for the 80 W option.

    3.2 Hardware required for upgrading P4LT or P4LU Optional set of connecting cables, if required NSK5 modules to be removed, as they are replaced by the internal NSK600

  • Revision: Language: Page:

    B EN 3/5 1KHW001508-EN

    3.3 Procedure 1. Check the tuning according to Appendix in ETL500 manual: "Tuning Instructions for RxRF

    Filter P4LR" (1KHL015117-EN), "Tuning Instructions for TxRF Filter E5LA/E5LB" (1KHL015570-EN) and "Tune RF hybrid P3LB, if present" according to "Programming and Testing Instructions ETL500" (1KHL015940-EN). Adjust if necessary.

    2. Produce a config file *.mmi for the existing ETL500 by means of the MMI500. A hardcopy on a printer might be helpful.

    3. If G4AI (teleprotection) is used: make a firmware upgrade of all G4AI by means of MMI500 version 3.20 or higher. See instructions in paragraph 5. Manual Firmware upgrade using MMI500.

    4. If O4LE is used: make a firmware upgrade of all O4LE by means of MMI500 version 3.20 or higher. See instructions in paragraph 5. Manual Firmware upgrade using MMI500.

    5. Start the HMI600 and enter offline the configuration of ETL600 (re-enter data manually from step 2 as far as applicable).

    If as receive filter P4LR instead of P4RX is used, please select P4RX in HMI600, Configure system / Equipment settings.

    Note:

    HMI600 uses always fn = nominal frequency for Rx and Tx frequency settings. ETL500 used the center frequency for double channel APLC. In order to select the correct Rx and Tx frequency in the ETL600, 4 kHz has to be subtracted from the ETL500 frequency configuration. For single channel APLC, the frequency could just be used in the HMI600 without modification.

    6. Replace P4LQ by P4LT or P4LU.

    The 5R and the 3R blanking plates on the left and right side of P4LQ must be removed. They are no longer used, as the front plate P4LT/P4LU is 14R wide.

    Note:

    Please use caution when inserting or removing P4LT/P4LU. These units have EMC springs on every side.

    7. Remove all G4AI and O4LE and re-insert them at the corresponding slot positions of ETL600 as given by the HMI600 (see also ETL600 manual).

    8. For all O4LE cables: Change the wiring according to the new port assignment of the teleoperation ports.

    9. Remove all NSK5 modules, if any. They have to be replaced by 6R blanking plates. Change the wiring to the P4LT/P4LU according to the configuration shown in the HMI600.

    10. Download the ETL600 configuration onto the ETL600 by means of the HMI600.

    11. Tune and test according to ETL600 Tuning and Testing instructions as per ETL600 manual, except Tx- and Rx filters. Especially the Adjust Tx RF level, Adjust Tx Alarm level and Adjust Rx RF level procedures have to be performed.

    "Tuning Instructions for ETL600 Rx RF filter P4RX", "Tuning Instructions for ETL600 Tx RF filter E5TX" and "Settings for ETL600 RF hybrid P3LE / Tune RF hybrid P3LE" are not applicable if the ETL500 Tx filter E5LA/E5LB, Rx filter P4LR and hybrid P3LB are re-used. The tuning was already done in step

    Note:

    1.

  • Revision: Language: Page:

    B EN 4/5 1KHW001508-EN

    For adjusting the Tx RF level: measure the test tone level at the RF line socket (X175) via an attenuator with impedance according to the ETL system impedance (75 of 125 Ohm) and a level meter set to the same input impedance (the attenuator is required to prevent overdriving of the level meter). The RF line monitor socket on the front plate of the hybrid P3LB has not the same impedance and level as the RF line monitor socket of the hybrid P4LE.

    Note:

    When performing Adjust Rx RF level with HMI600 tuning and testing, check the box Rx Filter P4RX plugged if the receive filter P4LR is used. Remove P4LR when P4RX is required to be removed during the adjustment. Do the adjustment at the potentiometer Rx Level on P3LB instead of P3LE as described by HMI600.

    Note:

    12. If necessary, perform a firmware update to the latest ETL600 release according to

    1KHW001496: Firmware Download for ETL600.

    4 Upgrade procedure for a nominal carrier frequency bandwidth BN greater than 8 kHz

    4.1 General description The existing Tx and Rx filters and RF hybrid are replaced by the corresponding units for ETL600.

    4.2 Hardware required for upgrading E5TX (Tx-filter), P4RX (Rx-filter), P3LE (RF-hybrid)

    and for 80 W only: P3LG (Combiner) with second Tx-filter E5TX P4LT or P4LU (with optional P1LX and R1LA, if needed) Optional set of connecting cables, if required NSK5 modules to be removed, as they are replaced by the internal NSK600

    4.3 Procedure 1. Produce a config file *.mmi for the existing ETL500 by means of the MMI500.

    2. If G4AI (teleprotection) is used: make a firmware upgrade of all G4AI by means of MMI500, version 3.20 or higher. See instructions in paragraph 5. Manual Firmware upgrade using MMI500.

    3. If O4LE is used: make a firmware upgrade of all O4LE by means of MMI500, version 3.20 or higher. See instructions in paragraph 5. Manual Firmware upgrade using MMI500.

    4. Start the HMI600 and enter offline the configuration of ETL600 (re-enter data manually from step 1 as far as applicable).

    5. Replace P4LQ by P4LT or P4LU. Replace existing RF set by new E5TX, P4RX, P3LE, and for 80 W only: P3LG.

    6. Remove all G4AI and O4LE and re-insert them at the corresponding slot positions of ETL600 as given by the HMI600 (see also ETL600 manual).

    7. For all O4LE cables: change the wiring according to the new port assignment of the teleoperation ports.

    8. Download the ETL600 configuration onto the ETL600 by means of the HMI600.

    9. Tune and test according to ETL600 Tuning and Testing Instructions, refer to ETL600 manual.

    10. If necessary, perform a firmware update to the latest ETL600 release according to 1KHW001496: Firmware Download for ETL600.

  • Revision: Language: Page:

    B EN 5/5 1KHW001508-EN

    5 Manual Firmware upgrade using MMI500 The firmware upgrade of the existing modules G4AI and O4LE may be effected with the MMI500 according to document 1KHL016378-EN "Firmware Download: < ETL500 Rel.3 >" in the ETL500 manual. In particular: Deselect the field "Automatic firmware update". Do a firmware update by selecting the slot where the card to be updated is plugged, and select

    "Start firmware download". Select the firmware. The new firmware is stored in the installation directory of HMI600,

    subdirectory "firmware/release x.x.x" (latest release has highest number). Note: The install directory is per default: C:\Program Files\ABB\HMI600\

    Repeat this step for all O4LE and G4AI.

    The firmware upgrade of the existing modules G4AI and O4LE may also be effected with the HMI600 according to document 1KHW001496-EN Firmware Download for ETL600 in the annex of the ETL600 manual.

    Note:

    1 Purpose of document 2 General 3 Upgrade procedure for a nominal carrier frequency bandwidth BN of 8 kHz or 4 kHz 3.1 General description 3.2 Hardware required for upgrading 3.3 Procedure 4 Upgrade procedure for a nominal carrier frequency bandwidth BN greater than 8 kHz 4.1 General description 4.2 Hardware required for upgrading 4.3 Procedure

    5 Manual Firmware upgrade using MMI500