ABB GroupApril 24, 2012 | Slide 2
Traditional grids
Years of development to provide automation of
well-established power system model
Electromechanical to numerical technology
Centralized and/or distributed architectures
Communication protocols : interoperability
Wide Area Monitoring SystemsFrom traditional to future grids
Future grids
Automati on systems for a new power system andbusiness model
Decentralized (renewable sources)
Demand-side management
FACTS (SVC, TCSC, STATCOM, PST), HVDC
Industry challenges
Need for more electricity
Emissions reduction
Integration and management of renewable energy
Optimal use of ageing assets
Ensure reliability of supply
Energy efficiency and security
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
3/35
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
4/35
ABB GroupApril 24, 2012 | Slide 4
Increasing demand for power
Transmission networks get bigger by aggregation (islandinterconnected)
Distance between generation and load changes
Laws, regulations & politics often impede building powerplants where they are needed
Introduction of distributed energy resources e.g. wind
Load flow becomes volatile
Modern supervision and tools are needed
Increase the utilization of new technologies e.g. WAMS
to allow the networks to operate closer to its capacitywhile maintaining system security
Svenska Kraftnt 2001
Wide Area Monitoring SystemsGeneral challenges in transmission networks
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
5/35
ABB GroupApril 24, 2012 | Slide 5
Wide Area Monitoring SystemsBasic idea
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
6/35
ABB GroupApril 24, 2012 | Slide 6
Wide Area Monitoring SystemsPhasor measurements
Timestamp accuracy: 1 microsecondAbsolute angle accuracy error: < 0.1 degreeCT/VT: 0.2 0.5%
High accuracy provides the basis for anaccurate monitoring of power networks
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
7/35
ABB GroupApril 24, 2012 | Slide 7
Local Measurements in Substations
CTs: high accuracy in small current values
requires connection to measurement cores
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
8/35
ABB GroupApril 24, 2012 | Slide 8
Phasor Measurement UnitABB RES521
Based on Protective Relay technology
18 Analog Inputs(4 x 3ph CTs, 2 x 3ph VTs)
Selectable transfer ratesup to 1 phasor/cycle
GPS Synchronization
Accurate frequency measurement < 5 mHzerror
Local functions such as frequency, df/dt
Local trigger functions
Synchrophasor data format(IEEE 1344-1995, IEEE C37.118)
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
9/35
ABB GroupApril 24, 2012 | Slide 9
Wide Area Monitoring SystemsPSGuard
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
10/35
ABB GroupApril 24, 2012 | Slide 10
PSGuard positioning
PSGuard
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
11/35
ABB GroupApril 24, 2012 | Slide 11
PSGuardWide Area Monitoring System
PSGuard System
Based on ABBs process control systemand Windows Server technology
Server/Client architecture
PMU data acquisition with OPC standardinterface
High resolution data storage and export
Graphical User Interface
WAMS applications
Connection to SCADA systems
PSGuard Communication Gateway
PMU data exchange in real-time betweenutilities
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
12/35
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
13/35
PSGuardWide Area Monitoring System
ABB GroupApril 24, 2012 | Slide 13
PSGuard Applications
Phase Angle Monitoring
Voltage Stability Monitoring
Line Thermal Monitoring
Event Driven Data Archiving
Power Oscillation Monitoring
Power Damping Monitoring
SCADA/EMS integration
Communication gateway
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
14/35
ABB GroupApril 24, 2012 | Slide 14
PSGuard Application Portfolio
Modular and scalable system structure
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
15/35
ABB GroupApril 24, 2012 | Slide 15
OPC (OLE for Process Control) is a standard forProcess Control Systems
Provides PMU measurements to the PSGuardSystem via OPC Standard Interface
Supervises GPS synchronisation andcommunication channels
Supports IEEE1344-1995 and IEEE C37.118
Connectivity OPC Data Access Server for PMUs
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
16/35
ABB GroupApril 24, 2012 | Slide 16
Basic Monitoring Process Visualization
Efficient Graphical User Interface engineering basedon a WAM library
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
17/35
ABB GroupApril 24, 2012 | Slide 17
Configurable ring buffer data storage
PMU measurements
Application results
Every data point stored with
Timestamp Value
Quality
Export application
Export to CSV files
Data Storage and Export
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
18/35
ABB GroupApril 24, 2012 | Slide 18
PSGuard Application Portfolio
Modular and scalable system structure
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
19/35
ABB GroupApril 24, 2012 | Slide 19
Event Driven Data Archiving (EDDA)
Wide Area Disturbance Recorder based onlogical trigger conditions
Central triggering by observing network-widedata
Configurable archiving length and resolution
Archives are provided in CSV file format (MSExcel)
Continuous archiving provides daily archiving forlong-term data storage
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
20/35
ABB GroupApril 24, 2012 | Slide 20
Phase Angle Monitoring (PAM)
Online calculation of voltage phase angledifference
Configurable alarming and warning thresholds
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
21/35
ABB GroupApril 24, 2012 | Slide 21
Power Oscillations Monitoring (POM)
Real-time detection of power swings
Algorithm is fed with selected voltage and currentphasors
Detection of various swing (power oscillation)modes
Quickly identifies amplitude and frequency ofoscillations
In service since 2005
Field experience in Switzerland, Croatia, Mexico,Thailand, Finland, Norway, Austria
Bus Voltage
Mode Frequency, HzDamping, %
Mode Amplitude, V
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
22/35
ABB GroupApril 24, 2012 | Slide 22
Power Oscillations Monitoring (POM)
ABB CRC research finalized on next generation ofPOM application
Accurate determination of damping levels underambient conditions
Mode shape determination
Use of multiple input signals
Simulationeous detection of multiple modes
Verified against simulated measurements and fieldmeasurements from the Fingrid WAMS
Verified against other algorithms in Universitycollaboration
Ready for piloting
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
23/35
ABB GroupApril 24, 2012 | Slide 23
Power Damping Monitoring (PDM)
Real-time detection and visualization of multipleoscillation modes to truly understand the systembehaviour
Monitor damping and modal activity of most dangerousmodes in the power system from ambient data (beforelarge excitations happen)
Quickly identify the participants and sources of inter-
area oscillations using online visualization of modalshapes
Early warning of poorly damped lines allows operators to react before anevent triggers an inter-area oscillation
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
24/35
ABB GroupApril 24, 2012 | Slide 24
PDM Modal Observability MapIdentify participants in inter-area oscillations
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
25/35
ABB GroupApril 24, 2012 | Slide 25
Line Thermal Monitoring (LTM)
Use PMU measurements of voltage and currentto calculate average line temperature of themonitored line
On-line display of average temperature
Initial field results correlate increased powertransfer from 950 MW to 1150 MW leads to anaverage temperature increase from 46 degreesto 49 degrees over 30 min
Sample recordings from Swissgrid
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
26/35
ABB GroupApril 24, 2012 | Slide 26
Provides power margin to the point ofmaximum loadability of transmission corridorsregarding voltage stability
High accuracy by using PMU data (dynamicdata)
Fast reaction (Usage of real-time data)
Voltage Stability Monitoring (VSM)
3 transmission
corridor
PMUPMU
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
27/35
ABB GroupApril 24, 2012 | Slide 27
PSGuard Communication Gateway
PMU data exchange between utilitiesin real-time
PMU standard protocols IEEE1344-1995 and IEEE C37.118 are supported
The external WAM systems are able tocommunicate with the Gateway as witha physical PMU device
Filter functionality allows selective datatransmission (e.g. only voltages but nocurrent measurements are provided)
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
28/35
ABB GroupApril 24, 2012 | Slide 28
The Interface Manager provides operatorswith processed data and alarms fromPSGuard in conventional SCADA/EMSsystems.
RTU standard protocols and specific
customer protocols are provided for theintegration in SCADA.
Interface Manager SCADA integration
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
29/35
ABB GroupApril 24, 2012 | Slide 29
ABB PSGuard / WAM-System Installations
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
30/35
ABB GroupApril 24, 2012 | Slide 30
Wide Area Monitoring SystemsPSGuard in Fingrid (Finland)
Since 2006
10 PMUs in Finland
Communication gateway to PMU in Norway
SCADA integration
Main application post-disturbance analysis of system performance
Collaboration project on power oscillation monitoring
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
31/35
ABB GroupApril 24, 2012 | Slide 31
Wide Area Monitoring SystemsPSGuard in Swissgrid (Switzerland)
Since 2004 7 PMUs ABB RES521
Connection to PDCs & PMUs from major European utilities allowmonitoring of dynamics across Europe
Monitoring and early warning system for the loading of the north-south corridor of the Swiss transmission grid
SCADA integration
Monitoring of reconnection of UCTE zones (2004)
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
32/35
ABB GroupApril 24, 2012 | Slide 32
Wide Area Monitoring SystemsPSGuard in HEP (Croatia)
Since 2003
14 PMUs ABB RES521
Enhance stability of transmissionsystem and optimize utilization oftransmission capacity
Features:
20 ms
Basic monitoring, storage andarchive
Line thermal monitoring
Voltage stability monitoring
Data exchange with other PDCs
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
33/35
ABB GroupApril 24, 2012 | Slide 33
Wide Area Monitoring SystemsPSGuard in APG (Austria)
Since 2005
Monitoring of the vital 220 kV double lines between Vienna andTernitz substations with phase angle monitoring and line thermalmonitoring
3 PMUs ABB RES521
8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04
34/35
ABB GroupApril 24, 2012 | Slide 34
Wide Area Monitoring SystemsPSGuard in EGAT (Thailand)
Since 2005 (First WAMS in Asia) 4 PMUs ABB RES521
Monitor stability of heavily loaded 230 kV transmission linesbetween southern and central region of Thailand
Application of Power Oscillation Monitoring to detect powerswings