1KHL501042 PSGuard WAMS Overview 2012-04

Embed Size (px)

Citation preview

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    1/35

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    2/35

    ABB GroupApril 24, 2012 | Slide 2

    Traditional grids

    Years of development to provide automation of

    well-established power system model

    Electromechanical to numerical technology

    Centralized and/or distributed architectures

    Communication protocols : interoperability

    Wide Area Monitoring SystemsFrom traditional to future grids

    Future grids

    Automati on systems for a new power system andbusiness model

    Decentralized (renewable sources)

    Demand-side management

    FACTS (SVC, TCSC, STATCOM, PST), HVDC

    Industry challenges

    Need for more electricity

    Emissions reduction

    Integration and management of renewable energy

    Optimal use of ageing assets

    Ensure reliability of supply

    Energy efficiency and security

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    3/35

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    4/35

    ABB GroupApril 24, 2012 | Slide 4

    Increasing demand for power

    Transmission networks get bigger by aggregation (islandinterconnected)

    Distance between generation and load changes

    Laws, regulations & politics often impede building powerplants where they are needed

    Introduction of distributed energy resources e.g. wind

    Load flow becomes volatile

    Modern supervision and tools are needed

    Increase the utilization of new technologies e.g. WAMS

    to allow the networks to operate closer to its capacitywhile maintaining system security

    Svenska Kraftnt 2001

    Wide Area Monitoring SystemsGeneral challenges in transmission networks

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    5/35

    ABB GroupApril 24, 2012 | Slide 5

    Wide Area Monitoring SystemsBasic idea

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    6/35

    ABB GroupApril 24, 2012 | Slide 6

    Wide Area Monitoring SystemsPhasor measurements

    Timestamp accuracy: 1 microsecondAbsolute angle accuracy error: < 0.1 degreeCT/VT: 0.2 0.5%

    High accuracy provides the basis for anaccurate monitoring of power networks

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    7/35

    ABB GroupApril 24, 2012 | Slide 7

    Local Measurements in Substations

    CTs: high accuracy in small current values

    requires connection to measurement cores

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    8/35

    ABB GroupApril 24, 2012 | Slide 8

    Phasor Measurement UnitABB RES521

    Based on Protective Relay technology

    18 Analog Inputs(4 x 3ph CTs, 2 x 3ph VTs)

    Selectable transfer ratesup to 1 phasor/cycle

    GPS Synchronization

    Accurate frequency measurement < 5 mHzerror

    Local functions such as frequency, df/dt

    Local trigger functions

    Synchrophasor data format(IEEE 1344-1995, IEEE C37.118)

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    9/35

    ABB GroupApril 24, 2012 | Slide 9

    Wide Area Monitoring SystemsPSGuard

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    10/35

    ABB GroupApril 24, 2012 | Slide 10

    PSGuard positioning

    PSGuard

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    11/35

    ABB GroupApril 24, 2012 | Slide 11

    PSGuardWide Area Monitoring System

    PSGuard System

    Based on ABBs process control systemand Windows Server technology

    Server/Client architecture

    PMU data acquisition with OPC standardinterface

    High resolution data storage and export

    Graphical User Interface

    WAMS applications

    Connection to SCADA systems

    PSGuard Communication Gateway

    PMU data exchange in real-time betweenutilities

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    12/35

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    13/35

    PSGuardWide Area Monitoring System

    ABB GroupApril 24, 2012 | Slide 13

    PSGuard Applications

    Phase Angle Monitoring

    Voltage Stability Monitoring

    Line Thermal Monitoring

    Event Driven Data Archiving

    Power Oscillation Monitoring

    Power Damping Monitoring

    SCADA/EMS integration

    Communication gateway

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    14/35

    ABB GroupApril 24, 2012 | Slide 14

    PSGuard Application Portfolio

    Modular and scalable system structure

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    15/35

    ABB GroupApril 24, 2012 | Slide 15

    OPC (OLE for Process Control) is a standard forProcess Control Systems

    Provides PMU measurements to the PSGuardSystem via OPC Standard Interface

    Supervises GPS synchronisation andcommunication channels

    Supports IEEE1344-1995 and IEEE C37.118

    Connectivity OPC Data Access Server for PMUs

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    16/35

    ABB GroupApril 24, 2012 | Slide 16

    Basic Monitoring Process Visualization

    Efficient Graphical User Interface engineering basedon a WAM library

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    17/35

    ABB GroupApril 24, 2012 | Slide 17

    Configurable ring buffer data storage

    PMU measurements

    Application results

    Every data point stored with

    Timestamp Value

    Quality

    Export application

    Export to CSV files

    Data Storage and Export

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    18/35

    ABB GroupApril 24, 2012 | Slide 18

    PSGuard Application Portfolio

    Modular and scalable system structure

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    19/35

    ABB GroupApril 24, 2012 | Slide 19

    Event Driven Data Archiving (EDDA)

    Wide Area Disturbance Recorder based onlogical trigger conditions

    Central triggering by observing network-widedata

    Configurable archiving length and resolution

    Archives are provided in CSV file format (MSExcel)

    Continuous archiving provides daily archiving forlong-term data storage

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    20/35

    ABB GroupApril 24, 2012 | Slide 20

    Phase Angle Monitoring (PAM)

    Online calculation of voltage phase angledifference

    Configurable alarming and warning thresholds

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    21/35

    ABB GroupApril 24, 2012 | Slide 21

    Power Oscillations Monitoring (POM)

    Real-time detection of power swings

    Algorithm is fed with selected voltage and currentphasors

    Detection of various swing (power oscillation)modes

    Quickly identifies amplitude and frequency ofoscillations

    In service since 2005

    Field experience in Switzerland, Croatia, Mexico,Thailand, Finland, Norway, Austria

    Bus Voltage

    Mode Frequency, HzDamping, %

    Mode Amplitude, V

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    22/35

    ABB GroupApril 24, 2012 | Slide 22

    Power Oscillations Monitoring (POM)

    ABB CRC research finalized on next generation ofPOM application

    Accurate determination of damping levels underambient conditions

    Mode shape determination

    Use of multiple input signals

    Simulationeous detection of multiple modes

    Verified against simulated measurements and fieldmeasurements from the Fingrid WAMS

    Verified against other algorithms in Universitycollaboration

    Ready for piloting

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    23/35

    ABB GroupApril 24, 2012 | Slide 23

    Power Damping Monitoring (PDM)

    Real-time detection and visualization of multipleoscillation modes to truly understand the systembehaviour

    Monitor damping and modal activity of most dangerousmodes in the power system from ambient data (beforelarge excitations happen)

    Quickly identify the participants and sources of inter-

    area oscillations using online visualization of modalshapes

    Early warning of poorly damped lines allows operators to react before anevent triggers an inter-area oscillation

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    24/35

    ABB GroupApril 24, 2012 | Slide 24

    PDM Modal Observability MapIdentify participants in inter-area oscillations

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    25/35

    ABB GroupApril 24, 2012 | Slide 25

    Line Thermal Monitoring (LTM)

    Use PMU measurements of voltage and currentto calculate average line temperature of themonitored line

    On-line display of average temperature

    Initial field results correlate increased powertransfer from 950 MW to 1150 MW leads to anaverage temperature increase from 46 degreesto 49 degrees over 30 min

    Sample recordings from Swissgrid

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    26/35

    ABB GroupApril 24, 2012 | Slide 26

    Provides power margin to the point ofmaximum loadability of transmission corridorsregarding voltage stability

    High accuracy by using PMU data (dynamicdata)

    Fast reaction (Usage of real-time data)

    Voltage Stability Monitoring (VSM)

    3 transmission

    corridor

    PMUPMU

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    27/35

    ABB GroupApril 24, 2012 | Slide 27

    PSGuard Communication Gateway

    PMU data exchange between utilitiesin real-time

    PMU standard protocols IEEE1344-1995 and IEEE C37.118 are supported

    The external WAM systems are able tocommunicate with the Gateway as witha physical PMU device

    Filter functionality allows selective datatransmission (e.g. only voltages but nocurrent measurements are provided)

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    28/35

    ABB GroupApril 24, 2012 | Slide 28

    The Interface Manager provides operatorswith processed data and alarms fromPSGuard in conventional SCADA/EMSsystems.

    RTU standard protocols and specific

    customer protocols are provided for theintegration in SCADA.

    Interface Manager SCADA integration

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    29/35

    ABB GroupApril 24, 2012 | Slide 29

    ABB PSGuard / WAM-System Installations

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    30/35

    ABB GroupApril 24, 2012 | Slide 30

    Wide Area Monitoring SystemsPSGuard in Fingrid (Finland)

    Since 2006

    10 PMUs in Finland

    Communication gateway to PMU in Norway

    SCADA integration

    Main application post-disturbance analysis of system performance

    Collaboration project on power oscillation monitoring

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    31/35

    ABB GroupApril 24, 2012 | Slide 31

    Wide Area Monitoring SystemsPSGuard in Swissgrid (Switzerland)

    Since 2004 7 PMUs ABB RES521

    Connection to PDCs & PMUs from major European utilities allowmonitoring of dynamics across Europe

    Monitoring and early warning system for the loading of the north-south corridor of the Swiss transmission grid

    SCADA integration

    Monitoring of reconnection of UCTE zones (2004)

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    32/35

    ABB GroupApril 24, 2012 | Slide 32

    Wide Area Monitoring SystemsPSGuard in HEP (Croatia)

    Since 2003

    14 PMUs ABB RES521

    Enhance stability of transmissionsystem and optimize utilization oftransmission capacity

    Features:

    20 ms

    Basic monitoring, storage andarchive

    Line thermal monitoring

    Voltage stability monitoring

    Data exchange with other PDCs

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    33/35

    ABB GroupApril 24, 2012 | Slide 33

    Wide Area Monitoring SystemsPSGuard in APG (Austria)

    Since 2005

    Monitoring of the vital 220 kV double lines between Vienna andTernitz substations with phase angle monitoring and line thermalmonitoring

    3 PMUs ABB RES521

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    34/35

    ABB GroupApril 24, 2012 | Slide 34

    Wide Area Monitoring SystemsPSGuard in EGAT (Thailand)

    Since 2005 (First WAMS in Asia) 4 PMUs ABB RES521

    Monitor stability of heavily loaded 230 kV transmission linesbetween southern and central region of Thailand

    Application of Power Oscillation Monitoring to detect powerswings

  • 8/13/2019 1KHL501042 PSGuard WAMS Overview 2012-04

    35/35