    Bulletin 193/592Model EC5

    E3 Plus Electronic

    Overload Relay with

    Voltage Protection and

    Energy Monitoring

    Customer Presentation

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    2/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 2

    The E3 Plus Electronic Overload Relay with Voltage Protection

    and Energy Monitoring provides you with enhanced motorprotection and motor energy consumption information Enhanced Protection

    Current Protection

    Voltage Protection

    Power Protection

    Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

    E3 Plus with Voltage Protection & EnergyMonitoring

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    3/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 3

    Enhanced Protection

    Current Protection

    Voltage Protection

    Power Protection

    Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

    E3 Plus with Voltage Protection & EnergyMonitoring

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    4/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 4

    Current Protection The E3 Plus with Voltage Protection and

    Energy Monitoring helps protect yourelectric motor investment by preventing

    damage from the following events:

    Thermal Overload

    Phase Loss Jam Warning

    Stall

    Under Load

    Current Unbalance

    Ground Fault Current

    Ground Fault Current Filtering for

    High Resistance Ground Systems

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    5/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 5

    Thermal Overload

    The E3 Plus Model EC5 helps protect your

    electric motor from consuming more electriccurrent than its nameplate rating which can be

    caused by:

    Excessive load

    Incorrectly sized motor

    Low incoming voltage Damaged equipment

    The trip class of the motor is selectablebetween 5 and 30 Trip class represents the maximum trip time in seconds

    when the motor consumes 720% of the Full Load

    Amperes (FLA) rating of the electric motor %Thermal Capacity Utilization (%TCU) can be

    monitored to continuously view the thermal statusof the electric motor

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    6/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 6

    Phase Loss

    The E3 Plus Model EC5 helps

    protect your electric motor whenone phase of power is lost

    causing the remaining phases to

    consume more electric current

    Phase loss is typically caused by: Blown fuse

    Loose wire

    Damaged contactor contacts

    Phase loss is a leading cause of motor failure!

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    7/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 7

    Jam, Stall, & Underload

    The E3 Plus Model EC5 helps provide these protection functions to

    ensure the safe operation of your electric motor or machine: Jam protection

    Prevents an electric motor from running when

    a sudden rise in electrical current

    consumption occurs during its normal running

    operation

    Stall protection

    Prevents an electric motor from running when

    an extended amount of electrical current is

    consumed during its starting sequence

    Underload protection

    Disables an electric motor when a sudden

    drop in electrical current occurs indicating a

    possible mechanical malfunction

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    8/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 8

    Current Imbalance

    The E3 Plus Model EC5 can help

    protect against the unequalconsumption of electrical current

    on each of the three phases for

    your electric motor

    Current imbalance protection canbe used to prevent electric motor

    damage from:

    Imbalance in the voltage supply

    Unequal motor winding impedance

    Long and varying cable lengths

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    9/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 9

    Ground Fault

    The E3 Plus Model EC5 has the capability to

    monitor for short circuits or current leakage toground and provide equipment level protection(20mA5A)

    Low levels of ground fault current can rise veryquickly causing damage to the electric motor ifnot caught early

    The E3 Plus Model EC5 can monitor groundfault current for:

    Solidly grounded systems

    High resistance grounded systems

    Ground Fault Current Filtering option for High

    Resistance Ground Systems to preventnuisance trips

    It is important to catch ground faults at the leakage stage!

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    10/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 10

    AvailableExternal Ground FaultCurrent Transformers

    Catalog

    Number

    Inner

    Diameter

    Max Wire

    Size

    3-Phase

    Current

    Rating

    NEMA

    Contactor

    IEC

    Contactor

    193-CBCT1 20 mm (1) #8 Awg 45A Size 001 C9C37

    193-CBCT2 40 mm (1) #2 Awg 90A Size 003 C9C85

    193-CBCT3 65 mm (1) 250MCM 180A Size 4 D180

    193-CBCT4 85 mm (2) 350 MCM 420A Size 5 D420

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    11/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 11

    E3 Plus with Voltage Protection & EnergyMonitoring

    Enhanced Protection

    Current Protection Voltage Protection

    Power Protection

    Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    12/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 12

    Voltage Protection

    The E3 Plus with Voltage Protection and

    Energy Monitoring helps you to protectagainst the following voltage issues:

    Under Voltage

    Over Voltage

    Phase Failure Voltage Unbalance

    Phase Rotation Mismatch

    Under Frequency

    Over Frequency

    Protection on the Line Side of the Contactor

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    13/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 13

    Supported Voltage Systems

    The E3 Plus Model EC5 can be used on the following voltage systems:

    Catalog Number 193-EC5ZZ

    Delta without Potential Transformers

    Delta with Potential Transformers

    Wye with or without Potential Transformers

    Open Delta with Potential Transformers

    Single Phase with or without Potential Transformers

    All Other Catalog Numbers

    Delta without Potential Transformers

    Wye with or without Potential Transformers

    Single Phase with or without Potential Transformers

    Supports direct connections up to 600 VAC(690 VAC IEC)

    E3 Pl i h V l P i & E

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    14/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 14

    E3 Plus with Voltage Protection & EnergyMonitoring

    Enhanced Protection

    Current Protection Voltage Protection

    Power Protection

    Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    15/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 15

    Power Protection

    To address power quality issues that

    could occur due to a specific application,the E3 Plus Electronic Overload Relay

    with Voltage Protection and Energy

    Monitoring also provides you with the

    following power based protection : Real Power (kW)

    Reactive Power (kVAR)

    Apparent Power (kVA)

    Power Factor (PF)

    Leading

    Lagging

    E3 Pl ith V lt P t ti & E

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    16/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 16

    E3 Plus with Voltage Protection & EnergyMonitoring

    Enhanced Protection

    Current Protection Voltage Protection

    Power Protection

    Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    17/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 17

    Advanced Diagnostics

    The E3 Plus Electronic Overload Relay not only helps protect your

    electric motor investment, but it can proactively assist in maintaining theelectric motor by limiting: Number of starts

    Operating hours

    The E3 Plus Electronic Overload Relay can also help provide diagnosticand metering information to help you understand the consumptionpatterns for the motor or process by providing: RMS current

    Percentage of full load current (%FLA)

    Current imbalance

    Thermal Capacity Utilization (%TCU)

    Trip log

    Warning log

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    18/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 18

    Energy Diagnostics To address energy usage

    concerns, the E3 Plus Electronic

    Overload Relay with Voltage

    Protection and Energy Monitoring

    provides you with the following

    energy diagnostic information: Real Energy (kWh)

    Reactive Energy (kVARh)

    Apparent Energy (kVAh)

    kW Demand kVAR Demand

    kVA Demand

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    19/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 19

    Energy Diagnostics The E3 Plus Model EC5 can

    be included in your energymanagement system

    Helps identify which motors

    contribute to the monthly peak

    demand and power factor lineitems on a utility bill

    Helps to verify energy reduction

    initiatives

    Monitoring consumption patterns and adjusting manufacturing

    procedures helps to use electricity more efficiently!

    E3 Pl s ith Voltage Protection & Energ

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    20/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 20

    E3 Plus with Voltage Protection & EnergyMonitoring

    Enhanced Protection

    Current Protection Voltage Protection

    Power Protection

    Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    21/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 21

    Historical Logs

    The E3 Plus Model EC5 internally

    records the last five trips and last fivewarnings

    Trip History - Selectively record trip events

    Warning History - Selectively recordwarning events

    Snapshot RecordRecords 12 real-timeparameters at the time of the trip event

    Your maintenance personnel can use

    the historical logsto minimize down

    time during an unplanned event

    Trip History

    Warning History

    Snapshot Record

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    22/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 22

    Inputs & Outputs

    The E3 Plus Model EC5 offers direct

    control capabilities by offeringdiscreet inputs and outputs in addition

    to the overload trip relay

    6 Inputs

    2 Outputs The E3 Plus Model EC5 also provides

    discreet outputs that can be used for:

    Remotely starting a motor

    Indicating a fault or warning

    Two speed motor control

    Logical discreet control

    DeviceLogix enabled

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    23/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 23

    New E3 Status Object

    The new E3 Status Object (Object Class 0x375) provides a

    more efficient means to read data from an E3 Plus ElectronicOverload Relay

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    24/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 24

    DeviceNet Configuration Terminal

    The DeviceNet Configuration Terminal (Cat. No.

    193-DNCT) is an optional device that providesusers the capability to configure and view data

    for any DeviceNet component including the E3

    Plus Electronic Overload Relays

    You can perform these functions locally on aDeviceNet network:

    Parameter monitoring

    Parameter editing

    Storage of device configuration data

    Network who

    Display network diagnostics

    Editing DeviceLogix programs

    Trend parameters

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    25/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 25

    E3 Plus Model EC5 Catalog Number Scheme

    Inputs Outputs PTC Dlogix HT Voltage

    193/592-EC1 2 1

    193/592-EC2 4 2 Internal 15A

    193/592-EC3 4 2 External 20mA5A * 193-EC4 4 2 External 20mA5A *

    193/592-EC5 6 2 External 20mA5A *

    Ground Fault

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    26/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 26

    E3 Plus Accessories

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    27/29Copyright 2009 Rockwell Automation, Inc. All rights reserved. 27

    E3 Plus Model EC5 Renewal Parts

    E3 Plus Replacement Overload Relay 193-NREC5ZZ

    E3 Plus Replacement Voltage input Module 193-NVEC5VIM

    E3 Plus Replacement Connectors 193-NCEC5CNT

    E3 Plus with Voltage Protection & Energy

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    28/29

    Copyright 2009 Rockwell Automation, Inc. All rights reserved. 28

    E3 Plus with Voltage Protection & EnergyMonitoring

    The E3 Plus Electronic Overload Relay with Voltage Protection

    and Energy Monitoring provides your with enhanced motorprotection and motor energy consumption information Enhanced Protection

    Current Protection

    Voltage Protection

    Power Protection Advanced Diagnostics

    Voltage Metering

    Energy Metering

    Additional Features

    Trip History

    Warning History

    Snapshot Record

    6 Digital Inputs

    E3 Status Object (Object Class 0x375)

  • 8/13/2019 193-ec5external-120127081657-phpapp02

    29/29

    Copyright 2009 Rockwell Automation, Inc. All r ights reserved.

    Bulletin 193/592Model EC5

    E3 Plus Electronic

    Overload Relay with

    Voltage Protection and

    Energy Monitoring