16
Introduction 19.1 Modern relay design 19.2 Thermal (Overload) protection 19.3 Start/Stall protection 19.4 Short circuit protection 19.5 Earth fault protection 19.6 Negative phase sequence protection 19.7 Wound rotor induction motor protection 19.8 RTD temperature detection 19.9 Bearing failures 19.10 Undervoltage protection 19.11 Loss-of-load protection 19.12 Additional protection for synchronous motors 19.13 Motor protection examples 19.14 19 A.C. Motor Protection

19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

  • Upload
    letram

  • View
    235

  • Download
    2

Embed Size (px)

Citation preview

Page 1: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

Introduction 19.1

Modern relay design 19.2

Thermal (Overload) protection 19.3

Start/Stall protection 19.4

Short circuit protection 19.5

Earth fault protection 19.6

Negative phase sequence protection 19.7

Wound rotor inductionmotor protection 19.8

RTD temperature detection 19.9

Bearing failures 19.10

Undervoltage protection 19.11

Loss-of-load protection 19.12

Additional protectionfor synchronous motors 19.13

Motor protection examples 19.14

• 1 9 • A . C . M o t o r P r o t e c t i o n

Page 2: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

19.1 INTRODUCTION

There are a wide range of a.c. motors and motorcharacteristics in existence, because of the numerousduties for which they are used. All motors needprotection, but fortunately, the more fundamentalproblems affecting the choice of protection areindependent of the type of motor and the type of load towhich it is connected. There are some importantdifferences between the protection of induction motorsand synchronous motors, and these are fully dealt within the appropriate section.

Motor characteristics must be carefully considered whenapplying protection; while this may be regarded asstating the obvious, it is emphasised because it appliesmore to motors than to other items of power systemplant. For example, the starting and stallingcurrents/times must be known when applying overloadprotection, and furthermore the thermal withstand ofthe machine under balanced and unbalanced loadingmust be clearly defined.

The conditions for which motor protection is requiredcan be divided into two broad categories: imposedexternal conditions and internal faults. Table 19.1provides details of all likely faults that require protection.

19.2 MODERN RELAY DESIGN

The design of a modern motor protection relay must beadequate to cater for the protection needs of any one ofthe vast range of motor designs in service, many of thedesigns having no permissible allowance for overloads. Arelay offering comprehensive protection will have thefollowing set of features:

a. thermal protection

b. extended start protection

c. stalling protection

• 19 • A.C. Motor P rote ct ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 3 7 •

External Faults Internal faults

Unbalanced supplies Bearing failures

Undervoltages Winding faults

Single phasing Overloads

Reverse phase sequence

Table 19.1: Causes of motor failures

Page 3: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

d. number of starts limitation

e. short circuit protection

f. earth fault protection

g. winding RTD measurement/trip

h. negative sequence current detection

i. undervoltage protection

j. loss-of-load protection

k. out-of-step protection

l. loss of supply protection

m. auxiliary supply supervision

(items k and l apply to synchronous motors only)

In addition, relays may offer options such as circuitbreaker condition monitoring as an aid to maintenance.Manufacturers may also offer relays that implement areduced functionality to that given above where lesscomprehensive protection is warranted (e.g. inductionmotors of low rating).

The following sections examine each of the possiblefailure modes of a motor and discuss how protection maybe applied to detect that mode.

19.3 THERMAL (OVERLOAD) PROTECTION

The majority of winding failures are either indirectly ordirectly caused by overloading (either prolonged orcyclic), operation on unbalanced supply voltage, or singlephasing, which all lead through excessive heating to thedeterioration of the winding insulation until an electricalfault occurs. The generally accepted rule is thatinsulation life is halved for each 10° C rise intemperature above the rated value, modified by thelength of time spent at the higher temperature. As anelectrical machine has a relatively large heat storagecapacity, it follows that infrequent overloads of shortduration may not adversely affect the machine.However, sustained overloads of only a few percent mayresult in premature ageing and insulation failure.

Furthermore, the thermal withstand capability of themotor is affected by heating in the winding prior to afault. It is therefore important that the relaycharacteristic takes account of the extremes of zero andfull-load pre-fault current known respectively as the'Cold' and 'Hot' conditions.

The variety of motor designs, diverse applications, varietyof possible abnormal operating conditions and resultingmodes of failure result in a complex thermal relationship.A generic mathematical model that is accurate istherefore impossible to create. However, it is possible todevelop an approximate model if it is assumed that themotor is a homogeneous body, creating and dissipating

heat at a rate proportional to temperature rise. This isthe principle behind the ‘thermal replica’ model of amotor used for overload protection.

The temperature T at any instant is given by:

T = Tmax (1 - e-t/τ)where:

Tmax = final steady state temperatureτ = heating time constant

Temperature rise is proportional to the current squared:

where:

IR = current which, if flowing continuously, producestemperature Tmax in the motor

Therefore, it can be shown that, for any overload currentI , the permissible time t for this current to flow is:

In general, the supply to which a motor is connected maycontain both positive and negative sequencecomponents, and both components of current give rise toheating in the motor. Therefore, the thermal replicashould take into account both of these components, atypical equation for the equivalent current being:

where

I1 = positive sequence current

I2 = negative sequence current

and

K =negative sequence rotor resistance———————————————————---------—positive sequence rotor resistance

at rated speed. A typical value of K is 3.

Finally, the thermal replica model needs to take intoaccount the fact that the motor will tend to cool downduring periods of light load, and the initial state of themotor. The motor will have a cooling time constant, τr ,that defines the rate of cooling. Hence, the final thermalmodel can be expressed as:

…Equation 19.1t k A ke= −( ) −( )τ log 2 2 2 1

I I KIeq = +( )12

22

tI I

e

R

=− ( ){ }

τ log 1

12

T KI eRt= − −2 1( )τ

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 3 8 •

Page 4: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

where:

Ith = thermal setting current

Equation 19.1 takes into account the ‘cold’ and ‘hot’characteristics defined in IEC 60255, part 8.

Some relays may use a dual slope characteristic for theheating time constant, and hence two values of theheating time constant are required. Switching betweenthe two values takes place at a pre-defined motorcurrent. This may be used to obtain better trippingperformance during starting on motors that use a star-delta starter. During starting, the motor windings carryfull line current, while in the ‘run’ condition, they carryonly 57% of the current seen by the relay. Similarly,when the motor is disconnected from the supply, theheating time constant τ is set equal to the cooling timeconstant τr.

Since the relay should ideally be matched to theprotected motor and be capable of close sustainedoverload protection, a wide range of relay adjustment isdesirable together with good accuracy and low thermalovershoot.

Typical relay setting curves are shown in Figure 19.1.

τ =

=

=

heating time constant

initial state of motor (cold or hot)

kI

I

A

eq

th

2

19.4 START/STALL PROTECTION

When a motor is started, it draws a current well in excessof full load rating throughout the period that the motortakes to run-up to speed. While the motor startingcurrent reduces somewhat as motor speed increases, it isnormal in protection practice to assume that the motorcurrent remains constant throughout the starting period.The starting current will vary depending on the design ofthe motor and method of starting. For motors startedDOL (direct-on-line), the nominal starting current can be4-8 times full-load current. However, when a star-delta

starter is used, the line current will only be of theDOL starting current.

Should a motor stall whilst running, or fail to start, dueto excessive loading, the motor will draw a current equalto its’ locked rotor current. It is not therefore possible todistinguish between a stall condition and a healthy startsolely on the basis of the current drawn. Discriminationbetween the two conditions must be made based on theduration of the current drawn. For motors where thestarting time is less than the safe stall time of the motor,protection is easy to arrange.

However, where motors are used to drive high inertialoads, the stall withstand time can be less than thestarting time. In these cases, an additional means mustbe provided to enable discrimination between the twoconditions to be achieved.

19.4.1 Excessive Start Time/Locked Rotor Protection

A motor may fail to accelerate from rest for a number ofreasons:

loss of a supply phase

mechanical problems

low supply voltage

excessive load torque

etc.

A large current will be drawn from the supply, and causeextremely high temperatures to be generated within themotor. This is made worse by the fact that the motor isnot rotating, and hence no cooling due to rotation isavailable. Winding damage will occur very quickly –either to the stator or rotor windings depending on thethermal limitations of the particular design (motors aresaid to be stator or rotor limited in this respect). Themethod of protection varies depending on whether thestarting time is less than or greater than the safe stalltime. In both cases, initiation of the start may be sensedby detection of the closure of the switch in the motorfeeder (contactor or CB) and optionally current risingabove a starting current threshold value – typically

1 3

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 3 9 •

Figure 19.1: Thermal overload characteristic curvesCold curves. Initial thermal state 0%

Ieq in terms of the currentthermal threshold Iθ Iθ I >

10

1

10

100

1000

10 000

100 000

10

Ope

ratin

g tim

e (s

econ

ds)

T =Te2T =30min2

Te1T =Te2T =24minTe1T

=12minTe1T e2=6minminmin

Te1e1T e2e2=1min

e1 e2=36minT =T =42min

Te1T =Te2T =48min

Te1T TTe2T =54min

Te1T e2=60min

Page 5: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

200% of motor rated current. For the case of bothconditions being sensed, they may have to occur withina narrow aperture of time for a start to be recognised.

Special requirements may exist for certain types ofmotors installed in hazardous areas (e.g. motors withtype of protection EEx ‘e’) and the setting of the relaymust take these into account. Sometimes a permissiveinterlock for machine pressurisation (on EEx ‘p’machines) may be required, and this can be convenientlyachieved by use of a relay digital input and the in-builtlogic capabilities.

19.4.1.1 Start time < safe stall time

Protection is achieved by use of a definite timeovercurrent characteristic, the current setting beinggreater than full load current but less than the startingcurrent of the machine. The time setting should be alittle longer than the start time, but less than thepermitted safe starting time of the motor. Figure 19.2illustrates the principle of operation for a successfulstart.

Figure 19.2. Relay setting for successful start: starttime<stall time

19.4.1.2 Start time => safe stall time

For this condition, a definite time overcurrentcharacteristic by itself is not sufficient, since the timedelay required is longer than the maximum time that themotor can be allowed to carry starting current safely. Anadditional means of detection of rotor movement,indicating a safe start, is required. A speed-sensingswitch usually provides this function. Detection of a

successful start is used to select relay timer used for thesafe run up time. This time can be longer than the safestall time, as there is both a (small) decrease in currentdrawn by the motor during the start and the rotor fansbegin to improve cooling of the machine as itaccelerates. If a start is sensed by the relay throughmonitoring current and/or start device closure, but thespeed switch does not operate, the relay element usesthe safe stall time setting to trip the motor beforedamage can occur. Figure 19.3(a) illustrates the principleof operation for a successful start, and Figure 19.3(b) foran unsuccessful start.

Figure 19.3. Relay settings for start time> stall time

19.4.2 Stall Protection

Should a motor stall when running or be unable to startbecause of excessive load, it will draw a current from thesupply equivalent to the locked rotor current. It isobviously desirable to avoid damage by disconnectingthe machine as quickly as possible if this conditionarises.

Motor stalling can be recognised by the motor currentexceeding the start current threshold after a successfulstart – i.e. a motor start has been detected and the motorcurrent has dropped below the start current thresholdwithin the motor safe start time. A subsequent rise inmotor current above the motor starting currentthreshold is then indicative of a stall condition, andtripping will occur if this condition persists for greaterthan the setting of the stall timer. An instantaneousovercurrent relay element provides protection.

In many systems, transient supply voltage loss (typicallyup to 2 seconds) does not result in tripping of designatedmotors. They are allowed to re-accelerate uponrestoration of the supply. During re-acceleration, they

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 4 0 •

Figure 19.3: Motor start protectionStart time > Safe stall time

0

1

1

0

1

0

0

1

Stall timesetting

(b) Unsuccessful start

0

(a) Successful start

0

1

0

1

1

TripCommand

SpeedSwitch

Information

Current

CB Closed

TripCommand

SpeedSwitch

Information

Current

CB Closed0

1

Time

Time

Time

Time

Time

Time

Figure 19.2: Motor start protectionstart time < safe stall time

0.10.1

Tim

e (s

)

1

10

Current (p.u. )

100

1 10

Relay time settingMotor starting current

Relay current setting

Page 6: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

draw a current similar to the starting current for a periodthat may be several seconds. It is thus above the motorstall relay element current threshold. The stallprotection would be expected to operate and defeat theobject of the re-acceleration scheme.

A motor protection relay will therefore recognise thepresence of a voltage dip and recovery, and inhibit stallprotection for a defined period. The undervoltageprotection element (Section 19.11) can be used to detectthe presence of the voltage dip and inhibit stallprotection for a set period after voltage recovery.Protection against stalled motors in case of anunsuccessful re-acceleration is therefore maintained.

The time delay setting is dependent on the re-acceleration scheme adopted and the characteristics ofindividual motors. It should be established afterperforming a transient stability study for the re-acceleration scheme proposed.

19.4.3 Number of Starts Limitation

Any motor has a restriction on the number of starts thatare allowed in a defined period without the permittedwinding, etc. temperatures being exceeded. Startingshould be blocked if the permitted number of starts isexceeded. The situation is complicated by the fact thenumber of permitted ‘hot’ starts in a given period is lessthan the number of ‘cold’ starts, due to the differinginitial temperatures of the motor. The relay mustmaintain a separate count of ‘cold’ and ‘hot’ starts. Bymaking use of the data held in the motor thermal replica,‘hot’ and ‘cold’ starts can be distinguished.

To allow the motor to cool down between starts, a timedelay may be specified between consecutive starts (againdistinguishing between ‘hot’ and ‘cold’ starts). The startinhibit is released after a time determined by the motorspecification. The overall protection function is illustratedin Figure 19.4.

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 4 1 •

Figure 19.4: Start lockout information.

Time

Time

Time

0

1

0

1

0

1

Supervising time

Supervising time

Start lockout

No. of starts

Inhib. start time

Motor start detection

Page 7: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

19.5 SHORT-CIRCUIT PROTECTION

Motor short-circuit protection is often provided to caterfor major stator winding faults and terminal flashovers.Because of the relatively greater amount of insulationbetween phase windings, faults between phases seldomoccur. As the stator windings are completely enclosed ingrounded metal, the fault would very quickly involveearth, which would then operate the instantaneous earthfault protection. A single definite time overcurrent relayelement is all that is required for this purpose, set toabout 125% of motor starting current. The time delay isrequired to prevent spurious operation due to CT spillcurrents, and is typically set at 100ms. If the motor is fedfrom a fused contactor, co-ordination is required withthe fuse, and this will probably involve use of a long timedelay for the relay element. Since the object of theprotection is to provide rapid fault clearance to minimisedamage caused by the fault, the protection is effectivelyworthless in these circumstances. It is therefore onlyprovided on motors fed via circuit breakers.

Differential (unit) protection may be provided on larger HVmotors fed via circuit breakers to protect against phase-phase and phase-earth faults, particularly where thepower system is resistance-earthed. Damage to the motorin case of a fault occurring is minimised, as the differentialprotection can be made quite sensitive and hence detectsfaults in their early stages. The normal definite timeovercurrent protection would not be sufficiently sensitive,and sensitive earth fault protection may not be provided.The user may wish to avoid the detailed calculationsrequired of capacitance current in order to set sensitivenon-directional earth fault overcurrent protectioncorrectly on HV systems (Chapter 9) or there may be noprovision for a VT to allow application of directionalsensitive earth fault protection. There is still a lower limitto the setting that can be applied, due to spill currentsfrom CT saturation during starting, while on some motors,neutral current has been found to flow during starting,even with balanced supply voltages, that would cause thedifferential protection to operate. For details on theapplication of differential protection, refer to Chapter 10.However, non-directional earth fault overcurrentprotection will normally be cheaper in cases whereadequate sensitivity can be provided.

19.6 EARTH FAULT PROTECTION

One of the most common faults to occur on a motor is astator winding fault. Whatever the initial form of thefault (phase-phase, etc.) or the cause (cyclic overheating,etc.), the presence of the surrounding metallic frame andcasing will ensure that it rapidly develops into a faultinvolving earth. Therefore, provision of earth faultprotection is very important. The type and sensitivity ofprotection provided depends largely on the systemearthing, so the various types will be dealt with in turn.

It is common, however, to provide both instantaneousand time-delayed relay elements to cater for major andslowly developing faults.

19.6.1 Solidly-Earthed System

Most LV systems fall into this category, for reasons ofpersonnel safety. Two types of earth fault protection arecommonly found – depending on the sensitivity required.

For applications where a sensitivity of > 20% of motorcontinuous rated current is acceptable, conventionalearth fault protection using the residual CT connectionof Figure 19.5 can be used. A lower limit is imposed onthe setting by possible load unbalance and/or (for HVsystems) system capacitive currents.

Figure 19.5. Residual CT connection for earth faultprotection

Care must be taken to ensure that the relay does notoperate from the spill current resulting from unequal CTsaturation during motor starting, where the highcurrents involved will almost certainly saturate themotor CT’s. It is common to use a stabilising resistor inseries with the relay, with the value being calculatedusing the formula:

…Equation 19.2

where:Ist = starting current referred to CT secondaryI0 = relay earth fault setting (A)Rstab = stabilising resistor value (ohms)Rct = d.c. resistance of CT secondary (ohms)Rl = CT single lead restistance (ohms)

RII

R kR Rstabst

Oct l r= + +( )

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 4 2 •

Figure 19.5: Residual CT connectionfor earth fault protection

Ia+Ib+Ic

Ic

Ib

Ia

MiCOMP241

Downstream

a b cc b

aUpstream

Flow ofcurrent

Page 8: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

k = CT connection factor(= 1 for star pt at CT= 2 for star pt at relay)

Rr = relay input restistance (ohms)

The effect of the stabilising resistor is to increase theeffective setting of the relay under these conditions, andhence delay tripping. When a stabilising resistor is used,the tripping characteristic should normally beinstantaneous. An alternative technique, avoiding the useof a stabilising resistor is to use a definite time delaycharacteristic. The time delay used will normally have tobe found by trial and error, as it must be long enough toprevent maloperation during a motor start, but shortenough to provide effective protection in case of a fault.

Co-ordination with other devices must also be considered.A common means of supplying a motor is via a fusedcontactor. The contactor itself is not capable of breakingfault current beyond a certain value, which will normally bebelow the maximum system fault current – reliance isplaced on the fuse in these circumstances. As a tripcommand from the relay instructs the contactor to open,care must be taken to ensure that this does not occur untilthe fuse has had time to operate. Figure 19.6(a) illustratesincorrect grading of the relay with the fuse, the relayoperating first for a range of fault currents in excess of thecontactor breaking capacity. Figure 19.6(b) illustratescorrect grading. To achieve this, it may require the use ofan intentional definite time delay in the relay.

If a more sensitive relay setting is required, it is necessaryto use a core-balance CT. This is a ring type CT, throughwhich all phases of the supply to the motor are passed,plus the neutral on a four-wire system. The turns ratioof the CT is no longer related to the normal line currentexpected to flow, so can be chosen to optimise the pick-up current required. Magnetising current requirementsare also reduced, with only a single CT core to bemagnetised instead of three, thus enabling low settingsto be used. Figure 19.7 illustrates the application of acore-balance CT, including the routing of the cablesheath to ensure correct operation in case of core-sheathcable faults.

19.6.2 Resistance-Earthed Systems

These are commonly found on HV systems, where theintention is to limit damage caused by earth faultsthrough limiting the earth fault current that can flow.Two methods of resistance earthing are commonly used:

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 4 3 •

Figure 19.6: Grading of relay with fused contactor

Time

Current

E/F relay

Fuse Contactorbreakingcapacity

Contactorbreakingcapacity

(b) Correct

Current(a) Incorrect

TimeFuse

E/F relay

Figure 19.7: Application of core-balance CT

Cable gland /sheathground connection

Cable gland

Cable box

SEF

SEF

SEF

No operation

(b) Incorrect wiring

Operation

(c) Correct wiring

(a) Connection

Page 9: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

19.6.2.1 Low resistance earthing

In this method, the value of resistance is chosen to limitthe fault current to a few hundred amps – values of200A-400A being typical. With a residual connection ofline CT’s, the minimum sensitivity possible is about 10%of CT rated primary current, due to the possibility of CTsaturation during starting. For a core-balance CT, the

sensitivity that is possible using a simple non-directionalearth fault relay element is limited to three times thesteady-state charging current of the feeder. The settingshould not be greater than about 30% of the minimumearth fault current expected. Other than this, theconsiderations in respect of settings and time delays areas for solidly earthed systems.

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 4 4 •

Figure 19.8: Current distribution in insulated-earth system for phase-earth fault

Ia1

Ib1

IR1

Ia2

Ib2

IR2

Ia3

Ib3

IR3

IH1

IR3=IH1+ IH2+ IH3-IH3:-

IR3= IH1+ IH2

-jXc1

IH2

IH3IH1+IH2

IH1+IH2+IH3

-jXc2

-jXc3

Page 10: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

19.6.2.2 High resistance earthing

In some HV systems, high resistance earthing is used tolimit the earth fault current to a few amps. In this case,the system capacitive charging current will normallyprevent conventional sensitive earth fault protectionbeing applied, as the magnitude of the charging currentwill be comparable with the earth fault current in theevent of a fault. The solution is to use a sensitivedirectional earth fault relay. A core balance CT is used inconjunction with a VT measuring the residual voltage ofthe system, with a relay characteristic angle setting of+45° (see Chapter 9 for details). The VT must be suitablefor the relay and therefore the relay manufacturer shouldbe consulted over suitable types – some relays requirethat the VT must be able to carry residual flux and thisrules out use of a 3-limb, 3-phase VT. A setting of 125%of the single phase capacitive charging current for thewhole system is possible using this method. The timedelay used is not critical but must be fast enough todisconnect equipment rapidly in the event of a secondearth fault occurring immediately after the first.Minimal damage is caused by the first fault, but thesecond effectively removes the current limitingresistance from the fault path leading to very large faultcurrents.

An alternative technique using residual voltage detectionis also possible, and is described in the next section.

19.6.3 Insulated Earth System

Earth fault detection presents problems on these systemssince no earth fault current flows for a single earth fault.However, detection is still essential as overvoltages occuron sound phases and it is necessary to locate and clearthe fault before a second occurs. Two methods arepossible, detection of the resulting unbalance in systemcharging currents and residual overvoltage.

19.6.3.1 System charging current unbalance

Sensitive earth fault protection using a core-balance CTis required for this scheme. The principle is that detailedin Section 9.16.2, except that the voltage is phase shiftedby +90° instead of -90°. To illustrate this, Figure 19.8shows the current distribution in an Insulated systemsubjected to a C-phase to earth fault and Figure 19.9 therelay vector diagram for this condition. The residualcurrent detected by the relay is the sum of the chargingcurrents flowing in the healthy part of the system plusthe healthy phase charging currents on the faultedfeeder – i.e. three times the per phase charging currentof the healthy part of the system. A relay setting of 30%of this value can be used to provide protection withoutthe risk of a trip due to healthy system capacitivecharging currents. As there is no earth fault current, it isalso possible to set the relay at site after deliberately

applying earth faults at various parts of the system andmeasuring the resulting residual currents.

If it is possible to set the relay to a value between thecharging current on the feeder being protected and thecharging current for the rest of the system, thedirectional facility is not required and the VT can bedispensed with.

The comments made in earlier sections on grading withfused contactors also apply.

19.6.3.2 Residual voltage method

A single earth fault results in a rise in the voltagebetween system neutral and earth, which may bedetected by a relay measuring the residual voltage of thesystem (normally zero for a perfectly balanced, healthysystem). Thus, no CT’s are required, and the techniquemay be useful where provision of an extensive number ofcore-balance CT’s is impossible or difficult, due tophysical constraints or on cost grounds. The VT’s usedmust be suitable for the duty, thus 3-limb, 3-phase VT’sare not suitable, and the relay usually has alarm and tripsettings, each with adjustable time delays. The settingvoltage must be calculated from knowledge of systemearthing and impedances, an example for a resistance-earthed system is shown in Figure 19.10.

Grading of the relays must be carried out with care, asthe residual voltage will be detected by all relays in theaffected section of the system. Grading has to be carriedout with this in mind, and will generally be on a timebasis for providing alarms (1st stage), with a high setdefinite time trip second stage to provide backup.

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 4 5 •

Figure 19.9: Relay vector diagram

An RCA setting of +90° shiftsthe MTA to here

Operate

Restrain

IR1IIb1II

Ia1I

VcpfVcpfV

VapfVV

VafVV

Vbf

Vbpf

Vres

(=-3VoVoV )

IR3I H1+ IH2I )

Page 11: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

19.6.4 Petersen Coil Earthed System

Earthing of a HV power system using a reactor equal tothe system shunt capacitance is known as Petersen Coil(or resonant coil) earthing. With this method, a singleearth fault results in zero earth fault current flowing (forperfect balance between the earthing inductance andsystem shunt capacitance), and hence the system can berun in this state for a substantial period of time while thefault is located and corrected. The detailed theory andprotection method is explained in Section 9.17.

19.7 NEGATIVE PHASE SEQUENCE PROTECTION

Negative phase sequence current is generated from anyunbalanced voltage condition, such as unbalanced

loading, loss of a single phase, or single-phase faults.The latter will normally be detected by earth faultprotection, however, a fault location in a motor windingmay not result in the earth fault protection operatingunless it is of the sensitive variety.

The actual value of the negative sequence currentdepends on the degree of unbalance in the supply voltageand the ratio of the negative to the positive sequenceimpedance of the machine. The degree of unbalancedepends on many factors, but the negative sequenceimpedance is more easily determined. Considering theclassical induction motor equivalent circuit withmagnetising impedance neglected of Figure 19.11:

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 4 6 •

Figure 19.10: Residual voltage earth fault protection for resistance-earthed system.

A - G

ZE

ZL

ZS

VA-G

VB-G

VC-G

VA-G

VA-G

VA-G

VRES

VRES

VRES V

B-GV

B-GV

B-G

VA-G

VB-G

VC-G

VC-G

VC-GV

C-G

VC-G V

B-G

N

ES R F

S

G,F

R

G,F

S

G,FR

S

VRES

ZSO +3Z

E

2ZS1 +Z

SO +2ZL1

+ZLO

+3ZE

x3E=

Page 12: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

Motor positive sequence impedance at slip s

Hence, at standstill (s=1.0), impedance

The motor negative sequence impedance at slip s

and, at normal running speed, the impedance

where:

suffix p indicates positive sequence quantities

and

suffix n indicates negative sequence quantities

Now, if resistance is neglected (justifiable as theresistance is small compared to the reactance), it can beseen that the negative sequence reactance at runningspeed is approximately equal to the positive sequencereactance at standstill. An alternative more meaningfulway of expressing this is:

positive seq. impedance =

starting current—-———————————---------— ——————---------—negative seq. impedance rated current

and it is noted that a typical LV motor starting current is6xFLC. Therefore, a 5% negative sequence voltage (dueto, say, unbalanced loads on the system) would producea 30% negative sequence current in the machine,

= +( ) + +( )

R R X Xn n n n1 22

1 22 0 5

2' '.

= +( ) + +( )

R R s X Xn n n n1 22

1 22 0 5

' '.

= +( ) + +( )

R R X Xp p p p1 22

1 22 0 5

' '.

= + −( )( ) + +( )

R R s X Xp p p p1 2 1 22

0 5

22' '

.

leading to excessive heating. For the same motor,negative sequence voltages in excess of 17% will resultin a negative sequence current larger than rated full loadcurrent.

Negative sequence current is at twice supply frequency.Skin effect in the rotor means that the heating effect inthe rotor of a given negative sequence current is largerthan the same positive sequence current. Thus, negativesequence current may result in rapid heating of themotor. Larger motors are more susceptible in thisrespect, as the rotor resistance of such machines tends tobe higher. Protection against negative sequence currentsis therefore essential.

Modern motor protection relays have a negativesequence current measurement capability, in order toprovide such protection. The level of negative sequenceunbalance depends largely upon the type of fault. Forloss of a single phase at start, the negative sequencecurrent will be 50% of the normal starting current. It ismore difficult to provide an estimate of the negativesequence current if loss of a phase occurs while running.This is because the impact on the motor may vary widely,from increased heating to stalling due to the reducedtorque available.

A typical setting for negative sequence currentprotection must take into account the fact that themotor circuit protected by the relay may not be thesource of the negative sequence current. Time should beallowed for the appropriate protection to clear thesource of the negative sequence current withoutintroducing risk of overheating to the motor beingconsidered. This indicates a two stage trippingcharacteristic, similar in principle to overcurrentprotection. A low-set definite time-delay element canbe used to provide an alarm, with an IDMT element usedto trip the motor in the case of higher levels of negativesequence current, such as loss-of-phase conditions atstart, occurring. Typical settings might be 20% of CTrated primary current for the definite time element and50% for the IDMT element. The IDMT time delay has tobe chosen to protect the motor while, if possible, gradingwith other negative sequence relays on the system.Some relays may not incorporate two elements, in whichcase the single element should be set to protect themotor, with grading being a secondary consideration.

19.8 FAULTS IN ROTOR WINDINGS

On wound rotor machines, some degree of protectionagainst faults in the rotor winding can be given by aninstantaneous stator current overcurrent relay element.As the starting current is normally limited by resistanceto a maximum of twice full load, the instantaneous unitcan safely be set to about three times full load if a slight

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 4 7 •

Figure 19.11: Induction motor equivalent circuit

(a) Positive phase sequence equivalent circuit

(b) Negative phase sequence equivalent circuit

R1 + R '2 j(X1 + X '2)

j(X1 + X '2)

[(1-s)/s] x R '2

[(s-1)/(2-s)] x R '2

R1 + R '2

Page 13: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

time delay of approximately 30 milliseconds isincorporated. It should be noted that faults occurring inthe rotor winding would not be detected by anydifferential protection applied to the stator.

19.9 RTD TEMPERATURE DETECTION

RTD’s are used to measure temperatures of motorwindings or shaft bearings. A rise in temperature maydenote overloading of the machine, or the beginning ofa fault in the affected part. A motor protection relay willtherefore usually have the capability of accepting anumber of RTD inputs and internal logic to initiate analarm and/or trip when the temperature exceeds theappropriate setpoint(s). Occasionally, HV motors are fedvia a unit transformer, and in these circumstances, someof the motor protection relay RTD inputs may beassigned to the transformer winding temperature RTD’s,thus providing overtemperature protection for thetransformer without the use of a separate relay.

19.10 BEARING FAILURES

There are two types of bearings to be considered: theanti-friction bearing (ball or roller), used mainly on smallmotors (up to around 350kW), and the sleeve bearing,used mainly on large motors.

The failure of ball or roller bearings usually occurs veryquickly, causing the motor to come to a standstill aspieces of the damaged roller get entangled with theothers. There is therefore very little chance that anyrelay operating from the input current can detectbearing failures of this type before the bearing iscompletely destroyed. Therefore, protection is limited todisconnecting the stalled motor rapidly to avoidconsequential damage. Refer to Section 19.2 on stallprotection for details of suitable protection.

Failure of a sleeve bearing can be detected by means ofa rise in bearing temperature. The normal thermaloverload relays cannot give protection to the bearingitself but will operate to protect the motor fromexcessive damage. Use of RTD temperature detection, asnoted in Section 19.9, can provide suitable protection,allowing investigation into the cause of the bearingrunning hot prior to complete failure.

19.11 UNDERVOLTAGE PROTECTION

Motors may stall when subjected to prolongedundervoltage conditions. Transient undervoltages willgenerally allow a motor to recover when the voltage isrestored, unless the supply is weak.

Motors fed by contactors have inherent undervoltageprotection, unless a latched contactor is used. Where aspecific undervoltage trip is required, a definite timeundervoltage element is used. If two elements areprovided, alarm and trip settings can be used. Aninterlock with the motor starter is required to block relayoperation when the starting device is open, otherwise astart will never be permitted. The voltage and time delaysettings will be system and motor dependent. They mustallow for all voltage dips likely to occur on the systemduring transient faults, starting of motors, etc. to avoidspurious trips. As motor starting can result in a voltagedepression to 80% of nominal, the voltage setting islikely to be below this value. Re-acceleration is normallypossible for voltage dips lasting between 0.5-2 seconds,depending on system, motor and drive characteristics,and therefore the time delay will be set bearing thesefactors in mind.

19.12 LOSS-OF-LOAD PROTECTION

Loss-of-load protection has a number of possiblefunctions. It can be used to protect a pump againstbecoming unprimed, or to stop a motor in case of afailure in a mechanical transmission (e.g. conveyor belt),or it can be used with synchronous motors to protectagainst loss-of-supply conditions. Implementation ofthe function is by a low forward power relay element,interlocked with the motor starting device to preventoperation when the motor is tripped and thus preventinga motor start. Where starting is against a very low load(e.g. a compressor), the function may also need to beinhibited for the duration of the start, to preventmaloperation.

The setting will be influenced by the function to beperformed by the relay. A time delay may be requiredafter pickup of the element to prevent operation duringsystem transients. This is especially important forsynchronous motor loss-of supply protection.

19.13 ADDIT IONAL PROTECTIONFOR SYNCHRONOUS MOTORS

The differences in construction and operationalcharacteristics of synchronous motors mean thatadditional protection is required for these types of motor.This additional protection is discussed in the followingsections.

19.13.1 Out-of-Step Protection

A synchronous motor may decelerate and losesynchronism (fall out-of-step) if a mechanical overloadexceeding the peak motor torque occurs. Otherconditions that may cause this condition are a fall in the

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 4 8 •

Page 14: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

applied voltage to stator or field windings. Such a fallmay not need to be prolonged, a voltage dip of a fewseconds may be all that is required. An out-of-stepcondition causes the motor to draw excessive currentand generate a pulsating torque. Even if the cause isremoved promptly, the motor will probably not recoversynchronism, but eventually stall. Hence, it must bedisconnected from the supply.

The current drawn during an out-of-step condition is ata very low power factor. Hence a relay element thatresponds to low power factor can be used to provideprotection. The element must be inhibited duringstarting, when a similar low power factor conditionoccurs. This can conveniently be achieved by use of adefinite time delay, set to a value slightly in excess of themotor start time.

The power factor setting will vary depending on the ratedpower factor of the motor. It would typically be 0.1 lessthan the motor rated power factor i.e. for a motor ratedat 0.85 power factor, the setting would be 0.75.

19.13.2 Protection againstSudden Restoration of Supply

If the supply to a synchronous motor is interrupted, itis essential that the motor breaker be tripped as quicklyas possible if there is any possibility of the supplybeing restored automatically or without the machineoperator’s knowledge.

This is necessary in order to prevent the supply beingrestored out of phase with the motor generated voltage.

Two methods are generally used to detect this condition,in order to cover different operating modes of the motor.

19.13.2.1 Underfrequency protection

The underfrequency relay element will operate in thecase of the supply failing when the motor is on load,which causes the motor to decelerate quickly. Typically,two elements are provided, for alarm and tripindications.

The underfrequency setting value needs to consider thepower system characteristics. In some power systems,lengthy periods of operation at frequencies substantiallybelow normal occur, and should not result in a motortrip. The minimum safe operating frequency of themotor under load conditions must therefore bedetermined, along with minimum system frequency.

19.13.2.2 Low-forward-power protection

This can be applied in conjunction with a time delay todetect a loss-of-supply condition when the motor mayshare a busbar with other loads. The motor may attemptto supply the other loads with power from the storedkinetic energy of rotation.

A low forward power relay can detect this condition. SeeSection 19.12 for details. A time delay will be requiredto prevent operation during system transients leading tomomentary reverse power flow in the motor.

19.14 MOTOR PROTECTION EXAMPLES

This section gives examples of the protection of HV andLV induction motors.

19.14.1 Protection of a HV Motor

Table 19.2 gives relevant parameters of a HV inductionmotor to be protected. Using a MiCOM P241 motorprotection relay, the important protection settings arecalculated in the following sections.

19.14.1.1 Thermal protection

The current setting ITH is set equal to the motor full loadcurrent, as it is a CMR rated motor. Motor full loadcurrent can be calculated as 211A, therefore (insecondary quantities):

Use a value of 0.85, nearest available setting.

The relay has a parameter, K, to allow for the increasedheating effect of negative sequence currents. In theabsence of any specific information, use K=3.

Two thermal heating time constants are provided, τ1 andτ2. τ2 is used for starting methods other than DOL,otherwise it is set equal to τ1. τ1 is set to the heatingtime constant, hence τ1=τ2=25mins. Cooling timeconstant τr is set as a multiple of τ1. With a cooling timeconstant of 75mins,

τr = 3 x τ1

I TH = =211250

0 844 .

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 4 9 •

Quantity Value

Rated output 1000kW CMR

Rated Voltage 3.3kV

Rated frequency 50Hz

Rated power factor/efficiency 0.9/0.92

Stall withstand time cold/hot 20/7s

Starting current 550% DOL

Permitted starts cold/hot 3/2

CT ratio 250/1

Start time@100% voltage 4s

Start time@ 80% voltage 5.5s

Heating/cooling time constant 25/75 min

System earthing Solid

Control device Circuit Breaker

Table 19.2: Motor data for example

Page 15: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

19.14.1.2 Short circuit protection

Following the recommendations of Section 19.5, with astarting current of 550% of full load current, the short-circuit element is set to 1.25 x 5.5 x 211A = 1450A. Interms of the relay nominal current, the setting value is1450/250 = 5.8IN.

There is a minimum time delay of 100ms for currents upto 120% of setting to allow for transient CT saturationduring starting and 40ms above this current value. Thesesettings are satisfactory.

19.14.1.3 earth fault protection

It is assumed that no CBCT is fitted. A typical setting of30% of motor rated current is used, leading to anearth fault relay setting of 0.3 x 211/250 = 0.25IN. Astabilising resistor is required, calculated in accordancewith Equation 19.2 to prevent maloperation due to CTspill current during starting as the CT’s may saturate.With the stabilising resistor present, instantaneoustripping is permitted.

The alternative is to omit the stabilising resistor and usea definite time delay in association with the earth faultelement. However, the time delay must be found by trialand error during commissioning.

19.14.1.4 Locked rotor/Excessive start time protection

The current element must be set in excess of the ratedcurrent of the motor, but well below the starting currentof the motor to ensure that a start condition isrecognised (this could also be achieved by use of anauxiliary contact on the motor CB wired to the relay). Asetting of 500A (2 x IN) is suitable. The associated timedelay needs to be set to longer than the start time, butless than the cold stall time. Use a value of 15s.

19.14.1.5 Stall protection

The same current setting as for locked rotor protectioncan be used – 500A. The time delay has to be less thanthe hot stall time of 7s but greater than the start time bya sufficient margin to avoid a spurious trip if the starttime happens to be a little longer than anticipated. Usea value of 6.5s.

The protection characteristics for Sections 19.14.1.1-5are shown in Figure 19.12.

19.14.1.6 Negative phase sequence protection

Two protection elements are provided, the first is definitetime-delayed to provide an alarm. The second is an IDMTelement used to trip the motor on high levels of negativesequence current, such as would occur on a loss of phasecondition at starting.

In accordance with Section 19.7, use a setting of 20%with a time delay of 30s for the definite time elementand 50% with a TMS of 1.0 for the IDMT element. The

resulting characteristic is shown in Figure 19.13. Themotor thermal protection, as it utilises a negativesequence component, is used for protection of the motorat low levels of negative sequence current.

19.14.1.7 Other protection considerations

If the relay can be supplied with a suitable voltage signal,stall protection can be inhibited during re-accelerationafter a voltage dip using the undervoltage element (set to80-85% of rated voltage). Undervoltage protection (setto approximately 80% voltage with a time delay of up toseveral seconds, dependent on system characteristics)and reverse phase protection can also be implemented toprovide extra protection. Unless the drive is critical to theprocess, it is not justifiable to provide a VT specially toenable these features to be implemented.

19.14.2 Protection of an LV Motor

LV motors are commonly fed via fused contactors andtherefore the tripping times of a protection relay for

• 19 •

A.C

.M

otor

Pro

tect

ion

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e• 3 5 0 •

Figure 19.12: Protection characteristicsfor motor protection example

1000

100

10

1

0.1

0.01

Tim

e (s

ec)

10.01 10IthI /I (pu)

Cold ThermalHot ThermalS/CLocked RotorStallStart Current (100%V)Start Current (80%V)

Motor tripping characteristics.

Figure 19.13: Motor protection example-negative sequence protection characteristic

Current (A) 1000010

10

1

0.1

Tim

e (s

ec)

Page 16: 19 A.C. Motor Protection - fecime.org · 19.1 INTRODUCTION There are a wide range of a.c. motors and motor characteristics in existence, because of the numerous duties for which they

overcurrent must be carefully co-ordinated with the fuseto ensure that the contactor does not attempt to break acurrent in excess of its rating. Table 19.3(a) gives detailsof an LV motor and associated fused contactor. AMiCOM P211 motor protection relay is used to providethe protection.

19.14.2.1 CT ratio

The relay is set in secondary quantities, and therefore asuitable CT ratio has to be calculated. From the relaymanual, a CT with 5A secondary rating and a motor ratedcurrent in the range of 4-6A when referred to thesecondary of CT is required. Use of a 150/5A CT gives amotor rated current of 4.4A when referred to the CTsecondary, so use this CT ratio.

19.14.2.2 Overcurrent (short-circuit) protection

The fuse provides the motor overcurrent protection, as theprotection relay cannot be allowed to trip the contactor onovercurrent in case the current to be broken exceeds thecontactor breaking capacity. The facility for overcurrentprotection within the relay is therefore disabled.

19.14.2.3 Thermal (overload) protection

The motor is an existing one, and no data exists for itexcept the standard data provided in the manufacturerscatalogue. This data does not include the thermal(heating) time constant of the motor.

In these circumstances, it is usual to set the thermalprotection so that it lies just above the motor startingcurrent.

The current setting of the relay, Ib , is found using theformula

Ib = 5 x In/Ip

whereIn = motor rated primary currentIp = CT primary current

Hence, Ib = 5 x 132/150 = 4.4A

With a motor starting current of 670% of nominal, asetting of the relay thermal time constant with motorinitial thermal state of 50% of 15s is found satisfactory,as shown in Figure 19.14.

19.14.2.4 Negative sequence(phase unbalance) protection

The motor is built to IEC standards, which permit anegative sequence (unbalance) voltage of 1% on acontinuous basis. This would lead to approximately 7%negative sequence current in the motor (Section 19.7).As the relay is fitted only with a definite time relayelement, a setting of 20% (from Section 19.7) isappropriate, with a time delay of 25s to allow for shorthigh-level negative sequence transients arising fromother causes.

19.14.2.5 Loss of phase protection

The relay has a separate element for this protection. Lossof a phase gives rise to large negative sequence currents,and therefore a much shorter time delay is required. Adefinite time delay of 5s is considered appropriate.The relay settings are summarised in Table 19.3(b).

• 19 •A

.C.

Mot

or P

rote

ctio

n

N e t w o r k P r o t e c t i o n & A u t o m a t i o n G u i d e • 3 5 1 •

Figure 19.14: Motor protection example - contactor-fed motor

(a) LV Motor Protection - contactor fed example

(b) Relay trip characteristic

Cable

CTP211

Contactor

250A

M

I/IbI/IbI/I0

1

Tim

e

1 2 3 4 5 6 7 8

10

100

1000

trip timestart current

Parameter Value Unit

Standard IEC 60034

Motor Voltage 400 V

Motor kW 75 kW

Motor kVA 91.45 kVA

Motor FLC 132 A

Starting Current 670 %

Starting Time 4.5 s

Contactor rating 300 A

Contactor breaking capacity 650 A

Fuse rating 250 A

(a) LV motor example data

Parameter Symbol Value Unit

Overcurrent Disabled -

Overload setting Ib 4.4 A

Overload time delay I>t 15 s

Unbalance I2 20 %

Unbalance time delay I2>t 25 s

Loss of phase time delay <Ip 5 s

(b) Relay settingsTable 19.3: LV Motor protection setting example