105
Installation and Operation Handbook Contents HA026696 Issue 1. Jul-99 Applies to 2208e and 2204e Controller software versions 3.03 i MODELS 2208e and 2204e TEMPERATURE CONTROLLERS INSTALLATION AND OPERATION HANDBOOK Contents Page Chapter 1 OPERATION ............................................................. 1-1 Chapter 2 INSTALLATION ........................................................... 2-1 Chapter 3 ACCESS LEVELS ...................................................... 3-1 Chapter 4 TUNING ..................................................................... 4-1 Chapter 5 CONFIGURATION ...................................................... 5-1 Chapter 6 USER CALIBRATION ................................................. 6-1 Chapter 7 ALARM CONFIGURATION ......................................... 7-1 Appendix A UNDERSTANDING THE ORDERING CODE ............. A-1 Appendix B SAFETY & EMC INFORMATION ............................ B-1 TECHNICAL SPECIFICATION ............................ B-6 Appendix C ADDRESS ............................ C-1 Appendix D VALVE POSITIONER ............................ D-1 Appendix E LOAD CURRENT MONITORING ………………… E-1 Appendix F RETRANSMISSION ………………… F-1 This product is covered by one or more of the following US Patents: 5,484,206 and 5,793,754; Additional patents pending. PDSIO is a registered trademark of Eurotherm. INSTANT ACCURACY™, SSRx Load Doctor™ and SSRx Enhanced Load Doctor ™ are trademarks of Eurotherm.”

170 0025

Embed Size (px)

DESCRIPTION

14

Citation preview

  • Installation and Operation Handbook Contents

    HA026696 Issue 1. Jul-99 Applies to 2208e and 2204e Controller software versions 3.03 i

    MODELS 2208e and 2204eTEMPERATURE CONTROLLERS

    INSTALLATION AND OPERATION HANDBOOK

    Contents Page

    Chapter 1 OPERATION ............................................................. 1-1

    Chapter 2 INSTALLATION ........................................................... 2-1

    Chapter 3 ACCESS LEVELS ...................................................... 3-1

    Chapter 4 TUNING ..................................................................... 4-1

    Chapter 5 CONFIGURATION ...................................................... 5-1

    Chapter 6 USER CALIBRATION ................................................. 6-1

    Chapter 7 ALARM CONFIGURATION ......................................... 7-1

    Appendix A UNDERSTANDING THE ORDERING CODE ............. A-1

    Appendix B SAFETY & EMC INFORMATION ............................ B-1

    TECHNICAL SPECIFICATION ............................ B-6

    Appendix C ADDRESS ............................ C-1

    Appendix D VALVE POSITIONER ............................ D-1

    Appendix E LOAD CURRENT MONITORING E-1

    Appendix F RETRANSMISSION F-1

    This product is covered by one or more of the following US Patents:5,484,206 and 5,793,754; Additional patents pending.

    PDSIO is a registered trademark of Eurotherm.INSTANT ACCURACY, SSRx Load Doctor and SSRx Enhanced Load Doctor

    are trademarks of Eurotherm.

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-1

    Chapter 1 OPERATION

    PAGE

    Front Panel Layouts1-2

    Getting Started1-4

    Navigation Diagram1-10

    Parameter Tables1-12

    Setting Alarm Levels1-19

    Diagnostic Alarms1-20

  • Operation Installation and Operation Handbook

    1-2 2208e and 2204e Controller

    FRONT PANEL LAYOUT

    Figure 1-1 Model 2208e front panel layout

    Figure 1-2 Model 2204e front panel layout

    DownButton

    Manual mode

    PageButton

    ScrollButton

    UpButton

    Remote Setpoint

    Output 2

    Upper readout

    Lower readout

    Output 1

    Setpoint 2active

    Setpoint ratelimit active

    OP1 OP2

    2204e

    SP2 REM

    PageButton

    ScrollButton

    DownButton

    UpButton

    Manual mode

    Setpoint 2 active PDSIO Remote Setpoint

    Setpoint rate limit active

    OP1 OP2

    SP2 REM

    2208e

    Output 1 Output 2

    Upper readout

    Lower readout

    RUN

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-3

    Button orindicator

    Name Explanation

    OP1 Output 1 When lit, it indicates that heating output is on.

    OP2 Output 2 When lit, it indicates that cooling output is on.

    SP2 Setpoint 2 When lit, this indicates that Setpoint 2 has beenselected.

    REM Remote SetpointWhen lit, this indicates that the PDSIO remoteSetpoint input has been selected. REM is alsoused to indicate that user comms is active.

    MAN Manual light When lit, it indicates that manual mode has beenselected

    RUN Run light When lit, it indicates that Setpoint rate limit isactive.

    Page button Press to select a new list of parameters.

    Scroll button Press to select a new parameter in a list.

    Down button Press to decrease a value in the lower readout.

    Up button Press to increase a value in lower readout.

    Figure 1.3 Controller buttons and indicators

    For Valve Positioning, please refer to Appendix D Motorised Valve ControlNOTE

  • Operation Installation and Operation Handbook

    1-4 2208e and 2204e Controller

    GETTING STARTED

    Thank you for selecting the EUROTHERM 2208e/2204e controller.This section shows the principle of operation.

    VIEWING THE PROCESS VALUE and SETPOINT

    Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3second self-test sequence, this is the display you will see,

    Figure 1.4 The Home Display

    The display may flash an alarm message. Refer to the Parameter Tables later in thischapter for a complete list and meaning of the messages.

    TO ADJUST THE SETPOINT

    Figure 1.5 The lower readout shows the setpoint

    After 2 seconds the lower readout will blink indicating that the new value has been accepted.For everyday use you may not need to do anymore than this.

    Output 1Actual Temperature (Process Value)Output 2

    Required Temperature (Setpoint)

    OP1 OP2

    Press and hold toincrease temperature

    Press and hold todecrease temperature

    OP1 OP2

    NOTE

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-5

    VIEWING THE DISPLAY UNITS

    Figure 1.6 Pressing or will flash the display units for 0.5 secs

    If you get lost, pressing and together will return you to the Home display

    USE OF THE SCROLL BUTTON

    Pressing the scroll button will display the output power level. Continued pressing willdisplay further parameters in the operator scroll list.

    Figure 1.7 Upper readout is parameter name. Lower is value

    Display Units

    Degrees Centigrade

    Degrees Farenheit

    Degrees KelvinNo units - Linear inputs

    Momentarilypress eitherbutton

    0.5 sec.

    Keep pressing to return to Homedisplay or select further parameters(if available)

    2nd press

    3rd press

    OutputActual output level %

    Manual/AutoActual state

    NOTE

  • Operation Installation and Operation Handbook

    1-6 2208e and 2204e Controller

    USE OF THE PAGE BUTTON

    The PAGE button accesses parameter LISTS.Parameters are settings in the instrument which, generally, can be changed by the user to suitthe process. Examples are: Alarms, Self Tune, etc. They are found under headings calledLISTS and a full set is given later in this chapter.

    Figure 1.8 Press to choose a parameter list

    The actual list headings may be longer or shorter than indicated above and you cancustomise this for the operators convenience in EDIT level, Chapter 3.

    1st press

    0.2 sec.

    Keep pressing toselect more list headings

    3rd press2nd press

    NOTE

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-7

    PARAMETER LISTS

    Press to choose a LIST - ALARMS is a good one. This list allows you to set thealarm trip levels. The parameters which appear in the list will vary according to theconfiguration of your controller.

    Figure 1.9 Choose a list. Press to select a parameter

    If, at any time, no key is pressed within 45 seconds, the display will alwaysreturn to the HOME display.

    or tochange trip level

    or tochange trip level

    1st press

    2nd press

    0.2 sec.

    There are 4 alarms inthe controller. The firstcharacter is the alarmnumber. The followingthree letters indicatealarm type as follows:

    Full Scale Low

    Full Scale High

    Deviation High

    Deviation Low

    Deviation Band

    Low current

    High currentDisabled alarms will notbe displayed.Chapter 7 gives a fulldescription of alarms.

    Alarm List

    Alarm 1

    Now pressthe SCROLLbutton

    2nd press

    Keep pressing1. to scroll through further parameters2. to return to list header

    Alarm 2

    NOTE

  • Operation Installation and Operation Handbook

    1-8 2208e and 2204e Controller

    OPERATING MODES

    The controller can be used in two modes:Automatic mode - in which the output power is automatically adjusted to hold thetemperature at the required value. The controller normally operates in this mode.Manual mode - in which the output is manually adjusted by the Operator. In this mode theMAN light will be on.

    One other mode is available:Remote setpoint - The setpoint is generated as an input signal from a master 2000 seriescontroller. In this mode the REM light is on.

    AUTO or MANUAL SELECT

    Figure 1.10 Auto/Manual select

    or to select

    2 sec.

    1st press

    OutputActual output level %

    Manual/Auto

    automatic mode

    manual mode

    2nd press

    3rd press

    Keep pressingto return to HOMEdisplay

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-9

    MANUAL ADJUSTMENT OF OUTPUT POWER

    Figure 1.11 The Home Display in manual mode

    SUMMARY

    To step through list headers press the Page button until the required header is obtained

    To step through parameters within a particular list press the Scroll button until therequired parameter is obtained

    To change the value (or state) of a parameter press the Raise button or theLower button

    The remainder of this chapter provides a complete list of all parameters available.

    Actual Temperature (Process Value)

    OP1 OP2

    Output Power Demand

    Manual Indicator on

    Press and hold toincrease power

    Press and hold todecrease power

    Manual mode is generally used for test and commissioning purposes, takecare not to leave the controller in this mode since damage or personal injurycould occur.

    NOTE

  • Operation Installation and Operation Handbook

    1-10 2208e and 2204e Controller

    NAVIGATION DIAGRAM (Part A)

    The navigation diagram shows a full list ofpossible parameters. However, some may notappear because they are dependent upon theparticular controller variant.

    Figure 1.12a Navigation diagram

    HomeList

    PID(1)List

    AlarmList

    AutotuneList

    SetpointList

    5

    2

    2

    2

    2

    8

    8

    8

    3

    3

    8

    8

    3

    3

    !

    4

    "

    9

    #$

    %&'

    $()

    *

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-11

    NAVAGATION DIAGRAM (PART B)

    .

    .

    The shaded boxes are normally hidden in Operator level. To see all the availableparameters you must select Full level. See Chapter 3, Access Levels

    Figure 1.12b Navigation diagram

    InputList

    OutputList

    CommsList

    AccessList

    On OffList(1)

    7

    7

    &

    Notes:1. Either the PID list or the On/Off list will be present

    depending upon the type of control in use.2. The last three characters depend upon the type of alarm

    configured3. Absolute setpoint limits are set in configuration, see Chapter

    5.4. VPOS only for VP. Refer to VP Appendix D.5. Amps is Mode 2 or Mode 5 PDSIO.6. mtr used for VP version. Refer to VP Appendix D.7. Beware! Used for calibration. See chapter 6.8. Is only available if using PDSIO comms in the HA slot.9. WSP is available if using ramp to setpoint.

    &

    %&

    %&

    $

    *

    Return toHome Display

    6

    +

    7

    +

    !

  • Operation Installation and Operation Handbook

    1-12 2208e and 2204e Controller

    PARAMETER TABLES

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingUK USA Value Value

    Home ListHome Measured Value and Setpoint(SP) SP=25C SP=75F as display

    Valve positioner output power

    %of mtr

    % Output Level

    %

    Working setpoint as display

    Setpoint

    as display

    Heater current (PDSIO modes 2 and 5)

    Amps

    Auto/manual select

    Configure lower readout of home display

    None, StD, AmPS,OP, stat, vPoS

    Customer ID

    Additional parameters may appear in the Home display if the promote feature has been used (see Edit Level, Chapter 3).

  • 2208e and 2204e Controller 1-13

    Installation and Operation Operation

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingUK USA Value Value

    Alarm List

    Alarm 1 set point value

    as display

    Alarm 2 set point value

    as display

    Alarm 3 set point value

    as display

    Alarm 4 set point value

    as displayIn place of dashes, the last three characters indicate the alarm type, as follows:

    Full Scale High alarm

    as display

    Full Scale Low alarm

    as display

    Deviation band alarm

    as display

    Deviation High alarm

    as display

    Deviation Low alarm

    as display

    Low current alarm

    AMPS

    High current alarm

    AMPS

    Hysteresis

    as display

    Loop break time

    secs

  • Operation Installation and Operation Handbook

    1-14 2208e and 2204e Controller

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value

    !

    !

    Autotune List!

    Self tune enable !

    Automatic droop compensation (ManualReset) enable (only present if ti set to OFF"! "! "!

    PID List

    Proportional band

    as display

    Integral time# #

    seconds

    Derivative time# #

    seconds

    Manual reset (appears when ti set to OFF)

    %

    Cutback low

    as display

    Cutback high

    as display

    Relative cool gain (set 1)

  • 2208e and 2204e Controller 1-15

    Installation and Operation Operation

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value

    Set Point List

    Select SP1 or SP2

    SP1 SP2

    Local or remote setpoint select

    Loc rmt

    Setpoint 1 value$ %

    As display range

    Setpoint 2 value$ %

    As display range

    Remote setpoint

    As display range

    Local trim

    As display range

    Setpoint 1 low limit

    As display range

    Setpoint 1 high limit

    As display range

    Setpoint 2 low limit

    As display range

    Setpoint 2 high limit

    As display range

    Local setpoint trim low limit #

    As display range

    Local setpoint trim high limit

    As display range

    Setpoint rate limit &&

    As display range'

    Dwell time

    0.1 to 999.9 minutes!

    End type , ,

    (

    Program control !,

    )

    Status of program

  • Operation Installation and Operation Handbook

    1-16 2208e and 2204e Controller

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value

    Input list* Input filter time constant # # && secs

    PV Offset

    as displayThe next 5 parameters will appear if User calibration has been enabled in configuration level. To perform a user calibration refer to Ch 6.

    FACt will re-instate factory settings and disable User Calibration. Default setting FACtUSEr will re-instate any previously set User Calibration offsets and make available User Calibration parameters as follows:

    User calibration select none none Hi, Lo, none*

    Adjust calibrated reference sourceThe following two parameters are always present in Full Access level but not in Operator level+

    Cold Junction compensation temperature

    ,

    Millivolt input

    * A minimum filter time constant of one second is recommended to provide sufficient noise immunity.

  • 2208e and 2204e Controller 1-17

    Installation and Operation Operation

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value

    Output list Note; If On/Off control is configured only , ! and ! will appear in the following list

    Low (power) output limit (cool) %

    High (power) output limit

    %

    Output setting when in sensor break

    %1-

    Heat cycle time (logic) (relay) secs!

    Heat output min. on time (50mS) secs

    1-

    Cool cycle time (logic) (relay) secs

    1!

    Cool output min. on time (50mS) secs

    VP motor travel time

    secs

    1 Are not used for Valve Position Control.

  • Operation Installation and Operation Handbook

    1-18 2208e and 2204e Controller

    Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value

    !&

    !&

    On/off listThis set of parameters only appear if On/Off control has been configured.-

    Heat hysteresis

    as display.-

    Cool hysteresis

    as display

    Heat/Cool dead band

    as display

    C omms list

    Communications address $

    Access list

    Full and Edit level password

    ( Goto level ///!

    !

    !

    Configuration level password

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-19

    SETTING ALARM LEVELS

    Up to 4 Alarms may be configured. Each alarm is given a name to describe its function -see table below:If an alarm is not configured it does not appear in the list below.

    In place of dashes,letters indicate alarmtype as follows: Full Scale Low Full Scale High Deviation Band Deviation High Deviation Low Low current High current

    Alarm List

    Alarm 1

    2nd press

    or to change

    3rd press

    4th press

    5th press

    Alarm 2

    Alarm 3

    Alarm 4

    Loop break time

    or to change

    or to change

    or to change

    or to change

    Press to returnto list header

    Figure 1.13

  • Operation Installation and Operation Handbook

    1-20 2208e and 2204e Controller

    DIAGNOSTIC ALARMSThese indicate that a fault exists in either the controller or the connected devices.

    Displayshows

    What it means What to do about it

    Electrically ErasableMemory Error:The value of an operatoror configurationparameter has beencorrupted.

    This fault will automatically take you intoconfiguration level. Check all of the configurationparameters before returning to operator level. Oncein operator level, check all of the operatorparameters before resuming normal operation. Ifthe fault persists or occurs frequently, contactEurotherm Controls.

    Sensor Break:Input sensor isunreliable or the inputsignal is out of range.

    Check that the sensor is correctly connected.

    Loop Break:The feedback loop isopen circuit.

    Check that the heating and cooling circuits areworking properly.

    Load failureIndication that there is afault in the heatingcircuit or the solid staterelay.

    This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR) operatingin PDSIO SSRx Load Doctor-see Electricalinstallation Chapter 2. It indicates either an open orshort circuit SSR, blown fuse, missing supply oropen circuit heater.

    Solid state relay failureIndication that there is afault in the solid staterelay

    This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR) operatingin PDSIO SSRx Load Doctor see Electricalinstallation Chapter 2. It indicates either an open orshort circuit condition in the SSR.

    Heater failureIndication that there is afault in heating circuit

    This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR) operatingin PDSIO SSRx Enhanced Load Doctor-seeElectrical installation Chapter 2. It indicates either ablown fuse, missing supply or open circuit heater.

    Hardware errorIndication that a moduleis of the wrong type.

    Check that the correct modules are fitted.

    No I/O moduleModules are configuredbut not fitted

    Fit module.

    Figure 1.14a Diagnostic alarms - continued on the next page

  • Installation and Operation Handbook Operation

    2208e and 2204e Controller 1-21

    Diagnostic alarms continued

    These indicate that a fault exists in either the controller or the connected devices.

    Displayshows

    What it means What to do about it

    Remote input failure. ThePDSIO input is opencircuit. (PDSIO Alsoknown as SST SmartSetpoint Transmission)

    Check for open or short circuit wiring on thePDSIO input

    Out of Display range, lowreading

    Check the value of the display range

    Out of Display range, highreading

    Check the value of the display range

    Error 1: ROM self-test fail Return the controller for repair

    Error 2: RAM self-test fail Return the controller for repair

    Error 3: Watchdog fail Return the controller for repair

    Error 4: Keyboard failureStuck button, or a buttonwas pressed during powerup.

    Switch the power off and then on withouttouching any of the controller buttons.

    Error 5: Input circuit failure Return the controller for repair*

    Power failure. The linevoltage is too low

    Check that the supply to the controller is withinthe rated limits

    Table 1.14b Diagnostic alarms

    *If the user has disassembled and reassembled the instrument, this error can occur if anyconnectors are not seated properly.

  • Installation and Operation Handbook Installation

    2208e and 2204e Controller 2-1

    Chapter 2 INSTALLATION

    PAGE

    Instrument Layouts ....................................................... 2-2

    Introduction ....................................................... 2-4

    Mechanical Installation ....................................................... 2-4

    Wiring ....................................................... 2-5

    Outputs 1 and 2 Connection ....................................................... 2-7

    Communication Connections ....................................................... 2-8

    Typical Wiring Diagram ....................................................... 2-10

  • Installation Installation and Operation Handbook

    2-2 2208e and 2204e Controller

    INSTRUMENT LAYOUTS

    Figure 2-1 2208e 1/8 DIN controller

    Figure 2-2 2204e 1/4 DIN controller

    3

    4

    4

    56

    78

    8

    1

    2

    2

    3

    4

    4

    5

    6

    7

    8

    8

    KEY

    1. Display screen

    2. Latching ears

    3. Panel sealing gasket

    4. Panel retaining clips

    5. Label

    6. Sleeve

    7. Terminal covers

    8. Ratchets

    2

    2

    1

  • Installation and Operation Handbook Installation

    2208e and 2204e Controller 2-3

    Outline dimensions Model 2208e

    Figure 2-3 Outline dimensions Model 2208e controller

    Outline dimensions Model 2204e

    Figure 2-4 Outline dimensions Model 2204es controller

    The controller plugs into a plastic sleeve, which in turn fits into the panel cutout shown inFigures 2-3 and 2-4.

    2208

    OP1 OP2

    SP2 REM

    Panelcutout

    92 x 45mm

    3.62x1.77in

    -0+0.8

    -0+0.6

    -0+0.03

    -0+0.02

    103mm (4.01in)48mm (1.89in)

    96mm(3.78in)

    38mm(1.5in)

    10mm(0.4in)

    (Not toscale)

    Recommendedminimum spacing ofcontrollers

    2204

    OP1 OP2

    SP2 REM

    Panel cutout

    92 x 92 -0 +0.8mm

    3.62 x 3.62 -0 +0.03in

    103mm (4.01in)96mm (3.78in)

    96mm3.78in

    Recommendedminimumspacing ofcontrollers

    38mm(1.5in)

    10mm(0.4in)

    (Not toscale)

  • Installation Installation and Operation Handbook

    2-4 2208e and 2204e Controller

    INTRODUCTION

    The Models 2208e and 2204e are precision temperature controllers with self tuning. Theyhave a modular hardware construction which provides two control outputs, two alarm relaysand one communications port. Two logic inputs are provided as standard. In addition theModel 2204e has an optional plug-in 10A relay heating output.

    Controller labels

    The labels on the sides of the controller identify the ordering code, the serial number, and thewiring connections.

    Appendix A, Understanding the Ordering Code explains the hardware and softwareconfiguration of your particular controller.

    MECHANICAL INSTALLATION

    To install the controller

    1. Cut the panel to the relevant hole size shown in Figure 2-3 and 2.4.

    2. Insert the controller through the front of this cutout.

    3. Spring the upper and lower panel retaining clips into place. Secure the controller inposition by holding it level and pushing both retaining clips forward.

    Note: If the panel retaining clips subsequently need removing, they can be unhooked from theside with either your fingers or a screwdriver.

    Unplugging and plugging-in the controller

    The controller can be unplugged from its sleeve by easing the latching ears outwards andpulling it forward out of the sleeve. When plugging the controller back into its sleeve, ensurethat the latching ears click into place to maintain the IP 65 sealing.

  • Installation and Operation Handbook Installation

    2208e and 2204e Controller 2-5

    WIRING

    Please read Appendix B, Safety and EMC information before proceeding.

    WARNINGPlease ensure that the controller is correctly configured for your application.Incorrect configuration could result in damage to the process being controlled,and/or personal injury. The controller may either have been configured whenordered, or may need configuring now. See Chapter 5, Configuration.

    The wiring connections are shown in figure 2-5. Outputs 1 and 2 are factory fitted moduleswhich can be any one of the types shown in figure 2-8. Check the ordering code on thecontroller side label to determine which have been fitted.

    Model 2208e connections

    Figure 2-5 Model 2208e wiring connections

    *The ground connection is not required for electrical safety but must be connected to satisfyEMC requirements.

    *Do not use unused terminals as wire holders.

    Pt100

    N

    L

    V+

    VI

    V-

    Line

    Neutral

    Ground

    +

    -

    +PV-

    2B

    2A

    1B

    1A

    HF

    HD

    HECommon

    Input 1

    Input 2

    85 to 264Vac

    LC

    LA

    LB

    AC

    AB

    Output 1

    3B

    3A

    3C

    Output 2

    Output 4

    Output 3

    AA

    HB

    HC

    HA

    Comms

  • Installation Installation and Operation Handbook

    2-6 2208e and 2204e Controller

    Wire Sizes

    All electrical connections are made to the screw terminals at the rear of the controller. Theyaccept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG), and are protected by a hinged cover toprevent hands or metal making accidental contact with live wires. Rear terminals should betightened to a torque of 0.4Nm (3.5 lb in).Wiring connections

    The wiring connections are shown in figure 2-6. Outputs 1 and 2 are factory fitted moduleswhich can be any one of the types shown in figure 2-8. Check the ordering code on thecontroller side label to determine which have been fitted.

    Model 2204e Connections

    Figure 2-6 Model 2204e Wiring connections

    *The ground connection is not required for safety purposes but must be connected to satisfyEMC requirements.

    *Do not use unused terminals as wire holders.

    Input 1

    Neutral

    *Ground*

    +

    -

    +PV-

    85-264VacHIGH

    CURRENT

    OUTPUT

    Pt100

    Output 1

    Output 2

    4B

    4C

    4D

    5A

    5B

    5D

    6A

    6B

    6C

    6D

    5C

    1B

    2A

    2B

    1A

    3A

    3B

    3C

    N

    LA

    LB

    LC

    L

    AB

    AC

    VI

    V+

    V-

    AA

    HB

    HC

    HD

    HE

    HF

    HA

    Line

    BUSBAR

    Line

    BUSBAR

    Output 4

    Output 3

    Input 2

    Common

    Comms

    Line4A

  • Installation and Operation Handbook Installation

    2208e and 2204e Controller 2-7

    Sensor input connectionsThe connections for the various types of input are as follows:

    Fig 2-7 Sensor input connections

    Sensor inputs should not be paralleled

    OUTPUTS 1 AND 2 CONNECTIONS

    Outputs 1 and 2 can be any one of the types shown in the table below, configured to performany one of the functions shown.

    To check which outputs are installed, and their configuration, refer to the ordering code andthe wiring information on the controller side labels.

    Connections

    Output 1 Output 2 Possible functions

    Module type 1A 1B 2A 2B

    Relay: 2-pin (2A, 264 Vac max.)

    HeatingCoolingAlarms

    Logic: non-isolated* (18Vdc at 24mA)

    + - + -+PDSIO modes 1 or 2 (SSRx

    Load Doctor Functions)HeatingCoolingAlarms

    Triac(1A, 30 to 264Vac) Heating or cooling

    DC control: isolated (18Vdc, 20mA max)

    + - DC not availablein output 2

    PID Heating or cooling

    *Logic output can also be configured as logic input on module 2A.+PDSIO Mode 1 & 2 are only supported in Module 1A.

    Figure 2-8 Outputs 1 and 2 connections

    VI

    V+

    V-

    VI

    V+

    V-

    VI

    V+

    V-

    VI

    V+

    V-

    Thermocouple Resistancethermometer mA inputVolts or mV

    inputs

    +

    -

    PV

    2.49currentsenseresistor

    Line Load Line Load

    NOTE

  • Installation Installation and Operation Handbook

    2-8 2208e and 2204e Controller

    PDSIO modes

    PDSIO is a proprietary technique developed by Eurotherm for bi-directional communicationover a single pair of wires. There are several operating modes. In SSRx Load Doctor a logic output delivers a power demand signal to a TE10 solid state(SSR) relay and the SSR responds with a single load circuit failure message.In SSRx Enhanced Load Doctor a logic output delivers a power demand signal to an SSRand the SSR responds with the ON state rms load current, and two fault messages - SSR failureor heater circuit failure.

    Snubbers

    The controller is supplied with snubbers (15nF +100) which should be wired across therelay or triac outputs when switching inductive loads such as mechanical contactors andsolenoid valves. The snubbers are used to prolong contact life and to suppress interferencewhen switching such loads. Snubbers pass 0.6mA at 110Vac and 1.2mA at 240Vac, whichmay be sufficient to hold in high impedance relay coils. They should not, therefore, be used insuch installations.

    WARNINGWhen a relay contact is used in an alarm circuit ensure that the current passing throughthe snubber when the relay contact is open does not hold in low power electrical loadsand thereby interfere with the failsafe operation of the alarm circuit.

    COMMUNICATION CONNECTIONS

    The communication option can be either of four types shown in the table below

    Connection

    Communications type HB HC HD HE HF

    4-wire EIA-422 serialcommunications*

    A (RX +)

    B (RX -)

    Common A (TX +)

    B (TX -)

    2-wire EIA-485 serialcommunications*

    Not used Not used Common A (TX +) (RX +)

    B (TX -) (RX +)

    EIA-232 serialcommunications

    Not used Not used Common A B

    PDSIO Setpoint input Not used Not used Not used Signal Common

    *The 4-wire EIA-422 communication board can be modified to support 2-wire 485communication. Please consult factory.

    Figure 2-9 Communication connections

  • Installation and Operation Handbook Installation

    2208e and 2204e Controller 2-9

    Wiring of EIA-485 serial communication links

    Local

    LocalEarth

    HF +S eries 2000Controller

    Com

    Note:All termination res istors are 220 ohm 1/4W carbon composition.Local grounds are at equipotential. Where equipotential is not available wire intoseparate zones us ing a galvanic isolator.

    AB

    PC

    Universal Convertor

    RXT XCom

    Com T XRX

    Up to 32controllers orInterface Units maybe included on thenetwork

    232

    Com B A

    Com

    AB

    GalvanicIsolationBarrier

    Com

    AB

    Com

    AB

    Local Earth

    Com

    AB

    Earth

    UniversalConverter

    MMI

    S eries 2000Controller

    S eries 2000Controller

    For safety reasons,do not connect tolocal earth here.

    HD

    HF+

    HE

    HD

    HF+

    HE

    HE

    HD

    Figure 2-10 2-wire EIA-485 wiring

    Standard EIA-485 is a 2-wire connection which allows upto 32 controllers to be multi-dropped from a singlecommunications link over a distance of up to 1.2Km. Toensure reliable operation of the communications link,(without data corruption due to noise or line reflections) theconnections between the controller should be made usinga twisted pair of wires inside a shielded cable with theconnections terminated with resistors in the manner shownin this diagram. This diagram also shows the use of aComms converter to connect the 2-wire EIA-485 link into astandard EIA-232 computer port.

    Common and LocalEarth cannot beconnected together.

  • Installation Installation and Operation Handbook

    2-10 2208e and 2204e Controller

    TYPICAL WIRING DIAGRAM

    Fig 2-11 Typical wiring diagram, Model 2208e Controller

    Neutral

    N

    L

    V+

    VI

    V-

    +

    -

    +

    PV-

    2B

    2A

    3B

    3A

    3C

    1B

    1A

    HF

    HD

    HE

    LC

    LA

    LB

    AC

    AA

    AB

    Cooling PowerFuse 1A(T)

    Heating power fuse(load dependent)

    CoolingSolenoid Valve

    HeaterThermocouple

    -

    ControllerFuse2A(T)

    Solid StateRelay

    such asTE10S+

    -

    Snubber

    Output 1logicheating

    Line

    Output 2Triaccooling

    HC

    HA

    HB

  • Installation and Operation Handbook Access Levels

    2208e and 2204e Controller 3-1

    Chapter 3 ACCESS LEVELS

    PAGE

    The Different Access Levels .......................................................... 3-2

    Selecting an Access Level .......................................................... 3-3

    Edit Level .......................................................... 3-5

  • Access Levels Installation and Operation Handbook

    3-2 2208e and 2204e Controller

    This chapter describes the different levels of access to the operating parameters within the2208e and 2204e controller.

    There are three topics: THE DIFFERENT ACCESS LEVELS SELECTING AN ACCESS LEVEL EDIT LEVEL

    THE DIFFERENT ACCESS LEVELS

    Access level Displayshows

    What you can do PasswordProtection

    Operator

    In this level operators can view and adjust thevalue of parameters defined in Edit level (seebelow).

    No

    Full

    In this level all the parameters relevant to aparticular configuration are visible. Allalterable parameters may be adjusted.

    Yes

    Edit

    In this level you can set which parameters anoperator in Operator level is able to view andadjust. You can hide or reveal complete listsand individual parameters within each list, andyou can make parameters read-only oralterable. You can also promote parametersto the home list. (See Edit level at the end ofthe chapter).

    Yes

    Configuration

    This special level allows access to set up thefundamental characteristics of the controller.

    Yes

    Figure 3-1 Access levels

  • Installation and Operation Handbook Access Levels

    2208e and 2204e Controller 3-3

    SELECTING AN ACCESS LEVEL

    Access to Full, Edit or Configuration levels is protected by a password to preventunauthorised access.If you need to change the password, see Chapter 5, Configuration

    Access list header

    Press until you reach the access list header .

    Press the Scroll button

    Password entry

    The password is entered from the display.Enter the password using the or buttons. Once

    the correct password has been entered, there is a two second delayafter which the lower readout will change to show indicating that access is now unlocked.The pass number is set to 1 when the controller is shipped fromthe factory.

    Note; A special case exists if the password has been set to . Inthis case access will be permanently unlocked and the lowerreadout will always show

    Press the Scroll button to proceed to the display.

    (If an incorrect password has been entered and the controller is stilllocked then pressing Scroll at this point will simply return you tothe list header.)

    Note: From this display, you can access read onlyconfiguration level by pressing and together.

    To escape, press and together.

  • Access Levels Installation and Operation Handbook

    3-4 2208e and 2204e Controller

    .

    .

    Level selection

    The display allows you to select the requiredaccess level.

    Use and to select from the following displaycodes: Operator level: Full level Edit level: Configuration level

    Press the Scroll button

    If you selected either , or level youwill be returned to the list header in the level thatyou chose. If you selected , you will get analternative display showing in the upper readout(see below).

    Configuration password

    When the display appears, you must enter theConfiguration password in order to gain access toConfiguration level. Do this by repeating the passwordentry procedure described in the previous sectionThe configuration password is set to when thecontroller is shipped from the factory. If you need tochange the configuration password, see Chapter 5,Configuration

    Press the Scroll button

    Configuration level

    The first display of configuration is shown. See chapter5, Configuration for details of the configurationparameters.For instructions on leaving configuration level seeChapter 5, Configuration.

  • Installation and Operation Handbook Access Levels

    2208e and 2204e Controller 3-5

    Returning to Operator Level

    To return to operator level from either or level, repeat entry of the passwordand select on the display.In Edit level the controller will automatically return to operator level if no button is pressedfor 45 seconds.

    EDIT LEVEL

    Edit level is used to set which parameters you can see and adjust in Operator level. It alsogives access to the Promote feature which allows you to select and add (Promote) up totwelve parameters into the Home display list, thereby giving simple access to commonly usedparameters.

    Setting operator access to a parameter

    First you must select level, as shown on the previous page.Once in level you select a list or a parameter within a list in the same way as you wouldin Operator or Full level. hat is, you move from list header to list header by pressing thePage button, and from parameter to parameter within each list using the Scroll button.However, in Edit level what is displayed is not the value of a selected parameter but a coderepresenting the parameters availability in Operator level.

    When you have selected the required parameter, use the and buttons to set itsavailability in operator level.There are four codes:

    Makes a parameter alterable in Operator level

    Promotes a parameter into the Home display list

    Makes a parameter or list header read-only (it can be viewed but not altered)

    Hides a parameter or list header.For example:

    The parameter selected is the set point for Alarm2 - Full Scale Low

    It will be alterable in Operator level

  • Access Levels Installation and Operation Handbook

    3-6 2208e and 2204e Controller

    Hiding or revealing a complete list

    To hide a complete list of parameters, all you have to do is hide the list header. If a list headeris selected only two selections are available: and .(It is not possible to hide the list which will always display the code: .)Promoting a parameter

    Scroll through the lists to the required parameter and choose the code. The parameter isthen automatically added (promoted) into the Home display list (the parameter will also beaccessible as normal from the standard lists. a maximum of 16 parameters can be promoted.Promoted parameters are automatically alterable.

  • Installation and Operation Handbook Tuning

    2208e and 2204e Controller 4-1

    Chapter 4 TUNING

    PAGE

    What is Tuning? .................................................................. 4-2

    Automatic Tuning .................................................................. 4-3

    Manual Tuning .................................................................. 4-6

  • Tuning Installation and Operation Handbook

    4-2 2208e and 2204e Controller

    Before tuning please read Chapter 1, Operation, to learn how to select and change aparameter.This chapter has three main topics: WHAT IS TUNING? AUTOMATIC TUNING MANUAL TUNING

    WHAT IS TUNING?

    In tuning you match the characteristics of the controller to that of the process being controlledin order to obtain good control. Good control means:Stable straight-line control of the temperature at setpoint without fluctuationAcceptable overshoot or undershoot of the temperature setpointQuick response to deviations from the setpoint caused by external disturbances, therebyrestoring the temperature rapidly to the setpoint value.Tuning involves calculating and setting the value of the parameters listed in Table 4-1. Theseparameters appear in the list.

    Parameter Code Meaning or Function

    Proportionalband

    The bandwidth in display units over which the output power isproportioned between minimum and maximum.

    Integral time

    Determines the time taken by the controller to remove steady-state error signals.

    Derivativetime

    Determines how strongly the controller will react to the rate-of-change of the measured value.

    Low cutback

    The number of display units below setpoint at which thecontroller will cutback the output power in order to preventovershoot on heat up.

    High Cutback

    The number of display units above setpoint at which thecontroller will increase the output power in order to preventundershoot on cool down.

    Relative coolgain

    Only present if cooling has been configured. Sets the coolingproportional band by dividing the Pb value by the rEL.C value.

    Table 4-1 Tuning parameters

  • Installation and Operation Handbook Tuning

    2208e and 2204e Controller 4-3

    AUTOMATIC TUNING

    This method automatically determines the value of the parameters listed in table 4-1 on theprevious page.The 2208e and 2204e use a one-shot tuner which works by switching the output on and offto induce an oscillation in the measured value. From the amplitude and period of theoscillation, it calculates the tuning parameter values.If the process cannot tolerate full heating or cooling being applied during tuning, then thelevel of heating or cooling can be restricted by setting the heating and cooling power limits inthe Output list. However, the measured value must oscillate to some degree for the tuner to beable to calculate valuesA One-shot Tune can be performed at any time but normally it is performed only once duringthe initial commissioning of the process. However, if the process under control subsequentlybecomes unstable (because its characteristics have changed), you can re-tune again for the newconditions.It is best to start tuning with the process at ambient temperature. This allows the tuner tocalculate more accurately the low cutback and high cutback values that restrict the amount ofovershoot or undershoot.

    Heating and Cooling Output Cycle Times

    Before commencing a tuning cycle, set the values of (heat cycle time) and (coolcycle time) in the op (output list). These values apply if you are using a logic, relay or triacoutput. They have no effect on a DC output.A logic output switching a solid state relay can be set to values such as 1 sec.A relay or triac output should be set to 20 sec.

  • Tuning Installation and Operation Handbook

    4-4 2208e and 2204e Controller

    How to tune

    1. Set the setpoint to the value at which you will normally operate the process.2. In the list, select and set it to 3. Press the Page and Scroll buttons together to return to the Home display. The display

    will flash to indicate that tuning is in progress.4. The controller will induce an oscillation in the temperature by turning the heating on and

    then off. The first cycle will not complete until the measured value has reached therequired setpoint.

    5. After two cycles of oscillation the tuning will be completed and the tuner will switchitself off.

    6. The controller will then calculate the tuning parameters listed in Table 4-1 and willresume normal control action.

    If you want Proportional only or PD or PI control, you should set the or parameters to before commencing the tuning cycle. The tuner will leave them off andwill not calculate a value for them.

    For valve position tuning and set-up, please refer to Appendix D.

  • Installation and Operation Handbook Tuning

    2208e and 2204e Controller 4-5

    Typical automatic tuning cycle

    Calculation of the cutback values

    Low cutback and High cutback are values that restrict the amount of overshoot or undershootthat occur during large step changes in temperature (for example, under startup conditions).If either low cutback or high cutback is set to the values will be fixed at three timesthe proportional band, and will not be changed during automatic tuning.

    Time

    SetpointTemperature

  • Tuning Installation and Operation Handbook

    4-6 2208e and 2204e Controller

    MANUAL TUNING

    If for any reason automatic tuning gives unsatisfactory results, you can tune the controllermanually. There are a number of standard methods for manual tuning. The one describedhere is the Ziegler-Nichols method.With the process at its normal running temperature:1. Set the Integral Time and the Derivative Time to .2. Set High Cutback and Low Cutback, and , to 3. Ignore the fact that the temperature may not settle precisely at the setpoint4. If the temperature is stable, reduce the proportional band so that the temperature just

    starts to oscillate. If the temperature is already oscillating, increase the proportional banduntil it just stops oscillating. Allow enough time between each adjustment for the loop tostabilise. Make a note of the proportional band value B and the period of oscillation T.

    5. Set the Pb, ti, td parameter values according to the calculations given in Table 4-2.

    Type of control Proportionalband Pb

    Integral time ti Derivative timetd

    Proportional only 2xB OFF OFF

    P + I control 2.2xB 0.8xT OFF

    P + I + D control 1.7xB 0.5xT 0.12xT

    Table 4-2 Tuning values

  • Installation and Operation Handbook Tuning

    2208e and 2204e Controller 4-7

    Setting the cutback values

    The above procedure sets up the parameters for optimum steady state control. If unacceptablelevels of overshoot or undershoot occur during start-up or for large step changes intemperature, then manually set the cutback parameters and .Proceed as follows:1. Set the low and high cutback values to three proportional bandwidths (that is to say, Lcb

    = Hcb = 3 x Pb).2. Note the level of overshoot or undershoot that occurs for large temperature changes (see

    the diagrams below).In example (a) increase by the overshoot value. In example (b) reduce by theundershoot value.Example (a)

    Temperature

    Example (b)

    Temperature

    Where the temperature approaches setpoint from above, you can set ina similar manner.

    Time

    Undershoot

    SetpointOvershoot

  • Tuning Installation and Operation Handbook

    4-8 2208e and 2204e Controller

    Integrating action and manual resetIn a full three-term controller (that is, a PID controller), the integral term ti automaticallyremoves steady state errors from the setpoint. If the controller is set up to work in two-termmode (that is, PD mode), the integral term will be set to . Under these conditions themeasured value may not settle precisely at setpoint. When the integral term is set to OFF theparameter manual reset (code ) appears in the in Access level.This parameter represents the value of the power output that will be delivered when the erroris zero. You may set this value manually in order to remove the steady state error.

    Automatic droop compensation (Adc)

    The steady state error from the setpoint, which occurs when the integral term is set to OFF, issometimes referred to as droop. automatically calculates the manual reset value inorder to remove this droop. To use this facility, you must first allow the temperature tostabilise. Then, in the autotune parameter list, you must set to . The controllerwill then calculate a new value for manual reset, and switch to . can be repeated as often as you require but between each adjustment you must allow timefor the temperature to stabilise.

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-1

    Chapter 5 CONFIGURATIONPAGE

    Selecting Configuration Level ...................................................... 5-2

    Leaving Configuration .................................................................. 5-3

    Steps Involved in Configuring a Controller ................................... 5-3

    Navigation Diagram ...................................................................... 5-4

    Configuration Parameter Tables .................................................. 5-6

    WARNINGConfiguration is protected and should only be carried out by an authorised person.Incorrect configuration could result in damage to the process being controlled and/orpersonal injury. It is the responsibility of the person commissioning the instrument toensure that the configuration is correct.

  • 5-2 2208e and 2204e Controller

    Configuration Installation and Operation Handbook

    SELECTING CONFIGURATION LEVEL

    Figure 5.1

    At this point thecontroller is inconfiguration level

    HOMEdisplay

    Press Pagebuttonrepeatedlyuntil AccessList appears

    or to enter password (factory default = 1)

    If incorrectpasswordentered

    or to enterpassword (factory default = 2)

    Note: Selectingor will allow direct entry tothese levels at this point

    1st press

    2nd press

    3rd press

    If the password hasbeen set to - accessis permanentlyunlocked & the lowerreadout always shows

    Repeated pressing of Page buttonselects configuration list headings in a

    continuous loop

    2 secs

    or to select

    4th press

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-3

    LEAVING CONFIGURATION LEVEL

    STEPS INVOLVED IN CONFIGURING A CONTROLLER

    The navigation diagram which follows shows the general location of parameters which definethe way in which the controller works. They are grouped under headings. The actual parametersshown in your controller may differ slightly since some appear only as a result of selectingothers. A full list of possibilities is included in the PARAMETER TABLES which follow thenavigation diagram.

    or to select

    Keep pressing untilExit display appears

    After a 2 second delay the screenwill blank, the instrument will reset,and revert to the Home display

    Figure 5.2

  • 5-4 2208e and 2204e Controller

    Configuration Installation and Operation Handbook

    NAVIGATION DIAGRAM (PART A)Instrument Input User cal. Alarms Logic input 1 Logic input 2 Output AA

    Config Config Config Config Config Config Config

    Seeparametertables

    !

    "

    #$

    %

    &

    !

    '

    '

    (

    !

    (

    )

    (

    &

    (

    The Principle of Operation is thesame as that already described inCh1.That is:

    Step through List Headers using the Page button

    Choose a parameter from a list using the Scroll button

    Change value using the Raise/Lower buttons

    The first 4 headings set up thecontroller functions, as follows:Instrument Config. - Groups thoseparameters associated with thedisplay and control action.Input Config. - selects the inputsensor typeUser cal. Config. - to calibrate toexternal reference sourcesAlarms Config. - sets up the alarmtypes

    *

    +

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-5

    NAVIGATION DIAGRAM (PART B)Comms Output 1 Output 2 Output 3 10A output PasswordConfig Config Config Config Config Config

    See Table Bparameter table,page 5-13

    See Table Bparameter table,page 5-14

    !

    )

    ,

    &

    "

    "

    "

    $

    -

    (+

    ./

    !

    0

    1

    2

    '+

    '+

  • Configuration Installation and Operation Handbook

    5-6 2208e and 2204e Controller

    Heading Input/Output Functions Wiring TerminalsThe first four headings set up the controller functions as follows:

    Sets up display and control parameters Not applicable

    Selects the input sensor type Not applicable

    To calibrate to external reference sources Not applicable

    Sets up the alarm types Not applicableThe remaining headings configure the controller input/output functions.The upper readout corresponds to rear terminal numbers associated with a particular i/o.

    Sets up the action of the two digital inputs LA & LB

    Sets up the action of the fixed relay on output AA AA to AC

    Sets up digital comms type HB to HF

    Sets up the output modules 1A and 2A 1A & 1B / 2A & 2B

    Sets up the action of the fixed relay on output 3A 3A to 3C

    Sets the action of the 10A output relay in 2204 4A to 6D

    To choose new passwords / To leave configuration level and return to operator level

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-7

    NOTE

    CONFIGURATION PARAMETER TABLES

    Name Parameter description Values Meaning

    Instrument configuration

    Instrument

    Centigrade (default UK)units

    Fahrenheit (default USA)

    Kelvin

    Units are not displayed

    Decimal places in the

    Nonedisplayed value

    One

    Two

    Control type

    On/off control

    PID controlVP Control

    Control action

    Reverse acting (required fortemperature control) - outputdecreases on approach tosetpoint.

    Direct acting

    Type of cooling

    Linear

    Oil (50mS min on time)

    Water(non-linear)

    Fan (0.5S min on time)

    Power feedback

    Power feedback is on(compensates for changes insupply voltage)

    Power feedback is off

    Bumpless manual/auto

    Non-bumpless transfertransfer when using PD control

    Bumpless transfer (auto to manualand manual to auto)

    Forced manual output

    Bumpless manual/auto transfer

    Returns to the manual value thatwas set when last in manualmode.

    Sensor break output

    Go to pre-set value (maintainsoutput at a known, safe level)

    Freeze output (maintains output atvalue immediately before break)

    Load Current Scaling Factor

    See Appendix E-10

    Factory default parameter values and states are included where applicable and areindicated by the shaded areas in the following tables.

  • Configuration Installation and Operation Handbook

    5-8 2208e and 2204e Controller

    Name Parameter description Value Meaning

    Input configuration

    Input type

    J thermocouple (default USA)

    K thermocouple (default UK)

    L thermocouple

    R thermocouple (Pt/Pt13%Rh)

    B thermocouple (Pt30%Rh/Pt6%Rh)

    N thermocouple

    T thermocouple

    S thermocouple (Pt/Pt10%Rh)

    PL 2 thermocoupleNOTE: 100 platinum resistance thermometer.

    After selecting an inputtype, do not forget toadjust the setpoint limitsin Full Access level

    Custom downloaded input type. Thedefault is C thermocouple, or the name ofthe downloaded custom input will bedisplayed.!"

    Linear millivolt (Also mA input via anexternal 2.49 current sense resistor)

    Linear voltage#

    Input range low Display low range for input#

    Input range high Display high range for input

    CJC ref. temperature

    Automatic cold junction compensation(CJC does not appear for 0C external reference

    linear inputs)$% 45C external reference% 50C external reference

    Linear Input Scaling - The next 4 parameters only appear if a linear input is chosen

    Input value low

    Input value high

    "

    Displayed reading low

    "

    Displayed reading high

    &!

    Sensor break inputimpedance trip level

    Sensor break detection is disabledAppears for mV or V inputs only

    Trip level set by the sensor input table Trip level set at 7.5K

    Trip level set at 15K (must be selectedwhen input is enabled)

    Displayed

    Value

    ElectricalInput

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-9

    Name Parameter description Value Meaning

    User calibration config. See Chapter 6 - User calibration

    User cal enable

    User calibration is disabled

    User calibration is enabled

    User calibrationpoint low

    This is the value (in display units) at which a Userlast performed a low point calibration

    User calibrationpoint high

    This is the value (in display units) at which a Userlast performed a high point calibration

    Low pointcalibration offset

    Offset, in display units, at the user low calibrationpoint Pnt.L. This value is automatically calculatedwhen performing low point calibration.

    High pointcalibration offset

    Offset, in display units, at the user high calibrationpoint Pnt.H. This value is automatically calculatedwhen performing a high point calibration.

    * If User calibration is enabled, then the User calibration parameters will appear in the Input list ofOperator Full access level. See Chapter 6, User calibration.

  • Configuration Installation and Operation Handbook

    5-10 2208e and 2204e Controller

    NOTE

    Name Parameter description Values

    Alarm configuration Values Defaults if not specified

    Alarm 1 Type As table A

    Alarm 1 Blocking(1)/

    '

    Alarm 1 Latching//!(

    Alarm 2 Type As table A

    Alarm 2 Blocking(1)/

    '

    Alarm 2 Latching//!(

    )

    Alarm 3 Type As table A

    Alarm 3 Blocking(1)/

    '

    Alarm 3 Latching/(/!(

    $

    Alarm 4 Type As table A

    Alarm 4 Blocking(1)/

    '

    Alarm 4 Latching/(/!(

    Table A: Alarm types

    No alarm

    Full scale low

    Full scale high

    Deviation band

    Deviation high

    Deviation low

    Low current

    High current

    (1) Blocking allows the alarm to become active only after it has first entered a safe state.

    These are soft alarms, i.e. Indication only. They would normally be attached to anoutput. See Chapter 7 for a step by step guide.

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-11

    Name Parameter description Values

    Logic input 1 configuration Functions Action on contact closure

    Identity of input+

    Logic input

    Function

    None!

    Manual mode select!

    Remote setpoint select

    Setpoint 2 select

    Integral hold

    Acknowledge alarms

    Lock Key pad

    Reset

    Standby - ALL outputs = OFF!

    PDSIO load current input

    Logic input 2 configuration Functions Action on contact closureAs per Logic input 1 except ! not available

  • Configuration Installation and Operation Handbook

    5-12 2208e and 2204e Controller

    Name Parameter description Functions Meaning

    Alarm relay configuration Functions Meaning

    Identity of output,

    Relay

    Function

    None+ Function set by + (as in

    Table B)

    Heating

    CoolingFor -tion = + go to table B on the next page

    Sense of output (alwaysappears)

    Normal (heat & cool outputs)Inverted (alarms de-energisedin the alarm state)

    Comms module config Functions Meaning

    Identity of the option installed.

    PDSIO setpoint input

    !

    2- or 4-wire EIA-485 (422) orEIA-232 comms module

    FunctionSome of the following parameters may appear if one of the comms options is installed

    !

    DIGITAL Communicationprotocol ordered

    NoneThe following parameters will appear if the PDSIO setpoint input option is installed.

    No PDSIO function

    PDSIO setpoint input"

    PDSIO low input value Range = -999 to 9999"

    PDSIO high input value Range = -999 to 9999The following parameters will appear if the function chosen is Mod protocol./

    Baud Rate 1200, 2400, 4800, 9600, 19.20, 1920 (19200)*, Comms Parity No parity

    Even parity

    Odd parity* Comms Resolution Full resolution&

    Integer resolution

    *Not used with some communication protocols. Please consult factory.

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-13

    Name Parameter description Function Meaning

    Output 1 configuration Function Meaning

    Identity of module installed

    No module fitted0,

    Relay output

    DC output (isolated)+

    Logic or PDSIO output

    Triac output

    Function1

    Module does not operate.&+ Function set by +

    Heating output

    Cooling outputOnly appear for id = dC.OP

    Retransmission of outputdemand

    Only appear for id = dC.OP"

    Retransmission of ProcessValue

    Only appear for id = dC.OP

    Retransmission of errorOnly appear for id = dC.OP

    Retransmission of setpointOnly appear for id = LoG

    PDSIO mode heatingOnly appear for id = LoG

    PDSIO mode 2 heatingFor -tion = + go to table B below

    Sense of output

    Normal (e.g.heating and cooling)Inverted (alarms - de-energise inalarm)

    DC output scaling For id = dC.OP the following parameters appear

    DC output minimum 0mA to 20mA

    DC output maximum 0mA to 20mA

  • Configuration Installation and Operation Handbook

    5-14 2208e and 2204e Controller

    Table B The following parameters appear if + is chosen as the function.+

    Digital output functions

    '

    No changeAny number of the functionslisted can be combined on tothe output. Use the

    and

    buttons to selecta desired digital function.After two seconds thedisplay will blink and returnto the

    ' display. Usethe arrows again to scrollthrough the function list.The previously selectedfunction display will showtwo decimal points indicatingthat it has been added to theoutput.

    2 2 2

    *

    2 2 2 *

    ) 2 2 2 *

    $ 2 2 2 *

    3

    -

    1

    1(

    0!

    '

    Clear all existing functionsAlarm 1 *Alarm 2 *Alarm 3 *Alarm 4 *Manual/AutoSensor BreakLoop BreakHeater FailLoad FailEND ProgramPV Out of RangePDSIO SSR FailureNew AlarmRemote Sp FailCTx open circuitCtx short circuit

    * From previous page. In place of the dashes, the last three characters indicate the alarm type as per tableA in the AL list: eg = Full Scale Low If an alarm is not configured the displayed name will differ:e.g. will be shown, for the first alarm.

    Name Parameter description Function Meaning

    Output 2 configuration Function Meaning

    Identity of module installed

    No module fitted,

    Relay output+

    Logic

    Triac output

    Function

    none

    Outputs+ Function set by +

    Heating output

    Cooling outputLogic Inputs!

    Manual mode select!

    Remote setpoint select

    Setpoint 2 select

    Integral hold

    Acknowledge alarms

    Standby - ALL outputs = OFFFor = + (Refer to table B on page 5-13).

    Sense of output

    Normal (heat and cool outputs)Inverted (alarms - de-energise in alarm)

  • Installation and Operation Handbook Configuration

    2208e and 2204e Controller 5-15

    )

    )

    Output 3 configuration As per output AA configuration

    $

    $

    10Amp heating output Available on 2204e only.As per Output 3A configuration

    Password list

    FuLL or Edit level password

    Configuration level Password

    4

    4

    Exit Configuration

    /

  • Installation and Operation Handbook User Calibration

    2208e and 2204e Controller 6-1

    Chapter 6 USER CALIBRATION

    PAGE

    What is the Purpose of User Calibration? ................................... 6-2

    User Calibration Enable ............................................................... 6-3

    Single Point Calibration ............................................................... 6-4

    Two Point Calibration .................................................................. 6-5

    Calibration Points and Calibration Offsets .................................. 6-6

  • User Calibration Installation and Operation Handbook

    6-2 2208e and 2204e Controller

    This chapter has five topics: WHAT IS THE PURPOSE OF USER CALIBRATION? USER CALIBRATION ENABLE SINGLE POINT CALIBRATION TWO POINT CALIBRATION CALIBRATION POINTS AND CALIBRATION OFFSETS

    To understand how to select and change parameters in this chapter you will need to have readChapter 2 - Operation, Chapter 3- Access Levels and Chapter 5 - Configuration.

    WHAT IS THE PURPOSE OF USER CALIBRATION?

    The basic calibration of the controller is highly stable and set for life. User calibration allowsyou to offset the permanent factory calibration to either:

    1. Calibrate the controller to your reference standards2. Match the calibration of the controller to that of a particular transducer or sensor input3. Calibrate the controller to suit the characteristics of a particular installation.

    User calibration works by introducing zero and span offsets onto the factory set calibration.The factory set calibration can always be retrieved.

  • Installation and Operation Handbook User Calibration

    2208e and 2204e Controller 6-3

    USER CALIBRATION ENABLEThe User calibration facility must first be enabled in configuration level by setting theparameter ' in the list to '' This will make the User calibrationparameters appear in Operator level.Select configuration level as shown in Chapter 5, Configuration

    The User calibration configuration List

    Press until you reach the list

    ress the Scroll button until you reach

    User calibration enable

    Use or to select:

    : Calibration enable: Calibration disabled

    Press and together to go to the Exit display

    Exit configuration

    Use or to select and return to Operator level.

  • User Calibration Installation and Operation Handbook

    6-4 2208e and 2204e Controller

    SINGLE POINT CALIBRATION

    Your controller is calibrated for life against known reference sources during manufacture. Acalibration offset is often used to allow the controller to compensate for sensor and othersystem errors. The normal procedure is to set up the system under test against a knownindependent reference, as follows:Set up the process to be calibrated such that the known reference displays the required value(temperature).Observe the reading on the controller. If it is different, proceed as follows:Select Access level as described in Chapter 3

    Input list header

    Press until you reach the input list header.

    Press Scroll until you reach the display

    Calibration type

    Use or to select either or .Selecting will reinstate the factory calibration andhide the following User calibration parameters.Selecting will reinstate any previously set Usercalibration and make available the User parameters, asfollows:

    Press the Scroll button

    Calibrate low point?

    Use or to select Selecting no will hide the next parameter

    Press the Scroll buttoncontinued on the next page

  • Installation and Operation Handbook User Calibration

    2208e and 2204e Controller 6-5

    To protect the calibration against unauthorised adjustment return to Operator level and makesure that the calibration parameters are hidden. Parameters are hidden using the facility describe in Chapter 3.

    TWO POINT CALIBRATION

    The previous section described how to perform a single point calibration which applies a fixedoffset over the full display range of the controller. A two-point calibration is used to calibratethe controller at two points and apply a straight line between them. Any readings above orbelow the two calibration points will be an extension of this straight line. For this reason it isbest to calibrate with the two points as far apart as possible.Proceed as follows:1. Decide upon the low and high points at which you wish to calibrate.2. Perform a single point calibration at the low calibration point in the manner

    described above3. Set the process under calibration such that the known reference exhibits the required

    higher Process Value (temperature) and allow to stabilize.4. Press the Scroll button to obtain the high calibration point as shown in the

    following diagrams.

    Adjust the low point calibration

    The controller will display the current measured input value in thelower readout.

    Use or to adjust the reading to the reference sourcevalue, if different.After a two second delay the display will blink and the reading willchange to the new, calibrated value. You can calibrate at any pointover the entire display rangeThis is a single point calibration which applies a fixed offset over thefull display range of the controller.The calibration is now complete. You can return to the factorycalibration at any time by select in the CAL display shownearlier.

    Press

    and

    together to return to theHome display

  • User Calibration Installation and Operation Handbook

    6-6 2208e and 2204e Controller

    To protect the calibration against unauthorised adjustment return to Operator level and makesure that the calibration parameters are hidden. Parameters are hidden using the facility described in Chapter 3.

    CALIBRATION POINTS AND CALIBRATION OFFSETS

    If you wish to see the points at which the User calibration was performed and the value of theoffsets introduced these are shown in Configuration, under . The parameters are:

    Name Parameter description Meaning

    User low calibration point This is the value (in display units) at which a Userlast performed an (adjust low calibration).

    User high calibration point This is the value (in display units) at which a Userlast performed an (adjust high calibration).

    Low point calibration offset Offset, in display units, at the user low calibrationpoint

    High point calibration offset Offset, in display units, at the user high calibrationpoint .

    Calibrate high point?

    Use or to select

    Press the Scroll button

    Adjust the high point calibration

    The controller will display the current measured input value in thelower readout.

    Use or to adjust the reading to the reference sourcevalue, if different.After a two second delay the display will blink and the reading willchange to the new, calibrated value.

    The calibration is now complete. You can return to the factorycalibration at any time by select in the display shownearlier.

  • Installation and Operation Handbook Alarm Operation

    2208e and 2204e Controller 7-1

    Chapter 7 ALARM CONFIGURATIONPAGE

    Definition of Alarms and Events ...................................................... 7-2

    Types of Alarms ................................................................................ 7-2

    Step 1 - Configuring the Four Soft Alarms .................................... 7-5

    Step 2 - Attaching an Alarm to a Physical Output .......................... 7-6

    Step 3 - Grouping Alarms on a Single Output ................................. 7-7

    Step 4 - Removing Alarms from an Output ...................................... 7-7

    The 2200e series controllers are capable of very sophisticated alarm strategies and, althoughsetting up of alarms has already been covered in previous chapters, this section has beenincluded to enable operators and commissioning engineers to design their own strategies foroptimum plant operation.

  • Alarm Operation Installation and Operation Handbook

    7-2 2208e and 2204e Controller

    DEFINITION OF ALARMS AND EVENTS

    Alarms are used to alert an operator when a pre-set level or condition has been exceeded.They are normally used to switch an output - usually a relay - to provide interlocking of themachine or plant or external audio or visual indication of the condition.

    Soft Alarms are indication only within the controller and are not attached to an output (relay).Events - can also be alarms - but are generally defined as conditions which occur as part of thenormal operation of the process. They do not generally require operator intervention.

    Events are referred to as Digital Output Functions in the manual (see Table B, page 5-13).For the purposes of the operation of this instrument alarms and events can be consideredthe same.

    TYPES OF ALARMS

    The use of alarms in the 2208e and 2204e controllers is extremely versatile.Up to 4 alarms can be configured. Any combination of these 4 alarms can be attached to anyone or more outputs, or any number of the available soft alarms can be combined to operatea single output.

    Note: In a three term controller at least one of these outputs is used to maintainthe required temperature of the process.

    Outputs 1A and 2A Are plug in modules.Normally used for control outputs, eg. Heat and Cool, but canbe used for alarm outputs.

    Outputs AA and 3A Are fixed relays.Normally used for alarms or events, but can be used as controloutputs.

    10A Output 4A (2204e 0nly) Is a plug in 10 Amp relay output.Normally used to switch heaters directly in control mode, butcan be used as an alarm output.

    NOTE

  • Installation and Operation Handbook Alarm Operation

    2208e and 2204e Controller 7-3

    There are seven process alarm types listed below. Alarm Types are found in configurationmode under the Alarm Config. List.

    ALARMS

    Full Scale High The PV exceeds a set high level

    Full Scale Low The PV exceeds a set low level

    Deviation Band The difference between PV & SP is outside a set band

    Deviation High The difference between PV & SP is higher than a set level

    Deviation Low The difference between PV & SP is lower than a set level

    High Current The measured current returned from a PDSIO slave is higher than aset level

    Low Current The measured current returned from a PDSIO slave is lower than aset level

    Each alarm can be set to:

    Latching Alarm is indicated until acknowledged(Off, Auto, MAN)

    Auto Acknowledge: ( )If the alarm is acknowledged while the alarm condition is stillpresent, it will cause the alarm to reset as soon as the alarmcondition is removed.

    Manual Acknowledge: ( )If the alarm is acknowledged while the alarm condition isstill present, it will be ignored. A further acknowledgementis required when the alarm condition has been removed tocause the alarm to reset.

    Blocking Alarm occurs after it has been through a start up phase not in alarmcondition.

    Sense Of Output Relay energised or de-energised in alarm condition.

  • Alarm Operation Installation and Operation Handbook

    7-4 2208e and 2204e Controller

    In addition there are nine digital output functions used as events or alarms depending uponthe requirements of the process under control:

    DIGITAL OUTPUT FUNCTIONS

    Sensor Break` The input is open circuit

    Loop Break The controller does not measure a response to anoutput change

    Load Failure Used with PDSIO Mode 1 load failure

    Manual Controller in manual mode

    PV Out Of Range Process Variable too high or too low

    Remote SP Fail No signal measured at the remote set point input terminals

    Heater Fail Used with PDSIO Mode 2 heater open circuit

    SSR Fail Used with PDSIO Mode 2 solid state relay open or shortcircuit

    Program END Signals the end of a program

    New Alarm Signals a new alarm

    The Sense of the Output can be set to relay energised or de-energised in the alarm conditionfor any of the above functions.

  • Installation and Operation Handbook Alarm Operation

    2208e and 2204e Controller 7-5

    STEP1 - CONFIGURING THE FOUR SOFT ALARMS

    Go To Configuration LevelRefer to Chapter 5

    Press PAGE keyas many times as necessaryto find Alarm Configuration

    Press SCROLL keyto the alarm which needs tobe configured

    Alarm Type choicesare

    OFF Full Scale Low Full Scale High deviation Band deviation High deviation low

    Low current High current

    Press SCROLL keyto choose alarm 1 latchingor non-latching

    Choices No/Auto/Man Press

    Press SCROLL keyto choose alarm 1 blocking

    Choices Yes/No press

    Press SCROLL keyto repeat for alarms 2 - 4to return to list header

    Figure 7.1

  • Alarm Operation Installation and Operation Handbook

    7-6 2208e and 2204e Controller

    STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUTThis may be necessary if:1. The instrument has been supplied un-configured or it is required to re-configure2. Alarm relays are added

    Press PAGE keyas many times as necessaryto find AA Configuration

    Press SCROLL keyto identification of outputtype (this is read only)

    Press SCROLL keyto output Function

    Use or to select Other choices are:1. 2. 3.

    Use or buttons toselect a desired digital function,e.g., . Other choices areshown in the table on the nextpage. After two seconds, thedisplay will blink and return tothe (no change) display.Use the arrows again to scrollthrough the function list. Thepreviously selected function willshow 2 decimal pointsindicating that it has beenadded to the output, i.e., .

    Use orto select:1. inverted (relay de-energised

    in alarm)2. direct (relay energised in

    alarm)

    Press SCROLL keyto digital output function

    Keep pressing SCROLLbutton to return to list header

    Figure 7.2

  • Installation and Operation Handbook Alarm Operation

    2208e and 2204e Controller 7-7

    STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT

    In the previous example one alarm condition is allocated to one output relay.

    The 2208e and 2204e controllers allow alarms and events to be grouped on to a single output.These events are shown in the table below.

    No change

    Clear all existingfunctionsAlarm 1*Alarm 2*Alarm 3*Alarm 4*

    * See Table B page 5-13

    Figure 7.3

    STEP 4 - REMOVING ALARMS FROM AN OUTPUT

    Figure 7.4

    !

    !

    Press until you reach the1stsoft alarm you wish to attach toan output, e.g., . The displayreturns to no change after 2 sec.accepting the condition.

    Press until you reach the2nd soft alarm you wish to attach tothe output, e.g., !. The displayreturns to no change after 2 sec.accepting the condition.

    Repeat for all alarms to beattached to the chosen output

    Press once to show clearAfter 2 sec. the lower readoutreverts to no change clearing allevents from the chosen output.

    Each time you scroll through thetable of alarms, note that 2decimal points appear confirmingacceptance that the particularalarm has been attached to theoutput, i.e., , !, etc.

  • Installation and Operation Handbook Understanding the Ordering Code

    2208e and 2204e Controller A-1

    Appendix AUNDERSTANDING THE ORDERING CODEThe 2208e and 2204e controllers have a modular hardware construction with the option offour outputs and one communications port. Two logic inputs are provided as standard. Inaddition the Model 2204e has an optional plug-in 10A heating output.

    The ordering code is in two parts: the hardware code followed by the software code. Thehardware code specifies the hardware build of the controller, and the software code thesoftware configuration. The software code is optional.

    UK Default USA DefaultType KT/C 0 to 1000C Type JT/C 32 to 2192F

    Hardware code Software code

    Model Output 1 Comms DisplayNumber Language units

    Supply Output 2 ManualVoltage Sensor

    Output 3 input

    Rangemin

    RangeMax Options

    Function

    Figure A.1

  • Understanding the Ordering Code Installation and Operation Handbook

    A-2 2208e and 2204e Controller

    Hardware code

    Modelnumber

    Function Supplyvoltage

    Output1

    Output2

    OutputAA

    Output3

    10Aoutput

    Comms Manual DefaultSettings

    2208e2204e CC VH LH RC FL FH XX 2YM ENG

    AO-AmericanEO-European

    Supply voltageVH 85-264Vac

    Output 1XX NoneRelay: 2-pinR1 UnconfiguredRU VP raise O/PRH PID heatingFH High alarm 1FL Low alarm 1DB Deviation band 1DL Low dev. alarm 1DH High dev alarm 1Logic: non-isolatedL1 UnconfiguredLH PID heatingM1 PDSIO mode 1(1)M2 PDSIO mode 2(1)TriacT1 UnconfiguredTH PID heatingTU VP raise O/PDC control -isolatedD3 UnconfiguredH6 0-20mA PIO heatingH7 4-20mA PID heatingC6 0-20mA PID coolingC7 4-20mA PID cooling

    Output 2XX NoneRelay: 2-pinR1 UnconfiguredRW

    VP lower O/P

    RC PID coolingFH High alarm 2FL Low alarm 2DB Deviation band 2DL Low dev. alarm 2DH High dev alarm 2Logic: non-isolatedL1 UnconfiguredLC PID coolingTriacT1 UnconfiguredTC PID coolingTW VP lower O/P

    Output 3(3)XX NoneRF UnconfiguredRH PID heatingFH High alarm 4FL Low alarm 4DB Deviation band 4DL Low dev. alarm 4DH High dev alarm 4LF PDSIO load failHF PDSIO heater failSF PDSIO SSR failRC PID cooling

    FunctionCC ControllerVC Valve

    PositionerNF On/Off

    Comms2XX None2-wire EIA-4852YM Modbus2YE EI Bisynch4-wire EIA-4222FM Modbus2FE EI BisynchEIA-2322AM Modbus2AE EI BisynchPDSIO input2M4 Fitted unconfig.2RS Setpoint input2NS Nonstandard

    Output AA(3)XX NoneRF UnconfiguredRH PID heatingFH High alarm 3FL Low alarm 3DB Deviation band 3DL Low dev. alarm 3DH High dev alarm 3LF PDSIO load failHF PDSIO heater failSF PDSIO SSR failRC PID cooling

    10A outputXX NoneR5 fitted unconfiig.RH PID heating

    ManualXXX No manualENG EnglishFRA FrenchGER GermanITA Italian

  • Installation and Operation Handbook Understanding the Ordering Code

    2208e and 2204e Controller A-3

    Software code

    Sensor input Range min Range max Units Logic input1

    Logic input2

    Options

    K 0(note 2)

    1000(note 2)

    C XX XX CF

    Sensor input Range Min Range MinStandard sensors Min C max Min F maxJ J thermocouple -210 1200 -340 2192K K thermocouple -200 1372 -325 2500T T thermocouple -200 400 -325 750L L thermocouple -200 900 -325 1650N N thermocouple -200 1300 -325 2370

    R R thermocouple -50 1768 -58 3200S S thermocouple -50 1768 -58 3200B B thermocouple 0 1820 32 3310P Platinel II thermple 0 1369 32 2496C *C thermocouple

    W5%Re/W26%Re(Hoskins)

    0 2319 32 4200

    Z RTD/PT100 -200 850 -325 1562Custom sensors (*replaces C thermocouple)D W3%Re/W25%Re 0 2399 32 4350E E thermocouple -200 1000 -325 18301 Ni/Ni18%Mo 0 1399 32 25502 Pt20%Rh/Pt40%Rh 0 1870 32 33983 W/W26%Re

    (Englehard) 0 2000 32 3632

    4 W/W26%Re(Hoskins)

    0 2010 32 3650

    5 W5%Re/W26%Re(Englehard)

    10 2300 50 4172

    6 W5%Re/W26%Re(Bucose)

    0 2000 32 3632

    7 Pt10%Rh/Pt40%Rh -200 1800 392 3272Linear inputs Min MaxF -100 to +100mV -999 9999Y 0 to 20mA -999 9999A 4 to 20ma -999 9999W 0 to 5Vdc -999 9999G 1 to 5Vdc -999 9999V 0 to 10Vdc -999 9999

    OptionsAdd as many options asrequiredControl optionsDP Direct acting PIDHeating optionPD Power feedback

    disabledCooling optionsXX Linear coolingCF Fan coolingCW Water coolingCL Oil cooling

    Logic inputs 1 & 2XX DisabledAM Manual mode selectSR Remote setpoint selectS2 Second setpointEH Integral holdAC Alarm acknowledgeSB Standby mode

    UnitsC CentigradeF FahrenheitK KelvinX Blank

  • Understanding the Ordering Code Installation and Operation Handbook

    A-4 2208e and 2204e Controller

    Notes:

    1. PDSIO is a proprietary technique developed by Eurotherm for bi-directionalcommunication over a single pair of wires. There are several operating modes.

    In SSRx Load Doctor a logic output delivers a power demand signal to a TE10 solidstate (SSR) relay and the SSR responds with a single load circuit failure message.

    In SSRx Enhanced Load Doctor a logic output delivers a power demand signal to anSSR and the SSR responds with the ON state rms load current, and two fault messages -SSR failure or heater circuit failure.

    2. Range min and Range max: Enter a numeric value, with a decimal point if required.Thermocouple and RTD sensor inputs will always display over the full operating rangeshown in the sensor input table. The values entered here will act as limits for the setpointhigh and low limit parameters and for alarm setpoints.

    3. Alarms are normally supplied configured as non-latching and de-energised-in-alarm, butthey can be configured as latching, energised-in-al