Installation and Operation Handbook Contents
HA026696 Issue 1. Jul-99 Applies to 2208e and 2204e Controller software versions 3.03 i
MODELS 2208e and 2204eTEMPERATURE CONTROLLERS
INSTALLATION AND OPERATION HANDBOOK
Contents Page
Chapter 1 OPERATION ............................................................. 1-1
Chapter 2 INSTALLATION ........................................................... 2-1
Chapter 3 ACCESS LEVELS ...................................................... 3-1
Chapter 4 TUNING ..................................................................... 4-1
Chapter 5 CONFIGURATION ...................................................... 5-1
Chapter 6 USER CALIBRATION ................................................. 6-1
Chapter 7 ALARM CONFIGURATION ......................................... 7-1
Appendix A UNDERSTANDING THE ORDERING CODE ............. A-1
Appendix B SAFETY & EMC INFORMATION ............................ B-1
TECHNICAL SPECIFICATION ............................ B-6
Appendix C ADDRESS ............................ C-1
Appendix D VALVE POSITIONER ............................ D-1
Appendix E LOAD CURRENT MONITORING E-1
Appendix F RETRANSMISSION F-1
This product is covered by one or more of the following US Patents:5,484,206 and 5,793,754; Additional patents pending.
PDSIO is a registered trademark of Eurotherm.INSTANT ACCURACY, SSRx Load Doctor and SSRx Enhanced Load Doctor
are trademarks of Eurotherm.
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-1
Chapter 1 OPERATION
PAGE
Front Panel Layouts1-2
Getting Started1-4
Navigation Diagram1-10
Parameter Tables1-12
Setting Alarm Levels1-19
Diagnostic Alarms1-20
Operation Installation and Operation Handbook
1-2 2208e and 2204e Controller
FRONT PANEL LAYOUT
Figure 1-1 Model 2208e front panel layout
Figure 1-2 Model 2204e front panel layout
DownButton
Manual mode
PageButton
ScrollButton
UpButton
Remote Setpoint
Output 2
Upper readout
Lower readout
Output 1
Setpoint 2active
Setpoint ratelimit active
OP1 OP2
2204e
SP2 REM
PageButton
ScrollButton
DownButton
UpButton
Manual mode
Setpoint 2 active PDSIO Remote Setpoint
Setpoint rate limit active
OP1 OP2
SP2 REM
2208e
Output 1 Output 2
Upper readout
Lower readout
RUN
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-3
Button orindicator
Name Explanation
OP1 Output 1 When lit, it indicates that heating output is on.
OP2 Output 2 When lit, it indicates that cooling output is on.
SP2 Setpoint 2 When lit, this indicates that Setpoint 2 has beenselected.
REM Remote SetpointWhen lit, this indicates that the PDSIO remoteSetpoint input has been selected. REM is alsoused to indicate that user comms is active.
MAN Manual light When lit, it indicates that manual mode has beenselected
RUN Run light When lit, it indicates that Setpoint rate limit isactive.
Page button Press to select a new list of parameters.
Scroll button Press to select a new parameter in a list.
Down button Press to decrease a value in the lower readout.
Up button Press to increase a value in lower readout.
Figure 1.3 Controller buttons and indicators
For Valve Positioning, please refer to Appendix D Motorised Valve ControlNOTE
Operation Installation and Operation Handbook
1-4 2208e and 2204e Controller
GETTING STARTED
Thank you for selecting the EUROTHERM 2208e/2204e controller.This section shows the principle of operation.
VIEWING THE PROCESS VALUE and SETPOINT
Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3second self-test sequence, this is the display you will see,
Figure 1.4 The Home Display
The display may flash an alarm message. Refer to the Parameter Tables later in thischapter for a complete list and meaning of the messages.
TO ADJUST THE SETPOINT
Figure 1.5 The lower readout shows the setpoint
After 2 seconds the lower readout will blink indicating that the new value has been accepted.For everyday use you may not need to do anymore than this.
Output 1Actual Temperature (Process Value)Output 2
Required Temperature (Setpoint)
OP1 OP2
Press and hold toincrease temperature
Press and hold todecrease temperature
OP1 OP2
NOTE
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-5
VIEWING THE DISPLAY UNITS
Figure 1.6 Pressing or will flash the display units for 0.5 secs
If you get lost, pressing and together will return you to the Home display
USE OF THE SCROLL BUTTON
Pressing the scroll button will display the output power level. Continued pressing willdisplay further parameters in the operator scroll list.
Figure 1.7 Upper readout is parameter name. Lower is value
Display Units
Degrees Centigrade
Degrees Farenheit
Degrees KelvinNo units - Linear inputs
Momentarilypress eitherbutton
0.5 sec.
Keep pressing to return to Homedisplay or select further parameters(if available)
2nd press
3rd press
OutputActual output level %
Manual/AutoActual state
NOTE
Operation Installation and Operation Handbook
1-6 2208e and 2204e Controller
USE OF THE PAGE BUTTON
The PAGE button accesses parameter LISTS.Parameters are settings in the instrument which, generally, can be changed by the user to suitthe process. Examples are: Alarms, Self Tune, etc. They are found under headings calledLISTS and a full set is given later in this chapter.
Figure 1.8 Press to choose a parameter list
The actual list headings may be longer or shorter than indicated above and you cancustomise this for the operators convenience in EDIT level, Chapter 3.
1st press
0.2 sec.
Keep pressing toselect more list headings
3rd press2nd press
NOTE
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-7
PARAMETER LISTS
Press to choose a LIST - ALARMS is a good one. This list allows you to set thealarm trip levels. The parameters which appear in the list will vary according to theconfiguration of your controller.
Figure 1.9 Choose a list. Press to select a parameter
If, at any time, no key is pressed within 45 seconds, the display will alwaysreturn to the HOME display.
or tochange trip level
or tochange trip level
1st press
2nd press
0.2 sec.
There are 4 alarms inthe controller. The firstcharacter is the alarmnumber. The followingthree letters indicatealarm type as follows:
Full Scale Low
Full Scale High
Deviation High
Deviation Low
Deviation Band
Low current
High currentDisabled alarms will notbe displayed.Chapter 7 gives a fulldescription of alarms.
Alarm List
Alarm 1
Now pressthe SCROLLbutton
2nd press
Keep pressing1. to scroll through further parameters2. to return to list header
Alarm 2
NOTE
Operation Installation and Operation Handbook
1-8 2208e and 2204e Controller
OPERATING MODES
The controller can be used in two modes:Automatic mode - in which the output power is automatically adjusted to hold thetemperature at the required value. The controller normally operates in this mode.Manual mode - in which the output is manually adjusted by the Operator. In this mode theMAN light will be on.
One other mode is available:Remote setpoint - The setpoint is generated as an input signal from a master 2000 seriescontroller. In this mode the REM light is on.
AUTO or MANUAL SELECT
Figure 1.10 Auto/Manual select
or to select
2 sec.
1st press
OutputActual output level %
Manual/Auto
automatic mode
manual mode
2nd press
3rd press
Keep pressingto return to HOMEdisplay
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-9
MANUAL ADJUSTMENT OF OUTPUT POWER
Figure 1.11 The Home Display in manual mode
SUMMARY
To step through list headers press the Page button until the required header is obtained
To step through parameters within a particular list press the Scroll button until therequired parameter is obtained
To change the value (or state) of a parameter press the Raise button or theLower button
The remainder of this chapter provides a complete list of all parameters available.
Actual Temperature (Process Value)
OP1 OP2
Output Power Demand
Manual Indicator on
Press and hold toincrease power
Press and hold todecrease power
Manual mode is generally used for test and commissioning purposes, takecare not to leave the controller in this mode since damage or personal injurycould occur.
NOTE
Operation Installation and Operation Handbook
1-10 2208e and 2204e Controller
NAVIGATION DIAGRAM (Part A)
The navigation diagram shows a full list ofpossible parameters. However, some may notappear because they are dependent upon theparticular controller variant.
Figure 1.12a Navigation diagram
HomeList
PID(1)List
AlarmList
AutotuneList
SetpointList
5
2
2
2
2
8
8
8
3
3
8
8
3
3
!
4
"
9
#$
%&'
$()
*
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-11
NAVAGATION DIAGRAM (PART B)
.
.
The shaded boxes are normally hidden in Operator level. To see all the availableparameters you must select Full level. See Chapter 3, Access Levels
Figure 1.12b Navigation diagram
InputList
OutputList
CommsList
AccessList
On OffList(1)
7
7
&
Notes:1. Either the PID list or the On/Off list will be present
depending upon the type of control in use.2. The last three characters depend upon the type of alarm
configured3. Absolute setpoint limits are set in configuration, see Chapter
5.4. VPOS only for VP. Refer to VP Appendix D.5. Amps is Mode 2 or Mode 5 PDSIO.6. mtr used for VP version. Refer to VP Appendix D.7. Beware! Used for calibration. See chapter 6.8. Is only available if using PDSIO comms in the HA slot.9. WSP is available if using ramp to setpoint.
&
%&
%&
$
*
Return toHome Display
6
+
7
+
!
Operation Installation and Operation Handbook
1-12 2208e and 2204e Controller
PARAMETER TABLES
Name Parameter Description Default Value Minimum Maximum Units Customer SettingUK USA Value Value
Home ListHome Measured Value and Setpoint(SP) SP=25C SP=75F as display
Valve positioner output power
%of mtr
% Output Level
%
Working setpoint as display
Setpoint
as display
Heater current (PDSIO modes 2 and 5)
Amps
Auto/manual select
Configure lower readout of home display
None, StD, AmPS,OP, stat, vPoS
Customer ID
Additional parameters may appear in the Home display if the promote feature has been used (see Edit Level, Chapter 3).
2208e and 2204e Controller 1-13
Installation and Operation Operation
Name Parameter Description Default Value Minimum Maximum Units Customer SettingUK USA Value Value
Alarm List
Alarm 1 set point value
as display
Alarm 2 set point value
as display
Alarm 3 set point value
as display
Alarm 4 set point value
as displayIn place of dashes, the last three characters indicate the alarm type, as follows:
Full Scale High alarm
as display
Full Scale Low alarm
as display
Deviation band alarm
as display
Deviation High alarm
as display
Deviation Low alarm
as display
Low current alarm
AMPS
High current alarm
AMPS
Hysteresis
as display
Loop break time
secs
Operation Installation and Operation Handbook
1-14 2208e and 2204e Controller
Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value
!
!
Autotune List!
Self tune enable !
Automatic droop compensation (ManualReset) enable (only present if ti set to OFF"! "! "!
PID List
Proportional band
as display
Integral time# #
seconds
Derivative time# #
seconds
Manual reset (appears when ti set to OFF)
%
Cutback low
as display
Cutback high
as display
Relative cool gain (set 1)
2208e and 2204e Controller 1-15
Installation and Operation Operation
Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value
Set Point List
Select SP1 or SP2
SP1 SP2
Local or remote setpoint select
Loc rmt
Setpoint 1 value$ %
As display range
Setpoint 2 value$ %
As display range
Remote setpoint
As display range
Local trim
As display range
Setpoint 1 low limit
As display range
Setpoint 1 high limit
As display range
Setpoint 2 low limit
As display range
Setpoint 2 high limit
As display range
Local setpoint trim low limit #
As display range
Local setpoint trim high limit
As display range
Setpoint rate limit &&
As display range'
Dwell time
0.1 to 999.9 minutes!
End type , ,
(
Program control !,
)
Status of program
Operation Installation and Operation Handbook
1-16 2208e and 2204e Controller
Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value
Input list* Input filter time constant # # && secs
PV Offset
as displayThe next 5 parameters will appear if User calibration has been enabled in configuration level. To perform a user calibration refer to Ch 6.
FACt will re-instate factory settings and disable User Calibration. Default setting FACtUSEr will re-instate any previously set User Calibration offsets and make available User Calibration parameters as follows:
User calibration select none none Hi, Lo, none*
Adjust calibrated reference sourceThe following two parameters are always present in Full Access level but not in Operator level+
Cold Junction compensation temperature
,
Millivolt input
* A minimum filter time constant of one second is recommended to provide sufficient noise immunity.
2208e and 2204e Controller 1-17
Installation and Operation Operation
Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value
Output list Note; If On/Off control is configured only , ! and ! will appear in the following list
Low (power) output limit (cool) %
High (power) output limit
%
Output setting when in sensor break
%1-
Heat cycle time (logic) (relay) secs!
Heat output min. on time (50mS) secs
1-
Cool cycle time (logic) (relay) secs
1!
Cool output min. on time (50mS) secs
VP motor travel time
secs
1 Are not used for Valve Position Control.
Operation Installation and Operation Handbook
1-18 2208e and 2204e Controller
Name Parameter Description Default Value Minimum Maximum Units Customer SettingsUK USA Value Value
!&
!&
On/off listThis set of parameters only appear if On/Off control has been configured.-
Heat hysteresis
as display.-
Cool hysteresis
as display
Heat/Cool dead band
as display
C omms list
Communications address $
Access list
Full and Edit level password
( Goto level ///!
!
!
Configuration level password
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-19
SETTING ALARM LEVELS
Up to 4 Alarms may be configured. Each alarm is given a name to describe its function -see table below:If an alarm is not configured it does not appear in the list below.
In place of dashes,letters indicate alarmtype as follows: Full Scale Low Full Scale High Deviation Band Deviation High Deviation Low Low current High current
Alarm List
Alarm 1
2nd press
or to change
3rd press
4th press
5th press
Alarm 2
Alarm 3
Alarm 4
Loop break time
or to change
or to change
or to change
or to change
Press to returnto list header
Figure 1.13
Operation Installation and Operation Handbook
1-20 2208e and 2204e Controller
DIAGNOSTIC ALARMSThese indicate that a fault exists in either the controller or the connected devices.
Displayshows
What it means What to do about it
Electrically ErasableMemory Error:The value of an operatoror configurationparameter has beencorrupted.
This fault will automatically take you intoconfiguration level. Check all of the configurationparameters before returning to operator level. Oncein operator level, check all of the operatorparameters before resuming normal operation. Ifthe fault persists or occurs frequently, contactEurotherm Controls.
Sensor Break:Input sensor isunreliable or the inputsignal is out of range.
Check that the sensor is correctly connected.
Loop Break:The feedback loop isopen circuit.
Check that the heating and cooling circuits areworking properly.
Load failureIndication that there is afault in the heatingcircuit or the solid staterelay.
This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR) operatingin PDSIO SSRx Load Doctor-see Electricalinstallation Chapter 2. It indicates either an open orshort circuit SSR, blown fuse, missing supply oropen circuit heater.
Solid state relay failureIndication that there is afault in the solid staterelay
This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR) operatingin PDSIO SSRx Load Doctor see Electricalinstallation Chapter 2. It indicates either an open orshort circuit condition in the SSR.
Heater failureIndication that there is afault in heating circuit
This is an alarm generated by feedback from aEurotherm TE10S solid state relay (SSR) operatingin PDSIO SSRx Enhanced Load Doctor-seeElectrical installation Chapter 2. It indicates either ablown fuse, missing supply or open circuit heater.
Hardware errorIndication that a moduleis of the wrong type.
Check that the correct modules are fitted.
No I/O moduleModules are configuredbut not fitted
Fit module.
Figure 1.14a Diagnostic alarms - continued on the next page
Installation and Operation Handbook Operation
2208e and 2204e Controller 1-21
Diagnostic alarms continued
These indicate that a fault exists in either the controller or the connected devices.
Displayshows
What it means What to do about it
Remote input failure. ThePDSIO input is opencircuit. (PDSIO Alsoknown as SST SmartSetpoint Transmission)
Check for open or short circuit wiring on thePDSIO input
Out of Display range, lowreading
Check the value of the display range
Out of Display range, highreading
Check the value of the display range
Error 1: ROM self-test fail Return the controller for repair
Error 2: RAM self-test fail Return the controller for repair
Error 3: Watchdog fail Return the controller for repair
Error 4: Keyboard failureStuck button, or a buttonwas pressed during powerup.
Switch the power off and then on withouttouching any of the controller buttons.
Error 5: Input circuit failure Return the controller for repair*
Power failure. The linevoltage is too low
Check that the supply to the controller is withinthe rated limits
Table 1.14b Diagnostic alarms
*If the user has disassembled and reassembled the instrument, this error can occur if anyconnectors are not seated properly.
Installation and Operation Handbook Installation
2208e and 2204e Controller 2-1
Chapter 2 INSTALLATION
PAGE
Instrument Layouts ....................................................... 2-2
Introduction ....................................................... 2-4
Mechanical Installation ....................................................... 2-4
Wiring ....................................................... 2-5
Outputs 1 and 2 Connection ....................................................... 2-7
Communication Connections ....................................................... 2-8
Typical Wiring Diagram ....................................................... 2-10
Installation Installation and Operation Handbook
2-2 2208e and 2204e Controller
INSTRUMENT LAYOUTS
Figure 2-1 2208e 1/8 DIN controller
Figure 2-2 2204e 1/4 DIN controller
3
4
4
56
78
8
1
2
2
3
4
4
5
6
7
8
8
KEY
1. Display screen
2. Latching ears
3. Panel sealing gasket
4. Panel retaining clips
5. Label
6. Sleeve
7. Terminal covers
8. Ratchets
2
2
1
Installation and Operation Handbook Installation
2208e and 2204e Controller 2-3
Outline dimensions Model 2208e
Figure 2-3 Outline dimensions Model 2208e controller
Outline dimensions Model 2204e
Figure 2-4 Outline dimensions Model 2204es controller
The controller plugs into a plastic sleeve, which in turn fits into the panel cutout shown inFigures 2-3 and 2-4.
2208
OP1 OP2
SP2 REM
Panelcutout
92 x 45mm
3.62x1.77in
-0+0.8
-0+0.6
-0+0.03
-0+0.02
103mm (4.01in)48mm (1.89in)
96mm(3.78in)
38mm(1.5in)
10mm(0.4in)
(Not toscale)
Recommendedminimum spacing ofcontrollers
2204
OP1 OP2
SP2 REM
Panel cutout
92 x 92 -0 +0.8mm
3.62 x 3.62 -0 +0.03in
103mm (4.01in)96mm (3.78in)
96mm3.78in
Recommendedminimumspacing ofcontrollers
38mm(1.5in)
10mm(0.4in)
(Not toscale)
Installation Installation and Operation Handbook
2-4 2208e and 2204e Controller
INTRODUCTION
The Models 2208e and 2204e are precision temperature controllers with self tuning. Theyhave a modular hardware construction which provides two control outputs, two alarm relaysand one communications port. Two logic inputs are provided as standard. In addition theModel 2204e has an optional plug-in 10A relay heating output.
Controller labels
The labels on the sides of the controller identify the ordering code, the serial number, and thewiring connections.
Appendix A, Understanding the Ordering Code explains the hardware and softwareconfiguration of your particular controller.
MECHANICAL INSTALLATION
To install the controller
1. Cut the panel to the relevant hole size shown in Figure 2-3 and 2.4.
2. Insert the controller through the front of this cutout.
3. Spring the upper and lower panel retaining clips into place. Secure the controller inposition by holding it level and pushing both retaining clips forward.
Note: If the panel retaining clips subsequently need removing, they can be unhooked from theside with either your fingers or a screwdriver.
Unplugging and plugging-in the controller
The controller can be unplugged from its sleeve by easing the latching ears outwards andpulling it forward out of the sleeve. When plugging the controller back into its sleeve, ensurethat the latching ears click into place to maintain the IP 65 sealing.
Installation and Operation Handbook Installation
2208e and 2204e Controller 2-5
WIRING
Please read Appendix B, Safety and EMC information before proceeding.
WARNINGPlease ensure that the controller is correctly configured for your application.Incorrect configuration could result in damage to the process being controlled,and/or personal injury. The controller may either have been configured whenordered, or may need configuring now. See Chapter 5, Configuration.
The wiring connections are shown in figure 2-5. Outputs 1 and 2 are factory fitted moduleswhich can be any one of the types shown in figure 2-8. Check the ordering code on thecontroller side label to determine which have been fitted.
Model 2208e connections
Figure 2-5 Model 2208e wiring connections
*The ground connection is not required for electrical safety but must be connected to satisfyEMC requirements.
*Do not use unused terminals as wire holders.
Pt100
N
L
V+
VI
V-
Line
Neutral
Ground
+
-
+PV-
2B
2A
1B
1A
HF
HD
HECommon
Input 1
Input 2
85 to 264Vac
LC
LA
LB
AC
AB
Output 1
3B
3A
3C
Output 2
Output 4
Output 3
AA
HB
HC
HA
Comms
Installation Installation and Operation Handbook
2-6 2208e and 2204e Controller
Wire Sizes
All electrical connections are made to the screw terminals at the rear of the controller. Theyaccept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG), and are protected by a hinged cover toprevent hands or metal making accidental contact with live wires. Rear terminals should betightened to a torque of 0.4Nm (3.5 lb in).Wiring connections
The wiring connections are shown in figure 2-6. Outputs 1 and 2 are factory fitted moduleswhich can be any one of the types shown in figure 2-8. Check the ordering code on thecontroller side label to determine which have been fitted.
Model 2204e Connections
Figure 2-6 Model 2204e Wiring connections
*The ground connection is not required for safety purposes but must be connected to satisfyEMC requirements.
*Do not use unused terminals as wire holders.
Input 1
Neutral
*Ground*
+
-
+PV-
85-264VacHIGH
CURRENT
OUTPUT
Pt100
Output 1
Output 2
4B
4C
4D
5A
5B
5D
6A
6B
6C
6D
5C
1B
2A
2B
1A
3A
3B
3C
N
LA
LB
LC
L
AB
AC
VI
V+
V-
AA
HB
HC
HD
HE
HF
HA
Line
BUSBAR
Line
BUSBAR
Output 4
Output 3
Input 2
Common
Comms
Line4A
Installation and Operation Handbook Installation
2208e and 2204e Controller 2-7
Sensor input connectionsThe connections for the various types of input are as follows:
Fig 2-7 Sensor input connections
Sensor inputs should not be paralleled
OUTPUTS 1 AND 2 CONNECTIONS
Outputs 1 and 2 can be any one of the types shown in the table below, configured to performany one of the functions shown.
To check which outputs are installed, and their configuration, refer to the ordering code andthe wiring information on the controller side labels.
Connections
Output 1 Output 2 Possible functions
Module type 1A 1B 2A 2B
Relay: 2-pin (2A, 264 Vac max.)
HeatingCoolingAlarms
Logic: non-isolated* (18Vdc at 24mA)
+ - + -+PDSIO modes 1 or 2 (SSRx
Load Doctor Functions)HeatingCoolingAlarms
Triac(1A, 30 to 264Vac) Heating or cooling
DC control: isolated (18Vdc, 20mA max)
+ - DC not availablein output 2
PID Heating or cooling
*Logic output can also be configured as logic input on module 2A.+PDSIO Mode 1 & 2 are only supported in Module 1A.
Figure 2-8 Outputs 1 and 2 connections
VI
V+
V-
VI
V+
V-
VI
V+
V-
VI
V+
V-
Thermocouple Resistancethermometer mA inputVolts or mV
inputs
+
-
PV
2.49currentsenseresistor
Line Load Line Load
NOTE
Installation Installation and Operation Handbook
2-8 2208e and 2204e Controller
PDSIO modes
PDSIO is a proprietary technique developed by Eurotherm for bi-directional communicationover a single pair of wires. There are several operating modes. In SSRx Load Doctor a logic output delivers a power demand signal to a TE10 solid state(SSR) relay and the SSR responds with a single load circuit failure message.In SSRx Enhanced Load Doctor a logic output delivers a power demand signal to an SSRand the SSR responds with the ON state rms load current, and two fault messages - SSR failureor heater circuit failure.
Snubbers
The controller is supplied with snubbers (15nF +100) which should be wired across therelay or triac outputs when switching inductive loads such as mechanical contactors andsolenoid valves. The snubbers are used to prolong contact life and to suppress interferencewhen switching such loads. Snubbers pass 0.6mA at 110Vac and 1.2mA at 240Vac, whichmay be sufficient to hold in high impedance relay coils. They should not, therefore, be used insuch installations.
WARNINGWhen a relay contact is used in an alarm circuit ensure that the current passing throughthe snubber when the relay contact is open does not hold in low power electrical loadsand thereby interfere with the failsafe operation of the alarm circuit.
COMMUNICATION CONNECTIONS
The communication option can be either of four types shown in the table below
Connection
Communications type HB HC HD HE HF
4-wire EIA-422 serialcommunications*
A (RX +)
B (RX -)
Common A (TX +)
B (TX -)
2-wire EIA-485 serialcommunications*
Not used Not used Common A (TX +) (RX +)
B (TX -) (RX +)
EIA-232 serialcommunications
Not used Not used Common A B
PDSIO Setpoint input Not used Not used Not used Signal Common
*The 4-wire EIA-422 communication board can be modified to support 2-wire 485communication. Please consult factory.
Figure 2-9 Communication connections
Installation and Operation Handbook Installation
2208e and 2204e Controller 2-9
Wiring of EIA-485 serial communication links
Local
LocalEarth
HF +S eries 2000Controller
Com
Note:All termination res istors are 220 ohm 1/4W carbon composition.Local grounds are at equipotential. Where equipotential is not available wire intoseparate zones us ing a galvanic isolator.
AB
PC
Universal Convertor
RXT XCom
Com T XRX
Up to 32controllers orInterface Units maybe included on thenetwork
232
Com B A
Com
AB
GalvanicIsolationBarrier
Com
AB
Com
AB
Local Earth
Com
AB
Earth
UniversalConverter
MMI
S eries 2000Controller
S eries 2000Controller
For safety reasons,do not connect tolocal earth here.
HD
HF+
HE
HD
HF+
HE
HE
HD
Figure 2-10 2-wire EIA-485 wiring
Standard EIA-485 is a 2-wire connection which allows upto 32 controllers to be multi-dropped from a singlecommunications link over a distance of up to 1.2Km. Toensure reliable operation of the communications link,(without data corruption due to noise or line reflections) theconnections between the controller should be made usinga twisted pair of wires inside a shielded cable with theconnections terminated with resistors in the manner shownin this diagram. This diagram also shows the use of aComms converter to connect the 2-wire EIA-485 link into astandard EIA-232 computer port.
Common and LocalEarth cannot beconnected together.
Installation Installation and Operation Handbook
2-10 2208e and 2204e Controller
TYPICAL WIRING DIAGRAM
Fig 2-11 Typical wiring diagram, Model 2208e Controller
Neutral
N
L
V+
VI
V-
+
-
+
PV-
2B
2A
3B
3A
3C
1B
1A
HF
HD
HE
LC
LA
LB
AC
AA
AB
Cooling PowerFuse 1A(T)
Heating power fuse(load dependent)
CoolingSolenoid Valve
HeaterThermocouple
-
ControllerFuse2A(T)
Solid StateRelay
such asTE10S+
-
Snubber
Output 1logicheating
Line
Output 2Triaccooling
HC
HA
HB
Installation and Operation Handbook Access Levels
2208e and 2204e Controller 3-1
Chapter 3 ACCESS LEVELS
PAGE
The Different Access Levels .......................................................... 3-2
Selecting an Access Level .......................................................... 3-3
Edit Level .......................................................... 3-5
Access Levels Installation and Operation Handbook
3-2 2208e and 2204e Controller
This chapter describes the different levels of access to the operating parameters within the2208e and 2204e controller.
There are three topics: THE DIFFERENT ACCESS LEVELS SELECTING AN ACCESS LEVEL EDIT LEVEL
THE DIFFERENT ACCESS LEVELS
Access level Displayshows
What you can do PasswordProtection
Operator
In this level operators can view and adjust thevalue of parameters defined in Edit level (seebelow).
No
Full
In this level all the parameters relevant to aparticular configuration are visible. Allalterable parameters may be adjusted.
Yes
Edit
In this level you can set which parameters anoperator in Operator level is able to view andadjust. You can hide or reveal complete listsand individual parameters within each list, andyou can make parameters read-only oralterable. You can also promote parametersto the home list. (See Edit level at the end ofthe chapter).
Yes
Configuration
This special level allows access to set up thefundamental characteristics of the controller.
Yes
Figure 3-1 Access levels
Installation and Operation Handbook Access Levels
2208e and 2204e Controller 3-3
SELECTING AN ACCESS LEVEL
Access to Full, Edit or Configuration levels is protected by a password to preventunauthorised access.If you need to change the password, see Chapter 5, Configuration
Access list header
Press until you reach the access list header .
Press the Scroll button
Password entry
The password is entered from the display.Enter the password using the or buttons. Once
the correct password has been entered, there is a two second delayafter which the lower readout will change to show indicating that access is now unlocked.The pass number is set to 1 when the controller is shipped fromthe factory.
Note; A special case exists if the password has been set to . Inthis case access will be permanently unlocked and the lowerreadout will always show
Press the Scroll button to proceed to the display.
(If an incorrect password has been entered and the controller is stilllocked then pressing Scroll at this point will simply return you tothe list header.)
Note: From this display, you can access read onlyconfiguration level by pressing and together.
To escape, press and together.
Access Levels Installation and Operation Handbook
3-4 2208e and 2204e Controller
.
.
Level selection
The display allows you to select the requiredaccess level.
Use and to select from the following displaycodes: Operator level: Full level Edit level: Configuration level
Press the Scroll button
If you selected either , or level youwill be returned to the list header in the level thatyou chose. If you selected , you will get analternative display showing in the upper readout(see below).
Configuration password
When the display appears, you must enter theConfiguration password in order to gain access toConfiguration level. Do this by repeating the passwordentry procedure described in the previous sectionThe configuration password is set to when thecontroller is shipped from the factory. If you need tochange the configuration password, see Chapter 5,Configuration
Press the Scroll button
Configuration level
The first display of configuration is shown. See chapter5, Configuration for details of the configurationparameters.For instructions on leaving configuration level seeChapter 5, Configuration.
Installation and Operation Handbook Access Levels
2208e and 2204e Controller 3-5
Returning to Operator Level
To return to operator level from either or level, repeat entry of the passwordand select on the display.In Edit level the controller will automatically return to operator level if no button is pressedfor 45 seconds.
EDIT LEVEL
Edit level is used to set which parameters you can see and adjust in Operator level. It alsogives access to the Promote feature which allows you to select and add (Promote) up totwelve parameters into the Home display list, thereby giving simple access to commonly usedparameters.
Setting operator access to a parameter
First you must select level, as shown on the previous page.Once in level you select a list or a parameter within a list in the same way as you wouldin Operator or Full level. hat is, you move from list header to list header by pressing thePage button, and from parameter to parameter within each list using the Scroll button.However, in Edit level what is displayed is not the value of a selected parameter but a coderepresenting the parameters availability in Operator level.
When you have selected the required parameter, use the and buttons to set itsavailability in operator level.There are four codes:
Makes a parameter alterable in Operator level
Promotes a parameter into the Home display list
Makes a parameter or list header read-only (it can be viewed but not altered)
Hides a parameter or list header.For example:
The parameter selected is the set point for Alarm2 - Full Scale Low
It will be alterable in Operator level
Access Levels Installation and Operation Handbook
3-6 2208e and 2204e Controller
Hiding or revealing a complete list
To hide a complete list of parameters, all you have to do is hide the list header. If a list headeris selected only two selections are available: and .(It is not possible to hide the list which will always display the code: .)Promoting a parameter
Scroll through the lists to the required parameter and choose the code. The parameter isthen automatically added (promoted) into the Home display list (the parameter will also beaccessible as normal from the standard lists. a maximum of 16 parameters can be promoted.Promoted parameters are automatically alterable.
Installation and Operation Handbook Tuning
2208e and 2204e Controller 4-1
Chapter 4 TUNING
PAGE
What is Tuning? .................................................................. 4-2
Automatic Tuning .................................................................. 4-3
Manual Tuning .................................................................. 4-6
Tuning Installation and Operation Handbook
4-2 2208e and 2204e Controller
Before tuning please read Chapter 1, Operation, to learn how to select and change aparameter.This chapter has three main topics: WHAT IS TUNING? AUTOMATIC TUNING MANUAL TUNING
WHAT IS TUNING?
In tuning you match the characteristics of the controller to that of the process being controlledin order to obtain good control. Good control means:Stable straight-line control of the temperature at setpoint without fluctuationAcceptable overshoot or undershoot of the temperature setpointQuick response to deviations from the setpoint caused by external disturbances, therebyrestoring the temperature rapidly to the setpoint value.Tuning involves calculating and setting the value of the parameters listed in Table 4-1. Theseparameters appear in the list.
Parameter Code Meaning or Function
Proportionalband
The bandwidth in display units over which the output power isproportioned between minimum and maximum.
Integral time
Determines the time taken by the controller to remove steady-state error signals.
Derivativetime
Determines how strongly the controller will react to the rate-of-change of the measured value.
Low cutback
The number of display units below setpoint at which thecontroller will cutback the output power in order to preventovershoot on heat up.
High Cutback
The number of display units above setpoint at which thecontroller will increase the output power in order to preventundershoot on cool down.
Relative coolgain
Only present if cooling has been configured. Sets the coolingproportional band by dividing the Pb value by the rEL.C value.
Table 4-1 Tuning parameters
Installation and Operation Handbook Tuning
2208e and 2204e Controller 4-3
AUTOMATIC TUNING
This method automatically determines the value of the parameters listed in table 4-1 on theprevious page.The 2208e and 2204e use a one-shot tuner which works by switching the output on and offto induce an oscillation in the measured value. From the amplitude and period of theoscillation, it calculates the tuning parameter values.If the process cannot tolerate full heating or cooling being applied during tuning, then thelevel of heating or cooling can be restricted by setting the heating and cooling power limits inthe Output list. However, the measured value must oscillate to some degree for the tuner to beable to calculate valuesA One-shot Tune can be performed at any time but normally it is performed only once duringthe initial commissioning of the process. However, if the process under control subsequentlybecomes unstable (because its characteristics have changed), you can re-tune again for the newconditions.It is best to start tuning with the process at ambient temperature. This allows the tuner tocalculate more accurately the low cutback and high cutback values that restrict the amount ofovershoot or undershoot.
Heating and Cooling Output Cycle Times
Before commencing a tuning cycle, set the values of (heat cycle time) and (coolcycle time) in the op (output list). These values apply if you are using a logic, relay or triacoutput. They have no effect on a DC output.A logic output switching a solid state relay can be set to values such as 1 sec.A relay or triac output should be set to 20 sec.
Tuning Installation and Operation Handbook
4-4 2208e and 2204e Controller
How to tune
1. Set the setpoint to the value at which you will normally operate the process.2. In the list, select and set it to 3. Press the Page and Scroll buttons together to return to the Home display. The display
will flash to indicate that tuning is in progress.4. The controller will induce an oscillation in the temperature by turning the heating on and
then off. The first cycle will not complete until the measured value has reached therequired setpoint.
5. After two cycles of oscillation the tuning will be completed and the tuner will switchitself off.
6. The controller will then calculate the tuning parameters listed in Table 4-1 and willresume normal control action.
If you want Proportional only or PD or PI control, you should set the or parameters to before commencing the tuning cycle. The tuner will leave them off andwill not calculate a value for them.
For valve position tuning and set-up, please refer to Appendix D.
Installation and Operation Handbook Tuning
2208e and 2204e Controller 4-5
Typical automatic tuning cycle
Calculation of the cutback values
Low cutback and High cutback are values that restrict the amount of overshoot or undershootthat occur during large step changes in temperature (for example, under startup conditions).If either low cutback or high cutback is set to the values will be fixed at three timesthe proportional band, and will not be changed during automatic tuning.
Time
SetpointTemperature
Tuning Installation and Operation Handbook
4-6 2208e and 2204e Controller
MANUAL TUNING
If for any reason automatic tuning gives unsatisfactory results, you can tune the controllermanually. There are a number of standard methods for manual tuning. The one describedhere is the Ziegler-Nichols method.With the process at its normal running temperature:1. Set the Integral Time and the Derivative Time to .2. Set High Cutback and Low Cutback, and , to 3. Ignore the fact that the temperature may not settle precisely at the setpoint4. If the temperature is stable, reduce the proportional band so that the temperature just
starts to oscillate. If the temperature is already oscillating, increase the proportional banduntil it just stops oscillating. Allow enough time between each adjustment for the loop tostabilise. Make a note of the proportional band value B and the period of oscillation T.
5. Set the Pb, ti, td parameter values according to the calculations given in Table 4-2.
Type of control Proportionalband Pb
Integral time ti Derivative timetd
Proportional only 2xB OFF OFF
P + I control 2.2xB 0.8xT OFF
P + I + D control 1.7xB 0.5xT 0.12xT
Table 4-2 Tuning values
Installation and Operation Handbook Tuning
2208e and 2204e Controller 4-7
Setting the cutback values
The above procedure sets up the parameters for optimum steady state control. If unacceptablelevels of overshoot or undershoot occur during start-up or for large step changes intemperature, then manually set the cutback parameters and .Proceed as follows:1. Set the low and high cutback values to three proportional bandwidths (that is to say, Lcb
= Hcb = 3 x Pb).2. Note the level of overshoot or undershoot that occurs for large temperature changes (see
the diagrams below).In example (a) increase by the overshoot value. In example (b) reduce by theundershoot value.Example (a)
Temperature
Example (b)
Temperature
Where the temperature approaches setpoint from above, you can set ina similar manner.
Time
Undershoot
SetpointOvershoot
Tuning Installation and Operation Handbook
4-8 2208e and 2204e Controller
Integrating action and manual resetIn a full three-term controller (that is, a PID controller), the integral term ti automaticallyremoves steady state errors from the setpoint. If the controller is set up to work in two-termmode (that is, PD mode), the integral term will be set to . Under these conditions themeasured value may not settle precisely at setpoint. When the integral term is set to OFF theparameter manual reset (code ) appears in the in Access level.This parameter represents the value of the power output that will be delivered when the erroris zero. You may set this value manually in order to remove the steady state error.
Automatic droop compensation (Adc)
The steady state error from the setpoint, which occurs when the integral term is set to OFF, issometimes referred to as droop. automatically calculates the manual reset value inorder to remove this droop. To use this facility, you must first allow the temperature tostabilise. Then, in the autotune parameter list, you must set to . The controllerwill then calculate a new value for manual reset, and switch to . can be repeated as often as you require but between each adjustment you must allow timefor the temperature to stabilise.
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-1
Chapter 5 CONFIGURATIONPAGE
Selecting Configuration Level ...................................................... 5-2
Leaving Configuration .................................................................. 5-3
Steps Involved in Configuring a Controller ................................... 5-3
Navigation Diagram ...................................................................... 5-4
Configuration Parameter Tables .................................................. 5-6
WARNINGConfiguration is protected and should only be carried out by an authorised person.Incorrect configuration could result in damage to the process being controlled and/orpersonal injury. It is the responsibility of the person commissioning the instrument toensure that the configuration is correct.
5-2 2208e and 2204e Controller
Configuration Installation and Operation Handbook
SELECTING CONFIGURATION LEVEL
Figure 5.1
At this point thecontroller is inconfiguration level
HOMEdisplay
Press Pagebuttonrepeatedlyuntil AccessList appears
or to enter password (factory default = 1)
If incorrectpasswordentered
or to enterpassword (factory default = 2)
Note: Selectingor will allow direct entry tothese levels at this point
1st press
2nd press
3rd press
If the password hasbeen set to - accessis permanentlyunlocked & the lowerreadout always shows
Repeated pressing of Page buttonselects configuration list headings in a
continuous loop
2 secs
or to select
4th press
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-3
LEAVING CONFIGURATION LEVEL
STEPS INVOLVED IN CONFIGURING A CONTROLLER
The navigation diagram which follows shows the general location of parameters which definethe way in which the controller works. They are grouped under headings. The actual parametersshown in your controller may differ slightly since some appear only as a result of selectingothers. A full list of possibilities is included in the PARAMETER TABLES which follow thenavigation diagram.
or to select
Keep pressing untilExit display appears
After a 2 second delay the screenwill blank, the instrument will reset,and revert to the Home display
Figure 5.2
5-4 2208e and 2204e Controller
Configuration Installation and Operation Handbook
NAVIGATION DIAGRAM (PART A)Instrument Input User cal. Alarms Logic input 1 Logic input 2 Output AA
Config Config Config Config Config Config Config
Seeparametertables
!
"
#$
%
&
!
'
'
(
!
(
)
(
&
(
The Principle of Operation is thesame as that already described inCh1.That is:
Step through List Headers using the Page button
Choose a parameter from a list using the Scroll button
Change value using the Raise/Lower buttons
The first 4 headings set up thecontroller functions, as follows:Instrument Config. - Groups thoseparameters associated with thedisplay and control action.Input Config. - selects the inputsensor typeUser cal. Config. - to calibrate toexternal reference sourcesAlarms Config. - sets up the alarmtypes
*
+
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-5
NAVIGATION DIAGRAM (PART B)Comms Output 1 Output 2 Output 3 10A output PasswordConfig Config Config Config Config Config
See Table Bparameter table,page 5-13
See Table Bparameter table,page 5-14
!
)
,
&
"
"
"
$
-
(+
./
!
0
1
2
'+
'+
Configuration Installation and Operation Handbook
5-6 2208e and 2204e Controller
Heading Input/Output Functions Wiring TerminalsThe first four headings set up the controller functions as follows:
Sets up display and control parameters Not applicable
Selects the input sensor type Not applicable
To calibrate to external reference sources Not applicable
Sets up the alarm types Not applicableThe remaining headings configure the controller input/output functions.The upper readout corresponds to rear terminal numbers associated with a particular i/o.
Sets up the action of the two digital inputs LA & LB
Sets up the action of the fixed relay on output AA AA to AC
Sets up digital comms type HB to HF
Sets up the output modules 1A and 2A 1A & 1B / 2A & 2B
Sets up the action of the fixed relay on output 3A 3A to 3C
Sets the action of the 10A output relay in 2204 4A to 6D
To choose new passwords / To leave configuration level and return to operator level
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-7
NOTE
CONFIGURATION PARAMETER TABLES
Name Parameter description Values Meaning
Instrument configuration
Instrument
Centigrade (default UK)units
Fahrenheit (default USA)
Kelvin
Units are not displayed
Decimal places in the
Nonedisplayed value
One
Two
Control type
On/off control
PID controlVP Control
Control action
Reverse acting (required fortemperature control) - outputdecreases on approach tosetpoint.
Direct acting
Type of cooling
Linear
Oil (50mS min on time)
Water(non-linear)
Fan (0.5S min on time)
Power feedback
Power feedback is on(compensates for changes insupply voltage)
Power feedback is off
Bumpless manual/auto
Non-bumpless transfertransfer when using PD control
Bumpless transfer (auto to manualand manual to auto)
Forced manual output
Bumpless manual/auto transfer
Returns to the manual value thatwas set when last in manualmode.
Sensor break output
Go to pre-set value (maintainsoutput at a known, safe level)
Freeze output (maintains output atvalue immediately before break)
Load Current Scaling Factor
See Appendix E-10
Factory default parameter values and states are included where applicable and areindicated by the shaded areas in the following tables.
Configuration Installation and Operation Handbook
5-8 2208e and 2204e Controller
Name Parameter description Value Meaning
Input configuration
Input type
J thermocouple (default USA)
K thermocouple (default UK)
L thermocouple
R thermocouple (Pt/Pt13%Rh)
B thermocouple (Pt30%Rh/Pt6%Rh)
N thermocouple
T thermocouple
S thermocouple (Pt/Pt10%Rh)
PL 2 thermocoupleNOTE: 100 platinum resistance thermometer.
After selecting an inputtype, do not forget toadjust the setpoint limitsin Full Access level
Custom downloaded input type. Thedefault is C thermocouple, or the name ofthe downloaded custom input will bedisplayed.!"
Linear millivolt (Also mA input via anexternal 2.49 current sense resistor)
Linear voltage#
Input range low Display low range for input#
Input range high Display high range for input
CJC ref. temperature
Automatic cold junction compensation(CJC does not appear for 0C external reference
linear inputs)$% 45C external reference% 50C external reference
Linear Input Scaling - The next 4 parameters only appear if a linear input is chosen
Input value low
Input value high
"
Displayed reading low
"
Displayed reading high
&!
Sensor break inputimpedance trip level
Sensor break detection is disabledAppears for mV or V inputs only
Trip level set by the sensor input table Trip level set at 7.5K
Trip level set at 15K (must be selectedwhen input is enabled)
Displayed
Value
ElectricalInput
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-9
Name Parameter description Value Meaning
User calibration config. See Chapter 6 - User calibration
User cal enable
User calibration is disabled
User calibration is enabled
User calibrationpoint low
This is the value (in display units) at which a Userlast performed a low point calibration
User calibrationpoint high
This is the value (in display units) at which a Userlast performed a high point calibration
Low pointcalibration offset
Offset, in display units, at the user low calibrationpoint Pnt.L. This value is automatically calculatedwhen performing low point calibration.
High pointcalibration offset
Offset, in display units, at the user high calibrationpoint Pnt.H. This value is automatically calculatedwhen performing a high point calibration.
* If User calibration is enabled, then the User calibration parameters will appear in the Input list ofOperator Full access level. See Chapter 6, User calibration.
Configuration Installation and Operation Handbook
5-10 2208e and 2204e Controller
NOTE
Name Parameter description Values
Alarm configuration Values Defaults if not specified
Alarm 1 Type As table A
Alarm 1 Blocking(1)/
'
Alarm 1 Latching//!(
Alarm 2 Type As table A
Alarm 2 Blocking(1)/
'
Alarm 2 Latching//!(
)
Alarm 3 Type As table A
Alarm 3 Blocking(1)/
'
Alarm 3 Latching/(/!(
$
Alarm 4 Type As table A
Alarm 4 Blocking(1)/
'
Alarm 4 Latching/(/!(
Table A: Alarm types
No alarm
Full scale low
Full scale high
Deviation band
Deviation high
Deviation low
Low current
High current
(1) Blocking allows the alarm to become active only after it has first entered a safe state.
These are soft alarms, i.e. Indication only. They would normally be attached to anoutput. See Chapter 7 for a step by step guide.
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-11
Name Parameter description Values
Logic input 1 configuration Functions Action on contact closure
Identity of input+
Logic input
Function
None!
Manual mode select!
Remote setpoint select
Setpoint 2 select
Integral hold
Acknowledge alarms
Lock Key pad
Reset
Standby - ALL outputs = OFF!
PDSIO load current input
Logic input 2 configuration Functions Action on contact closureAs per Logic input 1 except ! not available
Configuration Installation and Operation Handbook
5-12 2208e and 2204e Controller
Name Parameter description Functions Meaning
Alarm relay configuration Functions Meaning
Identity of output,
Relay
Function
None+ Function set by + (as in
Table B)
Heating
CoolingFor -tion = + go to table B on the next page
Sense of output (alwaysappears)
Normal (heat & cool outputs)Inverted (alarms de-energisedin the alarm state)
Comms module config Functions Meaning
Identity of the option installed.
PDSIO setpoint input
!
2- or 4-wire EIA-485 (422) orEIA-232 comms module
FunctionSome of the following parameters may appear if one of the comms options is installed
!
DIGITAL Communicationprotocol ordered
NoneThe following parameters will appear if the PDSIO setpoint input option is installed.
No PDSIO function
PDSIO setpoint input"
PDSIO low input value Range = -999 to 9999"
PDSIO high input value Range = -999 to 9999The following parameters will appear if the function chosen is Mod protocol./
Baud Rate 1200, 2400, 4800, 9600, 19.20, 1920 (19200)*, Comms Parity No parity
Even parity
Odd parity* Comms Resolution Full resolution&
Integer resolution
*Not used with some communication protocols. Please consult factory.
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-13
Name Parameter description Function Meaning
Output 1 configuration Function Meaning
Identity of module installed
No module fitted0,
Relay output
DC output (isolated)+
Logic or PDSIO output
Triac output
Function1
Module does not operate.&+ Function set by +
Heating output
Cooling outputOnly appear for id = dC.OP
Retransmission of outputdemand
Only appear for id = dC.OP"
Retransmission of ProcessValue
Only appear for id = dC.OP
Retransmission of errorOnly appear for id = dC.OP
Retransmission of setpointOnly appear for id = LoG
PDSIO mode heatingOnly appear for id = LoG
PDSIO mode 2 heatingFor -tion = + go to table B below
Sense of output
Normal (e.g.heating and cooling)Inverted (alarms - de-energise inalarm)
DC output scaling For id = dC.OP the following parameters appear
DC output minimum 0mA to 20mA
DC output maximum 0mA to 20mA
Configuration Installation and Operation Handbook
5-14 2208e and 2204e Controller
Table B The following parameters appear if + is chosen as the function.+
Digital output functions
'
No changeAny number of the functionslisted can be combined on tothe output. Use the
and
buttons to selecta desired digital function.After two seconds thedisplay will blink and returnto the
' display. Usethe arrows again to scrollthrough the function list.The previously selectedfunction display will showtwo decimal points indicatingthat it has been added to theoutput.
2 2 2
*
2 2 2 *
) 2 2 2 *
$ 2 2 2 *
3
-
1
1(
0!
'
Clear all existing functionsAlarm 1 *Alarm 2 *Alarm 3 *Alarm 4 *Manual/AutoSensor BreakLoop BreakHeater FailLoad FailEND ProgramPV Out of RangePDSIO SSR FailureNew AlarmRemote Sp FailCTx open circuitCtx short circuit
* From previous page. In place of the dashes, the last three characters indicate the alarm type as per tableA in the AL list: eg = Full Scale Low If an alarm is not configured the displayed name will differ:e.g. will be shown, for the first alarm.
Name Parameter description Function Meaning
Output 2 configuration Function Meaning
Identity of module installed
No module fitted,
Relay output+
Logic
Triac output
Function
none
Outputs+ Function set by +
Heating output
Cooling outputLogic Inputs!
Manual mode select!
Remote setpoint select
Setpoint 2 select
Integral hold
Acknowledge alarms
Standby - ALL outputs = OFFFor = + (Refer to table B on page 5-13).
Sense of output
Normal (heat and cool outputs)Inverted (alarms - de-energise in alarm)
Installation and Operation Handbook Configuration
2208e and 2204e Controller 5-15
)
)
Output 3 configuration As per output AA configuration
$
$
10Amp heating output Available on 2204e only.As per Output 3A configuration
Password list
FuLL or Edit level password
Configuration level Password
4
4
Exit Configuration
/
Installation and Operation Handbook User Calibration
2208e and 2204e Controller 6-1
Chapter 6 USER CALIBRATION
PAGE
What is the Purpose of User Calibration? ................................... 6-2
User Calibration Enable ............................................................... 6-3
Single Point Calibration ............................................................... 6-4
Two Point Calibration .................................................................. 6-5
Calibration Points and Calibration Offsets .................................. 6-6
User Calibration Installation and Operation Handbook
6-2 2208e and 2204e Controller
This chapter has five topics: WHAT IS THE PURPOSE OF USER CALIBRATION? USER CALIBRATION ENABLE SINGLE POINT CALIBRATION TWO POINT CALIBRATION CALIBRATION POINTS AND CALIBRATION OFFSETS
To understand how to select and change parameters in this chapter you will need to have readChapter 2 - Operation, Chapter 3- Access Levels and Chapter 5 - Configuration.
WHAT IS THE PURPOSE OF USER CALIBRATION?
The basic calibration of the controller is highly stable and set for life. User calibration allowsyou to offset the permanent factory calibration to either:
1. Calibrate the controller to your reference standards2. Match the calibration of the controller to that of a particular transducer or sensor input3. Calibrate the controller to suit the characteristics of a particular installation.
User calibration works by introducing zero and span offsets onto the factory set calibration.The factory set calibration can always be retrieved.
Installation and Operation Handbook User Calibration
2208e and 2204e Controller 6-3
USER CALIBRATION ENABLEThe User calibration facility must first be enabled in configuration level by setting theparameter ' in the list to '' This will make the User calibrationparameters appear in Operator level.Select configuration level as shown in Chapter 5, Configuration
The User calibration configuration List
Press until you reach the list
ress the Scroll button until you reach
User calibration enable
Use or to select:
: Calibration enable: Calibration disabled
Press and together to go to the Exit display
Exit configuration
Use or to select and return to Operator level.
User Calibration Installation and Operation Handbook
6-4 2208e and 2204e Controller
SINGLE POINT CALIBRATION
Your controller is calibrated for life against known reference sources during manufacture. Acalibration offset is often used to allow the controller to compensate for sensor and othersystem errors. The normal procedure is to set up the system under test against a knownindependent reference, as follows:Set up the process to be calibrated such that the known reference displays the required value(temperature).Observe the reading on the controller. If it is different, proceed as follows:Select Access level as described in Chapter 3
Input list header
Press until you reach the input list header.
Press Scroll until you reach the display
Calibration type
Use or to select either or .Selecting will reinstate the factory calibration andhide the following User calibration parameters.Selecting will reinstate any previously set Usercalibration and make available the User parameters, asfollows:
Press the Scroll button
Calibrate low point?
Use or to select Selecting no will hide the next parameter
Press the Scroll buttoncontinued on the next page
Installation and Operation Handbook User Calibration
2208e and 2204e Controller 6-5
To protect the calibration against unauthorised adjustment return to Operator level and makesure that the calibration parameters are hidden. Parameters are hidden using the facility describe in Chapter 3.
TWO POINT CALIBRATION
The previous section described how to perform a single point calibration which applies a fixedoffset over the full display range of the controller. A two-point calibration is used to calibratethe controller at two points and apply a straight line between them. Any readings above orbelow the two calibration points will be an extension of this straight line. For this reason it isbest to calibrate with the two points as far apart as possible.Proceed as follows:1. Decide upon the low and high points at which you wish to calibrate.2. Perform a single point calibration at the low calibration point in the manner
described above3. Set the process under calibration such that the known reference exhibits the required
higher Process Value (temperature) and allow to stabilize.4. Press the Scroll button to obtain the high calibration point as shown in the
following diagrams.
Adjust the low point calibration
The controller will display the current measured input value in thelower readout.
Use or to adjust the reading to the reference sourcevalue, if different.After a two second delay the display will blink and the reading willchange to the new, calibrated value. You can calibrate at any pointover the entire display rangeThis is a single point calibration which applies a fixed offset over thefull display range of the controller.The calibration is now complete. You can return to the factorycalibration at any time by select in the CAL display shownearlier.
Press
and
together to return to theHome display
User Calibration Installation and Operation Handbook
6-6 2208e and 2204e Controller
To protect the calibration against unauthorised adjustment return to Operator level and makesure that the calibration parameters are hidden. Parameters are hidden using the facility described in Chapter 3.
CALIBRATION POINTS AND CALIBRATION OFFSETS
If you wish to see the points at which the User calibration was performed and the value of theoffsets introduced these are shown in Configuration, under . The parameters are:
Name Parameter description Meaning
User low calibration point This is the value (in display units) at which a Userlast performed an (adjust low calibration).
User high calibration point This is the value (in display units) at which a Userlast performed an (adjust high calibration).
Low point calibration offset Offset, in display units, at the user low calibrationpoint
High point calibration offset Offset, in display units, at the user high calibrationpoint .
Calibrate high point?
Use or to select
Press the Scroll button
Adjust the high point calibration
The controller will display the current measured input value in thelower readout.
Use or to adjust the reading to the reference sourcevalue, if different.After a two second delay the display will blink and the reading willchange to the new, calibrated value.
The calibration is now complete. You can return to the factorycalibration at any time by select in the display shownearlier.
Installation and Operation Handbook Alarm Operation
2208e and 2204e Controller 7-1
Chapter 7 ALARM CONFIGURATIONPAGE
Definition of Alarms and Events ...................................................... 7-2
Types of Alarms ................................................................................ 7-2
Step 1 - Configuring the Four Soft Alarms .................................... 7-5
Step 2 - Attaching an Alarm to a Physical Output .......................... 7-6
Step 3 - Grouping Alarms on a Single Output ................................. 7-7
Step 4 - Removing Alarms from an Output ...................................... 7-7
The 2200e series controllers are capable of very sophisticated alarm strategies and, althoughsetting up of alarms has already been covered in previous chapters, this section has beenincluded to enable operators and commissioning engineers to design their own strategies foroptimum plant operation.
Alarm Operation Installation and Operation Handbook
7-2 2208e and 2204e Controller
DEFINITION OF ALARMS AND EVENTS
Alarms are used to alert an operator when a pre-set level or condition has been exceeded.They are normally used to switch an output - usually a relay - to provide interlocking of themachine or plant or external audio or visual indication of the condition.
Soft Alarms are indication only within the controller and are not attached to an output (relay).Events - can also be alarms - but are generally defined as conditions which occur as part of thenormal operation of the process. They do not generally require operator intervention.
Events are referred to as Digital Output Functions in the manual (see Table B, page 5-13).For the purposes of the operation of this instrument alarms and events can be consideredthe same.
TYPES OF ALARMS
The use of alarms in the 2208e and 2204e controllers is extremely versatile.Up to 4 alarms can be configured. Any combination of these 4 alarms can be attached to anyone or more outputs, or any number of the available soft alarms can be combined to operatea single output.
Note: In a three term controller at least one of these outputs is used to maintainthe required temperature of the process.
Outputs 1A and 2A Are plug in modules.Normally used for control outputs, eg. Heat and Cool, but canbe used for alarm outputs.
Outputs AA and 3A Are fixed relays.Normally used for alarms or events, but can be used as controloutputs.
10A Output 4A (2204e 0nly) Is a plug in 10 Amp relay output.Normally used to switch heaters directly in control mode, butcan be used as an alarm output.
NOTE
Installation and Operation Handbook Alarm Operation
2208e and 2204e Controller 7-3
There are seven process alarm types listed below. Alarm Types are found in configurationmode under the Alarm Config. List.
ALARMS
Full Scale High The PV exceeds a set high level
Full Scale Low The PV exceeds a set low level
Deviation Band The difference between PV & SP is outside a set band
Deviation High The difference between PV & SP is higher than a set level
Deviation Low The difference between PV & SP is lower than a set level
High Current The measured current returned from a PDSIO slave is higher than aset level
Low Current The measured current returned from a PDSIO slave is lower than aset level
Each alarm can be set to:
Latching Alarm is indicated until acknowledged(Off, Auto, MAN)
Auto Acknowledge: ( )If the alarm is acknowledged while the alarm condition is stillpresent, it will cause the alarm to reset as soon as the alarmcondition is removed.
Manual Acknowledge: ( )If the alarm is acknowledged while the alarm condition isstill present, it will be ignored. A further acknowledgementis required when the alarm condition has been removed tocause the alarm to reset.
Blocking Alarm occurs after it has been through a start up phase not in alarmcondition.
Sense Of Output Relay energised or de-energised in alarm condition.
Alarm Operation Installation and Operation Handbook
7-4 2208e and 2204e Controller
In addition there are nine digital output functions used as events or alarms depending uponthe requirements of the process under control:
DIGITAL OUTPUT FUNCTIONS
Sensor Break` The input is open circuit
Loop Break The controller does not measure a response to anoutput change
Load Failure Used with PDSIO Mode 1 load failure
Manual Controller in manual mode
PV Out Of Range Process Variable too high or too low
Remote SP Fail No signal measured at the remote set point input terminals
Heater Fail Used with PDSIO Mode 2 heater open circuit
SSR Fail Used with PDSIO Mode 2 solid state relay open or shortcircuit
Program END Signals the end of a program
New Alarm Signals a new alarm
The Sense of the Output can be set to relay energised or de-energised in the alarm conditionfor any of the above functions.
Installation and Operation Handbook Alarm Operation
2208e and 2204e Controller 7-5
STEP1 - CONFIGURING THE FOUR SOFT ALARMS
Go To Configuration LevelRefer to Chapter 5
Press PAGE keyas many times as necessaryto find Alarm Configuration
Press SCROLL keyto the alarm which needs tobe configured
Alarm Type choicesare
OFF Full Scale Low Full Scale High deviation Band deviation High deviation low
Low current High current
Press SCROLL keyto choose alarm 1 latchingor non-latching
Choices No/Auto/Man Press
Press SCROLL keyto choose alarm 1 blocking
Choices Yes/No press
Press SCROLL keyto repeat for alarms 2 - 4to return to list header
Figure 7.1
Alarm Operation Installation and Operation Handbook
7-6 2208e and 2204e Controller
STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUTThis may be necessary if:1. The instrument has been supplied un-configured or it is required to re-configure2. Alarm relays are added
Press PAGE keyas many times as necessaryto find AA Configuration
Press SCROLL keyto identification of outputtype (this is read only)
Press SCROLL keyto output Function
Use or to select Other choices are:1. 2. 3.
Use or buttons toselect a desired digital function,e.g., . Other choices areshown in the table on the nextpage. After two seconds, thedisplay will blink and return tothe (no change) display.Use the arrows again to scrollthrough the function list. Thepreviously selected function willshow 2 decimal pointsindicating that it has beenadded to the output, i.e., .
Use orto select:1. inverted (relay de-energised
in alarm)2. direct (relay energised in
alarm)
Press SCROLL keyto digital output function
Keep pressing SCROLLbutton to return to list header
Figure 7.2
Installation and Operation Handbook Alarm Operation
2208e and 2204e Controller 7-7
STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT
In the previous example one alarm condition is allocated to one output relay.
The 2208e and 2204e controllers allow alarms and events to be grouped on to a single output.These events are shown in the table below.
No change
Clear all existingfunctionsAlarm 1*Alarm 2*Alarm 3*Alarm 4*
* See Table B page 5-13
Figure 7.3
STEP 4 - REMOVING ALARMS FROM AN OUTPUT
Figure 7.4
!
!
Press until you reach the1stsoft alarm you wish to attach toan output, e.g., . The displayreturns to no change after 2 sec.accepting the condition.
Press until you reach the2nd soft alarm you wish to attach tothe output, e.g., !. The displayreturns to no change after 2 sec.accepting the condition.
Repeat for all alarms to beattached to the chosen output
Press once to show clearAfter 2 sec. the lower readoutreverts to no change clearing allevents from the chosen output.
Each time you scroll through thetable of alarms, note that 2decimal points appear confirmingacceptance that the particularalarm has been attached to theoutput, i.e., , !, etc.
Installation and Operation Handbook Understanding the Ordering Code
2208e and 2204e Controller A-1
Appendix AUNDERSTANDING THE ORDERING CODEThe 2208e and 2204e controllers have a modular hardware construction with the option offour outputs and one communications port. Two logic inputs are provided as standard. Inaddition the Model 2204e has an optional plug-in 10A heating output.
The ordering code is in two parts: the hardware code followed by the software code. Thehardware code specifies the hardware build of the controller, and the software code thesoftware configuration. The software code is optional.
UK Default USA DefaultType KT/C 0 to 1000C Type JT/C 32 to 2192F
Hardware code Software code
Model Output 1 Comms DisplayNumber Language units
Supply Output 2 ManualVoltage Sensor
Output 3 input
Rangemin
RangeMax Options
Function
Figure A.1
Understanding the Ordering Code Installation and Operation Handbook
A-2 2208e and 2204e Controller
Hardware code
Modelnumber
Function Supplyvoltage
Output1
Output2
OutputAA
Output3
10Aoutput
Comms Manual DefaultSettings
2208e2204e CC VH LH RC FL FH XX 2YM ENG
AO-AmericanEO-European
Supply voltageVH 85-264Vac
Output 1XX NoneRelay: 2-pinR1 UnconfiguredRU VP raise O/PRH PID heatingFH High alarm 1FL Low alarm 1DB Deviation band 1DL Low dev. alarm 1DH High dev alarm 1Logic: non-isolatedL1 UnconfiguredLH PID heatingM1 PDSIO mode 1(1)M2 PDSIO mode 2(1)TriacT1 UnconfiguredTH PID heatingTU VP raise O/PDC control -isolatedD3 UnconfiguredH6 0-20mA PIO heatingH7 4-20mA PID heatingC6 0-20mA PID coolingC7 4-20mA PID cooling
Output 2XX NoneRelay: 2-pinR1 UnconfiguredRW
VP lower O/P
RC PID coolingFH High alarm 2FL Low alarm 2DB Deviation band 2DL Low dev. alarm 2DH High dev alarm 2Logic: non-isolatedL1 UnconfiguredLC PID coolingTriacT1 UnconfiguredTC PID coolingTW VP lower O/P
Output 3(3)XX NoneRF UnconfiguredRH PID heatingFH High alarm 4FL Low alarm 4DB Deviation band 4DL Low dev. alarm 4DH High dev alarm 4LF PDSIO load failHF PDSIO heater failSF PDSIO SSR failRC PID cooling
FunctionCC ControllerVC Valve
PositionerNF On/Off
Comms2XX None2-wire EIA-4852YM Modbus2YE EI Bisynch4-wire EIA-4222FM Modbus2FE EI BisynchEIA-2322AM Modbus2AE EI BisynchPDSIO input2M4 Fitted unconfig.2RS Setpoint input2NS Nonstandard
Output AA(3)XX NoneRF UnconfiguredRH PID heatingFH High alarm 3FL Low alarm 3DB Deviation band 3DL Low dev. alarm 3DH High dev alarm 3LF PDSIO load failHF PDSIO heater failSF PDSIO SSR failRC PID cooling
10A outputXX NoneR5 fitted unconfiig.RH PID heating
ManualXXX No manualENG EnglishFRA FrenchGER GermanITA Italian
Installation and Operation Handbook Understanding the Ordering Code
2208e and 2204e Controller A-3
Software code
Sensor input Range min Range max Units Logic input1
Logic input2
Options
K 0(note 2)
1000(note 2)
C XX XX CF
Sensor input Range Min Range MinStandard sensors Min C max Min F maxJ J thermocouple -210 1200 -340 2192K K thermocouple -200 1372 -325 2500T T thermocouple -200 400 -325 750L L thermocouple -200 900 -325 1650N N thermocouple -200 1300 -325 2370
R R thermocouple -50 1768 -58 3200S S thermocouple -50 1768 -58 3200B B thermocouple 0 1820 32 3310P Platinel II thermple 0 1369 32 2496C *C thermocouple
W5%Re/W26%Re(Hoskins)
0 2319 32 4200
Z RTD/PT100 -200 850 -325 1562Custom sensors (*replaces C thermocouple)D W3%Re/W25%Re 0 2399 32 4350E E thermocouple -200 1000 -325 18301 Ni/Ni18%Mo 0 1399 32 25502 Pt20%Rh/Pt40%Rh 0 1870 32 33983 W/W26%Re
(Englehard) 0 2000 32 3632
4 W/W26%Re(Hoskins)
0 2010 32 3650
5 W5%Re/W26%Re(Englehard)
10 2300 50 4172
6 W5%Re/W26%Re(Bucose)
0 2000 32 3632
7 Pt10%Rh/Pt40%Rh -200 1800 392 3272Linear inputs Min MaxF -100 to +100mV -999 9999Y 0 to 20mA -999 9999A 4 to 20ma -999 9999W 0 to 5Vdc -999 9999G 1 to 5Vdc -999 9999V 0 to 10Vdc -999 9999
OptionsAdd as many options asrequiredControl optionsDP Direct acting PIDHeating optionPD Power feedback
disabledCooling optionsXX Linear coolingCF Fan coolingCW Water coolingCL Oil cooling
Logic inputs 1 & 2XX DisabledAM Manual mode selectSR Remote setpoint selectS2 Second setpointEH Integral holdAC Alarm acknowledgeSB Standby mode
UnitsC CentigradeF FahrenheitK KelvinX Blank
Understanding the Ordering Code Installation and Operation Handbook
A-4 2208e and 2204e Controller
Notes:
1. PDSIO is a proprietary technique developed by Eurotherm for bi-directionalcommunication over a single pair of wires. There are several operating modes.
In SSRx Load Doctor a logic output delivers a power demand signal to a TE10 solidstate (SSR) relay and the SSR responds with a single load circuit failure message.
In SSRx Enhanced Load Doctor a logic output delivers a power demand signal to anSSR and the SSR responds with the ON state rms load current, and two fault messages -SSR failure or heater circuit failure.
2. Range min and Range max: Enter a numeric value, with a decimal point if required.Thermocouple and RTD sensor inputs will always display over the full operating rangeshown in the sensor input table. The values entered here will act as limits for the setpointhigh and low limit parameters and for alarm setpoints.
3. Alarms are normally supplied configured as non-latching and de-energised-in-alarm, butthey can be configured as latching, energised-in-al