HCMC PC SPECIFICATION THREE PHASE TRANSFORMER LOSS MEASUREMENT SYSTEMS I. SCOPE :  This specification covers the supply of Three phase  Transformer Loss Measurement System II. STANDARD OF MANUFACTURE AND TEST :  The equipment shall conform to the latest edition of the appropriate IEC standards and/or other international standards. III. DESCRIPTION : 1. Functi on of equipment : -  The Three phase Transformer Loss Measurement System (TLMS) measures Losses of distribution transformers (Rated up to 2500 kVA three phase, with up to 7 % impedance at full kVA) quickly and accurately. -  TLMS is capable of measuring the following data in accordance with IEC 76 Standard : Excitation current, core losses (No load lo ss) , Coppe r losses, Imped ance volt age, temperature. 2. Technical specification : Measurement Principle : Three-wattmeter or two wattme ter met hod of measurement. By the dat a acquis iti on system ,TLMS acqui res and records data fr om al l of di gi tal meters of TLMS, normalizes the data to standard temperature conditions, perform the calculations to obtain the derived data according to IEC 76 Standard and enters the data into a data file....,produces test report Output : - For Losses Measurement : + Three phase 50 Hz + Voltage max : 1600 V + Current max : 100A - For Induced overvoltage Test : + Three phase 200 Hz + Voltage : 800V Instruments : Digital meters for output voltage, current, losses and temperature /var/www/apps/conversion/tmp/scratch_1/139052687.doc 1/6

12 Trans Loss

Embed Size (px)

Citation preview

7/28/2019 12 Trans Loss

http://slidepdf.com/reader/full/12-trans-loss 1/6

HCMC PC SPECIFICATION

THREE PHASE TRANSFORMER LOSS

MEASUREMENT SYSTEMS

I. SCOPE :

 This specification covers the supply of Three phase Transformer Loss Measurement System

II.STANDARD OF MANUFACTURE AND TEST :

 The equipment shall conform to the latest edition of theappropriate IEC standards and/or other international standards.

III. DESCRIPTION :

1. Function of equipment :-  The Three phase Transformer Loss Measurement System

(TLMS) measures Losses of distribution transformers (Ratedup to 2500 kVA three phase, with up to 7 % impedance atfull kVA) quickly and accurately.

-  TLMS is capable of measuring the following data inaccordance with IEC 76 Standard : Excitation current, corelosses (No load loss), Copper losses, Impedance voltage,temperature.

2. Technical specification :• Measurement Principle : Three-wattmeter or twowattmeter method of measurement. By the data acquisitionsystem ,TLMS acquires and records data from all of digitalmeters of TLMS, normalizes the data to standard temperatureconditions, perform the calculations to obtain the derived dataaccording to IEC 76 Standard and enters the data into a datafile....,produces test report

• Output :- For Losses Measurement :

+ Three phase 50 Hz+ Voltage max : 1600 V+ Current max : 100A

- For Induced overvoltage Test :+ Three phase 200 Hz+ Voltage : 800V

•Instruments : Digital meters for output voltage, current,losses and temperature

/var/www/apps/conversion/tmp/scratch_1/139052687.doc 1/6

7/28/2019 12 Trans Loss

http://slidepdf.com/reader/full/12-trans-loss 2/6

HCMC PC SPECIFICATION

THREE PHASE TRANSFORMER LOSS

MEASUREMENT SYSTEMS

• Accuracy : ± 0.5% reading

• Operation :- Power supply : Three phase 380 V ± 10%, 50Hz- Environmental :

+ Operating : 0 to 40o C, R.H. to 80%+ Storage : -40 to 65oC

- Duty Cycle :+ Continuous at 50% of the rating+ 5 min on, 15 min off at rated kVA range

IV. REQUIREMENT OF TECHNICAL DOCUMENTSUBMITTED WITH THE QUOTATION :

-  Technical description, data sheet, catalogues and othermaterial submitted with the quotation must enable thePurchaser to thoroughly evaluate the proposals as to itscompliance with the inquiry specification.

- Minimum requirements :

+ Detail summary of deviations to the inquiryspecification.

+ Completed inquiry datasheet expressed at section V.+ Catalogues containing outline dimension, technical

data…+ List of main equipment and completed accessorieswhich can perform all function described in section IIIhave the following requirements :

. Individual cost of main equipment and each accessory

. Total cost of main equipment and completed accessory

. Manufacture’s code of main equipment and eachaccessory

+ Connection diagram.+ Certificate of quality management.

V. REQUIREMENT OF DOCUMENT INCASE OF BID

WINNING :

/var/www/apps/conversion/tmp/scratch_1/139052687.doc 2/6

7/28/2019 12 Trans Loss

http://slidepdf.com/reader/full/12-trans-loss 3/6

HCMC PC SPECIFICATION

THREE PHASE TRANSFORMER LOSS

MEASUREMENT SYSTEMS

1. Documents required to be provide for commission :

In order to ensure the quality of supplied goods, in case of bidwinning, the Tenderer shall supply the following documents forthe Purchaser :

- Manufacturer’s Certificate of Quality.- Certificate of Origin issued by Chamber of Commerce of the manufacturing country.- Certificate of calibration of equipment approved by anindependent lawful organization.

2. Documents required to be provide in accompany withsupplied products :

 The Supplier shall enclose the following documents for suppliedproducts :

- 01 catalog- 01 instruction manual of installation, operation and

maintenance.

VI. REQUIREMENT OF INSTALLATION AND INSTRUCTION

FOR USE :

 The Supplier shall ensure to supply the following service :- Installation the equipment completely.- Instruction to Purchaser’s staff how to use this equipmenton site.-  Trial run this equipment.

VII. DATA SHEET :

N DESCRIPTION REQUIREMENT QUOTE

D

1. Manufacturer2. Country of origin3. Manufacture ′s code

4. Standard of manufactureand test

5. Standard of qualitymanagement

/var/www/apps/conversion/tmp/scratch_1/139052687.doc 3/6

7/28/2019 12 Trans Loss

http://slidepdf.com/reader/full/12-trans-loss 4/6

HCMC PC SPECIFICATION

THREE PHASE TRANSFORMER LOSS

MEASUREMENT SYSTEMS

6. Supply of the certificate of 

quality management7. In case of bid winning, the

 Tenderer shall supply thefollowing documents for thePurchaser :- Manufacturer’s Certificateof Quality.- Certificate of Origin issuedby Chamber of Commerce of 

the manufacturing country.- Certificate of calibration of equipment approved by anindependent lawfulorganization.

 Yes Yes

 Yes

8. List of main equipment andcompleted accessories metall requirements of sectionIV is supplied in tender

proposal.

 Yes

9. Quoted main equipment andcompleted accessoriesdescribed in above list canperform all functiondescribed in section IIIwithout addition of othernecessary materials.

 Yes

10. The Supplier shall ensure to

supply the following service :- Installation the equipment

completely.- Instruction to Purchaser’s

staff how to use thisequipment on site.

-  Trial run this equipment.

 Yes

 Yes

 Yes

11. Function of equipment -  The Three phase Transformer Loss

MeasurementSystem (TLMS)

/var/www/apps/conversion/tmp/scratch_1/139052687.doc 4/6

7/28/2019 12 Trans Loss

http://slidepdf.com/reader/full/12-trans-loss 5/6

HCMC PC SPECIFICATION

THREE PHASE TRANSFORMER LOSS

MEASUREMENT SYSTEMS

measures Losses

of distributiontransformers(Rated up to 2500kVA three phase,with up to 7 %impedance at fullkVA) quickly andaccurately.

-  TLMS is capable of 

measuring thefollowing data inaccordance withIEC 76 Standard :Excitation current,core losses (Noload loss), Copperlosses, Impedancevoltage,

temperature. Technical specification12. Measurement Principle Three-wattmeter or

two wattmetermethod of  measurement. Bythe data acquisitionsystem ,TLMSacquires and records

data from all of  digital meters of  TLMS, normalizes thedata to standardtemperatureconditions, performthe calculations toobtain the deriveddata according to IEC76 Standard andenters the data into

/var/www/apps/conversion/tmp/scratch_1/139052687.doc 5/6

7/28/2019 12 Trans Loss

http://slidepdf.com/reader/full/12-trans-loss 6/6

HCMC PC SPECIFICATION

THREE PHASE TRANSFORMER LOSS

MEASUREMENT SYSTEMS

a data

file....,produces testreport

13. Output :- For Losses Measurement

- For Induced overvoltage Test :

+ Three phase 50Hz

+ Voltage max :1600 V

+ Current max :100A

+ Three phase 200Hz

+ Voltage : 800V14. Instruments Digital meters for

output voltage,current, losses and

temperature15. Accuracy ± 0.5% reading

16. Operation- Power supply

- Environmental+ Operating+ Storage

- Duty Cycle

 Three phase 380 V ±

10%, 50Hz

0 to 40o C, R.H. to80%

-40 to 65oC

+ Continuous at 50%

of the rating+ 5 min on, 15 min

off at rated kVArange