37
1/164 PD 08 01 3AM 20060 0001 RJZZA INSTALLATION GUIDE INSTALLATION MANUAL OUTDOOR CABINET LITESPAN-1540 01 02/12/2009 FGM AND / LITESPAN EXCELLENCE CENTER MGM AND / LITESPAN EXCELLENCE CENTER ED DATE CHANGE NOTE APPRAISAL AUTHORITY ORIGINATOR SAD-OUTDOOR INSTAL. MANUAL LITESPAN 1540 FR3 I/T INSTALLATION GUIDE

1. Outdoor C Install

Embed Size (px)

DESCRIPTION

instalación panel oudoor

Citation preview

Page 1: 1. Outdoor C Install

1/164

PD 08 01

3AM 20060 0001 RJZZA

INSTALLATION GUIDE

INSTALLATION MANUAL

OUTDOOR CABINET

LITESPAN-1540

01 02/12/2009 FGM

AND / LITESPAN EXCELLENCE CENTER

MGM AND / LITESPAN

EXCELLENCE CENTER

ED DATE CHANGE NOTE APPRAISAL AUTHORITY ORIGINATOR

SAD-OUTDOOR INSTAL. MANUAL

LITESPAN 1540 FR3 I/T

INSTALLATION GUIDE

Page 2: 1. Outdoor C Install

17/164

PD 08 01

3AM 20060 0001 RJZZA

PEIC: (position 1-right)

One of these boards provides power input and PDH transport interfaces (16xE1) connections. It’s equipped in position 1 of the subrack and it should be always present in all shelves.

POW3-A/B: (position 1-right)

One of these boards provides power input. It’s equipped in position 1 of the subrack and it should be always present in all shelves.

In particular, POW3-B will be equipped when LINA (ADM) is equipped.

For details on ANIT-A and PEIC-POW3-A/B position and switches configuration se document 3AM 20059 0001 RJZZA, Indoor Installations Manual for Litespan 1540 FR3.1.

Regarding POW3-A/B or PEIC PCBs, it should be noted that before extracting it from the subrack ALL other PCBs must be REMOVED.

In particular, if POW3-A/B or PEIC are extracted with NEHC equipped in the subrack, the NEHC could be damaged.

4 LITESPAN-1540 FR3.2 OUTDOOR CONFIGURATIONS

There are several available configurations for the Outdoor Cabinet, depending on the cooling system, on the number of MLS used and on the inclusion or not of an ISAM equipment for Broadband.

4.1 Outdoor Cabinets Cooling System

• With Filtered External Air Exchange:

The cool air gets into the cabinet through some openings provided with filters on the lower part of the Electronics door and moves through the MLS-3F.

This air flux is enhanced by a Fans Tray with 4 axial non stop DC fans over the subrack, which forces it inside the double roof and then to the outside environment. The output has also filters

This fan tray can be the Litespan 3AM 20071 BGAA or else another fan tray with similar functionality, with 4 axial non stop fans.

The filters and the non-stop fans warrant the IP-55 condition in the inside of the Electronics. Compartment.

Adequate baffles are located inside the cabinet for guiding the air fluxes and thus enhancing the global thermal performance.

A thermostat is provided in each fans tray for activating the alarms in the case of excessive temperature or fans failure.

Fans stop when heaters are on, until working temperature reaches the minimum required for electronics (+ 5 ºC).

In battery area, no specific cooling actions are required.

Page 3: 1. Outdoor C Install

18/164

PD 08 01

3AM 20060 0001 RJZZA

4.2 Types of Cabinets

4.2.1 1 MLS Outdoor Cabinet configuration

Cabinet code Cooling System MLS Type Line Card Ner of Subscribers

3AM 20190 AA Filtered External Air Exchange

MLS_3F 20 LC / 48 Subscr. 960

Table 2. 1 MLS Outdoor Cabinet configuration

4.2.2 2 MLS Outdoor Cabinet configurations

Table 3. 2 MLS Outdoor Cabinet configurations

5 1 MLS OUTDOOR CABINET: FILTERED EXTERNAL AIR EXCHANGE

It's an outdoor IP-55 cabinet, except in battery area, equipped with an MLS_3F subrack with up to 960 subscribers, grouped in 48 subscribers per slot, along with its Powering System, Transmission System, MDF, ODF and batteries.

The ODF is prepared for up to 12 fibers with connectors type SC/XXX or E2000/APC or 24 fibers with connectors type LC.

The MDF has Reichle & De Massari disconnection strips in Primary side and connection strips in Secondary side, both for 960 subscribers.

The Powering System can be Xcend, Aspiro 1U or 2U from Power-One.

The maximum external dimensions of the cabinet are, roof included: 1465 x 1605 x 600 (W x H x D). (Roof included). And the weight of the cabinet, equipped, is roughly 180 Kg.

5.1 Internal Distribution

The cabinet includes three areas to house the following equipment:

I. Electronics area

• MLS_3F

• AC power subsystem, from Mains to -48V, including:

- AC/DC converter, including cold start control, battery controller and batteries temperature sensor: Power-One Aspiro 1U or 2U Power shelf, 3AM 20191 XA with up to 4 converters 3AM 20202 AX or Xcend 3AM 19867 AAAA.

- Electrical Protections Frame, protections and other control equipment.

Cabinet code Cooling System MLS Type Line Card Ner of Subscribers

3AM 20185 AA Filtered External Air Exchange

MLS_3F + MLS_3F 40 LC / 48 Subscr. 1920

3AM 20185 BA Filtered External Air Exchange

MLS_3F + ISAM 7330 FD

20 LC / 48 Subscr. + 10 LC 48 Subscr.

1440

Page 4: 1. Outdoor C Install

19/164

PD 08 01

3AM 20060 0001 RJZZA

The AC/DC is designed to be powered from Mains AC (230 Vac), providing secondary power to the MLS, as well as to the heating and cooling control equipment which are also required in the cabinet.

See Chapter 0.

The Electrical Protections Frame includes the elements listed below:

- 2 Overvoltage protection devices class C, with auxiliary contacts, between line and neutral and between neutral and ground. (VmaxAC/DC=320/420V, In=20 kA, Imax=40kA, tA<25ns, short circuit 25kA/50Hz)

- 1 relay 230 V, providing an alarm, upstream the differential breaker,

- 1 differential breaker class A for the complete equipment (40 A) (with 2P and a sensitivity of 30mA)

- 1 breaker for the AC/DCs (32 A) (C curve type, 6kA, 2P)

- 1 breaker for auxiliary socket (6 A) (C curve type, 6kA, 2P)

- 1 socket for powering auxiliary equipment (16A)

• Cooling equipment

Fans tray – 4 fans: 535 x 195 x 50 mm (WxDxH). ETSI fixing.

This fan tray can be the Litespan 3AM 20071 BGAA or else another fan tray with similar functionality with 4 axial non stop fans.

- Optional elements in Electronics area:

• Heating equipment, code: 3AM 20211 AAAA

• High temperature sensor, code: 3AM 20241 AAAA

Litespan 1540 items included in electronic area are specified for a working temperature above –10ºC. In order to comply with environmental condition classes, optionally, especially for class 4.1E, the use of heaters inside the electronic area is required.

These heaters will be activated below +10ºC in the electronics area and disconnected over +10ºC, by means of an adequate thermostat.

A thermostat adjusted at –20ºC guarantees the disconnection of the AC/DC below that temperature.

• Humidity sensor, Code: 3AM 20204 AAAA.

II. Interconnection area

In this area the MLS connectors are connected via cabling to the MDF - “primary” side, while the external cabling is connected to the MDF - “secondary”.

• MDF with Primary and Secondary sides

Connection strips are mounted on a fixed system, to overcome the problem of moving a big amount of cabling.

Room has been foreseen in the cabinet for several types of connection strips: R&M, Alcatel-Lucent, 3M SID-C, 3M STG type, Krone-LSA PLUS, Krone PROFIL.

For each RSA code its particular MDF kit contains the connections strips and their support.

Primary side: It has a capacity of 960 subscribers, equipped in disconnecting type strips. These ones are prepared for receiving overvoltage protections.

Secondary side: The relation between subscribers in Primary and Secondary is normally 1:1, and up to 1:1,3 when possible, depending on the volume of the strips equipped. Strips in this side can be connection type only.

• ODF

ODF device is capable of handling a minimum of 12 fibers.

The ODF is prepared for receiving SC/APC, SC-PC (for up to 12 fibers) or LC adaptors (for up to 24 fibers.

Page 5: 1. Outdoor C Install

20/164

PD 08 01

3AM 20060 0001 RJZZA

The possibility of E2000 or FC-PC adaptors (not included) will be on customer request.

• Cables entry

- Optional elements:

• Flooding sensor, Code: 3AM 20205 AAAA.

• Smoke sensor, Code: 3AM 20203 AAAA.

No specific heating actions are required under normal operating conditions, provided that suitable equipment for specified environmental class is used.

III. Battery area

• Battery pack

Batteries will provide a minimum of 10 hours of backup. For the maximum configuration expected in the cabinet, the requirement for the batteries is at least 78 A/h.

They will be AGM type.

Depending on the allocation of the batteries in the dedicated area, two configurations are possible:

Configuration A: 4 batteries on each tray (1 removable tray+ 1 fixed tray) (8 units)

Configuration B: 2 lain batteries on each tray (3 removable + 1 fixed) (8 units)

Configuration C: 8 batteries on one fixed tray (8 units)

Page 6: 1. Outdoor C Install

27/164

PD 08 01

3AM 20060 0001 RJZZA

3 2 DIN-6798 M4 Inox WASHER

4 1 MCD-080422-170 PBA-CONV. 48Vdc – 12Vdc 15A

5 1 MCD-080422-172 PBA SUPPORT

6 7 DIN-7985 M3x8 Inox SCREW

7 7 DIN-6798 M3 Inox WASHER

8 1 MCD-080422-174 COVER

9 L=0,80m CABLE 2X1.5 MM2 SECTION POWER DETECTOR TO COVERTER

10 L=0,80m CABLE 2X0.22 MM2 SECTION ALARM DETECTOR TO CONN. STRIPS

11 L=3,0 m CABLE 2X1.5 MM2 SECTION POWER CONN. CONV. TO MAINS (48Vdc)

12 1 MCD-980907-63 LABEL ENERGY HAZARD

Table 13. 1 & 2 MLS Outdoor Cabinet: Smoke Detection elements (Optional)

Figure 11. 1 MLS Outdoor Cabinet: Smoke Detection Elements (Optional)

6 2 MLS OUTDOOR CABINET: FILTERED EXTERNAL AIR EXCHANGE

It's an outdoor IP-55 cabinet, except in battery area, equipped with two possible configurations:

• Configuration 1:

Litespan MAIN: MLS-3F, 960 subscribers

Litespan EXTENSION: MLS-3F, 960 subscribers

with up to 1920 subscribers in MDF - Primary, grouped in 48 subscribers per subrack slot, along with its Powering System, Transmission System, MDF, ODF and batteries.

• Configuration 2:

Litespan MAIN: MLS-3F, 960 subscribers

ISAM: 7330 FD

with up to 1920 subscribers in MDF - Primary, grouped in 48 subscribers per Litespan subrack slot, along with its Powering System, Transmission System, MDF, ODF and batteries.

The ODF is prepared for receiving SC/APC, SC-PC (for up to 12 fibers) or LC adaptors (for up to 24 fibers.

The MDF has Reichle & De Massari disconnection strips in Primary side and connection strips in Secondary side, both for 1920 subscribers.

The Powering System can be Xscend, Aspiro 1U or 2U from Power-One.

The maximum external dimensions of the cabinet are, roof included: 2520 x 1550x 600 (W x H x D). (Roof included). See Figure 12.

And the weight of the cabinet, equipped, is roughly 450 Kg.

Depending on the batteries area distribution, configurations type A and B exist. See Chapter 6.2.1.

Page 7: 1. Outdoor C Install

28/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 12. 2 MLS Cabinet Main Dimensions

Page 8: 1. Outdoor C Install

29/164

PD 08 01

3AM 20060 0001 RJZZA

MLS-MAIN MLS-EXT

OR

ISAM 7330

ADM AC/DC ELECTRICAL

PROTECTIONS

FRAME

SWITCHES THIRD PARTY ODF MDF

Figure 13. 2 MLS Cabinet

6.1 Power Requirements

Maximum power consumption and dissipation foreseen, located in electronics area:

• DC Power consumption (incl. Fans and 3rd party equipment), @ 48Vdc <1450W

• AC Power consumption, @ 230Vac <1600W

In each particular installation, the Max DC and Max AC should be calculated as a function of the foreseen configuration.

The DC Power Supply unit is designed as N+1 redundancy. N is the number of rectifier modules whose total capacity is enough for powering all DC loads and to charge the batteries. See chapter 7.

Power dissipation for thermal management <1500W, distributed in the two electronics areas (max 750W each)

Voltage fluctuation in Mains: 230 V ± 10% according to standard EN50160 Power Quality Standard.

6.2 Internal Distribution

6.2.1 Litespan MLS-3F + MLS-3F Configuration See Figure 13.

The cabinet includes three areas to house the following equipment:

Page 9: 1. Outdoor C Install

30/164

PD 08 01

3AM 20060 0001 RJZZA

I. Electronics area (left & central doors)

• 2 x Litespan MLS_3F

• AC power subsystem, from Mains to -48V, including:

• AC/DC converter, including cold start control, battery controller and batteries temperature sensor: Power-One Aspiro 1U or 2U Power shelf, 3AM 20191 XA with up to 3 converters 3AM 20202 AX or Xcend 3AM 19867 AAAA. See Chapter 0.

• Electrical Protections Frame, with protections and other control equipment. See chapter 6.2.2.

• ADM 1642 EM

• Cooling equipment

Fans tray – 4 fans: 535 x 195 x 50 mm (WxDxH). ETSI fixing.

This fan tray can be the Litespan 3AM 20071 BGAA or else another fan tray with similar functionality with 4 axial non stop fans.

Optional elements in Electronics area:

• Heating equipment, code: 3AM 20211 ABAA

Litespan 1540 items included in electronic area are specified for a working temperature above –10ºC. In order to comply with environmental condition classes, optionally, especially for class 4.1E, the use of heaters inside the electronic area is required.

These heaters will be activated below +10ºC in the electronics area and disconnected over +10ºC, by means of an adequate thermostat.

A thermostat adjusted at –20ºC guarantees the disconnection of the AC/DC below that temperature.

• Humidity sensor, Code: 3AM 20204 AAAA

• Ethernet Switch from 3rd Party

• ODF from 3rd Party

II. Interconnection area (right door)

In this area the MLS connectors are connected via cabling to the MDF - “primary” side, while the external cabling is connected to the MDF - “secondary”.

• MDF with Primary and Secondary sides

Connection strips are mounted on a fixed system, to overcome the problem of moving a big amount of cabling.

Room has been foreseen in the cabinet for several types of connection strips: R&M, Alcatel-Lucent, 3M SID-C, 3M STG type, Krone-LSA PLUS, Krone PROFIL.

For each RSA code its particular MDF kit contains the connections strips and their support.

Primary side: It has a capacity of 1920 subscribers, equipped in disconnecting type strips. These ones are prepared for receiving overvoltage protections.

Secondary side: The relation between subscribers in Primary and Secondary is normally 1:1, and up to 1:1,3 when possible, depending on the volume of the strips equipped. Strips in this side can be connection type only.

• ODF supplied with the cabinet

The ODF is prepared for receiving SC/APC, SC-PC (for up to 12 fibers) or LC adaptors (for up to 24 fibers.

The possibility of E2000 or FC-PC adaptors (not included) will be on customer request.

According to the selected model, there are several available kits with their respective connections from the equipment to the ODF device:

Page 10: 1. Outdoor C Install

31/164

PD 08 01

3AM 20060 0001 RJZZA

KITS ADM ODF DESCRIPTION

3EC 40406 ABAA LC/PC SC/PC SET (ADM –ODF): 3 CABLES & 5 TRANSITIONS

3EC 40406 BBAA LC/PC SC/PC SET (ADM –ODF): 1 CABLES & 2 TRANSITIONS

3EC 40407 ABAA LC/PC SC/APC SET (ADM –ODF): 3 CABLES & 5 TRANSITIONS

3EC 40407 BBAA LC/PC SC/APC SET (ADM –ODF): 1 CABLES & 2 TRANSITIONS

3EC 41492 ABAA LC/PC FC/PC SET (ADM –ODF): 3 CABLES & 5 TRANSITIONS

3AM 20253 AAAA - LC/PC SET (ODF): 1 DOUBLE TRANSITION

3AM 20253 ABAA - SC/PC SET (ODF): 2 TRANSITIONS

3AM 20253 ACAA - SC/APC SET (ODF): 2 TRANSITIONS

Table 14. Optical Cables & Transitions Kits

Other optical kits could be developed on customer request.

• DDF 75 Ω (up to 8 coaxial cables) (optional), code 3AM 20224 AAAA

• DC Powered Lamps code 3AM 20226 AAAA

• Cables entry

• External Generator Socket

It is a MALE connector 32 A - 230 V. Number of contacts: 2P+Ground.

The access to this socket is permitted only when the cabinet is open but, a system is provided for the outlet of the power cable with the cabinet closed, for operation in emergency conditions.

For switching between normal powering system and emergency powering system a mechanical switch is provided. This switch is a bipolar selector, type ABB E222-4-2 or similar.

Optional elements in Interconnection area:

• Flooding sensor, Code: 3AM 20205 AAAA

• Smoke sensor, Code: 3AM 20203 AAAA

No specific heating actions are required under normal operating conditions, provided that suitable equipment for specified environmental class is used.

III. Battery area (left door)

• 2 strings x 4x12V Battery pack

Batteries will provide a minimum of 10 hours of backup. They are batteries of 12V and a capacity of 125 A/h up to 170 A/h, AGM type.

The AC/DC system always works providing the required power for equipment, and giving the remaining available power to recharge the batteries, assuring the proper charging process.

The frame for the batteries (columns + trays) has two possible configurations, depending on the trays height and the corresponding batteries position, as can be seen hereafter:

2 batteries on the bottom fixed tray and 2 batteries on the removal tray.

Batteries area configuration A:

3 batteries on the bottom fixed tray & 1 horizontal battery on the removable tray that can be fixed at 2/3 height position.

Batteries area configuration B:

2 batteries on the bottom fixed tray & 2 batteries on the removable tray that can be fixed at 1/2 height position.

Batteries which fit with the requirements of the different configurations are listed hereafter:

Page 11: 1. Outdoor C Install

76/164

PD 08 01

3AM 20060 0001 RJZZA

10 Installation of Outdoor Cabinet

This chapter explains the installation procedure for the Litespan-1540 FR3.2 Outdoor Cabinets:

1 MLS code: 3AM 20190 AX equipped with a MLS-3F

2 MLS code: 3AM 20185 XX equipped with 2 x MLS-3F or MLS-3F + ISAM 7330 FD

The installation procedure consists of the following steps:

• Unpacking and Warehousing: See chapter 10.1.3

• Mechanical Installation: See chapter 10.3

• Electrical Connections: See chapter 10.5

• Safety ground connection: See chapter 10.5

• Power supply connection: See chapter 10.5

• Transport signals connection: See chapter 10.5

• External synchronism signals connection: See chapter 10.5

• Subscriber lines connection: See chapter 10.5

• Optical Connections: See chapter 10.6

• Alarms: See chapter 10.8

• Local Management with MLS-3F Subrack: See chapter 10.9

• Optional Equipment management: See chapter 10.10

10.1 Necessary Infrastructure

The cabinet installation requires specific previous works to be executed:

• Specific basement for anchoring

• Mains 230 Vac connection

• Optic Fibers connection on the lower part (if necessary)

• Safety ground bar

• Secondary network cable pairs connection for the external connections towards subscriber lines

10.1.1 Basement 1 MLS Outdoor Cabinet The cabinet is installed over a concrete basement through a metal base where it is fixed.

The location of the cabinet basement must consider some features related to the ventilation:

- The minimum distance between the rear of the cabinet and any possible obstacle, usually a wall, will be 275 mm

- Don't locate it under trees

According to the floor conditions, the basement shall be built with the masonry traditional methods. Next figures show in detail how to make the concrete basement. Over the basement, a metal base will be placed, for fixing the cabinet unto it. See Figure 50.

For warranting the IP-55 of the cabinet, a sealing of the metal base with the cabinet itself is needed. This sealing will be made by means of polyurethane.

For building the basement, see Figure 51, Figure 52 & Figure 53, as an orientation.

Page 12: 1. Outdoor C Install

77/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 50. 1 MLS Outdoor Cabinet: Metal Base

Page 13: 1. Outdoor C Install

78/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 51. 1 MLS Outdoor Cabinet: Basement (I)

Page 14: 1. Outdoor C Install

79/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 52. 1 MLS Outdoor Cabinet: Basement (II)

Page 15: 1. Outdoor C Install

80/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 53. 1 MLS Outdoor Cabinet: Basement (III)

Page 16: 1. Outdoor C Install

81/164

PD 08 01

3AM 20060 0001 RJZZA

10.1.2 Basement 2 MLS Outdoor Cabinet The cabinet is installed over a concrete basement through a metal base where it is fixed.

The location of the cabinet basement must consider some features related to the ventilation:

- The minimum distance between the rear of the cabinet and any possible obstacle, usually a wall, will be 275 mm

- Don't locate it under trees

According to the floor conditions, the basement shall be built with the masonry traditional methods.

Next figures show in detail how to make the concrete basement.

Over the basement, a metal base will be placed, for fixing the cabinet unto it. See Figure 54 & Figure 55.

Two variants of bases can be installed, 3AN 48772 ABAA and BBAA.

• Variant ABAA will be mounted on a Basement TYPE A

• Variant BBAA will be mounted on a Basement TYPE B

The only difference between them, and thus, between the two types of basements, is the hole for the cables entry, as can be seen in next figure.

For the details on the fixing bolts and corrugated rods of the two bases, Figure 55 has been included.

Figure 54. Metal Bases

For warranting the IP-55 of the cabinet, a sealing of the metal base with the cabinet itself is needed. This sealing will be made by means of polyurethane.

For building the basement, see Figure 56, Figure 57, Figure 58, Figure 59 & Figure 60, as an orientation.

Page 17: 1. Outdoor C Install

82/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 55. 2 MLS Outdoor Cabinet: Metal Base Variant ABAA

Page 18: 1. Outdoor C Install

83/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 56. 2 MLS Outdoor Cabinet: Basement TYPE A (I)

Page 19: 1. Outdoor C Install

84/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 57. 2 MLS Outdoor Cabinet: Basement TYPE A (II)

Page 20: 1. Outdoor C Install

85/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 58. 2 MLS Outdoor Cabinet: Basement TYPES A & B (III)

Page 21: 1. Outdoor C Install

86/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 59. 2 MLS Outdoor Cabinet: Basement TYPE B (IV)

Page 22: 1. Outdoor C Install

87/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 60. 2 MLS Outdoor Cabinet: Basement TYPE B (V)

Page 23: 1. Outdoor C Install

88/164

PD 08 01

3AM 20060 0001 RJZZA

10.1.3 Cables Tubes Arrangement: 2 MLS cabinet For the placement of the tubes inside the basement, next recommendations should be followed, in order to prevent interferences between cables tubes and the cable entry edge of the cabinet, and to facilitate the routing of the cables at the inlet plate of the cabinet:

• Respect the forbidden area for tubes indicated in Figure 61 (20 / 20 / 25mm) (only for basement TYPE A)

• Locate Power / Fibers / Ground cables tubes on the left of the cable entry; preferably, ground at the front

• Locate Subscribers cables tubes distributed in the rest of the surface of the cable entry. The number of these tubes will depend on the tubes size and the cables size decided for each installation.

As an example, see Figure 62.

Figure 61. Forbidden Area for Cables Tubes in Basement TYPE A

Figure 62. Example of Tubes Layout

10.1.4 Grounding System The required Grounding System Resistance to Ground must have a low value, i. e. less than 10 Ohms according to BS 6651 or BS EN 62305, preferably 8 Ohms or less.

10.2 Instructions for Unpacking and Warehousing

10.2.1 Generalities The unpacking of the equipment must strictly follow the operations described below. As for the packing procedure, if needed, proceed reciprocally. In both cases, the use of the original wrapping materials is preferred.

The external packing frames used for equipment protection will depend on the mechanical and climatic conditions. There can be three types of packing frames:

• WOODEN BOXES: used for ship, plane or road transportation for a period of time more than 60 days

• PLYWOOD BOXES: used for ship, plane or road transportation for a period of time between 30 and 60 days

• CARDBOARD BOXES: used for ship, plane or road transportation for a period of time less than 30 days

Page 24: 1. Outdoor C Install

89/164

PD 08 01

3AM 20060 0001 RJZZA

10.2.2 Unpacking The package must have the following information on the outside:

• International symbols:

This side up

Keep in a dry place

Fragile

• Trademark and address of the manufacturer

• Labels (or other) that must state the consignee and the address of destination

• Packing list

Once the package has been received, the following must be checked:

• The actual address of destination is the same as indicated on the address label

• The package shows no external signs of damage.

For Unpacking procedure follow the steps below:

• Make sure the package was correctly placed during transportation, as indicated by the symbol

• Unwrap the package

• Take out the contents from the box

• Remove the wrapping, bags and other protection stuff

• Remove the dehydrating bags

• Check that the material shows no visible damage and that it is the same as indicated on the annexed shipping list

Note: Any damage shall invalidate the receipt of the package.

10.2.3 Warehousing The following requirements shall apply to store the material:

• Cardboard boxes shall be placed in ventilated areas

• Wooden or plywood boxes can be stored outdoor, whenever they are protected from rain or direct sunlight

10.3 Batteries Operation & Maintenance

For the correct operation and maintenance of the VRLA AGM batteries follow the instructions included hereafter.

10.3.1 Transport Cells and blocs must be transported in an upright position.

Page 25: 1. Outdoor C Install

90/164

PD 08 01

3AM 20060 0001 RJZZA

Batteries without any visible damage are not defined as dangerous goods under the regulations for transport of dangerous goods by road (ADR) or by railway (RID).

They must be protected against short circuits, slipping, upsetting or damaging.

Cells/blocs may be suitable stacked and secured on pallets (ADR and RID, special provision 598). Stapling pallets is prohibited.

No dangerous traces of acid shall be found on the exterior of the packing unit.

Cells/blocs whose containers leak or are damaged must be packed and transported as class 8 dangerous goods under UN no. 2794.

10.3.2 Maintenance and Control For a correct maintenance and control of the batteries, next instructions should be taken into account:

Keep the battery clean and dry to avoid creeping currents.

Plastic parts of the battery, especially containers, must be cleaned with pure water without additives. Never use any additives, acids and/or scourers.

At least every 6 months, measure and record next parameters:

• Battery voltage

• Voltage of several cells/blocs (See Note)

• Surface temperature of several cells/blocs

• Battery-room temperature

Note: If the cell voltage differs from the average float charge voltage by more than +/- 0,5V, or if the surface temperature difference between cells / mono-blocs exceeds 5ºC, service agent should be contacted.

Annual measurement and recording should be made:

• Voltage of all cells / blocs

• Surface temperature of all cells/blocs

• Battery-room temperature

Annual visual check should be made:

• Screw –connections

• Screw -connections without locking devices have to be checked for tightness

• Battery installation and arrangement

• Ventilation

Call a batteries service representative immediately if faults in the battery or the battery charger are found.

Recorded data as described in this chapter must be made available to the service representative.

10.3.3 Storage and Taking Out of Operation To store or decommission cells/blocs for a longer period of time they should be fully charged and stored in a dry frost-free room.

a) The storage location should provide the following functions:

• Shelter the cells / mono-blocs from harsh weather and risk of flooding

• Protect the batteries against any overheating risk induced by direct exposure to the sun radiation or by their amplification through glass walls

• Protect the batteries from any risk of electric shock resulting from short-circuiting by a conductive object or from a building-up of conductive dust

Page 26: 1. Outdoor C Install

91/164

PD 08 01

3AM 20060 0001 RJZZA

• Avoid any risk of mechanical shock caused by dropping objects onto the cell / mono-bloc or by dropping the cell / mono-bloc itself

• Avoid contamination of the lids by dust etc.

b) During storage period, checking the batteries voltage and applying maintenance charges to them is mandatory.

The average storage temperature determines the test and charges intervals:

• 20ºC: 6 months first time. Then, each 3 months.

• 30ºC: 4 months first time. Then, each 2 months.

Higher temperatures storage is not recommended.

In any case, if OCV (Open Circuit Voltage) measurement < 2,07 Vpc, consider a maintenance charge.

To avoid damage, the following general charging methods can be chosen. It is recommended to check for special instructions for each particular battery model.

Equalizing-charge as follows: 2.40Vpc Max. 20-30A / 100Ah depending on batteries model.

24 < t < 48h

The cells / bloc temperature must never exceed 45°C . If it does, stop charging.

Float charging, typically: 2,27Vpc. / 25ºC t > 48h

10.4 Mechanical Installation

The Outdoor Cabinet can be shipped in the following equipping stage:

• Subrack without equipped units

• Without batteries

• All internal cabling and Primary Network pre-connected

The procedure for anchoring the cabinet is as indicated hereafter:

• Open the doors of the cabinet for giving access to the cabinet bottom holes where the studs in the metal plate must be inserted.

• Lift the roof for giving access to the lifting eyes located on the internal part of the roof.

• Lift up the cabinet by means of those eyes on the internal part of the roof, and align the bottom holes with the threaded studs in the metal plate located on the basement.

Lifting Eyes

Figure 63. Outdoor Cabinet: Cabinet Lifting Eyes

Page 27: 1. Outdoor C Install

92/164

PD 08 01

3AM 20060 0001 RJZZA

Once the cabinet has been anchored to the threaded studs:

• Check the proper leveling of the structure, both horizontal and vertical, with a level or plumb line.

• Enter the grounding and power supply cables, the Secondary Network subscribers cables and the fiber optic cables towards the cables entry area, guiding them through the corresponding cable ducts, and fasten them properly.

10.5 Electrical Connections

The equipment has been designed to be directly powered from the external Mains supply (230 Vac).

Whenever any door of an area which contains a part which operates with a harmful voltage or which can be exposed to harmful voltages in the case of failure is open by the user, that potentially harmful part is protected from an eventual contact. The dangerous areas are labeled with an ENERGY HAZARD label.

The connection procedure must follow the sequential steps indicated below:

• Safety ground connection. See chapter 10.5.1

• Power supply connection. See chapter 10.5.4

• Transport signals connection. See chapter 10.5.6

• Subscriber lines connection. See chapter 10.5.7

10.5.1 General Cabling Inlet Rules Cables which are coming inside the cabinet must be led in according to Figure 64.

For keeping the IP Protection degree of the cabinet once the cables are passed through the cones, the cables must be tightly inserted through the plastic cones.

For that, and for each cone,

• the surface of the cone to be cut out must be smaller than the section of the cable to be inserted in it

• if more than one cable are to be inserted through one cone, this tightly insertion must be achieved by using silicone around the cables, for closing the gaps

Page 28: 1. Outdoor C Install

93/164

PD 08 01

3AM 20060 0001 RJZZA

Figure 64. Cabinet Inlet Plate Cables Distribution

Page 29: 1. Outdoor C Install

94/164

PD 08 01

3AM 20060 0001 RJZZA

10.5.2 General Cables Routing Rules As a general rule, the cabling will be guided without obstructing the handling or the viewing of the different cards or devices of the electronics equipment mounted in the cabinet.

The cabling will be also neatly arranged and fixed, so as to minimize the risk of a non-desired disconnection during the normal operation within the cabinet.

The cabinet is provided with several holes for the guiding of the cables between the different areas, Electronics, MDF, ODF, Batteries areas.

Figure 65. Cabling Holes Distribution

Next table shows the suggested allocation of the holes for the different cables which are susceptible of being connected during the installations process.

Page 30: 1. Outdoor C Install

95/164

PD 08 01

3AM 20060 0001 RJZZA

Example:

The Power 230 Vac cable going between outside AC Power Supply and the Power Selector located in the Electrical Protections Frame comes through hole 11 into the MDF area, then comes into Electronics area through hole 23 to the Power Selector.

HOLES DISTRIBUTION IN Figure 65

CABLES START - END START AREA MEDIUM AREA END AREA HOLE

POWER 230 Vac OUTSIDE AC POWER SUPPLY TO POWER SELECTOR

OUTSIDE MDF ELECTRONICS 11 & 23

GENERAL GROUND

OUTSIDE TO GENERAL GROUND STRIP

OUTSIDE - MDF 13

OTHER GROUND CABLES

EQUIPMENT TO GENERAL GROUND STRIP

ELECTRONICS - MDF 22

BATTERIES -48Vdc BATTERIES TO AC/DC BATTERIES - ELECTRONICS 24

BATTERIES +0 Vdc BATTERIES TO AC/DC BATTERIES - ELECTRONICS 24

POWER MLS-1 MLS-1 TO POWER STRIPS IN ELECTRICAL PROTECTIONS FRAME

ELECTRONICS - ELECTRONICS -

POWER MLS-2 OR 7330

MLS-1 OR 7330 TO POWER STRIPS IN ELECTRICAL PROTECTIONS FRAME

ELECTRONICS - ELECTRONICS -

POWER (-A) ADM ADM (–A) TO POWER STRIPS IN ELECTRICAL PROTECTIONS FRAME

ELECTRONICS - ELECTRONICS -

POWER (-B) ADM ADM (-B) TO BREAKERS BOX (RIGHT ETSI COLUMN) ELECTRONICS - ELECTRONICS -

POWER SWITCHES

SWITCHES TO BREAKERS BOX (RIGHT ETSI COLUMN)

ELECTRONICS - ELECTRONICS -

TRANSPORT CABLING MLS-1 OR 7330 TO ADM ELECTRONICS - ELECTRONICS -

INTERNAL FIBERS BETWEEN ELECTRONIC EQUIPMENT

ELECTRONICS - ELECTRONICS -

MDF DOOR ALARM MLS-1 TO MDF DOOR SWITCH ELECTRONICS - MDF 16

BATTERIES DOORS ALARMS

MLS-1 TO BATTERIES DOORS SWITCHES ELECTRONICS - BATTERIES 26

EXTERNAL ALARMS

MLS-1 TO ALARMS AUXILIARY CONN. STRIPS

ELECTRONICS - MDF 16

SUBSCRIBERS OUTSIDE TO MDF OUTSIDE - MDF 1 to 10

SUBSCRIBERS-MLS-1 MLS-1 TO MDF ELECTRONICS - MDF 20

SUBSCRIBERS-MLS-2 OR 7330 MLS-2 OR 7330 TO MDF ELECTRONICS - MDF 20

FIBERS CABLE OUTSIDE TO ODF OUTSIDE - ODF 12

FIBERS ODF TO OPTICAL EQUIPMENT ODF - ELECTRONICS 17

Page 31: 1. Outdoor C Install

96/164

PD 08 01

3AM 20060 0001 RJZZA

DDF CABLE MLS-1 TO DDF ELECTRONICS - MDF 18

BATTERIES HEATERS

BATTERIES HEATERS TO BATT. STRIPS IN ELECTRICAL PROTECTION FRAMES

ELECTRONICS - BATTERIES 25

SMOKE DETECTOR

SMOKE DETECTOR TO POWER STRIPS IN ELECTRICAL PROTECTIONS FRAME

MDF - ELECTRONICS 16

HUMIDITY DETECTOR

HUMIDITY DETECTOR TO ALARMS AUXILIARY CONN. STRIPS MDF - MDF -

FLOODING DETECTOR

FLOODING DETECTOR TO ALARMS AUXILIARY CONN. STRIPS

MDF - MDF -

MDF LAMP MDF LAMP TO POWER STRIPS IN ELECTRICAL PROTECTIONS FRAME

MDF - ELECTRONICS 19

ELECTRONICS LAMP

ELECTRONICS LAMP TO POWER STRIPS IN ELECTRICAL PROTECTIONS FRAME

ELECTRONICS - ELECTRONICS -

Table 29. Cabling Holes Allocation

Holes 14, 15, 19 & 21 in the cabinet are spare.

When the holes are provided with cones for the keeping of the IP-55 protection level, the same rules as in previous chapter apply.

10.5.3 Safety Ground Connection This is the first connection to be made, before any other connection, just after having anchored the cabinet.

Both 1 and 2 MLS outdoor cabinets have a safety ground cable which connects the Power Distribution Frame to the Safety Ground Terminal, located in the MDF area of the cabinet. See Figure 23.

Besides, the outdoor cabinets have another 10 mm2 cable which is connected to the Safety Ground Terminal on one end, and whose other end is to be connected to the Ground Stake located on the concrete basement, or close to it.

10.5.4 Power Supply Connection There are two main parts:

• 230 Vac Mains Power Supply Connection. See chapter 10.5.4.1.

• Batteries Connection. See chapter 10.5.4.2.

10.5.4.1 230 Vac Mains Power Supply Connection

According to EN 50160 – Power Quality Standard, the voltage fluctuation in Mains is 230 V ± 10%.

Proceed as follows:

- Let in the 230 Vac Power Supply cable through the appropriate hole in the base (see Table 29) of the cabinet and guide it to the Electronics area, to be connected to the terminals next to the Power Selector, which switches between the normal power and the Emergency Power.

- Remove the protection cover from the breakers box, located in the electronics area, in order to access the two terminals for power supply cable connection. The safety ground cable coming with the 230 Vac Power Supply cable should be connected to the Safety Ground Terminal in the MDF area of the cabinets.

See Figure 23 & Figure 24.

Page 32: 1. Outdoor C Install

97/164

PD 08 01

3AM 20060 0001 RJZZA

10.5.4.2 Batteries Connection For the battery pack installation, proceed as follows:

• Put the batteries on its support in the battery area of the cabinet

• Connect the cables coming from the Rectifier Unit to the batteries

As an example, document 3EC 44319 0020 BCZZA shows the recommended operation system for batteries 3AM 20221 AMAA in the 2 MLS cabinet.

See Figure 23 & Figure 24.

10.5.5 Insertion Procedure of a Board with a Big Amount of Rear Connectors

Due to the big amount of connectors, and thus a lot of connection pins at the rear of some boards, to be connected at the back panel, special care should be taken during the insertion process of GEB-3B and/or other cards with similar amount of rear connectors.

It is highly recommended to do the process in three steps:

• Do a first insertion of the card with a correct positioning of the extractors in the subrack profiles,

• Press once more over the front face of the extractors

• Check the position of the board

To see whether the board is correctly inserted, check that:

• the leds of the front plate are light,

• the internal face of the front plate is in contact with the front face of the subrack front profiles; see Figure 66

• for the bottom part, the top of the subrack profile must be inserted in the groove of the extractor; see Figure 66

• for the top part, similar situation

• the front face of the extractor is located at right angles with the top face of the cables guide of the front plate, and parallel to the front plate itself; see Figure 66.

SUBRACK LOWER PROFILE

CARD FRONT PLATE

CARD EXTRACTOR

FRONT PLATE &

PROFILE MUST BE IN CONTACT

90°

GROOVE

Figure 66. Insertion Procedure of a Board with a Big Amount of Rear Connectors

Page 33: 1. Outdoor C Install

98/164

PD 08 01

3AM 20060 0001 RJZZA

10.5.6 Transport Signals Connection In Alcatel-Lucent Litespan 1540 FR3.2 the 2 Mbit external connections are provided by:

Narrow Band PDH, provided by PEIC: 16 x 2Mb/s Electrical G.703

Drop & Insert from SHDSL line form SLT3: 4 x 2Mb/s G.703

Additional interfaces for PRA, TDM LL or transport: 8 x 2Mb/s G.703

IMA interfaces from ANITA: 8 x 2Mb/s G.703

LINA (Integrated ADM): Gigabit Ethernet (2 channels from/to front panel) and STM-1 (1 channel from/to front panel SFP) tributaries onto two front panel line/aggregate interfaces, each capable of STM-1/4/16.

The 16 x 2Mb/s G.703 from PEIC will be connected to an ADM, for example, the 1642 EMC, by using a dedicated cable, 3AM 20033 CX.

For asynchronous E1 connections, cable 3AM 20033 DX allows to flexibly connect the ADM 8-14 ports to PEIC and, through the DDF in the cabinet, to SLT3, as follows: 3xE1 to PEIC and 4xE1to SLT3.

At the PEIC front plate, four metral 24 way (6x4) connectors are used which contain, each of them 4 interfaces. Next figure shows Tx/Rx pin disposition on each metral connector.

Rx1P Rx1N

Tx1P Tx1N

Rx2PRx2N

Tx2PTx2N

EG

Rx3P Rx3N

Tx3P Tx3N

Rx4PRx4N

Tx4PTx4N

EG EG EG

EG EG EG EG

RxnP: PEIC 2M Rx active wire

RxnN: PEIC 2M Rx ground wire

TxnP: PEIC 2M Tx active wire

TxnN: PEIC 2M Tx ground wire

EG: Backpannel ground

Figure 67. PEIC E1 (2Mb/s G.703 ) connector

A Digital Distribution Frame (DDF) is foreseen as an optional kit, code 3AM 20224 ABAA, to be mounted in the MDF compartment. See Figure 14 & Figure 28.

10.5.6.1 SFP Modules

ETHERNET SFP MODULES

MODULE TYPE CODE DESCRIPTION

1000BT 3AM20070EA SFP pluggable electrical GE 1000BT module

1000FX 3AM20070AA GE MM SX 850nm -40+85 LC-duplex 550m(7db)

3AM20070AB GE SM LX 1310nm -40+85 LC-duplex10km(11db)

3AM20070AC GE SM EX 1310nm -40+85 LC-duplex 40km(18db)

3AM20070AD GE SM ZX 1310nm -25+85 LC-duplex 80km(24db)

100FX 3AM20070CC FE SM LX 1310nm -with SGMII

3AM20070CA FE MM SX 850nm -40 +85 LC duplex

3AM20070CB FE SM LX 1310nm -40 +85 LC duplex

Page 34: 1. Outdoor C Install

99/164

PD 08 01

3AM 20060 0001 RJZZA

STM SFP MODULES

MODULE TYPE CODE DESCRIPTION

STM1 (ATM) 3AM20070BA STM1 SM 1550nm, -25C to +85C, Duplex LC connector, 80km

STM1 S1.1 3AM20070BC SFP STM1 SHORT S1.1 -40/+85

STM1 L1.1 3AM20070BD SFP STM1 LONG L1.1 -40/+85

STM1 L1.2 3AM20070BH SFP STM1 LONG L1.2 -40/+85

STM4 S4.1 3AM20070BJ SFP STM4 SHORT S4.1 -40/+85

STM4 L4.1 3AM20070BK SFP STM4 LONG L4.1 -40/+85

STM4 L4.2 3AM20070BL SFP STM4 LONG L4.2 -40/+85

STM16 S16.1 3AM20070BE SFP STM16 SHORT S16.1 -40/+85

STM16 L16.1 3AM20070BF SFP STM16 LONG L16.1 -40/+85

STM16 L16.2 3AM20070BG SFP STM16 LONG L16.2 -40/+85

Table 30. SFP Types

The correspondence between each type of SFP and the cards to be used with is shown in next tables:

CODE GIO3 GEB3-B GEB3-A GEBC NTIO-A (SFP ONLY)

NTIO-A (COMBO)

ANIT-A LINA FESC-B

3AM20070EA YES (1)

YES (1) NO YES YES YES -- YES

3AM20070AA YES YES YES YES YES YES -- YES

3AM20070AB YES YES YES YES YES YES -- YES

3AM20070AC YES YES YES YES YES YES -- YES

3AM20070AD YES YES YES YES YES YES -- YES

3AM20070CC NO NO YES (2) NO NO NO -- NO

3AM20070CA NO NO YES NO NO NO -- NO

3AM20070CB NO NO YES NO NO NO -- NO

(1) Only with ethernet cables codes: 3AM19841CX and 3AM20359AX

(2) From FR3.1.32 onwards

Table 31. SFP/Cards Correspondence (I)

CODE GIO3 GEB3-B GEB3-A GEBC NTIO-A (SFPonly)

NTIO-A (COMBO)

ANIT-A LINA FESC-B

3AM20070BA -- -- YES -- -- YES -- --

3AM20070BC -- -- -- -- -- -- YES --

3AM20070BD -- -- -- -- -- -- YES --

3AM20070BH -- -- -- -- -- -- YES --

3AM20070BJ -- -- -- -- -- -- YES --

3AM20070BK -- -- -- -- -- -- YES --

3AM20070BL -- -- -- -- -- -- YES --

3AM20070BE -- -- -- -- -- -- YES --

3AM20070BF -- -- -- -- -- -- YES --

Page 35: 1. Outdoor C Install

100/164

PD 08 01

3AM 20060 0001 RJZZA

3AM20070BG -- -- -- -- -- -- YES --

Table 32. SFP/Cards Correspondence (II)

10.5.7 Craft Terminal Cabling The Craft Terminal cables to be connected between Litespan and the serial port of a PC are:

• For LIOC / GIO3-A: 3AM 19534 AA

• For GEB3-B: 3AM 20012 AB

• For GEBC, GEB3-A, ANIT-A & LINA: 3AM 20051 AA

10.5.8 Ethernet Cabling The Ethernet cables available for Litespan are:

• 3AM 19841 BX (Shielded – Point-to-point)

• 3AM 19841 CX (Shielded – Point-to-point - Earthing prepared)

• 3AM 20359 AX (Shielded – Swapped)

Page 36: 1. Outdoor C Install

101/164

PD 08 01

3AM 20060 0001 RJZZA

10.5.9 External Synchronism When an external clock signal is necessary for synchronizing the E1 links, use cables:

• Between LIOC card and an external MDF or DDF:

3AM 20102 AX (120 Ohm) or 3AM 20368 AX (75 Ohm)

• Between LIOC card and PRC3 card:

3AM 20376 AA

10.5.10 Subscribers Lines Connection

10.5.10.1 Subscriber Cables Inlet The subscribers cables coming through the cabinet inlet plate (see Figure 64) must be fixed at the MDF inlet by using the cable clamps as shown in Figure 68.

The clamps can be adjusted to the incoming cable by means of their screws.

For their screen to be connected with Ground, the cables must have a length without cover. In this way the screen can be pressed by the clamps and then connected with Ground.

Figure 68. MDF Inlet Cables Distribution

10.5.10.2 Subscribers Cables between Litespan and the MDF The whole cabling coming from the Electronics area towards the Main Distribution Frame (MDF) area is provided already wired up from the factory, therefore the equipment is delivered with a fixed pre-set configuration.

Note that the cabling is prepared for a Line card in each slot. So, if not all line cards are equipped, each one must use its own dedicated cable.

The cables not used in a particular configuration must be left fixed at the front lateral parts of the subrack, prepared for being used in a future, and not interfering with other cabling or with the air fluxes through the subrack.

The MDF, located in the right part of the cabinet, is mounted on a fixed structure which allows an easy access to all existing connection modules. The MDF has two parts: Primary (Upper part of the MDF) and Secondary (Lower part of the MDF).

Each connection module has:

• Primary Connection Module: 32 positions (16 pairs)

• Secondary Connection Module: 20 positions (10 pairs)

Page 37: 1. Outdoor C Install

102/164

PD 08 01

3AM 20060 0001 RJZZA

It is divided in two sections "a" (upper part) and "b" (lower part):

• In section "a" (upper one) the signals coming from MLS (Primary Network) or Subscriber Lines (Secondary Network) are connected

• In section "b" (lower one) is used for the associative connections between Primary Network and Secondary Network sides,

In any case, a special tool is required to connect/disconnect the wires in the module.

Figure 69. MDF Primary Connection Strip

The aspect of the Secondary side connection strip is similar to this figure, for 10 pairs instead of 16.

For meeting the ITU K.45 Recommendation, “Resistibility of Telecommunication Equipment installed in Access and Trunk Networks to overvoltages and overcurrents”, it is required to install Overvoltage protections on each subscriber line

They can be installed either on Primary side or in Secondary side (where the connection modules allow it), by means of adequate cartridges provided with the protections mounted on the connection modules.

10.5.10.3 Subscribers Cable for (MLS-3F+MLS-3F) Configuration The subscribers cable (included in 3AM 20213 ABAA), with 96 pairs, for connecting at the front plate of units inserted in MLS_3F is 3AM 20002 BXXX: