BID DOCS.pdfGATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH:
412.287.7333 FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
PROJECT DIRECTORY
DRAWING LIST
OWNER: DEPARTMENT OF VETERAN AFFAIRS PHILADELPHIA VAMC 400
UNIVERSITY AVENUE PHILADELPHIA, PA 19104
CONTRACTING OFFICER TECHNICAL REP: JEFF MACIEJEWSKI 215.823.5800
x6107
[email protected]
PROJECT MANAGER: AE WORKS LTD. 6587 HAMILTON AVENUE PITTSBURGH, PA
15206
POINT OF CONTACT: WAYNE TARVIN, RA 412.287.7333
[email protected]
ARCHITECT & MEP ENGINEERS:
LOCATION MAP
E001 EELCTRICAL SYMBOLS, NOTES AND ABBREVIATIONS ED101 ELECTRICAL -
DEMOLITION - BASEMENT FLOOR PLAN ED102 ELECTRICAL - DEMOLITION -
FIRST FLOOR PLAN EL101 LIGHTING - NEW WORK - BASEMENT FLOOR PLAN
EL102 LIGHTING - NEW WORK - FIRST FLOOR PLAN EP101 POWER - NEW
WORK- BASEMENT FLOOR PLAN EP102 POWER - NEW WORK - FIRST FLOOR PLAN
EP103 POWER - NEW WORK - PENTHOUSE PLAN EP104 POWER - NEW WORK -
ROOF PLAN E501 ELECTRICAL RISER DIAGRAMS E601 ELECTRICAL DETAILS
E701 LUMINAIRE DATA SHEETS E702 LUMINAIRE DATA SHEETS E703
PANELBOARD SCHEDULES
AE WORKS LTD. 6587 HAMILTON AVENUE PITTSBURGH, PA 15206
ARCHITECT POC: WAYNE TARVIN, RA 412.287.7333 x303
[email protected]
MECHANICAL POC: SCOTT LIZOTTE, PE 412.287.7333 x207
[email protected]
FIRE PROTECTION & PLUMBING POC: MICHAEL WELESKI 412.287.7333
x206
[email protected]
ELECTRICAL POC: SHANE SEMPLE, PE 412.287.7333 x211
[email protected]
LAB CONSULTANT:
POINT OF CONTACT: CHRIS BAKKILA, AIA 919.294.0915
[email protected]
ARCHITECTURAL
A001 PARTITION TYPES AND TYPICAL DETAILS AD101 DEMOLITION PLANS
AD102 DEMOLITITON REFLECTED CEILING PLANS A101 BASEMENT FLOOR PLAN
- NEW WORK A102 FIRST FLOOR PLAN - NEW WORK A103 ARCHITECTURAL ROOF
PLAN A111 EQUIPMENT BASEMENT PLAN A112 EQUIPMENT FIRST FLOOR PLAN
A113 EQUIPMENT ELEVATIONS A121 REFECTED CEILING PLANS A201 INTERIOR
ELEVATIONS AND DETAILS A301 DETAILS A302 DETAILS A311 EQUIPMENT
SCHEDULE A312 EQUIPMENT SCHEDULE A313 PLUMBING FIXTURE SCHEDULE
A314 GENERAL EQUIPMENT INFORMATION A401 ENLARGED PLANS AND DETAILS
A501 PLAN DETAILS A601 DOOR SCHEDULE, DOOR DETAILS AND WINDOW
ELEVATIONS AND DETAILS A701 FINISH FLOOR PLANS
M001 SYMBOLS, ABBREVIATIONS AND GENERAL NOTES MD101 BASEMENT FLOOR
- HVAC DUCTWORK DEMOLITION PLAN MD102 FIRST FLOOR - HVAC DUCTWORK
DEMOLITION PLAN MD107 PENTHOUSE HVAC DUCTWORK DEMOLITION PLAN MD108
ROOF HVAC DUCTWORK DEMOLITION PLAN MD201 BASEMENT FLOOR - HVAC
PIPING DEMOLITION PLAN MD202 FIRST FLOOR - HVAC PIPING DEMOLITION
PLAN M101 BASEMENT HVAC DUCTWORK NEW PLAN M102 FIRST FLOOR HVAC
DUCTWORK NEW PLAN M103 SECOND FLOOR HVAC DUCTWORK NEW PLAN M104
PENTHOUSE HVAC DUCTWORK NEW PLAN M105 ROOF HVAC DUCTWORK NEW PLAN
M201 BASEMENT - HVAC PIPING NEW PLAN M202 FIRST FLOOR - HVAC PIPING
NEW PLAN M301 BASEMENT AND FIRST FLOOR PRESSURIZATION PLANS M501
HVAC DETAILS M502 HVAC DETAILS M601 HVAC SUPPLY SHAFT SECTIONS M602
HVAC EXHAUST AIR RISER DIAGRAM M603 HVAC SUPPLY AND EXHAUST AIR
RISER DIAGRAMS M701 EQUIPMENT SCHEDULES M702 EQUIPMENT SCHEDULES
M801 HVAC LAB CONTROL SEQUENCES AND DETAILS
MECHANICAL
P001 SYMBOLS, ABBREVIATIONS, NOTES AND SCHEDULES PD101 BASEMENT
FLOOR - PLUMBING DEMOLITION PLAN PD102 FIRST FLOOR - PLUMBING
DEMOLITION PLAN P101 BASEMENT FLOOR - PLUMBING NEW WORK PLAN P102
FIRST FLOOR - PLUMBING NEW WORK PLAN P501 PLUMBING DETAILS P601
DOMESTIC WATER RISER DIAGRAMS P602 SANITARY AND VENT RISER DIAGRAM
P603 MEDICAL GAS RISER DIAGRAM
PLUMBING
G001 PROJECT COVERSHEET G002 SYMBOLS, ABBREVIATIONS AND GENERAL
NOTES G003 LIFE SAFETY PLANS ASB-1 ICRA AND ASBESTOS ABATEMENT
PLANS
GENERAL
ELECTRICAL
F001 FIRE PROTECTION - SYMBOLS, LEGEND, GENERAL NOTES AND DETAILS
FD101 BASEMENT AND FIRST FLOOR FIRE PROTECTION DEMOLITION PLANS
F101 BASEMENT AND FIRST FLOOR FIRE PROTECTION NEW WORK PLANS
N
STRUCTURAL
1
1 A2
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
ELEVATION REFERENCE
COLUMN GRID DESIGNATORS
VIEW SCALE
VIEW NUMBER
SHEET NUMBER
SHEET NUMBERING
WINDOW TYPE
CORNER GUARD
NEW WALL
PARTITION TYPE
EXISTING DOOR TO REMAIN
TILE (CERAMIC OR QUARRY) PLASTER, SAND, GYPSUM BOARD, PARTICLE
BOARD
WOOD (FINISH)
NOTE: CONTRACTOR SHALL PROVIDE ALL BLOCKING AND SUPPLEMENTAL
SUPPORT REQUIRED FOR SECURE AND PROPER INSTALLATION OF TOILET ROOM
FIXTURES AND ACCESSORIES.
48 "
42 "
18 "
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
&
A AAP AB ACFL ACOUS ACT AD ADD ADDL ADJ ADJ ADMIN AFF AHU AL ALT
ALUM AM AMEND ANES ANUN AP APC APROX ARCH AUTO AWT
BA BACT BASS BBD BC BD BFE BG BIT BKT BLDG BLKG BLT BLW BM BO BOF
BOT BPC BPG BR BRG BRL BSMT BTWN BUR
C C DISP CAB CANTL CAP CAT CBD CCT CCTV CD CG CH CHEM CJT CL CL CLG
CLR CM CMU CO CO CO2 COL COMB CONC CONF CONN CONST CONT CONTR COORD
CORR CPT CT CT CTR CTSK CUH CV CW CW CYL CYSTO
D DEMO DEPR DEPT DET DF DIA DIAG DICT DIFF DIM DIR DISP DIST DIV
DIW DJT DN DP DP DR DR DS DSW DW DWG DWLS
E EC ECG EEG EENT EF EIFS
EJ EL ELEC ELEV EMERG EMG ENCL ENT ENTR EO EP EQ EQUIP ES ETR EWC
EXA EXC EXH EXIST EXP EXT
AND
AIR (CLINICAL) ALARM ANNUNCIATOR PANEL ANCHOR BOLT ACCESS
ACOUSTICAL FIXT ACOUSTICAL CEILING TILE AREA DRAIN ADDENDUM
ADDITIONAL ADJUST/ ABLE ADJACENT ADMINISTRATION ABOVE FINISH FLOOR
AIR HANDLING UNIT ALIGN ALTERNATE ALUMINUM ANESTHESIA MONITOR
AMENDMENT ANESTHESIOLOGY ANNUNCIATOR ACCESS PANEL ARCHITECTURAL
PRECAST CONCRETE APPROXIMATE ARCHITECTURAL AUTOMATIC ACOUSTICAL
WALL TREATMENT
BACTERIOLOGY BUILDING ACCESSORY\ BASSINET BULLETIN BOARD BRICK
COURSES BOARD BOTIOM FOOTING ELEVATION BUMPER GUARD BITUMINOUS
BRACKET BUILDING BLOCKING BORROWED LIGHT BELOW BEAM BY OWNER BY
OWNER FUTURE BOTTOM BED PAN CABINET BLOOD PRESSURE GAUGE BRICK
BEARING BRICK LEDGE BASEMENT BETWEEN BUILT-UP ROOFING
CHANNEL CUP DISPENSER CABINET CANTILEVER CAPACITY CATEGORY
CHALKBOARD CUBICLE CURTAIN TRACK CLOSED CIRCUIT TELEVISION COlLING
GRILLE CORNER GUARD COAT HOOK CHEMISTRY CONTROL JOINT CENTER LINE
CLASS CEILING CLEAR CONSTRUCTION MANAGER CONCRETE MASONRY UNIT
CLEAN OUT CASED OPENING CARBON DIOXIDE COLUMN COMBINATION/-ED
CONCRETE CONFERENCE CONNECT/-ED./-!ON CONSTRUCTION CONTINUE/OUS
CONTRACT/OR COORDINATE CORRIDOR CARPET CERAMIC TILE CAT SCAN CENTER
COUNTERSUNK CABINET UNIT HEATER CARDIOVASCULAR CURTAIN WALL COLD
WATER CYLINDER CYSTOSCOPY
DEPTH OR DEEP DEMOLITION DEPRESSION DEPARTMENT DETAIL/S DRINKING
FOUNTAIN DIAMETER DIAGONAL DICTATION DIFFUSER DIMENSION DIRECTOR
DISPENSER DISTRIBUTION DIVISION DEIONIZED WATER DUMMY JOINT DOWN
DEMOUNTABLE PARTITION DATA PROCESSING DOOR DOCTOR DOWNSPOUT
DISTILLED WATER DUMBWAITER DRAWING DOWELS
EXISTING ELECTRIC CABINET ELECTROCARDIOGRAPHY
ELECTROENCEPHALOGRAPHY EYE EAR NOSE & THROAT EXHAUST FAN
EXTERIOR INSULATION AND FINISH SYSTEM EXPANSION JOINT ELEVATION
ELECTRICAL ELEVATOR EMERGENCY ELECTROMAYOGRAPHY ENCLOSURE EAR NOSE
THROAT ENTRANCE ELECTRICAL OUTLET EXPLOSION PROOF EQUAL EQUIPMENT
END SECTION EXISTING TO REMAIN ELECTRIC WATER COOLER EXHAUST AIR
EXCAVATE/-ED/-ION EXHAUST HOOD EXISTING EXPANSION EXTERIOR
FA FB FBR FD FDN FDV FE FEC FGS FH FHC FHP FHV FIN F!XT FL FL FLASH
FLEX FLG FLUOR FLUORO FP FRMG FRS FS FS FSTOP FT FTG FTR FURR FUT
FV
G GA GAL GALV GB GB GC GEN GEN GL GMU GR GYB GYN GYPSHGT
H HB HD HDCP HDR HOW HM HORIZ HPT HR HSKP HT HTR HVAC HW HW
HWD
IC ICCU ICU lD IN INSUL INT ISO ISOLPP IV
JAN JB JST JT
KO
L L LAV lB LCD LF LIN KKR LLH LLV LMC LOC LPT LS LT LTG LVR
LWC
M MAN MATL MAX MBD MC MCU MECH MED MEMB MET MEZZ MFR MGA MH MHC MIN
MIR MISC MO MONO MPC MPU MRI MTD MTL MTR MULL
NA NIC NO NOM NRC NT NTS
O OB OC OD OFF OH OP OP OPER OPNG OPP OR ORD ORTHO OT
FIRE ALARM FIRE BLANKET FACE BRICK FLOOR DRAIN FOUNDATION FIRE
DEPARTMENT VALVE FIRE EXTINGUISHER FIRE EXTINGUISHER CABINET FOAM
GASKET SEAL FIRE HOSE FIRE HOSE CABINET FULL HEIGHT PARTITION FIRE
HOSE VALVE FINISH FIXTURE FLOOR FLOW LINE FLASHING FLEXIBLE FLANGE
FLUORESCENT FLUOROSCOPY/FLUOROSCOPE FIRE PROOFING FRAMING FLUSHING
RIM SINK FULL SIZE FLOOR SINK FIRESTOPP!NG FOOT/FEET FOOTING FIN
TUBE RADIATION FURRING FUTURE FILM VIEWER
GAS GAUGE GALLONS GALVINIZED GRAB BAR GRADE BEAM GENERAL CONTRACTOR
GENERAL GENERATOR GLASS GLASS MASONRY UNIT GRADE GYPSUM BOARD
GYNECOLOGY GYPSUM SHEA THING
HIGH HOSE BIB HAND DRYER HANDICAP HEADER HARDWARE HOLLOW METAL
HORIZONTAL HIGHPOINT HANDRAIL HOUSEKEEPING HEIGHT HEATER HEATING,
VENTILATING, AIR CONDITIONING HOT WATER HEAD WALL HARDWOOD
INTERCOM INTENSIVE CARDIAC CARE UNIT INTENSIVE CARE UNIT INSIDE
DIAMETER INCH INSULATION INTERIOR ISOLATION ISOLATED POWER PANEL
INTRA VENOUS
JANITOR JUNCTION BOX JOIST JOINT
KNOCK OUT
L ANGLE LAVATORY LAVATORY POUND LINEAR CEILING DIFFUSER LINE
FIGURED LINEAR LOCKER LONG LEG HORIZONTAL LONG LEG VERTICAL LINEAR
METAL CEILING LOCATION OR LOCATE LOW POINT LAWN SPRINKLING LIGHT
LIGHTING LOUVER LINEAR WOOD CEILING
MIDDLE MANUAL MATERIAL MAXIMUM MARKER BOARD MEDICINE CABINET
MODULAR COOLING UNIT MECHANICAL MEDICAL/TION MEMBRANE METAL
MEZZANINE MANUFACTURER MEDICAL GAS ALARM MANHOLE MATERIAL HANDLING
CONVEYOR MINIMUM MIRROR MISCELLANEOUS MASONRY OPENING MONOLITHIC
METAL PAN CEILING MULTI-PURPOSE UNIT MAGNETIC RESONANCE IMAGING
MOUNTED METAL MOTOR MULLION
NOT APPLICABLE NOT IN CONTRACT NUMBER NOMINAL NOISE REDUCTION
COEFFICIENT NOTE NOT TO SCALE
OXYGEN OBSTETRICS ON CENTER OUTSIDE DIAMETER OFFICE OVERHEAD
OPERABLE PARTITION OUTPATIENT OPERATOR OPENING OPPOSITE OPERATING
ROOM OVERFLOW ROOF DRAIN ORTHOPEDICS OCCUPATIONAL THERAPY
PAR PART PB PC PCD PED PEDS PHARM PHYS PHYSICS PICU PL PL PLAM PLBG
PLS PLW PNL PR PRELIM PREP PRES PRESS PRIM PROC PROJ PRV PSYCH PT
PT PTC PTR PTS PULMO PVC
QT
R R RA RAD RB RD RE REC RECP REF REFR REG REHAB REINF REM REQD RET
REV REV RF RF RFI RH RM RO RS RWCS
SAN SCHED SD SD SDISP SECT SECY SF SF SH SHD SHT SHTG SIM SL SLNT
SLV SM SNC SND SOG SP SPC SPEC SPR SQ SQ YD SR SS SSS SST ST ST STA
STC STD STER STL STN STNL STOR STRUCT STS SUPV SURG SUSP SW SW SWD
SYM
T TAN TBD TC TCAB TDISP TOR TEL TEMP TER TG THER THRES TPH TR
TRANSF TS TSC TV TYP
U UC UC UFO UG UH UNF!N UNO US UTIL
V VB VC VCO VENT VERT VEST VIF VR VTR
W W W/ W/0 WC WC WD WE WDW WG WH WHCH WHTR WP WPS WR WS WS WSCT WT
WT WW WWF
ZVB ZBC
QUARRY TILE RADIUS RISER RETURN AIR RADIATION/OLOGY RESILIENT BASE
ROOF DRAIN RELOCATE EXISTING RECESSED RECEPTION REFERENCE REFRIGERA
TOR REGISTER REHABILITATION REINFORCE/-ED/-ING REMOVE REQUIRED
RETAINING REVERSE REVISE RESILIENT FLOOR RADIO FREQUENCY REQUEST
FOR INFORMATION ROOF HATCH ROOM ROUGH OPENING ROUGH SLAB RAIN WATER
CONDUCTOR
SINK SANITARY SCHEDULE SHOWER DRAIN SMOKE DAMPER SOAP DISPENSER
SECTION SECRETARY STORE FRONT SQUARE FOOT SHOWER SHOWER HEAD SHEET
SHEATHING SIMILAR SEALER SEALANT SLEEVE SURFACE MOUNTED SANITARY
NAPKIN CABINET SANITARY NAPKIN DISPOSER SLAB ON GRADE STANDPIPE
SPECIMEN PASS THROUGH CABINET SPECIFICATIONS SINGLE PLY ROOF SQUARE
SQUARE YARD SERVICE RECEPTOR SERVICE SINK SURGEONS SCRUB SINK
STAINLESS STEEL STREET STONE TILE STATION SOUND TRANSMISSION
STANDARD STERILIZER STEEL STONE STONE LEDGE STORAGE STRUCTURAL
STEEL STRUCTURE SUPERVISOR SURGERY/ICAL SUSPENDED STEEL WINDOWS
SWITCH SOFTWOOD SYMMETRICALTOP
TOP TANGENT TACK BOARD TIME CLOCK TOWEL CABINET TISSUE DISPENSER
TRENCH DRAIN TELEPHONE TEMPERATURE TERRAZZO TONGUE & GROOVE
THERAPIST/Y THRESHOLD TOILET PAPER HOLDER TREAD TRANSFORMER TUBE
SECTION TOILET SEAT COVER DISPENSER TELEVISION TYPICAL
URINAL UNDERCUT UNDER COUNTER UNDER FLOOR DUCT UNDERGROUND UNIT
HEATER UNFINISHED UNLESS NOTED OTHERWISE UTILITY SHELF
UTILITY
VACUUM VACUUM BREAKER VALVE CABINET VACUUM CLEANING OUTLET
VENTILATION VERTICAL VESTIBULE VERIFY IN FIELD VAPOR RETARDER VENT
THROUGH ROOF
WIDTH/WIDE WIDE FLANGE WITH WITHOUT WATER CLOSET WALL COVERING WOOD
WASHER EXTRACTOR WINDOW WALL GUARD WALL HYDRANT WHEELCHAIR WATER
HEATER WATERPROOF WALL PROTECTION SYSTEM WASTE RECEPTACLE
WEATHERSTRIP WASHER STERILIZER WAINSCOT WINDOW TREATMENT WEIGHT
WOOD WINDOW WELDED WIRE FABRIC
ZONE VALVE BOX ZONE VALVE CABINET
ARCHITECTURAL ABBREVIATIONS
S
T
U
V
W
Z
F
GENERAL NOTES DO NOT SCALE DRAWINGS. USE FIGURED DIMENSIONS ONLY.
VERIFY ALL DIMENSIONS PRIOR TO START OF WORK. IN THE EVENT OF
DISCREPANCY, NOTIFY THE ARCHITECT AND OBTAIN RESOLUTION BEFORE
PROCEEDING.
NOTIFY THE COTR OF ANY AND ALL DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND THE CONTRACT DOCUMENTS BEFORE PROCEEDING WITH THAT
PORTION OF WORK. FAILURE TO NOTIFY THE ARCHITECT WILL NOT RELIEVE
THE CONTRACTOR OF RESPONSIBILITY TO PERFORM THE WORK AS INTENDED BY
THE CONTRACT DOCUMENTS. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY AND
ALL WORK ARISING FROM SUCH FAILURE TO COORDINATE DISCREPANCIES TO
THE SATISFACTION OF THE ARCHITECT.
VERIFY EXISTING DIMENSIONS, CONDITIONS, AND CLEARANCES PRIOR TO THE
SUBMITTAL OF SHOP DRAWINGS.
WHERE WORK OCCURS IN AREAS WITH EXISTING FINISHES TO REMAIN,
REFINISH DISTURBED AREAS TO MATCH EXISTING FINISHES AND MATERIALS
U.N.O.
ADDITIONAL PLAN INFORMATION IS SHOWN ON LARGER SCALE PLANS WHERE
INDICATED BY KEYED REFERENCE. LARGE SCALE DRAWINGS TAKE PRECEDENCE
OVER SMALLER SCALE DRAWINGS.
PLAN DIMENSIONS ARE TO FINISHED FACE OF PARTITION EXCLUDING FINISH
MATERIAL SUCH AS CERAMIC TILE, WOOD PANELING, ETC
PARTITION TYPES NOTED THUSLY: SEE SHEET X5 FOR DESCRIPTION OF
PARTITION TYPES AND OTHER INFORMATION.
WHERE NEW ROOMS ARE SCHEDULED WITHOUT CEILINGS, PARTITION SHALL
EXTEND TO STRUCTURE ABOVE U.N.O..
VERIFY THE FOLLOWING WITH THE RESPECTIVE TRADES: A. SIZES AND
LOCATIONS OF MECH. AND/OR ELEC. PENETRATIONS. B. LOCATIONS FOR
BACKING/BLOCKING REQUIRED FOR MOUNTING MECH. AND/OR ELEC. EQUIPMENT
C. CUTTING AND PATCHING FOR WORK REQUIRED BY MECH. AND/OR
ELEC.
FOR TYPICAL MOUNTING HEIGHTS OF TOILET, BUILDING EQUIPMENT, AND
ACCESSORIES, (SUCH AS PLUMBING FIXTURES, FIRE EXTINGUISHER
CABINETS, ELECTRICAL WATER COOLERS AND TOILET ACCESSORIES), SEE
"TYPICAL MOUNTING HEIGHTS" NOTES ON THIS SHEET.
THE FOLLOWING DIAGRAMS INDICATE HOW TO DIMENSIONALLY LOCATE METAL
FRAMES U.N.O.
PROTECT AND PRESERVE ALL EXISTING ITEMS TO REMAIN AND REPAIR AND/OR
REPLACE ANY ITEMS DAMAGED DURING THE COURSE OF THE WORK TO THE
SATISFACTION AND APPROVAL OF THE COTR WITHOUT ADDITIONAL COST TO
THE OWNER.
PROVIDE ALL BLOCKING AND ANCHORAGE AS NECESSARY FOR PROPER
INSTALLATION OF NEW WORK ITEMS OR ITEMS TO BE REUSED.
SEE DOOR SCHEDULE ON A17 FOR SPECIFIC DOOR AND HARDWARE TYPES. SEE
DRAWING A17 FOR INTERIOR FRAME TYPES AND DOOR TYPE
ELEVATIONS.
FURNITURE IS SHOWN ON THE PLANS FOR LOCATION AND DESIGN INTENT
ONLY. FURNITURE IS N.IC. AND WILL BE COORDINATED AND PURCHASED BY
OWNER.
ALL SLEEVES, OPENINGS, ETC. FOR CONDUIT, PIPES, DUCTS, ETC.
(OUTSIDE OF RATED CHASES) THROUGH FLOOR SLABS AND RATED PARTITIONS
ARE TO BE FIRE SEALED IN ACCORDANCE WITH FIRE RATED ASSEMBLY
DESIGNS, APPLICABLE CODES AND FIRE MARSHAL'S REQUIREMENTS.
WHERE CONDUIT, PIPES, DUCTS, ETC. ARE INDICATED TO BE INSTALLED IN
EXISTING WALLS AND NO FURRING IS SHOWN, THE WALLS SHALL BE NEATLY
CHASED, CONDUITS, ETC. INSTALLED, AND WALLS PATCHED TO MATCH
EXISTING. IN AREAS OF NEW PARTITIONS WHERE CONDUITS, DUCTS, PIPING,
ETC., PASS THROUGH FINISHED SPACES, ENCLOSE WITHIN PARTITION
CONSTRUCTION.
THE FACE OF EVERY CONTINUOUS PARTITION SHALL BE FLUSH WITHOUT
OFFSET. CHANGES IN PARTITION THICKNESS SHALL OCCUR AT CORNERS OR
OTHER FEATURES WHICH INTERRUPT THE PLANE OF THE PARTITION. FACES OF
CORRIDOR PARTITIONS SHALL ALIGN ALONG THEIR ENTIRE LENGTH
REGARDLESS OF CHANGES IN PARTITION THICKNESS. ALL ADJUSTMENTS ARE
TO BE MADE TO THE ROOM SIDE OF THE CORRIDOR PARTITIONS AND AT
CORNERS.
ALIGN FINISH FACE OF NEW PARTITION WHERE ABUITING EXISTING
CONSTRUCTION U.N.O. ALIGN FINISH FACE ON NEW PARTITION ON BOTH
SIDES WHERE ABUTTING EXTSTING PARTITION U.N.O.
SHOW NEW PARTITION AS REQUIRED TO ACHIEVE A FLUSH, SMOOTH
TRANSITION.
ALL DEMOLITION AND NEW WORK TO BE DONE DURING SECOND SHIFT AND
COORDINATED WITH THE COTR.
THE PROJECT WILL PROGRESS ONE FLOOR AT A TIME. ALL WORK MUST BE
COMPLETED ON THE ONE FLOOR BEFORE WORK ON THE OTHER FLOOR
BEGINS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
X
SYMBOLS INDICATION OF MATERIAL
34" Door(s)
EXIT WIDTH
EXIT PATH
ROOM
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
2 FIRST FLOOR PLAN
CONSTRUCTION TYPE
FIRE RESISTIVE REQUIREMENTS
Bearing Walls Exterior Interior
Floor construction Including supporting beams and joists
Shaft Enclosures Corridors(with sprinkler system)
Fire Extinguisher Max Travel Distance
EXITING REQUIREMENTS
Occupant Load
Egress Width
Exit Access Travel Distance
Common Path of Travel
75'
3
2 3
MORTAR
TOILET ROOM CHASE PARTITION
SEALANT SEALANT SEALANT SEALANT
7 9
UNDERSIDE OF FLOOR SLAB
UNDERSIDE OF FLOOR SLAB
METAL CHANNEL RUNNER
5/8" CONCRETE BACKERBOARD
TOILET ROOM SHAFT PARTITION UL NO. U415 SYSTEM D - 2 HR RATED
5
METAL CHANNEL RUNNER
6 1/4"
5/8" CEMENT BOARD
5/8" LEAD LINED GWB MIN. 20 GAUGE STEEL STUDS @ 16" O.C.
5/8" LEAD LINED GWB 5/8" GWB
CORNER INTERSECTION DETAILPLAN VIEW WALL DETAIL INSIDE CORNER
OUTSIDE CORNER
MIN. 20 GAUGE STEEL STUDS @ 16" O.C.
2" WIDE STRIPES AT GWB JOINTS. SAME THICKNESS AS
LEAD LINING.
3/8" DIAM. LEAD DISCS
5/8" LEAD LINED GWB
2" WIDE STRIPS - SAME THICKNESS AS LEAD LINING
MIN. 20 GAUGE STEEL STUDS @ 16" O.C.
3/8" DIAM. LEAD DISCS
5/8" LEAD LINED GWB
2" WIDE STRIPS - SAME THICKNESS AS LEAD LINING
MIN. 20 GAUGE STEEL STUDS @ 16" O.C.
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
8
1. THERE CAN BE NO GAPS OR HOLES IN THE SHIELDING. SEAMS NEED TO
EITHER OVERLAP OR HAVE A 2 INCH LEAD STRIP COVERING THE SEAMS
BETWEEN 2 PANELS AND EXTEND TO OVERLAP THE FLOOR BY 3 INCHES.
2. PENETRATIONS: THERE CAN BE NO UNWRAPPED PENETRATIONS: ELECTRICAL
AND PHONE BOXES, COMPUTER JACKS, AIR AND GAS LINES, AND OTHER
PENETRATIONS NEED TO BE FULLY WRAPPED. THE BOXES NEED TO BE WRAPPED
ON AT LEAST 5 SIDES OF THE BOX AND OVERLAP WITH LEAD IN THE
WALLS.
3. DUCT WORK AND PIPES: IF THEY PENETRATE WALLS AND/OR FLOORS, THEY
NEED TO BE FULLY WRAPPED WITH THE SAME LEAD THICKNESS AS THE WALL
THEY PENETRATE ON BOTH SIDES OF THE PENETRATED WALL TO A DISTANCE
OF 5 TIMES THE DIAMETER OF THE DUCT OR PIPE.
4. DOORS REQUIRE THE SAME LEAD THICKNESS AS THE WALLS: DOORS WITH
LEAD PLACED IN THE CENTER OF THE DOOR REQUIRE LEAD TO BE REMOVED TO
ALLOW INSTALLATION OF THE HANDLE AND LOCKSET. THIS CAUSES LEAKS AND
PREVENTS ACCEPTANCE.
THE VA RECOMMENDS DOORS BE PURCHASED WITH LEAD ON THE SIDE OF THE
DOOR THAT IS IN CONTACT WITH THE LEAD LINED DOOR FRAME WHEN THE
DOOR IS CLOSED AND ON THE SAME SIDE OF THE DOOR IN CONTACT WITH THE
ASTRAGAL.
DOOR FRAMES ARE TO BE COMPLETELY WRAPPED WITH THE SAME LEAD
THICKNESS AS THE WALLS.
WINDOW PANELS IN THE DOOR: THE DOORS WILL REQUIRE LEADED GLASS OR
ACRYLIC PANELS WITH THE SAME LEAD EQUIVALENCY AS THE WALLS. THE
LEAD GLASS OR ACRYLIC PANEL SHOULD BE PURCHASED FOR THE DESIGNATED
THICKNESS FOR A LEAD EQUIVALENCY AT 125 KVP X-RAY.
LEAD LINED WALLS GENERAL NOTES:
MARK DATE DESCRIPTION
EXISTING DOOR AND FRAME ASSEMBLY TO BE REMOVED
EXISTING CASEWORK ASSEMBLY TO BE REMOVED (ASSEMBLY INCLUDES
ASBESTOS UNDER SINK COATINGS)
EXISTING TRANSITE FUME HOOD ASSEMBLY TO BE REMOVED (ASSEMBLY
CONTAINS ASBESTOS)
EXISTING BIOLOGICAL SAFETY CABINET ASSEMBLY TO BE REMOVED
EXISTING VCT FLOORING TO BE REMOVED
EXISTING CERAMIC TILE FLOORING TO BE REMOVED
EXISTING CARPET TO BE REMOVED
EXISTING EPOXY FLOORING TO BE REMOVED
EXISTING CONCRETE SLAB ON GRADE TO BE REMOVED. COORDINATE REMOVAL
WITH NEW CONSTRUCTION DOCUMENTS.
A
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
WALL MOUNTED FIRE EXTINGUISHER TO BE REMOVED
RECESSED FIRE HOSE CABINET TO BE REMOVED
CERAMIC TILE WALL TO BE DEMOLISHED
FLOOR MOUNTED CHAIN LINK FENCING TO BE REMOVED
CURBED AREA TO BE DEMOLISHED
REMOVE EXISTING LEAD LINED WALLS
REMOVE EXISTING LEAD LINED DOOR AND FRAME ASSEMBLY
REMOVE EXISTING METAL LOCKERS
ELECTRIC PANELS E.T.R.
COORDINATE WITH VA BEFORE REMOVAL AND SALVAGE OF EXISTING
EQUIPMENT
REMOVE WINDOW STOOL
6
7
8
9
10
11
12
13
14
9
15
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND COORDINATE
ALL DEMOLITION ACTIVITIES WITH ANY NEW CONSTRUCTION AS INDICATED
WITHIN THE CONSTRUCTION DOCUMENTS. DO NOT SCALE DRAWINGS.
2. CONTRACTOR SHALL PERFORM ALL NECESSARY DEMOLITION ACTIVITIES AS
REQUIRED FOR INSTALLATION OF NEW CONSTRUCTION AS INDICATED WITHIN
THE CONSTRUCTION DOCUMENTS. COORDINATE WITH THOSE DOCUMENTS FOR
EXACT DIMENSIONS AND LOCATIONS OF FINISHED WORK.
3. ALL DEMOLITION NOT SPECIFICALLY INDICATED, BUT NECESSARY TO
COMPLETE THE PROJECT AS INDICATED ON THE CONSTRUCTION DOCUMENTS,
SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
4. THE CONTRACTOR SHALL INSPECT AND ACCESS EACH SPACE AND FULFILL
THE INTENT OF THE WORK REQUIRED BY THE CONTRACT DOCUMENTS.
DEVIATIONS REQUIRED BY EXISTING FIELD CONDITIONS SHALL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT PRIOR TO PROCEEDING WITH THE
WORK.
5. ANY CUTTING AND REMOVAL INDICATED ON THE CONSTRUCTION DOCUMENTS
ARE GENERAL INDICATIONS ONLY AND MAY NOT NECESSARILY SHOW THE FULL
EXTENT OF CUTTING AND REMOVAL NECESSARY.
6. THROUGHOUT THE COURSE OF DEMOLITION ACTIVITIES, PROPERLY PROTECT
ANY EXISTING CONSTRUCTION INDICATED TO REMAIN. EXERCISE CARE WHEN
REMOVING ADJACENT CONSTRUCTION AND PROPERLY REPAIR (TO ORIGINAL
CONDITION) ANY AREAS SCHEDULED TO REMAIN THAT SUSTAIN DAMAGE AS A
RESULT OF DEMOLITION ACTIVITIES.
7. CONTRACTOR SHALL CONSTRUCT DUST PROOF PROTECTIVE BARRIERS AS
NECESSARY AT AREAS OF INTERIOR DEMOLITION TO PROTECT EXISTING
CONSTRUCTION AND EQUIPMENT SCHEDULED TO REMAIN.
8. PERFORM ALL WORK REQUIRED TO PROTECT BUILDING OCCUPANTS AND
EXISTING BUILDING UTILITIES. THE BUILDING WILL REMAIN IN OPERATION
THROUGHOUT THE COURSE OF DEMOLITION AND CONSTRUCTION
ACTIVITIES.
9. THE CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE ALL NECESSARY
TEMPORARY BRACING AND SHORING AS REQUIRED TO MAINTAIN THE INTEGRITY
AND STRUCTURAL STABILITY OF THE BUILDING AND ITS INDIVIDUAL
ELEMENTS.
10. EXCEPT AS NOTED OTHERWISE, REMOVE ALL DEMOLISHED MATERIALS FROM
THE SITE AND DISPOSE OF IN ACCORDANCE WITH ALL LOCAL, STATE AND
FEDERAL LAWS REGULATIONS. DO NOT BURN, BURY, OR SELL MATERIALS ON
THE PROJECT SITE. AT THE COMPLETION OF EACH WORK DAY, CLEAN THE
ENTIRE WORK AREA AND LEAVE IN A NEAT CONDITION FREE OF DEBRIS AND
RUBBISH.
11. STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL,
TELECOMMUNICATION, AND CIVIL DOCUMENTS PROVIDE ADDITIONAL
DEMOLITION REQUIREMENTS FOR EACH PRIME CONTRACT. ALL PRIME
CONTRACTORS ARE RESPONSIBLE FOR FAMILIARIZING THEMSELVES WITH THOSE
DOCUMENTS THAT MAY PROVIDE ADDITIONAL DEMOLITION REQUIREMENTS
BEYOND THOSE SPECIFICALLY INDICATED ON THE ARCHITECTURAL DEMOLITION
PLANS.
12. THROUGHOUT THE COURSE OF DEMOLITION ACTIVITIES, THE CONTRACTOR
SHALL PATCH, REPAIR AND PREPARE EXISTING EXPOSED SURFACES AND/OR
ADJACENT MATERIAL AS REQUIRED TO RECEIVE NEW FINISHES.
13. CAREFULLY REMOVE AND DELIVER TO THE OWNER ANY EXISTING FIRE
EXTINGUISHERS FOUND WITHIN THE LIMIT OF DEMOLITION
ACTIVITIES.
14. THE OWNER RESERVES THE RIGHT TO REMOVE AND ITEMS SCHEDULED FOR
DEMOLITION PRIOR TO THE START OF DEMOLITION ACTIVITIES AND CLAIM
ANY ITEMS REMOVED BY THE CONTRACTOR THROUGHOUT THE COURSE OF
DEMOLITION.
15. ALL BASEMENT WALLS ARE CMU
16. ALL BASEMENT FLOORING IS EXISTING EPOXY TO BE REMOVED
17. ALL FIRST FLOOR WALLS ARE GWB AND STUD TO BE REMOVED
MARK DATE DESCRIPTION
REMOVE EXISTING 2x4 ACT, GRID AND HANGERS FROM STRUCTURE
ABOVE
REMOVE EXISTING 2x2 ACT, GRID AND HANGERS FROM STRUCTURE
ABOVE
REMOVE EXISTING PLASTER CEILING, FRAMING AND SUPPORTS FROM
STRUCTURE ABOVE
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
SCALE: 1/8" = 1'-0"AD102
10
10' - 2" 10' - 8" 10' - 6" 10' - 6" 10' - 9"
6' - 11"
4' - 5"
20' - 2"
S LO
PE D
O W
N 1/
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
KEY NOTES
FILL IN EXISTING EQUIPMENT PIT - SEE DETAIL ON SHEET A301
PROVIDE ELECTRONIC CARD READER
EXISTING FIRE HOSE CABINET LOCATION. REMOVE EXISTING CABINET AND
PROVIDE AND INSTALL NEW
WALL MOUNTED ELECTRICAL PANEL E.T.R.
PROVIDE WALL MOUNTED SPILL CONTROL STATION
10" DEEP PIT TO SUIT EQUIPMENT FURNISHED, SEE DETAIL ON SHEET
A301.
STAINLESS STEEL PLATE AS REQUIRED BY EQUIPMENT FURNISHED
TRENCH DRAIN - SEE DETAIL ON SHEET A301.
EMERGENCY SHOWER FLOOR DRAIN - SEE DETAIL ON SHEET A301.
FRP PANELS TO BE INSTALLED ON ALL WALLS IN ROOM.
PROVIDE ALUMINUM CRASH RAILS ON ALL WALL IN ROOMS IDENTIFIED WITH
THIS KEYNOTE. COORDINATE WITH OPENINGS AND OTHER ITEMS INSTALLLED
ON THE WALL SURFACE THAT WILL INTERFERE WITH MOUNTING OF THE
RAILS.
OFFSET WALL ABOVE CEILING TO AVOID DUCTS THROUGH FLOOR ABOVE.
MAINTAIN ACOUSTIC RATING. COORDINATE WITH COLD ROOM IN AB10.
1
2
3
4
5
6
7
8
9
10
11
A102/A
A104B/B
A104C/B
A104C/A
A104B/A
A104/A
A109/A
A116/A
AC1-3/A
6' - 2" 5' - 5" 9' - 2" 10' - 10" 10' - 9" 11' - 5" 10' - 11" 15' -
2"
20 '-
14 '-
10 "
A501 16
C.G.
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
RECESSED PROJECTION SCREEN - SEE DETAIL ON SHEET A301. CONTRACTOR
FURNISHED, CONTRACTOR INSTALLED
FLOOR OPENINGS, REFER TO HVAC DRAWINGS
EXISTING FIRE HOSE CABINET LOCATION. REMOVE EXISTING CABINET AND
PROVIDE AND INSTALL NEW
PROVIDE WALL MOUNTED SPILL CONTROL STATION. HANDLE TO BE MOUNTED NO
HIGHER THAN 48"
INSTALL ELECTRONIC CARD READER
PATCH AND PAINT EXISTING SURFACE TO MATCH ADJACENT NEW
CONSTRUCTION
1/16" LEAD SHIELDING TO A HEIGHT OF 8'-0" A.F.F. SEE WALL DETAILS
ON SHEET A001 AND DOOR SCHEDULE FOR DOOR AND HARDWARE
REQUIREMENTS.
3/32"LEAD SHIELDING TO A HEIGHT OF 8'-0" A.F.F. SEE WALL DETAILS ON
SHEET A001.
INSTALL NEW WINDOW STOOL
PROVIDE ALUMINUM CRASH RAILS ON ALL WALL IN ROOMS IDENTIFIED WITH
THIS KEYNOTE. COORDINATE WITH OPENINGS AND OTHER ITEMS INSTALLED ON
THE WALL SURFACE THAT WILL INTERFERE WITH MOUNTING OF THE
RAILS.
1
2
GENERAL NOTES 1. SEE DRAWING A112 FOR EQUIPMENT LAYOUT
2. ALIGN NEW EXTERIOR WINDOWS WITH EXISTING WINDOWS OR PARGING ON
FLOORS ABOVE U.N.O.
3
4
5
6
7
8
12
9
10
1 BEAM ROOF CURB - SEE DETAILS ON SHEET A302.
PROVIDE ROOF CURB FOR CONDENSING UNIT - SEE DETAIL ON SHEET
A302.
EXISTING POST AND BEAM SYSTEM
EXISTING POST AND BEAM SYSTEM
1 BEAM ROOF CURB - TYPICAL FOR 5. SEE DETAIL ON SHEET A302. EQUALLY
SPACE PER AHU SIZE.
OUTLINE OF NEW AHU. VERIFY SIZE W/ MANUFACTURER.
OUTLINE OF EXISTING EXHAUST PLENUM
OUTLINE OF EXISTING MAKE-UP AIR HANDLING UNIT
OUTLINE OF EXISTING EXHAUST FANS UNITS
OUTLINE OF EXISTING EXHAUST FANS
OUTLINE OF EXISTING EXHAUST FAN
OUTLINE OF NEW EXHAUST FANS UNITS. VERIFY SIZE W/
MANUFACTURER.
NEW BEAM SUPPORT SYSTEM. DESIGN SHALL BE BY CONTRACTOR
NEW POST. POST LOCATION CAN ONLY OCCUR AT COLUMN LOCATION
NEW POST. POST LOCATION CAN ONLY OCCUR AT COLUMN LOCATION
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
1 ARCHITECTURAL ROOF PLAN
NOTE: VERIFY ALL ROOFTOP EQUIPMENT LOCATION AND SIZES WITH THE
MECHIANICAL DRAWINGS. THEY ARE ONLY SHOWN ON THIS PLAN FOR
COORDINATION PURPOSES.
13
EQ3.006.02 EQ3.006.02 EQ3.006.02
A113
7
A113
9
10
EQ1.006.02
EQ1.024.00EQ3.019.00
EQ3.020.00
EQ3.021.00
EQ1.019.00
483036TTM
STAINLESS STEEL MODULAR WALL AND ACCESS DOOR BY WASHING EQUIPMENT
MANUFACTURER
STAINLESS STEEL MODULAR WALL BY WASHING EQUIPMENT
MANUFACTURER
EQ3.006.02
EQ3.006.02
EQ3.006.02
EQ3.006.02
EQ3.006.02
EQ3.006.02EQ3.006.02EQ3.006.02
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A111
EQ1.020.01EQ1.020.01
STORAGE A121
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A112
541631WC 541631WC 541631WC 541631WC
541206AS 541206AS 541206AS 541206AS
- 6 "
4 ELECTRICAL OUTLETS PER WORKSTATION - TOTAL 16 ELECTRICAL OUTLETS
MINIMUM
03SR
03SR
Basement EL +0' - 0"
PTDSD
362235BS
181410.5SK
SKA4SF
302235BC
EQ1.025.00
30XX31WFA
EQ1.006.02
EQ3.023.00
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A113
DIFFUSERS
ACCESS PANELA
GENERAL NOTES 1. ALL CEILING HEIGHTS TO BE 8'-6" UNLESS NOTED
OTHERWISE
2. PROVIDE SOUND INSULATING BATTS ON ALL DRYWALL CEILINGS
3. WHERE BULKHEAD IS IDENTIFIED, SEE DETAIL ON THIS SHEET.
4. ALL PENETRATION JOINTS OF DRYWALL CEILINGS MUST BE FULLY SEALED.
SEAL AROUND ALL LIGHTS, DUCTS, DIFFUSERS, DEVICES, ETC. WITH
APPROVED SEALANT.
S/S SPEAKER STROBE
ACT CEILING SYSTEM
SURFACE MOUNTED STRIP LIGHT FIXTURE
ST STROBE NOTE: STUD PROJECTING BELOW KICKER SHOULD NOT EXCEED
2'-0"
CEILING BOTH SIDES SEE CEILING PLAN FOR CEILING SYSTEM
3 5/8" METAL STUD BRACING @ 48" OC
3 5/8" METAL STUDS @ 16" OC. ATTACH TO STRUCTURE ABOVE
FO R
H EI
G H
5/8" GYP. BD.
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
2 FIRST FLOOR REFLECTED CEILING PLAN
SCALE: 1 1/2" = 1'-0"A121
2' -
ALUMINUM INTEGRATED REVEAL TRIM WITH CHARTRAIL INSERT, SEE DETAIL
6/A201
2' -6
ALUMINUM INTEGRATED REVEAL TRIM WITH CHARTRAIL INSERT, SEE DETAIL
6/A201
2' -6
2' -
MANUFACTURED WOOD CASEWORK
MANUFACTURED WOOD CASEWORK
ALUMINUM INTEGRATED FUNCTION REVEAL RAIL, FRY REGLET OR APPROVED
EQUAL
3 3 /4"2"
CHARTRAIL CLIP
QUARTZ COUNTERTOP
5/8" PARTICLE BOARD FILLER ON EACH END
3/4" PARTICLE BOARD W/ OAK VENEER FINISH. P. LAM EDGING ON ALL
EXPOSED SIDES
QUARTZ COUNTERTOP
1' - 4"
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
SCALE: 1/2" = 1'-0"A201
5 CONFERENCE ROOM A122 SOUTH
SCALE: 1/2" = 1'-0"A201
2 COPY CENTER
SCALE: 3" = 1'-0"A201
7 MAILBOX ELEVATION AND SECTION
18
8" REINFORCED CONCRETE ROOF SLAB - SEE STRUCTURAL DRAWINGS
CONTINUOUS WATERPROOFING MEMBRANE
1/2" COMPRESSED FILLER
M IN
8" REINFORCED CONCRETE ROOF SLAB - SEE STRUCTURAL DRAWINGS
WATERSTOP
WATERSTOP
EXISTING CONCRETE WALL
WATERSTOP
INFILL EXISTING DOOR OPENING WITH CMU
EXISTING CONCRETE COLUMN
EXISTING CONCRETE WALL
NEW INTERIOR PARTITION
EXISTING CONCRETE WALL
SMOOTH AND SKIM COAT CUT CONCRETE EDGE
EXISTING CONCRETE WALL AND COLUMN
12" REINFORCED CONCRETE WALL - SEE STRUCTURAL DRAWINGS
WATERSTOP
CONTINUOUS WATERPROOFING MEMBRANE AND PROTECTION BOARD TO OVERLAP
EXISTING BOARD AND MEMBRANE ON EXISTING WALL 48"
C.G.
REINFORCED CONCRETE
NEW CONCRETE FOOTING, SEE STRUCTURAL DRAWINGS
S.S. PLATE AS REQUIRED BY EQUIPMENT PROVIDED, SET IN GROUT AND
LEVEL +/- 1/8"
10 "
WATERPROOF MEMBRANE
BONDING ADHESIVE
ACOUSTICAL SEALANT
STEEL STUDS
DRYWALL CONTROL JOINT NOTES:
1. PROVIDE CONTROL JOINTS IN UNTINTERRUPTED LONG EXPANSES OF
PARTITION @ 30'-0" OC MAX 2. LOCATED JOINTS AT EACH CORNER OF
NON-FULL HEIGHT DOOR OR BORROWED LIGHT FRAMES. 3. JOINTS SHALL
OCCUR ON BOTH SIDES OF PARTITION WHERE GYPSUM BOARD OCCURS.
SLOPED CONCRETE FLOOR
POURED MEMBRANE
THREADED ROD CONNECTED TO UNISTRUCT AND ENCLOSURE
CEILING TILE
TA PE
A ND
JO IN
T CO
MP OU
TO TO
P 4'
-0 "M
VERIFY TRENCH WIDTH WITH THE TRENCH CHANNEL MANUFACTURER.
VERIFY TRENCH DEPTH WITH THE TRENCH CHANNEL MANUFACTURER. TRENCH
NEEDS TO BE DEEP ENOUGH TO ACCOMANDATE THE HIGH POINT OF THE TRENCH
CHANNEL.
NOTES: 1.
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
1 NEW WALL W/CONCRETE CAP
SCALE: 1 1/2" = 1'-0"A301
SCALE: 1 1/2" = 1'-0"A301
5 NEW CMU WALL AND EXISTING SCALE: 1 1/2" = 1'-0"A301
7 EQUIPMENT PIT REMOVAL
SCALE: 3/4" = 1'-0"A301
11
SCALE: 3" = 1'-0"A301
12 CORNERGUARD DETAIL SCALE: 1" = 1'-0"A301
14 FIRE EXTINGUISHER DETAIL SCALE: 1 1/2" = 1'-0"A301
15 TRENCH DETAIL
EXISTING LIGHTWEIGHT CONCRETE
EXISTING RIGID INSULATION
MIN 3"
MIN 3"
EXISTING COVERBOARD
MODIFIED BITUMEN CAP SHEET
WOOD BLOCKING
METAL COUNTERFLASHING
1/2" PLYWOOD
EXISTING LIGHTWEIGHT CONCRETE
EXISTING RIGID INSULATION
MIN 3"
MIN 3"
EXISTING COVERBOARD
MODIFIED BITUMEN CAP SHEET
MODIFIED BITUMEN CAP SHEET
WOOD BLOCKING
CONTRACTOR TO SUBMIT DESIGN.
CONTRACTOR TO SUBMIT DESIGN.
MODIFIED BITUMEN CAP SHEET
PRESERVATIVE TREATED WOOD BLOCKING
STEEL ANGLE PERIMETER FRAMING
MULTI-PURPOSE FLASHING CEMENT
6" MINIMUM FLANGE SET IN FLASHING CEMENT OVER FIELD PLIES
MODIFIED BITUMEN CAP SHEET
MODIFIED BITUMEN CAP SHEET
EXISTING LIGHTWEIGHT CONCRETE
BASE AND INTERPLY SHEETS AS REQUIRED
CAP EXISTING HOLE WITH FLASHING
MODIFIED BITUMEN CAP SHEET
MIN 3"
NOTE: TYPICALLY USED FOR INFILLING THE REMOVAL OF PIPE VENTS
EXISTING LIGHTWEIGHT CONCRETE
MODIFIED BITUMEN CAP SHEET
STEEL ANGLE PERIMETER FRAMING
NOTE: TYPICALLY USED FOR INFILLING THE REMOVAL OF EXHAUST
FANS
EXISTING BRICK
EXISTING CMU
BRICK INFILL TO MATCH EXISTING BRICK COLOR AND SIZE. TOOTH INTO
EXISTING WALL.
CMU INFILL TO MATCH EXISTING CMU SIZE. TOOTH INTO EXISTING
WALL.
1' -
0"
2"
JAMB ANCHOR - 3 PER SIDE
METAL COUNTERFLASHING
EXISTING LIGHTWEIGHT CONCRETE
EXISTING RIGID INSULATION
MODIFIED BITUMEN CAP SHEET
PRESERVATIVE TREATED WOOD BLOCKING, TYP.
1' - 0"1' - 0"
NON-SHRINK GROUT
5" GRAVEL
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
3 ROOF CURB - 4 BEAM
SCALE: 1 1/2" = 1'-0"A302
5 PLATFORM SECTION
7 SMALL PATCH DETAIL
10 WALL INFILL DETAIL
SCALE: 1 1/2" = 1'-0"A302
20
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A311
SPECIALTY EQUIPMENT EQ1
SG E Number Room Number Room: Name Item Name Basis of Design
Sizes
CFCI New/Existing/Future/Relocate Air Vacuum CO2 Data Exhaust Gas
Steam Drain Cold Water Hot Water Flow Pressure Electrical
NotesLength Width Depth Height Hertz Watts/Amps Voltage Emergency
Power
EQ1.002.00 A104 SURGICAL PACKS AND SCRUBS Scrub Sink SS Series -
Mac Medical 5' - 4" 5' - 4" 2' - 3 1/2" Yes No No No Yes Yes Yes
50.00 psi 120V 20 - 50 PSIG
EQ1.003.00 A104B OPERATING ROOM Surgery Lights Berchtold
Chromophare E Series E 805 Yes No No No No No No 50/60 Hz 2 Amps
120VAC No 80 - 160,000 Lux EQ1.003.00 A104B OPERATING ROOM Surgery
Lights Berchtold Chromophare E Series E 805 Yes No No No No No No
50/60 Hz 2 Amps 120VAC No 80 - 160,000 Lux EQ1.003.00 A104C
OPERATING ROOM Surgery Lights Berchtold Chromophare E Series E 805
Yes No No No No No No 50/60 Hz 2 Amps 120VAC No 80 - 160,000 Lux
EQ1.003.00 A104C OPERATING ROOM Surgery Lights Berchtold
Chromophare E Series E 805 Yes No No No No No No 50/60 Hz 2 Amps
120VAC No 80 - 160,000 Lux
EQ1.004.00 AB5A PROCEDURE Biosafety Cabinet - Exhausted Baker Co. -
NCB-D4 4' - 6" 2' - 8" 7' - 3" Yes No Yes Yes Vented - 281 CFM No
No Yes No 60 Hz 12 Amps/20 Breaker 115V,AC Yes .70" wc
EQ1.006.00 A106 ANIMAL WATER SYSTEM Animal Water System Edstrom
8550-697 3' - 0" 3' - 0" 6' - 2" Yes Yes Cat-5 4CFM No No Yes Yes
No 50/60Hz 15amps 100-240VAC - GFCI Outlet for 3 prong plug Water =
100 psi max, 30 psi min., 12 GPM max at 30 - 75 psi, 0-4.5 GPM
Continuous
EQ1.006.01 A106 ANIMAL WATER SYSTEM Ultra Filter Edstrom Yes Yes
Yes 50/60Hz 15amps 120 VAC, GFIC
EQ1.006.02 AB7 CLEAN CAGE PREP Bottle Filler Lynx 100LX Yes Yes Yes
120 VAC EQ1.006.02 AB7 CLEAN CAGE PREP Flushing Station Edstrom Yes
Yes 4 CFM Yes 15-60 psi max
EQ1.006.03 AB5C HOLDING Flushing Station Edstrom 1' - 10" 7" 1' -
6" Yes
EQ1.007.00 AB7 CLEAN CAGE PREP Cage & Bottle Washer Lynx 310LX
10' - 0" 5' - 0" Yes Yes Cat-5 200CFM No Yes Yes Yes No 0.00 psi
3-60-208/230/460 V No Steam 30-80 PSI, Compressed Air 80PSI. Cold
Water Flow Pressure = 40 GPM, Drain 90 GPM, Air Flow Rate
4CFM
EQ1.009.00 AB14 CLEAN CAGE PREP Cage & Rack Washer Lynx 810LX
"Hybrid" 19' - 7" 5' - 2" Yes No No Yes Yes Yes Yes No
EQ1.011.00 A102 ANIMAL PREP/RECOVERY Point Exhaust Nederman FX50
Yes No 200CFM No No No No No
EQ1.012.00 AB10 PROCEDURE/NECROPSY Cold Room As specified Yes
EQ1.013.00 AB5BC Watch Dog Touch Screen Edstrom Yes No Cat5e No No
No No No No EQ1.013.00 AB6 CORRIDOR Watch Dog Touch Screen Edstrom
1' - 6" 1/4" 4 1/2" 1' - 6" Yes No Cat5e No No No No No 60Watts -
Plug in screw connectors 12VDC No EQ1.013.00 AB8A VESTIBULE Watch
Dog Touch Screen Edstrom 1' - 6" 1/4" 4 1/2" 1' - 6" Yes No Cat5e
No No No No No 60Watts - Plug in screw connectors 12VDC No
EQ1.013.00 AB8B VESTIBULE Watch Dog Touch Screen Edstrom 1' - 6"
1/4" 4 1/2" 1' - 6" Yes No Cat5e No No No No No 60Watts - Plug in
screw connectors 12VDC No EQ1.013.00 AB8C VESTIBULE Watch Dog Touch
Screen Edstrom 1' - 6" 1/4" 4 1/2" 1' - 6" Yes No Cat5e No No No No
No 60Watts - Plug in screw connectors 12VDC No EQ1.013.00 AB11
CORRIDOR Watch Dog Touch Screen Edstrom 1' - 6" 1/4" 4 1/2" 1' - 6"
Yes No Cat5e No No No No No 60Watts - Plug in screw connectors
12VDC No EQ1.013.00 AB12 CORRIDOR Watch Dog Touch Screen Edstrom 1'
- 6" 1/4" 4 1/2" 1' - 6" Yes No Cat5e No No No No No 60Watts - Plug
in screw connectors 12VDC No EQ1.013.00 AB13 CORRIDOR Watch Dog
Touch Screen Edstrom 1' - 6" 1/4" 4 1/2" 1' - 6" Yes No Cat5e No No
No No No 60Watts - Plug in screw connectors 12VDC No EQ1.013.00
AB15 VESTIBULE Watch Dog Touch Screen Edstrom Yes No Cat5e No No No
No No EQ1.013.00 AB18 ELEVATOR LOBBY Watch Dog Touch Screen Edstrom
1' - 6" 1/4" 4 1/2" 1' - 6" Yes No Cat5e No No No No No 60Watts -
Plug in screw connectors 12VDC No
EQ1.014.00 AB5 VESTIBULE Pressure Reducing Station Edstrom 8550-697
2' - 1" 6 1/2" 1' - 4" Yes Yes Yes Yes EQ1.014.00 ACB-2 CORRIDOR
Pressure Reducing Station Edstrom 8550-697 0" 2' - 1" 6 1/2" 1' -
4" Yes Yes Signal Output for digital connection No No Yes Yes No
15.00 psi 24 VDC No Flow rate 10 - 14 GPM EQ1.014.00 ACB-2 CORRIDOR
Pressure Reducing Station Edstrom 8550-697 2' - 1" 6 1/2" 1' - 4"
Yes Yes Yes Yes
EQ1.018.00 A104 ANIMAL PREP/RECOVERY Recessed Safety Station
Guardian GBF2160 Yes Yes Yes Yes EQ1.018.00 AB1 ELEVATOR LOBBY
Recessed Safety Station Guardian GBF2160 0" 0" Yes No No No Yes Yes
Yes Yes EQ1.018.00 AB5A PROCEDURE Recessed Safety Station Guardian
GBF2160 0" 0" Yes No No No Yes Yes Yes Yes EQ1.018.00 AB8 VESTIBULE
Recessed Safety Station Guardian GBF2160 0" 0" Yes No No No Yes Yes
Yes Yes EQ1.018.00 AB14 DIRTY CAGE WASH Recessed Safety Station
Guardian GBF2160 Yes EQ1.018.00 AC1-5 SECURE CORRIDOR Recessed
Safety Station Guardian GBF2160 Yes Yes Yes Yes EQ1.018.00 ACB-2
CORRIDOR Recessed Safety Station Guardian GBF2160 0" 0" Yes No No
No Yes Yes Yes Yes
EQ1.019.00 AB10 PROCEDURE/NECROPSY Downdraft Table TBJ 36-72-S DD
6' - 0" 3' - 0" 3' - 6" Yes Yes Yes Yes Yes 60Hz 15amps 115V
EQ1.020.00 AB8 VESTIBULE Matheson Tri-Gas Cylinder Holder Model 710
Yes
EQ1.020.01 A106 ANIMAL WATER SYSTEM Matheson Tri-Gas Cylinder Rack
6532-2 Yes EQ1.020.01 A106 ANIMAL WATER SYSTEM Matheson Tri-Gas
Cylinder Rack 6532-2 Yes
EQ1.023.00 A104B OPERATING ROOM Surgical Boom Berchtold Teletom
Power Boom 500 & 700 Series 2' - 0" 2' - 0" Yes Yes Yes No No
No No No No Air, Vacuum, Oxygen, Nitrogen EQ1.023.00 A104C
OPERATING ROOM Surgical Boom Berchtold Teletom Power Boom 500 &
700 Series 2' - 0" 1' - 6" Yes Yes Yes No No No No No No Air,
Vacuum, Oxygen, Nitrogen
EQ1.024.00 A104 CLEAN CAGE PREP Autoclave Getinge 700 Series 0" 3'
- 0" 4' - 4" 6' - 2" Yes Yes Vented No Yes Yes Yes No 50/60 Hz
Customer Interface Box 15A, Junction Box Vacuum Pump Motor (3HP)
10A
Customer Interface Box 115V, 50/60 Hz, 1P; Junction Box Vacuum Pump
Motor (3HP) 208V, 60Hz, 3P
No Cabinet Enclosed
EQ1.025.00 AB7 CLEAN CAGE PREP Bedding Dispenser Lynx 710LX 3' - 7"
2' - 6" Yes No Vent 650CFM No No No No No 60 hz 30 amps 120V, AC No
Single Phase
EQ1.026.00 AB10 PROCEDURE/NECROPSY Cold Storage Shelving A356EC 4'
- 0" 1' - 6" Yes No No No No No No No EQ1.026.00 AB10
PROCEDURE/NECROPSY Cold Storage Shelving A356EC 4' - 0" 1' - 6" Yes
No No No No No No No
SPECIALTY EQUIPMENT EQ2
SG E Number Room Number Room: Name Item Name Model Size
OFCI New/Existing/Future/Relocate Air Vacuum Exhaust Gas Steam
Drain Cold Water Hot Water Vacuum Flow Pressure Hertz Watts/Amps
Voltage Emergency Power NotesLength Width Height
EQ2.002.00 AB6 RODENT SURGERY Biosafety Cabinet Baker Co. -
SterilGARD e3 4' - 6" 2' - 8" 5' - 1 3/4" Yes Existing - Relocate
No Yes Recirculating - 290-871 CFM No No Yes 60 Hz 20amps 115V,AC
No Single Phase EQ2.002.00 AB8B BARRIER HOLDING/PROCEDURE Biosafety
Cabinet Baker Co. - SterilGARD e3 4' - 6" 2' - 8" 5' - 1 3/4" Yes
Existing - Relocate No Yes Recirculating - 290-871 CFM No No No No
No Yes 60 Hz 20amps 115V,AC No Single Phase
EQ2.003.00 A104 SURGICAL PACKS AND SCRUBS Autoclave Getinge 8128
EC1 0" 3' - 0" Yes Existing - Relocate No No Vented No Yes Yes Yes
Yes 50/60 Hz 15A 120V No Cabinet Enclosed
EQ2.004.00 AB5 VESTIBULE Autoclave Primus PSS5-F-MSSD 0" 6' - 6" 6'
- 9" Yes Existing - Relocate No No Vented No Yes Yes Yes Yes
50/60Hz, 50/60 Hz, 50/60 Hz, 60 Hz 12A, 5A, 84A, 5.7A 115V, 230V,
208V, 208V No
20
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A312
SPECIALTY EQUIPMENT EQ3
SG E Number Room Number Room: Name Item Name Basis of Design
Sizes
OFOI New/Existing/Furture/
Relocate Air Data Exhaust Steam Drain Cold Water Hot Water Flow
Pressure Hertz Watts/Amps Voltage Emergency Power NotesLength Width
Height
EQ3.001.01 A102 ANIMAL PREP/RECOVERY Moveable Cart 5' - 0" 2' - 6"
Yes Relocate No No No No No No EQ3.001.01 A104 SURGICAL PACKS AND
SCRUBS Moveable Cart 2' - 0" 1' - 6" Yes Relocate No No No No No No
EQ3.001.01 AB5A PROCEDURE Moveable Cart 6' - 8" 2' - 8" Yes
Relocate No No No No No No
EQ3.001.02 A104B OPERATING ROOM Case Cart 3' - 0" 2' - 4 1/2" 3' -
6" Yes No No No No No No EQ3.001.02 A104B OPERATING ROOM Case Cart
3' - 0" 2' - 4 1/2" 3' - 6" Yes No No No No No No EQ3.001.02 A104B
OPERATING ROOM Case Cart 3' - 0" 2' - 4 1/2" 3' - 6" Yes No No No
No No No EQ3.001.02 A104C OPERATING ROOM Case Cart 3' - 0" 2' - 4
1/2" 3' - 6" Yes No No No No No No EQ3.001.02 A104C OPERATING ROOM
Case Cart 3' - 0" 2' - 4 1/2" 3' - 6" Yes No No No No No No
EQ3.001.02 A104C OPERATING ROOM Case Cart 3' - 0" 2' - 4 1/2" 3' -
6" Yes No No No No No No
EQ3.002.01 A104B OPERATING ROOM Surgery Table Shor-Line 903.3120.00
6' - 0" 3' - 0" Yes No No No No No No EQ3.002.01 A104C OPERATING
ROOM Surgery Table Shor-Line 903.3120.00 6' - 0" 3' - 0" Yes No No
No No No No
EQ3.003.00 A102 ANIMAL PREP/RECOVERY Animal Recovery Units/ICU
Tecniplast Laminar Flow Ventilated Cabinet 9ARMV2124 3' - 4" 2' -
5" Yes No No No No No Yes EQ3.003.00 A102 ANIMAL PREP/RECOVERY
Animal Recovery Units/ICU Tecniplast Laminar Flow Ventilated
Cabinet 9ARMV2124 3' - 4" 2' - 5" Yes No No No No No Yes
EQ3.004.00 AB5B HOLDING Cage Change Stations Tecniplast CS5 Evo 3'
- 11" 2' - 6" 7' - 6" Yes No No No No No 50/60 Hz 230V No > .30
m/s EQ3.004.00 AB5C HOLDING Cage Change Stations Tecniplast CS5 Evo
3' - 11" 2' - 6" 7' - 6" Yes No No No No No 50/60 Hz 230V No >
.30 m/s EQ3.004.00 AB8A BARRIER HOLDING Cage Change Stations
Tecniplast CS5 Evo 3' - 11" 2' - 6" 7' - 6" Yes No No No No No
50/60 Hz 230V No > .30 m/s EQ3.004.00 AB8A BARRIER HOLDING Cage
Change Stations Tecniplast CS5 Evo 3' - 11" 2' - 6" 7' - 6" Yes No
No No No No 50/60 Hz 230V No > .30 m/s EQ3.004.00 AB18
QUARANTINE Cage Change Stations Tecniplast CS5 Evo 3' - 11" 2' - 6"
7' - 6" Yes No No No No No 50/60 Hz 230V No > .30 m/s
EQ3.005.00 AB22 RECEIVING Animal Transfer Station Anigard II by
Baker 4' - 4" 2' - 6" 6' - 0" Yes No 70 FPM No No No No 10.3/15
amps 115V, AC No
EQ3.006.01 AB5B HOLDING Ventilated Cage Racks Single Sided
Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 45 CFM @ 0.22
in. H2O No No No No Outlet Yes EQ3.006.01 AB5B HOLDING Ventilated
Cage Racks Single Sided Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6"
Yes No 45 CFM @ 0.22 in. H2O No No No No Outlet Yes EQ3.006.01 AB5B
HOLDING Ventilated Cage Racks Single Sided Allentown IVC Rack 6' -
0" 1' - 10" 6' - 6" Yes No 45 CFM @ 0.22 in. H2O No No No No Outlet
Yes EQ3.006.01 AB5C HOLDING Ventilated Cage Racks Single Sided
Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 45 CFM @ 0.22
in. H2O No No No No Outlet Yes EQ3.006.01 AB6 RODENT SURGERY
Ventilated Cage Racks Single Sided Allentown IVC Rack 6' - 0" 1' -
10" 6' - 6" Yes No 45 CFM @ 0.22 in. H2O No No No No Outlet Yes
EQ3.006.01 AB8A BARRIER HOLDING/PROCEDURE Ventilated Cage Racks
Single Sided Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 45
CFM @ 0.22 in. H2O No No No No Outlet Yes EQ3.006.01 AB8A RECEIVING
Ventilated Cage Racks Single Sided Allentown IVC Rack 6' - 0" 1' -
10" 6' - 6" Yes No 45 CFM @ 0.22 in. H2O No No No No Outlet Yes
EQ3.006.01 AB18 QUARANTINE Ventilated Cage Racks Single Sided
Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 45 CFM @ 0.22
in. H2O No No No No Outlet Yes
EQ3.006.02 AB8A BARRIER HOLDING Ventilated Cage Racks Double Sided
Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 88 CFM @ 0.23
in. H2O No No No No Yes EQ3.006.02 AB8A BARRIER HOLDING Ventilated
Cage Racks Double Sided Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6"
Yes No 88 CFM @ 0.23 in. H2O No No No No Yes EQ3.006.02 AB8A
BARRIER HOLDING Ventilated Cage Racks Double Sided Allentown IVC
Rack 6' - 0" 1' - 10" 6' - 6" Yes No 88 CFM @ 0.23 in. H2O No No No
No Yes EQ3.006.02 AB8A BARRIER HOLDING Ventilated Cage Racks Double
Sided Allentown IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 88 CFM @
0.23 in. H2O No No No No Yes EQ3.006.02 AB8A BARRIER HOLDING
Ventilated Cage Racks Double Sided Allentown IVC Rack 6' - 0" 1' -
10" 6' - 6" Yes No 88 CFM @ 0.23 in. H2O No No No No Yes EQ3.006.02
AB8A BARRIER HOLDING Ventilated Cage Racks Double Sided Allentown
IVC Rack 6' - 0" 1' - 10" 6' - 6" Yes No 88 CFM @ 0.23 in. H2O No
No No No Yes EQ3.006.02 AB19 CAGES AND PENS Ventilated Cage Racks
Double Sided Allentown IVC Rack Yes 88 CFM @ 0.23 in. H2O
EQ3.006.02 AB19 CAGES AND PENS Ventilated Cage Racks Double Sided
Allentown IVC Rack Yes 88 CFM @ 0.23 in. H2O EQ3.006.02 AB19 CAGES
AND PENS Ventilated Cage Racks Double Sided Allentown IVC Rack Yes
88 CFM @ 0.23 in. H2O EQ3.006.02 AB19 CAGES AND PENS Ventilated
Cage Racks Double Sided Allentown IVC Rack Yes 88 CFM @ 0.23 in.
H2O EQ3.006.02 AB19 CAGES AND PENS Ventilated Cage Racks Double
Sided Allentown IVC Rack Yes 88 CFM @ 0.23 in. H2O EQ3.006.02 AB19
CAGES AND PENS Ventilated Cage Racks Double Sided Allentown IVC
Rack Yes 88 CFM @ 0.23 in. H2O EQ3.006.02 AB19 CAGES AND PENS
Ventilated Cage Racks Double Sided Allentown IVC Rack Yes 88 CFM @
0.23 in. H2O EQ3.006.02 AB19 CAGES AND PENS Ventilated Cage Racks
Double Sided Allentown IVC Rack Yes 88 CFM @ 0.23 in. H2O
EQ3.008.00 A105 SURGERY STERILE STORAGE Miscellaneous Equipment
Equipment Zone Yes No No No No No No
EQ3.009.01 AB13 HOLDING/RABBITS Cages & Racks - Rabbit Lab
Products 40305-MOD & AWS-SS 3' - 2" 2' - 1" 6' - 6" Yes No No
No No No No Water supply EQ3.009.01 AB13 HOLDING/RABBITS Cages
& Racks - Rabbit Lab Products 40305-MOD & AWS-SS 3' - 2" 2'
- 1" 6' - 6" Yes No No No No No No Water supply EQ3.009.01 AB13
HOLDING/RABBITS Cages & Racks - Rabbit Lab Products 40305-MOD
& AWS-SS 3' - 2" 2' - 1" 6' - 6" Yes No No No No No No Water
supply EQ3.009.01 AB13 HOLDING/RABBITS Cages & Racks - Rabbit
Lab Products 40305-MOD & AWS-SS 3' - 2" 2' - 1" 6' - 6" Yes No
No No No No No Water supply EQ3.009.01 AB13 HOLDING/RABBITS Cages
& Racks - Rabbit Lab Products 40305-MOD & AWS-SS 3' - 2" 2'
- 1" 6' - 6" Yes No No No No No No Water supply
EQ3.009.02 AB11 LA HOLDING Cages & Racks - Pig Lab Products
SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No Water
supply EQ3.009.02 AB11 LA HOLDING Dog/Pig Modular Pen Lab Products
SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No Water
supply EQ3.009.02 AB11 LA HOLDING Cages & Racks - Pig Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB11 LA HOLDING Cages & Racks - Pig Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB11 LA HOLDING Cages & Racks - Pig Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB12 LA HOLDING Cages & Racks - Dog Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB12 LA HOLDING Cages & Racks - Dog Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB12 LA HOLDING Cages & Racks - Dog Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB12 LA HOLDING Cages & Racks - Dog Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply EQ3.009.02 AB12 LA HOLDING/RABBITS Cages & Racks -
Dog Lab Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No
No No No Water supply EQ3.009.02 AB12 LA HOLDING/RABBITS Cages
& Racks - Dog Lab Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0"
Yes No No No No No No Water supply EQ3.009.02 AB12 LA
HOLDING/RABBITS Cages & Racks - Dog Lab Products SPCL-KENNEL 5'
- 0" 4' - 0" 7' - 0" Yes No No No No No No Water supply EQ3.009.02
AB12 LA HOLDING/RABBITS Cages & Racks - Dog Lab Products
SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No Water
supply EQ3.009.02 AB12 LA HOLDING Cages & Racks - Dog Lab
Products SPCL-KENNEL 5' - 0" 4' - 0" 7' - 0" Yes No No No No No No
Water supply
EQ3.011.01 AB14 DIRTY CAGE WASH Bedding Dump Station Lab Products
59020 3' - 10" 2' - 7" Yes No No No No No 60hz 15amp 115V, AC
No
EQ3.014.00 AB20 FOOD/BEDDING Refrigerator 263C-AEW-TS 2' - 8" 2' -
6" 5' - 10" Yes No No No No No 50hz 230V Yes
EQ3.017.00 A102 ANIMAL PREP/RECOVERY Drug Dispenser KL20 -
Kirbylester 1' - 0 1/2" 1' - 0 1/2" 1' - 2 1/2" Yes No Cat-5 No No
No No 110 V Outlet No
EQ3.018.00 A104B OPERATING ROOM Mobile C-Arm Philips BV Pulsera 7'
- 5" 2' - 2" Yes Yes No No No No 20amps 120V Yes EQ3.018.00 A104C
OPERATING ROOM Mobile C-Arm Philips BV Pulsera 7' - 5" 2' - 2" Yes
Yes No No No No 20amps 120V Yes EQ3.018.00 A105 SURGERY STERILE
STORAGE Mobile C-Arm Philips BV Pulsera 7' - 5" 2' - 2" Yes Yes No
No No No 20amps 120V Yes
EQ3.019.00 A104 CLEAN CAGE PREP Washing Machine GE Profile Energy
Star 4.1 Cu. Ft. Colossal Capacity Hight-Efficiency Washer Yes Yes
Yes 60Hz 10A 120V
EQ3.020.00 A104 CLEAN CAGE PREP Clothes Dryer GE 7.0 Cu. Ft..
Capacity DuraDrum Electric Dryer Yes Standard rear exhaust (vented
at floor level) 60Hz 22A 208V
EQ3.021.00 AB6 RODENT SURGERY Animal Recovery ICU Scanbur
Technology Warming Cabinet 48-VS-IV Yes No No 230V, 50/60 Hz
EQ3.022.00 AB19 CAGES AND PENS Floor Scrubber Square Scrub SQSEBG20
1' - 8" 1' - 2" Yes 120V
EQ3.023.00 AB7 CLEAN CAGE PREP RODI Yes No No No No No No
21
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A313
Room: Name Room:
Number Description Type Width Depth Height Drain Mixing Faucet Cold
Water Hot Water Single Faucet CW
CLEAN CAGE PREP AB7 Integral Stainless Steel Sink 181410.5 1' - 6"
1' - 2" 10 1/2" Yes Yes Yes Yes Yes DIRTY CAGE WASH AB14 Integral
Stainless Steel Sink 281512 2' - 4" 1' - 3" 1' - 0" Yes Yes Yes Yes
Yes ANIMAL PREP/RECOVERY AB-77 Integral Stainless Steel Sink
181410.5 1' - 6" 1' - 2" 10 1/2" Yes Yes Yes Yes No SURGICAL PACKS
AND SCRUBS AB-80 Integral Stainless Steel Sink 181410.5 1' - 6" 1'
- 2" 10 1/2" Yes Yes Yes Yes No SURGICAL PACKS AND SCRUBS AB-80
Stainless Steel Scrub Sink Scrub Sink 5' - 4" 2' - 3 1/2" 3' - 1"
Yes Yes Yes Yes No QUARANTINE AB-99 Handwash Sink See Mechanical
13" x 13" 1' - 1" 1' - 1" 9" Yes Yes Yes Yes No HOLDING/RABBITS
AB-100 Handwash Sink See Mechanical 13" x 13" 1' - 1" 1' - 1" 9"
Yes Yes Yes Yes No LA HOLDING/RABBITS AB-102 Handwash Sink See
Mechanical 13" x 13" 1' - 1" 1' - 1" 9" Yes Yes Yes Yes No LA
HOLDING AB-103 Handwash Sink See Mechanical 13" x 13" 1' - 1" 1' -
1" 9" Yes Yes Yes Yes No LA HOLDING AB-104 Handwash Sink See
Mechanical 13" x 13" 1' - 1" 1' - 1" 9" Yes Yes Yes Yes No
PROCEDURE/NECROPSY AB-105 Integral Stainless Steel Sink 181410.5 1'
- 6" 1' - 2" 10 1/2" Yes Yes Yes Yes Yes BARRIER HOLDING AB-108
Handwash Sink See Mechanical 13" x 13" 1' - 1" 1' - 1" 9" Yes Yes
Yes Yes No VESTIBULE AB-109 Integral Stainless Steel Sink 181410.5
1' - 6" 1' - 2" 10 1/2" Yes Yes Yes Yes No BARRIER HOLDING AB-113
Handwash Sink See Mechanical 13" x 13" 1' - 1" 1' - 1" 9" Yes Yes
Yes Yes No RODENT SURGERY AB-114 Integral Stainless Steel Sink
181410.5 1' - 6" 1' - 2" 10 1/2" Yes Yes Yes Yes Yes VESTIBULE
AB-115 Integral Stainless Steel Sink 181410.5 1' - 6" 1' - 2" 10
1/2" Yes Yes Yes Yes Yes PROCEDURE AB-116 Integral Stainless Steel
Sink 181410.5 1' - 6" 1' - 2" 10 1/2" Yes Yes Yes Yes Yes HOLDING
AB-117 Handwash Sink See Mechanical 13" x 13" 1' - 1" 1' - 1" 9"
Yes Yes Yes Yes No HOLDING AB-118 Handwash Sink See Mechanical 13"
x 13" 1' - 1" 1' - 1" 9" Yes Yes Yes Yes No
GAS FIXTURE SCHEDULE Room: Name Room: Number Description Type
Comments
RODENT SURGERY AB-114 Gas cock - Air A Wall mounted. RODENT SURGERY
AB-114 Gas cock - Air A Wall mounted. RODENT SURGERY AB-114 Gas
cock - Air A Wall mounted. RODENT SURGERY AB-114 Gas cock - Air A
Wall mounted. RODENT SURGERY AB-114 Gas cock - Carbon Dioxide CO2
Wall mounted. RODENT SURGERY AB-114 Gas cock - Carbon Dioxide CO2
Wall mounted. RODENT SURGERY AB-114 Gas cock - Carbon Dioxide CO2
Wall mounted. RODENT SURGERY AB-114 Gas cock - Carbon Dioxide CO2
Wall mounted. RODENT SURGERY AB-114 Gas cock - Oxygen O2 Wall
mounted. RODENT SURGERY AB-114 Gas cock - Oxygen O2 Wall mounted.
RODENT SURGERY AB-114 Gas cock - Oxygen O2 Wall mounted. RODENT
SURGERY AB-114 Gas cock - Oxygen O2 Wall mounted. RODENT SURGERY
AB-114 Gas cock - Vacuum V Wall mounted. RODENT SURGERY AB-114 Gas
cock - Vacuum V Wall mounted. RODENT SURGERY AB-114 Gas cock -
Vacuum V Wall mounted. RODENT SURGERY AB-114 Gas cock - Vacuum V
Wall mounted.
22
23
120V120 VOLTAGE ELECTRICAL RECEPTACLE 208V208 VOLTAGE ELECTRICAL
RECEPTACLE AS ADJUSTABLE SHELF ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR BA BASE CABINET - OPEN SHELF BB BASE
CABINET - DOOR BBM BASE CABINET - DOOR - MOBILE BC BASE CABINET -
DOOR DRAWER BCM BASE CABINET - DOOR DRAWER - MOBILE BD BASE CABINET
- DRAWERS BDM BASE CABINET - DRAWERS - MOBILE BEM BASE CABINET -
DRAWERS - MOBILE BN BASE CABINET - ACID BP BASE CABINET - FLAMMABLE
BQ BASE CABINET - BASE BS BASE CABINET - SINK BSM BASE CABINET -
SINK - MOBILE BSC BIOLOGICAL SAFETY CABINET CG CASEWORK GROUP CFCI
CONTRACTOR FURNISHED CONTRACTOR INSTALLED CHW CHILLED WATER CO2
CARBON DIOXIDE CP CLOSURE PANEL CR CYLINDER RESTRAINTS CS CUP SINK
CSP CEILING SERVICE PANEL CT CASEWORK TYPE CW COLD WATER DC BASE
CABINET - SUSPENDED DD DEPTH D DATA RECEPTACLE DI DEIONIZED WATER
EP EMERGENCY POWER EQ EQUAL ER EPOXY RESIN ESEW EMERGENCY SHOWER
EYE WASH EW EYE WASH/DRENCH HOSE EXH EXHAUST FA FAUCET ASSEMBLY FC
FILE CABINET FD FLOOR DRAIN FF&E FURNITURE, FIXTURES, &
EQUIPMENT FH FUME HOOD FP FOOT PEDAL OR SENSOR OPERATED FS FIXED
SHELF GC GAS COCK GFI GROUND FAULT INTERRUPTER GR COUNTER GROMMET
HB HOSE BIBB HH HEIGHT HP HIGH PRESSURE HW HOT WATER IFA ISLAND
FRAME ASSEMBLY IS INNER SHELF ISRSS ISLAND SERIES REAR SUPPORT
STRUCTURE KS KNEE SPACE KSD KNEE SPACE DRAWER KSR KNEE SPACE RAIL
LS LIGHT SWITCH LM LAB MODULE MB MARKERBOARD MF MIXING FAUCET NIC
NOT IN CONTRACT OFCI OWNER FURNISHED CONTRACTOR INSTALLED OFOI
OWNER FURNISHED OWNER INSTALLED OH OPPOSITE HAND PB GLASSWARE
PEGBOARD PE POINT EXHAUST PT POTTING BENCH PC PIPE CHASE PTD PAPER
TOWEL DISPENSER RB RUBBER BASE RO REVERSE OSMOSIS WATER RO/DI
REVERSE OSMOSIS DEIONIZED WATER SA OVERHEAD SHELVING SC SUSPENDED
CABINET SCG SINK CABINET GROUP SD SOAP DISPENSER SF SQUARE FOOTAGE
SG SPECIALTY GAS SIM SIMILAR SK SINK SKA SINK FIXTURE ASSEMBLY SR
SURFACE RACEWAY SS STAINLESS STEEL TBD TO BE DETERMINED TC TALL
CASE - GLASS DOORS TL TASK LIGHT TP TALL CABINET - FLAMMABLE TR
TRASH RECEPTACLE TT TABLE - ADJUSTABLE HEIGHT TTB TABLE -
ADJUSTABLE HEIGHT - BACKSPLASH TTS TABLE - ADJUSTABLE HEIGHT - SINK
TTM TABLE - ADJUSTABLE HEIGHT - MOBILE TU TABLE - FIXED HEIGHT UC
UNDER COUNTER UON UNLESS OTHERWISE NOTED V VACUUM VB VACUUM BREAKER
VIF VERIFY IN FIELD WB WALL CASE - DOOR WG WALL GROUP WS WIRE
SHELVING WSL WIRE SHELVING - WITH GROW LIGHTS WSRSS WALL SERIES
REAR SUPPORT STRUCTURE WW WIDTH
1. CASEWORK IS IDENTIFIED WITH A FOUR PART TAG: CT WWDDHH
CT=CASEWORK TYPE WW=NOMINAL WIDTH IN INCHES DD=NOMINAL DEPTH IN
INCHES HH=NOMINAL HEIGHT IN INCHES
2. PROVIDE FINISHED SIDE/BACK CLOSURE/INSERT PANELS AT ALL KNEE
SPACE UNITS AND KNEE SPACE DRAWER UNITS AND UNDER COUNTER
EQUIPMENT. COORDINATE RECEPTACLES INDICATED WITH ELECTRICAL
DIVISION.
3. RUBBER BASE TO BE APPLIED TO FIXED CASEWORK/COMPONENTS AND KNEE
SPACES.
4. PROVIDE TASK LIGHTS AT UNDERSIDE OF SHELVES WHERE INDICATED ON
ELEVATIONS. FIXTURES TO BE CENTERED ON UNIT. PROVIDE FIXTURES IN
LENGTHS AS NOTED ON ELEVATIONS. NO VALANCE UNLESS OTHERWISE NOTED
ON ELEVATION.
5. PROVIDE SURFACE RACEWAYS BENEATH LOWEST SHELF AS INDICATED ON
ELEVATIONS.
6. PROVIDE RAIL COVERS AT ALL WALL FRAME ASSEMBLIES.
7. ALL SINK ACCESSORIES TO BE OWNER PROVIDED AND OWNER INSTALLED
UON.
8. FACEPLATES FOR RECEPTACLES BY CASEWORK MANUFACTURER. DEVICES BY
DIVISION 16.
9. PROVIDE LOCKS AT ALL CASEWORK NOTED WITH * (ASTERISK).
10. SEE EQUIPMENT PLANS AND EQUIPMENT SCHEDULES FOR EQUIPMENT AND
SERVICES REQUIRED FOR THIS PROJECT.
11. ALL COUNTERTOPS AND SINKS ARE STAINLESS STEEL UON. SEE
SPECIFICATION SECTION 12 30 00.
GENERAL CASEWORK NOTES CC = CONTRACTOR FURNISHED AND INSTALLED,
CONSTRUCTION FUNDS (EQ1.XX.XXX)
EXISTING EQUIPMENT TO BE RELOCATED BY CONTRACTOR (EQ2.XX.XXX)
CF = CONSTRUCTION FUNDS, VA FURNISHED, INSTALLED BY VA OR
CONTRACTOR (EQ3.XX.XXX)
VC = VA FURNISHED CONTRACTOR INSTALLED, VHA FUNDS FOR PURCHASE,
CONSTRUCTION FUNDS FOR INSTALLATION (EQ3.XX.XXX)
VV = VA FURNISHED AND INSTALLED, VHA APPROPRIATION
(EQ3.XX.XXX)
EQUIPMENT PROCUREMENT
LINETYPE LEGEND
CF, VC, OR VV =
- 1 1"
3' - 0"
ELEVATION SIDE
1' - 10"
PROVIDE LOCKS AS REQUIRED BY GENERAL CASEWORK NOTE NUMBER 9
1' - 1
CASEWORK DESCRIPTION
Similar: BS 482235
BC 182235 Base Cabinet - door drawer 1 door 1 drawer
BC 302235 Base Cabinet - door drawer 2 doors 2 drawers
Similar: BC 362235
7' - 1
AS 361206 Adjustable Shelf
AS 360806 Adjustable Shelf
BSCS 533236 BIOSAFETY CABINET STAND
SEE EQUIPMENT PLANS AND SCHEDULES FOR BIOSAFETY CABINET
SERVICES
TT 723036 Table - adjustable height
Similar: TT 543030
SI TT
IN G
HE IG
HT 2'
- 4 5
/1 6"
ST AN
DI NG
Add-a-drawerALL ADD-A-DRAWERS HAVE A REMOVABLE EXTENDED WORK
SURFACE.
ALL MOBILE BASE CABINETS HAVE A RETRACTING GRAB BAR HANDLE AND
FRONT AND REAR RUBBER BUMPERS.
SF SKA4
1 MF mixing faucet (CW/HW) 1 single faucet (CW)
SK 181410.5 Integral Stainless Steel Sink 18"W x 14"D x
10.5"H
SF SKA4
1 MF mixing faucet (CW/HW) 1 single faucet (CW)
SK 181410.5 Integral Stainless Steel Sink 28"W x 15"D x 12"H
SF MF
1 MF mixing faucet (CW/HW)
SK 181410.5 Integral Stainless Steel Sink 18"W x 14"D x
10.5"H3'
- 0 "
PLAN
ELEVATION
SEE EQUIPMENT PLANS AND SCHEDULES FOR BIOSAFETY CABINET
SERVICES
2' - 1
1 /3
2"
TC 361684 Tall Cabinet - glass doors 2 doors 1 fixed shelf (middle
shelf) 4 adjustable shelves
AS 541206 on wall rails
3' - 0
TT 543030 Table - adjustable height
GC1 Gas Cock wall mounted 1 nozzle see plans for locations and
types
WB 241337 Wall case - door 1 door 2 adjustable shelves
Similar: WB 151631, WB 241331
WC 541631 Wall case - glass door 2 doors 2 adjustable shelves
6" 6"
Handwash Sink See mechanical
Hose Bibb See mechanical
Point Exhaust EQ1.011.00
KS 302235 Knee space rail Rear knee space closure panel with
electrical outlet cutout
BB 362235 Base Cabinet - door 2 doors
Similar: BB 482235
WB 361331 Wall case - door 2 doors 2 adjustable shelves
Similar: WB 481331
8' - 0
1' - 8
1 /2
1' - 0
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
A314
GWB
13 ' -
0 "
"
3' x 4'9" MIRROR
GWB 2"X6" BULLNOSE CT3
GLASS TILE 1 CT4
GLASS TILE 2 CT5
6x12 COVE BASE CT76x6 WALL TILE CT2 6"X6" WALL TILE CT2
6"X6" BULLNOSE CT8
6" x 6" WALL TILE CT2
2
7
1
5
4
8
4 SOAP DISPENSER, V.C.
6 SEMI-RECESSED WASTE RECEPTACLE, C.C.
7 VERTICAL GRAB BAR, C.C.
8 ALUM. FLUSH MOUNT SUPPORT BRACKET 2"x2"x1/4" L-SHAPED. VERTICAL
LEG MOUNTED TO STUD OR BLOCKING BEHIND THE DRYWALL. RAKKS "EH"
BRACKET OR EQUAL, C.C.
6" 6'
6x6 COVE BASE
2x6 PRESSURE TREATED BLOCKING W/ 1/2" PRESSURE TREATED PLYWOOD
TOP.
2x6 PRESSURE TREATED BLOCKING @ 16" OC
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
6 INTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A401
10 INTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A401
SCALE: 1/2" = 1'-0"A401
14 INTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A401
16 INTERIOR ELEVATION
SCALE: 1/2" = 1'-0"A401
19 LOCKER SECTION
8
C.G.
6
7
7
1
9
1
1
2
1
7
7
7
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
4 PLAN DETAIL
SCALE: 1" = 1'-0"A501
8 PLAN DETAIL
SCALE: 1" = 1'-0"A501
12 PLAN DETAIL
SCALE: 1" = 1'-0"A501
16 PLAN DETAIL
SCALE: 1" = 1'-0"A501
17 PLAN DETAIL
DOOR TYPES
Life Safety Fire Exit Plans
Room number ID signage is mounted at 2" for the edge of the door
frame, mounted on the handle side of the door.
The top of the sign shall be mounted at 64" from the floor.
Contractor shall be responsible for removal of existing signage and
protecting for reinstallation. Any signage not being reused shall
be turned over to the owner. New and existing room identification
signage should be installed to attached sketch.
Contractor shall provide one room identification sign for each
numbered area on the plan. Where two or more doors into a room
exist, provide one sign per room entrance at the main entrance to
the room - verify with the owner. Room identification signage is
not required at corridors.
Signs shall be installed using standard #10 x 1" flat head screws
with blue plastic dry-wall plugs unless being installed on concrete
or lead line walls. For concrete and lead lined walls, hand signs
with GE #1200 clear silicone adhesive. Use double faced tape to
hold them in place until silicone cures.
Leave room identification titles / messages slots blank when
ordering. The VA will provide the inserts.
Any existing directory signage or overhead identification signage
and hardware should be removed by the contractor and turned over to
the VA. New directory and overhead signage will be provided and
installed by the VA.
The Architect shall identify locations for evacuation plans on the
drawing. Contractor shall provide and install the evacuation plan
frames and plastic insert. The VA will provide the plan artwork for
the sign.
Submittals - Contractor shall provide a listing of sign types, room
identification numbers, quantities and finishes for approval to the
VA prior to purchase.
1 1/4"STUD3/4"
1/2" 1/2"
2"
LEAD LINED GWB GWB EXTENDED AS REQ'D TO NEAREST INSIDE CORNER
2 1/2"x2"x3/8"ANGLES, FASTEN BOTH ENDS
FRAME MUSE BE AT LEAST 2 PIECE TO INSTALL OVER ANGLE
WHEN LEAD OCCURS ON THIS PARTITION FACE, EXTEND LEAD
SHIEDLING COMPLETELY AROUND INSIDE FACE OF BUCK
GROUT FRAME
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
AND DETAILS
RATING UNDERCUT TYPE MATERIAL BASEMENT
AB2/A PAIR 3' - 0" 8' - 0" 1 3/4" H SS N/A 0' - 0" 2 SS 9 AB2/B
PAIR 3' - 0" 8' - 0" 1 3/4" H SS N/A 0' - 0" 2 SS 6 ELECTRONIC CARD
READER AB3/A 3' - 0" 7' - 0" 1 3/4" H WOOD N/A 0' - 0" 3 HM 33
AB4/A 3' - 0" 7' - 0" 1 3/4" H WOOD N/A 0' - 0" 3 HM 36
AB4A/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 35 AB4B/A 3'
- 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 34 AB5/A 3' - 6" 8' -
0" 1 3/4" H SS N/A 0' - 0" 1 SS 25
AB5A/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 31 AB5B/A 7' -
0" SS 4 SS 39 AB5C/A 7' - 0" SS 4 SS 39 AB6/A 3' - 6" 7' - 0" 1
3/4" W SS N/A 0' - 0" 1 SS 31 AB7/A PAIR 3' - 0" 8' - 0" 1 3/4" W
SS N/A 0' - 0" 2 SS 22 AB8/A 3' - 6" 8' - 0" 1 3/4" H SS N/A 0' -
0" 1 SS 25
AB8A/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 25 RED GLASS
LIGHT W/FLAP PANEL COVER AB8B/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0'
- 0" 1 SS 25 RED GLASS LIGHT W/FLAP PANEL COVER AB8C/A 3' - 6" 8' -
0" 1 3/4" W SS N/A 0' - 0" 1 SS 25 RED GLASS LIGHT W/FLAP PANEL
COVER AB9/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 18
AB10/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 30 SOUND
GASKETING AND DROP SEALS AB11/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0'
- 0" 1 SS 30 SOUND GASKETING AND DROP SEALS AB12/A 3' - 6" 8' - 0"
1 3/4" W SS N/A 0' - 0" 1 SS 30 SOUND GASKETING AND DROP SEALS
AB13/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 30 SOUND
GASKETING AND DROP SEALS AB14/A PAIR 3' - 0" 8' - 0" 1 3/4" W SS
N/A 0' - 0" 2 SS 15 AB14/B 3' - 0" 7' - 0" 1 3/4" F SS N/A 0' - 0"
1 SS 16 AB15/A PAIR 3' - 0" 8' - 0" 1 3/4" H SS N/A 0' - 0" 2 SS 7
AB15/B PAIR 3' - 0" 8' - 0" 1 3/4" H SS N/A 0' - 0" 2 SS 6
ELECTRONIC CARD READER AB16/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0' -
0" 1 SS 30 SOUND GASKETING AND DROP SEALS AB17/A PAIR 2' - 0" 7' -
0" 1 3/4" L WOOD N/A 0' - 0" ETR ETR 13 AB18/A 3' - 6" 8' - 0" 1
3/4" W SS N/A 0' - 0" 1 SS 17 AB19/A 3' - 6" 8' - 0" 1 3/4" W SS
N/A 0' - 0" 1 SS 25 AB20/A UNEVEN 5' - 0" 8' - 0" 1 3/4" F SS N/A
0' - 0" 2 SS 14 AB21/A UNEVEN 5' - 0" 8' - 0" 1 3/4" F SS N/A 0' -
0" 2 SS 15 AB22/A 2' - 6" 7' - 0" 1 3/4" L WOOD N/A 0' - 0" ETR ETR
18 AB23/A 3' - 6" 8' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 20 AB24/A 3'
- 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" ETR ETR 16 ACB-3/A PAIR 3' -
0" 8' - 0" 1 3/4" W SS B 0' - 0" 2 SS 2 ELECTRONIC CARD READER
ACB-4/A PAIR 2' - 6" 7' - 0" 1 3/4" W HM N/A 0' - 0" 2 ETR 5 48"
ACROVYN, ELECTRONIC CARD READER S1-B/A 3' - 8" 7' - 0" 1 3/4" W HM
B 0' - 0" ETR ETR 1
FIRST FLOOR A101/A PAIR 2' - 10" 7' - 0" 1 3/4" H SS N/A 0' - 0" 2
HM 8 A101/B PAIR 2' - 10" 7' - 0" 1 3/4" H WOOD N/A 0' - 0" 2 HM 4
A102/A UNEVEN 4' - 0" 7' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 27
A103/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" ETR ETR 16 A104/A
UNEVEN 4' - 0" 7' - 0" 1 3/4" W SS N/A 0' - 0" 2 SS 28
A104B/A 3' - 8" 7' - 0" 1 3/4" W SS N/A 0' - 0" 2 SS 29 LEAD LINED
A104B/B 3' - 8" 7' - 0" 1 3/4" W SS N/A 0' - 0" 2 SS 29 LEAD LINED
A104C/A 3' - 8" 7' - 0" 1 3/4" W SS N/A 0' - 0" 2 SS 29 LEAD LINED
A104C/B 3' - 8" 7' - 0" 1 3/4" W SS N/A 0' - 0" 2 SS 29 LEAD LINED
A105/A 3' - 0" 7' - 0" 1 3/4" F SS N/A 0' - 0" 1 SS 19 A105/B 3' -
6" 7' - 0" 1 3/4" W SS N/A 0' - 0" 1 SS 24 A106/A 3' - 0" 7' - 0" 1
3/4" F SS N/A 0' - 0" 1 SS 19 A107/A 3' - 0" 7' - 0" 1 3/4" F WOOD
N/A 0' - 0" 1 HM 32 A108/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' -
0" 1 HM 32 A109/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 21
HALF LIGHT A110/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 16
A111/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 16 A112/A 2'
- 6" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 16 A113/A 3' - 0" 7' -
0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A114/A 3' - 0" 7' - 0" 1 3/4"
F WOOD N/A 0' - 0" 1 HM 38 A115/A 3' - 0" 7' - 0" 1 3/4" G WOOD N/A
0' - 0" 3 HM 26 FULL GLASS W/SIDELIGHT
A115A/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 16 A115B/A
3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A115C/A 3' - 0"
7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A115D/A 3' - 0" 7' - 0" 1
3/4" F WOOD N/A 0' - 0" 1 HM 32 A116/A 3' - 0" 7' - 0" 1 3/4" F
WOOD N/A 0' - 0" 1 HM 37 A117/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A
0' - 0" 1 HM 32 A118/A PAIR 2' - 0" 7' - 0" 1 3/4" L WOOD N/A 0' -
0" ETR ETR 13 A119/A 3' - 0" 7' - 0" 1 3/4" G WOOD N/A 0' - 0" 3 HM
23 FULL GLASS W/SIDELIGHT
A119A/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A119B/A
3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A119C/A 3' - 0"
7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A119D/A 3' - 0" 7' - 0" 1
3/4" F WOOD N/A 0' - 0" 1 HM 32 A119E/A 3' - 0" 7' - 0" 1 3/4" F
WOOD N/A 0' - 0" 1 HM 21 A119F/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A
0' - 0" 1 HM 32 A120/A 3' - 0" 7' - 0" 1 3/4" L WOOD N/A 0' - 0"
ETR ETR 16 A121/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 16
A122/A 3' - 0" 7' - 0" 1 3/4" G WOOD N/A 0' - 0" 1 HM 21 HALF LIGHT
A123/A 3' - 0" 7' - 0" 1 3/4" H WOOD N/A 0' - 0" 1 HM 36 HALF LIGHT
A124/A 3' - 0" 7' - 0" 1 3/4" G WOOD N/A 0' - 0" 3 HM 23 FULL GLASS
W/SIDELIGHT
A124A/A 3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A124B/A
3' - 0" 7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A124C/A 3' - 0"
7' - 0" 1 3/4" F WOOD N/A 0' - 0" 1 HM 32 A124D/A 3' - 0" 7' - 0" 1
3/4" F WOOD N/A 0' - 0" 1 HM 32 A124E/A 3' - 0" 7' - 0" 1 3/4" F
WOOD N/A 0' - 0" 1 HM 32 AC1-1/A PAIR 2' - 10" 7' - 0" 1 3/4" H SS
N/A 0' - 0" 2 SS 4 AC1-2/A PAIR 2' - 10" 7' - 0" 1 3/4" H SS N/A 0'
- 0" 2 SS 4 AC1-3/A 3' - 0" 7' - 0" 1 3/4" F HM B 0' - 0" 1 HM 3
AC1-4/A 3' - 0" 7' - 0" 1 3/4" N WOOD N/A 0' - 0" 1 HM 10 S1-1/A 3'
- 8" 7' - 0" 1 3/4" N HM B 0' - 0" ETR ETR 12 S1-1/B 3' - 0" 7' -
0" 1 3/4" N HM B 0' - 0" 1 HM 11
SCALE: 1/4" = 1'-0"A601
6 WINDOW DETAILS
WINDOW KEYNOTES 1 EXISTING BRICK VENEER 2 EXISTING RIGID INSULATION
3 EXISTING CONCRETE MASONRY UNIT (CMU) 4 METAL STUD - SEE PARTITION
TYPES 5 GYPSUM WALLBOARD 6 ALUMINUM WINDOW FRAME 7 INSULATED
GLAZING 8 SEALANT AND BACKER ROD 9 SHIM AS REQUIRED 10 ALUMINUM
SILL BY WINDOW MANUFACTURER 11 MARBLE STOOL - MATCH EXISTING 12
SEALANT 13 METAL CORNER BEAD 14 6x6x3/8 STEEL LINTEL - 6" BEARING
ON EACH SIDE 15 4x3 1/2x5/16 STEEL LINTEL - 4" BEARING ON EACH SIDE
16 THRU WALL FLASHING W/ WEEP HOLES @ 24" OC MAX
SCALE: 1/2" = 1'-0"A601
SCALE: 3" = 1'-0"A601
4 TYPICAL DOOR DETAILS
DOOR DETAIL KEYNOTES 1 DOOR -SEE SCHEDULE 2 FRAME - SEE SCHEDULE 3
SEALANT - BOTH SIDES 4 JAMB ANCHOR - 3 PER SIDE
27
DOORS REQUIRE THE SAME LEAD THICKNESS AS THE WALLS: DOORS WITH LEAD
PLACED IN THE CENTER OF THE DOOR REQUIRE LEAD TO BE REMOVED TO
ALLOW INSTALLATION OF THE HANDLE AND LOCKSET. THIS CAUSES LEAKS AND
PREVENTS ACCEPTANCE.
THE VA RECOMMENDS DOORS BE PURCHASED WITH LEAD ON THE SIDE OF THE
DOOR THAT IS IN CONTACT WITH THE LEAD LINED DOOR FRAME WHEN THE
DOOR IS CLOSED AND ON THE SAME SIDE OF THE DOOR IN CONTACT WITH THE
ASTRAGAL.
DOOR FRAMES ARE TO BE COMPLETELY WRAPPED WITH THE SAME LEAD
THICKNESS AS THE WALLS.
WINDOW PANELS IN THE DOOR: THE DOORS WILL REQUIRE LEADED GLASS OR
ACRYLIC PANELS WITH THE SAME LEAD EQUIVALENCY AS THE WALLS. THE
LEAD GLASS OR ACRYLIC PANEL SHOULD BE PURCHASED FOR THE DESIGNATED
THICKNESS FOR A LEAD EQUIVALENCY AT 125 KVP X-RAY.
LEAD LINED DOORS GENERAL NOTES:
MARK DATE DESCRIPTION
CT
LVT2
LVT3
GENERAL FINISHES NOTES 1. ALL WALLS TO BE PAINTED PT1 U.N.O.
2. ALL WALLS IN AREAS OF EPOXY FLOOR TO HAVE EPOXY PAINT, COLOR
PT1.
3. (20) 36"X48" MAGNETIC MARKERGLASS. ONE IN EACH PRIVATE
OFFICE.
4. C.G. = CORNER GUARD. CORNER GUARDS ARE CORNER TRIM, FRY REGLET
#DMCT-1250 OR APPROVED EQUAL WITH A 6" TAPE AND JOINT COMPOUND. TO
BE PAINTED THE SAME AS ADJACENT WALL.
RUBBER BASE RB1- RUBBER BASE MANUFACTURER: JOHNSONITE COLOR: 29
MOONROCK SIZE: 4"
CARPET CPT1- CARPET MANUFACTURER: SHAW CONTRACT GROUP COLOR: BLUE
SMOKE 63481 STYLE: PRISMA TILE 59463 SIZE: 24" X 24"
CPT2- CARPET MANUFACTURER: SHAW CONTRACT GROUP COLOR: BLUE SMOKE
63481 STYLE: MIRROR IMAGE TILE SIZE: 24" X 24"
PAINT PT1- PAINT MANUFACTURER: BENJAMIN MOORE COLOR: 2147-70 ALPINE
WHITE
PT2- PAINT MANUFACTURER: BENJAMIN MOORE COLOR: 2132-50 PILGRIM
HAZE
PT3- PAINT MANUFACTURER: BENJAMIN MOORE COLOR: HC-14 PRINCETON
BLUE
PT4- PAINT MANUFACTURER: BENJAMIN MOORE COLOR: HC-149 BUXTON
BLUE
LUXURY VINYL TILE LVT1- LUXURY VINYL TILE MANUFACTURER: JOHNSONITE
COLOR: 886 BELUGA SERIES: OPTIMA SIZE: 24" X 24"
LVT2- LUXURY VINYL TILE MANUFACTURER: JOHNSONITE COLOR: 856 MORNING
SKY SERIES: OPTIMA SIZE: 24" X 24"
LVT3- LUXURY VINYL TILE MANUFACTURER: JOHNSONITE COLOR: 850 FLAN
SERIES: OPTIMA SIZE: 24" X 24"
CERAMIC TILE CT1- CERAMIC TILE FLOOR MANUFACTURER: CROSSVILLE
STYLE: COLOR BLOX COLOR: SANDBOX SIZE: 6x6 SQUARE
CT2- CERAMIC TILE WALL MANUFACTURER: DALTILE STYLE: SEMI
GLOSS/MATTE GROUP 1 COLOR: ALMOND / 0135 SIZE: 6X6 SQUARE
CT3- CERAMIC TILE WALL MANUFACTURER: DALTILE STYLE: SEMI
GLOSS/MATTE GROUP 1 COLOR: ALMOND / 0135 SIZE: 2X6 BULLNOSE
CT4- CERAMIC TILE WALL MANUFACTURER: DALTILE STYLE: MARACAS TILE
GLASS SOLIDS COLOR: P656 RAFFIA GOLD FROSTED SIZE: 1X1
CT5- CERAMIC TILE WALL MANUFACTURER: DALTILE STYLE: MARACAS TILE
GLASS SOLIDS COLOR: P663 EVERGREEN FROSTED SIZE:1X1
CT6- CERAMIC TILE WALL MANUFACTURER: DALTILE STYLE: SEMI
GLOSS/MATTE GROUP 1 COLOR: ALMOND / 0135 SIZE: 3X6 SQUARE
CT7- CERAMIC TILE FLOOR MANUFACTURER: CROSSVILLE STYLE: COLOR BLOX
COLOR: SANDBOX SIZE: 6X12 COVE BASE
CT8- CERAMIC TILE WALL MANUFACTURER: DALTILE STYLE: SEMI
GLOSS/MATTE GROUP 1 COLOR: ALMOND / 0135 SIZE: 6X6 BULLNOSE
QUARRY TILE QT1- QUARRY TILE MANUFACTURER: DALTILE STYLE: QUARRY
TILE COLOR: ARID FLASH 0Q48(2) SIZE: 6"X6"
BID DOCUMENTS
GATEHOUSE SUITE 401 PITTSBURGH, PENNSYLVANIA 15219 PH: 412.287.7333
FAX: 412.287.7334
www.ae-works.com
A
B
C
D
E
F
U ni
ve rs
ity a
nd W
oo dl
an d
Av en
ue Ph
ila de
lp hi
a, P
2 FIRST FLOOR FINISH PLAN
ROOM FINISH SCHEDULE ROOM
NUMBER NAME FLOOR FINISH
WALL FINISH CEILING MATERIAL RemarksNORTH SOUTH EAST WEST
ACB-5 CORRIDOR EPOXY EPOXY EP EP EP EP S-1 STAIR ETR FIRST FLOOR
A101 ELEVATOR LOBBY LVT RB PT1 PT1 PT1 PT1 ACT A102 ANIMAL
PREP/RECOVERY EPOXY INT PT1 PT1 PT1 PT1 MGWB A103 HAC EPOXY INT PT1
PT1 PT1 PT1 ACT A104 SURGICAL PACKS AND
SCRUBS EPOXY INT PT1 PT1 PT1 PT1 MGWB
A104A STERILE CORRIDOR EPOXY INT PT1 PT1 PT1 PT1 MGWB A104B
OPERATING ROOM EPOXY INT PT1 PT1 PT1 PT1 MGWB A104C OPERATING ROOM
EPOXY INT PT1 PT1 PT1 PT1 MGWB A105 SURGERY STERILE STORAGE EPOXY
INT PT1 PT1 PT1 PT1 MGWB A106 MECHANICAL WATER SYSTEM
- LAB GASSES EPOXY INT PT1 PT1 PT1 PT1 MGWB
A107 ADDITIONAL OFFICE CPT1 RB PT1 PT1 PT1 PT2 ACT A108 ADDITIONAL
OFFICE CPT1 RB PT1 PT1 PT1 PT2 ACT A109 SHARED OFFICE LVT RB PT1
PT1 PT3 PT1 ACT A110 MECH. CAVs SC ETR PT1 PT1 PT1 PT1 NONE A111
MECH. CAVs SC ETR PT1 PT1 PT1 PT1 NONE A112 STORAGE LVT RB PT1 PT1
PT1 PT1 GWB A112A COPY CENTER LVT RB PT1 PT4 PT1 PT4 ACT A113
COORDINATOR OFFICE CPT2 RB PT1 PT1 PT2 PT1 ACT A114 MEN'S CT CT PT1
& CT PT1 & CT PT1 & CT PT1 & CT ACT 5'-0" CT
WAINSCOT A115 SHARED WORK AREA CPT1 & CPT2 RB PT1 & WC PT1
PT1 PT1 ACT A115A FILES LVT RB PT1 PT1 PT1 PT1 ACT A115B IRB COORD.
CPT1 RB PT1 PT1 PT3 PT1 ACT A115C IRB COORD. CPT1 RB PT1 PT1 PT3
PT1 ACT A115D PROGRAM COORD CPT1 RB PT1 PT1 PT1 PT3 ACT A116
WOMEN'S CT CT PT1 & CT PT1 & CT PT1 & CT PT1 & CT
ACT 5'-0" CT WAINSCOT A117 IRB CHAIR CPT1 RB PT3 PT1 PT1 PT1 ACT
A118 DATA LVT RB PT1 PT1 PT1 PT1 NONE A119 SHARED WORK SPACE CPT1
& CPT2 RB PT1 PT1 PT1 PT1 & WC ACT A119A COMPLIANCE OFFICER
CPT1 RB PT1 PT1 PT2 PT1 ACT A119B SAFETY OFFICER CPT1 RB PT1 PT1
PT1 PT2 ACT A119C SAFETY COORDINATOR CPT1 RB PT1 PT2 PT1 PT1 ACT
A119D COMPLIANCE ASST. CPT1 RB PT2 PT1 PT1 PT1 ACT A119E PREF
ADMIN. ASSIST. CPT1 RB PT1 PT1 PT2 PT1 ACT A119F PREF DIRECTOR CPT1
RB PT1 PT1 PT1 PT2 ACT A120 ELEC LVT RB PT1 PT1 PT1 PT1 NONE A121
STORAGE LVT RB PT1 PT1 PT1 PT1 ACT A122 CONFERENCE CPT1 & CPT2
RB PT1 PT1 PT1 PT4 ACT A123 BREAK ROOM LVT RB PT1 PT1 PT1 PT4 ACT
A123A MAIL ROOM LVT RB PT4 PT4 PT4 PT4 ACT A124 SHARED WORK AREA
CPT1 & CPT2 RB PT1 PT1 PT1 & WC PT1 ACT A124A ORDERING
CLERK CPT1 RB PT1 PT1 PT1 PT3 ACT A124B BA CPT1 RB PT1 PT3 PT1 PT1
ACT A124C AO/VP CPT1 RB PT1 PT3 PT1 PT1 ACT A124D ACOS CPT1 RB PT3
PT1 PT1 PT1 ACT A124E HR AO CPT1 RB PT1 PT1 PT3 PT1 ACT AC1-1
SECURE CORRIDOR EPOXY INT PT1 PT1 PT1 PT1 MGWB AC1-2 CORRIDOR LVT
RB PT1 PT1 PT1 PT1 ACT AC1-3 CORRIDOR LVT RB PTI PT1 PT1 PT1 ACT A