    Coupling Capacitor VoltageTransformers TransientsFundamentals

    Roger Hedding ABB Dousman,WI

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    2/31

    Not this Transient

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    3/31

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    4/31

    Agenda

    Introduction

    Capacitor Voltage Transformer Design

    Transient Response

    Transient Response Effect on DistanceRelays

    Selection of Capacitor Voltage Transformer

    Conclusion

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    5/31

    Why Capacitor Voltage Transformer and What isthe Problem ?

    Voltage transformer needed to transform system

    voltage to voltage usable to IED.

    Wire wound voltage transformers not economical

    above 138kV.Capacitor voltage transformers consist of

    capacitors and inductors that can discharge and

    cause problems

    Not a problem for e/m relays.

    Faster sol id state and microprocessor relays need

    attention

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    6/31

    Capacitor Voltage Transformer Cross Section

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    7/31

    CVT Schematic

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    8/31

    CVT Equivalent Circuit

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    9/31

    Transient response

    Ability to reproduce rapid changes in

    the primary voltage.

    The remaining secondary voltage after aspecific t ime due to a short circuit on

    the primary voltage

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    10/31

    Transient response

    Transient oscil lations in the secondary

    Two components

    High frequency component

    600 4000 Hz

    Damped out in 10 milliseconds

    Low frequency component

    2 15 Hz

    Lasts much longer

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    11/31

    Capacitor Voltage Transformer Transient Response

    Transient Response function of

    Equivalent Capacitance

    Voltage Tap Ferroresonant Suppression

    Connected Burden

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    12/31

    Transient Response vs Capacitance

    Early work by Rusnak and Sweetana vintage 1970s

    345kV PCA-7 CCVT

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    13/31

    Transient Response vs Tap Voltage

    Early work by Rusnak and Sweetana vintage 1970s

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    14/31

    Transient Response vs Capacitance and Tap V

    Early work by Rusnak and Sweetana vintage 1970s

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    15/31

    Transient Response Vs. Ferroresonant Suppression

    Early work by Rusnak and Sweetana vintage 1970s

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    16/31

    Transient Response vs Burden

    Early work by Rusnak and Sweetana vintage 1970s

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    17/31

    What has changed in modern day CVT design ?

    Higher tap voltage up to 13kV

    Higher capacitance

    Changes in Ferroresonant suppression

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    18/31

    Transient Response for Current Design

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    19/31

    CVT Design Choices

    Under control of

    Designer

    Stack

    Capacitance

    Ferroresonant

    Suppression

    Tap voltage

    Under control of

    user

    Burden

    Stack capacitance

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    20/31

    CVT Transient Response Effect on DistanceRelays

    Impedance relays rely on

    accurate information of CTs

    and PTs to calculateimpedance to fault.

    CVT transients cause

    erroneous information to be

    presented to the relay Transients last a relatively

    short period of time

    Zone 2 and Zone 3 timers

    are set much longer the

    transient time period. Zone 2 and Zone 3

    impedance relays not

    effected by CVT Transient

    Zone 1 relay with nointentional delay will be

    effected

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    21/31

    Factors effecting impedance relay

    Type of fault

    Fault incidence angle

    Source Impedance Ratio of

    protected line

    Load current magnitude and

    direction

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    22/31

    Franklin and Horton Paper

    How much does zone 1 setting need to

    be pulled back so it wont overrreach due

    to CVT transient ?

    Used CVT with active Ferroresonant

    suppression

    Worst case

    Phase phase fault

    Heavily loaded line flowing toward

    relay

    Fault occurs at voltage zero

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    23/31

    Impedance trajectories for Ideal VT and CVT

    Franklin and Horton Determining Distance Relay Zone 1 Reach Settings to Prevent CCVT Transient Overreach

    Phase Phase fault

    SIR = 5

    Zline = 0.1+J1.0

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    24/31

    Maximum Reach to compensate for CVT Transient

    Franklin and Horton Determining Distance Relay Zone 1 Reach Settings to Prevent CCVT

    Transient Overreach for a particular relay

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    25/31

    Modern Microprocessor relays

    Use low pass filters and counters to mitigate

    effects of CVT transients

    Security comes at price of speed

    Relay operation may be delayed by up to 10msec

    Some manufactures use CVT Transient

    filtering as setting (yes/no) in case

    conventional wire wound VTs are used.

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    26/31

    Capacitance Selection for CVT

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    27/31

    Recommend EMTP Studies

    Several models of CVTs have been developed for use with

    EMTP Program.

    To understand how a particular CVT will respond

    on a given power system recommend EMTP Study

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    28/31

    Conclusion

    Reviewed CVT Design

    For lower CVT Transient

    High Capacitance

    High Tap Voltage

    Passive Ferroresonant Circuit

    Lower Burden

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    29/31

    Conclusion

    Due to long time delay settings Zone 2 and Zone

    3 relays typically not effected by CVT Transient

    Zone 1 relays with no intentional delay subject to

    overreach as a result of CVT transient.

    Factors influencing Zone 1 overreach

    SIR

    Line Loading

    Type of Fault

    Fault inception angle

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    30/31

    Conclusion

    Modern relays employ filtering techniques to

    lessen impact of CVT transient

    For further questions on your system do

    EMTP study

  • 8/12/2019 1 4-3 am coupling capacitor voltage transformer transient fundamentals [frp-1]

    31/31