86
1 2002 National Electrical Code Changes Developed and Presented by: The Codes and Standards Group of Schneider Electric Where We Started

1 2002 National Electrical Code Changes Where We Started

Embed Size (px)

Citation preview

Page 1: 1 2002 National Electrical Code Changes Where We Started

1

2002 National Electrical Code

Changes

Developed and Presented by:The Codes and Standards Group of

Schneider Electric

Where We Started

Page 2: 1 2002 National Electrical Code Changes Where We Started

2

Development Timeline

Proposal DeadlineNovember 5, 1999

Code-MakingPanels Meet

Jan 10-22, 2000

Written Ballots DueFeb 17 (or 24),

2000

Technical CorrelatingCommittee Meeting

May 8-12, 2000

NEC Report on Comments Available

July 14, 2000

Public Comment

Development Timeline

Public CommentsDue to NFPA

October 27, 2000

Code-MakingPanels meet

Dec 4-16, 2000

Written Ballots Due

Jan 5 (or 12), 2001

Technical CorrelatingCommittee Meeting

Feb 25 - Mar 1

NEC Report onComments Available

April 16, 2001

NFPA AnnualMeeting

May 13-17, 2001

Standards Council hears

Appeals on July 11, 2001

2002 NEC Issued with

Effective date of August 2, 2001

Page 3: 1 2002 National Electrical Code Changes Where We Started

3

Use of the 2002 NEC

l 2002 is the Latest Edition of NFPA 70l Most jurisdictions specify what edition of

the NEC they followl Adoption process must recognize the 2002

edition in order for it to be the “active” document in the locality

l Some jurisdictions have already completed process to utilize the 2002 edition on January 1, 2002n e.g. North Carolina, Massachusetts

l Other jurisdictions may not adopt the 2002 edition until some future date

Numbering FormatFrom Dash to Dot

Page 4: 1 2002 National Electrical Code Changes Where We Started

4

Acronyms

l 2002 NEC will use standard acronymsl Examples

n RMC – Rigid Metal Conduitn RNMC – Rigid Nonmetallic Conduitn EMT – Electrical Metallic Tubingn LFMC – Liquidtight Flexible Metal Conduitn ENT – Electrical Nonmetallic Tubing

n IMC – Intermediate Metal Conduitn NUCC – Nonmetallic Underground Conduit with Conductorsn AC – Armored Cablen NM – Nonmetallic sheathed cable

Article 80 (New)

l Provides a set of model administrative rules to apply and enforce the NEC

l Coversn Inspectionn Investigation of electrical firesn Review of construction plans, drawings and

specificationsn Design, alteration, modification, construction,

maintenance and testing

n Regulation and control of special events

l Article 80 is informative only (not part of the Code) unless specifically adopted by the jurisdiction

Administration and Enforcement

Page 5: 1 2002 National Electrical Code Changes Where We Started

5

90.1(D) - Purpose

l NEC addresses fundamental principles of protection for safety contained in IEC 60364-1, Section 131

l Protection against:n Electrical shockn Thermal effectsn Overcurrent

n Fault-currentsn Overvoltage

Relation to International Standards

90.2(B)(5) – ScopeNot Covered

Service drops or laterals and associated metering

Located in legally established easements, rights of way, etc and recognized by regulatory agencies

Under exclusive control of a utility:

On property owned or leased by the utility for purpose of communications, metering, generation, control, transformation, transmission, or distribution of electric energy.

Page 6: 1 2002 National Electrical Code Changes Where We Started

6

90.3

Chapter 1 - General

Chapter 2 - Wiring and Protection

Chapter 3 - Wiring Methods and Materials

Chapter 4 - Equipment for General Use

Chapter 5 - Special Occupancies

Chapter 6 - Special Equipment

Chapter 7 - Special Conditions

Chapter 8 - Communications Systems

Chapter 9 - Tables

Annex A through Annex D

Applies generally to all electrical installations

Supplements or modifies Chapters 1 through 4

Information only not mandatory

Applicable as referenced

Chapter 8 is not subject to the requirements of Chapters 1 through 7 except as specifically referenced in Chapter 8

{}

}}}

Code Arrangement

90.4

l The authority having jurisdiction can waive specific requirements or permit alternative methods

l Only allowed where “equivalent safety” is assured

l Now requires “special permission”n Special permission as defined in Article

100 requires written consent of the authority having jurisdiction

Enforcement

Page 7: 1 2002 National Electrical Code Changes Where We Started

7

90.7Examination of Equipment for Safety

Definition of “Listed” in Article 100 states that products must meet appropriate designated standards.

90.7 states that examination of equipment for safety under standard conditions provide a basis for approval.

What are the “appropriate” designated standards?

90.7 FPN No. 3 notes that Annex A contains and informative product standards list

Annex A – Product Safety Standards

• Informative only

• List of standards used for product listing

• Makes the connection between the Code rules and properly evaluated products

90.9 – Units of Measurement

l NEC now has metric as the first dimension listedl The conversions are not exact

n e.g. 1m (3 ft)

l The installation can be made to either the SI (metric) or the “inch-pound” units

l Wire sizes did not change – still AWG and kcmil

Compliance

Page 8: 1 2002 National Electrical Code Changes Where We Started

8

Article 100 – Definitions

l The organization, office, or, individual responsible for approving equipment, materials, an installation, or a procedure.

l This term is standardized through out the NFPA system

l Examples includen Public safety – electrical inspector, fire marshal,

fire chief, building official, others having statutory authority

n Insurance purposes – insurance inspection department, rating bureau

n Others – property owner or designeen Government – commanding officer,

departmental official

Authority Having Jurisdiction

Article 100 - DefinitionsGround-Fault Circuit Interrupter

Definition now makes it clear that a device intended to provide protection of personnel must be a Class A device.

Page 9: 1 2002 National Electrical Code Changes Where We Started

9

Article 100 - DefinitionsLuminaire

A complete lighting unit consisting of a lamp or lamps together with the parts designed to distribute the light, to position and protect the lamps and ballast (where applicable), and to connect the lamps to the power supply.

Fixture

Lighting fixtureLuminaire

Article 100 – DefinitionsQualified Person

One who has the skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training on the hazards involved.

Page 10: 1 2002 National Electrical Code Changes Where We Started

10

Article 100 – Definitions

l “That which is built or constructed”

l Not previously defined in the NEC

l Compatible with other building codes and standards

Structure

110.12(A) – Mechanical Execution of Work

l Combines the requirements in Article 110 with the requirements covering cabinets and cutout boxes

l Applies to boxes, raceways, auxiliary gutters, cabinets, cutout boxes, meter socket enclosures, equipment cases and housings

l Must be substantially equivalent to the wall of the equipment

l Metallic plugs in nonmetallic enclosures must be recessed at least 6 mm

Unused Openings

Box

Close all unused openings

Page 11: 1 2002 National Electrical Code Changes Where We Started

11

110.14(C) – Electrical TerminationsTemperature Limitations

Ampacities for conductors at equipment terminations must be

based on Table 310.16

Ampacity of the conductor (for ambient adjustment and derating) is permitted to be based

on appropriate table (e.g. 310.17 for single conductors in free-air)

110.15 (new)

l New section added to require the marking of the high- leg of a 4-wire delta connect system with orange color or other effective means

l Identification required at each point on the system where a connection is made if the grounded conductor is also present

High-leg Marking

208V

120V120V

Page 12: 1 2002 National Electrical Code Changes Where We Started

12

110.16 (New)Flash Protection

Switchboards, panelboards, industrial control panels, and motor control centers that are likely to be worked on while energized

Field Marked with a label to warn of potential electric arc flash hazards

Equipment in dwelling units is not included in the requirement

DANGER Arc -Flash Hazard

Protective Equipment requiredin accordance with NFPA 70E

Failure to use proper equipment can result in serious injury or death

110.26(C)(2) – Entrance to Working SpaceLarge Equipment

Equipment over 1200A and over 6 feet wide

Where the entrance to the space has a personnel door, it must open in the direction of egress and be equipped with panic bars, pressure plates, etc.

Similar rule for over 600V equipment in 110.33

Page 13: 1 2002 National Electrical Code Changes Where We Started

13

110.26(F) – Spaces about Electrical EquipmentDedicated Equipment Space

Dedicated space extends 6 feet above the height of the equipment. Only electrical equipment allowed in this space.

Space is the same width and depth as the equipment.

Piping

Space above the dedicated space up to the structural ceiling is permitted to have foreign systems, provided protection from leaks or breaks is provided

Drip protection

110.31

l Fence shall not be less than 7ft in heightl Table 110.31 Minimum Distance from Fence to Live Partsl Does not apply to enclosed equipment

Nominal Voltage m ft601 - 13,799 3.05 10

Minimum Distance to

Live Parts

13,800 -230,000 4.57 15Over 230,000 5.49 18

Enclosure for Electrical Installations

Page 14: 1 2002 National Electrical Code Changes Where We Started

14

110.58 – Tunnel Installations over 600V

l A switch or circuit breaker shall be installed within sight of each transformer or motor location to serve as the disconnect.

Disconnecting Means

200.6

l The word “natural” has been deleted from “natural gray”

l Gray conductors are now permitted as grounded conductors

l Allows “gray” to be used for an ungrounded conductor to distinguish one system from the othern e.g. white for 120/240V and gray for

480Y/277V

Means of Identifying Grounded Conductors

Page 15: 1 2002 National Electrical Code Changes Where We Started

15

210.6(E) – Voltage LimitationsOver 600 Volts Between Conductors

Over 600V circuits can supply utilization equipment in installations where conditions of maintenance and supervision ensure that qualified persons will service the installation.

4160V Compressor

210.7Branch Circuit Receptacle Requirements

1999 NEC

210-7 covered:

•Requirements for grounding type receptacles

•Methods of grounding receptacles

•Replacement of receptacles

Moved to

New Article 406 covering

Receptacles

Page 16: 1 2002 National Electrical Code Changes Where We Started

16

210.7(C) – Receptacle RequirementsMultiple Branch Circuits

N

ØØ

More than one receptacle on a yokeSupplied by more than one branch

circuit (can be multiple single circuits or a multi-wire circuit)

Must be provided with a means to simultaneously disconnect the ungrounded conductors at the panelboard where the circuits originate

210.8(A)(5) Exception No. 3 – Dwelling UnitsUnfinished Basements

Fire and/orBurglar AlarmControl Panel

Receptacle supplying only a permanently installed fire alarm or burglar-alarm

Remove tab to limit to one receptacle

Omission of GFCI protection

Page 17: 1 2002 National Electrical Code Changes Where We Started

17

210.8(A)(8) – Dwelling UnitsBoathouses

15- and 20-ampere receptacles in boathouses on dwelling unit property are required to have GFCI protection.

Article 555 now excludes private, noncommercial docking facilities for single-family dwellings

210.8(B)(3) – Other than Dwelling Units

GFCI protection now required for 15 and 20A receptacles in kitchens located in other than dwelling unit

Kitchens

Page 18: 1 2002 National Electrical Code Changes Where We Started

18

210.12Arc-Fault Circuit-Interrupter Protection

Requirements:

• All branch circuits supplying 15 or 20A outlets in the bedroom

• NOTE: see definition of “outlet” in Article 100, this includes lighting outlets

• AFCI must be listed to provide protection of the entire branch circuit

210.19(B) – Minimum Ampacity and Size

l Ampacity in accordance with Table 310.15 and 310.60

l Size conductors at not less than 125% of the “designed potential load” of equipment to be operated simultaneously OR

l Sized by the engineer for supervised installationsn Design and installation are under

engineering supervisionn Qualified persons with documented training

and experience in over 600V systemsprovide maintenance, monitoring, and servicing of equipment

Branch Circuits Over 600 Volts

Page 19: 1 2002 National Electrical Code Changes Where We Started

19

210.23

l No change to the code languagel Panel Statement is significant:

n The 80% limitation on any single cord- and plug-connected appliance on a circuit with two or more receptacles applies to both continuous or intermittent loads

Permissible Loads

210.52

Modified to indicate this section provides requirements for 125-volt, 15 and 20 ampere receptacle outlets.

Dwelling Unit Receptacle Outlets

Page 20: 1 2002 National Electrical Code Changes Where We Started

20

210.52(C)Countertops

Receptacle installed in appliance garage does not count as one of the required outlets.

Must be not more than 24” to meet 210.52(C)(1)

210.52(C)(5) Exception - CountertopsReceptacle Outlet Location

Not more than 20”

Where a receptacle is mounted above the cabinets, it must be within 20” of the countertop to be counted as one of the required receptacles.

Page 21: 1 2002 National Electrical Code Changes Where We Started

21

210.52(D)

l Receptacle now permitted to be installed on a partition or a wall

l Wall or partition must be “adjacent” to the basin or basin countertop

l The receptacle must be within 3 feet of the outside edge of the basin

Bathrooms

Wall

Half-wall or partition

210.52(G)

Finished Basement -normal receptacle

placement

Unfinished portion

GFCI Protected

Unfinished portion

GFCI Protected

A receptacle must be placed in each unfinished portion of the basement

Basements

Page 22: 1 2002 National Electrical Code Changes Where We Started

22

210.63Heating, AC, and Refrigeration Equipment Outlet

25’ max

Receptacle required within 25’ of all heating, AC or refrigeration equipment regardless of the type of installation

210.70(A)(2)(c) – Dwelling Units

Switch required at landing level if there is an entry at the landing.

Lighting Outlet Switch Locations

Page 23: 1 2002 National Electrical Code Changes Where We Started

23

215.2(B) – Minimum Rating and Size

l Ampacity in accordance with 310.15 and 310.60l Transformers – conductors supplying transformers shall not

be less than the nameplate rating of the transformerl Transformers and utilization equipment - Size conductors at

not less than 125% of the “designed potential load” of equipment plus the nameplate ratings of the transformersOR

l Sized by the engineer for supervised installationsn Design and installation are under engineering supervisionn Qualified persons with documented training and experience in over

600V systems provide maintenance, monitoring, and servicing of equipment

Feeders Over 600 Volts

225.26Vegetation as Support

Support of overhead conductor spans by vegetation is not permitted. The exception for temporary wiring has been deleted.

Page 24: 1 2002 National Electrical Code Changes Where We Started

24

230.6Conductors Considered Outside the Building

Installed under not less than 2” of concrete beneath a building or structure

Installed in conduit and under not less than 18” of earth beneath a building or structure

Encased in not less than 2” of concrete or brick

Installed in a vault that meets Article 450 Part III

230.40 Exception No. 1 – Service Entrance ConductorsNumber of Service Entrance Conductor Sets

Occupancy #1 Occupancy #2 Occupancy #3

240V Service 480V Service

Permits a set of service entrance conductors run to each occupancy for each service of different characteristics as defined in 230.2(D)

Page 25: 1 2002 National Electrical Code Changes Where We Started

25

230.70(A)(3) - LocationRemote Control

Shunt trip or “remote control”

The service equipment must still be located at a readily accessible location where the conductors enter the building

230.82

l Additional Equipment n Meter socketsn Meter disconnect switches rated 600

Volts maxn Fuel Cell Systems

l Surge Protective Devices removed from list of permitted devicesn Surge Arresters are still included in the

permitted list of devicesn Removed in order to clarify TVSS

products are not permitted

Equipment Connected to the Supply Side of Service Equip

On to service equipment

Meter disconnect switch

480Y/277V Typical

Supply

Page 26: 1 2002 National Electrical Code Changes Where We Started

26

230.212

l Section previously applied when voltage exceeded 15,000 volts

l Where service conductors enter a building they must terminate in metal-enclosed switchgear compartment or a vault complying with Article 450 Part III

Over 35,000 Volts

240.2

l Coordinationn The proper localization of a fault condition to restrict outages to the

equipment affected, accomplished by the choice of selective fault-protective devices

l Current limiting overcurrent protective devicen Moved from 240.11

l Supervised industrial installationn Moved from 240.91

l Tap conductorsn Moved from 240.3(D)n Clarified to exclude service conductors

Definitions

Page 27: 1 2002 National Electrical Code Changes Where We Started

27

240.21(B)(5)(4)c – Feeder TapsOutside Taps of Unlimited Length

Feeder Tap

Conductors installed in accordance with 230.6

Equipment at a readily accessible location where the conductors enter

240.21(C)(6) – Transformer Secondary Conductors

Primary conductors protected at their ampacity

25’ max

Conductors terminate in a single CB or set of fuses that limit load current to the ampacity of the secondary conductors

Secondary conductors have an ampacity that is at least 1/3 the rating of the primary device when multiplied by the voltage ratio

480V 240V

Secondary Conductors Not Over 25’ Long

200A

150A

150A conductors

Page 28: 1 2002 National Electrical Code Changes Where We Started

28

240.24(B) Exception No. 2 – Location In Premises

l General rule requires that each occupant have ready access to overcurrent devices that supply that occupancy

l Exception recognizes that occupants of hotel/motel rooms do not need access if the building is under continuous building management supervision

Occupancy

240.83(D) - Marking

l Requires a breaker listed and marked as HID (high intensity discharge) to be used as a switchfor HID lighting

l Florescent lighting can be switched with breakers marked SWD or HID

Used as Switches

Page 29: 1 2002 National Electrical Code Changes Where We Started

29

240.85 – Circuit Breakers

Clarifies that “slash” rated breakers should be applied only in solidly grounded circuits

Applications

Slash Rated Breaker OK

Article 240 Part VIIISupervised Industrial Installations

Conditions of maintenance and engineering supervision ensure that only qualified persons monitorand service the system

System has at least 2500 kVA of load used in industrial process and/or manufacturing (calculated in accordance with Article 220)

At least one service more than 150V to ground and 300V phase-to-phase

Does not apply to offices, garages, warehouses, etc.

Page 30: 1 2002 National Electrical Code Changes Where We Started

30

240.92(B)(1)(1) – Transformer Secondary ConductorsShort-Circuit and Ground-Fault Protection

Secondary conductor length changed from 50 feet to 100 feet

Primary overcurrent device not more than 150% of the secondary conductor ampacity multiplied by the secondary to primary voltage ratio

See 240.92(B)(2) for overload protection requirements

240.92(B)(1)(2) – Transformer Secondary Conductors

Differential Relay

Short-Circuit and Ground-Fault Protection

Conductor secondary is now permitted to be of any length

See 240.92(B)(2) for overload protection requirements

Page 31: 1 2002 National Electrical Code Changes Where We Started

31

240.92(B)(1)(3) – Transformer Secondary ConductorsShort-Circuit and Ground-Fault Protection

Secondary conductor length limitation removed

Secondary conductors considered protected if calculations made under engineering supervision determine that the system overcurrent devices will protect the conductors within the recognized time-current limits for ALL short-circuit and ground-fault conditions.

240.92(D) – Location in Circuit

l Secondary conductors are permitted to be protected by the primary overcurrent device

l Primary device time-current characteristics multiplied by the effective primary to secondary voltage ratio must effectivelyprotect the secondary conductors

l Difficult to use with transformers that have greater than a 1:1 ratio of primary L-L voltage to secondary L-L voltage

Protection by Primary Overcurrent Device

Page 32: 1 2002 National Electrical Code Changes Where We Started

32

250.4(B) – General Requirements for Grounding

l Material moved from 250.2 where it was mixed with grounding system requirements

l Ground all non-current carrying conductive materials of electrical equipment

l Bond together all non-current carrying conductive materials together to create a permanent, low-impedance path for ground-fault current

Ungrounded Systems

1st fault grounds the system

250.20

l Specifies what systems are required to be grounded

l Notes that other systems are permitted to be grounded

l Now clarifies that if a system is grounded (either required or permitted) the grounding must comply with Article 250

AC Circuits and Systems to Be Grounded

Page 33: 1 2002 National Electrical Code Changes Where We Started

33

250.30(A)(2)(b) and (3) – Sep Derived Systems

l Allows a common grounding electrode for multiple separately derived systems

l Must use exothermic weld, irreversible compression or connect to copper bus bars

l Keep main grounding electrode conductor without a splice or joint

Grounding Electrode Conductor

Grounding Electrode (example shown is water pipe)

Separately Derived Systems

Size common grounding electrode conductor based on 250.66 using the total area of largest derived phase conductor from each system

Size “tap” conductors based on 250.66 based on the derived phase conductor size

250.32(E) – Two or More Buildings/Structures

Service Equip - Bldg #1 Bldg #2Grounding Electrode Conductor

Grounding electrodeconductor sized by 250.66 based on largest ungrounded supply conductor.

Page 34: 1 2002 National Electrical Code Changes Where We Started

34

Article 250

l 250.52 establishes the electrodes PERMITTED for groundingn Metal underground water pipen Metal frame of the building or structuren Concrete encased electroden Ground ring

n Rod and Pipe electrodesn Plate electrodesn Other local metal undergrounds systems

or structures

l 250.52(B) establishes electrodes NOT permitted for groundingn Metal underground gas pipingn Aluminum electrodes

Part III – Grounding Electrode system

Gas Pipe

250.53(C) – Grounding Electrode System InstallationBonding Jumper

• Install – 260.64(A), (B) and (E)• Size - 250.66• Connect – 250.70

Page 35: 1 2002 National Electrical Code Changes Where We Started

35

250.102(E) – Equipment Bonding JumperInstallation

Rigid nonmetallic conduit

Rigid metal conduit

Equipment bonding jumper permitted longer than 6’ permitted to bond isolated sections of metal raceways

250.104(A) – Bonding of Piping SystemsMetal Water Piping

Requires bonding of water pipe that is “installed in” or “attached to” a building or structure.

“Installed in”

“Attached to”

Page 36: 1 2002 National Electrical Code Changes Where We Started

36

250.104(B)

l Deleted old 250-104(c) that required bonding of all metal gas piping to the grounding electrode

l Gas piping now covered under 240.104(B) which requires bonding of piping that is “likely to become energized”.

l Bonding jumper sized based on the overcurrent device protecting the circuit that is likely to energize the piping.

l The equipment grounding conductor of the circuit is permitted to serve as the bonding means

Bonding of Other Metal Piping

Branch Circuit

Gas Piping

250.122(B) – Equipment Grounding Conductors

Now requires proportional increase in equipment grounding conductor when phase conductors are increased for any reason.

Increase in Size

Page 37: 1 2002 National Electrical Code Changes Where We Started

37

250.146(A)Surface Mounted Box

Box must be mounted “on” the surface

Direct metal to metal contact acceptable for grounding the receptacle

Previous code allowed a box mounted “at” the surface to use metal to metal contact. Now a yoke must be listed to establish the grounding path for other than surface mounted boxes.

Article 285

l Service. The TVSS shall be connected on the load side of a service disconnect overcurrent device

l Separately Derived System. The TVSS shall be connected on the load side of the first overcurrent device in a separatelyderived system.

l Short Circuit Current Rating. The TVSS shall not be installed at a point on the system where the available fault current exceeds the marking on the equipment.

Transient Voltage Surge Suppressors (TVSS)

Page 38: 1 2002 National Electrical Code Changes Where We Started

38

285.1 - TVSS

l Covers n general requirementsn installation requirementsn connection requirements

l Permanently installed only

Article Scope

285.3 - TVSS

l Circuits exceeding 600 volts.l Ungrounded electrical systems as

permitted in Section 250.21.l Where the rating of the TVSS is less

than the maximum continuous phase-to-ground power frequency voltage available at the point of application.

Uses Not Permitted

Page 39: 1 2002 National Electrical Code Changes Where We Started

39

285.5 - TVSS

l The TVSS shall be Listed. l Most TVSS products will reference:

n UL 1449 2nd Edition on the product.

Listing

285.6 - TVSS

l The TVSS shall be marked with a short circuit current rating... n DO NOT confuse the Short Circuit Current Rating (SCCR) with the

Surge Current (Capacity) Rating !!!u The Surge Current Rating is the maximum transient current level that can

be suppressed by the TVSS. u The Short Circuit Current Rating is the available and sustainable power

current level that can flow in the circuit, at the point of connection to the system, during a fault condition until the circuit is opened.

Short Circuit Current Rating

Page 40: 1 2002 National Electrical Code Changes Where We Started

40

Chapter 3 Reorganization

305 527

Moving to

380 404

384 408

Articles Moving to Different Chapters

Chapter 3 Reorganization

l See new Annex F for cross-referencel Articles 312-314 covers boxes and enclosures

n Outlet boxes, cabinets, etc.

l Articles 320-340 covers cablesn MI, MC, AC, NM, UF, etc.

l Articles 342-356 covers conduitsn RMC, RNMC, FMC, etc.

l Articles 358-362 covers tubingn EMT, ENT, FMT, etc.

l Articles 366-390 covers other methodsn Busway, cable bus, etc.

l Articles 392-398 covers open wiringn Knob and tube, open wiring on insulators, etc.

Wiring Method Article Renumbering

Page 41: 1 2002 National Electrical Code Changes Where We Started

41

Chapter 3 Reorganization

.1 Scope

.2 Definitions

.6 Listing RequirementsPart B Installation.10 Uses Permitted.12 Uses Not Permitted.16 Temperature Limits.30 Securing and Supporting.60 GroundingPart C - Construction Specifications.110 Corrosion Protection.120 Markings

Common Number Method for all articles

300.1(C)

615551294103

3 ½91378

2 ½63253

1 ½41

1 ¼35127¾21½163/812

Trade SizeMetric DesignatorNeither the metric designator nor the trade size relate to actual dimensions of the conduit or tubing.

Metric Designators and Trade Sizes

Page 42: 1 2002 National Electrical Code Changes Where We Started

42

300.4(B)(1) – Protection Against Physical Damage

Metal Stud

A listed bushing or grommet must cover all metal edges and be securely fastened to the opening

NM Cable and EMT Through Metal Framing Members

300.5(D)(3) – Underground Installations

18” or more18” or more

Applies to all underground service conductors

Service Conductors

At least 12” Warning Ribbon

Page 43: 1 2002 National Electrical Code Changes Where We Started

43

300.5(K) – Protection Against Physical DamageDirectional Boring

Cables and raceways installed using directional boring equipment shall be “approved” for the purpose.

300.6(A) – Protection Against Corrosion

Where threads are cut in the field, the threads shall be coated with an approved, electrically conductive, corrosion resistant compound.

General

Located in an area where corrosion protection is necessary

Page 44: 1 2002 National Electrical Code Changes Where We Started

44

300.7(A) – Raceways Exposed to Different Temperatures

Sealing

Interior - 72°FExterior - 25°F

Fill raceway with approved material to prevent circulation of warm air to cold air region

Raceway

300.11(C) – Securing and SupportingCables Not Used as Means of Support

Cable wiring method (e.g. MC cable)

Other cable or raceway (e.g. Class 2 circuit)

Cable wiring methods are not permitted to support other cables or raceways

Page 45: 1 2002 National Electrical Code Changes Where We Started

45

300.22(B) – Wiring in Ducts, Plenums or Other Spaces

Change specifically prohibits conduit with an overall nonmetallic coating

Ducts or Plenums Used for Environmental Air

Ducts or plenums in 300.22(B) are those specifically fabricated to transport environmental air.

300.22(C) – Other Spaces Used for Env AirWiring Methods

Return Air SpaceSuspended ceiling

Rigid metal conduit with a nonmetallic coating now prohibited

Page 46: 1 2002 National Electrical Code Changes Where We Started

46

310.15(B)(2) – Exception No. 5Adjustment Factors – AC or MC Cable

MC or AC cable

• #12 AWG conductors

• Not more than 3 current carrying conductors per cable

• No overall outer jacket

No adjustment factor required where not more than 20 current carrying conductors are in the stack or bundle.

For more than 20 current carrying conductors, a 60% adjustment factor applies

Table 312.6(B)Minimum Wire Bending Space at Terminals

The table now recognizes smaller wire bending space for compact stranded AA-8000 aluminum conductors

Using an example of a 400A circuit:

1999 NEC

Cu – 3/0 - 6 ½ inches

Al – 250 kcmil – 8 ½ inches

2002 NEC

Cu – 3/0 - 6 ½ inches

Al – 250 kcmil – 6 ½ inches

Page 47: 1 2002 National Electrical Code Changes Where We Started

47

314.20

Surface of concrete, tile, gypsum, plaster or other noncombustible material

In Wall or Ceiling

Box not set back more than ¼” from the finished surface

For surfaces of wood or other combustible material, the box must be flush with the finished surface

314.23(B)(1) – Structural MountingNails and Screws

Where nails or screws are used to fasten a box, the nail or screw must pass thru a bracket outside of enclosure or must pass through the inside with ¼” of the back of the enclosure.

Page 48: 1 2002 National Electrical Code Changes Where We Started

48

314.27(A) ExceptionBoxes at Luminaire Outlets

Permits mounting of luminaire to a “standard” outlet box where the luminaire does not weigh more than 6 lb. Dimensional limitation on the fixture has been removed.

Use #6 screws minimum

Maximum Luminaire Weight

Luminaire weighing not more than 50 lbs.

Outlet box identified for luminaire (fixture) support

Luminarie’s weighing over 50 lbs must be supported independently of the outlet box

314.27(B) – Outlet Boxes

Page 49: 1 2002 National Electrical Code Changes Where We Started

49

330.10(13) – Uses PermittedSingle-Conductor MC

Where single conductor MC is used, the phase and neutral (if used) conductors shall be grouped together to minimize induced voltage

Single-conductor MC is required to have a nonmagnetic sheath or armor (NEC 330.116)

Installation of single-conductor MC must comply with NEC 300.20.

332.80 – AmpacitySingle Type MI Conductors Grouped Together

Open runs or on a messenger in a triangle or square configuration

Permitted to use Table 310.17 ampacities for the MI cable.

Temperature limitation of equipment terminations must be considered. Ampacity will be required to be reduced back to Table 310.16 levels before terminated within equipment.

Not less than 2.15 times diameter of largest conductor in the group

Page 50: 1 2002 National Electrical Code Changes Where We Started

50

334.6 – NM CableListed

NM Cable is required to be listed

334.10(2) – NM CableUses Permitted

Multifamily dwellings and other buildings that are of Type III, IV or V construction.

New Appendix E will contain a table from NFPA 220 to explain the different building Types

The building code in effect locally will also define the building types

In general, this permits NM to be used in 4-story apartment buildings (typically R-2 buildings, Type III and IV)

Page 51: 1 2002 National Electrical Code Changes Where We Started

51

Annex E

l Type III – typically constructed of noncombustible, limited-combustible, or other approved combustible material

l Type IV – typically timber frame construction

l Type V – typical stick built construction

Types of Construction

Explanation of Headers – Example = 211 Construction

2 = 2 hr fire rating of exterior load bearing walls

1 = 1 hr fire rating of columns, beams, girders that support bearing walls or loads from more than one floor

1 = 1 hr fire rating of floor

334.12(A)(1) – Uses Not PermittedTypes NM, NMC and NMS

Space above suspended ceiling in other than one, two and multi-family locations

NM cable not permitted in this space

Page 52: 1 2002 National Electrical Code Changes Where We Started

52

338.10(B)(4) – Uses Permitted

l Applies installed as a branch circuit or feeder

l Must be installed in accordance with Article 334 (NM Cable) Parts I and II

l Specifically excludes 334.80 requirement that limits ampacity of NM cable to 60C

Installation Methods for Branch Circuits and Feeders

342.22Number of Conductors

IMC

Conductor fill must comply with Table 1, Chapter 9

Cables are permitted to be installed where such use is permittedby the respective cable articles.

Page 53: 1 2002 National Electrical Code Changes Where We Started

53

344.24

l One shot and Full shoe benders contained in one table

l Minimum radius is now measured to the centerline of the conduit

Bends – How Made

362.10(2) Exception – InstallationUses Permitted

ENT

NFPA 13 sprinkler system throughout the building15 minute finish rating not

required

Page 54: 1 2002 National Electrical Code Changes Where We Started

54

400.8(5)

Flexible cord not permitted above a suspended or drop ceiling

Uses Not Permitted

404.6(C)

l General rules says that blades must be de-energized when in the open position

l New text recognizes that a bottom fed bolted pressure switch can have energized blades if barriers are provided

Connection of Switches

Page 55: 1 2002 National Electrical Code Changes Where We Started

55

404.8(B) – Accessibility and Grouping

l Applies to switches grouped in an enclosure with other switches, receptacles or similar devices

l Voltage between adjacent devices must not exceed 300V

l A permanently installed barrier can be used to separate devices where the voltage does exceed 300V

Voltage Between Adjacent Devices

404-14(E)Dimmer Switches

Dimmer switches are permitted to supply only permanently installed incandescent luminaries, unless listed for the control of other loads.

Page 56: 1 2002 National Electrical Code Changes Where We Started

56

404.15(B) – MarkingOff Indication

OffAuto

On

If a switch has a marked off position, it shall disconnect all ungrounded conductors

406.4(E)Receptacles in Countertops and Similar Work

Surfaces in Dwelling Units

Receptacles not permitted to be mounted face-up in any countertop or work surface in a dwelling unit

Page 57: 1 2002 National Electrical Code Changes Where We Started

57

406.8(B)(1)15- and 20-Ampere Outdoor Receptacles

Requires the use of a “weatherproof” while in use cover in all outdoor wet locations.

Applies to 15 and 20 ampere, 125 and 250-volt receptacles

406.8(B)(2)Other Receptacles

Requires the use of a “weatherproof” while in use cover in all outdoor wet locations where the product intended to be plugged in is not attended while in use (e.g. sprinkler controllers, landscape lighting, holiday lighting, etc.

For applications where the plugged in equipment will be attended while in use (e.g portable tools), a basic weatherproof cover can be used.

Applies to receptacles other than 15 and 20 ampere, 125 and 250-volt

Page 58: 1 2002 National Electrical Code Changes Where We Started

58

408.4

l All circuits or circuit modifications shall be legibly identified as to their purpose

l Located on the panel face or inside the panel door

l Located at each switch on a switchboard

Circuit Directory

Now applies to both switchboards and panelboards!

408.21

l Each grounded conductor must terminate in an individual terminaln Do not put two “neutrals” in

one terminaln Do not put a neutral and an

equipment ground in one terminal

l Multiple equipment grounding conductors can still be terminated in a terminal if the panel is identified to allow the multiple connection

Grounded Conductor Terminations

Page 59: 1 2002 National Electrical Code Changes Where We Started

59

410.18(B) Exception – Exposed Luminaire Parts

Grounding means not available at the outlet

Grounding Electrode

Separate equipment grounding conductor installed in accordance with 250.130(C)

Replacement luminaire. Permitted to have conductive parts.

Made of Insulating Material

430.32(C) – Continuous Duty MotorsSelection of Overload Relays

Clarifies that the sensing element or the setting of the overload relay can be increased if the values in 430.32(A) and (B) are not sufficient to start the motor.

NA130% to 140%430-32(A) and (B)

430-32(C)

Approved for use with the motor

115% to 125%One HP or less, automatically started

430-32(B)

140% to 170%115% to 125%More than 1HP430-32(A)

Thermal Protector

Sep Overload DeviceCoversNEC

NA130% to 140%430-32(A) and (B)

430-32(C)

Approved for use with the motor

115% to 125%One HP or less, automatically started

430-32(B)

140% to 170%115% to 125%More than 1HP430-32(A)

Thermal Protector

Sep Overload DeviceCoversNEC

Page 60: 1 2002 National Electrical Code Changes Where We Started

60

430.52(C)(1) – Rating or SettingIn Accordance with Table 430.52

Table moved from 430-152 to become Table 430.52

430.53(D) – Several Motors or LoadsSingle Motor Taps

Listed manual motor controllers additionally marked “suitable for tap conductor protection in group installations”

Group Installation: multiple motors installed on one branch circuit

Branch short-circuit/ground-fault device

Conductors not less than 1/10 the rating of the branch SC/GF device Conductors sized by

430.22

Not more than 10’ in length

Page 61: 1 2002 National Electrical Code Changes Where We Started

61

430.62(A) Exception No. 2 – Rating or SettingSpecific Load

Feeder overcurrent device supplying a Motor-Control Center

Feeder device must have a rating or setting that does not exceed the rating of the MCC main power bus (see 430.92)

430.102(B) – Disconnect LocationMotor

430.102(A) requires the disconnect in sight of the controller

430.102(B) requires a disconnect in sight of the motor

430.102(B) Exception allows omission of the disconnect in sight of the motor if one of the following applies:

(a) the location is impracticable or introduces additional hazards

(b) Industrial installation with maintenance and supervision and written safety procedures

Page 62: 1 2002 National Electrical Code Changes Where We Started

62

430.102(B) Exception

l Where the exception is used to eliminate the disconnect at the motor the controller disconnect must ben Capable of being locked in the open

positionn Each disconnect must be

individually lockable

n The locking means must be permanently installed on or at the switch or circuit breaker

Motor Disconnect

440.65 – Room Air Conditioners

l Single-phase cord- and plug-connected room air conditioners

l Must be provided with factory- installed n LCDI (Leakage Current

Detection and Interruption)n or AFCI (Arc-Fault Circuit

Interrupter)

LCDIMust be integral with the attachment cap or located within 12” of the attachment cap

LCDI or AFCI Protection

Page 63: 1 2002 National Electrical Code Changes Where We Started

63

500.7(K) – Protection Techniques

Detection system restrictions:l In industrial establishments with restricted

public access andl Where conditions of maintenance and

supervision ensure only qualified persons service installation

l System is listed for detection of specific gas or vapor

Permitted equipment with detection system:

l Inadequate Ventilation establishes Class I, Div. 1 location– Electrical equipment suitable for Class I, Div. 2

l Interior of Building with opening into Class I, Div. 2 – Electrical equipment for unclassified locations

l Interior of Control Panel – Instrumentation measuring gas– Electrical equipment suitable for Class I, Div. 2

Combustible Gas Detection System

500.8(A)(1) – Suitable for Class and Properties

l Suitability of Identification byn Equipment listing or labelingn Evidence of equipment

evaluation from a qualified testing lab or inspection agency

n Evidence acceptable to the AHJ such as a manufacturer’s self-evaluation or owner’s engineering judgment

Identified

Page 64: 1 2002 National Electrical Code Changes Where We Started

64

501.4(B)(3) – Class I Division 2Nonincendive Field Wiring

Unclassified LocationClassified Location

Nonincendive field wiring –not capable of igniting (through arcing or thermal effects) flammable gas or vapor under normal operating conditions.

Nonincendive field wiring apparatus

• Install in accordance with the control drawings

• Install in separate cables, cables where each conductor has a grounded metal shield or in multi-conductor cables where each conductor has a min of .25mm of insulation

Cable or wiring method permitted for unclassified location

504.80(B) – Intrinsically Safe Systems

l Labels located at least every 25 feetl Visible after installationl Must appear in every section separated by walls, partitions,

etc.

Identification of Wiring

Intrinsic SafetyWiring

Page 65: 1 2002 National Electrical Code Changes Where We Started

65

511.1 – Commercial GaragesScope

l Includes locations used for service and repair operations

l Self-propelled vehiclesl Flammable liquids or

flammable gases used for propulsion

511.3(B)(2) – Classified LocationsWithin 18” of the Ceiling

Class I Division 2 unless provided with four air changes per hour

CNG Vehicle

18”

Page 66: 1 2002 National Electrical Code Changes Where We Started

66

Articles 513 and 515

Div 1

Div 2

Zone 0

Zone 1

Zone 2

Article 513Aircraft Hangers

Article 515

Bulk Storage Plants

Zone Classification

Zone classification system now permitted

514.1 – Motor Fuel Dispensing FacilitiesScope

Scope and title changed from “Gasoline Dispensing” to “Motor Fuel Dispensing”

Now includes: gasoline, LNG, CNG, etc.

Page 67: 1 2002 National Electrical Code Changes Where We Started

67

517.2 – Definitions

l Definition correlates with NFPA 99l Buildings or portions of buildings that include:

n Medicaln Dentaln Psychiatricn Nursingn Obstetricaln Surgical

l Includes (but not limited to):n Hospitalsn Nursing homesn Limited care facilitiesn Clinicsn Medical and dental officesn Ambulatory care

Health Care Facilities

517.18 – Tamper Resistant Receptacles

l Applies to ALL receptacles in patient care areas of pediatric wards, rooms or areas

l Listed tamper resistant receptacle, or l Listed tamper resistant cover

Pediatric Locations

Page 68: 1 2002 National Electrical Code Changes Where We Started

68

517.30(E) – Essential Electrical Systems

Identification required for receptacles supplied from the emergency system.

Identification shall be of the cover plate or the receptacle itself.

Distinctive color or marking so as to be readily identifiable

Receptacle Identification in Hospitals

Similar requirement exists for emergency receptacles in nursing homes and limited care facilities [see 517.41(E)]

517.32(G) – Life Safety BranchAutomatic Doors

Connect to the life safety branch

Automatically operated doors used for building egress

EXIT EXIT

Page 69: 1 2002 National Electrical Code Changes Where We Started

69

517.34 ExceptionEquipment System Connection to Alternate Power Source

Requirement for time-lag interval for the equipment system is not required for essential systems of less than 150kVA

Omission of the time-lag interval allows a single transfer switch to be used

520.1 – TheatersScope

Scope now includes performance areas and applies to both indoor and outdoor locations

Page 70: 1 2002 National Electrical Code Changes Where We Started

70

Article 527Temporary Installations

Temporary Wiring has been renamed Temporary Installations

The article covers more than just wiring methods allowed. GFCI’s, receptacle grounding, disconnecting means, etc. are also covered.

527.3(B) – Time Constraints90 Days

The new wording now reflects that the 90 day time limit applies to all holiday wiring, not just Christmas.

Page 71: 1 2002 National Electrical Code Changes Where We Started

71

527.6(A) – Ground-Fault Protection for Personnel

l GFCI Protection Required for all 125-volt, 15, 20 and 30 ampere receptacle outletsn Used by personnel during construction, remodeling, maintenance,

repair or demolitionn GFCI in cords sets is acceptable

l Exception for Industrial establishments wheren Qualified personnel are involvedn Assured Equipment Grounding Conductor Program is applied

n Only permitted for receptacle outlets where having GFCI protection would be a greater hazard or equipment is not compatible with GFCI protection

Receptacle Outlets

527.6(B) – Ground-Fault Protection for Personnel

l Applies to all receptacles other than 15, 20 and 30-ampere 125-volt

l Requires eithern GFCI, orn Assured Equipment Grounding Conductor Program [527.6(B)(2)]

Use of Other Outlets

Page 72: 1 2002 National Electrical Code Changes Where We Started

72

547.5(G) – Wiring Methods

l Requires GFCI protection on all 125-volt, 15 and 20-ampere general purpose receptacles installed inn Areas having an equipotential planen Outdoors

n Damp or wet locations

Receptacles

547.9 – Power DistributionElectrical Supply to Buildings/Structures from Distribution Point

Site isolating device (may be a pole-top disconnect)

Disconnects permitted to be located at distribution point – treat like a feeder (250.32 and Article 225)

Alternatively, disconnects may be located at the buildings instead of the distribution point –547.9(B)(1)

Page 73: 1 2002 National Electrical Code Changes Where We Started

73

547.10

l Required where the following existn Concrete floor of

confinement arean Animals have access to

metal equipmentn The metal equipment is

likely to become energized

l Must be bonded to the electrical grounding system

Equipotential Plans and Bonding of Equipotential Planes

550.25(B) – AFCI Protection

l Requires AFCI protection on branch circuits that supply 15 and 20 ampere, 125 volt outlets in bedrooms

l Parallel with 210.12 requirementl HUD rules govern the construction of

manufactured homes. HUD does not yet include the AFCI requirement.

Bedrooms of Mobile Homes and Manufactured Homes

Page 74: 1 2002 National Electrical Code Changes Where We Started

74

Article 555

l Revised to be more consistent with NFPA 303 –Fire Protection for Marinas and Boatyards

l Specifically excludes private, noncommercial docking facilities associated with single-family dwellings

l Relates electrical requirements to the “electrical datum plane”n 2 ft above highest tide level for area under normal

circumstances

n 2 ft above highest water level under normal circumstances

n 30” above water level at floating pier or landing stage and a minimum of 12” above the level of the deck

Marinas and Boatyards

555.19 – Receptacles

l Receptacles for shore power must ben Not less than 30 ampsn single outlet type

l Receptacles that are 30 to 50 amps must be of the locking and grounding type

l Receptacles 60 to 100 amperes must be of the pin and sleeve type

l GFCI protection required for receptacles other than shore power locatedn Outdoorsn In boathousesn Buildings used for storage, maintenance or repair

where electrical hand tools or diagnostic equipment are to be used.

Shore Power and Other than Shore Power

Page 75: 1 2002 National Electrical Code Changes Where We Started

75

600.21(F) – Ballasts, Transformers and…

Support wires

Suspended Ceilings

Power supply for electric sign

Flexible cord not permitted

Securely supported in place and not dependent on suspended ceiling grid for support

604.6(E) – Construction

New requirement clarifying that manufactured wiring systems shall be supported in accordance with the applicable cable or conduit article.

Support

Page 76: 1 2002 National Electrical Code Changes Where We Started

76

645.5(D)(5)(c) – Under Raised Floors

l Type ITC Cable is now permitted under raised floors to supply IT equipment.

l Equipment grounding conductor may be either green insulation or green insulation with one or more yellow stripes

l Driven by more use of computer systems in instrumentation and control of industrial locations

ITC Cable

645.5(D)(6) – Under Raised Floors

Abandoned cables beneath a raise floor assembly shall be removed unless contained within a metal raceway.

Abandoned Cables

Page 77: 1 2002 National Electrical Code Changes Where We Started

77

Article 647

l New Articlel Material from Part G of Article 530l Covers the installation and wiring of

separately derived systems operating at 120V line-to-line and 60V to ground for sensitive electronic equipment

l Expands the permitted use of this system outside television and motion picture venues.

Sensitive Electronic Equipment

60V

120V

60V

Article 680

l Article completely revisedl Part I – Generall Part II – Permanently Installed

Poolsl Part III – Storable Poolsl Part IV – Spas and Hot Tubsl Part V – Fountainsl Part VI – Pools and Tubs for

Therapeutic Use

Swimming Pools, Fountains, and Similar Installations

Page 78: 1 2002 National Electrical Code Changes Where We Started

78

680.6

“Pool” changed to “specified body of water”n Grounding requirements for all bodies of water covered

under the scope of 680 now grouped in 680.6

Grounding

680.12

Maintenance disconnect within sight of the electrical equipment (not the pool or spa itself)

5ft minimum distance from pool moved to 680.22(C)

Maintenance Disconnecting Means

Page 79: 1 2002 National Electrical Code Changes Where We Started

79

680.23(F)(1) Exception – Branch-Circuit Wiring

LFNC-B permitted to be used in lengths longer than 6ft where connecting a transformer to pool lights.

X-fmr

Wiring Methods

680.26(B)(1) – Bonded Parts

l Basic rule requires bonding of steel structure of a pool (i.e. rebar)

l If rebar is insulated by encapsulation it is not be required to be bonded

l Provisions shall be made for an alternate means to eliminate voltage gradientsn Example: installation of a #8

AWG bare copper conductor throughout the structure

Metallic Structural Components

Page 80: 1 2002 National Electrical Code Changes Where We Started

80

680.26(B)(4) – Bonded Parts

l Basic rule requires bonding of all equipment associated with the circulating system

l Double insulated pumps are permittedl Where a double insulated pump is installed, a #8 AWG

bonding conductor is required at the pump location for use with a replacement motor.

Double-insulated motor

No. 8 copper

Electrical Equipment

680.27(B)(1) – Electrically Operated Pool CoversMotors and Controllers

Controls for an electrically operated pool cover shall be located so that the operator has full view of the pool

Page 81: 1 2002 National Electrical Code Changes Where We Started

81

680.44(B) – Spas/Hot Tubs – Protection

GFCI protection required for outlets that supply a:

• self-contained spa or hot tub

• packaged spa or hot tub

• field assembled spa or hot tub with a heater load of 50A or less

Listed assemblies with integral GFCI protection for all electrical parts do not require additional GFCI at the outlet.

A spa or hot tub rated greater than 250V or 3-phase shall not require GFCI protection.

Other Units

680.57(C)(2) – Location

Portable electric signs shall not be placed within the pool or fountain, or within 5 ft (1.52 m ) measured horizontally from the inside walls of the pool or fountain

5 ft

Portable Signs

Page 82: 1 2002 National Electrical Code Changes Where We Started

82

Article 692Fuel Cells

Includes requirements for:

• Listing of the fuel cell

• Identification of multiple power sources

• Circuit requirements

• Etc.

700.12(B)(6) – Generator Sets

l Allows disconnect at a generator to also serve as the disconnect for a building or structure

l Comply with the following:n Generator disconnect must be readily accessiblen Must be “within sight” of the building (visible and

not more than 50 feet away)n Must still meet the requirements for a building

disconnect in Article 225 (e.g. 225.36 requires that disconnect be suitable for use as service equipment)

Outdoor Generator Sets

Similar language in 701.11(B)(5) for legally required systems

Page 83: 1 2002 National Electrical Code Changes Where We Started

83

702.1 – Optional Standby Systems

l ... The systems covered by this article consist of those that are permanently installed in their entirety, including prime movers, and those that are arranged for a connection to a premises wiring system from a portable alternate power supply.

Scope

702.6

l Transfer equipment required forn permanently installed standby systems n and where an electric-utility supply is

either the normal or standby source

l Must prevent the inadvertent interconnection of supplies

l Supplementary overcurrent protective devices shall be part of a listed transfer equipment. n Not a substitute for branch circuit or

feeder overcurrent protection

l Comply with Article 705 if system will be operated in parallel

Transfer Equipment

Page 84: 1 2002 National Electrical Code Changes Where We Started

84

725.3(A) – Locations and Other Articles

l References 300.17 for all of Article 725

l This extends the raceway wire fill restrictions to Class 2 and 3 circuits

l Applies Chapter 9, Table 1 through references

Number and Size of Conductors in Raceway

725.6

l Installed in a neat and workmanlike mannerl Support to structural componentsl Use proper straps, hangers or similar fittings

Mechanical Execution of Work

Class 1, 2 or 3 circuits

Support wires

Page 85: 1 2002 National Electrical Code Changes Where We Started

85

725.52(A) Exception No. 2 – Load Side of Class 2 or 3

l Can reclassify Class 2 and Class 3 circuits as Class 1 circuits

l Must install as Class 1l Class 2 and Class 3 markings

required in Section 725-42 are eliminated

l Entire circuit is installed using the wiring methods and materials in accordance the requirements for Class 1 circuits

Class 1 Wiring Methods and Materials

800.48 – Communications Wiring within Buildings

New Exception 2: Conduit fill restrictions shall not apply.

Communications Raceways

Page 86: 1 2002 National Electrical Code Changes Where We Started

86

Annexes

l Annex A – Product Standardsl Annex B – Application of 310.10(A) formulal Annex C – Conduit and Tubing Fill Tablesl Annex D – Examplesl Annex E – NFPA 220 Table for Building

Typesl Annex F – Chapter 3 Cross Reference from

1999 to 2002 NECl The Annex material is for information only

and is not part of the Code requirements

Square D Company

l The Codes and Standards group can offer on-site custom training on the NEC and related topics

l Our staff has extensive involvement in codes and standards development, interpretation and application

l Excellent resource for resolution of field issues

Codes and Standards