Copyr ight by NNE Pharmaplan. The information contained in this document may be used only for the purpose for which it is supplied by NNE Pharmaplan, and must not be shown to third parties. INDIAN IMMUNOLOGICALS LTD., KARAKAPATLA ABHAYRAB BULK ABHAYRAB FORMULATION & ANIMAL HEALTH FORMULATION Doc. Name Basic Engineering Design Philosophy for BAS System Doc. No. NPI/090408/BAS(DPH)/F2/D-01 Location Karakapatla, A.P Date / Rev 18.03.2011/00 File Name 090408_BAS(DPH)_01_R1 Project No. 090408 Page Number Page 13 of 21 Prepared by RP Checked By SMTJ/VNIR Approved By KUMAR DATA POINT SUMMARY Input / Output summary AHU Description Analog Digital Function I O I O Outside air temp 1 -- -- -- Display & monitor Outside air RH 1 -- -- -- Display & monitor Temp. Ch W IN 1 -- -- -- Display & monitor R A Temperature 1 -- -- -- Display & monitor R A Humidity 1 -- -- -- Display & monitor R A Flow measuring station 1 -- -- -- Display & monitor R A H-14 (HEPA) filter Diff.Press. (Bag In Bag Out Type) 1 -- -- -- Clean / dirty status R A Fan Diff. Press. -- -- 1 -- On / Off status R A Fan VFD -- 1 -- -- Regulate Audio / Visual alarm -- -- -- 1 Alarm E A Damper -- 1 -- -- Regulate R A Fan start / stop command -- -- -- 1 On / Off Command S A Fan start / stop command -- -- -- 1 On / Off Command M A Damper -- 1 -- -- Regulate F A Damper -- 1 -- -- Regulate Temp. Ch W OUT 1 -- -- -- Display & monitor Ch W 3-way valve control -- 1 -- -- Regulate & Position Ch W 3-way valve position 1 -- -- -- Indicate S A Fan VFD -- 1 -- -- Regulate S A Fan Diff. Press. -- -- 1 -- On / Off status F-6 filter Diff. Press. -- -- 1 -- Clean / dirty status F-9 filter Diff. Press. -- -- 1 -- Clean / dirty status S A Flow measuring station 1 -- -- -- Display & monitor Duct heater -- -- -- 1 On / Off Command Emergency once through -- -- -- 1 Once through Room Diff. Press. 10 -- -- -- Display & monitor Room Motorised damper -- 10 -- -- Regulate Spare 1 1 1 1 Spare Total 21 17 6 5

090408_BAS_DPH__01_R1

Embed Size (px)

DESCRIPTION

090408_BAS_DPH__01_R1

Citation preview

Copyright by NNE Pharmaplan. The information contained in this document may be used only for the purpose for which it is supplied by NNE Pharmaplan, and must not be shown to third parties.

I N D I AN I M M U N O L O G I C AL S L T D . , K AR A K A P AT L A

ABHAYRAB BULK ABHAYRAB FORMULATION & ANIMAL HEALTH FORMULATION

Doc. Name

Basic Engineering Design Philosophy for BAS System

Doc. No. NPI/090408/BAS(DPH)/F2/D-01

Location Karakapatla, A.P Date / Rev 18.03.2011/00

S/

File Name 090408_BAS(DPH)_01_R1 Project No. 090408 Page Number Page 13 of 21

Prepared by RP Checked By SMTJ/VNIR Approved By KUMAR

DATA POINT SUMMARY

Input / Output summary

AHU

Description Analog Digital

Function I O I O

Outside air temp 1 -- -- -- Display & monitor

Outside air RH 1 -- -- -- Display & monitor

Temp. Ch W IN 1 -- -- -- Display & monitor

R A Temperature 1 -- -- -- Display & monitor

R A Humidity 1 -- -- -- Display & monitor

R A Flow measuring station 1 -- -- -- Display & monitor

R A H-14 (HEPA) filter Diff.Press. (Bag In Bag Out Type)

1 -- -- -- Clean / dirty status

R A Fan Diff. Press. -- -- 1 -- On / Off status

R A Fan VFD -- 1 -- -- Regulate

Audio / Visual alarm -- -- -- 1 Alarm

E A Damper -- 1 -- -- Regulate

R A Fan start / stop command -- -- -- 1 On / Off Command

S A Fan start / stop command -- -- -- 1 On / Off Command

M A Damper -- 1 -- -- Regulate

F A Damper -- 1 -- -- Regulate

Temp. Ch W OUT 1 -- -- -- Display & monitor

Ch W 3-way valve control -- 1 -- -- Regulate & Position

Ch W 3-way valve position 1 -- -- -- Indicate

S A Fan VFD -- 1 -- -- Regulate

S A Fan Diff. Press. -- -- 1 -- On / Off status

F-6 filter Diff. Press. -- -- 1 -- Clean / dirty status

F-9 filter Diff. Press. -- -- 1 -- Clean / dirty status

S A Flow measuring station 1 -- -- -- Display & monitor

Duct heater -- -- -- 1 On / Off Command

Emergency once through -- -- -- 1 Once through

Room Diff. Press. 10 -- -- -- Display & monitor

Room Motorised damper -- 10 -- -- Regulate

Spare 1 1 1 1 Spare

Total 21 17 6 5