1. Description
3-way electrical isolation TRMS measurement Adjustable voltage ranges ZERO/SPAN adjustment 20%
MCR voltage transducers measure DC voltages in
several signal ranges 024 V DC to 0550 V DCand convert them into standardized analog signals. DCvoltages can be can be processed with both positiveand negative polarity.
The input voltage ranges of input terminals 1
7
can be adjusted by 20% using an adjustmentpotentiometer.
Upon delivery, the voltage transducer is set to024 V input and 010 V output and is ready foroperation. If you set the device to other input/outputvalues you must carry out a ZERO/SPAN adjustmentusing the potentiometer on the front plate.
2. Method of Operation
The input circuit divides the DC voltage at terminals1
7
. The resultant signal is transmitted electricallyisolated to the output circuit and is available as astandardized analog signal at the output.
3. Area of Application
When using the voltage transducer, ensure that thepotential difference between terminal1
7
andground potential PE, and terminal 8
and groundpotential PE does not exceed U = 660 V (prerequisite
for ungrounded circuits).In DC voltage networks, this potential differenceshould not exceed U = 100V (prerequisite forgrounded circuits).
If all of these conditions are met, safe isolation
isprovided between the input, output, and supply.
99
114,
5
22,5
Voltage Measuring Transducer for DC VoltageMCR-VDC-UI-B-DC
Headquarters: Phoenix Contact GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg GermanyPhone +49 - 52 35 - 30 0 Fax +49 - 52 35 - 34 12 00 www.phoenixcontact.com
Local contact: www.phoenixcontact.com/salesnetwork
8/21/2019 0900766b803e248b
2/5
PHOENIX CONTACT page 2 of 5
Voltage Measuring Transducer for DC Voltage MCR-VDC-UI-B-DC
4. Technical Data
rigid flexible[mm
2
] AWG
Connection d ata 0.2-2.5 0.2-2.5 24-14
DescriptionOutputsignal
MCR voltage measuring transducer,
for DC voltages from0...20 V AC to 0...660 V AC
10 V/20 mA
Technical Data
Input
Input voltage rangeInput resistanceInput voltage rangeInput resistanceAdjustment options:
Frequency responseNominal voltage ungroundedNominal voltage to ground 1
)
ZEROSPAN
Output
Output signalMaximum output signalLoadRipple
Voltage/currentVoltage/currentVoltage/current
General Data
Supply voltageCurrent consumptionTransmission errorTemperature coefficientLimit frequency (3 dB)Step-response (10 - 90%)
Test voltage:
Ambient operating temperature rangeElectromagnetic compatibility Noise emission Immunity to interference
Input/outputPower supply/output
MCR-VDC-UI-B-DC
for converting DC voltagesfrom 0
20 V DC to 0
660 V DC
A a
Type Order No.
Pcs.Pkt.
MCR-VDC-UI-B-DC 28 11 11 6
1
550 V DC
370 V DC
250 V DC
170 V DC
120 V DC550 k
370 k
250 k
170 k
120 k
80 V DC
54 V DC
36 V DC
24 V DC80 k
54 k
36 k
24 k
20%
20%
660 V DC
100 V DC
10 V/
20 mA
15 V/
30 mA> 10 k
/< 500
< 50 mV
pp
18.530.2 V DC< 50 mA< 1% of the final value< 0.015%/K40 Hz12 ms
1.5 kV, 50 Hz, 1 minute1.0 kV, 50 Hz, 1 minute-25C to +50C (-13F to +131F)
c
Conformance with EMC Directive 89/336/EECEN 50 081-2EN 50 082-2
1
) If these values are observed, safe isolation (EN 50 178/DIN EN 50178/VDE 0160) is provided between the input, output, and supply.
M 3
8
550V
GND 2
OUTIN
1 0
23 !"4
OUT I9
24VDC
GND 3
GND 3
$%&
5
24VDC
J
8GND 1
7J
J
6
OUT U
GND 2370V
250V
170V
120V
80V54V36V24V
8/21/2019 0900766b803e248b
3/5
PHOENIX CONTACT page 3 of 5
Voltage Measuring Transducer for DC VoltageMCR-VDC-UI-B-DC
ccccConformance With EMC Directive 89/336/EECand Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility)
Noise immunity in accordance with EN 50082-2
Electrostatic discharge (ESD)
Electromagnetic HF field Amplitude modulation Pulse modulation
Fast transients (burst)
Surge current loads (surge)
Conducted interference
Noise emission in accordance with EN 50081
EN 61000 corresponds to IEC 1000/EN 55011 corresponds to CISPR11
1)
Criterion A: Normal operating characteristics within thespecified limits.
2)
Criterion B: Temporary adverse effects on the operatingcharacteristics, which the device corrects automatically.
Class A: Industrial application, without specialinstallation measures
Voltage Measuring Transducer for AC Voltage
MCR-VAC-UI-0-DC
1
ZERO/SPAN potentiometer
2
Plug-in screw-cage terminal blocks
3
Housing cover, can be removed toset the jumpers
4
Metal lock for fastening on the DIN rail
5
Plug-in screw-cage terminal block
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 55011
8 kV air discharge 2)
10 V/m 1)
10 V/m 1)
Input/output/supply2 kV/5 kHz 2)
Input/output: 2 kV/42 2)
Supply: 0.5 kV/2 2)
Input/output/supply10 V 1)
Class A
5 6
7 8
1 2
3 4
567
8
MCR-V
DC-UI
-B-DC
Art.-N
r.:28
11 1
1 6
GND2
OUTI
APPR
OBAT
IONEN
/ A
PPROVAL
S
GND2
1
23
4
13
14
15
16
OUTU
9
10
11
12
GND3
+24V
DC
GND3
+24V
DC550V
170V
370V
OUT
IN
1
0
23
!"
4
9
$%&
5 J1
87
J1
J16
56
78
250V
120V
GND1
80V
54V/36V/ 2
4V
MCR
-VDC
-UI-B
-DC
IN
OUT
POWER
U1
GND1
I
GND2GND
2
+24VGND2
GND2
+24V
U
U5 U2
U6 U3
U7 U4
POWER
ZERO
SPAN
1
4
Fig. 05
2
3
5
8/21/2019 0900766b803e248b
4/5
PHOENIX CONTACT page 4 of 5
Voltage Measuring Transducer for DC VoltageMCR-VDC-UI-B-DC
Fig. 06
5 6
7 8
1 2 3
4
5
MCArt
.-
1
2
3
4
550V
170V
370V
IN
1234
5 J1
87
J1
J16
5
250V
120V
80V36V/
24V
MCR
-
IN
U1
GND1
U5 U2
U6 U3
U7 U4
POWER
AN
1
2
Fig. 07
HYBRID TV1
PHOENIX
CONTACT
J123
54V36V24V
J1
23
54V36V24V
5. Connection Notes
Table 1:
Selecting the input voltage range (see also Fig. 07)
5.1. Opening the Device (Fig. 06)
The locked housing cover is released on both sidesusing a screwdriver1
. The housing cover andelectronics can now be pulled out about 3 cm(1.181 in.)2
.
5.2. Jumper Setting (Fig. 07)
Insert jumper J in the desired position to set the input
voltage.Finally, close the housing until it engages with a
click.
InputVoltage
AdjustmentRange(20%)[V AC]
InputTerminal
Jumper/Setting
0...550 V (440 - 660)
1
0...370 V (296 - 444)
2
0...250 V (200 - 300)
3
0...170 V (136 - 204)
4
0...120 V (96 - 144)
5
0...80 V (64 - 96)
6
0...54 V (43 - 65)
7
J1/setting 1
0...36 V (28 - 43)
7
J1/setting 2
0...24 V (19 - 29)
7
J1/setting 3
Factorysetting
Caution: Never carry out work when thepower is turned on, this is highlydangerous.
If the voltage signal exceeds the voltagerange specified at the input signalterminal by more than 15% (with0...660 V by more than 5%), the inputcircuit may be damaged.
Every timethe input or output range is modified, aZERO/SPAN adjustment mustbe carried out.
8/21/2019 0900766b803e248b
5/5
PHOENIX CONTACT page 5 of 5
Voltage Measuring Transducer for DC VoltageMCR-VDC-UI-B-DC
3 4
MCR-V
DC-UI
-B-DC
Art.-N
r.:28
11
11 6
OUT 0
!"
9
MCR
-VDC
-UI-B
-DC
IN
OUT
POWER
U1
GND1
I
GND2GND2
+24VGND2GND2
+24V
U
U5 U2
U6 U3
U7 U4
POWER
ZERO
SPAN
Fig. 08
6. ZERO/SPAN Adjustment
Upon delivery, the module is set to 0...24 V inputand 010 V output.
Two potentiometers are available on the front side ofthe module for adjustment (Fig. 08):
ZERO:
Zero point adjustment
SPAN:
Final value adjustment
d) Zero point adjustment
Connect a calibration source to the input terminals
(U
(1-7)
and GND1) and specify a voltage of 0 mV.
Set the output signal value using the ZERO
potentiometer.
Voltage output (010 V): U
OUT
= 0 VCurrent output (020 mA): I
OUT
= 0 mA
b) Final value adjustment
Use the calibration source to specify the maximumvoltage used in the framework of the input voltagerange (table 1).
Set the output signal value (U
OUT
= 10 V and I
OUT
=20 mA) using the SPAN
potentiometer.
Allow the module to warm up for 4minutes before starting the adjustment
P
HOENIXCONTACT
July1,2001
TNR
:5106381-00