Upload
marcilio-carvalho
View
221
Download
0
Embed Size (px)
Citation preview
7/29/2019 09 TIA569 Standard
1/28
EIA/TIA 569
Design Considerations forTelecommunications
Pathways and Spaces
1
ELCM 254PRGodin @gmail.com
Updated January 2012
7/29/2019 09 TIA569 Standard
2/28
EIA/TIA 569
A communications infrastructure in todayscommercial buildings is essential. All buildings,new and old, must have allowance for this
infrastructure.
This standard addresses the architectural designelements ofcable pathways and dedicated
rooms for telecommunications equipment.
7/29/2019 09 TIA569 Standard
3/28
EIA/TIA 569
The TIA/EIA 569 recommendations include: Physical Characteristics: Backbone and Horizontal pathway systems such as
conduit and tray
Entrance Facilities Room space, size, conditions and design
Installation and Performance Issues:
Backboard installation
Electromagnetic Interference Firestop
Cable management and physical support
Other factors that may affect cable performance
3
7/29/2019 09 TIA569 Standard
4/28
4
7/29/2019 09 TIA569 Standard
5/28
Entrance Facilities
Includes service entrance, interbuildingbackbone, alternate entrance and antennaeentrance pathways.
Consist of a termination field interfacing anyoutside cabling to the intrabuilding cabling.
5
7/29/2019 09 TIA569 Standard
6/28
Service Entrance A service entrance is where outside companies
physically bring their services into a building.
Electrical (power, ground)
Communication (Voice, Video, Data)
Alarm (Fire, Security) Wireless equipment connections (antenna)
Other services outside of communications (water,gas, etc)
There may be more than one Service Entrancefacility in a building.
6
7/29/2019 09 TIA569 Standard
7/28
Demarcation on Service Entrance
The Demarcation (Demarc) is the separationbetween the service companys cabling and thebuilding internal cabling structure.
7
Telco Cable Building Cable
Telco Bldg
Demarc
Telco Ownership Building Ownership
7/29/2019 09 TIA569 Standard
8/28
8
7/29/2019 09 TIA569 Standard
9/28
Room General Guidelines
Located away from sources of electromagneticinterference and sources of flooding
No false ceilings.
Should have limited, secure access (36 X 80single or double lockable doors).
9
7/29/2019 09 TIA569 Standard
10/28
Room Guidelines
There are many additional guidelines addressedspecifically in the standards. Factors include:
Humidity, temperature, vibration and dust controls
Physical access issues, security and fire suppression Lighting and electrical requirements
Ceiling height, construction, paint color
7/29/2019 09 TIA569 Standard
11/28
Building Entrance Facility
Must contain protection against:
Lightning
Water
Humidity Fire Spread
Tampering
11
7/29/2019 09 TIA569 Standard
12/28
Entrance Facility Cables and Safety
Local fire regulations will dictate terminationrequirements and fire protection.
Recommendation is terminate as close to the
entrance as possible. Fire control systems should be implemented.
If the cable contains metallic elements it must be
lightning protected, even if buried.
12
7/29/2019 09 TIA569 Standard
13/28
Entrance Facilities
Includes service entrance,
interbuilding backbone,alternate entrance andantennae entrancepathways.
Consist of a terminationfield interfacing anyoutside cabling to theintrabuilding cabling.
7/29/2019 09 TIA569 Standard
14/28
Entrance Facilities (Details)
Recommendation and Standards:
One wall must contain a inch sheet of plywood,painted white.
Must not have false ceiling Has minimum standards for lighting, door size andoverall space.
The service entrance pathway is either
underground, buried, aerial or tunnel. Must be secure.
Must avoid electrical cable pathways.
14
7/29/2019 09 TIA569 Standard
15/28
Entrance Facilities (Details)
Recommendation and Standards:
Minimum conduit size:
Minimum 4 conduit of PVC type B,C, or D ormultiple plastic duct or galvanized steel or fiberglass(all with appropriate encasement)
No more than 2 - 90 manufactured bends (10times the diameter of conduit)
Drain slope:
should not be less than 12 per 100
Conduit fill varies
should not exceed 40% for more than 2 cables
15
7/29/2019 09 TIA569 Standard
16/28
Entrance Facilities (Details)
For buildings > 20,000 usable square feet, alocked, dedicated, enclosed room isrecommended
Buildings greater than 70,000 usable square feetrequire such a room with a plywood terminationfield installed on 2 walls.
Up to 100,000 square footage, a wall mounted
termination field may serve as the entrancefacility (3/4 and 8 high) Beyond 100,000 square footage, rack mounted
and free standing frames may be required.
16
FYIOnly
7/29/2019 09 TIA569 Standard
17/28
Equipment Room
The Equipment Room is a facility which housesitems of more complexity such as:
Telephone related equipment such as an MDF
(Main Distribution Frame), PBXs (Private BranchExchange), secondary voltage protection, and thelike.
Networking equipment such as switches, hubs,
routers, servers, etc., although a separate butconnected computer room is usual.
17
7/29/2019 09 TIA569 Standard
18/28
Equipment Room Size
The rule of thumb is 0.75 square feet of floorspace for every 100 square feet of user area.
Recommendation:
18
# Workstations ER Floor Space (ft2)
1-100 150101-400 400
401-800 800
801-1,200 1,200
7/29/2019 09 TIA569 Standard
19/28
Equipment Room Details
It should be accessible for delivery of large itemsbut shall not be used as access to other rooms orfacilities.
It should contain a wall with inch plywood.
7/29/2019 09 TIA569 Standard
20/28
Equipment Room Guidelines Away from sources of electromagnetic
interference
Avoid sources of flooding
All surfaces should be treated to reduce dust and
there should be no false ceilings Should have limited access (36 X 80 single or
double lockable doors)
Humidity, temperature , lighting and electrical
considerations must be addressed.
20
7/29/2019 09 TIA569 Standard
21/28
Typical Telecom Room
Image Source: Anixter.com
7/29/2019 09 TIA569 Standard
22/28
Pathways
Allowances must memade for thephysical routing ofcommunication
cabling throughoutthe building.
22 22
7/29/2019 09 TIA569 Standard
23/28
Cable Pathway Planning
Building Pathways:
Vertical & Horizontal cable pathways
walls, ceiling, plenums, floors
Exterior or interior
Cable Pathway and Support Structures:
Conduit, raceway, tray, duct, sleeves, etc
J-Hook, clamps, cable shoes, waterfall, etc
7/29/2019 09 TIA569 Standard
24/28
Backbone Pathways
Telecommunication Rooms should be stackedvertically and 3, 4-inch conduit or other cablepathways provided between these rooms.
Firestopping is required between verticallystacked rooms.
For rooms that are not stacked they should beconnected with a minimum of 4 inch conduit. Fillshould not exceed 40%.
24
7/29/2019 09 TIA569 Standard
25/28
TIA/EIA 569A Conduit Systems
Flexible metal tubing is not recognized
Should not be more than 30 meters install a pull box for greater distances
No more than two 90 degree bends Typical fill ratio between 30-60%, recommend
40% max
Diameter of 4 min. should be used underground
manholes within first 150 meters no more than 300 meters between manholes
25
7/29/2019 09 TIA569 Standard
26/28
Conduit (continued)
Flexible metal tubing is not permitted
Should not be longer than 30 meters
install a pull box for greater distances
4 min. should be used underground
manholes within first 150 meters
no more than 300 meters between manholes
7/29/2019 09 TIA569 Standard
27/28
Architectural Masterformat
The Masterformat is a reference document used byarchitectural engineers when designing a building.
The communication infrastructure is part of theMasterformat under Division 27 (since 2004).
Other cabling requirements have their owndivision numbers: Security & safety (28) Electrical (26) Automation (25)
7/29/2019 09 TIA569 Standard
28/28
Conclusion
The TIA/EIA 569-B is a structured cablingstandard that addresses the physicalrequirements and design issues for pathways and
spaces for cable within a building.
Since each building and installation has uniquechallenges, the standard is frequently used as a
guideline and not the rule.
END