Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
Type of Property
Standard Meter Location(s)
Standard Criteria Reference Drawings and
Policies
Notes Charges
Residential, Outdoor, • Accessible for • Residential • • Single Homes Front or Front-
Side of maintenance and
manual meter Meter
Installation structure
• reading
Not subject to future damage or
obstruction •
Drawings, Figures in
Section 8. Section 8.1
• Readable by Automatic Meter
• Reading System Adequate
clearance/spacing of equipment
Residential, Outdoor, Same as above • Residential Multiple Meters (e.g.
twins)
Front or Front- Side of
structure
Meter Installation
Drawings, Figures in
Section 8. • Section 8.1
Residential Outdoor, Same as above • Residential • Location of outdoor Condominiums
(individual metering)
Front or Front- Side of
structure OR Approved outdoor ganged meter location OR
•
Meter Installation
Drawings, Figures in
Section 8. Section 8.1,
8.2
•
or indoor-ganged meter must be
approved by PECO during design. Use of ganged
meters may change the installation, maintenance, and
ownership responsibilities of
some facilities. Approved indoor ganged meter location
These particulars should be discussed
and understood by the builder prior to construction.
8. METERING
8.1 METER LOCATIONS
8.1.1 General RequirementsThe Customer shall provide, free of expense to the Company and at a location inaccordance with these Electric Service Requirements, equipment suitable for meters andaccessories furnished by the Company and installed for billing the various types of electricservices offered. All locations shall be clear to allow access to the meter and its accessories for the purpose of reading, testing, and maintenance. The table below givesclarification and more clearly structure the “Electric Service Requirements” (ESR)information around meter locations.
Metering Rev-10 February 2016 Page 1 of 84
Commercial, Outdoor, Rear • Accessible for • Commercial • All commercial Cost of commercial Single or Rear-side of maintenance and Meter meter locations metering and associated
Customer structure
•
•
•
manual meter reading
Not subject to future damage or
obstruction Readable by
Automatic Meter Reading System Adequate
clearance/spacing of equipment
•
•
Installation Drawings, Figures in Section 8 Section 6.16.5
(PUT INTO
SECTION 8)
Section 8.1
should be reviewed with PECO prior to construction, to
ensure a mutually agreeable location is
determined during design.
work will be included in cost estimates per appropriate Tariff sections.
Commercial, Multiple-Customers
Outdoor, Rear or Rear-
Side of structure OR Approved outdoor ganged meter location OR Approved indoor ganged meter location
• •
•
Commercial Meter
Installation Drawings, Figures in Section 8
Section 8.1, 8.2
•
•
•
All commercial meter locations
should be reviewed with PECO prior to construction, to
ensure a mutually agreeable location is
determined during design.
Location of outdoor or indoor ganged
meter must be approved by PECO
during design. Use of ganged
meters may change the installation, maintenance, and
ownership responsibilities of
some facilities. These particulars
should be discussed and understood by
the builder prior to construction.
Cost of commercial metering and associated
work will be included in cost estimates per appropriate Tariff sections.
8.1.2 Indoor and Outdoor Locations In general, new installations of self-contained socket type meters for both single phase and three phase services will be located outdoors. Transformer rated meters with CT cabinets,shall have meter and cabinet located in close proximity with each other. Where numerousmeters are required at one location or where the Company determines that outdoormetering is impractical or inadvisable for other reasons, the meters will be located indoors.ALL indoor meters shall have provisions for automatic meter reading. Meters that communicate through the RF network (AMI) meters shall be located where there issufficient signal strength, or have provisions for an antenna. Meters that communicate through a pots line (MV90) shall have accommodations for a phone line.
When replacing or upgrading services, existing indoor meter installations of all self-contained socket type meters should be relocated outdoors. Metering Rev-10 February 2016 Page 2 of 84
8.1.3 Unacceptable Locations Under no circumstances shall meters be installed in any of the following locations:
Attics Fire Towers Manholes
Bathroom Incinerator Rooms Shafts Bedrooms Kitchens Silos Coal bins Lavatories Stairways
Crawl spaces Living Rooms 8.1Me
.4 Unaters sh
cceptable Areas all not be insta
lled behind, over, under, or adjacent to the following:
Boilers Hatches Steam pipes Doors Heaters Stoves
Exposed machinery Laundry Tubs Tanks Fire escapes Radiators Tracks for overhead doors
Furnaces Sinks Windows
Outdoor meters will not be installed on building walls close to highways, driveways,alleyways or sidewalks if the locations interfere with pedestrian or vehicular traffic, orsubject the meter to the likelihood of physical damage. Meter locations shall not require access over property not owned by the Customer. See above table for more clarifications.
8.1.5 Unacceptable EnvironmentsMeters and service equipment shall not be installed indoors within 2 feet of any gas meter,gas valve, or disconnectable gas fitting. Meters shall not be installed in locations where there is excessive heat, moisture, vibration, fumes, dust, or against downspouts, or in locations subject to flooding. See above table for more clarifications.
8.2 METER ROOM
8.2.1 General Where meter rooms are necessary they shall be of sufficient size to allow ready access tothe meter, metering transformers and accessories for the purpose of reading, testing, and maintenance. The required dimensions of such rooms for any particular installation should be secured from the local PECO Energy Company office in the Region in which the installation is located. Minimum requirements for an outdoor meter house will be furnished on request. For high voltage services, the space provided for metering purposes in Customer's substation equipment must be acceptable to the Company as provided in Section 7 of these Electric Service Requirements. See above table for more clarifications.
8.2.2 Outdoor Meter Houses or Enclosures Where a meter panel is to be located in an outdoor house or enclosure, the Customer maybe required to furnish suitable lighting and thermostatically controlled heaters to maintain atemperature of no less than 40o F at the metering instruments. Sufficient internal working Metering Rev-10 February 2016 Page 3 of 84
space shall be provided as required by Fig. 8.39. Enclosure requirements depend onexpected load and the number of meters involved. Typical outdoor enclosure requirementsfor metering installation are shown in Figure 8.40 and 8.41. See above table for more clarifications.
8.2.3 AccessibilityAll metering installations shall be readily accessible to the Company's employees during business hours. See above table for more clarifications.
8.3 SELF-CONTAINED SINGLE PHASE METER INSTALLATIONS All self contained, meter mounting equipment shall be approved by PECO Energy.Meter sockets are of the ringless style except for manufactured grouped meterinstallations.
Acceptable socket type meter mounting equipment shall be provided by the Customer forinitial single-phase loads up to approximately 320 continuous amperes, or up to 400 ampservices as computed by the National Electrical Code.
For single-phase installations exceeding a maximum current of 320 amperes theCustomer shall provide a current transformer enclosure.
Metering Rev-10 February 2016 Page 4 of 84
8.4 CABLE CONNECTIONS TO METERING AND SERVICE EQUIPMENT Approved types of cable connectors shall be used to connect the service cable to themetering and service equipment. Cable connectors shall be properly installed on theservice cable. This means securely fastened to the metering and service equipment in a way that prevents the insertion of foreign conductors into the meter socket. Service cableis acceptable for top entrances in outdoor metering installations if hex nut type weathertight connectors having tapered threads and neoprene or similar bushings with proper size and shape openings are used in weather tight hubs. In all cases of top entrance, the cable and fitting shall create a weather tight seal.
No service equipment is permitted ahead of the metering unless such installation is required by the NEC or other regulating agencies.
8.5 APPROVED TERMINALS FOR METER SOCKETS Because of the different characteristics of copper and aluminum, terminals and connectorsmust be approved as suitable for the particular metal being used. Suitably plated terminalsof the lay in or saddle type are preferred. The contact areas of aluminum conductors should be cleaned, coated with an acceptable oxide-inhibiting compound, and the terminalscratch brushed with a wire brush before connection is made.
8.5.1 Pressure Pads for Meter Socket Terminals The setscrew type of terminal will not be approved unless it employs a pressure pad.Cone screws in cylindrical barrel type terminals are acceptable. Unplated copper terminalsand connectors will be approved for use only with copper conductors.
8.6 METERING FOR OFF-PEAK SERVICE
THIS SECTION HAS BEEN REMOVED
Metering Rev-10 February 2016 Page 5 of 84
8.7 METERING REQUIREMENTS FOR MOBILE HOMES Meter sockets shall not be attached to mobile homes. Meter mounting equipment mayconsist of either factory constructed pedestal equipment (See Table 8.11) or of individualdesigned metal supports (See Fig. 8.34). In either case, the following conditions must be met:
Final installation must be rigid, plumb, and suitably painted or coated to resist rustand corrosion.
The supporting upright shall be of 3 inch steel pipe or other form of equivalentstrength. All structural metal below grade must have a bitumastic coating such asKoppers #50 or equivalent.
A factory-constructed pedestal must be set a minimum of 24" in the ground and beprovided with an approved stabilizing foot as it base. An individually designedmetal support must be set a minimum of 36" in the ground and be provided with astabilizing foot as its base. The foot shall be of 12 gauge-galvanized steel and of at least 50 sq. in. in area.
Adequate space for the entrance of Company service conductors shall be reservedin the bottom wall of the meter. See Fig. 8.32. This suggests the mounting ofservice equipment below and rotated 90 degrees with respect to the meter socketand precludes the use of the center knockout in the meter socket for wires to the service equipment.
Nothing in the above is intended to prohibit the location of the service equipmentremote from the meter socket and adjacent to the mobile home structure.
8.8 MULTIPLE METER INSTALLATIONS On all installations involving more than one meter, each set of service entrance and metering equipment shall be legibly and permanently marked to designate the portion ofthe building that it supplies. Gang-type meter sockets are unacceptable for buildings notunder common ownership. Service connections between individual meter supports in multiple metering installations shall be run in rigid metallic conduit, electrical metallictubing, or flexible metallic tubing, and shall be properly bonded. Mechanically unprotected service entrance cable shall not be used for connections between meter sockets. Customer shall provide provisions for PECO to lock and fasten any potential tamper pointsahead of metering.
Metering Rev-10 February 2016 Page 6 of 84
8.8.1 More than Six Meters When more than six meters and associated disconnecting devices are installed at one location, a main sealable fused service switch or circuit breaker, of a type acceptable tothe Company, may be provided as required by the National Electrical Code. If installed outdoors, it shall be in a raintight enclosure.
8.8.2 Connections in Meter Mounting EquipmentOn all multiple metering installations adequate space shall be provided for the serviceconductors to each meter position. Where additions are to be made to existing meteringinstallation, the service conductors shall not be tapped in existing meter mountingequipment unless there is adequate space without overcrowding. Not more than one set of load side conductors shall be installed from each meter to supply the Customer's service switches or circuit breakers. In cases where a meter supplies more than one service switch or circuit breaker, a single set of load conductors (unless connectors supplied by the manufacturer are designed to accommodate more than oneconductor) shall be installed from the meter to a separate trough or splice box from which the conductors to each switch or circuit breaker shall be connected. Two service and load conductors in parallel, which conform to the requirements of the National Electrical code,will be permitted if required for capacity.
8.9 SELF-CONTAINED POLYPHASE METERING INSTALLATIONS
8.9.1 Three Phase PECO approved socket type meter mounting equipment shall be provided by theCustomer for all three phase four wire installations, both wye and delta configurations, and arranged so that the meter is installed on the line side of the service equipment.
8.9.2 Two Phase (Maintenance Only-Not for New Construction)Meter mounting equipment designed for bottom-connected meters shall be provided for alltwo-phase metering installations and arranged so that the meter is installed on the line side of the service equipment. A sealable metal meter connection box equipped with terminal blocks of a type acceptable to the Company shall be installed on the line side ofthe service equipment. The connection box may be an isolated sealable compartment of a combination meter and switch assembly (see Figures 8.09 and 8.10), or it may be a transformer enclosure. Acceptable equipment is listed in Table 8.09 and 8.15. Connection blocks used for the services and metering connections shall be equipped with approved solderless wire connectors. Eight terminals are required for 2 phase installations. Thegeneral requirements for terminal blocks are shown in Figure 8.10 and acceptable terminalblocks listed in Table 8.15.
Metering Rev-10 February 2016 Page 7 of 84
8.10 TRANSFORMER RATED METERING INSTALLATIONS
8.10.1 General All transformer rated metering installations shall be arranged so that the meteringtransformers are installed on the source side of the service equipment. Indoor transformer-rated metering installations shall be located immediately adjacent to the point at which the service conductors enter the building. A working clearance of 4 inches shall be provided between the back of the metering transformer enclosure and the building wall, or theenclosure may be mounted on a 1-inch minimum painted lumber backboard.
No service equipment is permitted ahead of the metering unless such installation isrequired by the NEC or other regulating agencies.
8.10.2 Single Phase InstallationsThe following installation is acceptable for residential and commercial loads exceeding 320 continuous amperes as computed according to the National Electrical Code.
8.10.2.1 Outdoor Combination Current Transformer and Meter Enclosure A combination current transformer and meter enclosure, provided and installed by the contractor in an outdoor location, as shown in Figure 8.12. The contractor shall install the two current transformers supplied by the Company.
This type of installation may also be used as an alternate to 320 amp self contained metering.
8.10.3 Polyphase InstallationsDepending upon the type of service installation, metering transformers for Polyphaseservices may be installed in the following:
8.10.3.1 Indoor Metering Transformer EnclosureSee Table 8.09 and Figs. 8.15, 8.16 and 8.18
8.10.3.2 Secondary Compartment of a 3∅ Padmounted Transformer See Figs. 8.17, 8.19, 8.20, 8.22, and 8.23
8.10.3.3 Outdoor Weathertight EnclosuresSee Figure 8.40
8.10.3.4 Requirements When Metering Transformers and Meter Are Separated (all voltages)Where metering transformers are installed in the secondary compartment of padmountedtransformers, switchgear, or other acceptable enclosures remote from the meter location,a rigid metal conduit shall be provided and installed by the contractor between the metertransformer enclosure and the meter location. The conduit and meter-mounting deviceshall be adequately grounded.
Metering Rev-10 February 2016 Page 8 of 84
The meter and meter panel(s) will be supplied, installed, and connected by PECO EnergyCompany. For secondary services, meters and metering transformers should be located in close proximity of each other without physical barriers between them. (i.e. Locatedeither inside together or outside together).
8.10.3.5 Secondary Conduit from SwitchgearThe Customer's Contractor shall furnish and install an adequate rigid metal conduitconnection for the meter secondary wiring between the metering transformer location anda meter location acceptable to the Company. The termination at the meter end will be anacceptable junction box listed in Table 8.13. (See Figure 8.39) All installations shall bedesigned so that not more than 4 quarter bends will be necessary in any run of conduitbetween pull boxes. Pull boxes, junction boxes, or other suitable conduit fittings shall beprovided to meet these limitations. All pull boxes shall be clear of any obstructions and bereadily accessible to PECO personnel. The Contractor shall provide removable coverswith means for sealing by the Company. Minimum sizes of conduit for meter transformersecondary wiring shall be as follows:
Length of Run Exposed Conduit Concealed Conduit
Up to 100' 1-1/4" 1-1/2"
100' to 300' 2" 2-1/2"
300' to 600' 2-1/2" 3" For conduit runs not exceeding nominally 5 ft. totally within equipment, 1 in. conduit isacceptable.
8.10.3.6 Secondary ConductorsIn general, it is desirable to design an installation so that the length of run for meteringtransformer secondary conductors will be as short as practicable, preferably under 30 feet.For secondary runs that do not exceed nominally 100 feet, the Company will furnish and install its standard color-coded wire in the conduit provided by the Contractor. For all secondary runs that exceed nominally 100 feet, the Contractor will install the secondarywire. The Company will furnish wire to suit the requirements of secondary runs between 100 and 600 feet. For secondary runs more than 600 feet, consult PECO Energy.
Customer equipment shall not interfere with or introduce burden in the metering circuit.
8.11 CONDUCTOR ENTRANCES
8.11.1 Current transformer enclosures Service and load conduits shall be connected through the side, bottom or back of anenclosure, but shall not obstruct any metering equipment.
8.11.2 Combination current transformer and meter enclosures Service and load conduits may be connected in the top and/or bottom of combination current transformer and meter enclosures. Top entrances of cable outdoors shall alwaysbe through an approved weatherproof connector installed in a weathertight hub with additional caulking.
Metering Rev-10 February 2016 Page 9 of 84
8.11.3 Alternate Location - Metering TransformerWhere the requested location of the metering transformer enclosure is not acceptable to the Company as a suitable meter location, the Contractor shall provide and install an adequate rigid metal conduit between the metering transformer enclosure and the accepted alternate meter location.
8.11.4 Enclosure Size *** Minimum sizes of current transformer enclosures acceptable for various sizes of service conductors are as follows:
Phases Wires Minimum Enclosure Suggested SuggestedSize Maximum Maximum Cable
Number of Size (kcmil) *** Cables ****
1 3 24" x 18" x 10" 32" x 24" x 10"
3 3
350 500
2 5 32" x 24" x 10" 42" x 32" x 10"
5 5
400 750
3 3 4∆ 4Y
32" x 24" x 10" 32" x 32" x 10" 32" x 32" x 10" 42" x 32" x 10" 54" x 42" x 12"
3 3 4 4 4
500* 500 400 750 750**
*Exclusive of neutral or ground conductor as required by N.E.C.**277/480 volt installations require this enclosure. (See Fig. 8.21)***Outdoor enclosures require minimum 15" depth****Customer is responsible to see that installation is NEC compliant
In instances where the NEC and/or amp capacity requires either a larger enclosure, more than the maximum number of cables, or larger than the maximum cable size, the customershall provide a switchgear enclosure for the metering transformers.
Metering Rev-10 February 2016 Page 10 of 84
8.12 METERING TRANSFORMERS The metering transformers will be supplied to the Customer's Contractor by the PECOEnergy Company office in the region in which the work is located. The Contractor shallinstall the transformers and make all primary connections. Manufacturers who mount the transformers in service control equipment may obtain the transformers from PECO EnergyCompany.
All voltage transformers will be fused for new installations. For 13kV metering, the voltagetransformers will be supplied by the Company with fuses already mounted. For 34kVmetering, the customer must install fuses directly ahead of the voltage transformers.Contact New Business Customer Engineering for type and size of fuses required.
8.12.1 DeliveryWhen the metering transformer service equipment and connecting conduits have been installed and are ready for wiring, the Contractor shall obtain the metering transformersfrom the local PECO Energy Company office. An advance phone call will assure the Contractor that the metering equipment is ready for pickup.
8.12.2 Mounting Metering Transformers in Metering EnclosuresUnistrut rails shall be attached securely to the back of the transformer enclosure with a minimum of two 1/4" x 20 corrosion resistant machine screws or thread cutting machine screws per rail. Sheet metal screws are not acceptable. Metering transformers shall beattached to the Unistrut with springnuts and machine bolts. Mounting of transformers on wood is no longer acceptable for new installations.
8.12.3 Mounting in Padmounted Transformers and SwitchgearMounting of metering transformers in a single-phase padmounted transformer isprohibited.
When a three-phase padmounted transformer supplies a single customer, the metering transformers may be installed in the padmounted transformer (See Figure 8.17, 8.19,8.20, 8.22). Metering transformers shall not be installed in padmounted transformers thatinitially supply multiple customers or may supply multiple customers in the future. In thesecases, the metering transformers shall be installed in a metering transformer or switchgearenclosure. The contractor shall make all metering transformer primary connections. The term "metering transformer" includes current and voltage transformers with voltagetransformers required only when the service voltage is 277 volts or greater.
When the Company supplies bus bar type metering current transformers for installation ina padmounted transformer, the metering current transformer primary bars shall always bebolted to the secondary spades of the padmounted transformer. If window type meteringcurrent transformers are supplied by the Company, for installation in a padmountedtransformer, they shall be mounted directly over the secondary spades of the padmounted transformer.
8.12.4 Metering Transformer ConnectionsThe Contractor shall terminate the service and load conductors with approved solderlessconnectors and securely bolt these to the terminals of the metering current transformers.Each service conductor shall be of sufficient length to permit it to be connected to a service terminal of any transformer in the enclosure. When window-type currenttransformers are required for capacity, the conductors must terminate in straight throughbolted connectors immediately adjacent to the load side of the current transformer. Metering Rev-10 February 2016 Page 11 of 84
Only one bolted connection (may involve the use of multiple bolts) shall be made to eachprimary terminal of a metering current transformer or secondary spade of a pad-mounttransformer. Where parallel conductors are required for capacity, all conductors shallterminate in multi-conductor connectors or on short pieces of suitable copper bus that, in turn, shall be the only bolted connection to the current transformer primary terminal, orsecondary spade of a pad-mount transformer. All primary terminals shall be properlyinsulated without concealing polarity markings or meter potential connection points.
Air is considered an acceptable insulating medium when the distance between energizedcomponents or energized components and ground meet applicable codes.
Metering transformer enclosures shall not be used as splicing enclosures to supplymultiple disconnecting devices. If the load side conductors extended from the metering transformer enclosure are to supply more than one disconnecting device, a splicing trough or gutter shall be installed between the metering transformer enclosure and the multiple disconnecting devices. Load side conductors extended from a metering transformerenclosure may supply both the heating/air conditioning and general load disconnectingdevices.
8.12.5 Meters The Company will furnish, install, and connect the meter and associated meter secondarywiring prior to the service being energized.
Metering Rev-10 February 2016 Page 12 of 84
8.13 METER MOUNTING EQUIPMENT The required types of meter mounting equipment for various classes of new andmodernized secondary services and maximum initial loads are as follows:
Maximum Initial Load Equipment Rating Total kVA Amperes per Phase Amperes and Type
Single Phase18 up to 75 100 Amp. socket (Note 2)
19 to 36 (Note 76 to 150 200 Amp Socket 1)
37 to 77 151 to 320 320 Amp Socket (Table 8.16) or
400 amp combination transformer-socket enclosure
over 77 over 320 transformer enclosure (Note 3)(Table 8.09 and 8.10)
Two Phase all loads all currents transformer enclosure (Note 3)
(Table 8.09 and 8.10)
Three Phase up to 62 (∆) up to 150 200 amp socket (Table 8.07)
over to 62 (∆) over 150 transformer enclosure (Note 3)(Table 8.09 and 8.10)
up to 54 (Y) up to 150 200 amp socket (Table 8.07)
over 54 (Y) over 150 transformer enclosure (Note 3)Table 8.09)
Note 1: For residential electric heating, may be up to 46 kW as computedaccording to N.E.C.
Note 2: 200 Amp. UG socket required on single position URD installations.For 6 meters or less, the service equipment shall be installed on the load side of each meter. For more than 6 meters a main control shall be installed on the line side of the meters.
Note 3: Current transformers are sized in relation to the contracted load.
8.14 METERING EQUIPMENT FASTENING REQUIREMENTS All metering equipment shall be fastened securely, level, and plumb. Metering equipment shall not be fastened to floor joists. Manufactured fastening devices, such as expansion shields, anchors, toggle bolts, or wood screws specifically designed for the application are acceptable when properly applied.
Metering Rev-10 February 2016 Page 13 of 84
8.15 METERING EQUIPMENT MOUNTING REQUIREMENTS
8.15.1 Outdoor In general, outdoor metering equipment may be mounted directly upon building walls. All mounting holes provided by the manufacturer shall be utilized, and no additional holesshall be made. All fastenings shall be made only to solid portions of the building materialand not to structural joints.
8.15.2 Indoor Metering equipment shall not be installed directly on indoor walls, which contribute to corrosion of the metal. Offset metal brackets providing a minimum of one-inch air space between the metering equipment and the wall shall be used, or a supporting backboard ofwood on battens may be erected. Where wood is used, it shall be of good grade, at leastone inch dressed thickness, or 3/4" exterior grade plywood, and shall be of sufficient area to fully support the equipment that is to be mounted on it. All fastenings, whether bracketsor backboards are used, shall conform to Company guidelines. Supporting battens shallbe used to provide a minimum of one-inch air space, and they shall extend beyond the backboard sufficiently to permit verification of fastenings employed. The backboard maybe securely nailed to the battens which shall be minimum 1-1/4"x2". All wood shall be painted with a good grade of paint.
Metering Rev-10 February 2016 Page 14 of 84
8.16.1 Socket and Self-Contained Meters The preferred mounting height for all socket and self-contained meters, except those
supplying temporary services, is 4 feet. Normally allowed variances from this dimension are shown in the references listed below:
Phases No. of Meter Sockets Service Reference
1 Single & Multiple Overhead Fig. 8.03
1 Multiple Underground Fig. 8.03
1 Single Underground Fig. 8.05
3 Single & Multiple Overhead & Fig. 8.08 Underground
8.16 MOUNTING HEIGHT OF METERS For the purposes of these Rules, the specified mounting heights for both indoor andoutdoor meters shall be the distance between the horizontal center line of the meter and the floor or finished grade level.
8.16.2 Transformer Rated Meters Where the size of the transformer enclosure precludes compliance with the minimumelevations required by the National Electrical Code for classified areas, the height shall be the least, which will result in conformance.
8.16.2.1 Installations 600 volts or LESS The top of indoor current transformer enclosures above which meters are to be mounted shall be approximately 45" above the floor. See Figures 8.15, 8.16, 8.18, and 8.21
8.16.2.2 Installations OVER 600 volts The top of the junction box above which a meter panel is to be set shall be 40" above thefloor or working surface. See Figure 8.39. Where pre-wired meter boards are used (Figures 8.41 and 8.52), the junction box is not used
8.17 PROVISIONS FOR SEALING All boxes, cabinets, troughs, fittings, and other enclosures containing unmetered service conductors or secondary wiring from Company metering transformers shall be providedwith acceptable means for sealing. All unnecessary openings shall be adequately closed to prevent unauthorized access. All outdoor CT cabinets or enclosures shall be furnished with a hasp or other means which enable locking with a 5/16” padlock.
8.17.1 Access to Company EquipmentThe Company's identified employees shall have access to the premises of the Customerduring business hours for the purpose of reading meters, and for installing, testing,inspecting, repairing, removing or changing any or all equipment belonging to theCompany. The Customer shall maintain a minimum of 3 feet clear working space in frontof each meter. Additional space will be required adjacent to moving machinery.
Metering Rev-10 February 2016 Page 15 of 84
8.17.2 Metering ProtectionThe Customer may have to install protective enclosures in areas where the Company's metering equipment is subjected to excessive moisture, dust, metal filings, grindings orsimilar substances, or to mechanical injury or acts of vandalism.
8.17.3 Ownership and RemovalAll equipment supplied by the Company shall remain its exclusive property. PECO EnergyCompany reserves the right to upgrade the metering to keep pace with new technologiesor to meet corporate missions. PECO shall have the right to remove the metering equipment from the premises of the Customer at any time after the termination of service for whatever cause. The Customer shall do all necessary work required because ofchange of service and meter facilities.
8.17.4 Metering SecurityPECO Energy maintains the right to lock and secure, with a PECO Energy lock, customerequipment containing PECO Energy metering equipment.
8.18 ACCEPTED METERING EQUIPMENT
8.18.1 General In order to meet the minimum specifications of these Electric Service Requirements,certain equipment must have the acceptance of the Company. Manufacturers of metering equipment covered by these regulations may be required to submit samples of such equipment for Company acceptance. The Company will list the manufacturer's catalog number of accepted equipment in the following tables of this section. Each table listsequipment that is accepted only for the class of service and conditions described in thetable heading. Accepted equipment is not interchangeable between tables unless listed ineach table by manufacturer's catalog number. ALL EQUIPMENT MUST MEET PECO APPROVAL PRIOR TO INSTALLATION. PECO reserves the right to require customers to remove unapproved equipment. PECO shall not be liable for any costs incurred on the customer due to installation and/or removal of unapproved equipment.
Prefix/suffix, number/letter variations to catalog numbers as listed, that identify items such as hub size of hub plate, are acceptable with local regional approval.
Metering Rev-10 February 2016 Page 16 of 84
The company reserves the right to install security devices on equipment that containsunmetered conductors.
8.18.2 Fifth Socket Jaw Where a 5th jaw is required in a meter socket, the Contractor should verify that theequipment selected has, or will accept, the 5th jaw in the 9 o'clock position. For connection diagrams of meter sockets, refer to Figures 8.06-B and 8.07.
8.18.3 Interruptible Rate Meter SocketsAcceptable meter sockets for interruptible rate meter installations are listed in Tables 8.01 and 8.02. Meter socket and breaker combinations listed in Table 8.05 are unacceptablefor this installation.
8.19 METERING FOR SERVICES OVER 600 VOLTS
8.19.1 Customer's ResponsibilityIn addition to the general requirements for metering outlined earlier in this section, theCustomer shall furnish and install all acceptable equipment necessary to accommodate the Company's metering devices required for the high voltage service. PECO Energy shallprovide the metering voltage and current transformers to be installed by the customer in acceptable enclosures or on adequate outdoor structures. The customer shall install the metering transformers and make all primary connections. VTs shall be connected on the source side of the CTs. CTs shall be mounted with the polarity marks toward the source. Depending upon such factors as service voltage, conductor size, and size of load to be served, meteringtransformers may be supplied separately or as assemblies (pre-mounted with secondarieswired) on flat type standard frames.
When the Company determines that compensated metering is to be used on high tension servicesthrough power transformer banks owned by the Customer, the Customer shall connect the meteringtransformers on the secondary side of his power transformer banks at a suitable location ahead ofany disconnecting devices. The Customer must provide a certified test report and a copy of thenameplate drawing for each transformer that is to have compensated metering. The certified test report shall include the following information: Manufacturer’s Name, Transformer Serial Number, KVA rating, Primary Voltage Rating, Secondary Voltage Rating, % Impedance, %Exciting Current, No Load Core Loss in Watts, and Full Load Winding Loss in Watts.
Only one bolted connection (may involve the use of multiple bolts) shall be made to eachprimary terminal of a metering transformer or secondary spade of a padmounted transformer. Where parallel conductors are required for capacity, all conductors shallterminate in multi-conductor connectors or on short pieces of suitable copper bus that, in turn, shall be the only bolted connection to the current transformer primary terminal orsecondary spade of a padmounted transformer. Secondary terminals of currenttransformers should be faced to allow dressing of secondary wires with maximumclearance from the high voltage conductors. After primary connections for meter voltagetransformers have been made, all primary terminals of the current transformers shall beproperly insulated without concealing polarity markings. All conductors connected to metering current transformers or passing through current transformer windows shall havethe phases clearly and permanently identified.
8.19.2 33 KV Metering Requirements
Metering Rev-10 February 2016 Page 17 of 84
8.19.2.1 Availability PECO Energy’s New Business Customer Engineering shall determine the metering voltage for all 33 KV high-voltage services. The preferred method, for up to 4 transformers per service, is to meter on the low voltage side of each transformer and; compensate each meter for the associated transformer loss. Customer owned transformers metered on the low voltage side, with a loss compensated meters, shall be located where the metering secondaries are within a reasonable distance from a common meter instrument location. A decision to meter at the primary voltage, for 33 KV customers, is based on economic impact to PECO’s metering installation. Typically, 33 KV primary meter installations are used for services with more than 4 transformers, or where the customer’s facility is a campus setting with customer owned 33 KV distribution, having transformers that are remote from one another.
8.19.2.2 33 KV Primary Metering Requirements The customer shall provide a switchgear compartment or outdoor structure for mounting of the Company’s metering voltage transformers, primary fuses, and current transformers. The metering structure or enclosure shall include surge protection and the required live parts to accommodate 3 - GECO EJO-1 38 KV, 2E current limiting fuses, and GECO catalogue #9F60FPK002. Metal clad or metal enclosed metering compartments incorporated into a 33 KV service equipment line-up, equipped with surge arresters in the service cable compartment do not require additional surge protection in the metering compartment. The customer’s transformer winding configurations and the expected load shall determine the number and rating of voltage transformers. Grounded-wye primary and secondary power transformer winding configurations are preferred to limit the impacts of ferroresonance. Such installations are metered with 3 element metering. Three (3) VTs rated 20,125-115 Volts and three (3) CTs are specified. Customers with delta connected transformers or services that do not include a PECO Energy system neutral are metered with 2 element meters. Two (2) VTs rated 34,500-115 Volts and two (2) CTs are specified.
8.19.3 Metering Panel MountingFor meter panel mounting, the Customer's Contractor is required to furnish and installmounting facilities for the meter panel in accordance with Fig. 8.39 & 8.40, 8.41 or 8.52.For metering 3 or more services at any voltage, consult the Company for mountinginstructions.
In instances where the meter panel is mounted on a standalone pedestal, the verticalpoles shall be rigid steel pipe. The pipes shall be set in 36" (minimum) of concrete. The structure shall be at least 3 feet from any transformer.
Metering Rev-10 February 2016 Page 18 of 84
8.19.4 Telephone ConnectionMany industrial and commercial meter installations are read remotely through a telephone line. The Company will arrange for the installation of the telephone. However, it is theresponsibility of the Customer to be certain that there is a means, through a separate conduit to the meter location, for the telephone line to be installed. The Customer should contact the Telephone Company to determine their requirements for the installation to the meter location.
8.19.5 Company's Responsibility - Meters and AccessoriesThe Company will furnish, and connect all meter panels and accessory equipment, and will connect the associated meter secondary wiring between the metering transformersand the meter panel prior to the service being energized.
Metering Rev-10 February 2016 Page 19 of 84
Table 8.01 Single Phase Socket Metering Equipment (Form 2S Ringless)
120/240 Volts, with Horn Bypass
Ampere Meter Talon Capacity Position Anchor Durham (3) (Landis & Gyr) Milbank Midwest Siemens Murray 100 1 URS1004B K3 HO UBH-RS101B UAT111-OPZA U7487-RL-KK-BL LRLPU412UALK ------- RJ192PX 100 1 UBHTTZRSS101B 200 1 Oh. URS1804B K3 HO UBH-RS202B UAT317-OPZA U7021-RL-KK-BL LQRLPU414BALK WRS192PX RS192PX 200 1 Ug. 1URS1804B K3 UBH-RS212B UAS817-PPZA U1980-0-KK-BL LQRLPU41412BALK ------- R499P
U4413-0-KK-BL 200 1 Ug. Side Wire UBH-RS223A ------- LTU276BALK ------- WRL199P -------100 2 Hor. 2URS1004L B K3 C350 HO UBH-2R1121B UA2311-0PZA U8032-XL-KK-BL ------- WRN291AR RN291PR 100 3 Hor. 3URS1004L B K3 C350 HO UBH-3R1121B UA3311-0PZA U8033-XL-KK-BL ------- WRN391AR RN391PR 100 4 Hor. 4URS100RL B K3 C350 HO UBH-4R1121B UA4311-0PZA U8034-XL-KK-BL ------- WRN491AR RN491PR 100 5 Hor. 5URS1004L B K3 C350 HO UBH-5R1121B U8035-XL-KK-BL ------- ------- -------100 6 Hor. 6URS1004L B K3 C350 HO UBH-6R1131B U8036-XL-KK-BL ------- ------- -------200 2 Hor. 2URS1804 B K3 C600 HLO UBH-2R2332T UA2717-YPZA U1252-X-KK-BL-K3 ------- ------- RM291PR 200 3 Hor. 3URS1804 B K3 C600 HLO UBH-3R2332T UA3717-YPZA U1253-X-KK-BL-K3 ------- ------- RM391PR 200 4 Hor. 4URS1804 B K3 C600 HLO UBH-4R2352T UA4717-YPZA U1254-X-KK-BL-K3(1) ------- ------- RM491PR 200 5 Hor 5URS1804 B K3 C600 HLO UBH-5R2392TT UA5719-KPZA U1255-X-KK-BL-K3(1) ------- ------- -------200 6 Hor. 6URS1804 B K3 C600 HLO UBH-6R2392TT UA6719-KPZA U1256-X-KK-BL-K3(2) ------- ------- -------
Note: Ringless meter socket covers have a 7/16" knockout provision for a barrel lock. (1) OH Service requires #K3923 extension kit (2) OH Service requires #K3955 extension kit
(3) Durham manufactures boards under Square D (SQD), Eaton (CH) and Midwest (MEP) brand labels.
Metering Rev-10 February 2016 Page 20 of 84
Table 8.02 Single Phase Metering Equipment
120/240 Volts (Form 2S Ringed & Ringless)
Ampere Meter Anchor Talon (L&G) Milbank Murray Siemens Capacity Positions
100 2 Vertical 2USV1004-HOSR2 (1) ----- U2692-XL-KK-BL ----- -----100 3 Vertical 3SV1004-HOSR2 (1) UA3B11-OPZA U2693-XL-KK-BL ----- -----125 2 Vertical UA2B11-OPD ----- RV291AX SUA2B11-OPD
Metering Rev-10 February 2016 Page 21 of 84
Table 8.03 Single Phase Socket Metering Equipment - Transformer Rated 240 Volt, Ringless - Indoor or Outdoor - 6 Jaws, Form 4S
Anchor (OBSOLETE) URS1006B-HO w/Horn Bypass Milbank CE-136 w/Test Switches Eaton/Cutler Hammer USTH61A195CH w/Test Switches
Metering Rev-10 February 2016 Page 22 of 84
Table 8.04 Combination Single Phase Meter Socket and Service Equipment
100, 150 & 200 Amperes, 120/240 Volts (Form 2S) & 120/208 Volts (Form 25S)
Meter Positions Anchor Cutler Hammer Midwest Murray Siemens
1 US7511 FP 100 HO MBP200BTSD (5) MO36G(1)(3) JC002CZ (7) 1 M100C(3) JC0406L1200RH(6)(7) MM0406ML1200F/S/H 1 M101C(3) MM0406L1200RH 1 M281C1(3) 1 R256EV-1 (4)
Milbank Talon 1 U5168-XTL-100-KK-BL UAB111-OPCH 1 U5168-XTL-150-KK-BL UAB317-OPCH 1 U5168-XTL-200-KK-BL 1 U5898-O-200-KK-BL
(1) For temporary and construction applications (2) Note has been deleted (3) Substitute an 'R' for 'M' to indicate ringless (4) Replaces RS250C & MS250C which are still acceptable (5) Replaces CGBT2125S & CGBT2200S which are still acceptable (6) Replaces JC904CZ which is still acceptable (7) Obsolete but still on system
Metering Rev-10 February 2016 Page 23 of 84
Table 8.05 Single Phase Multiple Meter Breaker Equipment
100 and 200 Amperes, 120/240 Volts (Form 2S) & 120/208 Volts (Form 25S) STEEL Trough - Indoor and Outdoor
Eaton Cutler Hammer General Electric Murray (Obsolete) Siemens ITE Square D 1MM Series (5)(9) Mini Mod III UM (10) Series (5)(6) WMM Series (4)(9) EZM Series 3 through 6 positions TMM Series (4)(5)(6) AM (10) Series (4)(5) 2 through 6 positions 3 through 10 positions
2 through 6 positions DC, DG Series (4)(5 1MP Series (5)(9) 2 through 6 positions
AC (10) Series MP (PAK) Series (4) 2 through 6 positions
WP (PAK) Series (4) 2 through 6 positions
MP Series (3) 2 through 6 positions
Milbank U5902-X-KK-BL U5903-X-KK-BL U5904-X-KK-BL U5905-X-KK-BL U5906-X-KK-BL U5882-X-KK-BL U5883-X-KK-BL U5884-X-KK-BL U5885-X-KK-BL U5886-X-KK-BL
(1)(2) These notes have been deleted (3) Add a suffix of "R" for ringless (4) 200 ampere per position available (5) Acceptable for outdoor installations (6) Use adapter HDRXA and Hub RX200 for underground entrance (7) This note has been deleted (8) 200 Amp per position (9) Totalizer/General (10) Obsolete but still acceptable
Metering Rev-10 February 2016 Page 24 of 84
Table 8.06 Single Phase Combination Transformer Socket
Metering Equipment, 120/240 Volts
Trans-Rated Unit
Anchor S002091 Obsolete unit, but still acceptable Milbank U2228
Metering Rev-10 February 2016 Page 25 of 84
Table 8.07 Three Phase Socket Metering Equipment
100 & 200 Amperes, 4 Wire, Wye or Delta, 250-Volt Max.
Manufacturer Anchor
C atalogue No. --------TB2072-HO/HLO U22572-HO
Manufacturer General Electric
Catalogue No. TMP Series (1)(2)
Eaton/ Cutler Hammer SCMM(2)
37MM120(2) 37MM220(2) 37MM320(2) 37MM420(2)
Talon (Landis & Gyr)
40407-025 40407-9 40007-01
Siemens WRH173GR (3) UB-C 7213B S40407-025 UB-H7213-(1) WML13100RJ EZM743200R WML13225RJ WML23100RJ WML23225RJ WML33100RJ WML33225RJ WML43100RJ WML43225RJ
Square D EZM742200R
Milbank U7423-RXL
Murray RH173GR DL141W7 DL241W7 DL341W7 DL441W7 DL142W7 DL242W7 DL342W7 DL442W7
(1) With clamping jaw (2) Totalizer (3) Square D (SQD), Cutler Hammer (CH), Midwest (MEP)
Metering Rev-10 February 2016 Page 26 of 84
Table 8.08 Primary Metering Transformer Enclosures
Type Penn Panel Indoor ISTC Outdoor OSTC
Where means for primary disconnections are required within these enclosures use cutouts with solid links rated 200 Amperes, 5.5kV, 10,000 Amp. momentary.
Metering Rev-10 February 2016 Page 27 of 84
Table 8.09 Secondary Metering Transformer Enclosures
Indoor Only Enclosure Size*
W x H x D Austin Penn Panel Unity East Coast K & S 24" x 18" x 10" ----- 241810 PEC241810DDCT PE-182410 1-10 32" x 24" x 10" AB243210CTD-PECO 322410 PEC322410DDCT PE243210 2-10 32" x 32" x 10" AB323210CTD-PECO 323210 PEC323210DDCT PE323210 3-10 42" x 32" x 10" AB324210CTD-PECO 423210 PEC423210DDCT PE324210 4-10 54" x 42" x 12" AB425412CTD-PECO 544212 PEC544212DDCT PE425412 5-10
Enclosure Size*
W x H x D C & I Hoffman Milbank 24" x 18" x 10" C-182410DCT-PECO A241810CTDP-PECO 182410-CTC1-SP 32" x 24" x 10" C-243210DCT-PECO A322410CTDP-PECO 243210-CTC1-SP 32" x 32" x 10" C-323210DCT-PECO A323210CTDP-PECO 323210-CTC1-SP 42" x 32" x 10" C-324210DCT-PECO A423210CTDP-PECO 324210-CTC1-SP 54" x 42" x 12" C-425412DCT-PECO A544212CTDP-PECO 324210-CTC1-SP
*Refer to Paragraph 8.11.4 for application
Metering Rev-10 February 2016 Page 28 of 84
Table 8.10 Secondary Metering Outdoor Transformer Enclosures
Enclosure Size* H x W x D Austin C & I Penn Panel Unity K & S
28" x 18" x 15" ----- C-281815WD3R-PECO OWM-281815 PEC182815SDCT3 M2810 35" x 30" x 15" AB353015WLD-PECO C-353015WD3R-PECO OWM-353015 PEC303515DDCT3 M3530 35" x 40" x 15" AB354015WLD-PECO C-354015WD3R-PECO OWM-354015 PEC403515DDCT3 M3540 42" x 32" x 15" AB423215WLD-PECO C-423215WD3R-PECO OWM-423215 PEC324215DDCT3 M4232 42" x 54" x 15" AB425415WLD-PECO C-425415WD3R-PECO OWM-425415 PEC544215DDCT3 M5442
Enclosure Size* H x W x D Hoffman Milbank
28" x 18" x 15" A281815CTDP-PECO3R 182815-CT3R-SP 35" x 30" x 15" A353015CTDP-PECO3R 303515-CT3R-SP 35" x 40" x 15" A354015CTDP-PECO3R 324215-CT3R-SP 42" x 32" x 15" A423215CTDP-PECO3R 403515-CT3R-SP 42" x 54" x 15" A425415CTDP-PECO3R 544215-CT3R-SP
Metering Rev-10 February 2016 Page 29 of 84
Table 8.11 Single Phase Meter Pedestals
100 and 200 Amperes, 125/250 Volts With Service Equipment (1)
Ampere Positions Anchor (OBSOLETE) Midwest Capacity 100 1 PB1-B200-PE M100CP6 100 2 PB2-B200-PE M100CB6 200 1 2PB2-B200-PE M101CB6 200 2 ----- M200CP6(2)
M200CB6(2)
(1) Use with post and stabilizing foot (2) Available w/150 amp main breaker
Metering Rev-10 February 2016 Page 30 of 84
Table 8.12 Totally Recessed
Meter Mounting Enclosures
Enclosure Size W x H x D Penn Panel
17" x 19" x 15" RWM-191715
NOTE: MAINTENANCE ONLY- NOT FOR NEW CONSTRUCTION
Metering Rev-10 February 2016 Page 31 of 84
Table 8.13 Junction Boxes for Transformer Type Meter Panels
Size of Box H x W x D
12” x 12” x 4”* H & R Ind. 12124-PE
K & S 4-12
Standard Penn Panel 12124
Standard Elec. Supply 12124
*includes channels
Metering Rev-10 February 2016 Page 32 of 84
Table 8.14 End Boxes for Underground Secondary Services
Size of Box Standard Standard H x W x D H & R K & S Penn Panel Queen Products Elec. Supply 12” x 12” x 5” UGB-12125 5-12 12125 USB 12125 PE 125 16” x 16” x 6” UGB-16166 6-16 16166 USB 16166 PE 166 20” x 20” x 8” UGB-20208 8-20 20208 USB 20208 PE 228 24” x 24” x 10” UGB-242410 10-24 242410 USB 242410 PE 248 36” x 36” x 18” UGB-363618 36-18 ----- ----- -----42” x 42” x 24” UGB-424224 42-24 ----- ----- -----
Metering Rev-10 February 2016 Page 33 of 84
Table 8.15 Meter Connection Blocks
For Use in Secondary Metering Transformer Enclosures
Standard Capacity Anchor Elec. Supply Superior 100-2 Pole PE9102 C-14 2043-C 200-2 Pole PE 9402 C-155 2094-G 200-4 Pole PE9404 ----- -----200-8 Pole ----- ----- -----
NOTE: MAINTENANCE ONLY- NOT FOR NEW CONSTRUCTION
Metering Rev-10 February 2016 Page 34 of 84
----
Table 8.16 Single Phase Metering Equipment – Self Contained
240 Volt Ringless – 320 Amp Continuous
Manufacturer Catalog Number
Talon (Landis & Gyr) 44704-8265 (1) Milbank U3000-0-2/K3L-BL
Cutler Hammer 1008435-ECH (2) Midwest 1008435-MEP (2) Square D 1008435-SQD (2)
(1) Murray & Siemens offer identical unit with "S" prefix (2) Cutler Hammer, Midwest, and Square D boards manufactured by Durham.
Metering Rev-10 February 2016 Page 35 of 84
AFTER THE METERING TRANSFORMERS ARE INSTALLED, CALL METER SERVICES
7 TO 10 BUSINESS DAYS PRIOR TO SERVICE DATE AT 610-648-7869
Meter Services will wire CT's & PT's before service is energized
NOTE: White dot is line side of CT (H1) DO NOT REMOVE THE SHUNTS FROM THE CT'S
If CT's are installed in a CT cabinet. Mount them with Unistrut and spring nuts
DO NOT USE PLYWOOD
Figure 8.00
Metering Rev-10 February 2016 Page 36 of 84
I ' \ '
D
I I I I ·1-.
I I I
j - J. -I I
I I
- T - I
I I I I I I I
0
EXPLANATION OF TERMS USED IN TYPICAL SERVICES TO SINGLE RESIDENTIAL PROPERTIES
UNDERGROUND OVERHEAD LINE STREET MAIN
SERVICE LATERAL
COMPANY POLE
BUILDING WALL
OUTDOOR METER
INDOOR METER
SERVICE EQUIPMENT
BASIC OVERHEAD SYSTEM BASIC UNDERGROUND SYSTEM
POINT OF DELIVERY
SERVICE DROP
PROPERTY LINE
ATTACHMENT TO BUILDING MAST,
LATERAL TERMINATES AND SERVICE ENTRANCE CONDUCTORS BEGIN AT POINT OF DELIVERY 18” INSIDE PROPERTY LINE
ARE SPLICED AT THIS POINT OR CONTINUOUS INTO BUILDING.
ON SERVICES INSTALLED AFTER AUG. 1970 THE LAT-ERAL TERMINATES AT AN END BOX IF THE METER IS INDOORS. SE
RVICE ENTRANCE
CONDUCTORS
SERVICE ENTRANCE
CONDUCTORS
POLE, ETC. OR CONNECTION OF SERVICE ENTRANCE CONDUCTORS TO REAR BUS.
WHETHER CONDUCTORS
POINT OF DELIVERY WHEN BUILDING IS AT PROPERTY LINE.
END BOX
Figure 8.01
Metering Rev-10 February 2016 Page 37 of 84
I - - -
SEQUENCE OF METERING AND SERVICE EQUIPMENT GROUPED FOR MULTIPLE OCCUPANCIES
INCOMING SERVICE
BUILDING WALL
SPLICE BOX-(WHERE SPLICE BOX IS NOT USED, TYPE SE CABLE IS ACCEPTABLE IN A CONTINUOUS SHORT RUN INTO SERVICE EQUIPMENT)
RACEWAY (REQUIRED WITH SPLICE BOX)
RACEWAY
SERVICE EQUIPMENT (MAIN DISCONNECTING AND OVERCURRENT DEVICE) *
METERS
FEEDER PROTECTIVE AND DISCONNECTING DEVICES
FEEDERS
BRANCH CIRCUIT PANELS (LOCATED IN INDIVIDUAL OCCUPANCIES)
FOR MORE THAN 6 METERS, A MAIN DISCONNECTING AND OVERCURRENT DEVICE MAY BE USED TO COMPLY WITH THE N.E.C.
Figure 8.02
*
Metering Rev-10 February 2016 Page 38 of 84
0
0
MOUNTING HEIGHT OF METER SOCKETS INDOOR AND OUTDOOR
3’ MINIMUM 4’ PREFERRED 5’ MAXIMUM
CL
SINGLE SOCKET OR SINGLE ROW OF HORIZONTALLY GROUPED SOCKETS (see note)
BOTTOM POSITION MINIMUM 3’
TOP POSITION MAXIMUM 6’
CL
CL CL
CL
VERTICALLY GROUPED SOCKETS OR MULTIPLE ROWS OF HORIZONTALLY GROUPED SOCKETS (see note)
Note: Three feet of clear working space must be maintained in front of each meter.
For 6 position board min and max positions are 2-1/'2' to 6-1/2'
Figure 8.03
Metering Rev-10 February 2016 Page 39 of 84
RECESSED INSTALLATION SINGLE-PHASE RESIDENTAL
UNDERGROUND SERVICE
Figure 8.04
1. All equipment shown installed by contractor at time of building construction.
2. Front cover of meter socket shall be located not greater than 14" nor less than 10" from the door of the enclosure.
NOTE: MAINTENANCE ONLY- NOT FOR NEW CONSTRUCTION
Metering Rev-10 February 2016 Page 40 of 84
1 OOA 2 200A 2 300A 2 400A 400A
PREFERED LOCATION
1/2 11
1/2" 1 /2"
3" 3"
3-#2AL. 3-#2/0AL.
ALTERNATE LOCATION
2-#4/0AL.&1-2/0AL. 2-350kcmi I AL.&1-4/0AL 2-500kcmi I AL.& 1-4/0AL
ITEM
{ { {
{ {
10
11
NOTES (al CONDUIT AND STRAPS TD BE
PROVIDED BY DEVELOPER.
( b) APPROVED PECO METER SOCKET TO BE PROVIDED BY DEVELOPER.
(cl EXTEND CDNDUIT (ITEM 71 TD UNDISTRUBED EARTH 2' -0" BEYDND EXCAVATION LINE.
( d l USE CEMENT ( ITEM 4 l ON ALL CONDUIT JOINTS.
(el CLEAN ALL CONDUCTORS, COAT WITH COMPOUND C ITEM 5 l. THEN TIGHTEN METER CONNECTION FIRMLY.
Cf l INSTALL STRAP ( ITEM 9 l JUST BELOW BEND COUPLING. ANCHOR SECURELY INTO MASONRY USING ITEM 1 Q.
(gl INSTALL N,E.C. CONDUIT STRAP ( ITEM 81 APPROX. HALF WAY UP EXPOSED CONDUIT. ANCHOR SECURELY INTO WALL USING ITEM 10.
INSTALLED SIU. OF MATERIAL
CODE NO. DESCRIPTION OUANITY
"" RISER.2 1,," X 10' PVC} W/TERM ADAPTER
** RISER, 3" X 10' PVC W/TERM ADAPTER
"" LOCKNUT 21,z' } ** LOCKNUT 3"
** 21,z' PVC TERMINAL ADAPTER } .. "" 3" PVC TERMINAL ADAPTER
** PVC CEMENT,PINT .. COMPOUND, ELECTRICAL .. CONNECTION
** 21,{ 90 BEND 18" MIN.R}
** 3" 90 BEND 18" MIN. R.
** 21,z' S40 CONDUIT } ** 3" S40 CONDUIT
** N.E.C. CONDUIT STRAP
** GALV. HEAVY GAUGE 2 HOLE STRAP
** 3'8" GAL V. F ASTNER .. ** 21,z' S40 CONDUIT COUPLINGS ..
3" S40 CONDUIT CDUPL I NGS
•AS REQUIRED ffSUPPLIED BY DEVELOPER
UNDERGROUND RESIDENTIAL DIST. SECONDARY SERVICE INSTALLATION
Figure 8,05 Ref. Constr. Std.S-5537 /G-2600
Metering Rev-10 February 2016 Page 41 of 84
w z _, z D
>.,: >
~ w
10"
CAUTION 1
CAUTION 1
6" MIN,
~EXCAVATION LI NE _______________________ _
PLAN VIEW
w :rn===~--=~-.L----j z D
>.,: > .,: u X w
100A 200A 300A 400A 400A
ELEVATION TABLE
2 1 /2" 2 1 /2" 2 1 /2"
3" 3"
3-#2AL. 3-#2/0AL. 2-#4/0AL.&1-2/0AL. 2-350komi I AL.&1-4/0AL 2-500kcmi I AL,& 1-4/0AL
CAUTION 1
z
"
UNDERGROUND RESIDENTIAL DIST. SECONDARY SERVICE INSTALLATION
Figure 8.05-A
Ref. Constr. Std.S-5537 /G-2600
Metering Rev-10 February 2016 Page 42 of 84
SINGLE PHASE METER SOCKET CONNECTIONS
APPLY TAPE TO BARE NEUTRAL INSIDE METER SOCKETS
INCOMING SERVICE
NEUTRAL
NEUTRAL
TO SERVICE EQUIPMENT
120/240 VOLT, 3 WIRE Figure 8.06-A
Metering Rev-10 February 2016 Page 43 of 84
SINGLE PHASE 120/208 VOLT METER SOCKET CONNECTIONS FOR RESIDENTIAL APPLICATIONS
INCOMING SERVICE 120/208 VOLT, 3 WIRE SERVICE FROM 3 PHASE 4 WIRE WYE SYSTEM.
NEUTRAL
TO SERVICE EQUIPMENT
NEUTRAL
APPLY TAPE TO BARE NEUTRAL INSIDE METER
FOR METERING NETWORK 120/208 VOLT SERVICE WHEN DERIVED 2 PHASES OF A 3 PHASE, 4 WIRE WYE SYSTEM.
CONTRACTOR TO SUPPLY AND INSTALL 5TH JAW AND CONNECTION TO NEUTRAL TERMINAL WITH #14 AWG WIRE.
NOTE: PRIOR TO PURCHASING EQUIPMENT OR INSTALLING THESE METER CHECK WITH COMPANY TO DETERMINE AVAILABILITY OF THIS VOLTAGE.
Figure 8.07
Metering Rev-10 February 2016 Page 44 of 84
THREE PHASE METER SOCKET CONNECTIONS
B
120V
120V
120V
NEUTRAL
208V
208V208V
A
C
THREE PHASE, 4 WIRE WYE
CENTER OF METER TO BE BETWEEN 3’ AND 5’ ABOVE FINISHED GRADE.
4’ ABOVE FINISHED GRADE IS PREFERRED.
.
A B N C
120V
208V
120V
NEUTRAL
240V
240V240V
A
B
C
HIGH LEG
THREE PHASE, 4 WIRE DELTA NOTE: HIGH LEG TO BE MARKED WITH RED TAPE AT ALL WIRE ENDS OF SERVICE AND BE ON THE RIGHT SIDE OF THE METER BOX.
A B N C Figure 8.08
Metering Rev-10 February 2016 Page 45 of 84
--Al
.- -I I I I I I I I I - - -
I I I -t-~-... I -------------,--T--
1 I
I
TWO PHASE, FIVE WIRE, SELF-CONTAINED METERING INSTALLATION
MAINTENANCE ONLY NOT FOR NEW CONSTRUCTION
LOAD
SERVICE
FUSED SERVICE SWITCH OR
CIRCUIT BREAKER
OPTION 1
METER
SEALABLE METER CONNECTION BOX
3’ MINIMUM 4’ PREFERRED 5’ MAXIMUM
METER AND CONNECTION BOX TO BE MOUNTED ON BACKBOARD, MINIMUM 1” LUMBER OR 3/4” PLYWOOD
FUSED SERVICE SWITCH OR
CIRCUIT BREAKER
OPTION 2 LOAD
METALLIC NIPPLES TO BE AS SHORT AS
POSSIBLE
Figure 8.09
Metering Rev-10 February 2016 Page 46 of 84
t ~ @~ ~ Q -
© © © © © © © 0 0 0 0 0 0 0 0 ~
0 0 0 ~ ~
0 0 K) t' 0" 'IO" t' 0 \ ~ l ~ l ~ I. """"" """"" """"" 0 0 0 0 0 0 0 0
© © © © © © © © _J I
-
SERVICE AND METER CONNECTION BLOCK TWO PHASE, FIVE WIRE, SELF-CONTAINED
METERING INSTALLATIONS MAINTENANCE ONLY - NOT FOR NEW CONSTRUCTION
CERAMIC MATERIAL OR EQUIVALENT REQUIRED FOR BLOCK BASE
3
2
1
LOAD SERVICE NOTES: 100 AMPHERE TERMINAL BLOCKS
1. 1/2” HEXAGON NUTS AND AT LEAST 3/8” OF EXCESS STUD TO PROVIDED ON EACH WIRE TERMINAL, UNLESS SPARE FOR BRIDGING PURPOSES ARE PROVIDED. THESE STUDS MAY EITHER 12-24 OR 1/4”-20 THREAD.
2. 1/2” HEXAGON DISCONNECT NUTS OR REMOVABLE LINKS MAY BE USED.
3. 3/4” MINIMUM CLEARANCE BETWEEN BLOCKS EQUIPPED DISCONNECT STUDS AND NUTS, OR A MINIMUM CLEARANCE BETWEEN BLOCKS EQUIPPED WITH REMOVABLE LINKS EXCEEDS THE LENGTH OF THE REMOVABLE LINKS, IS UNLESS AN ADEQUATE INSULATING BARRIER EXTENDING TO TOP TERMINALS IS PROVIDED AT EACH OF THESE
4. ALL STUDS AND NUTS TO BE MADE OF CORROSION RESISTANT MATERIAL OR ADEQUATELY
5. TERMINALS SHALL BE SUITABLE FOR COPPER OR ALUMINUM CONDUCTORS.
Figure 8.10
Metering Rev-10 February 2016 Page 47 of 84
CURRENT TRANSFORMER METERING INSTALLATION SINGLE PHASE SERVICE
120/240 VOLT 3 WIRE SERVICES IN EXCESS OF 400 AMPS* (*Can be used for 400 Amp Service upon Company Approval)
UNDERGROUND OR AERIAL INSTALLATION
FUSED SERVICE SWITCH OR CIRCUIT BREAKER
C T
C T
3’ MINIMUM 4’ PREFERRED 5’ MAXIMUM
RIGID METAL CONDUIT 1 1/2” MINIMUM
CURRENT TRANSFORMERS MOUNTED ON UNI-STRUT WITH SPRING NUTS.
TRANSFORMER RATED 6 JAW METER SOCKET
BOND THE CABINET
Figure 8.11
Metering Rev-10 February 2016 Page 48 of 84
CURRENT TRANSFORMER METERING INSTALLATION SINGLE PHASE 120/240 VOLT 3 WIRE.
FROM AERIAL SERVICE (UNDERGROUND SERVICE TO ENTER FROM BOTTOM OF SOCKET)
BUILDING WALL
TWO CURRENT TRANSFORMERS MAX. 400/5
3’ MINIMUM 4’ PREFERRED 5’ MAXIMUM
Figure 8.12
FUSED SERVICE SWITCH OR CIRCUIT BREAKER
COMBINATION TRANSFORMER
METER ENCLOSURE
CT
Metering Rev-10 February 2016 Page 49 of 84
THIS FIGURE HAS BEEN DELETED
Figure 8.13
THIS FIGURE HAS BEEN DELETED
Figure 8.14
Metering Rev-10 February 2016 Page 50 of 84
--""""o '-----I
---10
-----10 '-----I
0
0 i----.. 1--------'
0 i----
0
0
NEUTRALBOND CABINET
C T
C T
MINIMUM SIZE 32”x24”x10”
OPTION#1
OPTION#2
TO SERVICEEQUIPMENT
C T
C T
EELLEECCTTRRIICCIIAANN TTOO IINNSSTTAALLLL EEVEVERRYTYTHHIINGNG SSHHOWOWN.N. MMEETTEERR BBOAROARDD CCAAN BN BEE IINSNSTTALALLLEEDD ON TON TOPOP OROR
EEIITTHHERER SSIIDDEE OOFF CCTT CCAABBIINNETET.. CCEENNTERTER OOFF MMETERETER PECPECOO WWIILLLL SSUUPPLPPLYY MMETETERER,, TTO BO BEE BBEETTWWEEEEN 3N 3’’ && 55’’ ABABOVEOVE TTHEHE FFLLOOROOR.. BBOOAARRDD,, && CC.T.T.’.’SS
OPTION #2
1 1/1 1/22”” OPTION RRIIGGIID MD MEETTALAL #1 NNIIPPLPPLEE
AATTTTAACCHH CC..TT..’’SS TOTO CCAABBIINNEETT WWIITTH UNH UNIISSTTRRUUTT AANND SD SPPRRIINNGG
MINIMUM SIZE 32”x24”x10”
WWWHHHIIITTTEEE DDDOOOTTT IIISSS LLLIIINNNEEE SISISIDDDEEE OOOF CF CF C...TTT...’’’SSS (((HHH111)))
FRFROOMM PEPECCOO TTRRAANNS.S. OROR SSEECCONDONDAARRYY MMAIAINN ((CCUUSSTTOOMMEERR SSUUPPPPLILIEEDD))
Metering Rev-10 February 2016 Page 51 of 84
Figure 8.15
NUTS.
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S.(MAY INCLUDE MULTIPLE BOLTS)FOR MORE THAN ONE CABLE USEMULTI-CONDUCTOR CONNECTORS
NEUTRAL BOND CABINET
C T
C T
NUTS.
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS
TO SERVICE EQUIPMENT
CCURURRREENTNT TTRR
ANS
ANSFFO
RORMMEERR MMEETTEERR
IINGNG IINSNSTTA
LALLLA
TATIIOO
NN
2 P2 PHH
AASSEE 12O12O
//240 V240 V
OOLLTT 5 W5 W
IIRREE
-------~~---------------
C T
C T
C TNEUTRAL
B 0
C 0
BOND THE CABINET
120 VOLT
120 VOLT
120 VOLT
OPTION#1
A 0
OPTION#2
C T
C T
C T
CCOOMMMMEERRCCIIAALL CCUUSSTTOOMMEERR,, 3 P3 PHHAASSEE 120/120/208 V208 VOOLLTT RARATTEE CMCM
EELLEECCTTRRIICCIIAANN TTO IO INSNSTTALAL EEVEVERRYTYTHHIINGNG SSHHOWOWN.N.
PECPECOO WWIILLLL SSUUPPLPPLYY MMETETERER,, BOBOAARRDD,, && CC..TT..’’SS
ATATTTACACH CH C..TT..’’SS TTOO CCAABBIINNEETT WWIITTH UNH UNIISSTTRRUUTT AANNDD SPRSPRIINNGG NNUUTTS.S.
FRFROOMM PEPECCOO TTRRAANNS.S. OROR SSEECCONDONDAARRYY MMAIAINN ((CCUUSSTTOOMMEERR SSUUPPPPLILIEEDD))
((IINDOORNDOOR MMEETTEERR)) AABBOVOVEE 5544 KVKVAA MMEETTEERR BBOAROARDD CCAAN BN BEE IINSNSTTALALLLEEDD ON TON TOPOP OROR
EEIITTHHERER SSIIDDEE OOFF CCTT CCAABBIINNETET.. CCEENNTERTER OOFF MMETERETER TTO BO BEE BBEETTWWEEEEN 3N 3’’ && 55’’ ABABOVEOVE TTHEHE FFLLOOROOR..
AABBOVOVEE 5544 KVKVAA 1 1/1 1/22””
RRIIGGIID MD MEETTALAL OPTION NNIIPPLPPLEE #1
TTOO SSEERRVVIICCEE EEQQUUIIPPMMEENNTTC T
C T
B 0
C T C 0
NEUTRAL BOND THE CABINET
120 VOLT
120 VOLT
120 VOLT
A 0
OPTION #2
WWWHHHIIITTTEEE DDDOOOTTT IIISSS LLLIIINNNEEE SISISIDDDEEE OOOF CF CF C...TTT...’’’SSS (((HHH111)))
MMIINNIIMMUUMM SSIIZZEE CCAABBIINNEETT ((32”32”HH xx 3232””WW xx 1010””DD))
ONLONLYY ONEONE BBOLOLTTEEDD CCONNEONNECCTTIIONON SSHHAALLLL BBEE MMAADDEE TTOO TTHHEE CC..TT..’’SS.. ((MMAAYY IINNCCLLUUDDE ME MUULLTTIIPPLLEE BBOOLLTTSS)) FFOROR MMOROREE TTHAHAN ONEN ONE CCAABBLLEE UUSSEE MMUULTILTI--CCONDONDUUCCTTOROR CCONONNENECCTTORORSS
((DDRRAAWWIINGNG FFOROR RREEFFEERREENCNCEE ONLONLY)Y) NOTNOT DRDRAAWWNN TTO SO SCCAALLEE CCONDONDUUIITT MMAYAY EENTNTEERR CCAABBIINENETT FFRROMOM SSIIDEDESS,, BBAACCK,K, OROR BBOTOTTTOMOM
Figure 8.16
Metering Rev-10 February 2016 Page 52 of 84
SINGLE COJ\,fl\,ffiRCIAL CUSTO11ER, 3 PHASE 120/208 VOLT RATE CM (OUTDOOR 11ETERING)
PECO WILL m\TALL TRANSFORMER. CONTRACTOR TO SUPPLY PRJMARY AND SECONDARY CABLES AND MAKE ALL CONNECTIONS. PECO WILL SUPPLY METER BOARD AND CT. 'S (CONTRACTOR TO INSTALL EVERY THING SHOWN)
A
PRTh1ARY SECONDARY
B C
B c• • A
PECO ENERGY WIIL SUPPLY AND INSTAIL LIGHI'NING ARRESTERS ON TIIE OUTGOING BUSHINGS
CONTRACTOR INSTALLED
....._PRJMARY CABLES
A C
N B
METER BOARD TO BE INSTALLED ON UNISTRUT MOUNTED BETWEEN TWO RIGID METAL l-7/8"(MIN)OD STEEL PIPES ENCASED IN CONCRETE OR ON AN OUTSIDE WALLA WAY FROM VEHICLE AND PEDESTRIAN TRAFFIC. CENTER OF METER TO BE BETWEEN 3' AND 5' ABOVEGROUND.
SECONDARY TRANSFORMER
BUSHINGS
BAR TYPE OR
WINDOW TYPE
' NOTE: 11/2" RIGID MET AWC CONDUIT WITH FISH LINE 100' MAXIMUM IF LONGER SEE THE ESR MANUAL (FOR SIZING)
CONTRACTOR INSTALLED SERVICE CABLE
WHITE DOT IS LINE SIDE OF C.T.'S (HI)
l PRECAST CONCRETEMANHOLE WITH PROPER COVER 4KV & 13KV 7'x7' COVER 34KV 8'x8' COVER
Figure 8.17
Metering Rev-10 February 2016 Page 53 of 84
COMMERCIAL CUSTOMER,3 PHASE 240 VOLT 4 WIRE DEL TA RATE CM <INDOOR METER>
ELECTRICIAN TO INSTIIILL EVERYTNINC SHOWN.
PEco wg,L Slffln • Ml'IR, BOARD. & c,,,·s
IIGN Ll!G TO Ill MAlll<!D WlfN RED It.PE AND BE IN IIE BOITOM POSlflON <LOWEST AM>ERAGE CTI
ICTER BOARD CAN BE INSTALLED ON TOP OR EIJl£R Sl!E IF Cl CABlt€T. CEN1ER IF ME1ER 10 BE BElwEEN 3' & 6 ' ABOvE IIE FLOOR
ONLY OtE B<L1ED CCltff:CIION SIMLL IE MADE TO THE c.T.·s <MAY INCLUDE Ml.I. TIPLE 8(1.151 FOR M0AIE 1IIAN Qt,£ CABLE USE Ml.I. Tl•COO..CTOR CCltff:C10RS
<DRAWING FOR REFERENCE ONL YI NOT DRAWN TO SCALE CONOUIT MAY ENIER CABlt4il FROM SIIES. BACK. OR BOTTOM
F'1gor• B.18
30”30”
Metering Rev-10 February 2016 Page 54 of 84
SINGLE CO:t\,fl\,ffiRCIAL CUSTOJ\1ER, 3 PHASE 120/240 VOLT DELTA RATE CM (OUTDOOR J\1ETERING) l 3KV DISTRIBUTION AREA ONLY PECO WILL m\TALL TRANSFORMER. CONTRACTOR TO SUPPLY METER BOARD TO BE INSTAllED ON UNISTRUT MOUNTED PRJMARY AND SECONDARY CABLES AND MAKE ALL BETWEEN TWO RIGID METAL 1-7/8" (MIN) OD STEEL PIPES CONNECTIONS. PECO WILL SUPPLY METER BOARD AND CT. 'S ENCASED IN CONCRETE OR ON AN OUTSIDE WALLA WAY (CONTRACTOR TO INSTALL EVERYTHING SHOWN) HIGH LEG FROM VEHICLE AND PEDESTRIAN TRAFFIC. CENTER OF
INSTALL LOWEST METER TO BE BETWEEN 3' AND 5' ABOVEGROUND.
A
30"
PRTh1ARY SECONDARY
C
A
PECO ENERGY WIIL SUPPLY AND INSTAIL LIGIITN!NG ARRESTERS ON TIIE OUTGOING BUSHINGS
CONTRACTOR INSTAllED
....._PRJMARY CABLES
IJJV
A IJJV
N B
AMPERAGEC.T.
NOTE: 1112" RIGID MET AWG CONDUIT WITH FISH LINE 100' MAXIMUM IF LONGER SEE THE ESR MANUAL (FOR SIZING)
CONTRACTOR INSTAllED SERVICE CABLE
WHITE DOT IS LINE SIDE OF C.T.'S (HI)
PRECAST CONCRETEMANHOLE WITH PROPER COVER 4KV & 13KV 7'x7' COVER 34KV 8'x8' COVER
Figure 8.19
Metering Rev-10 February 2016 Page 55 of 84
SINGLE COJ\,1J\,1ERCIAL CUSTO11ER, 3 PHASE 240 VOLT GROUNDED WYE RATE CM (OUTDOOR 11ETERING) 34KV DISTRIBUTION AREA ONLY PECO WILL IMTALL TRANSFORMER CONTRACTOR TO SUPPLY METER BOARD TO BE INSTAllED ON UNISTRUT MOUNTED PRJMARY AND SECONDARY CABLES AND MAKE ALL BETWEEN TWO RIGID METAL 1-7/8" (MIN) OD STEEL PIPES CONNECTIONS. PECO WILL SUPPLY METERBOARDAND CT. 'S ENCASED IN CONCRETE OR ON AN OUTSIDE WALLA WAY (CONTRACTOR TO INSTALL EVERY THING SHOWN) FROM VEHICLE AND PEDESTRIAN TRAFFIC. CENTER OF
A
PRI!VIARY
PECO ENERGY WIIL SUPPLY AND INSTAIL LIGHI'NING ARRESTERS ON TIIE OUTGOING BUSHINGS
METER TO BE BETWEEN 3' AND 5' ABOVEGROUND.
" NOTE: 11/2" RIGID MET AWC CONDUIT WITH FISH LINE 100' MAXIMUM IF LONGER SEE THE ESR MANUAL (FOR SIZING)
CONTRACTOR INSTAllED SERVICE CABLE
PRECAST CONCRETEMANHOLE WITH PROPER COVER 4KV & 13KV 7'x7' COVER 34KV 8'x8' COVER
Metering Rev-10 February 2016 Page 56 of 84
T 0 0
Q I
I I I I r----I I I I I I
0
Q I
0
0
,-' .......... ___ ...J.
I I I I
0 I I I I I I
~----------------------:
4” MIN.
NEUTRAL
C T
C T
C T
.
..
P TX2 X1
H2 H1
120V
288VP T
X2 X1
H2 H1
120V
288VP T
X2 X1
H2 H1
120V
288V
BOND THE CABINET
A 0
/
A 0 /
B 0
/
C 0
/ C 0
/
B 0
/
OPTION#1
OPTION#2
277 VOLT
277 VOLT
277 VOLT
P TX2 X1
H2 H1
120V
288VP T
X2 X1
H2 H1
120V
288VP T
X2 X1
H2 H1
120V
288V
OPTION#2
CCOOMMMMEERRCCIIAALL CCUUSSTTOOMMEERR,, 3 P3 PHHAASSEE 277/277/480 V480 VOOLLTT
FROM PECOTRANS. ORSECONDARYMAINS
1 1/2”RIGID METALNIPPLE
(INDOOR METER) RATE CMPECO WILL SUPPLY METER BOARD, P.T.’S, & C.T.’S
ELECTRICIAN TO INSTALL EVERYTHING SHOWN INCLUDING WIRING THE HIGH SIDE OF THE P.T.’SWITH #8 STRANDED 600 VOLT COVERED COPPERWIRED TO LINE SIDE OF C.T.’S.
.
TO LOADCENTER
MINIMUM SIZE C.T. CABINET(54”W x 42”H x 12”D)
. ONLY ONE BOLTED CONNECTIONSHALL BE MADETO THE C.T.’S.
ATTACH P.T.’S & C.T.’S TOCABINET WITH UNISTRUTAND SPRING CLIPS.
WHITE DOT IS LINESIDE OF C.T.’S (H1)
METER BOARD CAN BE INSTALLED ON TOP OREITHER SIDE OF C.T. CABINET. CENTER OF METERTO BE BETWEEN 3’ & 5’ ABOVE THE FLOOR.
FROM PECO TRANS. OR SECONDARY MAINS
4” MIN.
1 1/2” RIGID METAL NIPPLE
(INDOOR METER) RATE CM PECO WILL SUPPLY METER BOARD, P.T.’S, & C.T.’S
ELECTRICIAN TO INSTALL EVERYTHING SHOWN INCLUDING WIRING THE HIGH SIDE OF THE P.T.’S WITH #8 STRANDED 600 VOLT COVERED COPPER WIRED TO LINE SIDE OF C.T.’S.
NEUTRAL
C T
C T
C T
.
. .
.
TO LOAD CENTER
MINIMUM SIZE C.T. CABINET (54”W x 42”H x 12”D)
P TX2 X1
H2 H1
120V
288V P T
X2 X1
H2 H1
120V
288V P T
X2 X1
H2 H1
120V
288V
. ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S.
ATTACH P.T.’S & C.T.’S TO CABINET WITH UNISTRUT AND SPRING CLIPS.
BOND THE CABINET
A 0
/
A 0
/
A 0/
A 0/
B 0
/
B 0
/
C 0
/
C 0
/ C 0
/
C 0
/
B 0
/
B 0
/ WHITE DOT IS LINESIDE OF C.T.’S (H1)WHITE DOT IS LINE SIDE OF C.T.’S (H1)
OPTION #1
OPTION #2
METER BOARD CAN BE INSTALLED ON TOP OR EITHER SIDE OF C.T. CABINET. CENTER OF METER TO BE BETWEEN 3’ & 5’ ABOVE THE FLOOR.
277 VOLT
277 VOLT
277 VOLT
((MMAAYYIINNCCLLUUDDEE MMUULLTTIIPPLLEE BBOOLLTTSS)) FFOORRMMOROREE TTHAHAN ON ONNEE CCAABBLLEE USUSEE MMUULLTTII--CCONDONDUCUCTTOROR CCOONNENNECCTTORORSS
((DDRRAAWWIINGNG FFOROR RREEFFEERREENCNCEE ONLONLY)Y) NOTNOT DRDRAAWWNN TTO SO SCCAALLEE CCONDONDUUIITT MMAYAY EENTNTEERR CCAABBIINENETT FFRROMOM SSIIDEDESS,, BBAACCK,K, OROR BBOTOTTTOMOM
Figure 8.21
Metering Rev-10 February 2016 Page 57 of 84
SINGLE CO:t\,fl\,ffiRCIAL CUSTOJ\AER, 3 PHASE 277/480 VOLT RATE CM (OUTDOOR J\AETERING)
PECO WILL m\TALL TRANSFORMER. CONTRACTOR TO SUPPLY METER BOARD TO BE INSTALLED ON UNISTRIJT MOUNTED PRJMARY AND SECONDARY CABLES AND MAKE ALL BETWEEN TWO RIGID METAL 1-7/8" (MIN) OD STEEL PIPES CONNECTIONS. PECO WILL SUPPLY METER BOARD AND CT. 'S ENCASED IN CONCRETE OR ON AN OUTSIDE WALLA WAY (CONTRACTOR TO INSTALL EVERY THING SHOWN) FROM VEHICLE AND PEDESTRIAN TRAFFIC. CENTER OF
r.==========;a========; INSTALL/18 COVERED METER TO BE BETWEEN 3' AND 5' ABOVEGROUND.
A
30"
PRIMARY SECONDARY
C
PECO ENERGY WIIL SUPPLY AND INSTAIL LIGHI'NING ARRESTERS ON TIIE OUTGOING BUSHINGS
CONTRACTOR INSTALLED
......_i'RlMARY CABLES
A C
STRANDED COPP. :ER::.:.-_ _ _
' NOTE: 11/2" RIGID MET AWC CONDUIT WITH FISH LINE 100' MAXIMUM IF LONGER SEE THE ESR MANUAL (FOR SIZING)
CONTRACTOR INSTALLED SERVICE CABLE
WHITE DOT IS LINE SIDE OF C.T.'S (HI)
PRECAST CONCRETEMANHOLE WITH PROPER COVER 4KV & 13KV 7'x7' COVER 34KV 8'x8' COVER
Figure 8.22
Metering Rev-10 February 2016 Page 58 of 84
l I
1 0
V1 I
I I I
I/
...-
277 / 480 VOLT SERVICE
P TH1 H2
X1 X2
288V
120V
P TH1 H2
X1 X2
288V
120V
P TH1 H2
X1 X2
288V
120V
CONTRACTOR TO WIRE PRIMARY SIDE OF POTENTIAL TRANSFORMERS INSTALL #8 STRANDED 600 VOLT COVERED COPPER
WIRED TO LINE SIDE OF C.T.’S
CT
CT
CT
NEUTRAL BUSHING
SECONDARY SIDE OF PADMOUNT TRANS.
PT
PT
PT
MOUNT P.T.’S ON UNISTRUT WITH SPRINGNUTS IN TRANS. ON SIDE WALL 2” BACK FROM THE OPENING
IN TRANSFORMER IN C.T. CABINET 4” MIN.
NEUTRAL
C T
. C T
C T
A 0
A 0
B 0
C 0
B 0 C 0
A 0
B 0
C 0
X1
X1
X2X2
X3
X3
X0 X0
OPTIONAL WINDOW TYPE C.T. ON TRANSFORMER SECONDARY BUSHING
ORN E U T R A L
MIN. 2” BETWEEN TRANSFORMERS
BAR TYPE C.T.’s SHOWN ON DETAIL
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS.
P TX2 X1
H2 H1
120V
288V
P TX2 X1
H2 H1
120V
288V
P TX2 X1
H2 H1
120V
288V
MOUNT C.T.’S & P.T.’S ON UNISTRUT WITH SPRING NUTS.
A 0
B 0
C 0
BOND THE CABINET .
METER SHOP TO COMPLETE THEIR WIRING BEFORE WORK WILL BE ENERGIZED WHITE DOT IS LINE SIDE OF C.T. ( H1) DO NOT REMOVE THE SHUNTS FROM THE C.T.’S
Figure 8.23
Metering Rev-10 February 2016 Page 59 of 84
ELECTRIC SPACE HEATING SERVICE METERING FOR GS HEATING MODIFICATION
APPLIES WHERE AREA IS HEATED SOLELY BY CONNECTED ELECTRICAL SPACE HEATING EQUIPMENT.
LINE
TOTAL METER
SINGLE METER INSTALLATION (SPACE HEATING REQUIREMENTS TO BE AT LEAST EQUAL TO ENERGY REQUIREMENTS FOR OTHER PURPOSES).
POWER/LIGHT AND SPACE HEATING/AIR CONDITIONING
LINE
GENERAL SERVICE METER
TOTAL METER
SEPARATE METER OPTION (SPACE HEATING LOAD TO BE NOT LESS THAN 5KW).
POWER/LIGHT SPACE HEATING/AIR CONDITIONING
Figure 8.24
Metering Rev-10 February 2016 Page 60 of 84
TOTALIZER GENERAL METER INSTALLATION FOR SELF-CONTAINED METERS
GENERAL LOAD
T
HEAT & A/C
G
LIMITED TO 100 AMP.
Figure 8.25-A
T G
SEALABLE TROUGH
GENERAL LOAD
HEAT & A/C
Figure 8.25-B
OVERHEAD SERVICE MAY ENTER METER SOCKET FROM TOP OR SIDE.
Metering Rev-10 February 2016 Page 61 of 84
0 /o
0 /o
0 /o
A ~
- - - - - - -~ - - - - - - .. ~
A ~
3 PHASE 120/208 VOLT, TOTALIZER(CH9) AND GENERAL(CH8) C.T.’S FOR TOTALIZER ONLY (INDOOR METER)
METER BOARDS CAN BE INSTALLED ON TOP OR ABOVE 54 KVAEITHER SIDE OF C.T. CABINET. CENTER OF METERS BELOW 54 KVA
ELECTRICIAN TO INSTALL EVERYTHING SHOWN.
PECO WILL SUPPLY CH9 METER BOARD, & C.T.’S
ATTACH C.T.’S TO CABINET WITH UNISTRUT AND SPRING NUTS.
WHITE DOT IS LINE SIDE OF C.T.’S (H1)
FROM PECO TRANS. OR SECONDARY MAIN (CUSTOMER SUPPLIED)
GEN. LOAD
GEN. LOAD
TO SER
V. EQ
UIP.
GENERAL LO
AD
NEUTRAL
C T
C T
C T
A 0
B 0
CH 9
TO SERV. EQUIP. ELEC. HEAT & A/C
CH 9 CH 8
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS.
BOND THE CABINET
C 0
OPTION # 2
OPTION # 2 CH 8
TO BE BETWEEN 3’ & 5’ ABOVE THE FLOOR.
OPTION # 1 OPTION # 1
120 VOLT
120 VOLT
120 VOLT
(DRAWING FOR REFERENCE ONLY) NOT DRAWN TO SCALE CONDUIT MAY ENTER CABINET FROM SIDES, BACK, OR BOTTOM
Figure 8.26
Metering Rev-10 February 2016 Page 62 of 84
0
0
A ~
GEN.LOAD
GEN.LOAD
CH 9
NEUTRAL
C T
C T
C T
120 VOLT
208 VOLT HIGH LEG
120 VOLT
BOND THE CABINET
ONLY ONE BOLTED CONNECTION SHALL BE MADETOTHE C.T. S. (MAY INCLUDE MULTIPLE BOLTS) FORMORE THAN ONE CABLE USE MULTI CONDUCTORCONNECTORS.
TO SERV
.EQUIP.
GENERAL LO
AD
A 0
B 0
C 0
CH 9CH 8
CH 8
OPTION # 1 OPTION # 1
OPTION # 2
OPTION # 2C T
C T
3 P3 PHHAASSEE 240 V240 VOOLLTT,, TOTOTTAALILIZEZERR((CCHH99)) AANDND GEGENENERRAALL((CCH8H8)) CC..TT..’’SS FFOROR TTOOTTAALLIIZZEERR ONLONLY (Y (IINDOONDOORR MMEETTEERR))
ABOVE 62 KVA
FROM PECO TRANS.OR SECONDARY MAIN(CUSTOMER SUPPLIED)
ELECTRICIAN TO INSTALLEVERYTHING SHOWN.
PECO WILL SUPPLY CH9METER BOARD & C.T.’S
1 1/2”RIGID METALNIPPLE
TO SERV. EQUIP.ELEC. HEAT & A/C
3 PHASE LOAD ONLYNO SINGLE PHASE LOADFROM THIS SERVICE
EXTREME RIGHT LINE SIDE.
HIGH LEG TO BE MARKED WITH RED TAPE AND BE INTHE BOTTOM POSITION (LOWEST AMPERAGE CT)
’-ATTACH C.T.’S TO CABINET
WITH UNISTRUT AND SPRING NUTS.
METER BOARDS CAN BE INSTALLED ON TOP OREITHER SIDE OF C.T. CABINET. CENTER OFMETERS TO BE BETWEEN 3’ & 5’ ABOVE THEFLOOR.
BELOW 62 KVA
GEN. LOAD
GEN. LOAD
ABOVE 62 KVA
CH 9
FROM PECO TRANS. OR SECONDARY MAIN (CUSTOMER SUPPLIED)
ELECTRICIAN TO INSTALL EVERYTHING SHOWN.
PECO WILL SUPPLY CH9 METER BOARD & C.T.’S
1 1/2” RIGID METAL NIPPLE
NEUTRA L
C T
C T
C T TO SERV. EQUIP. ELEC. HEAT & A/C
120 VOLT
208 VOLT HIGH LEG
3 PHASE LOAD ONLY NO SINGLE PHASE LOAD FROM THIS SERVICE
120 VOLT
EXTREME RIGHT LINE SIDE.
HIGH LEG TO BE MARKED WITH RED TAPE AND BE IN THE BOTTOM POSITION (LOWEST AMPERAGE CT)
BOND THE CABINET
ONLY ONE BOLTED CONNECTION SHALL BE MADETO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLT S) FOR MORETHAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS.
TO SERV
. EQUIP.
GENERAL LO
AD
A 0
B 0
C 0
ATTACH C.T.’S TO CABINET WITH UNISTRUT AND SPRING NUTS.
METER BOARDS CAN BE INSTALLED ON TOP OR EITHER SIDE OF C.T. CABINET. CENTER OF METERS TO BE BETWEEN 3’ & 5’ ABOVE THE FLOOR.
CH 9
BELOW 62 KVA
CH 8
CH 8
OPTION # 1 OPTION # 1
OPTION # 2
OPTION # 2
HIHIGGHH LLEEGG 208V208VOOLLTT TTOO BBEE MMARARKKEEDD WWIITTHH RREEDD TTAPAPEE,, AANDND IINSNSTTALALLLEEDD ON TON THEHE
WWWHHHIIITTTEEE DDDOOOTTT IIISSS LLLIIINNNEEE SISISIDDDEEE OOOF CF CF C...TTT...’’’SSS (((HHH111)))
((DDRRAAWWIINGNG FFOROR RREEFFEERREENCNCEE ONLONLY)Y) NOTNOT DRDRAAWWNN TTO SO SCCAALLEE CCONDONDUUIITT MMAYAY EENTNTEERR CCAABBIINENETT FFRROMOM SSIIDEDESS,, BBAACCK,K, OROR BBOTOTTTOMOM
Figure 8.27
Metering Rev-10 February 2016 Page 63 of 84
3 PHASE 120/ 208 VOLT, T OTALIZER(C H 9) AND GENERAL(CH8)
C.T.'S FOR TOTALIZER ONLY (OU1DOOR l\1E1ERING) PECO WILL INSTALL TRANSFORMER ON PAD CONTRACTOR TO SUPPLY PR1MARY AND SECONDARY CABLES AND MAKE ALL CONNECTIONS. PECO WILL S UPPLY TOTALIZER METER BOARD AND CT. 'S(CONTRACTOR TO INSTALL EVERYTHING SHOWN)
ONLY ONE EOLTEDCONNECTION SHALL BEMADETO THEC .T.'S. (MAY INCL UDE MULTIPLE BOLTS) FORMORE THAN ONE CABLE USE MULTI-CONDUCIQR CONNECTORS.
METER BOARD TO BE INSTALLED ON UNlSTRUT MOUNTED BETWEENT\1.IO RIGID METAL l-7.6"(MIN)OD STEELPIPES ENCASED IN CONCRETE OR ON AN OUTSIDE WALLAWAY FROM VE!ilCLE AND PEDESTRIAN TRAmc. CEIITER OF METER TO BE BETWEEN3' ANDS' ABOVEGROUND.
PRilv.lAR Y SECONDARY
A A
1 P.ECO ENEU;,YWU.L rtJPPL Y ANDDIS! ALL LIGB! NING l>.ll:ESt!:1.1
DUS! C1'.PSON' taz !GOIN:;- BtfmDIGJ.
REQUlRED C ONCREIE MANHOIE& COVER
F igure 8.28
A
' '
WHITE DOT IS LINE SIDE OF C .T.'S (H I)
SECONDARY TRANSFORMER
BUSH~
C.T.' s i BARTYPE
OR WINOOWTYPE
' NOTE: 1 112 .. RIGIDMETAI.I.IC CONDUIT WITH FISH LnlE 100' lltAl(IMUM IF LONG ER SEETHEESRMANUAI. (FOR SIZING)
TOGENERALMEfER ( NOC.T.'S)
TO SERVICE EQUIPMENT ELECTR1C HEAT & AJC
CH9
~ ~ CH8
Minimum distance from transformer to meter pedestal is 36”
Metering Rev-10 February 2016 Page 64 of 84
GI]) - - GI]) I I
- -
11 I I I I 1111111 1111111 f' 11 I - - I I I I ...i.. I I I - -
'----..1 I f-- n n n n: f--
~ lo 0 JIii 0 I ol
------4 I I II II II II
lo :> 1111 ° / 0 L-, II II II II ~I
II II 0
1111 ° I 0~
I
~ ~ LI LI I I I I
~ I I I ~------------------~--------------------------------------
I
-~
C T
C T
C T
C T
C T
GENERAL
NEUTRAL .
C TTOTALIZER
CH9 CH8
1 1/2” RIGID METAL NIPPLES TO C.T.CABINET & 1 BETWEEN METER BOARDS
TOTALIZER
TOTALIZER
GENERAL
GENERAL
. BOND THE CABINET
A 0
B 0
C 0
120 VOLT
120 VOLT
120 VOLT
CH8CH9
OPTION # 1 OPTION # 1
OPTION # 2 OPTION # 2
C T
C T
C T
C T
CH9 CH8
CH8CH9
3 P3 PHHAASSEE 120/120/208 V208 VOOLLTT,, TOTOTTAALILIZEZERR((CCHH99)) ANDAND GEGENENERRAALL((CCH8H8)) ((IINDOORNDOOR MMEETTEERRSS))
MMEETTEERR BBOAROARDDSS CCAAN BN BEE IINSNSTTALALLLEEDDABABOVOVEE 5544 KVKVAA ABABOVOVEE 5544 KVKVAA ON TON TOPOP OROR EEIITTHEHERR SSIIDEDE OFOF TTHEHE
FROM PECO TRANSFORMER OR SECONDARYMAINS (CUSTOMER SUPPLIED)
TO SERV. EQUIP.GENERAL LOAD
TO SERV. EQUIP.ELEC. HEAT & A/C
ELECTRICIAN TO INSTALL EVERYTHING SHOWN.
PECO WILL SUPPLY METER BOARDS & C.T.’S
”
WHITE DOT IS LINESIDE OF C.T.’S (H1)
C.T. CABINET. CENTER OF METERSTO BE BETWEEN 3’ AND 5’ ABOVETHE FLOOR.
6”MAX.
(54”W x 42”H x 12”D) CABINET
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S.(MAY INCLUDE MULTIPLE BOLTS)FOR MORE THAN ONE CABLE USEMULTI-CONDUCTOR CONNECTORS
ATTACH C.T.’S TO CABINET WITH UNISTRUT AND SPRING CLIPS.
6”MAX.ABOVE 54 KVAABOVE 54 KVA
FROM PECO TRANSFORMER OR SECONDARY MAINS (CUSTOMER SUPPLIED)
C T
C T
C T
C T
C T
TO SERV. EQUIP. GENERAL LOAD
TO SERV. EQUIP. ELEC. HEAT & A/C
GENERAL
NEUTRAL .
C T TOTALIZER
ELECTRICIAN TO INSTALL EVERYTHING SHOWN.
PECO WILL SUPPLY METER BOARDS & C.T.’S
CH9 CH8
1 1/2” RIGID METAL NIPPLES TO C.T. CABINET & 1” BETWEEN METER BOARDS
TOTALIZER
TOTALIZER
GENERAL
GENERAL
. BOND THE CABINET
WHITE DOT IS LINESIDE OF C.T.’S (H1)WHITE DOT IS LINE SIDE OF C.T.’S (H1)
A 0
B 0
C 0
120 VOLT
120 VOLT
120 VOLT
C.T. CABINET. CENTER OF METERS TO BE BETWEEN 3’ AND 5’ ABOVE THE FLOOR.
CH8CH9 6” MAX.
(54”W x 42”H x 12”D) CABINET
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS
ATTACH C.T.’S TO CABINET WITH UNISTRUT AND SPRING CLIPS.
6” MAX.
OPTION # 1
ABOVE 54 KVAABOVE 54 KVA
OPTION # 1
OPTION # 2 OPTION # 2
((DDRRAAWWIINGNG FFOROR RREEFFEERREENCNCEE ONLONLY)Y) NOTNOT DRDRAAWWNN TTO SO SCCAALLEE CCONDONDUUIITT MMAYAY EENTNTEERR CCAABBIINENETT FFRROMOM SSIIDEDESS,, BBAACCK,K, OROR BBOTOTTTOMOM
Figure 8.29
Metering Rev-10 February 2016 Page 65 of 84
3 PHASE 120/208 VOLT, TOTALIZER(CH9) AND GENERAL(CH8)
PECO WILL INSI'ALL TRANSFORMER ON PAD CONTRACTOR TO SUPPLY PRIMARY AND SECONDARY CABLES AND MAKE ALL CONNECTIONS. PECO WILL SrJPP LY TOTALIZER & GENERAL METER BOARDS AND C. T. 'S (CONTRACTOR TO INSTALL EVERY THING SHOWN)
ONLY ONE IDLTEDCONNECTION SHAIL BEMADETO TIIEC.T.'S. (MAY INCLUDE MULTIPLE BOLTS) FORMORE TIIAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS.
WlfiTE DOT JS UNE SIDE OFC.T.'S (HI)
A
B
30"
PRTh1ARY SECONDARY BARTYPE
TOTAUZER CT
C N
P!COJ!l:IEJGYWILL IUPPLYANDDUII\LL ! LlGlltmNG All!$ll!J.S . Ol.OOS? CI.PSON tD ' OlJ'tGQll,[J BU'mDIGS. :
' '
REQUIRED CONCREl'E : MANHOLE& COVER :
'
CONTRACTOR rn5TAf.LED ,
l : ' ' ' I
PRmlARY CJ\BLEl ' TO POLE OR swrrcHINd\
MODULE. \
' ' ' ' ' ' ' ' ' '
C
°!I l z I 1 V l 0
0 E N E R A L
c+-'-11- GROJNDJNG BUSHINGS
NOTI!: 11/l"RIOID MEfALLIC CONDUIT WITI{FISHLINE 100' loLolXll,IUl,I IF LONOER SEETIIEElRMANUAL
l l/2"META!LIC NIPPLES TO C.T. CABINEI' & I" BETWEENMETERBOARDS. CENTEROFMETERSTO BE BETWEEN 3' & 5' ABOVE TIIE FLOOR.
ATTACH C.T.'S TO CABINET WITH UNI-STRUT
~~-~ &SPRING NUTS.
METER BOARDS TO BE NIPPLED TOGETIIERANDINSTALLEDONTIIE TOP OR l!JTIIER SIDE OFTIIE C.T. CABINET.
TOP OF CONDUITS TO BE 24" BELOW FINISHED GRADE.
' , TO SERVICE EQUIPMENT ELECTRIC HEAT & A/C ',,~;::;:;;:J _ _:_::_:==::..:.::::..::::::.:..==::.:;;;;;.:::.:__ ______ _ Figure 8.30
Minimum distance from transformer to meter pedestal is 36”
Metering Rev-10 February 2016 Page 66 of 84
0
___ o
0
0 0
0 0
0 0
I I I I
~ : r--------------r------------------------------------------1
CH8CH9OPTION # 2 OPTION # 2
C T
C T
C T
C T
C T
GENERAL
NEUTRAL .
C TTOTALIZER
120 VOLT
120 VOLT
208 VOLT
HIGH LEG
1 1/2” RIGID METAL NIPPLES TO C.T.CABINET & 1 BETWEEN METER BOARDS
TOTALIZER
TOTALIZER
GENERAL
GENERAL
. BOND THE CABINET
A 0
/
/
B 0/
C 0
CH9 CH8OPTION # 1 OPTION # 1
C T
C T
C T
C T
CH9 CH8OPTION # 1 OPTION # 1
3 P3 PHHAASSEE 240 V240 VOOLLTT,, TOTOTTAALILIZEZERR((CCHH99)) AANDND GEGENENERRAALL((CCH8H8)) ((IINDOORNDOOR MMEETTEERRSS))EELLEECCTTRRIICCIIAANN TTO IO INSNSTTALALLLEEVEVERRYTYTHHIINGNG SSHHOWOWN.N.
MMEETTEERR BBOAROARDDSS CCAAN BN BEE IINSNSTTALALLLEEDDOVOVOVEEERRR 666222 KVKVKVAAA OVOVOVEEERRR 666222 KVKVKVAAA ON TON TOPOP OROR EEIITTHEHERR SSIIDEDE OFOF TTHEHEPECPECOO WWIILLLL SSUUPPLPPLYY MMETETERER BOBOAARRDDSS && CC..TT..’’SS CC..TT.. CCAABBIINNETET.. CCEENNTTERER OOFF MMETERETERSS666”””
MMMAAAX.X.X. TTO BO BEE BBEETTWWEEEEN 3N 3’’ AANDND 55’’ ABABOVEOVE 33 PPHASHASEE LLOOAAD OD ONNLLYY NONO SSIINGNGLLEE PPHAHASSEE LLOADOAD TTHHEE FFLLOOOORR.. FRFROOMM TTHHIIS SES SERRVVIICCEE..
TTOO SSEERRVV.. EEQQUUIIPP.. GGEENNEERRAALL LLOOAADD
TTOO SSEERRVV.. EEQQUUIIPP.. EELLEECC.. HHEEAATT && AA//CC
((54”54”WW xx 4242””HH xx 1212””DD)) CCAABIBINNEETT
6”MAX.
FROM PECO TRANSFORMER OR SECONDARYMAINS (CUSTOMER SUPPLIED)
HIGH LEG TO BE MARKED WITHRED TAPE AND BE IN THEBOTTOM POSITION.LOWEST AMPERAGE CT
”
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S.(MAY INCLUDE MULTIPLE BOLTS)FOR MORE THAN ONE CABLE USEMULTI-CONDUCTORCONNECTORS.
ATTACH C.T.’S TO THECABINET WITH UNISTRUTAND SPRING CLIPS.
WHITE DOT IS LINESIDE OF C.T.’S (H1)
CH8CH9 M6” AX.
OPTION # 2 OPTION # 2
FROM PECO TRANSFORMER OR SECONDARY MAINS (CUSTOMER SUPPLIED)
C T
C T
C T
C T
C T
GENERAL
NEUTRAL .
C T TOTALIZER
HIGH LEG TO BE MARKED WITH RED TAPE AND BE IN THE BOTTOM POSITION. LOWEST AMPERAGE CT
120 VOLT
120 VOLT
208 VOLT
HIGH LEG
1 1/2” RIGID METAL NIPPLES TO C.T. CABINET & 1” BETWEEN METER BOARDS
TOTALIZER
TOTALIZER
GENERAL
GENERAL
. BOND THE CABINET
ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS.
ATTACH C.T.’S TO THE CABINET WITH UNISTRUT AND SPRING CLIPS.
A 0
/
/
B 0/
C 0
WHITE DOT IS LINESIDE OF C.T.’S (H1)WHITE DOT IS LINE SIDE OF C.T.’S (H1)
CH9 CH8 OPTION # 1 OPTION # 1
((DDRRAAWWIINGNG FFOROR RREEFFEERREENCNCEE ONLONLY)Y) NOTNOT DRDRAAWWNN TTO SO SCCAALLEE CCONDONDUUIITT MMAYAY EENTNTEERR CCAABBIINENETT FFRROMOM SSIIDEDESS,, BBAACCK,K, OROR BBOTOTTTOMOM..
Figure 8.31
Metering Rev-10 February 2016 Page 67 of 84
0 1=========1 0
,----'-----
0 0
0 0
0 0
--~---------------------------------
----------------~
0
0
0
~--..,_._ __ _ I I I I I I I I
I I I I
-----------------------~----J
C T
C T
C T
C T
C T
C T
1 1/2” RIGID METAL NIPPLES TO C.T.CABINET & 1 BETWEEN METER BOARDS
TOTALIZER
TOTALIZER
TOTALIZER
GENERAL
NEUTRAL
.
..
A 0
/
B 0
/
C 0
/ P TX2 X1
H2 H1
120V
288V
4 MINIMUM
B 0
/
C 0
/
A 0
/
X2 X1
H2 H1 P T
X2 X1
H2 H1
120V
288VP T
X2 X1
H2 H1
120V
288V
GENERAL
GENERAL
CH9 CH8
CH8CH9
OPTION # 1 OPTION # 1
OPTION # 2 OPTION # 2
C T
C T
C T
P TX2 X1
H2 H1
120V
288V
X2 X1
H2 H1 P T
X2 X1
H2 H1
120V
288V
CH8
CH8CH9
3 P3 PHHAASSEE 277/277/480 V480 VOOLLTT,, TOTOTTAALILIZEZERR((CCHH99)) AND GEAND GENENERRAALL((CCH8H8)) PECO WILL SUPPLY METER BOARDS, P.T.’S & C.T.’S
ELECTRICIAN TO INSTALL EVERYTHING SHOWN INCLUDING WIRING THE HIGH SIDE OF THE P.T.’SWITH #8 STRANDED 600 VOLT COVERED COPPERWIRED TO LINE SIDE OF C.T.’S.
FROM PECO TRANS.OR SECONDARY MAINS
TO SERV. EQUIP.GENERAL LOAD
TO SERV. EQUIP.ELEC. HEAT & A/C
”
(54”W x 42”H x 12”D) CABINET. .ONLY ONE BOLTED CONNECTION
SHALL BE MADE TO THE C.T.’S.(MAY INCLUDE MULTIPLE BOLTS)FOR MORE THAN ONE CABLE USEMULTI-CONDUCTOR CONNECTORS
ATTACH P.T.’S & C.T.’S TO CABINETWITH UNISTRUT AND SPRING CLIPS.
.BOND THE CABINET
”
WHITE DOT IS LINESIDE OF C.T.’S (H1)
METER BOARDS CAN BE INSTALLEDON TOP OR EITHER SIDE OF THEC.T. CABINET. CENTER OF METERSTO BE BETWEEN 3’ AND 5’ ABOVETHE FLOOR.6”
MAX.
6”MAX.
PECO WILL SUPPLY METER BOARDS, P.T.’S & C.T.’S
ELECTRICIAN TO INSTALL EVERYTHING SHOWN INCLUDING WIRING THE HIGH SIDE OF THE P.T.’S WITH #8 STRANDED 600 VOLT COVERED COPPER WIRED TO LINE SIDE OF C.T.’S.
C T
C T
C T
C T
C T
C T
FROM PECO TRANS. OR SECONDARY MAINS
TO SERV. EQUIP. GENERAL LOAD
TO SERV. EQUIP. ELEC. HEAT & A/C
1 1/2” RIGID METAL NIPPLES TO C.T. CABINET & 1” BETWEEN METER BOARDS
(54”W x 42”H x 12”D) CABINET TOTALIZER
TOTALIZER
TOTALIZER
GENERAL
NEUTRAL
.
. .
. . ONLY ONE BOLTED CONNECTION SHALL BE MADE TO THE C.T.’S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS
ATTACH P.T.’S & C.T.’S TO CABINET WITH UNISTRUT AND SPRING CLIPS.
A 0
/
A 0
/
B 0
/
C 0
/
C 0
/ P TX2 X1
H2 H1
120V
288V
. BOND THE CABINET
4” MINIMUM
B 0
/
C 0
/
C 0
/
A 0
/ A 0
/
P TX2 X1
H2 H1
120V
288V P T
X2 X1
H2 H1
120V
288V
GENERAL
GENERAL
WHITE DOT IS LINESIDE OF C.T.’S (H1)WHITE DOT IS LINE SIDE OF C.T.’S (H1)
METER BOARDS CAN BE INSTALLED ON TOP OR EITHER SIDE OF THE C.T. CABINET. CENTER OF METERS TO BE BETWEEN 3’ AND 5’ ABOVE THE FLOOR.
CH9 CH8 6” MAX.
CH8CH9 6” MAX.
OPTION # 1 OPTION # 1
OPTION # 2 OPTION # 2
((DDRRAAWWIINGNG FFOROR RREEFFEERREENCNCEE ONLONLY)Y) NOTNOT DRDRAAWWNN TTO SO SCCAALLEE CCONDONDUUIITT MMAYAY EENTNTEERR CCAABBIINENETT FFRROMOM SSIIDEDESS,, BBAACCK,K, OROR BBOTOTTTOMOM
Figure 8.32
Metering Rev-10 February 2016 Page 68 of 84
3 PHASE 277/480 VOLT, TOTALIZER(CH9) AND GENERAL(CH8) (INDOOR METERlNG) TOTALIZER C. T 'S IN TRANSFORMER AND GENERAL C. T'S. IN CABINET
PECO WILL INSTALL 'IRANSFORMERONPAD CONTRACTOR TO SUPPLY PRIMARY AND SECONDARY CABLES AND MAKE ALL CONNECTIONS. PECO WILL SUPPLYMEI1!R i/OARI$. PT 'S AND C r 'S OONTRACTOR TO INST ALL EVERYTil!NG SHOWN INCLUDING WllllNG THE HIGH SIDE OF THE P.T.'S WITH /El STRANDED 600 VOLT COVERED COPPER WIREDTO LlNE SIDEOF C.T.'S
ONLY ONE e::>LTEDCONNECTION SHALL BE MADETO THE C.T. 'S. (MAY INCLUDE MULTIPLE BOLTS) FOR MORE THAN ONE CABLE USE MULTI-CONDUCTOR CONNECTORS.
A
PRJMARY
A
Ps::OS'<aOYl'tll SCJU>LYANDMTAU. L~ ~ R:E:SratS CG: CX£TC.APSO<'~
"""°"""""""'
SECONDARY WN. r BEtwEEN
\ ' I ' M'OO?"T PT 'S I
ct"tn--'li1Rf.lr • Wlllfs:>R~ I ~.,r•a.-.c,::• FRQ.lmE 1 .,,.,,... ,
' ' '
REQUIRED CONCRETE MANHOLE & COVER
B..U T\!Pt C.T.~
SHOWN 01< D I'EAD.
BAR T YPE TOTA!JZER CT
NOTE:
CONIRACTOR INSTALLID
PRIMARY C.ABLES
' ' ' ' ' . I 112 .. RIOID b!ETALUC CONDUIT WlIH FISH LINE 100 . b!AX!h!UM
~ - - IF LONOERSEE IHEESR b!ANUAL
-- TO POLE OR SWITCHING b!ODULE.
' . . • . .
'
I 112"METALLIC NIPPLES TO C.T . CABINET & I" BETWEE:11 METER BOARDS. CENTER OF METERS TO BE BETWEEN 3' & 5' ABOVE THE FLOOR.
' NElTI'RAL I
t - - - - -,- - - - - - - - - - - - - - · 1 - BOND THE CABINET
METER BOARDS TO BE NIPPLED TOGETHER AND INST All.ED ON THE TOPOREITHERSIDEOFTHEC.T. CABINET.
TOP OF CONDUITS TO BE 24" BELOW FINISHED GRADE.
TO SERVICE EQUIPMENT ELECTRIC HEAT & AIC
Figure 8.33
Minimum distance from transformer to meter pedestal is 36”
Metering Rev-10 February 2016 Page 69 of 84
:.:.s.~.:.i. \ f ili \ ~ t .::·:·:.:::·:.:::::.:.:.::: f G m %
- 0 :.~.:.~ y 2 .·.'.··.:.·.·.·.'.··.: ~~
i I w m
METER BOARD TO BE INSTALLED ON UNISTRUT MOUNTED BETWEEN TWO 3” STEEL PIPES ENCASED IN CONCRETE AWAY FROM VEHICLE AND PEDESTRIAN TRAFFIC. THERE MUST BE 3’ OF CLEAR WORKING SPACE IN FRONT OF THE METER.
BETWEEN 3’ & 5’
36”
24”
CL
SERVICE EQUIPMENT (SUGGESTED ARRANGEMENT) IF LOCATED ON METER SUPPORT
APPROVED GROUND PER N.E.C.
MINUMUM REQUIRMENTS FO
R INDIVIDUALLY
DESIG
NED
OUTDOOR METER
SUPPO
RT
Figure 8.34
Metering Rev-10 February 2016 Page 70 of 84
0 0
0 0
CONNECTIONS FOR RESIDENTIAL AND INTERRUPTIBLE RATE SERVICE METERS
IF SEPARATE SOCKETS ARE USED, CONNECT BY METALLIC NIPPLE OR EMT.
(UNPROTECTED SE CABLE IS NOT ACCEPTABLE).
SERVICE ENTRANCE CONDUCTORS
TO SERVICE EQUIPMENT FOR GENERAL RESIDENTIAL USE.
CONTROLLED SUPPLY TO INTERRUPTIBLE RATE SERVICE EQUIPMENT.
CUSTOMER INSTALLED CONDUCTORS AND ASSOCIATED EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH THE REQUIREMENTS OF LOAD AS SPECIFIED BY THE N.E.C.
APPLY TAPE TO BARE NEUTRAL INSIDE METER
Figure 8.35
Metering Rev-10 February 2016 Page 71 of 84
..,, <5" C
al 0, (,) O>
SERVICE ENTRANCE CONDUCTORS
NEUTRAL GROUNDING -CONDUCTOR
EXISTING GENERAL SERVICE ENTRANCE EQUIPMENT OR METER SOCKET
NOTES:
GENERAL LOAD -......
METER SOCKET FOR NEW INTERRUPTABLE RATE METER 1NTERRUPTABLE LOAD
0 a
D
/
SERVICE ENTRANCE PANEL
.---'-<
CONDUCTORS CON"NECTED TO SERVICE TERMINALS IN NIPPLE, CONDUIT, EMT OR GREENFIELD, !UNPROTECTED SE CABLE NOT ACCEPTABLE~
0
I CUSTOMER INSTALLED CONDUCTORS AND ASSOCIATED EQUIPMENT SHALL BE SIZED IN ACCORDANCE WITH THE REQUIREMENTS OF THE LOAD AS SPECIFIED BY THE NEC. 2 SEE PAR 8.6.2 FOR LOADS GREATER THAN 24 KW 3 APPLY TAPE TO BARE NEUTRAL INSIDE METER SOCKET.
Interruption Rate Service Indoor Meter Installation
Figure 8.36
Metering Rev-10 February 2016 Page 72 of 84
SERVICE ENlRANCE CONDUCTORS
GENERAL SERVICE
INTERRUPTABLE SERVICE
0 /'-------
CONDUCTORS IN NIPPLEJ CONDUIT OR EMT. ( UNPROTECTt:.O SE CABLE NOT ACCEPTABLE.)
"EXTERIOR VIEW"
INTERRUPTABLE LOAD SERVICE ENTRANCE PANEL
11 1NTERIOR VIEW"
I CUSTOMER INSTALLED CONDUCTORS AND ASSOCIATED EQUIPMENT SHALL BE SIZEO IN ACCORDANCE WITH THE REQUIREMENTS OF THE LOAD AS SPECIFIED BY THE NEC
2 SEE PARS.6.2 FOR LOADS GREATER THAN 2-4 KW. 3 APPLY 'l'API!: TO BARE NEUTRAL INSIDE METER SOCKET.
GENERAL LOAD SERVICE ENTRANCE PANEL
Interruptable Rate Service Outdoor Meter Installation
Figure 8.37
Metering Rev-10 February 2016 Page 73 of 84
INDOOR TRANSFORMER RATED METER SOCKET SINGLE METERING POINT CMETER SOCKET SUPPLIED BY PECOJ
z ::E
-.., re,
-------s2" MIN S?ACE ---'-' -
I I - - - - - -·- ________ _! ___ _
FRONT
PRE-WI RED METER SOCKET
1 1/2" RIGID MET AL CONDUIT
FLOOR
l
o
~ 0::: < "' ...J u
-.,, ,-..
SIDE
NOTE: 1. 20" X 30" X 3/4" FL Y\liOOO BACKBOARD REOU!REO ON
POOR WALL SURFACE.
Figure 8.38
Metering Rev-10 February 2016 Page 74 of 84
INDOOR METER PANEL WALL MOUNTING
-----------~-
t : .. 20" .. 1
.. 20" ... , 2"-j
3te·eor1--31 2"x1"x 3M/
CONDUIT MAY ENTER EITHER SIOE, BOTTOM OR BACK.
·o SPECIAL CHANNELS "' OR UNISTRUT
I- OR EQUAL
- ~ 12"x 12"x 4" 12' ~~ . w JUNCTION BOX
v~:3 ! .J
II II 0
U W •o·., .,. t-
f'I.OOR
FRONT
I. SEE TABLE 8.13 FOR ACCEPTABLE JUNCTION BOX WITH CHANNELS. CHANNELS AND TOP OF JUNCTION BOX SHALL BE LEVEL.
Figure 8.39
Metering Rev-10 February 2016 Page 75 of 84
OUTDOOR METER PANEL INSTALLATION (OUTDOOR Ivt:ETER PEDESTAL E~CLOS~)
HANDLE WITH PROVISIONS FOR 5/16"DIA_ PAD LOCK
lVIOUNTING FEET TOP AND BOT'TOM:
NEIV1A TYPE 3R CABINET
ENCLOSURE TO BE INSTALLED C>N UNI STRUT BETWEEN {TWO) 3'~ STEEL PIPES ENCASED IN CONCRETE OR ON AN OUTSIDE WALL AVVAY FROJ'v'.I VEHICLE AND PEDESTRIAN TRAFFIC_
RIDGID METAL CONDUIT TO PECO l'VIETERING TR.ANSFC>RNIE RS, SIZE PER ESR IvlANUAL
l"PVC SCHEDULE 40 INTO BLDCL (PECO PHONE LINE)
]"PVC SCHEDULE 40 INTO BLDCL(CUSTCHvlER DEl'vlAND CON'TACTS)
NOTES: l _ LOCATED OUTSIDE SUBSTATION ENCLOSURE (H_T_ O~LY). 2. CUSTOlvlER USE REQUIRES PECO ENERGY ACiR..EEl'vfENT. 3. PECO PI-IONE LINE AND CUSTCHvfERS CONTACT CONDUITS
l'VfUST BE INTO CUSTO.l'vfERS PR.El'vfISES_ Figure 8.40
I 35"
--t 40"
36"
Minimum distance from transformer to meter pedestal is 36”
Metering Rev-10 February 2016 Page 76 of 84
I I I I I
------L .J_ - - - - - - -
MODEM UNDER GLASS METER PANEL INSTALLATIONS FOR SINGLE SERVICE
Single Panel Duplex Panel (For Isolated Contacts) 12”
Metering Rev-10
36”
22-1/2”
17-3/8”
62”
P1000 Unistrut or equilivalent
1-7/8” Min I.D. Rigid Steel Pipe
6” x 6” Contact Box (1)
Rigid Steel Conduit To PECO Metering Transformer Specs Per Section 8 (2)
Phone Box (1)
1” PVC for Modem Line (2) 1” PVC for Contacts (2)
Figure 8.41
Prewired Meter Panel PECO Supplied
Prewired Meter Panel PECO Supplied
February 2016 Page 77 of 84 Notes: (1) Contact Box and Phone Box to be fitted to suit in field.
(2) Conduit to be aligned with panel knockouts. (3) For indoor installations, eliminate ballards. Mount Unistrut on wall.
10
LOM’
NEMA TYPE3R
ENCLOSUR
CH 9 CH 8
Figure 8.42 Minimum distance from transformer to meter pedestal is 36”
OOUTUTDDOOOORR CC..TT.. CCABABININEETT TOTOTATALILIZERZER C.C.T.T.’’SS IINN TRATRANNSSFFOORRMMER,ER, GGENENERAERALL C.C.T.T.’’SS IINN CACABIBINNEETT
C.T. CABINET TO BE INSTALLED ON UNISTRUT MOUNTED BETWEEN TWO 3” RIGID STEEL PIPES ENCASED IN CONCRETE OR ON
AN OUTSIDE WALL AWAY FROM VEHICLE AND PEDRESTRIAN TRAFFIC. METER CAN BE INSTALLED ON EITHER SIDE
PECPECOO WWIILLLL SSUUPPLPPLYY MMETETER BOER BOARDARD’’SS && EELLECECTRTRIICCIIAANN TOTO IINNSSTATALLLL EVEVERERYYTHTHIINNGG SSEE THE APPPRROPRRIIAATE IINDOOREE THE AP OP TE NDOOR OR.. CCABABIINENETT FFOR TTHEHE PPRROPOPEERR WWIIRRIINGNG
Metering Rev-
BETWEE3’ & 5’
36”
24”
MOUNT METERINGEQUIPMENT
ON UNISTRUT INSIDETHE C.T. CABINET
HANDLEPROVISIONS5/16” DIA.
CL
1 1/2” RIGID METALNIPPLES BETWEENTHE METER BOARDSAND THE C.T.CABINET.
GENERALFROM
1 1/2” RIGID METAWITH FISH LINE FRTRANSFORMER, 100 MAX.LONGER SEE THE ESR
DRAWING FORONLY (NOT DRAWN TO
BETWEE 3’ & 5’
36”
24”24”
MOUNT METERING EQUIPMENT
ON UNISTRUT INSIDE THE C.T. CABINET
HANDLE PROVISIONS 5/16” DIA.
CLCL
1 1/2” RIGID METAL NIPPLES BETWEEN THE METER BOARDS AND THE C.T. CABINET.
GENERAL FROM
1 1/2” RIGID METALWITH FISH LINE FROM TRANSFORMER, 100’MAX. LONGER SEE THE ESR
NEMA TYPE 3R
ENCLOSUR
CH 9 CH 8
DRAWING FOR ONLY (NOT DRAWN TO
February 2016 Page 78 of 84
l
&
24”
NEMA TYPE3R
ENCLOSURE
Figure 8.43 Minimum distance from transformer to meter pedestal is 36”
OUTOUTDODOOROR CC..TT.. CCABABINEINETT C.T. CABINET TO BE INSTALLED ON UNISTRUT MOUNTED BETWEEN TWO 3” RIGID STEEL PIPES ENCASED IN CONCRETE OR
ON AN OUTSIDE WALL AWAY FROM VEHICLE AND PEDRESTRIAN TRAFFIC. METER CAN BE INSTALLED ON EITHER SIDE
OF THE CABINET THERE MUST BE 3’ OF CLEAR WORKING SPACE IN FRONT OF THE METER PECO WILL SUPPLY METER BOARD & C.T.’S EELLEECCTTRRIICCIIAN TAN TO IO INSNSTTALALLL EEVVEERRYTYTHIHING SNG SHOHOWWN.N. . SEE THE APPROPRIATE INDOOR C.T. CABINET FOR THE PROPER WIRING DIAGRAM.
Metering Rev-10
BETWEEN3’ 5’
36”
MOUNT METERING EQUIPMENT
ON UNISTRUT INSIDETHE C.T. CABINET
HANDLE WITH PROVISIONS FOR5/16” DIA. PADLOCK
CL
BETWEEN 3’ & 5’
36”
24”
MOUNT METERING EQUIPMENT
ON UNISTRUT INSIDE THE C.T. CABINET
HANDLE WITH PROVISIONS FOR 5/16” DIA. PADLOCK
NEMA TYPE 3R
ENCLOSURE
CLCL
February 2016 Page 79 of 84
FIGURE 8.44 DELETED
FIGURE 8.45 DELETED
FIGURE 8.46 DELETED
FIGURE 8.47 DELETED
FIGURE 8.48 DELETED
THIS PAGE LEFT BLANK INTENTIONALLY
Metering Rev-10 February 2016 Page 80 of 84
METERING TRANSFORMER SECONDARY CONNECTIONS TO BE COMPLETED BY PECO METER SERVICES
W METERING TRANSFORMER PRIMARY CONNECTIONS TO BE COMPLETED BY CUSTOMER/CONTRACTOR
A¢ SOURCE
CABLE CONCENTRIC
NEUTRAL
0
METER I NG VOLTAGE
TRANSFORMER VT X
B ¢ SOURCE
CABLE CONCENTRIC
NEUTRAL
METERING VOLTAGE
TRANSFORMER VT X
3
C ¢ SOURCE
CABLE CONCENTRIC
NEUTRAL
METER I NG VOLTAGE
TRANSFORMER VT X
3
POLARITY MARK POLARITY MARK POLARITY MARK
0
0
: X
METER! NG CURRENT
TRANSFORMER CT
0 I I I I
A ¢ LOAD
(WHITE DOT)
0
0
: X
METERING CURRENT
TRANSFORMER CT
0 I I I I
B ¢ LOAD
(WHITE DOT)
0
0
~
X ME TERI NG CURRENT
TRANSFORMER CT
0 I I I I
C ¢ LOAD
(WHITE DOT)
PRIMARY WIRING DIAGRAM FOR 3-PHASE, 4 WIRE, THREE ELEMENT METERING OVER 600 VOL TS
Figure 8.49
Metering Rev-10 February 2016 Page 81 of 84
WIRING DIAGRAM FOR 3-PHASE 3 WIRE, TWO ELEMENT METERING OVER 600 VOLTS
Figure 8.50
0 METERING TRANSFORMER SECONDARY CONNECTIONS TO BE COMPLETED BY PECO METER SERVICES
0 METERING TRANSFORMER PRIMARY CONNECTIONS TO BE COMPLETED BY CUSTOMER/ CONTRACTOR
A 0SOURCE
0 0
METERING VOLTAGE
TRANSFORMER VT-Fused
X
0 0
.. Q, ___ _
X
METERING CURRENT
TRANSFORMER C.T.
0
A0LOAD
POLARITY MARK (WilTE DOT)
B 0SOURCE C0 SOURCE
0 I I
0 0 I METERING I VOLTAGE
TRANSFORMER
I POLARITY MARK I POLARITY MARK VT-Fused (WHITE DOT) (WilTE DOT) X
0 0
I I
I I
0 I I
3
I I POLARITY MARK
('MilTE DOT)
I 0 METERI NG
CURRENT
0 TRANSFORMER C.T.
I I 0
I 2
I I I B 0LOAD C0LOAD
Metering Rev-10 February 2016 Page 82 of 84
/
/
A
KV
4.2 14.4
INS ULA TING BARRIER AS REQUIRED **
0-GRD DIM II A// ( I NCH l
3 5
0-0 DIM "B" ( I NCH l
4 1 /2 7 1/2
** IF CLEARENCES ARE LESS THAN LISTED AN INTER PHASE BARRIER OF INSULATING
MATERIAL IS REQUIRED
13.2 & 4.16KV PECO METERING VT CLEARENCE REQUIREMENTS
Figure 8.51
Metering Rev-10 February 2016 Page 83 of 84
~; ________ ----------- ------ -~~
0 0 -1-o·······O···O········O
---- r -------- ----------- -----
MODEM UNDER GLASS METER PANEL INSTALLATIONS FOR DUAL SERVICE
36”
36”
17-3/8”
62”
P1000 Unistrut or Equilivalent
1-7/8” Min I.D. Rigid Steel Pipe (2)
8” x 8” Weatherproof Contact Box (if required)
Rigid Steel Conduit To PECO Metering Transformer Specs Per Section 8
1” PVC for Contacts – Minimum height 25”
c b
a a
Pipe Centerline Dimensions a = 2-3/4” b = 15” c = 21”
12” 12” x 12” Weatherproof Contact Box (if required)
AA AA
Section AA
3-1/4”
Tri – Plex Meter Panel PECO Supplied (1)
Figure 8.52 Metering Rev-10 1” PVC for Modem Line February 2016 Notes: Page 84 of 84
(1) PECO catalog # 12981 for 13 jaw board (wye service) and 12982 for 11 jaw board (delta service). (2) For indoor installations, eliminate ballards. Mount Unistrut on wall.