ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 1 of 11
08900
EXTERIOR GLAZED CURTAINWALL SYSTEM
Contents
PART 1 GENERAL........................................................................................................................2
1.1 DESCRIPTION OF WORK ...............................................................................................2
1.2 QUALITY CONTROL.......................................................................................................2
1.3 SUBMITTAL......................................................................................................................6
1.4 WARRANTEES AND GUARANTEES............................................................................7
PART 2 PRODUCTS .....................................................................................................................72.1 MATERIALS......................................................................................................................7
2.2 FABRICATION / MANUFACTURE................................................................................9
PART 3 EXECUTION ...................................................................................................................9
3.1 INSPECTION .....................................................................................................................9
3.2 INSTALLATION/APPLICATION/PERFORMANCE/ERECTION.................................9
3.3 FIELD QUALITY CONTROL.........................................................................................10
3.4 ADJUSTMENT AND CLEARANCE..............................................................................10
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 2/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 2 of 11
PART 1 GENERAL
1.1 DESCRIPTION OF WORK
A. General
This Section covers the detailed design, fabrication and installation of the curtain wall
system located on the exterior walls as detailed on the Drawings.
1. Provide all fastenings accessory features, all connections to the building
structure and other items not mentioned specifically herein, but which are
necessary to make a complete installation.
2. Primary components of the glazed curtain wall system include but are not
limited to the following:
a. Extruded aluminum curtain wall framing system, with thermal break
units, designed as a thermal isolator.
b. Internal reinforcements.
c. Architectural metal panels.
d. Doors and frames, where indicated.
e. Trim, covers, flashing (which are provided by the curtain wall
manufacturer), soffits, copings, and similar border and filler items.
f.
Anchors, shims, fasteners, inserts and accessories.g. Glazing, setting blocks, concealed flashing, joint fillers, sealant, gaskets
and glass.
h. Insulation and fire stopping within the curtain wall system as required
by manufacturer.
i. Stainless steel mullion caps in specified finish. Refer to 2.1.A.4.
B. Related Work Specified Elsewhere:
1. Glass and glazing materials shall be as specified in section 08800 - GLASS &
GLAZING.
2. Structural steel work shall be as specified in section 05100 - STRUCTURAL
STEEL.
3. Sealants as specified in section 07900 - CAULKING AND SEALANTS.
1.2 QUALITY CONTROL
A. Standards
The publications listed below form a part of this Specification to the extent referenced.
The publications are referred to in the text by basic designation only.
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 3/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 3 of 11
ALUMINIUM ASSOCIATION (AA)
Guide Specification Designation System for Aluminum Finishes
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 101 Specifications for Aluminum Prime Windows and
Sliding Glass Doors
AAMA 501.3 Methods of Tests for metal curtain walls
AAMA 1503.2 Test method for condensation resistance of windows,
doors and glazed wall sections
(this is a separate test in addition to typical testing.This is normally conducted on standard products)
AAMA TIR-A2 Design wind loads for aluminum curtain walls
AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM)
ASTM A 167 Specification for stainless and heat resisting chromium
nickel steel plate, sheet and strip
ASTM A 666 Specification for Austenitic Stainless Steel, sheet, strip,
plate and flat bar
ASTM B 209 Specification for Aluminum and Aluminum-Alloy
Sheet and PlateASTM B 221 Specification for aluminum-alloy extruded bars, rods,
wire, shapes, and tubes (Metric)
ASTM C 509 Specification for cellular elastomeric preformed gasket
and sealing material
ASTM E 283 Determining the rate of air leakage through exterior
windows, curtain walls, and doors under specified
pressure differences across the specime
ASTM E330 Structural Performance
ASTM E 331 Test method for water penetration of exterior windows,
curtain walls, and doors by uniform static air pressure
difference
ASTM E 783 Test method for field measurement of air leakage
through installed exterior windows and doors.
ASTM E 1105 Test method for field determination of water
penetration of installed exterior windows, curtain walls
and doors by uniform cyclic static air pressure
difference.
FLAT GLASS MARKETING ASSOCIATION (FGMA)
Glazing Manual
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 4/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 4 of 11
Sealant Manual
B. Design Criteria:
1. Structural properties.
a. The wall shall be designed, engineered, fabricated and installed to
withstand inward and outward pressures in accordance with "Minimum
Design Loads in Buildings and Other Structures" ANSI/ASCE 7-88
formerly known as ANSI A58.1 and as recommended by AAMA TIR-
A2, "Design Wind Loads for Aluminum Curtain walls".
b. The exterior walls shall be designed to withstand both the inward
pressure acting inward and the outward pressure acting outward, the two
pressures being applied separately.
c. Copies of structural calculations made by or for this Contractor in
connection with the supplementary design and/or detailing of the Work
herein specified shall be furnished to the COMPANY. These
calculations shall be stamped and signed by a professional engineer
registered in the Country of manufacture.
d. The deflection of any metal framing member, in a direction normal to
the plane of the wall shall not exceed 1/175 of the clear span of the
member or 10mm, whichever is least, except that when a finished
surface is affected this deflection shall be not more than 1/360 of the
clear span.
e. The deflection of any member, in a direction parallel to the wall plane,
when the member carries its full design load, shall not exceed 75
percent of the design clearance dimension between that member and the
panel, sash, glass or other part adjacent to it.
f. Structural strength : The system is to capable of carrying
the vertical loads safely to the steel
structure at each floor level.
The system is to be able to withstand
forces from the wind as defined in the
wind tunnel test , or a minimum of 1.2
kN/m² applied as a suction or pressure.
For the purposes of pricing only:
The following loads shall be
considered for design purposes:
• In areas local to corners adjacent to
existing towers extending
- 4.5 kN/m².
• In areas local to all other corners,
extending 5m back from corner
- 2.5 kN/m²
Otherwise - 1.75 kN/m²
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 5/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 5 of 11
2. Water infiltration.
a. Provision shall be made in the design to drain to the exterior face of the
wall, any leakage of water occurring at joints and/or any condensation
taking place within the construction with no damage to the wall,
adjacent construction or finishes.
b. Resistance to water infiltration. No water infiltration shall occur when
the wall is tested (or has been previously tested by a nationally
recognized testing laboratory) as follows: under a static pressure of 600
Pascal, 203 liters per hour per square meter shall be applied to the
exterior face of the unit for a period of 1/4 hour in accordance with
ASTM E-331-86. No uncontrolled water shall pass the interior face of
the unit.
3. Resistance to air infiltration. Air infiltration through the wall, when tested by a
nationally recognized testing laboratory, shall not exceed 18290 cubic
centimeters -per min. per square meter of fixed wall area equivalent to
1.09m³/hr/m² @ 75 Pa.
4. Condensation resistance for the aluminum framing shall not be less than 51 CRF
per AAMA 1503.2.
5. Dissimilar metals shall be isolated to prevent staining or galvanic corrosion.
6. Base design of curtainwall system on the rain screen principle as described in
volume 2 of the Aluminum Curtainwall Design Guide Manual, latest addition,
published by Architectural Aluminum Manufacturer’s Association (AAMA).
7. Provisions to ensure complete floor-to-floor fire and air barrier separation
between curtainwall and perimeter of structure.
C. Source Quality Control:
1. Entire curtain wall installation, including all fastenings and anchors shall be
done by or under the direction of a single manufacturer.
D. Installer Qualifications:
1. Engage an experienced installer who has successfully completed installation of
entrance, window, curtain wall and storefront systems similar in material,
design, and extent to that indicated for the project for a period of not less than 5years.
E. Glazing Standards:
1. Comply with recommendations of Flat Glass Marketing Association (FGMA)
"Glazing Manual" and "Sealant Manual" except where more stringent
requirements are indicated. Refer to those publications for definitions of glass
and glazing terms not otherwise defined in this Section or referenced standards.
F. Pre installation Meeting:
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 6/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 6 of 11
1. Before beginning installation, conduct a pre installation meeting at the project
Site with the system manufacturer, installer and other interest parties to review
procedures, schedules and coordination of the installation with other elements of
the Work.
G. Field Measurements
1. The Contractor shall check and guarantee openings for the curtain wall to the
installer for this Section by field measurement before fabrication to ensure
proper fitting of Work of this Section. Show measurements on final shop
drawings. Coordinate fabrication schedule with construction progress to avoid
delay in the Work and coordinate fabrication tolerances to ensure proper fit. In
order to expedite final engineering drawings and permit glass to be ordered, the
Contractor may elect to guarantee openings by means of a written release to thecurtain wall manufacturer to start the fabrication process and eliminate field
dimensions.
1.3 SUBMITTAL
A. Submit the following in accordance with Division 01340.
1. Certificate of Compliance:
a. Submit manufacturer's certificate stating compliance of the curtain wall
with performance requirements specified herein.
2. Product Data:
a. Submit manufacturer's general product description and installation
recommendations for the curtain wall required for this Project.
3. Shop Drawings:
a. Submit shop drawings for fabrication and installation of curtain wall
which shall include elevations, interfaces with building construction,
details of sections and condition, anchorage, steel reinforcement,
expansion provisions, flashing, glazing details and drainage methods.
b. All details shall be cross-referenced to elevations, or large scale
drawings.
4. Qualifications:
a. Submit certification signed by the curtain wall manufacturer that the
installer of the curtain wall system is capable of executing the
installation in accordance with the shop drawings and installation
instructions. Preference will be given to manufacturer’s that are ISO
9001 registered.
5. Samples:
a. Submit two (2) samples of each specified finish on 300mm long
sections of a representative member. Where finishes involve normal
colour variations, include sample sets showing the full range of
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 7/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 7 of 11
variations expected. Samples to be labeled with location description and
project name.
b. Submit 1 meter x 1 meter complete assembled sample with approved
colors.
6. Test Reports:
a. Submit copies of the test reports resulting from the requirements
specified in the Quality Control criteria for the design and installation.
1.4 WARRANTEES AND GUARANTEES
A.
Before final payment is made, the Contractor shall warrant to the COMPANY in writingthat all parts of the Work will meet the specified overall performance requirements and
will be free from defects in materials and workmanship for a period of ten (10) years
following the date of issue of the Substantial Completion Certificate. He shall certify in
writing also that all Work is in accordance with the Contract Documents and authorized
alterations and/or additions thereto and that, should any defect develop during the
warranty period due to improper workmanship or materials under his jurisdiction, such
defects shall, upon written request, be repaired or replaced by the Contractor at his own
expense.
B. The warranty shall not deprive the COMPANY of other rights or remedies that the
COMPANY may have under other provisions of the Contract Documents and is in
addition to and runs concurrent with other warranties made by the Contractor underrequirements of the Contract Documents.
C. Curtain wall failures include but are not limited to the following:
1. Structural failures including excessive deflection, excessive leakage, or air
infiltration.
2. Deterioration of metals, metal finishes, and other materials beyond normal
weathering.
3. Failure in glass and glazing within curtain wall framed units.
PART 2 PRODUCTS
2.1 MATERIALS
A. Curtain wall shall be standard units with a silicone compatible elastomeric thermal
barrier manufactured by a firm that specializes in the design and manufacture of the type
of curtain wall system specified in this Section. Framing intersection to incorporate
silicon compatible “zone dams”. All horizontal-glazing pockets will provide weep holes
to drain all accumulated water to exterior. The aluminum curtainwall will be designed
on the “rain screen” principle of pressure equalization. The firm shall have a minimum
of 20 (twenty) years of documented successful experience. Manufacturer shall have
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 8/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 8 of 11
production facilities capable of meeting the requirements of the Contract Documents and
shall be able to provide single-source-responsibility and the warranty specified herein.
1. Grid members and perimeter framing at bottom level and with Roofs shall be
extruded aluminum designed to meet the required wind load. Grid members
shall have the dimensions shown on the drawings or satisfy the design loads in
fit, form and function
2. Glazing gaskets shall be heavy extruded neoprene or EPDM as recommended
by the manufacturer. .
3. All fittings, nuts, bolts, expanding bolts, shims, shall be stainless steel type
316L.
4. Stainless steel for exterior caps, type 316L, shall comply with requirements of the following.
a. Sheet, strip, plate and flat bars: ASTM A 666.
b. Plate. sheet and strip: ASTM A 167.
c. Exposed/visible stainless steel shall have No. 4 satin finish.
5. Aluminum of alloy, temper and thickness as recommended by the manufacturer
for type and use indicated shall comply with requirements of the following.
a. Extruded bar and shapes: ASTM B 221.
b. Plate and sheet: ASTM B 209.
c.
Extrusions – 6063 - T5B. Organic Coating for all interior mullion surfaces– Thermosetting fluropolymer
containing Kynar 500. (70% by volume weight)in accordance with AAMA 2605.
Colour shall be white RAL 9010 from the standard range of the manufacturer.
C. Anodized finish shall be in accordance with AAMA AA-M12C22A44 with a minimum
coating of 18 microns. (when specified on drawings)
D. Fasteners and Accessories: Provide manufacturer's standard 316L series stainless steel
or aluminium noncorrosive fasteners and accessories compatible with materials used in
the framing system and with exposed portions that match finish of the system. Where
movement is expected, provide slip-joint linings of sheets, pads, shims, or washers of
fluorocarbon resin or a similar material recommended by the manufacturer.
1. Where fasteners anchor into aluminum less than 3.175 mm thick, provide
noncorrosive pressed-in splined grommet nuts or other type reinforcement to
receive fastener threads.
2. Exposed Fasteners. Do not use exposed fasteners except where unavoidable for
application of hardware. For application of hardware use fasteners that match
the finish of the member of hardware being fastened as appropriate.
3. Provide flat-head machine screws for exposed fasteners.
E. Concealed Flashing: Provide 0.70 mm thick minimum dead-soft stainless steel flashing.
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 9/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 9 of 11
F. Brackets and Reinforcements: Provide high strength stainless steel brackets and
reinforcements as and when indindicated on drawings.
G. Concrete/Masonry Inserts: Provide concrete and masonry inserts fabricated from
stainless steel 316L.
H. Compression-Type Weather-stripping: Provide compressible molded expanded
Santoprene, EPDM or neoprene weather-stripping gaskets complying with ASTM C
509.
I. Anchors and embeds: Anchors and embeds shall be made from mild steel (ASTM A 36)
finished with zinc chromate paint. The embeds shall be cast into the concrete as
indicated by the curtainwall manufacturer.
2.2 FABRICATION / MANUFACTURE
A. Curtain wall.
1. Provide shop fabricated curtain wall system for site assembly and installation.
All components shall be fabricated to comply with indicated standards specified
herein.
2. Curtain walls shall be designed with sufficient weep hole area to allow quick
drainage from any water penetration that might occur. Weep hole size to be
9.5mm minimum.3. Thermal barrier shall be an extruded silicone compatible elastomer separator or
similar performing product as recommended by the specialist and approved by
the COMPANY.
PART 3 EXECUTION
3.1 INSPECTION
A. Inspect openings before beginning installation. Verify that rough or masonry opening is
correct and the sill plate is level.
B. Masonry surfaces shall be visibly dry and free of excess mortar, sand and other
construction debris.
C. Metal surfaces shall be dry, clean, free of grease, oil, dirt, rust and corrosion, and
welding slag, and without sharp edges or offsets at joints.
3.2 INSTALLATION/APPLICATION/PERFORMANCE/ERECTION
A. Installation shall be in strict accordance with the metal curtain wall manufacturer's
specifications.
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 10/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 10 of 11
1. Anchor components securely in place in the manner indicated. Provide
separators and isolators to prevent corrosion, electrolytic deterioration, and
freeze-up of moving joints.
2. Set units plumb, level, and true to line, without warp or rack of frames or sash.
Provide proper support and anchor securely in place. Do not bridge thermal
breaks.
3. Separate aluminum and other corrodible surfaces from sources of corrosion or
electrolytic action at points of contact with other materials by complying with
the requirements specified under paragraph "Dissimilar Materials" in the
Appendix to AAMA 101.
4. Set sill members and other members in a bed of compound or with joint fillers
or gaskets, as shown, to provide weathertight construction. Refer to Section07900, CAULKING AND SEALANTS for compounds, fillers and gaskets to be
installed concurrently with window units. Coordinate installation with wall
flashing and other components of the Work.
B. Overall performance requirements.
1. Provisions for thermal movements. The wall shall be so detailed as to provide
for such expansion and/or contraction of the component materials as will be
caused by an ambient temperature range of 49°C. without causing harmful
buckling, opening of joints, undue stress on fasteners, or other detrimental
effects.
3.3 FIELD QUALITY CONTROL
A. Conduct two separate on-site tests for air and water infiltration with the manufacturer's
representative present. Units not meeting specified requirements and other units having
similar deficiencies shall be corrected and re-tested at no cost to the COMPANY.
Testing shall be performed by an accredited testing agency in accordance with
procedures specified in AAMA 501.3.
1. Air Infiltration Tests. Conduct tests in accordance with ASTM E 783. Allowable
infiltration per square foot of curtain wall area shall not exceed the amountspecified herein (Paragraph 1.2A.3.)
2. Water Resistance Tests: Conduct tests in accordance with ASTM E 1105. No
water penetration as defined in Paragraph l.2A.2. shall be permitted.
3. Costs for all tests shall be paid for by the system manufacturer.
3.4 ADJUSTMENT AND CLEARANCE
A. Cleaning
7/31/2019 08-08900- 3 Exterior Glaz.doc.
http://slidepdf.com/reader/full/08-08900-3-exterior-glazdoc 11/11
ABU DHABI NATIONAL OIL COMPANY (ADNOC)
RUWAIS HOUSING COMPLEX EXPANSION PHASE III
CONSTRUCTION OF NEW HOSPITAL - PHASE 1&2
PROJECT No. 5980
TENDER ENQUIRY No. 115980C1
VOL 5-DIV: 8 DOORS & WINDOWS SEC: 08900
REV: 00 11 of 11
1. Clean surfaces promptly after installation. Exercise care to avoid damage to
protective coatings and finishes.
2. Remove excess glazing and sealant compounds, dirt, and other substances.
Lubricate hardware and other moving parts.
B. Breakage And Protection
1. Replace units broken or damaged in the process of the Work. Curtain wall
Installer shall be relieved of responsibility of breakage or damage after units are
installed and will not be required to replace units at his expense unless breakage
or damage was caused by poor or faulty workmanship or materials. Broken or
damaged units shall be replaced at the expense of the party causing damage as
determined by the Contractor. If no responsibility for damage can bedetermined, the Contractor shall pay for all replacement costs.
2. Contractor shall initiate and maintain protection and other precautions required
through the remainder of the construction period to ensure that, except for
normal weathering, units will be free of damage or deterioration at the date of
the Provisional Acceptance Certificate.
C. Maintenance Instructions
1. A representative of the curtain wall manufacturer shall coordinate with the
Contractor and meet with the COMPANY’s maintenance staff so as to provide
sufficient instructions for maintenance and up-keep of the curtain wall
installation.
2. Provide maintenance procedure in accordance with the conditions of the
contract.