06156683

Embed Size (px)

Citation preview

  • 7/30/2019 06156683

    1/7

    1

    Comparison of Various Voltage Source Inverterbased UPQC Topologies

    Srinivas Bhaskar Karanki, Mahesh K. Mishra, Senior Member, IEEE, B. Kalyan Kumar, Member, IEEE

    Department of Electrical Engineering,

    Indian Institute of Technology Madras, Chennai, India.Corresponding author: Tel.:+91 44 22575459; Fax:+91 44 22574402; E-mail: [email protected]

    AbstractThe Unified Power Quality Conditioner (UPQC) isa custom power device, which mitigates voltage and currentrelated power quality issues in the power distribution systems. Inthis paper, two new Voltage Source Inverter (VSI) topologies forUPQC application are proposed. The proposed topologies enablesUPQC to have a reduced DC link voltage without compromisingthe compensation capability. These proposed topologies also helpto match the DC link voltage requirement of the shunt andseries active filters in the UPQC. In this paper the proposed

    UPQC topologies are compared with the existing topologies inthe literature. A simulation study of the proposed topologies hasbeen carried out and the results are presented.

    Index TermsUPQC topologies, DC link Voltage, UPQC, Non-

    stiff source.

    I. INTRODUCTION

    With the proliferation of the power electronics devices, non-

    linear loads and unbalanced loads, the power quality (PQ)

    in the power distribution network has degraded significantly[1]. To improve the quality of power, custom power devices

    are used in the distribution system. UPQC is one of the

    custom power device, which is a combination of back-to-backconnected shunt active filter and series active filter with a

    common DC link. Unified Power Quality Conditioner (UPQC)

    is used to provide balanced and sinusoidal source currents

    and load voltages under unbalanced and distorted three-phase

    supply voltages and load currents in a power distributionnetwork.

    In case of the three phase four wire system, neutral clamped

    topology is used for UPQC [2][4]. This topology enables the

    independent control of each leg of both the shunt and series

    inverters, but it requires capacitor voltage balancing [5]. In [6],four leg VSI topology for shunt active filter has been proposed

    for three phase four wire system. This topology avoids thevoltage balancing of the capacitor, but the independent control

    of the inverter legs is not possible. To overcome this problem

    in [7], [8], the authors have proposed a T-connected trans-

    former and three phase VSC based DSTATCOM. However

    this topology increases the cost and bulkiness of the UPQC

    because of the presences of extra transformer. In [9], H-bridge

    based VSI topology is used for UPQC operation. Although it

    has independent control of each legs of the inverter with single

    DC capacitor, the number of switches required for each leg is

    double when compared to other topologies. The compensation

    978-1-4577-1510-5/11/$ 26.00 @ 2011 IEEE

    performance of any active filter depends on the voltage ratingof DC link capacitor [10]. In general the DC link voltage for

    the shunt active filter has much higher value than the peakvalue of the line to neutral voltages [11][14]. This is done

    in order to ensure a proper compensation at the peak of the

    source voltage. Similarly for series active filter the DC link

    voltage is maintained at a value equal to the peak of the line

    to line voltage of the system for proper compensation [15][17].In case of the UPQC, the DC link voltage requirement for

    the shunt and series active filters is not the same, the shuntactive filter requires higher DC link voltage when compared

    to the series active filter for proper compensation. The shunt

    active filter provides a path for real power flow to aid the

    operation of the series compensator and to maintain constant

    average voltage across the DC storage capacitor [18]. In order

    to have a proper compensation for both series and shunt activefilter, common DC link voltage based on shunt active filter

    requirement have to be selected. This will result in over ratingthe series active filter as it requires lesser DC link voltage

    for proper compensation when compared to shunt active filter.Due to this criterion in literature, a higher DC link voltagebased on the UPQC topology have been chosen [6], [19],

    [20]. With the high value of DC link capacitor, the Voltage

    Source Inverters (VSI) becomes bulky and the switches used

    in the VSI also need to be rated for higher value of voltage

    and current. This in turn increases the entire cost and size of

    the VSI. To reduce the DC link voltage storage capacity afew attempts were made in literature. In [21], a hybrid filter

    has been discussed for motor drive applications. The filteris connected in parallel with diode rectifier and tuned at 7th

    harmonic frequency. Although an elegant work, the design is

    specific to the motor drive application and the reactive power

    compensation is not considered, which is an important aspectin shunt active filter applications.

    In this paper, two UPQC topologies with reduced DC linkvoltage are proposed. The first topology is a combination of

    the conventional neutral clamped topology and a capacitor inseries with the interfacing inductor of the shunt active filter.

    The series capacitor enables reduction in DC link voltage

    requirement of the shunt active filter and simultaneously

    compensating the reactive power required by the load, so as to

    maintain unity power factor, without any compromise on the

    performance of the UPQC. This allows us to match the DC link

    voltage requirements of the series and shunt active filter with

  • 7/30/2019 06156683

    2/7

    2

    vsa

    vsbN

    PCC

    Linear load

    Non-linear loadRf

    Lf

    Rf

    Lf

    Rf

    Lf

    Sc

    S'c

    Sa

    S'a

    Sb

    S'b

    Vdc

    Rs Ls

    Rs Ls

    Rs Ls

    Rla Llailaisa

    Rlb Llbilbisb

    Rlc Llcilcisc

    Rnl

    Lnl

    vsc

    ifbifa ifc

    Vdc

    'n

    n

    dcC

    dcC

    lav

    lbv

    lcv

    Scc

    S'cc

    Saa

    S'aa

    Sbb

    S'bb

    lni

    fni

    sni

    Cse Cse Cse

    tv

    dvrav

    dvrbv

    dvrcv

    Lse Lse LseThree Phase

    Supply

    Series Injection

    Transformers Unbalanced

    Distorted Load

    Series Active Filter Shunt Active Filter

    Fig. 1. Equivalent circuit of neutral clamped VSI topology based UPQC.

    a common DC link capacitor. In second topology, the system

    neutral is connected to the negative terminal of the DC bus.

    This will avoid the requirement of the fourth leg in VSI of

    the shunt active filter and enables the independent control ofeach leg of the VSI with single DC capacitor. In this paper

    various topologies are compared and the simulation studiesfor the conventional neutral clamped topology and the two

    proposed topologies are carried out using PSCAD simulator

    and detailed results are presented.

    I I . CONVENTIONAL AND PROPOSED TOPOLOGIES OFUPQC

    In this section, the conventional and proposed topologies

    of the UPQC are discussed. Figure 1 shows the power circuitof the neutral clamped VSI topology based UPQC which isconsidered as the conventional topology in this study. Even

    though this topology requires two DC storage devices, each

    leg of the VSI can be controlled independently and tracking is

    smooth with less number of switches when compared to other

    VSI topologies [5]. In this figure, vsa, vsb and vsc are source

    voltages of phases a, b and c respectively. Similarly, vta, vtband vtc are the terminal voltages. vdvra, vdvrb and vdvrc are

    the injected voltages of the series active filter. The sourcecurrents in three phase are represented by isa, isb and isc, load

    currents are represented by ila, ilb and ilc. The shunt active

    filter currents are denoted by ifa , ifb, ifc and iln represents

    the current in the neutral leg. Ls and Rs represent the feederinductance and resistance, respectively. The interfacing induc-

    tance and resistance of the shunt active filter are representedby Lf and Rf respectively. The interfacing inductance and

    filter capacitor of the series active filter are represented by Lseand Cse respectively. The load constituted of both linear and

    nonlinear loads as shown in this figure. The DC link capacitors

    and voltages across them are represented by Cdc1 = Cdc2 =Cdc and Vdc1 = Vdc2 = Vdc, respectively. Vbus is the total DC

    link voltage. In this conventional topology, the voltage across

    each common DC link capacitance is chosen as 1.6 times the

    peak value of the source voltage as given in [5].

    Vdc

    Vdc

    n

    dcC

    dcC

    fni

    PCC

    Rf

    Lf

    Rf

    Lf

    Rf

    Lf

    Sc

    S'c

    Sa

    S'a

    Sb

    S'b

    lav

    lbv

    lcv

    Scc

    S'cc

    Saa

    S'aa

    Sbb

    S'bb

    Three

    Phase

    Supply

    Series

    Injection

    Transformer

    Unbalanced

    Distorted

    Load

    sai

    sbi

    sci

    lai

    lbi

    lci

    sni

    tv

    lni

    nN

    fai fbi fci

    Cf Cf Cf

    Fig. 2. Equivalent circuit of neutral clamped VSI topology based UPQCwith series capacitor.

    Figure 2 shows the equivalent circuit of neutral clamped VSI

    topology based UPQC with series capacitor Cf. This topology

    is a combination of the conventional UPQC topology with a

    capacitor, Cf in series with the interfacing shunt branch ofthe shunt active filter. This topology is referred as proposed

    topology-I in this work. The passive capacitor Cf has thecapability to supply a part of the reactive power required

    by the load and the active filter will compensate the balance

    reactive power requirement and the harmonics present in the

    load. The addition of capacitor in series with the interfacinginductor of the shunt active filter will significantly reduce the

    DC link voltage requirement and consequently reduces theaverage switching frequency of the switches. This concept

    will be illustrated with analytic description in the followingsection. The reduction in the DC link voltage requirement of

    the shunt active filter enables us to match the DC link voltage

    requirement of the series active filter. This topology avoids theover rating of the series active filter in the UPQC compensation

    system. The design of the series capacitor Cf and the other

    VSI parameters have significant effect on the performance of

    the compensator. These are given in the next section.

  • 7/30/2019 06156683

    3/7

    3

    Cf

    PCC

    Rf

    Lf

    Rf

    Lf

    Rf

    Lf

    Sc

    S'c

    Sa

    S'a

    Sb

    S'bVbus

    dcC

    lav

    lbv

    lcv

    Scc

    S'cc

    Saa

    S'aa

    Sbb

    S'bb

    fni

    Three

    Phase

    Supply

    Series

    Injection

    Transformer

    Unbalanced

    Distorted

    Load

    sai

    sbi

    sci

    lai

    lbi

    lci

    sni

    tv

    lni

    nN

    fai fbi fci

    Cf Cf

    Fig. 3. Equivalent circuit of proposed VSI topology for UPQC compensatedsystem.

    Figure 3 represents the equivalent circuit of the proposed

    VSI topology for UPQC compensated system. In this topology

    the system neutral has been connected to the negative terminal

    of the DC bus along with the capacitor Cf in series with theinterfacing inductance of the shunt active filter. This topology

    is referred as proposed topology-II. This topology uses a

    single DC capacitor unlike the neutral clamped topology and

    consequently avoids the need of balancing the DC link volt-

    ages. Each leg of the inverter can be controlled independently

    both in shunt and series active filters. Unlike the topologies

    mentioned in the literature [2][4], [6], this topology does notrequire the fourth leg in the shunt active filter for three phase

    four wire system. The performance of this topology will beexplained in detailed in the following section.

    III. OPERATION OF THE PROPOSED TOPOLOGIES

    In this section the operation of the two proposed topologies

    are discussed. In case of the neutral clamped VSI topology

    with series capacitor, the fundamental voltage across the

    capacitor (vcf1) adds to the inverter terminal voltage (uVdc)

    when the load is inductive in nature. This is because, whenthe load is inductive in nature, the fundamental of the filter

    current lags the voltage at the PCC by 90o for reactive powercompensation and thus the fundamental voltage across the

    capacitor again lags the fundamental filter current by 90o.Finally the fundamental voltage across the capacitor will be

    in phase opposition to the voltage at the PCC. Thus, the

    fundamental voltage across the capacitor adds to the inverter

    terminal voltage. This allows us to rate the DC link voltage atlower value than conventional design [22].

    In the proposed topology-II, along with the series capacitorin the shunt active filter, the system neutral is connected to the

    negative terminal of the DC bus capacitor. This will introducea positive DC voltage component in the inverter output voltage,

    because when the top switch is ON +Vbus(= 2Vdc) appearsat the inverter output and 0 Vappears when the bottom switchis ON. Thus the inverter output voltage will have DC voltage

    component along with the AC voltage. The DC voltage is

    blocked by the series capacitor and thus the voltage across

    the series capacitor will be having two components, one is

    TABLE ISYSTEM PARAMETERS

    System Quantities Values

    System voltages 230 V (line to neutral), 50 Hz

    Feeder impedance Zs = 1 + j3.141

    Linear Load Zla = 34 + j47.5 , Zlb = 81 + j39.6 ,

    Zlc = 31.5 + j70.9

    Non-Linear Load Three phase full bridge rectifier load

    feeding a R-L load of 150 -300 mHShunt VSI parameters Cdc = 1100 F,Vbus = 1040 V,

    Lf = 26 mH, Rf = 1

    Series VSI parameters Cse=80 F, Lse= 5 mH

    Rsw = 1.5

    Series interfacing 1:1, 100 V and 700 V A

    transformer

    PI controller gains Kp = 6, Ki = 5.5

    Hysteresis band h1 = 0.5 A, h2= 6.9 V

    the AC component, which will be in phase opposition to the

    PCC voltage and the other is the DC component. Whereas, incase of the conventional topology the inverter output voltage

    varies between +Vdc when top switch is ONand Vdc whenthe bottom switch ON. Similarly, when a four leg topology

    is used for shunt active filter with a single DC capacitor, the

    inverter output voltage varies between +Vbus and Vbus. So,these topologies does not contain any DC component in the

    inverter output voltage. This topology contains only one DC

    capacitor as the neutral is directly connected to the negative

    terminal of the DC bus, this avoids the need of balancing

    of capacitor voltages, which is a major setback of the neutralclamped topology. Since the neutral wire is directly connected

    to the negative terminal of the DC bus, the necessity of fourth

    leg in the inverter is avoided. In case of the four leg basedVSI topology, independent control is not possible. In the

    modified topology, the three legs of the shunt active filter are

    independently controlled and which results in the automatic

    tracking of the neutral current. Thus the modified topology

    has the advantage of both the neutral clamped topology and

    four leg inverter topology.

    The parameters of the VSI need to be designed carefully

    for better tracking performance. The important parameters thatneed to be taken into consideration while designing conven-

    tional VSI are Vdc, Cdc, Lf , Lse, Cse and switching frequency

    (fsw). A detailed design procedure of VSI parameters for the

    shunt and series active filter are given in [23], [24], basedon the the equations in the [23], [24] the parameters of the

    conventional VSI topology are chosen and given in Table I.The series capacitor design is given in [22] and the value

    of the Cf is chosen to be 65 F for a reduced DC linkvoltage of 280 V across each DC link capacitor. In this

    work, the reference currents for the active filters are generated

    using Instantaneous symmetrical component theory [25] Toovercome the limitation of the algorithm, fundamental positive

    sequence voltages v+la1(t), v+

    lb1(t) and v+

    lc1(t) of the PCCvoltages are extracted and are used in the shunt algorithm

    [26].

  • 7/30/2019 06156683

    4/7

    4

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -10.0

    -5.0

    0.0

    5.0

    10.0

    Current(A)

    Time (s)

    lai lbi lci

    lni

    (a)

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    Voltage(V)

    Time (s)

    tav tbv tcv

    (b)

    Fig. 4. Simulation results (a) Load currents before compensation (b) Terminalvoltages before compensation.

    IV. SIMULATION RESULTS

    In order to validate the proposed topologies, simulations

    are carried out using PSCAD software. The same system

    parameters which are given Table I with Cf = 65 F are

    used in PSCAD simulation. The simulation results for both

    the conventional topology and the proposed topologies I and

    II are presented in this section for better understanding and

    comparison between the topologies.

    The load currents and terminal (PCC) voltages before com-

    pensation are shown in Fig. 4. The load currents are unbal-

    anced and distorted, the terminal voltages are also unbalanced

    and distorted because these load currents flow through thefeeder impedance in the system. Figure 5 gives the simulation

    results of the UPQC using conventional VSI topology. The

    DC link voltages across the top and bottom DC link capacitors

    are shown in Fig. 5(a), using PI controller the voltage across

    each capacitor is maintained constant to the reference value

    of 520 V as shown in the figure. The source currents after

    compensation are balanced and sinusoidal as shown in Fig.

    5(b). Figure 5(c) represents the compensation performance ofthe series active filter. A sag of 50 % is considered in allphases of the terminal voltages for 5 cycles, which start from

    1.9 seconds and ends at 2.0 seconds. The compensated DVR

    voltages and load voltages after compensation are shown in the

    same figure. The load voltages are maintained to the desiredvoltage using series active filter. In this topology the peak to

    peak voltage across the inductor is 1040 V.

    The simulation results for the topology shown in Fig. 2

    and (i.e., the neutral clamped VSI topology based UPQC withcapacitor in series with the interfacing inductor of the shunt

    active filter) are shown in Figs. 6(a) and 7. In this topology

    The value of the capacitor (Cf) in the shunt active filter branchis chosen to be 65 F and the reference DC link voltage

    is 280 V for each capacitor. The voltage across the series

    capacitor in phase-a (vcfa) is shown in Fig. 6(a). This figure

    also shows the phase-a load voltage (vla). From the figure

    0.0 0 0 .5 0 1. 00 1. 50 2 .0 0 2 .5 0 3 .0 0 3. 50 4.0 0 4 .5 0 5 .0 0

    0

    200

    400

    600

    0

    200

    400

    600

    Voltage(V)

    Time (s)

    1dcV

    2dcV

    (a)

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -10.0

    -5.0

    0.0

    5.0

    10.0

    Current(A)

    Time (s)

    sai sbi sci

    sni

    (b)

    1.860 1 .880 1 .900 1 .920 1 .940 1 .960 1 .980 2 .000 2 .020 2 .040

    -500

    -250

    0

    250

    500

    -300

    -150

    0

    150

    300

    -500

    -250

    0

    250

    500

    Voltage(V)

    Time (s)

    tav tbv tcv

    dvrav dvrbv dvrcv

    lav lbv lcv

    (c)

    Fig. 5. Simulation results using conventional topology (a) DC capacitorvoltages (top and bottom) (b) Source currents after compensation (c) Terminalvoltages with sag, DVR injected voltages and Load voltages after compensa-tion

    it is clear that the voltage across the capacitor is in phase

    opposition to the terminal voltage. The voltage across thecapacitor eventually adds to the DC link voltage and injects

    the required compensation currents into the PCC. The reasonbeyond showing phase-a capacitor voltage is that the design of

    the reference DC link voltage is based on phase-a filter current,

    which has the maximum filter current among the three phases.

    Figure 7 gives the simulation results of the UPQC usingproposed VSI topology-I. The DC link voltages across the top

    and bottom DC link capacitors are shown in Fig. 7(a), using

    PI controller the voltage across each capacitor is maintained

    constant to the reference value of 280 V as shown in thefigure. The source currents after compensation are balanced

    and sinusoidal as shown in Fig. 7(b). It can be observed fromthe Fig. 7(b), the band violation of the sources currents are

    less when compared to the conventional topology. Figure 7(c)represents the compensation performance of the series active

    filter. A sag of 50 % is considered in all phases of the theterminal voltages for 5 cycles, which start from 1.9 secondsand ends at 2.0 seconds. The compensated DVR voltages and

    load voltages after compensation are shown in the same figure.

    The load voltages are maintained to the desired voltage using

    series active filter. In this topology the peak to peak voltage

  • 7/30/2019 06156683

    5/7

    5

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    Time (s)

    Voltage(V)

    cfavlav

    (a)

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    500

    Voltage(V)

    Time (s)

    cfavlav

    (b)

    Fig. 6. Voltage across series capacitor and load voltage in phase - a (a)Proposed topology-I (b) Proposed topology-II.

    across the inductor is 560 V.

    The simulation results with the proposed topology-II are

    shown in Figs. 6(b) and 8. In this topology the total DC bus

    voltage is maintained at 560 V. The voltage across the series

    capacitor in phase-a (vcfa) and the phase-a load voltage (vla)

    are shown in Fig. 6(b). Both are in phase opposition and

    eventually the series capacitor voltage supports in injecting

    the compensation currents into the PCC. The inverter output

    voltage varies between 0 and +Vbus, which will introduce a

    dc component along with the AC components. The same dccomponent will be reflected across the series capacitor voltage

    (vcfa).The DC bus voltage (Vbus) is shown in figure Fig. 8(a). The

    source currents after compensation using proposed topology-II

    are shown in Fig. 8(b). Figure 8(c) represents the compensa-

    tion performance of the series active filter. A sag of 50 %is considered in all phases of the the terminal voltages for 5

    cycles, which start from 1.9 seconds and ends at 2.0 seconds.

    The compensated DVR voltages and load voltages are shown

    in the same figure. The load voltages are maintained to the

    desired voltage using series active filter. The peak to peak

    voltage across the inductor is 560 V, which is far lower thanthe voltage across the inductor using conventional topology.

    As the voltage across inductor is high in case of conventional

    topology, the rate of rise of filter currentdifdt will be higher

    than that of proposed topologies. Thus the slope of the actual

    filter currents in case of the conventional topology will be

    high and this will allow the filter currents to hit the hysteresisboundaries at a faster rate and increases the switching fre-

    quency when compared to the proposed topologies. Thus, the

    average switching frequency of the switches in the proposed

    topology will be less as compared to conventional topology.

    Since the average switching is less, the switching loss will

    also decrease in proposed topologies.

    One more advantage of having less voltage across the

    inductor is that the hysteresis band violation will be less.

    0. 00 0. 50 1 .0 0 1 .5 0 2 .0 0 2 .5 0 3 .0 0 3 .5 0 4 .0 0 4. 50 5 .0 0

    0

    100

    200

    300

    0

    100

    200

    300

    Voltage(V)

    Time (s)

    (a)

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -10.0

    -5.0

    0.0

    5.0

    10.0

    Current(A)

    Time (s)

    sai sbi sci

    sni

    (b)

    1.860 1.880 1.900 1.920 1.940 1.960 1.980 2.000 2.020 2.040

    -500

    -250

    0

    250

    500

    -300-200-100

    0100200300

    -500

    -250

    0

    250

    500

    Voltage(V)

    Time (s)

    tav tbv tcv

    dvrav dvrbv dvrcv

    lav lbv lcv

    (c)

    Fig. 7. Simulation results using proposed topology-I (a) DC capacitorvoltages (top and bottom) (b) Source currents after compensation (c) Terminalvoltages with sag, DVR injected voltages and Load voltages after compensa-tion.

    This will improve the quality of compensation and Total

    Harmonic Distortion (THD) will be less in the proposed

    topology. Similarly the switching in the series active filter

    also reduces marginally as the DC link voltage is reduced.

    The THD of the source currents and load voltages before and

    after compensation in all the three phases are given in Table

    II. Table II also gives the average switching frequency in each

    leg of the inverter. This clearly shows the proposed topologiesperformance is better than the conventional topology with a

    less DC link voltage, reduction in switching operation andregular tracking of reference compensator currents.

    Table III gives the comparison of various topologies in

    the literature with the proposed topologies. From this tableit is clear that the proposed topologies required reduced

    DC link voltage and subsequently the rating of the switches

    also reduces. Proposed topology-II has advantages of all the

    other topologies with a extra requirement of three AC series

    capacitors. Both the proposed topologies enables the matching

    of the DC link voltage requirement of the shunt and series

    active filters.

    V. CONCLUSIONS

    Two UPQC topologies for three phase four wire system

    has been proposed in this paper, which has the capability of

  • 7/30/2019 06156683

    6/7

    6

    TABLE IICOMPARISON OF PROPOSED TOPOLOGIES WIT H CONVENTIONAL TOPOLOGY

    Type of Topology THD (%) Average Switching Frequency (kHz)

    Source Currents Load Voltages Shunt Active Filter Series Active Filter

    isa isb isc vla vlb vlc Leg- a Leg- b Leg- c Leg- a Leg- b Leg- c

    Without Compensation 9.2 11.7 12.75 5.99 5.86 6.17 - - - - - -

    Conventional Topology 2.96 3.20 2.55 1.48 1.59 2.10 3.96 4.12 3.95 8.10 8.30 8.40Proposed topology-I 1.91 2.56 2.43 1.27 1.32 1.48 2.90 2.40 2.75 6.50 7.00 7.10

    Proposed topology-II 1.59 2.19 1.31 1.12 1.24 1.58 3.10 2.44 2.98 6.80 7.20 7.40

    TABLE IIICOMPARISON OF VARIOUS TOPOLOGIES

    Parameter Conventional Four leg H-Bridge Proposed Proposed

    Topology [5] Topology [6] Topology [9] Topology-I Topology-II

    DC link voltage (Vbus) 2 1.6 Vm1 2.2 Vm 2.45 Vm 2 0.86 Vm 1.72 Vm

    (In this paper Vm = 325V ) 1040 V 715 V 800 V 560 V 560 V

    Number of Switches 6+6 = 12 6+8 =14 12+12 = 24 6+6 = 12 6+6 = 12

    (Series+Shunt = Total)

    Voltage Rating of Switch Vbus Vbus Vbus Vbus Vbus

    Number of DC Capacitors 2 1 1 2 1

    DC Capacitor Balancing R 2 NR 3 NR R NR

    Series AC Capacitors - - - 3 3

    Control of Shunt Inverter Legs I 4 D 5 I I I

    1 Vm is the peak of the source voltage;2R = Required; 3 NR = Not Required; 4I = Independent; 5D = Dependent

    compensating the load at a lower DC link voltage under non

    stiff source. The proposed method is validated through simu-

    lation studies in a three-phase four wire distribution system.

    The proposed topology-II has the advantages of both the con-ventional neutral clamped topology and the four leg topology.

    Detailed comparative studies are made for the conventionaland proposed topologies. From the study, it is found that the

    proposed topologies have less average switching frequency,less THDs in the source currents and terminal voltages with

    reduced DC link voltage as compared to the conventional

    UPQC topology.

    REFERENCES

    [1] M. Bollen, Understanding Power Quality Problems : Voltage Sags andInterruptions. IEEE press, New York, 1999.

    [2] T. Zhili, L. Xun, C. Jian, K. Yong, and D. Shanxu, A direct controlstrategy for UPQC in three-phase four-wire system, in Power Electron-ics and Motion Control Conference, 2006. IPEMC 2006. CES/IEEE 5th

    International, vol. 2, Aug. 2006, pp. 15.[3] T. Zhili, L. Xun, C. Jian, K. Yong, and Z. Yang, A new control

    strategy of UPQC in three-phase four-wire system, in Power ElectronicsSpecialists Conference, 2007. PESC 2007. IEEE, June 2007, pp. 10601065.

    [4] M. Brenna, R. Faranda, and E. Tironi, A new proposal for power qualityand custom power improvement: Open UPQC, IEEE Transactions onPower Delivery,, vol. 24, no. 4, pp. 21072116, Oct. 2009.

    [5] V. George and Mahesh K. Mishra, DSTATCOM topologies for threephase high power applications, Int. J. Power Electronics, vol. 2, no. 2,pp. 107124, 2010.

    [6] V. Khadkikar and A. Chandra, A novel structure for three-phase four-wire distribution system utilizing unified power quality conditioner

    (UPQC), IEEE Transactions on Industry Applications, vol. 45, no. 5,pp. 18971902, Sept.-Oct. 2009.

    [7] Y. Pal, A. Swarup, and B. Singh, A comparative analysis of three-phase four-wire UPQC topologies, in Power Electronics, Drives and

    Energy Systems (PEDES) 2010 Power India, 2010 Joint InternationalConference on, Dec. 2010, pp. 16.

    [8] B. Singh, P. Jayaprakash, and D. Kothari, A T-connected transformerand three-leg VSC based DSTATCOM for power quality improvement,

    IEEE Transactions on Power Electronics,, vol. 23, no. 6, pp. 27102718,Nov. 2008.

    [9] F. Fang, G. Qin-Xiang, and B. Fanpeng, Research on the hybridtopology of unified power quality conditioner based on direct controlphilosophy, in Electric Utility Deregulation and Restructuring andPower Technologies (DRPT), 2011 4th International Conference on, july2011, pp. 245249.

    [10] S. V. R. Kumar and S. S. Nagaraju, Simulation of DSTATCOM andDVR in Power Systems , ARPN Journal of Engineering and AppliedScience, vol. 2, no. 3, pp. 713, 2007.

    [11] R. Gupta, A. Ghosh, and A. Joshi, Multiband hysteresis modulation andswitching characterization for sliding-mode-controlled cascaded multi-level inverter, IEEE Transactions on Industrial E lectronics, vol. 57,no. 7, pp. 23442353, July 2010.

    [12] S. Srikanthan and M. Mishra, DC capacitor voltage equalization in neu-tral clamped inverters for DSTATCOM application, IEEE Transactionson Industrial Electronics, vol. 57, no. 8, pp. 27682775, Aug. 2010.

    [13] R. Gupta, A. Ghosh, and A. Joshi, Switching characterization ofcascaded multilevel-inverter-controlled systems, IEEE Transactions on

    Industrial Electronics, vol. 55, no. 3, pp. 10471058, March 2008.

    [14] B. Singh and J. Solanki, Load compensation for diesel generator-basedisolated generation system employing DSTATCOM, IEEE Transactionson Industrial Electronics, vol. 47, no. 1, pp. 238244, Jan.-Feb. 2011.

    [15] P. Roncero S, E. Acha, J. Ortega-Calderon, V. Feliu, and A. Garcia-Cerrada, A versatile control scheme for a dynamic voltage restorerfor power-quality improvement, IEEE Transactions on Power Delivery,vol. 24, no. 1, pp. 277284, Jan. 2009.

    [16] Y. W. Li, P. C. Loh, F. Blaabjerg, and D. Vilathgamuwa, Investigation

  • 7/30/2019 06156683

    7/7

    7

    0 .0 0 0. 50 1 .0 0 1 .5 0 2 .0 0 2 .5 0 3 .0 0 3 .50 4 .00 4. 50 5. 00

    0

    100

    200

    300

    400

    500

    600

    Voltage(V)

    Time (s)

    dcV

    (a)

    1.9600 1.9650 1.9700 1.9750 1.9800 1.9850 1.9900 1.9950 2.0000

    -10.0

    -5.0

    0.0

    5.0

    10.0

    Time (s)

    Voltage(V)

    sai sbi sci

    sni

    (b)

    1.860 1 .880 1 .900 1 .920 1 .940 1 .960 1 .980 2 .000 2 .020 2 .040

    -500

    -250

    0

    250

    500

    -300

    -150

    0

    150300

    -500

    -250

    0

    250

    500

    Voltage(V)

    Time (s)

    tav tbv tcv

    dvrav dvrbv dvrcv

    lav lbv lcv

    (c)

    Fig. 8. Simulation results using modified topology (a) DC link voltage(b) Source currents after compensation (c) Terminal voltages with sag, DVRinjected voltages and Load voltages after compensation.

    and improvement of transient response of DVR at medium voltage level,IEEE Transactions on Industry Applications, vol. 43, no. 5, pp. 13091319, Sept.-Oct. 2007.

    [17] Y. W. Li, D. Mahinda Vilathgamuwa, F. Blaabjerg, and P. C. Loh, Arobust control scheme for medium-voltage-level DVR implementation,

    IEEE Transactions on Industrial Electronics, vol. 54, no. 4, pp. 22492261, Aug. 2007.

    [18] I. Axente, M. Basu, and M. F. Conlon, DC link voltage controlof UPQC for better dynamic performance, Electric Power Systems

    Research, vol. 81, no. 9, pp. 1815 1824, 2011.[19] M. Kesler and E. Ozdemir, Synchronous-reference-frame-based control

    method for UPQC under unbalanced and distorted load conditions,IEEE Transactions on Industrial Electronics, vol. 58, no. 9, pp. 39673975, Sept. 2011.

    [20] K. H. Kwan, Y. C. Chu, and P. L. So, Model-based Hinfty control ofa unified power quality conditioner, IEEE Transactions on Industrial

    Electronics, vol. 56, no. 7, pp. 24932504, July 2009.[21] H. Akagi and R. Kondo, A transformer less hybrid active filter usinga three-level pulse width modulation (PWM) converter for a medium-voltage motor drive, IEEE Transactions on Power Electronics, vol. 25,no. 6, pp. 13651374, June 2010.

    [22] S. Karanki, G. Nagesh, Mahesh K. Mishra, and B. Kumar, A hybridtopology for reducing DC link voltage rating in DSTATCOM applica-tions, in Energytech, 2011 IEEE, May 2011, pp. 16.

    [23] Mahesh K. Mishra and K. Karthikeyan, Design and analysis of voltagesource inverter for active compensators to compensate unbalanced andnon-linear loads, in International Power Engineering Conference, 2007,

    IPEC 2007., 2007, pp. 649654.[24] S. Sasitharan and M. Mishra, Design of passive filter components for

    switching band controlled DVR, in TENCON 2008 - 2008 IEEE Region10 Conference, Nov. 2008, pp. 16.

    [25] A. Ghosh and A. Joshi, A new approach to load balancing and power

    factor correction in power distribution system, IEEE Transactions onPower Delivery, vol. 15, no. 1, pp. 417422, Jan. 2000.

    [26] U. K. Rao, Mahesh K. Mishra, and A. Ghosh, Control strategies forload compensation using instantaneous symmetrical component theoryunder different supply voltages, IEEE Transactions on Power Delivery,vol. 23, no. 4, pp. 23102317, 2008.