13
POWER TRANSFORMER NEUTRAL GROUNDING REACTOR APPLICATION AND DISTRIBUTION FEEDER PROTECTION ISSUES AT CENTERPOINT ENERGY Patrick Sorrells and Alberto Benitez CenterPoint Energy ABSTRACT This paper discusses the ramifications of grounding a substation power transformer through a reactor on the CenterPoint Energy distribution system. The purpose of the reactor is to reduce the magnitude of ground fault currents. This is expected to increase transformer life expectancy by significantly reducing transformer short circuit forces. The higher ground impedance provided by the Neutral Grounding Reactor (NGR) also causes an increased voltage drop in the ground return path, raising the temporary overvoltage on the unfaulted phases and deepening the voltage sag on the faulted phase during a ground fault. Under normal operating conditions with large load imbalances, voltage regulation can be also impacted. The reduction in ground fault current requires the modification of ground protective device coordination and settings. The paper discusses how these issues are addressed for a successful implementation of an NGR in an effectively grounded, 4-wire distribution system. 1. INTRODUCTION From 1989 to 1996, CenterPoint Energy experienced an usually high number of failures among its substation power transformers. A total of 36 power transformers failed during this time. The single largest cause of failure was through faults, accounting for 36% of all failures. Through faults are faults that occur on the distribution system. These faults can stress the power transformer’s windings since the windings must carry an unusually high current magnitude while the fault persists. Given the expense of replacing power transformers - transformers account for two-thirds of the cost of a substation – CenterPoint Energy formed a team to make recommendations for reducing failures from these faults. One of the ideas suggested was the installation of a Neutral Grounding Reactor (NGR) between the transformer neutral bushing and the system ground. Grounding a power transformer through an NGR increases the impedance of the system ground, lowering the magnitude of ground fault currents. The decreased fault current magnitude reduces the mechanical stress on the transformer’s windings. This should result in fewer transformer failures from through faults. All of CenterPoint Energy’s power transformers are core form, two winding units connected delta on the high side and grounded wye on the secondary side. The secondary side is energized at either 12.47kV (12kV) or 34.5kV (35kV) and serves 4-wire, multigrounded distribution feeders. Prior to 1996, all of the transformers had their neutral bushing bonded directly to the substation ground mat. No impedance was intentionally added. In 1996, CenterPoint Energy began a pilot project at its Westfield substation. The four power transformers at the substation – two serving 12kV feeders and two serving 35kV feeders – were grounded through NGRs. The intention was to collect data on how the NGRs impacted the distribution feeders. However, equipment problems and personnel changes caused the project to languish. Since that time, overall power transformer failures have decreased to 21 while the transformer fleet itself has increased. But through fault failures remained steady in absolute terms – 11 transformers - and rose as a percentage of all failures to 52%. The continued prevalence of through fault failures renewed interest in NGRs. Around the same time, concern was voiced about the possible effects on the distribution system. Voltage regulation, power quality, protective device coordination, and ground fault protection are all impacted to a greater or lesser degree. In addition, the NGR changes some of the standard assumptions used for setting the feeder relays at CenterPoint Energy. This paper presents these issues as they relate to CenterPoint Energy’s system and discusses data collected from the Westfield project since 2001. 2. EFFECT OF A NEUTRAL GROUNDING REACTOR A NGR is an inductor intentionally inserted between the substation transformer’s neutral and the system ground. The impedance of the NGR adds to the impedance of the grounding system, raising the total impedance that 27 0-7803-8896-8/05/$20.00 ©2005 IEEE

01430419

Embed Size (px)

DESCRIPTION

reactor

Citation preview

  • POWER TRANSFORMER NEUTRAL GROUNDING REACTOR APPLICATION AND

    DISTRIBUTION FEEDER PROTECTION ISSUES AT CENTERPOINT ENERGY

    Patrick Sorrells and Alberto Benitez

    CenterPoint Energy

    ABSTRACT

    This paper discusses the ramifications of grounding a

    substation power transformer through a reactor on the

    CenterPoint Energy distribution system. The purpose of

    the reactor is to reduce the magnitude of ground fault

    currents. This is expected to increase transformer life

    expectancy by significantly reducing transformer short

    circuit forces. The higher ground impedance provided by

    the Neutral Grounding Reactor (NGR) also causes an

    increased voltage drop in the ground return path, raising

    the temporary overvoltage on the unfaulted phases and

    deepening the voltage sag on the faulted phase during a

    ground fault. Under normal operating conditions with

    large load imbalances, voltage regulation can be also

    impacted. The reduction in ground fault current requires

    the modification of ground protective device coordination

    and settings. The paper discusses how these issues are

    addressed for a successful implementation of an NGR in

    an effectively grounded, 4-wire distribution system.

    1. INTRODUCTION

    From 1989 to 1996, CenterPoint Energy experienced an

    usually high number of failures among its substation

    power transformers. A total of 36 power transformers

    failed during this time. The single largest cause of failure

    was through faults, accounting for 36% of all failures.

    Through faults are faults that occur on the distribution

    system. These faults can stress the power transformers

    windings since the windings must carry an unusually

    high current magnitude while the fault persists.

    Given the expense of replacing power

    transformers - transformers account for two-thirds of the

    cost of a substation CenterPoint Energy formed a team

    to make recommendations for reducing failures from

    these faults. One of the ideas suggested was the

    installation of a Neutral Grounding Reactor (NGR)

    between the transformer neutral bushing and the system

    ground. Grounding a power transformer through an NGR

    increases the impedance of the system ground, lowering

    the magnitude of ground fault currents. The decreased

    fault current magnitude reduces the mechanical stress on

    the transformers windings. This should result in fewer

    transformer failures from through faults.

    All of CenterPoint Energys power transformers

    are core form, two winding units connected delta on the

    high side and grounded wye on the secondary side. The

    secondary side is energized at either 12.47kV (12kV) or

    34.5kV (35kV) and serves 4-wire, multigrounded

    distribution feeders. Prior to 1996, all of the transformers

    had their neutral bushing bonded directly to the

    substation ground mat. No impedance was intentionally

    added.

    In 1996, CenterPoint Energy began a pilot

    project at its Westfield substation. The four power

    transformers at the substation two serving 12kV feeders

    and two serving 35kV feeders were grounded through

    NGRs. The intention was to collect data on how the

    NGRs impacted the distribution feeders. However,

    equipment problems and personnel changes caused the

    project to languish.

    Since that time, overall power transformer

    failures have decreased to 21 while the transformer fleet

    itself has increased. But through fault failures remained

    steady in absolute terms 11 transformers - and rose as a

    percentage of all failures to 52%. The continued

    prevalence of through fault failures renewed interest in

    NGRs. Around the same time, concern was voiced about

    the possible effects on the distribution system. Voltage

    regulation, power quality, protective device coordination,

    and ground fault protection are all impacted to a greater

    or lesser degree. In addition, the NGR changes some of

    the standard assumptions used for setting the feeder

    relays at CenterPoint Energy. This paper presents these

    issues as they relate to CenterPoint Energys system and

    discusses data collected from the Westfield project since

    2001.

    2. EFFECT OF A NEUTRAL GROUNDING

    REACTOR

    A NGR is an inductor intentionally inserted between the

    substation transformers neutral and the system ground.

    The impedance of the NGR adds to the impedance of the

    grounding system, raising the total impedance that

    270-7803-8896-8/05/$20.00 2005 IEEE

  • ground currents must flow through. Since the magnitude

    of a fault current is determined by dividing the system

    voltage by the impedance of the path it flows through

    (I=V/Z), the additional impedance reduces the magnitude

    of the fault current. Note that only ground faults are

    affected by a NGR.

    To see how the NGR raises the impedance of the

    fault path for ground faults, consider that all currents

    whether load or fault - must flow in a loop and must

    return to their source. For CenterPoint Energys

    distribution system, that source is effectively the windings

    of the substation transformer. During a line to ground

    fault, current flows from the winding of the transformer,

    through the phase conductor, into the earth. The current

    will then split and flow through the neutral conductor and

    the earth as it returns to the transformer. The current

    returns to the transformer winding through the

    transformers neutral bushing. Adding the NGR forces

    all currents returning through the neutral and the earth to

    pass through the NGR to return to the transformers

    windings. Currents that do not have to flow through the

    transformers neutral to return to the windings line to

    line fault currents, for instance will not flow through

    the NGR and are unaffected.

    The reduction in ground fault current depends

    on the relative magnitude of the NGR's impedance

    compared to the impedance of the fault path without the

    NGR and the fault type. For single line to ground faults

    near the substation, the additional impedance the NGR

    contributes to the fault path is large compared to the

    existing impedance. A dramatic reduction in the fault

    current can be achieved. For single line to ground faults

    located at the end of the feeder, the additional impedance

    the NGR contributes to the fault path is small compared

    to the existing impedance to the fault. The NGR will

    reduce these fault currents, but only slightly. The NGRs

    effect on double line to ground faults is also greatest for

    faults near the substation and least for faults near the end

    of the feeder. However, increasing the ground impedance

    makes these faults appear more like a line to line fault.

    This can reduce the line current magnitude seen at the

    transformer, but the change is generally not significant.

    The NGRs effect on the ground fault current is

    not limited to the symmetrical AC current. For faults that

    are initially asymmetrical a DC offset current exists -

    the rate of decay of the DC offset current decreases

    because the NGR increases the X/R ratio of the system.

    Effectively, the DC component of the fault current

    remains at a higher value for longer, relative to the AC

    component, than would occur otherwise without the

    NGR. The change in the DC offset partially cancels some

    of the reduction in fault current magnitude while it exists.

    However, the reduction in ground fault current magnitude

    dominates the slower decay of the DC offset for all points

    on the feeder. As expected, the NGRs effect on the X/R

    ratio is greatest for ground faults near the substation and

    least for ground faults at the end of the feeder.

    Practical considerations limit the amount of fault

    current reduction that can be achieved. The most

    important of these is the voltage rating of the lightning

    arrestors used on the feeder. Lightning arrestors rated for

    line to neutral voltages, as opposed to line to line

    voltages, can only be used on effectively grounded

    systems [1]. An effectively grounded system is defined as

    having an X0/X1 ratio of 3 or less and a R0/X1 ratio

    between 0 and 1[1]. Here, R0 and X0 represent the zero

    sequence resistance and reactance of the distribution

    system at any given point; X1 represents the positive

    sequence reactance of the distribution system at that same

    point. The impedance of the NGR adds to the zero

    sequence values, but not the positive sequence values.

    Since the NGRs impedance is predominantly reactive, its

    primary effect is to raise the X0 value for all points on the

    distribution system. The resistance of the NGR is

    generally small enough that its effect on the R0/X1 ratio

    can be ignored. Since all of CenterPoint Energys existing

    lightning arrestors are rated for line to neutral voltages,

    an effectively grounded system must be maintained.

    Thus, the size of the NGR that can be installed is limited

    by the requirement to maintain an X0/X1 ratio of 3 or

    less. Given this requirement, the single line to ground

    fault current can be limited, at best, to 60% of the value

    of the three-phase fault current.

    3. THE SHORT CIRCUIT STRENGTH OF

    TRANSFORMERS

    The significance of reducing the fault current magnitude

    lies in its relationship to the mechanical forces

    experienced by the winding during a fault. The

    mechanical forces acting on the windings are

    proportional to the square of the fault current magnitude

    [2]. Thus, when the fault current magnitude doubles, the

    mechanical forces in the transformer increase by a factor

    of four. Physically, these forces act to crush, bend, or

    stretch the conductors and their associated

    insulation.[3]. The short circuit strength of a

    transformer is its ability to withstand these effects.

    The design and construction of the transformer

    determine its initial short circuit strength. Once it is

    placed in service, the transformers ability to retain its

    short circuit strength is predominantly a function of the

    clamping pressure on the windings [4]. The clamping

    pressure is intended to keep the windings securely in

    place during faults so that they do not move from their

    original placement [4]. As long as the windings are

    properly aligned, the mechanical forces that act on them

    during a fault can be minimized [5]. However, if they are

    28

  • allowed to move slightly, the forces exerted on the

    windings will grow rapidly [2], [5]. Once some small

    movement has occurred, the effect tends to accelerate

    the forces increase, causing the windings to move a little

    more, causing the forces to increase further, etc.

    Eventually, either the windings will become deformed

    and/or collapse or an insulation rupture will occur [5],

    [6].

    Not surprisingly, the clamping pressure and

    thus the transformers short circuit strength - will not

    remain constant over time [6]. Changes in the thickness

    of the winding insulation or the end insulation will cause

    the clamping pressure to vary [4]. Both insulation aging

    and the mechanical forces associated with faults can

    gradually reduce the clamping pressure, while short term

    environmental effects can cause a temporary increase in

    clamping pressure [6], [4]. Each of these processes is

    discussed below.

    3.1. Insulation Aging

    The primary reason the transformers short circuit

    strength does not remain constant is the aging of the

    cellulose insulation [6]. The cellulose insulation

    physically changes in several ways while a transformer is

    in service. First, the aging process breaks down the

    chemical bonds that give the insulation its tensile

    strength its ability to resist being torn [6]. As the

    insulation weakens, it becomes more susceptible to

    tearing when stressed by the mechanical forces of a fault.

    If it does tear, the result will be a new fault internal to the

    transformer that will very likely lead to a failure.

    The same process that breaks down the

    insulations tensile strength also causes the cellulose to

    decompose, so that less material physically exists over

    time [4]. As noted above, a change in the insulation

    thickness will cause a change in the clamping pressure.

    In this case, the loss of insulation will cause a loss of

    clamping pressure. The reduction in clamping pressure

    increases the chances for winding movement and,

    eventually, a failure due to the increased forces acting on

    the winding.

    Finally, the clamping pressure itself causes the

    cellulose to relax and settle [6]. The clamping pressure

    acts as a load on the insulation, compressing it. When

    the insulation is compressed over a long period of time, it

    develops a permanent set. Even if the compressive force

    is reduced or removed, the insulation will not recover to

    its original size. Although manufacturers specially pre-

    treat the insulation to reduce the amount of settling as

    much as possible, it cannot be completely eliminated [4].

    Thus, due to the clamping pressures action on the

    insulation, it is impossible to maintain the initial pressure

    on the windings. As noted above, the chance of an

    internal failure increases as the clamping pressure

    decreases.

    3.2. Fault Forces

    The forces associated with faults can also erode the

    transformers short circuit strength over time. Similar to

    the relaxation and settling caused by the clamping

    pressure, the fault forces act to compress the winding

    insulation as well [6], [5]. Unlike the clamping pressure,

    the fault forces apply a compressive force that rapidly

    builds and diminishes as the sinusoidal instantaneous

    magnitude of the fault current changes during each cycle.

    The overall result is the same the insulation develops a

    permanent set that causes a reduction in clamping

    pressure.

    Although there seems to be general agreement

    that fault currents can degrade the short circuit strength

    of a transformer and that their effects are cumulative, the

    exact fault current magnitudes and duration at which

    these effects occur are not clear [2], [5], [6], [7].

    3.3. Short Term Effects

    In the long term, insulation aging and the fault forces will

    cause a decrease in clamping pressure. In the short term,

    however, it is possible for the insulation to expand,

    causing a temporary increase in clamping pressure.

    Often, the same factor that accelerates aging over the

    long term causes a short-term benefit.

    Prevost [4] has shown that the thermal

    coefficient of expansion for cellulose is roughly three

    times higher than for the conductor in the winding and

    the steel in the clamping system. The thermal coefficient

    of expansion for the conductor and the steel is roughly the

    same. High temperatures, therefore, cause the insulation

    to expand more than the conductor and the steel,

    increasing the clamping pressure. Because of this effect,

    Prevost believes that transformers are less likely to fail

    due to faults during periods of high loading as opposed to

    periods of lighter loading.

    Prevost has also shown that moisture causes the

    cellulose to swell. Again, this causes the expansion of the

    insulation, increasing clamping pressure. However,

    moisture also acts as a catalyst in the aging process. As

    the insulation decomposes, it releases moisture into the

    transformer. In general, the aging process releases more

    moisture than consumed so that there is a net increase in

    the amount of moisture. In terms of the clamping

    pressure, Prevost is uncertain which process dominates

    the increase in pressure due to more water absorption by

    the insulation or the decrease in pressure due to the

    increased aging rate.

    29

  • 3.4. Impact of a Neutral Grounding Reactor

    From the discussion above, it should be clear that several

    factors influence the short circuit strength of the

    transformer once it enters service. While it is possible to

    have a short term increase in the short circuit strength,

    over the long haul the short circuit strength of the

    transformer will decrease. As it decreases, a fault that

    might have been successfully survived previously may

    now be severe enough to result in a failure. To extend the

    transformers life, its short circuit strength must be

    maintained at a higher level for a longer period of time or

    the fault forces it is subjected to must be reduced.

    The NGR accomplishes both of these. The

    erosion of short circuit strength slows since the NGR

    reduces the ground through fault forces to much less than

    they would be otherwise. In addition, the likelihood of a

    failure from any given ground through fault is decreased

    since the short circuit strength of the transformer need

    not be as high to prevent a failure. Although the NGR

    only significantly affects line to ground faults, these faults

    represent approximately 70% of the all the faults the

    transformer will see [8]. Thus, the NGR offers an

    attractive way to decrease the failure rate of transformers.

    4. THE NGR AND THE DISTRIBUTION SYSTEM

    While the NGRs impedance can be beneficial in

    extending transformer life expectancy, it also has

    repercussions on the distribution system. Grounding the

    power transformer through a reactor causes two main

    effects - it increases the neutral shift produced by current

    flowing through the system ground and it reduces the

    ground fault current magnitude. The impact of each of

    these issues on CenterPoint Energys distribution system

    is discussed below.

    4.1. Voltage Regulation

    Unbalanced loading on the phases of the distribution

    system will cause a current to flow in the neutral. With

    the installation of a NGR, this unbalanced current will

    now flow through the NGRs impedance. The voltage

    developed across the NGR will cause the neutral point

    between the phases to shift. Depending on the direction

    the neutral shifts which is governed by the angle of the

    neutral current each line to neutral voltage will be

    higher or lower than before. Note that the neutral current

    that flows through the NGR is the result of the

    unbalanced loading on all the feeders tied to that

    transformer.

    CenterPoint Energy regulates the distribution

    voltage by monitoring the C phase voltage at the

    secondary side of the transformer. The transformers

    Load Tap Changer adjusts the taps to keep this voltage

    within a specified bandwidth. This system will regulate

    the voltage adequately for all three phases as long as the

    phases remain reasonably balanced. This will continue to

    be true as long as the magnitude of the transformers

    neutral current remains low. However, at higher

    magnitudes, the neutral shift may become significant.

    High neutral currents could result in high or low voltages

    on A and/or B phases the tap changer would adjust to

    keep the C phase voltage within the specified bandwidth.

    Despite the possibility of a problem, the

    likelihood of it occurring appears quite low. Monitors

    installed as part of CenterPoint Energys Westfield

    Project, discussed later in this paper, recorded no

    instances of high or low voltage that were attributable to

    the NGR.

    If a problem arises, only certain types of

    customers will be affected. Single-phase customers on A

    or B phase may see a high or low voltage condition.

    Three-phase customers served from a transformer bank

    with a closed delta connection on the high side will not

    see any problems, because the line to line voltages on the

    distribution system will not be affected by a neutral shift.

    Three-phase customers served from a grounded wye

    connection on the high side may experience a voltage

    problem with single-phase loads, but three-phase loads

    would not be affected. Customers served from an open

    wye-open delta bank could experience problems with both

    their single-phase and three-phase equipment.

    There are several possible solutions if a high or

    low voltage condition arises. The best solution is to

    balance the loading on the transformer. Alternately, the

    NGR could be purchased with a middle tap position so

    that its impedance could be reduced. This, in turn,

    reduces its voltage drop by half for a given amount of

    neutral current. Another possibility would be to simply

    bypass the NGR. This would completely eliminate any

    voltage drop associated with its impedance. The danger

    in not balancing the circuit is that both the alternate

    solutions reduce or eliminate the benefits of the NGR.

    Nonetheless, they provide a way to address a voltage

    regulation issue associated with the NGR quickly.

    4.2. Increased Temporary Overvoltage on Unfaulted

    Phases

    Just as unbalanced current can cause a neutral shift, so

    too does ground fault current. In this case, the neutral

    shift causes the potential between the system ground and

    the unfaulted phases to rise. The result is a Temporary

    Overvoltage (TOV) that lasts until the ground fault is

    cleared. The addition of the NGR's impedance increases

    30

  • the magnitude of the neutral shift, and thus the TOV on

    the unfaulted phases.

    An example may help clarify how the TOV has

    risen if the ground fault current has been reduced.

    Assume a line to ground fault occurs on Phase A of a

    12.47kV distribution feeder. With no NGR installed at

    the substation, assume that the single line to ground fault

    current is 3600/-75 Amps. Now, assume the ground

    impedance at the fault location is 0.5/75 ohms. The

    voltage drop in the ground is 3600/-75 Amps * 0.5/-75

    ohms = 1800/0 volts. The voltage from Phase B to the

    ground is the system voltage minus the voltage drop in

    the ground, which is 7200/120 1800/0 = 8248/131.

    The Phase B to ground voltage has risen from 7200 volts

    to 8248 volts. A similar result would be calculated for the

    Phase C to ground voltage. The voltage drop in the

    ground shifts the neutral away from Phases B and C,

    increasing the voltage difference (TOV) between them.

    Now add an NGR of 0.4 ohms at the

    transformer. The single line to ground fault current for

    the same fault at the same location becomes 3000/-80

    Amps. The fault current has been reduced. However, the

    ground impedance has increased to 0.9/80 ohms. The

    voltage drop through the ground is 3000/-80 Amps *

    0.9/80 ohms = 2700/0 volts. The Phase B to ground

    voltage is now 7200/120 2700/0 = 8863/135. The

    voltage has risen from 8248 volts to 8863 volts. The

    NGR has reduced the current, but increased the neutral

    shift.

    For a solidly grounded, 4-wire, three-phase

    distribution system designed with open-wire conductors,

    the largest expected TOV generally has been considered

    to be 1.20 per unit (pu)[9]. Since voltage regulation

    allows the nominal system voltage to be 1.05, the

    maximum expected TOV becomes 1.25pu (1.20*1.05, but

    often rounded to 1.25). However, the actual maximum

    TOV experienced on a feeder may be higher or lower

    than this theoretical limit. Computer studies have shown

    that a number of factors can impact the TOV the

    impedance of the system neutral conductor, the number

    and footing resistance of the pole grounds, and the

    impedance of the substation grounding mat all have an

    impact on the TOV [9], [10]. It may be possible to see

    TOVs of 1.30pu or more in practice without installing an

    NGR [9].

    The addition of an NGR will cause these values

    to rise. CenterPoint Energy modeled a typical 12kV and

    35kV distribution feeder in Microsoft Excel and ATP

    (Alternative Transient Program) to determine what the

    maximum expected TOV would be. The simulations

    assumed the largest possible NGR that allowed the system

    to remain effectively grounded. The maximum TOV in

    the simulations - 1.35pu - occurred on the 12kV feeder

    with a single line to ground fault.

    Any increase in the TOV must be considered in

    light of the arrestors TOV withstand capabilities. Most

    faults on the distribution system will last less than 10

    cycles. Some faults could last much longer than this,

    especially if a large fuse or a breaker operating on a CO-9

    curve clears a low magnitude fault. However, a low

    magnitude fault implies a lower TOV since the current

    flowing through the system ground is less. For the

    arrestors used by CenterPoint Energy, the TOV withstand

    at 10 cycles for prior duty is approximately 1.6pu of the

    Maximum Continuous Operating Voltage (MCOV) for

    distribution class arrestors and 1.47pu of the MCOV for

    riser pole arrestors. For faults lasting 1 second, the TOV

    withstand is approximately 1.54pu and 1.41pu of the

    MCOV, respectively. Since the worst case expected TOV

    was 1.35pu, the increase in TOV levels caused by an

    NGR should not be above the withstand levels of the

    arrestors.

    A second concern related to the elevated TOV is

    its impact on customer equipment. Direct information on

    the TOV withstand capabilities of customer equipment is

    limited. In 1990, Northeast Utilities conducted a study in

    which three types of typical consumer electronic devices

    digital clocks, microwaves, and VCRs were subjected

    to various power system disturbances to gauge their

    response [11]. Ten devices of each type were tested. One

    of the tests subjected the devices to a TOV of 1.22pu for

    periods ranging from 0.5 to 120 cycles. The authors

    noted that none of the devices showed any adverse effects

    from the TOV testing. The study did not consider any

    potential accelerated aging effects.

    In lieu of direct evidence, utility operating

    experience can provide an excellent guide to the implied

    TOV withstand abilities of customer equipment. A

    customers equipment should be able to withstand the

    maximum TOV inherent in the utility systems used in the

    United States. Previously it was noted that a solidly

    grounded, 4-wire, three-phase distribution system with

    open-wire conductors has a maximum expected TOV of

    1.25pu. However, distribution systems utilizing spacer-

    cable designs have a maximum expected TOV of 1.50pu

    [12]. In addition, customer equipment installed on

    ungrounded secondary systems (i.e. 480volt 3-wire) must

    be capable of handling 1.82pu (1.05*1.73) during ground

    faults until the fault is located and removed [12], [13].

    This implies that, at a minimum, single-phase customer

    equipment should be able to withstand a TOV of 1.50pu

    while three-phase customer equipment should be able to

    withstand a TOV of 1.82pu. This suggests that the increased TOV should not have a significant impact on

    customer equipment.

    31

  • 4.3. Voltage Sags

    When the neutral shifts during a ground fault, it not only

    increases the potential difference between the system

    ground and the unfaulted phases, it also decreases the

    potential difference between the system ground and the

    faulted phase. The result is a voltage sag on the faulted

    phase. Not surprisingly, the NGRs impedance increases

    the depth of the voltage sag experienced by customers

    along the faulted phase.

    Its depth and its duration typically characterize

    the impact of a voltage sag. With an NGR, the depth of

    the voltage sags seen by customers both on the faulted

    feeder and those served by adjacent feeders from the same

    transformer will increase. The NGRs impedance

    essentially appears as an increase in the transformers

    impedance. The combined transformer/NGR impedance

    becomes a larger percentage of the total impedance of the

    fault path, causing a larger percentage of the voltage drop

    to appear across the transformer. The effect of the NGR

    will be determined by its size relative to the total

    impedance of the fault path. The duration of a voltage sag

    could also be impacted by the NGR since most protective

    devices operate slower for lower magnitude fault currents.

    It is important to gauge these changes in the

    context of the actual faults seen on the feeders. For

    instance, data collected by CenterPoint Energy about

    faults on its distribution feeders shows that approximately

    70% of all faults lasted 3 cycles or less and approximately

    17% of all faults lasted more than 11 cycles. Faults

    lasting 3 cycles or less are either self-cleared or cleared by

    a fuse. The authors believe the duration of self-cleared

    faults will not be affected by an NGR. For ground faults

    cleared by fuses, the NGR will increase the operating

    time. However, since these fuses are operating so quickly,

    the NGR is likely to add only a cycle or two to the

    clearing time. Faults lasting more than 11 cycles are

    almost always cleared by the breaker. For customers on

    the faulted feeder, the initial voltage sag associated with a

    fault will be followed by a complete outage when the

    breaker opens. For customers served by the same

    transformer but on a separate feeder from the faulted

    feeder, the duration of the initial voltage sag will remain

    the same. This occurs because the breakers first

    operation is caused either by an instantaneous relay, not a

    time overcurrent relay. Data collected by CenterPoint

    Energy has shown that faults causing the breaker to

    operate are cleared 70% of the time by the first breaker

    operation.

    This data suggests that the increased duration of

    the voltage sags is unlikely to be an issue. Whether the

    change in the depth of the voltage sags causes them to

    move from an acceptable level to the customer to an

    unacceptable level will depend largely on the type of

    customers undergoing them. In the experience of the

    authors, voltage sags are typically a concern only for

    industrial customers and then only when these customers

    are using sensitive computerized equipment. Nonetheless,

    the general effect of an NGR will be to deepen and

    prolong the voltage sags seen by the customer.

    4.4. Protective Device Coordination

    While the neutral shift impacts voltage regulation, TOV,

    and voltage sags, it is the reduction in ground fault

    current magnitude that affects the coordination of

    protective devices on the distribution system. Since

    CenterPoint Energy uses a fuse-blowing scheme for all its

    distribution feeders, fuse to fuse coordination will

    improve. The improved fuse to fuse coordination will

    decrease the number of customers out of power during a

    fault, improving SAIFI and CAIDI numbers. Conversely,

    the coordination between a breaker or recloser and a fuse

    will worsen, increasing the number of circuit operations

    and reducing customer satisfaction.

    Improved fuse to fuse coordination occurs

    because of the way CenterPoint Energy sizes its fuses.

    For transformer banks and the terminal poles for URD

    (Underground Residential) loops, fuses are selected based

    on the KVA of the transformer(s) to be protected - fault

    current is not considered. These fuses are unaffected by

    an NGR. However, for parent fuses - upstream fuses - the

    available fault current is often the deciding factor in

    determining what size the fuse should be. Although it is

    possible for parent fuses protecting a two phase or three

    phase line to see a line to line fault, fuses are sized to

    coordinate for line to ground faults since these are the

    most common. Parent fuses are sized to allow a child

    fuse - a downstream fuse - time to operate in response to a

    fault before the parent fuse operates. This minimizes the

    number of customers out for a fault behind a child fuse.

    Coordinating the parent and child fuses in this

    manner is dependent on the speed at which the fuses

    operate. Fuses operate very quickly for high magnitude

    faults and much slower for low magnitude faults. At

    higher fault currents, coordination between fuses becomes

    very difficult since adequate time separation between the

    fuse operations cannot be insured. Both the parent and

    the child fuse may operate for a fault behind a child fuse.

    Thus, the reduction in ground fault currents afforded by

    the NGR makes it more likely that coordination between

    the parent and child fuses can be obtained.

    This same effect is what worsens coordination

    with reclosers and breakers. CenterPoint Energy

    instantaneously trips the feeder breaker for any fault

    above 7200 Amps. On the first trip for a fault below

    7200 Amps, the instantaneous trip is delayed, typically

    for 10 cycles. This same general scheme is used for

    32

  • reclosers. The fuse must coordinate with this time-

    delayed trip if an unnecessary operation is to be avoided.

    With the NGR, the lower fault current magnitudes will

    cause the fuses to take longer to operate. Thus, it

    becomes more likely that the breaker or recloser will trip

    for a fault behind a fuse.

    Even without an NGR, it is possible for the

    breaker or recloser to trip for a fault behind a fuse. With

    the NGR, the point at which the breaker and fuse begin to

    mis-coordinate moves closer to the substation because the

    ground fault currents have been reduced along the feeder

    (See Figure 1). More fuses will now fall into the mis-

    coordination area, potentially increasing the number of

    circuit operations. For example, assume a 12 kV feeder

    where the breaker and a certain size fuse do not

    coordinate for faults with a magnitude of 2700 Amps or

    less. If the fuse is installed at a location where the

    ground fault magnitude is 2900 Amps, then coordination

    would exist and a breaker operation is avoided (assumes

    no fault impedance). Now a 0.4 ohm NGR is added to

    the circuit. The impedance at the fuse location is now

    (7200/2900) + 0.4 ohms = 2.88 ohms. The fault current

    has been reduced to 7200/2.88 = 2500 Amps. A

    coordination problem now exists.

    Approximately 99% of the fuses on CenterPoint

    Energys system are 100 Amp fuses or smaller, with T

    and K links being the dominant types. Assuming the

    time delayed instantaneous trip and a fuse can be

    coordinated with a separation of 6 cycles [14], the typical

    10-cycle delay provides coordination for fault magnitudes

    of 4400 Amps and greater for a 100T fuse and 3400

    Amps and greater for an 80T fuse. Increasing the time

    delay to 20 cycles would allow coordination to extend to

    2200 Amps for a 100T and 1600 Amps for an 80T fuse.

    Extending the time delay is a controversial subject within

    CenterPoint Energy because of the potential for fault

    duration to be damaging to the transformer. However,

    with modern microprocessor relays, it is possible to

    implement a stair-step time delay. Essentially, the

    time delay can be changed depending on the magnitude

    of the fault current. For example, a 12-cycle delay

    provides coordination for fault magnitudes of 3400 Amps

    and greater for a 100T. Thus, the time delay could be set

    so that it would be 10 cycles for faults between 7200

    Amps and 4400 Amps, 12 cycles for faults between 4400

    Amps and 3400 Amps, and 20 cycles for faults below

    3400 Amps. These times would allow coordination of the

    breaker with a 100T fuse down to 2200 Amps, helping to

    alleviate the coordination issues presented by the addition

    of the NGR.

    4.5. Ground Fault Protection

    In addition to affecting coordination, the reduced ground

    fault current magnitude also plays into how well the

    substation relays will protect for a ground fault. The

    relays at the substation are set so that the substation

    breaker can protect for ground faults at the end of the

    feeder. If the available ground fault current on the feeder

    becomes too low, the relays will not be able to detect that

    a ground fault has occurred and will not clear the fault.

    To avoid this, either the relay settings have to be reduced

    or a recloser must be installed. Since the NGR lowers the

    available ground fault current, it is important to consider

    if either of these actions will have to be taken.

    CenterPoint Energys standard relaying practice

    assumes a ground fault with an impedance of 10 ohms

    when setting neutral relays. Currently, CenterPoint

    Energys standard is to set the feeder neutral relays to

    pickup at 480 Amps. At 12kV, this is equivalent to 5

    ohms of feeder impedance: 7200/480 = 15 ohms 10

    ohms for the impedance of the fault. This limits the

    available single-phase fault current to 1440 Amps

    (7200/5). In other words, a recloser would be called for

    whenever the available ground fault current on the feeder

    main is 1440 Amps or less. However, it is also possible

    to reduce the neutral relay setting to protect for lower

    currents as well.

    The requirement to protect for ground faults at

    the end of the feeder does not change with the installation

    of an NGR. However, the location of a given available

    ground fault current does change it moves closer to the

    substation (See Figure 1). This means the relay cannot

    protect as far out along a feeder as before. For example,

    F ig . 1 . G ro u n d F a u l t C u r r e n t s W it h a n d W i th o u t a n N G R f o r a n I d e n t i c a l F e e d e r

    D i s t a n c e

    1 2 k V S u b s ta ti o n

    W i th o u t N G R

    W i th 0 .4 o h m N G R

    I fc = 2 9 0 0 A I fc = 2 5 0 0 A

    I fc = 2 1 9 5 AI fc = 2 5 0 0 A

    N o te : T h e N G R c a u s e s a g i v e n f a u lt

    c u rr e n t m a g n i tu d e t o m o v e c l o s e r t o th e

    s u b s t a t io n

    33

  • assume an NGR with an impedance of 0.4 ohms is

    installed. As shown above, the breaker can protect for

    faults along the feeder as long as the available ground

    fault current is 1440 Amps or greater. This point now

    occurs when the feeders own impedance is 4.6 ohms (5

    ohms 0.4 ohms). The location where 1440 Amps

    occurs has moved closer to the substation.

    A similar analysis can be performed at 35 kV.

    The effect of the NGR is negligible at this voltage because

    the relay can already protect out to an available ground

    fault current of 630 Amps or greater. It is extremely rare

    to find an available ground fault current of this

    magnitude on a feeder.

    In general, the impact of the NGR is likely to be

    small. It will only be of consequence at 12 kV and even

    then only if the feeder is unusually long or small wire is

    being used. In either of these cases, the standard

    solutions of installing a recloser or lowering the neutral

    relay setting can be used.

    4.6. Standard Feeder Protection Scheme

    Although it is not immediately obvious, the reduction in

    ground fault current magnitude also impacts CenterPoint

    Energys standard feeder protection scheme. In the

    standard scheme, an instantaneous trip for both the phase

    and neutral relays is set at 7200 Amps. While the phase

    setting remains important for line to line and three phase

    faults, the reduction in the available ground fault current

    caused by an NGR will prevent the neutral relay from

    ever seeing a fault above 7200 Amps. Thus, the

    instantaneous neutral setting is no longer useful with this

    setting.

    As an example, consider what happens to the

    ground fault current on a 12kV feeder when a 0.4 ohm

    NGR is added to a 30/40/50 MVA transformer. Assume

    a very high available single line to ground fault current at

    the substation bus prior to installing an NGR 11,500

    Amps. With the NGR, the available ground fault current

    at the substation bus falls to 7020 Amps. As this example

    demonstrates, even for substations at very strong busses

    (high available fault currents), the NGR will reduce the

    fault current below the 7200 Amp setting. Similar results

    occur at 35kV.

    The question arises as to whether the setting

    should be revised and, if so, to what value. First,

    consider the physical significance of the neutral

    instantaneous setting on the feeder. At 35kV, the

    distance to 7200 Amps is approximately 5200 feet while

    at 12kV it is approximately 2000 feet. If we assume zero

    fault impedance, then any ground fault that occurred on

    this portion of the feeder would be removed as quickly as

    possible. Faults on the feeder beyond this point - having

    a maximum magnitude of 7199 Amps or less would be

    removed only after some time delay. On the first trip,

    this time delay is intentionally added to the instantaneous

    trip. On all reclosing attempts, it is a function of the

    time-overcurrent relay since the instantaneous element is

    disabled.

    If an NGR of 0.4 ohms is added to this 12KV

    transformer, the available ground fault current at the

    substation bus will be 7020 Amps and 5050 Amps 2000

    feet out on the feeder. Ground faults that occur within

    this same region of the feeder will now be removed only

    after some time delay. Since the fault current magnitude

    has been reduced, this may be entirely acceptable. In this

    case, the relay setting can be left at 7200 Amps.

    However, the setting could also be reduced to maintain

    the same zone of protection out on the feeder. Here, the

    setting would be lowered to 4800 Amps so that any fault

    within the first 2000 feet at 12 kV and 5200 feet at 35 kV

    causes an instantaneous trip. This option provides the

    same level of protection for both the feeder and the

    transformer that is currently in place.

    Note that having one instantaneous neutral

    setting for transformers with NGRs versus another for

    transformers without NGRs could present a new problem.

    Temporary switching could move a feeder from a

    substation transformer with an NGR to one without an

    NGR. The lowered instantaneous neutral setting will

    cause the feeder to experience more circuit operations

    from faults behind fuses. This problem could be avoided

    if all the transformers at a given secondary voltage had an

    NGR installed. Thus, under this option, it appears that

    the neutral instantaneous setting should remain

    unchanged until all transformers at 12kV or 35kV at a

    substation have NGRs added to them. Once this occurs,

    concerns about temporary switching would no longer

    exist and the setting could be reduced to further protect

    the transformer.

    CenterPoint Energy has decided to standardize

    on the lowered neutral instantaneous setting for feeders

    served from transformers with NGRs. This change will

    be implemented only after all transformers with the same

    secondary voltage at a substation have NGRs installed.

    5. WESTFIELD PROJECT

    CenterPoint Energy has been conducting a pilot project

    for NGRs at its Westfield substation for approximately 8

    years. NGRs were installed at each of the four

    transformers at Westfield. Two of these transformers are

    132kV 12.47kV, delta wye grounded, 25/33/42/47

    MVA units while the other two are 138kV 34.5 kV,

    delta wye grounded, 50/60/83/93 MVA units. All

    transformers are served at 138kV, with the 12.47kV units

    tapped to 138kV on the high side. The NGRs installed

    on the 12kV transformers were set at 0.4 ohms of

    34

  • impedance while those on the 35kV transformers were set

    at 1.4 ohms of impedance. This impedance provides the

    maximum reduction possible while still maintaining an

    effectively grounded system.

    In 2001, monitors were installed along two

    distribution feeders to record the TOVs experienced

    during ground faults. The goal of the monitoring project

    was to validate the expected maximum TOV results

    modeled by CenterPoint Energy. However, the project

    also helped to address the issue of voltage regulation.

    Data was collected from July 2001 through August 2003.

    5.1. Monitoring Project Setup

    The two feeders selected for the project were Westfield 41

    and Westfield 02 - a 35kV and a 12kV feeder. Four

    monitors were deployed along each feeder. The monitors

    were installed on the low side of a customers distribution

    transformer at each of the selected locations, either

    directly on the secondary conductors or at the meter.

    Originally, a combination of monitors was used

    Five Telog Linecorder (LC) 800, one Power Monitors

    Incorporated (PMI) VI/600 and two PMI VS-1S. The

    Telog LC 800 and the PMI VI/600 record three phase

    voltages and currents; the PMI VS-1S records single-

    phase voltages and currents. During the project, the

    Telog units failed frequently, producing gaps in the data.

    All the Telog units were replaced with PMI IV/600s after

    April 2002.

    On 35kV circuits, the most common transformer

    connection for a three-phase customer is grounded wye-

    grounded wye. This type of connection was preferable for

    the project since the voltages measured line to neutral on

    the customers side of the transformer are analogous to

    the line to neutral voltages on the feeder. On Westfield

    41, all four of the monitoring locations used this

    connection.

    On 12kV circuits, different types of transformer

    connections are common. This proved to be a challenge

    as suitable grounded wye - grounded wye locations could

    not be found on Westfield 02. Instead, an alternate

    method of getting analogous readings to the feeder line to

    neutral voltages was found. Two customer locations were

    combined to cover all three phases. One location was

    served by an open wye-open delta transformer bank; the

    other by a single-phase transformer. All three of the

    transformers were served line to neutral on the high side

    from different phases. In the case of the open wye-open

    delta bank, reading the low side line to line voltages

    provides analogous readings to the high side line to

    neutral readings. Low side AB is analogous to high side

    AN and low side BC is analogous to high side BN. Low

    side CA is the ghost phase the vector sum of low side

    AB and BC and is analogous to the vector sum of high

    side AN and BN. This two-customer combination was

    used twice to provide two different points on the feeder

    where all three voltages could be recorded.

    Both feeders serve predominantly residential and

    commercial customers, with some light industrial. The

    12kV feeder is 4.1 miles long. The two monitoring

    locations were 1.25 and 2.5 miles from the substation.

    The 35kV feeder is 4.6 miles long. After 1.8 miles, the

    feeder branches into two parts that each having about the

    same length. The four monitoring locations for this

    feeder were located 1.3, 2.4, 3.4, and 3.5 miles from the

    substation. The last two locations on the 35kV feeder

    were on different branches. All distances are calculated

    by following the path of the actual conductor.

    5.2. Results

    The data in the following figures represent the recorded

    voltage events. A voltage event was defined as a change

    in voltage of +/-10% of the nominal secondary voltage at

    that location. Only one location had to report a +/-10%

    change in voltage for the event to be listed the same

    event may not have caused as great a rise or dip at the

    other monitored locations. Where possible, events were

    confirmed as being seen at other locations before being

    included in this list. If the other monitors did not record

    a voltage change, then the event was considered

    unconfirmed and not included. However, in a few

    instances, only one monitor was operating. These events

    are included in the figures.

    020406080

    100120140160180200220240

    L-G L-L 2L-G L-L-L All

    Fault Type

    No

    . o

    f F

    ault

    s

    Fig. 2 Distribution of Recorded Fault Types

    Figure 2 shows the types of fault recorded by the

    monitors. The results of both the 12kV and 35kV feeders

    are shown combined. Line to ground faults account for

    58% of all faults while line to line faults account for 32%.

    35

  • The unusually high number of line to line faults occurred

    due to faults on the transmission system. Because the

    power transformers are connected delta on the high side,

    line to ground faults on the transmission system appear as

    line to line faults on the secondary side. When

    transmission faults are eliminated, the breakdown of fault

    types generally matches the expected distribution. Figure

    3 shows the distribution with transmission system faults

    eliminated. In Figure 3, the breakdown of faults is 71%

    single line to ground and 17% line to line.

    020

    406080

    100

    120140160

    180200

    L-G L-L 2L-G L-L-L All

    Fault Type

    No

    . o

    f F

    ault

    s

    Fig. 3 Distribution of Recorded Fault Types, Excluding

    Transmission Events

    Single line to ground faults are generally

    expected to account for 70% of all faults while line to line

    faults are generally expected to account for 15% of all

    faults [10]. Note that seventeen of the faults recorded

    changed type before being cleared. Their initial fault type

    categorizes these faults.

    0

    2

    4

    6

    8

    10

    12

    14

    16

    1.30

    Maximum TOV in p u of No minal Seco ndary Vo ltage

    (12 kV Event s )

    No. o

    f E

    ven

    ts

    Fig. 4 Distribution of Maximum TOVs Recorded for the

    12kV Feeder

    0

    5

    10

    15

    20

    25

    30

    35

    40

    1.30

    M aximum TOV in pu o f No minal Sec o nda ry Vo ltage

    (35kV Events )

    No

    . o

    f ev

    ents

    Fig. 5 Distribution of Maximum TOVs Recorded for the

    35kV Feeder

    Figures 4 and 5 show the highest TOV recorded on any

    phase by any of the monitors for each event on the 12kV

    and the 35kV feeders, respectively. The TOV in both

    figures is expressed in per unit of nominal secondary

    voltage. There were a total of 35 events on the 12kV

    feeder and 101 events on the 35kV feeder recorded. The

    35kV feeder results include one event associated with a

    transmission fault while the 12kV events do not include

    one line to ground fault for which no TOV was recorded.

    Of the 136 events, approximately 15% caused a TOV of

    1.20pu or greater at one of the monitoring locations. The

    highest recorded TOVs were 1.26pu on the 35kV feeder

    and 1.24pu on 12kV feeder.

    It is important to note that it would be virtually

    impossible to record the maximum TOV that can occur

    on a feeder. For any given fault, the maximum TOV

    occurs at the fault location. This maximum TOV value

    will vary depending on the point along the feeder where

    the fault occurs. Thus, directly determining the

    maximum TOV capable of being experienced on the

    feeder would require installing a monitor at and applying

    a fault to every point on the feeder. Clearly, this is not

    practical.

    Instead, the project sought to gather indirect

    evidence. The largest TOV recorded at any location

    would indicate that the maximum TOV was this value or

    greater. The more faults recorded by the monitors, the

    more likely that the maximum value recorded would be

    closer to the actual maximum value. In addition, one can

    form an opinion as to the frequency and magnitude of the

    voltage events seen on these feeders. Since the recorded

    TOV values are substantially below the predicted value of

    1.35pu, the authors believe it is very likely that the

    1.35pu value represents a reasonable upper limit for the

    TOV.

    36

  • 02468

    101214

    0 - 3 3.0 1 -

    6

    6.01 -

    9

    9 .01 -

    11

    11.0 1

    - 15

    15.01

    - 20

    2 0.0 1

    - 25

    2 5.01

    - 3 0

    30 .01

    - 4 0

    4 0.0 1

    - 50

    >50

    Line to Ground Fault Duration in Cycles

    (12kV Events)

    No

    . o

    f E

    ve

    nts

    Fig. 6 Distribution of Line to Ground Fault Durations

    for the 12kV Feeder

    010

    2030405060

    0 - 3 3.0 1 -

    6

    6.01 -

    9

    9 .01 -

    11

    11.0 1

    - 15

    15.01

    - 20

    2 0.0 1

    - 25

    2 5.01

    - 3 0

    30 .01

    - 4 0

    4 0.0 1

    - 50

    >50

    Line to Ground Fault Duration in Cycles

    (35kV Feeder)

    No

    . o

    f E

    ve

    nts

    Fig. 7 Distribution of Line to Ground Fault Durations

    for the 35kV Feeder

    Figures 6 and 7 show the duration of the 12kV

    and 35kV line to ground events, respectively. The data in

    these figures excludes 12 events at 35kV and 2 events at

    12kV in which fault duration did not get recorded. It also

    excludes 14 events at 35kV and 2 events at 12kV that

    changed fault type before the fault was cleared. As

    previously mentioned, a separate study by CenterPoint

    Energy showed that at both 12kV and 35kV,

    approximately 70% of all faults last less than 3 cycles and

    approximately 17% of all faults last more than 11 cycles.

    This includes all fault types; however, since line to

    ground faults account for the majority of the data, a valid

    comparison can be made. At 12kV, fault duration was

    noticeably longer than would typically be expected while

    at 35kV the results were in line with the expected data.

    Only 42% of the events on the 12kV feeder lasted 3

    cycles or less while 25% lasted longer than 11 cycles. On

    the 35kV feeder, 73% of the events lasted 3 cycles or less

    and 14% lasted 11 cycles or more. This suggests the

    NGRs impedance does not significantly increase fault

    duration at 35kV, but does at 12kV. It is unclear to the

    authors why such a difference would exist.

    Although not originally a purpose of the

    monitoring project, voltage regulation data was collected

    by each of the monitors. This data was reviewed to see if

    a voltage regulation problem had occurred on the feeders.

    Each monitor recorded an average voltage for a user-

    defined period of time. This was generally set as 1

    minute, but other times were inadvertently used as well

    and are noted in the tables. For each data point, the

    phase with the highest or lowest average voltage was

    compared to +/-5% of the nominal secondary voltage.

    These limits were chosen based on the Range A limits in

    ANSI C84.1 Voltage Ratings for Electric Power Systems

    and Equipment (60Hz) [15]. CenterPoint Energy is

    required to provide its customers service in accordance

    with this standard.

    Table I shows the data for the 35kV feeder and

    Table II shows the data for the 12kV feeder. Although

    efforts were made to keep all monitors operating

    simultaneously, this wasnt always possible. Thus, the

    total number of minutes is different for each monitor.

    In Table I, it is clear that the average voltage

    rarely moved above or below +/-5% of nominal voltage.

    The results are consistent with providing service in

    accordance with the standard - no regulation problems

    occurred. The 156 minutes of high voltage recorded at

    Location B all occurred on two days, with the highest

    average voltage reaching 107% of nominal voltage.

    Voltage on all three phases was near the 105% voltage

    limit. Since all the phases moved together, this was not

    the result of installing the NGR.

    37

  • In Table II, Location E and G are the open delta

    transformer banks and Locations F and H are the single-

    phase transformer banks. Location E and F combined

    give all three phases and Locations G and H combined

    give all three phases. Note that the single-phase monitors

    are on different phases.

    Of the 857 low voltage data points occurring at

    Location E, 823 of them occurred because of a bad

    connection at this transformer bank. Excluding these

    points, the results for Locations E and F show no voltage

    regulation problems. Location G recorded by far the most

    data points outside the limits. These data points occurred

    almost exclusively during the summer months and are

    attributable to an overloaded transformer bank. Although

    this does indicate a voltage regulation problem, it is not

    from the NGR. Overall, the results show no voltage

    regulation problem associated with the NGR.

    6. CONCLUSION

    The primary driver for installing an NGR is its beneficial

    effect on transformer life expectancy. Most transformer

    failures at CenterPoint Energy are attributed to the stress

    placed on the windings by faults on the distribution

    system. By lowering the magnitude of single line to

    ground faults, which make up 70% of all faults, the NGR

    can greatly diminish these stresses. The transformers

    short circuit strength its ability to withstand the forces

    associated with carrying fault current need not be as

    high to prevent an internal failure. Furthermore, the

    reduction in ground fault current magnitude slows the

    erosion of the transformers short circuit strength. For

    these reasons, the NGR is an attractive method for

    addressing the most common type of transformer failure.

    The increase in the system ground impedance

    caused by an NGR also affects the distribution system.

    The NGRs impedance increases the neutral shift that

    results from unbalanced loading or ground fault currents.

    In addition, it affects protective device coordination,

    ground fault protection, and the standard feeder

    protection scheme by reducing the magnitude of ground

    faults. However, the NGRs impact on each of these

    areas is generally small and manageable.

    The Westfield Project strongly suggests that

    voltage regulation is not significantly impacted by the

    NGR. It also provides support for the modeled maximum

    TOV value of 1.35pu a value that should be acceptable

    for both the lightning arrestors on the system and

    customer owned equipment. Breaker/recloser to fuse

    coordination problems can be handled by using a stair-

    step approach to the time delay of the instantaneous

    element. Ground protection settings may need to be

    lowered slightly, if required to protect the end of the

    feeder. It is true that some aspects of power quality

    such as the deepening and lengthening of voltage sags

    will worsen. Whether this represents a practical problem

    for customers will depend largely on the type of

    equipment the customer owns. The authors of this paper

    believe it will not.

    7. ACKNOWLEDGEMENTS

    The authors of this report wish to acknowledge the many

    individuals who contributed to this report. The High

    Voltage Metering Meter Functions group helped select,

    install, maintain, and download all of the monitoring

    devices installed on the Westfield project. M. Khayat of

    CenterPoint Energy helped build the model used to

    estimate the maximum TOV for 12 kV and 35 kV

    feeders.

    8. REFERENCES

    1. Central Station Engineers of the Westinghouse

    Electric Corporation, ELECTRICAL

    TRANSMISSION AND DISTRIBUTION

    REFERENCE HANDBOOK, 1964. Westinghouse

    Electric Corporation, East Pittsburgh, Pennsylvania,

    4th Ed.

    2. G. Bertagnolli, THE SHORT-CIRCUIT DUTY OF

    POWER TRANSFORMERS, 1996. ABB, Milano,

    Italy, 2nd Ed.

    3. S. Khan, R.W. Brown, PLANNING AND

    PROTECTION IMPLICATIONS OF REDUCED

    FAULT WITHSTAND TIME OF POWER

    TRANSFORMERS, IEEE Transactions on Power

    Delivery, Vol. PWRD-1, No. 4, October 1986.

    4. T.A. Prevost, MAINTAINING SHORT CIRCUIT

    STRENGTH IN TRANSFORMERS, Weidmann-

    ACTI Second Annual Technical Conference 2003.

    5. M. Waters, THE SHORT-CIRCUIT STRENGTH

    OF POWER TRANSFORMERS, 1966.

    MacDonald, London, England.

    38

  • 6. W.J. McNutt, C.J. McMillen, P.Q. Nelson, J.E. Dind,

    TRANSFORMER SHORT-CIRCUIT STRENGTH

    AND STANDARDS A STATE-OF-THE-ART

    PAPER, IEEE Transactions on Power Apparatus

    and Systems, Vol. PAS-94, No. 2, March/April 1975.

    7. IEEE Standard C57.109-1993, IEEE GUIDE FOR

    LIQUID-IMMERSED TRANSFORMER

    THROUGH-FAULT-CURRENT DURATION.

    8. L.M. Faulkenberry, W. Coffer, ELECTRICAL

    POWER DISTRIBUTION AND TRANSMISSION,

    1996. Prentice Hall, Englewood Cliffs, NJ.

    9. M.V. Lat, DETERMINING TEMPORARY

    OVERVOLTAGE LEVELS FOR APPLICATION

    OF METAL OXIDE SURGE ARRESTORS ON

    MULTIGROUNDED DISTRIBUTION SYSTEMS,

    IEEE Transactions on Power Delivery, Vol. 5, No. 2,

    April 1990.

    10. R.T. Manaco, J.J. Burke, A. Myers, THE EFFECT

    OF DISTRIBUTION SYSTEM GROUNDING ON

    MOV SELECTION, IEEE Transactions on Power

    Delivery, Vol. 8, No. 1, January 1993.

    11. L.M. Anderson, K.B. Bowes, THE EFFECTS OF

    POWER-LINE DISTURBANCES ON CONSUMER

    ELECTRONIC EQUIPMENT, IEEE Transactions

    on Power Delivery, Vol. 5, No. 2, April 1990.

    12. IEEE Standard C62.92.4-1991, IEEE GUIDE FOR

    APPLICATION OF NEUTRAL GROUNDING IN

    ELECTRICAL UTILITY SYSTEMS, PART IV-

    DISTRIBUTION.

    13. A. Mansoor, F. Martzloff, THE DILEMMA OF

    SURGE PROTECTION VS. OVERVOLTAGE

    SCENARIOS: IMPLICATIONS FOR LOW-

    VOLTAGE SURGE-PROTECTIVE DEVICES, 8th

    International Conference on Harmonics and Quality

    of Power, Athens, Greece, 1998.

    14. IEEE Standard 242-1986, IEEE RECOMMENDED

    PRACTICE FOR PROTECTION AND

    COORDINATION OF INDUSTRIAL AND

    COMMERCIAL POWER SYSTEMS.

    15. ANSI Standard C84.1-1995, VOLTAGE RATINGS

    FOR ELECTRIC POWER SYSTEMS AND

    EQUIPMENT (60HZ).

    39