Upload
tamann2004
View
214
Download
0
Embed Size (px)
Citation preview
7/27/2019 00871373
1/7
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 1045
Filtering Dispersed Harmonic Sources on DistributionWard Jewell, Senior Member, IEEE, William (Bill) L. Miller, and Tom Casey
AbstractTelephone company customers reported audible
noise in their telephone service. Through measurements, analysis,and simulations, 540 Hz noise was found to be coupling frompower distribution to telephone cables in a shared undergroundright-of-way. The source of the noise was small single-phaseelectronic loads dispersed throughout the power distributionsystem in the area. A passive shunt filter was designed using anexisting capacitor bank. Installation of this filter reduced the noiseto acceptable levels.
Index TermsEarth, grounding, harmonic analysis, passivefilters, power distribution electromagnetic interference, powerfilters, power system harmonics, power system modeling, powersystem simulation, wire communication interference.
I. INTRODUCTION
TELEPHONE customers in a suburban area complained to
the telephone company of noisy telephone service. In one
case the noise interfered with the operation of a PBX system.
Telephone company personnel investigated and found evidence
of noise contribution from the electric power system serving
the area. Electric utility and telephone company engineers then
began working together to find a mutually acceptable solution.
II. TELEPHONE NOISE
Telephone company personnel initially received a call from a
hospital complaining of getting wrong numbers when calls were
placed through their PBX. An excessive common mode voltage,
93 dBrnC at 540 Hz, the ninth harmonic of 60 Hz, was found onthe telephone trunk lines of the analog telephone system serving
the hospital.
For an immediate solution to the hospitals problem noise
chokes were installed on the affected trunks. These reduced the
trunk lines susceptibility to common mode voltage and solved
the hospitals outbound calling problems.
The telephone company then performed a shield investigation
and found an open shield on one telephone cable. The shield
was repaired, reducing the 540 Hz common mode voltage to
84 dBrnC. This is acceptable.
Within a few months, however, calls were again received
from the hospital and from other customers in the area com-
plaining of audible noise when using their telephones. The
540 Hz common mode voltage was measured on the trunk lines
and was again above 90 dBrnC. An inductive survey showed
the telephone systems shielding to be in good condition. The
Manuscript received March 16, 1998; revised November 15, 1999.W. Jewell is with the Power Quality Laboratory, Wichita State University,
Wichita, KS 67260 USA.W. L. Miller is with Southwestern Bell Telephone, Topeka, KS 66603 USA.T. Casey is with Kansas City Power and Light, Kansas City, MO 64141 USA.Publisher Item Identifier S 0885-8977(00)08134-6.
Fig. 1. Power and telephone circuits.
survey found high 540 Hz influence from the power system
along one exposure.
It is common for 540 Hz to be the dominant frequency in in-
terference between telephone and electric power systems, even
though third harmonic, 180 Hz, current has a higher magni-
tude in the power system. The design of the telephone system
makes it more susceptible to inductively-coupled interference at
540 Hz than at 180 Hz. Telephone equipment is has a highpass
filter on the input to reduce its exposure to 60 Hz and low order
harmonics. Loaded telephone cable also has a lowpass filter ef-
fect that reduces these frequencies. The human ear is also non-
linear and is more sensitive to 540 Hz than 180 Hz audible noise.
This is reflected in the C-Message curve [1], which is a productof several elements in the telephone network and the function
of the human ear.
The exposure is shown in Fig. 1. Two 7200/12 470 V
three-phase distribution circuits begin at the utility substation.
For 1.5 miles these circuits share a common underground
right-of-way with telephone cables. Circuit 1 serves residential
loads and the hospital; circuit 2 serves residential loads.
An insulated probe wire 100 feet in length was run along
the ground parallel to and above the underground right-of-way.
The wire was electrically connected at each end to a conducting
metal stake driven into the earth. The current flowing on this
probe wire indicated an earth current of 41 A, with an excessive
contribution at 540 Hz. The spectrum of this current is shown inFig. 2.
The probe wire and stakes were then moved perpendicular
to their original path and to the path of the right-of-way. The
same earth current, 41 A, was measured. This indicated that the
current measured was earth current, which will flow on a probe
wire running any direction. Current in thepowerconductors will
only induce probe wire current when the probe wire is parallel
to the conductors.
Earth current is power system neutral current. In a multi-
grounded neutral distribution system, it is commonfor only 40%
08858977/00$10.00 2000 IEEE
http://-/?-http://-/?-7/27/2019 00871373
2/7
1046 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000
Fig. 2. Earth current spectrum.
of the neutral current to return through the system neutral con-
ductors. The other 60% returns through the earth; these are com-
monly accepted numbers in the telephone industry.
All currents in the power distribution phases, neutral, and
other return paths, contribute to the magnitude of the magnetic
fieldalong thepath of a distribution system. If phase currents are
balanced, the geometry of the phase conductors cancels most of
this magnetic field. If phase currents are unbalanced but all re-
turn current were to flow on the system neutral, geometry could
still cancel the field. However, because much of the return cur-
rent does not flow on the neutral, geometric cancellation is de-
creased and the magnetic field becomes stronger. This magnetic
field links with telephone cables and induces common mode
voltage, or power influence, on them. When power influence
becomes too large, the audible noise on telephone circuits be-
comes unacceptable. In addition, earth current may flow on thegrounded telephone shield, further increasing the noise coupling
with the telephone conductors.
Telephone cable shielding reduces the effect of magnetically-
induced current by conducting a similar current on the shield in
the opposite direction. This shield current reduces the common
mode voltage on the cable. In this case, however, the net 540 Hz
disturbing currentthe current contributing to the distribution
system 540 Hz magnetic fieldwas too great for its effects to
be cancelled by shielding.
Another way to eliminate the interference problem would be
to convert the analog telephone system in the area to a fiber
optic system. This is very expensive, however, and the telephone
company wanted to investigate less expensive options beforetaking this step. The electric utility was contacted for assistance
with the problem.
III. FIELD ANALYSIS
The troubleshooting and mitigation process now turned to lo-
cating the source of the harmonic currents and the path through
which they were entering the earth.
A. Capacitors
Telephone company personnel used a van-mounted loop an-
tenna feeding a spectrum analyzer to search for power factor
TABLE ICIRCUIT 1 FIELD MEASUREMENTS
correction capacitors that might be in series resonance with dis-
tribution line reactance. Series resonant capacitors provide a
low-impedance path to neutral and earth for harmonic currents
at the resonant frequency. Most harmonic current at that fre-
quency on the distribution conductors will return to the neu-
tral/earth return through the resonant capacitor bank. This pro-
duces high harmonic currents in the earth at that point, which
can increase telephone noise.If capacitors are in resonance, harmonic suppression reac-
tors can be installed in the neutrals to change the resonant fre-
quency to one that will not produce high capacitor currents.
Alternately, the capacitor connection to neutral and earth can
simply be opened, breaking the path for harmonic currents to
flow to earth.
The harmonic levels in the distribution conductors are signif-
icantly different on either side of the resonant bank, because
the bank shunts most of the resonant harmonic current from
the lines to neutral and earth. The radiated harmonic energy de-
tected by the loop antenna therefore changes when the antenna
passes a bank in resonance. The loop antenna survey of this dis-
tribution system found no such resonances.
Resonances can also be found by switching capacitor banks
off one at a time while watching the harmonic currents on the
distribution lines. When a bank in resonance is switched off,
harmonic currents will decrease significantly. On these two cir-
cuits, harmonic currents on phase conductors were monitored at
the substation, and telephone noise was monitored at an affected
customer, while capacitors on the system were switched off.
The most significant effects were found when capacitors on
circuit 1 were removed. On this circuit harmonic currents on
the phase conductors and audible telephone noise changed each
time a bank was removed. The recorded values are presented in
Table I. By the time all banks were removed from the two cir-cuits, the telephone noise level was at an acceptable level. These
changes indicate the harmonic currents were traveling to earth
through the capacitors. Capacitors, whether in resonance or not,
provide a lower impedance path to neutral and earth than loads
or transformers because their impedance decreases as frequency
increases. However, no single significant change was measured,
and no significant decrease was measured until all capacitors
were switched off, indicating that no banks were in resonance.
Observation over an extended period indicated that the tele-
phone noise was worse during spring and fall, the utilitys light
load times. This is common in situations where harmonic cur-
rents are conducted to earth through capacitors. Increased load
7/27/2019 00871373
3/7
JEWELL et al.: FILTERING DISPERSED HARMONIC SOURCES 1047
TABLE IITRANSFORMER SATURATION TEST
means decreased resistance in parallel with the capacitor banks.
The lower resistance tends to dampen the tuned circuit of capac-
itor banks and systemreactance. Damping reduces the harmonic
levels.
Y-connected three-phase capacitor banks conduct only
unbalanced currents and zero-sequence currents to neutral and
earth. Balanced positive and negative sequence currents sum to
zero at the Y neutral point. Open fuses in one or two phases
of a three-phase capacitor bank cause severe imbalances in the
currents, and greatly increase the current conducted to earth. Autility line crew checked all capacitors on the circuits for open
fuses; none were found.
B. Harmonic Sources
Customers on the distribution system were evaluated for har-
monic sources. The two circuits involved in this study served
residential loads and the hospital. While hospitals can be signif-
icant harmonic sources [2], this hospital was not drawing sig-
nificant harmonic currents. Its location between the substation
and the exposure between power and phone lines also made it
unlikely to be the cause of noise problems.
Harmonic currents were measured at various places on the
distribution circuits. Harmonic current levels of around 5%
THD were found on the phase conductors at the substation,
with the 540 Hz contribution being less than 0.5%. These are
acceptable levels that usually cause no harmonic problems [3].
No significant sources of harmonic currents were found.
One possible source of harmonics on a distribution system is
saturated transformers. Saturated transformers draw high levels
of exciting current, which is distorted with odd harmonics. Re-
ducing the voltage magnitude will decrease transformer satura-
tion currents.
The tap-changing transformer at the substation was stepped
down from its normal voltage levels. The voltage levels and re-sulting telephone interference levels are shown in Table II. No
significant change was measured, indicating no transformers in
saturation.
C. System Neutral
If the system neutral conductor is open, then the approxi-
mately 40% of the return current it normally carries will flow
through the earth. This significantly increases earth currents and
the resulting telephone noise. Line crews therefore inspected
the underground system neutrals and found them to be in good
condition.
D. Conclusions of Field Analysis
No significant sources of harmonic current were found on the
circuits involved. Harmonic levels were not unusually high on
any of the phase conductors anywhere in the system. The dis-
tribution system was in good condition with no open capacitor
fuses or capacitors in resonance. The conclusion was, then, that
the source of harmonics was the many small single-phase elec-
tronic loads dispersed throughout customers homes in the af-
fected area. This conclusion was tested by developing a model
of the system and simulating the system operation.
IV. MODELING AND SIMULATION
The distribution system of circuit 1, including neutral con-
ductors and earth return, was simulated using techniques similar
to the practices outlined by the IEEE Task Force on Harmonics
Modeling and Simulation [4], [5]. The flow of ninth harmonic
current in the earth was of primary interest in this analysis, so
load flow constraints were not needed. Because of this, time-do-
main analysis was acceptable [4] and the Electromagnetic Tran-sients Program (EMTP) [6], [7] was used.
EMTP software creates and solves the time-based differential
equations describing the circuit being simulated. Outputs are
time-varying voltage, current, and power at any selected points
in the system. Any of these may then be analyzed for harmonic
content using a Fourier transfer algorithm.
A. System Model
The circuit models used in the simulation are shown in
Figs. 35. Three-phase models were used because zero-se-
quence (neutral/earth return) currents were to be calculated;
Figs. 3 and 4 show only one of the three phases. Fig. 3
shows the models for phase conductors, Y-connected power
factor correction capacitors, and connections to neutral and
earth. Fig. 4 shows the model representing lumped linear and
harmonic loads, while Fig. 5 shows the model of the system
neutral.
The utility provided values of phase conductor impedances
used in power flow and short circuit studies. These impedances
were used in this model. They are the reactance and resistances
shown in Fig. 3 between main nodes, such as Substation to 1,
or 3 to 4. Because the model only needed to be accurate at rela-
tively low frequencies, up to about 3000 Hz, the 50th harmonic
of 60 Hz, and because the lines being modeled were very short,
less than 5 miles in length a frequency-dependent model withdistributed parameters was not needed [4].
Power factor correction capacitors are shown in Fig. 3 from
the numbered node to the neutral N nodes, such as 1 to 1N, 2
to 2N, etc. Loads are modeled as lumped equivalents in parallel
with the capacitors.
The load model, shown in Fig. 4, combines a linear resistive
load with a nonlinear single-phase rectifier load. This model
represents the collective effects of a large number of single-
phase rectifiers dispersed throughout the portion of the distri-
bution system between the node to which it is connected and
the next node on the system [8]. It can accurately simulate any
combination of linear load and single-phase rectifier load. The
http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-7/27/2019 00871373
4/7
1048 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000
Fig. 3. Distribution system circuit model.
Fig. 4. Lumped load model.
Fig. 5. System neutral model.
values of linear load resistance, dc load resistance, and rectifier
filter capacitance are calculated from measured current values,
Fig. 6. Capacitors on circuit 1.
including harmonic currents, and from utility load estimates. No
reactance was included in the linear load because it would have
little effect on the relevant simulation results for this system. It
could be included if needed, however.In Fig. 3 the resistance from the neutral N to the system
neutral SN node, for example, 1N to 1SN, represents current
flowing onto the system neutral from the loads and capacitors
at the node. The resistance from the N node to ground repre-
sents current flowing through earth and other return paths. The
current is assumed to split evenly between system neutral and
other paths in this case, so the two resistances are equal.
The system neutral is then modeled as shown in Fig. 5. This
circuit allows the neutral current to be monitored as a simulation
output. Because neutral and other return currents are assumed to
be equal, the neutral current output can also be considered to be
the earth and other return current output.
This is an extremely simplified model of earth current thatassumes the earth current flows in a straight path parallel to the
system neutral conductors. In reality, earth current spreads out
over a wide geographic area as it flows. It will follow theshortest
path, the path of least resistance, to return to its source. Anal-
ysis of earth current usually requires the use of Carsons equa-
tions [9]. However, in this simulation we are concerned with the
earth current that is coupling with the telephone cables in the
same right-of-way as the system neutral and phase conductors.
For this reason, and because the lines are short, and because
only relative values, i.e., increases or reductions in earth current
magnitudes, were needed from the simulation, it was felt that
this simple model would be adequate.
B. Simulation Results
Initial simulations were run to compare the models results
with actual conditions. In each case, simulation results were
compared with measured values of currents and voltages on the
phase conductors under similar conditions.
The first case simulated was with all capacitors energized and
daytime light-load conditions, with normal levels of rectifier
load dispersed throughout the circuit. Following this, capacitors
were removed one at a time, beginning with node 1, and moving
outthrough nodes 24, until allcapacitors were off. Fig. 6 shows
the location of capacitors on circuit 1.
http://-/?-http://-/?-7/27/2019 00871373
5/7
JEWELL et al.: FILTERING DISPERSED HARMONIC SOURCES 1049
TABLE IIISIMULATION BASE CASE RESULTS
TABLE IVSIMULATION RESULTS: OPEN CAPACITOR NEUTRAL
The simulated earth return current and the 540 Hz component
were recorded for each case. The 540 Hz component with all
capacitors energized was equated to the high noise levels mea-
sured at the affectedcustomer forthe same conditions. Thenoise
calculated for the case with all capacitors off was equated to the
acceptable noise levels measured during that condition. These
values were then used in subsequent simulations to judge the
telephone noise levels. Relative noise values, both simulated and
measured, for these firstfive cases arepresented in Table III. The
noise value for the base case, all capacitors energized, is used asthe per unit base, so that noise is presented as 1.0.
While the increased earth current as banks 13 are removed
does not agree with the measured values, the simulation results
do indicate, in agreement with field measurements, that when
all capacitors are off, 540 Hz noise drops significantly.
These simulation results supported the conclusion that the
telephone noise was caused by small, dispersed single-phase
electronic loads throughout the distribution system, especially
on circuit 1.
In the next series of simulations the capacitors were ener-
gized, but the neutral point on each bank was disconnected from
the system neutral and earth. This was accomplished in the sim-
ulation by removing the connection from the lower end of thecapacitor to the neutral node, (1N4N on Fig. 3) leaving the
three-phase Y-connected bank energized but isolated from the
system neutral and ground. This blocks the flow of harmonic
current through the capacitor bank into earth. The results of
these simulations are presented in Table IV.
Table IV shows that as successive capacitor neutrals are re-
moved, beginning near the substation and moving out on the
feeder, the harmonic currents in the earth and other return paths
increase until allcapacitor banks are removed. When a capacitor
bank is grounded, harmonic currents from loads near that bank
see the bank as the low impedance path back to their source.
When the capacitor ground is opened, the currents then see
TABLE VSIMULATION RESULTS: HARMONIC SUPPRESSION REACTORS
the next bank out on the feeder as the lowest impedance path,
causing them to flow through the neutral, earth, and other re-
turn paths to the next bank and across a greater length of the
telephone exposure. This continues until all banks are removed
from the feeder, when the harmonic currents no longer see any
low impedance capacitor paths back to neutral and earth, and the
system returns to close to the original condition of all capacitors
being grounded.
These results indicate that removing the ground connections
from the capacitor banks will not accomplish the desired tele-
phone noise reduction. By the time this result was available the
utility had already considered this solution and rejected it. A
safety problem for line crews occurs when capacitor grounds
are opened. The capacitor neutral point, which has always be-
fore been at earth potential, can no longer be assumed to be at
that low voltage. It must now be assumed to be at any voltage up
to full line voltage, and line crews must be retrained to assumethis.
The next set of simulations installed a harmonic suppression
reactor (HSR) in the neutral of each capacitor bank. While there
was no resonant capacitor, the common use of HSRs, it was
thought that the additional reactance might decrease the har-
monic earth current to acceptable levels. Table V shows the re-sulting noise levels, which were still unacceptably high.
The next step, then, was to consider installing a shunt filter to
reduce the harmonic currents in the earth exposure between the
distribution lines and telephone cables.
V. FILTER DESIGN
A shunt harmonic filter provides a low impedance path to
neutral for currents at the tuned frequency. This is accomplished
by placing an appropriate reactance in series with existing ca-
pacitors. Because this retunes thewhole distribution system, it is
necessary to simulate the filter under varying conditions during
the design process.
Fig. 7 shows two designs for a shunt filter on a three-phase
bank. Design (b) is recommended, with one reactor per phase.
But the telephone company and electric utility already had expe-
rience with harmonic suppression reactors, which are installed
as shown in design (a), so this design was used.
To tune the filter in design (a) for low impedance at frequency
, the inductance is
(1)
Two different 7200 V capacitor sizes were installed on this
circuit; 1200 kVAR (20.5 F), and 600 kVAR (10.2 F). The
7/27/2019 00871373
6/7
1050 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000
Fig. 7. Shunt filter designs.
TABLE VISIMULATION RESULTS: 540 Hz SHUNT FILTER
inductance required to tune the 1200 kVAR capacitor to 540 Hz
is 1.4 mH. The 600 kVAR requires 2.8 mH.
Three cases were simulated:
1) Filters at all four capacitor banks.
2) Filter at bank 2 only.
3) Filter at bank 3 only.
The results are shown in Table VI.
Applying filters at all four banks reduces the harmonic noise
to an acceptable level. Filtering at only bank 2 or 3 produces
even lower noise than filters at all four. A filter at bank 2 or 3
removes from the exposure much of the 540 Hz current gen-
erated between banks 2 and 4, while not drawing a significant
harmonic current from the other end of the exposure. On thiscircuit it was physically impractical to install a filter reactor on
the pole at bank 2, so the filter at bank 3 was chosen for further
study.
All combinations of capacitors on and off the system were
then simulated with the shunt filter installed at bank 3. Higher
load levels were also simulated. The noise levels remained at
acceptable levels for all conditions.
The simulated values of currents through the capacitor bank
were analyzed to insure the bank would not be overloaded by the
increased 540 Hz current it was carrying. The current through
the filter reactor was used to specify the current capacity of the
reactor itself.
VI. FILTER TEST AND INSTALLATION
The shunt filter was tested at bank 3. A harmonic suppression
reactor of the correct inductance was temporarily installed in
the capacitor neutral. Telephone noise levels were monitored at
the affected customers. Capacitor and filter reactor current and
voltage were also recorded.
VII. FILTER RESULTS
Before the reactor was switched in, the 540 Hz noise at the
affected telephone customers was 95 dBrnC. When the reactor
was switched in, the noise level dropped to 87 dBrnC, an ac-
ceptable level. Capacitor and reactor voltages and currents were
within their ratings and design ranges.
The steady-state current ratings of the harmonic suppression
reactor used in the test were too low to permanently install it as
a filter reactor; it is intended to block currents, so its ampacity
is relatively low. An oil filled reactor was ordered from a trans-
former manufacturer and was permanently installed at bank 3.
The permanent reactor produced the same noise reduction as the
test reactor. Noise levels on the telephone circuit have stayed
within acceptable ranges ever since.
VIII. CONCLUSIONS
Small, dispersed single-phase electronic loads on a residen-
tial/commercial feeder caused harmonic distortion significant
enough to cause unacceptable telephonenoise. An analysis tech-
nique involving field measurements and simplified modeling
of the distribution system was used to successfully analyze the
problem and design and implement a solution. The technique
involves a very simple model of earth and other return paths,
which assumes the return current splits equally between the
system neutral and the earth and other return paths, and follows
the geographical path of the phase conductors.
An existing three-phase power factor correction capacitor
bank was converted to a shunt harmonic filter to divert har-
monic currents from the exposure between electric power and
telephone cables. This reduced noise to an acceptable level.
REFERENCES
[1] IEEE Recommended Practice for Inductive Coordination of Electric
Supply and Communication Lines, IEEE Std. 776-1992, 1992.[2] W. Jewell, The effects of voltage sags in hospitals, in Proceedings of
PQA 93, San Diego, CA, November 1993, pp. 5-3:15-3:7.[3] 345 E. 47th St.10 017-2394IEEE recommended practice for harmonic
control in electric power systems, IEEE, New York, NY, IEEE 519,1992.
[4] IEEE Task Force on Modeling and Simulation, Modeling and simula-tion of the propagation of harmonics in electric power networks, PartI: Concepts, models, and simulation techniques, IEEE Transactions onPower Delivery, vol. 11, no. 1, pp. 452465, January 1996.
[5] IEEE Task Force on Modeling and Simulation, Modeling and simula-tion of the propagation of harmonics in electric power networks, Part II:Sample systems and examples, IEEE Transactions on Power Delivery,vol. 11, no. 1, pp. 466474, January 1996.
[6] The Fontaine, Unit 6B, 1220 NE 17th Ave.97232W. S. Meyer,Alternative Transients Program (ATP) Rule Book. Portland, OR:Canadian/American EMTP User Group.
7/27/2019 00871373
7/7
JEWELL et al.: FILTERING DISPERSED HARMONIC SOURCES 1051
[7] H. W. Dommel,Electromagnetic Transients Program Reference Manual(EMTP Theory Book): Bonneville Power Administration, August 1986.
[8] D. J. Pileggi, E. M. Gulachenski, C. E. Root, T. J. Gentile, and A. E.Emanuel, Effect of modern compact fluorescent lights on voltagedistortion, IEEE Transactions on Power Delivery, vol. 8, no. 3, pp.14511459, Jul. 1993.
[9] R. H. Galloway et al., Calculation of electrical parameters for shortand long polyphase transmission lines, Proceedings of IEE, vol. 111,no. 12, pp. 20512059, Dec. 1964.
Ward Jewell (M80SM90) teaches courses in electric power systems andelectric machinery as a Professor of Electrical Engineering at Wichita StateUniversity. Dr. Jewell is Director of the WSU Power Quality Laboratory andperforms research in electric power quality and advanced energy technologies.He has been with WSU since 1987.
Dr. Jewell earned the Ph.D. in electrical engineering from Oklahoma StateUniversity in 1986. He received the M.S. in electrical engineering fromMichigan State University in 1980, and the B.S. in electrical engineering fromOklahoma State University in 1979. From 19801984 Dr. Jewell worked withthe Power Systems Technology Program at the Oak Ridge National Laboratory.Dr. Jewells consulting work is in electric power quality troubleshooting andanalysis for commercial, industrial, and utility systems. He also consults inother areas of electric power systems and vehicle power systems.
William L. Miller is presently Manager, Technical Network Support, South-western Bell Telephone Company in Topeka, KS. He has taken courses in elec-tronics and related fields at Wichita State University, University of Wisconsin,and University of West Virginia following two years of Vocational Electronicsat CKAVTS. He has been employed for 24 years, which includes 12 years ofexperience with Inductive Interference. He is the Subject Matter Expert (SME)for the Kansas City Market Center in the areas of electrical protection, inductiveinterference, loop transmission, and dial-up data.
Mr. Miller is the Founder and Chairman of the Midwest Power and Commu-
nications Association.
Tom Casey supervisesthe electrical testing laboratoryat Kansas City Power andLight Company in Kansas City, MO. His duties include the repair and testingof distribution line equipment, tools, and test instruments. He received the B.S.in electrical engineering from the University of Kansas in 1981. For the last 15years he has held various customer service positions at Kansas City Power andLight andwas instrumental in developingthe powerquality program at KCP&L.