Upload
others
View
2
Download
0
Embed Size (px)
Citation preview
1
CALIBRATION OF BOND DURABILITY FACTOR FOR EXTERNALLY BONDED CFRP SYSTEMS IN CONCRETE STRUCTURES
By
JOVAN TATAR
A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT
OF THE REQUIREMENTS FOR THE DEGREE OF MASTER OF SCIENCE
UNIVERSITY OF FLORIDA
2013
2
© 2013 Jovan Tatar
3
To my parents
4
ACKNOWLEDGMENTS
I would like to express sincere gratitude to my committee chair Dr Trey Hamilton,
for his continuous support during this research; his patience, guidance, motivation, and
overall extraordinary mentoring skills. Aside from influencing the development of my
technical skills, Dr. Hamilton took a great part in my personal development.
I would like to thank Dr. Gary Consolazio for serving on my committee and
providing valuable comments regarding the thesis. In addition, I would like to
acknowledge Dr. Chris Ferraro for his insights and help in the experimental phase of the
project, Dr. Kurt Gurley for his suggestions in statistical analysis of data; and Dr. Elliot
Douglas for his support in carrying out the project research activities.
I would also like to express thanks to undergraduate and graduate students that
helped in specimen fabrication and testing phases of the project: Alex Randell, James
McCall, Paige Blackburn, Zack Workman, Juan Ponce, Peter Whitfield, Anthony
Kiessling, Charbel Raad, Philip Strauss, Garrett Littlejohn, Brad Krar.
Financial support for this research project was provided by Florida Department of
Transportation (FDOT). I am grateful for the technical support provided by staff at FDOT
State Materials Office in Gainesville, FL: Patrick Carlton, Dale DeFord, Richard
DeLorenzo, and Bill Baumann, in particular.
I would like to thank my parents, Slavica and Stevo Tatar for their unconditional
love and support during the course of my studies.
Last, but definitely not the least, I would like to express sincere gratitude to Gino
Blanco, for being of immense emotional support; a great guide and true help during my
adjustment to American culture. Thanks to him, my years at University of Florida, so far,
have been filled with joy.
5
TABLE OF CONTENTS page
ACKNOWLEDGMENTS .................................................................................................. 4
LIST OF TABLES ............................................................................................................ 7
LIST OF FIGURES .......................................................................................................... 9
ABSTRACT ................................................................................................................... 13
CHAPTER
1 INTRODUCTION .................................................................................................... 15
2 RESEARCH SIGNIFICANCE AND MOTIVATION .................................................. 18
3 LITERATURE REVIEW .......................................................................................... 19
Bond of FRP Composites to Concrete .................................................................... 19 Bond Test Methods ................................................................................................. 20 Durability of Bond ................................................................................................... 21 Effects of High Temperature, Moisture, UV, Alkaline Environment and Cycling ..... 24
4 DURABILITY TESTING APPROACH ..................................................................... 59
5 DURABILITY TEST SPECIMEN DESIGN AND FABRICATION ............................. 61
Specimen Design .................................................................................................... 61 Three-point Bending Test Bond Strength Index ...................................................... 63 CFRP Composites .................................................................................................. 64 Epoxy Adhesives .................................................................................................... 66 Specimen Fabrication ............................................................................................. 68 Specimen Preparation ............................................................................................ 75 Durability Test Procedures ...................................................................................... 83
6 RESULTS AND DISCUSSION ............................................................................... 86
7 DATA ANALYSIS .................................................................................................... 91
NCHRP Database ................................................................................................... 91 Analysis of Data for CFRP Wet-layup Without Putty ............................................... 97
Data Subset 1 for Wet-layup Without Putty Analysis ...................................... 100 Data subset 2 for Wet-layup Without Putty Analysis ...................................... 106
CFRP Wet-layup With Putty (Composite C) .......................................................... 113 Data Subset 1 for Wet-layup With Putty Analysis ........................................... 115 Data subset 2 for Wet-layup With Putty .......................................................... 117
6
CFRP Laminates .................................................................................................. 122 Literature Data ...................................................................................................... 123
8 INFLUENCE OF FAILURE MODE ON BOND STRENGTH INDEX...................... 126
9 BOND DURABILITY FACTOR .............................................................................. 132
Environmental Reduction Factor and Bond Durability Factor ............................... 132 Characteristic Bond Durability Factor ................................................................... 133 Bond Durability Factor for Wet-layup Without Putty .............................................. 139 Bond Durability Factor for Wet-layup With Putty ................................................... 147
10 SUMMARY AND CONCLUSIONS ........................................................................ 154
11 FUTURE WORK ................................................................................................... 157
APPENDIX
TOLERANCE FACTORS FOR CHARACTERISTIC BDF ..................................... 158
LIST OF REFERENCES ............................................................................................. 159
BIOGRAPHICAL SKETCH .......................................................................................... 166
7
LIST OF TABLES
Table page 3-1 Distribution of failure modes ............................................................................... 54
3-2 Change in ultimate bond strength after 12 months of exposure ......................... 57
4-1 Summary of conditioning protocols ..................................................................... 59
5-1 Properties of composite systems (information provided by manufacturers) ....... 66
5-2 Adhesive A mechanical properties 72 hours post cure at 140˚ F (60˚ C) – as reported by the manufacturer ............................................................................. 66
5-3 Adhesive B mechanical properties (14 day cure at 73˚F (23˚C) and 50% R.H.) – as reported by the manufacturer ............................................................ 67
5-4 Adhesive C mechanical properties (based on cured samples at 72˚F (20˚C) and 40% R.H.) – as reported by the manufacturer ............................................. 67
5-5 Adhesive E mechanical properties (at 73˚F (23˚C) and 50% R.H.) – as reported by the manufacturer ............................................................................. 68
5-6 Exemplary 10,000 psi mix proportions ................................................................ 69
5-7 Exemplary 4,000 psi mix proportions .................................................................. 69
5-8 Concrete mechanical properties ......................................................................... 74
7-1 NCHRP exposure conditions .............................................................................. 93
7-2 Specifics of Group 1 and Group 2 test specimens.............................................. 94
7-3 Statistical models parameters........................................................................... 103
7-4 Statistical test results ........................................................................................ 103
7-5 Normal distribution parameters for 30˚C and 60˚C of Data subset 1 ................ 106
7-6 Statistical tests results for Group 1 data ........................................................... 108
7-7 Levene’s and F-test results .............................................................................. 110
7-8 ANOVA results ................................................................................................. 113
7-9 Statistical tests results ...................................................................................... 116
7-10 Statistical tests results ...................................................................................... 119
8
7-11 Theoretical normal distribution parameters for different groups of data from literature ........................................................................................................... 125
8-1 Comparison of failure loads and failure modes for control specimens .............. 130
9-1 Environmental reduction factors as per ACI 440.2R-08 .................................... 132
9-2 Results of ANOVA analysis .............................................................................. 138
9-3 Conditioning protocol subgroups for wet-layup without putty ............................ 141
9-4 Normal distribution parameters for conservative and overly conservative characteristic BDFk ........................................................................................... 145
9-5 Conditioning protocol subgroups for wet-layup with putty ................................. 149
9-6 Normal distribution parameters for conservative and overly conservative characteristic values ......................................................................................... 152
A-1 Tolerance factors, K (Hahn and Meeker 1991) ................................................. 158
9
LIST OF FIGURES
Figure page 1-1 Number of publications in Web of Science ......................................................... 17
3-1 Possible failure modes in FRP-concrete bond system ....................................... 20
3-2 a) direct pull-off (bottom) and direct torsion (top) test; and b) direct shear (α=0˚), peel (α=90̊) and mixed-mode (0̊
10
3-22 Beam flexure specimen ...................................................................................... 53
3-23 Direct shear test setup ........................................................................................ 55
3-24 Direct sehar test specimen ................................................................................. 57
3-25 Failure surfaces for normal strength concrete .................................................... 57
3-26 Failure surfaces for high strength concrete ........................................................ 58
5-1 Three-point bending test setup ........................................................................... 62
5-2 Loading modes in interfacial region .................................................................... 64
5-3 Fine aggregate, coarse aggregate and cement (left to right) .............................. 70
5-4 Darex AEA, Adva Cast 600 and WRDA 60 (left to right) .................................... 70
5-5 Beam production procedures.............................................................................. 71
5-6 Specimen sandblasting ...................................................................................... 75
5-7 Procedure for repair with Composite systems A, B and D .................................. 76
5-8 Procedure for repair with Composite C system .................................................. 79
5-9 Procedure for repair with Composite E system................................................... 81
5-10 Exposure of test specimens ............................................................................... 83
5-11 Concrete beam in test fixture .............................................................................. 84
5-12 a) Debonding failure; b) shear failure ................................................................. 85
6-1 Representative averaged load-displacement plots for control and exposed samples .............................................................................................................. 86
6-2 Failure modes: a) 0% adhesive; b) 50% adhesive; c) 100% adhesive ............... 87
6-3 Bond strength index: a) immersion in water at 30˚C; b) immersion in water at 60˚C; and c) RH=100% at 60˚C .......................................................................... 89
6-4 CFRP laminate failure modes: a) adhesive failure between CFRP laminate and epoxy; b) CFRP laminate decohesion ......................................................... 90
7-1 a) Wet-layup without putty; b) wet-layup with putty; c) CFRP laminates ............. 96
7-2 Histogram and density distribution of test data ................................................... 99
11
7-3 Q-Q plot for all test data ................................................................................... 100
7-4 Histogram and density distribution of test data ................................................. 100
7-5 Q-Q plot for test data ........................................................................................ 101
7-6 Statistical fit models for Data subset 1: probability density function (left) and cumulative distribution function (right) .............................................................. 104
7-8 Histogram and probability density estimate for samples exposed to 60˚C ....... 105
7-9 Comparison of probability density estimates for 30˚C and 60˚C of Data subset 1 ............................................................................................................ 106
7-10 Histogram and probability density estimate for Data subset 2 .......................... 107
7-11 Q-Q plot for Data subset 2 ................................................................................ 107
7-12 Normal distribution fit for Data subset 2 ............................................................ 108
7-13 Comparison of normal distribution models for two data subsets (wet-layup without putty) .................................................................................................... 109
7-14 Histogram and probability density estimate for wet-layup with putty ................. 113
7-15 Q-Q plot for wet-layup with putty ...................................................................... 114
7-16 Histogram and probability density estimate for Data subset 1 .......................... 115
7-17 Q-Q plot for Data subset 1 ................................................................................ 115
7-18 Normal distribution fit for Data subset 1 ............................................................ 116
7-19 Histogram and probability density estimate for Data subset 2 .......................... 117
7-20 Q-Q plot for Data subset 2 ................................................................................ 118
7-21 Normal distribution fit for Data subset 2 ............................................................ 119
7-22 Comparison of normal distribution models for two data subsets (wet-layup with putty) ......................................................................................................... 121
7-23 Histogram and probability density function for CFRP laminates ....................... 122
7-24 Small-scale data distribution (literature) ........................................................... 124
7-25 Large-scale data distribution (literature) ........................................................... 124
7-26 Comparison of distributions for different groups of data from literature ............ 125
12
8-1 Failure mode of concrete specimens ................................................................ 127
8-2 Cohesive failure mode (0% adhesive) .............................................................. 128
8-3 Adhesive failure mode (100% adhesive) .......................................................... 128
8-4 Partially adhesive failure mode (70% adhesive) ............................................... 129
8-5 Comparison of control to conditioned (60 days immersion in water at 60˚C) specimen load capacity for Composite B .......................................................... 131
9-1 Tolerance factor, K vs. number of tests, n ........................................................ 135
9-2 Illustration of bond strength index degradation with respect to time from NCHRP study ................................................................................................... 136
9-3 Illustration of bond strength index degradation with respect to time from FDOT study ...................................................................................................... 137
9-4 Characteristic values for wet-layup without putty excluding Group 1 exposure to water immersion to 30˚C through 60˚C ......................................................... 140
9-5 Whisker plot ...................................................................................................... 142
9-6 Whisker plots for each subgroup for conservative characteristic values ........... 144
9-7 Whisker plots for each subgroup for overly conservative characteristic values 144
9-8 Fitted cumulative distribution function for wet-layup without putty excluding Group 1 exposure to water immersion to 30˚C through 60˚C ........................... 146
9-9 Cumulative distribution functions for small-scale (left) and large-scale (right) data for wet-layup from literature ...................................................................... 147
9-10 Characteristic values for wet-layup with putty ................................................... 148
9-11 Whisker plots for each subgroup for conservative characteristic values ........... 150
9-12 Whisker plots for each subgroup for overly conservative characteristic values 151
13
Abstract of Thesis Presented to the Graduate School of the University of Florida in Partial Fulfillment of the Requirements for the Degree of Master of Science
CALIBRATION OF BOND DURABILITY FACTOR FOR EXTERNALLY BONDED CFRP
SYSTEMS IN CONCRETE STRUCTURES
By
Jovan Tatar
December 2013
Chair: Homer R. Hamilton III Major: Civil Engineering
Use of carbon fiber-reinforced polymer (CFRP) composites in civil infrastructure
has shown an increase in the past two decades. Externally bonded CFRP materials
(wet-layup and laminate) have found their application in repair of damaged concrete
structures, particularly bridges.
Lack of understanding and confidence in the long-term performance of externally
bonded FRP systems in concrete structures still inhibits the use of FRP composites to
repair bridges. The most significant issue with externally bonded FRP composites is
their susceptibility to degradation when exposed to moisture. One method to gage this
sensitivity to moisture is to accelerate the effect of the moisture by exposing the material
to high heat and moisture.
This research utilized small-beam specimens to study FRP-concrete bond
performance when subjected to accelerated conditioning environments (immersion in
water and exposure to high humidity at elevated temperatures). Small beams with
bonded CFRP reinforcement were conditioned and then tested to failure under three-
point bending. The bond strength index was determined by dividing the average
conditioned strength by the average control strength.
14
Test results from the present research were combined with other test data to
form a database of over 900 test results. By utilizing an apparent analogy of FRP-
concrete bonded systems to adhesive anchors, a bond durability factor that quantifies
loss in bond capacity due to accelerated conditioning is determined equivalently as
characteristic test value for adhesive anchors.
For the purpose of the analyses, and based on available data, it was determined
that all FRP systems may be split into three categories. Bond durability factors
corresponding to wet-layup without putty and wet-layup with putty were determined to
be 0.6 and 0.4, respectively. Bond durability factor for CFRP laminate was not
established due to a lack of prolonged exposure data corresponding bond failure; CFRP
laminate specimens failed prematurely due to low material quality. Analysis of failure
modes revealed a dependency between ultimate load and failure mode. Cohesive
failure modes allowed for higher ultimate loads than adhesive failure modes. Moreover,
it was noted that failure mode and ultimate strength is not directly a function of concrete
strength, but rather its porosity and surface preparation.
15
CHAPTER 1INTRODUCTION
Aging infrastructure in the US, bridges in particular, is in need of reliable,
economical, and fast repair method. Eleven percent of bridges in 2012 were classified
as structurally deficient (ASCE 2013 Report Card definition: “Bridges that require
significant maintenance, rehabilitation, or replacement.”), and 24.9% were functionally
obsolete (ASCE’s 2013 Report Card definition: “Bridges that no longer meet the current
standards that are used today.”). In Florida, situation is somewhat better, with 262 or
2.2% of bridges being structurally deficient and 1,764 or 14.7% functionally obsolete.
Application of externally bonded fiber reinforced polymer (FRP) composite
reinforcement is becoming one of the most popular repair techniques in aging bridges
due to ease of installation, and its cost-effectiveness. FRP composites are typically
composed of glass, Kevlar, aramid, or carbon fibers oriented in specific directions and
embedded in an epoxy matrix. Most-commonly used fibers in bridge repair and
strengthening is carbon.
CFRP composites are light-weight, resistant to corrosion and have a high
strength-to-weight ratio relative to traditional construction materials, such as steel.
Currently, there are two types of CFRP based on application methods: wet-layup CFRP
and CFRP laminate. Wet-layup CFRP application is performed by saturating a dry fiber
fabric with epoxy. The wet fabric is then placed on the concrete surface. Primers are
sometimes used to facilitate adhesion to the concrete substrate.
CFRP laminates are formed by pultrusion. In this process the fibers undergo
impregnation by epoxy resin and are pulled through a heated stationary die which
allows for epoxy polymerization. CFRP laminate is usually adhered to concrete surface
16
with paste epoxy with higher viscosity than epoxies normally used in wet-layup
applications. CFRP compositesare mostly used as flexural and shear reinforcement, or
as a confinement in columns.
ACI 440R-08 characterizes the typical failure modes for members strengthened
with bonded CFRP composites as follows:
1. Crushing of concrete in compression before yielding of reinforcing steel 2. Steel yielding followed by rupture of CFRP 3. Yielding of the steel in tension followed by concrete crushing 4. Concrete cover delamination 5. Debonding of the FRP from concrete substrate
From design standpoint failure modes 2 and 3 are favorable because they are
less brittle than the other failure modes. Failure mode 1 is of a brittle nature and is not
desirable. Finally, modes 4 and 5 are debonding modes and are the most common due
to high stress concentrations at the ends of external CFRP reinforcement and due to
development of stresses at the bond line as the flexural cracks open. CFRP debonding
is considered a premature failure mode and is not desirable.
Debonding of CFRP, and CFRP-concrete bond behavior has been an
increasingly popular research topic in the past decade. Figure 1-1 presents number of
published papers relating to search terms “FRP” and “FRP” AND “Bond” in Web of
Science achieve, showing increasing trends in the past years. This demonstrates high
level of interest in FRP composite research.
17
Figure 1-1. Number of publications in Web of Science
Year
No.
of p
ublic
atio
ns
1980 1985 1990 1995 2000 2005 2010 20150
100
200
300
400
500Search: "FRP"Search: "FRP" AND "Bond"
18
CHAPTER 2RESEARCH SIGNIFICANCE AND MOTIVATION
Short-term performance and behavior of FRP-repaired concrete systems has
been extensively studied. However, research on issues that may arise due to exposure
of FRP-concrete systems to highly aggressive environments.
Since use of CFRP composite reinforcement in concrete structures is a relatively
novel repair method information on long-term performance of these systems is scarce.
ACI 440R-07 indicates that research and development are needed in the
following areas:
1. Identification of appropriate environments for durability testing 2. Durability studies of externally bonded FRP repair or retrofit measures 3. Service life prediction of structures using FRP 4. Development of standardized test methods with an accent on durability testing 5. Design and construction guidelines and specifications
The above-mentioned facts motivated development of a research plan that would
address durability issues in FRP materials’ performance in concrete structures when
exposed to harsh environmental conditions. This thesis presents research that is
primarily concerned with the development of a bond durability factor. This factor would
quantify the loss in bond properties between CFRP (carbon fiber reinforced polymer)
and concrete over time, and eventually affect the design factors in ACI 440.2R-08.
Furthermore, the intent of presented work is to promote development of a standardized
test method for durability of FRP-concrete bond.
19
CHAPTER 3LITERATURE REVIEW
Bond of FRP Composites to Concrete
Bond between FRP and concrete is established through the epoxy adhesive.
Bond is formed by means of mechanical interlocking and chemical bonding.
Mechanical interlock is established by flow of epoxy into the holes, crevices and
pores of concrete substrate. After it cures, epoxy locks in mechanically to the surface.
However, due to plasticization effects in epoxy, caused by its exposure to water,
mechanical bond may be weakened. Plasticization is a change in the thermal and
mechanical properties of a given polymer which involves: (a) lowering of rigidity at room
temperature; (b) lowering of temperature, at which substantial deformations can be
effected with not too large forces; (c) increase of the elongation to break at room
temperature; (d) increase of the toughness (impact strength) down to the lowest
temperature of serviceability (Immergut and Mark 1965).
Chemical bond is established through hydrogen bonding. Hydrogen bond forms
as a result of interaction between positively charged hydrogen atom and highly
negatively charged atom like oxygen (O) or nitrogen (N). In general, hydrogen bond
represents a combination of electrostatic, covalent and Van der Vaals interaction, and
should not be mistaken with covalent bond. In case of concrete, hydrogen bonds are
established through oxygen atoms on concrete surface and hydrogen atoms of epoxy
hydroxyl groups. Once the bond is exposed to moisture, hydrogen bonds get replaced
by water molecules (Lefebvre 2000) causing chemical bond to degrade.
Furthermore epoxy structure is affected by temperatures higher than Tg which
causes epoxy to lose stiffness due to increased chain mobility. Tg (glass transition
20
temperature) is approximate midpoint of the temperature range over which reversible
change in an amorphous polymer, or in amorphous regions of a partially crystalline
polymer, to a rubbery or viscous condition from a glassy or hard condition
(ISO 22768:2006)
As a result of aforementioned behavior, distinguishing failure modes occur in
FRP-concrete joints. Failure mode that is the most common and inherent to dry ambient
condition is cohesive failure mode in concrete substrate (Figure 3-1). Due to exposure
to moisture failure mode shifts to the interface between concrete substrate and
adhesive (Figure 3-1). This failure mode is termed adhesive failure mode. Failure
modes corresponding to adhesive decohesion or adhesive failure between FRP and
adhesive are typically not experienced (Figure 3-1). FRP decohesion (Figure 3-1) is
usually not an issue and may occur in underreinforced members, due to development of
high interlaminar stresses, or due to exposure to aggressive environments.
Figure 3-1. Possible failure modes in FRP-concrete bond system
Bond Test Methods
Bond of FRP-concrete joints is usually a critical component of the repaired
system. Debonding of FRP from concrete substrate is most commonly adopted limit
state. A number of test methods was developed in an attempt to study the phenomenon
of debonding of FRP from concrete substrate. These tests can generally be separated
into two groups.
Cohesive failureAdhesive decohesion
FRP decohesion
Adhesive failureAdhesive failure betweenFRP and adesive
Concrete
Adhesive
FRP
21
Direct bond tests (Figure 3-2), where FRP is subjected to controlled loading
mode, consist of:
• Direct pull-off • Direct torsion • Direct shear pull-off • Peel test • Mixed-mode test
Indirect bond tests, that utilize flexural test setup to test the bond performance,
are usually performed as:
• Three-point bending beam tests • Four-point bending beam tests
The following literature review discusses different test setups in more detail.
a) b)
Figure 3-2. a) direct pull-off (bottom) and direct torsion (top) test; and b) direct shear (α=0˚), peel (α=90̊) and mixed-mode (0̊
22
specific material’s properties. When referred to durability in terms of concrete, one
usually assumes ability of the material to withstand deterioration caused by weather and
chemical exposure, or surface abrasion. For the purpose of this study, by bond
durability of FRP-to-concrete, its long-term resistance to aggressive environmental
conditions is implied (e.g. high temperature, high moisture levels, UV, alkali, etc.). The
following chapter presents findings from the literature related to the durability of FRP-to-
concrete joints.
Since a wide range of tests methods and test specimens at different size scales
are utilized to study the topic, the term “loss in capacity” needs to be defined. By “loss in
capacity” is considered the quantitative decay in exposed specimen’s ultimate failure
load, ultimate stress, or fracture energy, when compared to control specimen with the
same characteristics that was not conditioned in an aggressive environment. It should
be noted that loss in capacity, as defined here, may not be necessarily equivalent to the
loss in bond capacity. This is mainly dependent the specimen design. For example, in
the ultimate load capacity of reinforced concrete beams that are repaired with FRP, R/C
beam’s residual capacity provided by the steel reinforcement at the tension face will
have a portion in both exposed and unexposed FRP-reinforced specimen. In order to
quantify the loss of bond capacity, residual load capacity of R/C concrete beam ought to
be eliminated when calculating the loss in bond capacity. In other words, only the
portions of capacity above the dotted line in Figure 3-3 shall be compared, as they
represent the contribution of FRP. This approach assumes that residual capacity is
determined from unexposed specimen. It shall be regarded that this is a more
conservative approach, as opposed to using the exposed specimen residual capacity in
23
calculations. In case of concrete-only flexural specimens, assumption is that its capacity
to resist tensile stresses comes from FRP only (concrete contribution is neglected).
Therefore, specimen’s load capacity is assumed to be representative of FRP-concrete
bond strength.
Figure 3-3. Specimen capacity
Cap
acity
Decrease due to exposure
Effective strengthIncrease due to FRP
24
Effects of High Temperature, Moisture, UV, Alkaline Environment and Cycling
One of the first times that the issue of long-term performance of the composite-
to-concrete bond was mentioned in the literature was in paper by Saadatmanesh and
Ehsani (1990). However, amongst the first attempts to conduct tests that included
environmental considerations was by Xie et al. (1995). They subjected multiple
reinforced concrete specimens, with an addition of CFRP laminates at the beam soffit to
both accelerated and long-term environmental tests (Figure 3-4). The exposure
conditions were as follows: (1) 2 weeks water immersion at room temperature followed
by 10 days of drying at room conditions; and (2) heating in oven at 40˚C for a week
followed by refrigeration at -23˚C for a week, for a total of two months. Authors found
that specimens exposed to water experienced a slight increase in strength (about 2%),
which they credited to increased fracture toughness of epoxy due to plasticization. On
the other hand, specimens that were exposed to hot-cold cycles experienced a
decrease in strength of about 10%.
Figure 3-4. Three-point bending test setup
Chajes et al. (1995) studied the influence of aggressive environmental
conditioning on durability of bond between FRP and concrete. The concrete test
25
specimens measuring 1.5 x 1.1 x 13 in. (38.1 x 28.6 x 330 mm) were reinforced with
one threaded steel bar placed 0.75 in. (19.1 mm) from the compression face of the
beam. Graphite FRP strip was adhered to the beam with the same width as the test
specimen – 1.5 in. (38.1 mm). Beams were first covered with a calcium chloride solution
and then conditioned at: (a) 50 and 100 freeze/thaw cycles as per ASTM C672-84
(freezing at -17˚C for 16 h, followed by thawing at room temperature for 8 h); and (b) 50
and 100 wet/dry cycles (immersion in calcium chloride solution for 16 h, followed by
drying at room temperature for 8 h). After conditioning, beams were loaded until the
total failure in four point bending test setup. Authors recorded a loss in additional
capacity provided by FRP from control (not exposed samples) to the samples subjected
to 100 wet/dry cycles peaking at around 13%.
Figure 3-5. Four-point bending test setup
Further work in addressing an issue of long-term performance of FRP-concrete
bond was undertaken by Karbhari and Engineer (1996). They tested small concrete
beams (measuring 2 x 1 x 13 in. or 50.8 x 25.4 x 330.2 mm) reinforced with different
26
FRP materials (GFRP and CFRP) in four point bending tests. All beams were exposed
to the following environments for a period of 60 days before testing: (1) immersion in
water at 20˚C; (2) immersion in synthetic seawater at 20˚C; (3) freezing at -15.5˚C; and
(4) Freeze-thaw cycling (-15.5˚C for 24 hours followed by 50˚C for 24 hours). Control
samples were kept in ambient conditions at 20˚C. Test results showed the highest loss
in capacity in beams immersed in fresh and seawater, peaking at around 35%. The
minimum overall change was observed for specimens exposed to freezing at -15.5˚C.
According to the authors, the loss in bond capacity was due to epoxy’s susceptibility to
plasticization and increase in compliance caused by the water absorption. Moreover, a
significant drop in glass transition temperature (Tg) of resins was noticed after exposure
to continuous water ingress. According to the authors, the reduction in Tg due to water
absorption signifies a degradation in epoxy matrix properties which may lead to
decreased load carrying capacity.
Furthermore, in a separate study, Kabhari et al. (1997) subjected specimens
exposed to the same environmental conditions to a controlled mixed mode test (Figure
3-6). They measured interfacial fracture energy for each exposure condition as a
function of phase angle ψ (mode mixity parameter - I
II
KK1tan −=ψ ) and the angle at
which peel force was applied. It should be noted that the phase angle ψ=0˚ corresponds
to a pure Mode I conditions, and ψ=90˚ relates to pure Mode II loading. They observed
a clear difference in interfacial fracture energy magnitudes between the systems
exposed to water immersion and freeze/freeze-thaw cycles, with the former set of
specimens having higher values of interfacial fracture energy.
27
It was also noted that this difference was not as apparent in specimens
reinforced with carbon fiber as opposed to specimens with glass fibers. Additionally,
specimens reinforced with carbon fibers showed almost no change in interfacial fracture
energy in respect to phase angle. On the other hand, an increase in fracture energy of
up to 300% (from Mode I to Mode II) was observed for specimens with glass fibers.
Analysis of dependency of peel force, Mode I fracture energy (GI), Mode II fracture
energy (GII) and total fracture energy (G=GI+GII) to the peel angle showed that
exposure to water not only resulted in a decrease of peel force and interfacial energy,
but it also causes a shift in overall trends – variation of GII in respect to peel angle
changes from exponential (for ambient conditions) to linear dependency (after exposure
to water). According to the authors, this indicates a change in mechanisms during peel
due to exposure to water. In addition to this, authors observed a change in failure mode
from cohesive to adhesive. Specimens exposed to freezing and freeze-thaw conditions
showed an increase in peel force and interfacial fracture energy when compared to
control specimens.
28
Figure 3-6. Mixed mode peel test setup
Another study pertaining to long-term durability of concrete bonded with external
FRP in marine environments was performed by Toutanji and Gomez (1997). The test
specimen consisted of small concrete beam, measuring 2 x 2 in (51 x 51 mm) with a
total length of 14.4 in (365 mm), reinforced with either a CFRP or a GFRP laminate over
the full length of the beam. Three different adhesives were used to bond FRP sheets to
concrete. Test method consisted of loading the specimens in four-point bending at a
constant crosshead displacement rate until the failure. Specimens were exposed to 300
wet and dry cycles (hot air at 35˚C average and 90% relative humidity) in a salt
environment (35 g of salt per 1 liter of water). Control specimens were kept in standard
room conditions. Test results showed that there was a significant reduction in specimen
capacity ranging from 3 to 33%, depending on the type of fibers and epoxy used. The
loss in capacity was attributed to degradation of epoxy.
29
Figure 3-7. Four-point bending test setup
Beaudoin et al. (1998) performed a durability study on reinforced concrete beams
with external FRP. Beams measured 3.9 x 5.9 x 47.2 in. (100 x 150 x 1200 mm) and
were reinforced with two 0.26 in. (6.5 mm) diameter steel bars (0.1 in2 or 65 mm2) in
addition to stirrups that were placed to avoid shear failure. Beams were reinforced with
Mitsubishi Replak 20 and Sika CarboDur CFRP laminates too. Control specimens were
kept in dry laboratory conditions, while the rest of the samples were exposed to 13 wet-
dry cycles. Cycles consisted of immersion in water at 21˚C for five days, followed by
drying for two days at 27˚C. After conditioning beams were subjected to four-point
bending tests. Test results showed that beams reinforced with Replak 20 had a loss in
ultimate capacity of around 10%, while beams strengthened with CarboDur experienced
an increase in ultimate load capacity of approximately 10%. The loss in FRP bond
capacity was around 20% for Replak 20. CarboDur samples had an increase of 15% in
FRP bond capacity on average.
30
Figure 3-8. Four-point bending test setup
31
Sen et al. (1999) conducted another study on durability of FRP-concrete bond in
marine environments. Test specimens were prepared by bonding two types of carbon
fibers (either bidirectional woven fabric or unidirectional carbon fiber procured sheet) to
a concrete slab using five different epoxy systems. Concrete slabs were each 17.9 x
17.9 in. (455 x 455 mm) with the thickness varying between 2.95 and 3.74 in. (75 and
95 mm). Four different exposure conditions were investigated: (1) combined wet/dry
cycles and hot/cold cycles in 5% salt water for 17 months; (2) wet/dry cycles in 15% salt
water for 17 months; (3) outdoor conditions for 23 months; and (4) air conditioned
laboratory conditions (control) for 23 months. To measure the bond strength destructive
direct pull-off or direct torsion tests were performed. Test results showed that bond
degradation was least under outdoor exposure and greatest under wet/dry cycles.
Consequently, authors concluded that moisture absorption is potentially more damaging
to bond durability, than other environmental factors. Test results indicated that direct
pill-off test generally produced a bond failure at lower stresses than direct torsion test.
As stated by the authors, direct torsion test is, therefore, more appropriate for identifying
bond degradation in flexural applications.
32
a) b)
Figure 3-9. a) torsion test setup; b) pull-off test setup
33
Leung et al. (2001) evaluated environmental impacts on the flexural behavior of
reinforced concrete beam strengthened with CFRP. Beams were made of concrete and
had the following dimensions: 2.95 x 2.95 x 11.8 in. (75 x 75 x 300 mm). Test beams
were subjected to three-point bending until the failure. The following four exposure
conditions were introduced: (1) water immersion at 27˚C; (2) Wetting/drying cycle (water
immersion at 27˚C for half a week, followed by storage in a control room for half a week
– 25±2˚C and RH 65±2%); (3) constant moisture condition (25±2˚C and RH 65±2%);
and (4) heating/cooling cycle (oven at 60˚C for half a week, followed by storage in a
control room for half a week). Authors found that exposure to the aforementioned
environments caused changes in the concrete and the adhesive. Generally, plain
concrete specimens had higher failure loads with decreasing in moisture contents. Also,
longer exposure to the moist environments resulted in an increase in strength of plain
concrete beams. Finally, authors concluded that long-term exposure of CFRP reinforced
beams to highly moist environments affects the adhesive and leads to decrease in load-
carrying capacity and midspan deflection. Observed failure mode for beams reinforced
with CFRP was “shear failure with plate peel-off”.
Myers and Ekenel (2005) conducted a study that investigated the effects of
moisture and temperature of the concrete surface at time of installation on FRP-
concrete bond strength. Direct pull-off and direct torsion tests were performed in order
to identify the critical surface moisture content and R.H. of concrete. Additionally,
flexural tests were performed on precracked reinforced concrete beams to determine
the effects of temperature at installation on the performance of bond between FRP and
concrete. Authors found that specimens that were constructed with at a high surface
34
moisture contents exhibited poor bond performance. Furthermore, it was found that
specimens that were strengthened at a relative humidity higher than 82% may have
lower bond quality. When it comes to the effects of temperature, it was concluded that
the extremely low temperatures affected the bond adversely. However, installation of
FRP in high temperatures did not prove to affect the bond behavior.
a) b)
c)
Figure 3-10. a) flexural specimens; b) direct pull-off test setup; c) direct torsion test setup
Grace and Singh (2005) explored the effects of various environmental conditions
on the performance of reinforced concrete beams externally strengthened with CFRP
35
laminates and fabrics. Reinforced concrete beams specimens used in this study
measured 6 x 10 in. (152.4 x 254 mm) in cross-sectional dimensions and were 108 in.
(2743 mm) long. Specimens were exposed to the following environmental conditions:
(a) 100% humidity; (b) dry heat; (c) saltwater solution; (d) alkaline solution; (e) freeze-
thaw cycles; and (f) thermal expansion. Beams were then tested in four-point bending
by loading and unloading in two stages until the complete failure. All beams failed either
due to debonding of FRP or “onset of delamination (shear-tension failure)”. Again, the
highest loss in capacity (of up to 30%) was observed in beams that were exposed to
highly moist environments. Beams experienced either a smaller loss or an increase in
capacity due to exposure to other environmental conditions. Authors noted that CFRP
laminates are more susceptible to aggressive environmental conditions than the beams
reinforced with CFRP fabric. Furthermore, they observed that duration of exposure for
the beams exposed to humidity and saltwater solution had no significant influence on
beams that were reinforced with CFRP fabric, while beams strengthened with CFRP
laminates experienced further deterioration in strength due to the prolonged exposure.
36
Figure 3-11. Drawings of test specimen
37
Attempt in determining the influence of temperature only on the bond
performance of concrete externally strengthened with FRP was undertaken by Klamer
et al. (2005). They conducted both shear-lap tests and three point bending tests at
different environmental temperatures. Concrete specimens were strengthened with
CFRP laminate and paste epoxy (Adhesive B in this report) with a glass transition
temperature Tg=62˚C. Change in the failure mode, from cohesive to adhesive, was
observed for temperatures higher than 50˚C. In shear-lap specimens, an increase in
temperature (below the Tg) produced an increase in the bond capacity. Authors
concluded that the bond capacity is affected by the increase in temperature due to the
decrease in adhesive stiffness and reduction in adhesive strength (especially for
temperatures above the Tg). It should be regarded that the measured force in CFRP
was lower and the displacement was higher at higher temperatures in the three-point
bending test, which ultimately resulted in a higher specimen capacity. Authors explained
this by effects introduced by the test setup.
38
Figure 3-12. Double lap shear test setup (left); and three-point bending test setup (right)
39
Au and Buyukozturk (2006) performed a study on influence of moisture on the
bond behavior in peel (Mode I) and shear (Mode II) test configurations. Pre-cracked
peel and direct shear fracture specimens were conditioned at: (a) RH=100% at 23˚C;
and (b) RH=100% at 50˚C. Specimens were conditioned for 2, 4 and 8 weeks. Control
samples were kept in dry conditions. Results from these tests were presented in terms
of specialized fracture energy release rate, based on the tri-layer fracture model
developed by Au and Buyukozturk (2006). Under the peel conditions exposed
specimens experienced a sudden drop in bond capacity of around 60%. Shear fracture
specimens, however, experienced a more gradual drop in capacity peaking at around
50% loss. Higher temperature did not significantly affect the peel properties of test
specimens, whereas shear fracture specimens achieved lower capacities at higher
conditioning temperature. Additionally, Tuakta and Buyukozturk (2010) extended this
study to include specimens conditioned by immersion in water at same temperatures
and wet-dry cycling. They also explored the influence of drying before testing the
specimens (referred to as moisture reversal tests). They noted that decrease in fracture
energy of FRP-concrete bond may be up to 70%. Furthermore, they concluded that
bond properties cannot be fully regained after drying or successive wet-dry cycles.
Authors observed a shift in failure mode from cohesive to adhesive in all conditioned
samples.
40
Figure 3-13. Direct shear/peel test specimen
41
Study on assessment of quality of bond between FRP and concrete with the
presence of water at the time of installation was undertaken by Wan et at. (2006). They
used the modified double cantilever beam (MDCB) test to obtain the energy release rate
of FRP debonding when subjected to mixed mode loading conditions. Details on the test
setup and analytical model may be found in the referenced journal article. To simulate
the presence of water at time of installation of wet-layup CFRP, four different surface
moisture conditions were introduced: (a) dry; (b) saturated surface dry 1 (SSD1); (c)
saturated surface dry 2 (SSD2); and (d) wet. For dry surface condition specimens were
left in ambient conditions to cure before and after priming. For SSD1 condition
specimens were submerged in water for 3 days, followed by drying the surface with a
paper towel and then applying the primer. Additionally, specimens were submerged in
water after priming with the water level below the concrete surface. For SSD2 condition,
the same procedure was followed, however, specimens were left in ambient conditions
after priming. For the wet condition, primer was applied to the wet concrete surface
directly. Specimens were then submerged in water again. Based on the test data
authors concluded that the bond capacity decreases with the amount of water present
at the surface. Namely, loss in capacity for SSD2, SSD1, and wet specimens was 58,
38, and 8% of the specimens kept in dry conditions, respectively. The prevailing failure
mode for all conditioned specimens was mixed or adhesive. In addition to the previously
described test program, authors performed a series of tests to investigate the influence
of water on bond after FRP cures. The specimens were conditioned in water for 3, 6,
and 8 weeks and then subjected to MDCB test. Results showed that FRP-concrete
42
bond degrades in respect time, with a loss of up to about 75% in ultimate energy
release rate when compared to results for specimens kept in dry conditions.
Figure 3-14. Mixed mode peel test setup
Alfar (2006) studied the durability of CFRP strengthened reinforced concrete
members subjected to real-time exposure in environments typical for Amman city (at
Building Research Center of the Royal Scientific Society of Jordan), Dead Sea region
(salt extracting plant), and Aqaba region (splash and tidal zone) in Jordan. According to
the authors, the latter two locations provided exposure to some of the most severe
marine environments. Salinity of Dead Sea is close to 34% (340 parts per thousand)
compared to only around 3.5% (35 parts per thousand) that is the salinity of North
Atlantic ocean. Specimens were also subjected to high temperatures ranging from 37 to
49.5˚C in the summer and RH=80%. Additionally, some samples were exposed to
43
artificially created laboratory conditions that included: (a) wetting specimens with
chloride solution (9.6% NaCl) and storing them at RH=65% at 20˚C; and (b) RH=65% at
20˚C (control). Specimens consisted of reinforced concrete slabs measuring 63 x 19.7 x
4.7 in. (1600 x 500 x 120 mm) and concrete prisms measuring 5.9 x 5.9 x 17.7 in. (150
x 150 x 450 mm) in nominal dimensions.
Slab specimens were notched on both sides, at 200 and 300 mm from the
midspan. Moreover, after curing, each pair of slabs was tied together, and applied a
sustained load in excess of theoretical cracking load in order to produce cracking. Then,
pairs of slab specimens were conditioned in previously described environments. After
four months of exposure specimens were repaired with CFRP laminates and three
types of epoxies. Then, sustained load was increased by 20%, and specimens were
conditioned for additional 12 months. Eventually, slab specimens were tested in three
point bending test setup. Authors noted the highest loss in slab capacity in specimens
conditioned in Dead Sea environment of about 12%. Most of the specimens failed by
debonding of CFRP laminate caused by an intermediate flexural crack. Moreover, a
shift from cohesive to adhesive failure mode was observed in all specimens after
conditioning in severe environments.
Concrete prism specimens were used to perform direct shear test, and were
subjected to the same conditioning and repair protocol as slab specimens. Results from
direct shear tests showed that exposure to severe environments did not have
detrimental effect on FRP-concrete bond.
Frigione et al. (2006) studied the efficiency of bond in concrete joints adhered by
epoxy when affected by moisture. The slant shear tests were performed based on
44
ASMT C882-91. Two different concrete mixes (25 MPa and 50 MPa) and three different
epoxy adhesives used mainly applied to concrete members for different bonding
purposes. Test results for only one of the epoxies will be included, as that is the only
one that can be used to bond CFRP to concrete. Adhesive thickness in concrete-
concrete joint was varied at 0.5, 2, and 5 mm. Shear slant specimens were conditioned
in distilled water at 23±1˚C for 2, 7, 14, and 28 days before testing. Test results
indicated that the bond strength decay plateaus after 14 days of exposure, peaking at
around 35%. Relatively slight decrease in bond strength was observed as the epoxy
thickness was increased.
Figure 3-15. Slant shear test specimen
Fava et al. (2007) used the direct shear test in Mode II loading to assess the
performance of FRP-concrete bond after conditioning in multiple environments. Test
setup essentially follows the one described in Taljsten (1996) and Au and Buyukozturk
(2006). Test specimens were exposed to: (a) standard conditions – at 20˚C and
RH=60%; and (b) one month of salt spray fog at 50˚C. Authors noted an increase in
strength of around 30% in specimens conditioned in salt fog environment when
compared to the specimens kept in standard conditions. They attributed this rise in bond
45
capacity to “beneficial effects on epoxy resin of high humidity level” as found by Wu et
al. (2004).
Figure 3-16. Direct shear test setup
Soudki et al. (2007) tested 11 reinforced concrete beams repaired with CFRP
laminate or wet-layup. Eight beams were precracked before repairing, while the
remaining three beams were kept intact as a control. Each beam was 5.9 in. (150 mm)
wide, 9.8 in. (250 mm) deep and 94.5 in. (2,400 mm) long (Figure 3-17). Beams were
lightly reinforced, with a reinforcing ratio of 0.6%. Control beams were kept at a room
temperature, while the rest of the beams were conditioned in 100, 200 and 300 wet/dry
cycles with a 3% solution of NaCl. One wet/dry cycle lasted two days – one day of
wetting followed by one day of drying. This condition protocol was established to
achieve active corrosion of reinforcing steel in a reasonable time. After exposure
specimens were tested in four-point bending. In addition, corrosion rates of reinforcing
steel, and chloride contents at different depths were measured. Authors noted that all
specimens failed by debonding of FRP followed by a maximum loss in capacity of 11
and 28% for wet-layup sheets and laminates, respectively. Furthermore, CFRP and the
resin system seemed to decrease the corrosion rate of the reinforcing steel.
46
Figure 3-17. Four-point bending test beam design
Silva and Biscaia (2008) developed an experimental program to evaluate the
degradation of bond between FRP and concrete. They tested hinged concrete
specimens in four-point bending. Specimens were conditioned as follows: (a) salt fog
cycles at 35˚C – 16 h dry followed by 8 h of fog; and (b) moisture cycles – RH=20% for
12 h, followed by RH=90% for 12 h. Specimens from the first group were conditioned for
3000 and 6000 h, while the specimens in the second group were exposed for 1000,
5000 and 10,000 hours. Authors noted that failure mode was affected by the exposure
environment. They observed cohesive failure mode in specimens exposed to moisture
cycles, while the specimens conditioned in salt fog cycles experienced adhesive failure
along the interface. However, they noted that both groups of specimen had almost the
same reduction in load capacity of about 20%.
47
Figure 3-18. Hinged beam specimen
48
Garmage et al. (2009) performed a durability study of FRP-concrete bond using
75 x 75 x 250 mm3 reinforced with wet layup CFRP sheets. All specimens were
conditioned at temperature cycles ranging from 20 to 50˚C within 4.5 hours period, with
1.25 hours soaking time at minimum and maximum temperatures. Relative humidity
was kept constant at 90%. Some of the conditioned specimens were subjected to
different levels of sustained loading. As this study is not concerned with effect of
sustained loading on bond performance, findings related to those samples will be
omitted in the literature review. Control samples were not conditioned. Authors tested
specimens in single lap shear test setup after 175, 325, 1250, and 2400 hours of
conditioning and reported a reduction in ultimate load capacity peaking at close to 30%.
Banthia et al. (2010) performed a series of infrared thermography measurements
and pull-off tests on four concrete bridges in Canada that were repaired with FRP
materials. This literature review will include bridges repaired with CFRP only. The
following bridges were included in the study: (a) St. Etienne de Bolton Bridge near
Sherbrooke, QC “exposed to temperatures ranging from -18 to 24˚C, notable amounts
of deicing salts, and physical impact during snow cleaning”; (b) Leslie Street Bridge in
Toronto, ON exposed to varying temperatures (from -10˚C to 27˚C) with multiple
freezing and thawing cycles; (c) Maryland Bridge in Winnipeg, MB exposed to “a
relatively dry climate with temperatures between -23 and 6˚C”. Authors noted that
debonded areas determined based off of thermographs corresponded to areas with
reduced bond strength. Furthermore, they observed that cohesive failures were related
to pull-off strengths higher than 330 psi. Relatively low bond strengths were observed
on Safe Bridge “probably because the geometry of the girders allowed for the infiltration
49
of water behind the FRP layer”. Authors also reported that aside from water infiltration it
was not clear why many of the bond strengths were low. They suspected that the low
values were related to general deterioration; however, this could not be proven as the
initial bond strength data was not obtained.
To determine the sensitivity of FRP-concrete bond to chloride content Pan et al.
(2010) performed direct shear tests on specimens conditioned in water solutions with
the following concentrations of NaCl: (a) 3%, (b) 6%; (c) 10%; and (d) 15%. Specimens
were conditioned for 15, 30, 60, 90, and 120 days. Authors concluded that concrete
compressive strength significantly increases with the immersion time in NaCl solution.
However, the chloride concentration did not have significant effect on the compressive
strength of concrete. Furthermore, authors noted a slight decrease in initial and ultimate
debonding loads after 15 and 30 days of conditioning. Specimens that were conditioned
longer, however, experienced a slight increase in bond strength when compared to
unconditioned samples. Moreover, there was no apparent correlation between the bond
strength and the chloride concentration of the water solution.
Figure 3-19. Direct shear test specimen
50
Dai et al. (2010) performed a study on influence of moisture of concrete surface
during the application of FRP, and in service moisture on performance of FRP-concrete
bond. Authors utilized direct pull-off and bending tests to assess the bond performance
after conditioning for 8, 14 and 24 months in wet-dry cycles consisting of four day
immersion in 60˚C followed by drying for three days in standard laboratory conditions.
Additional variables were: (1) curing conditions after repair (RH=48% vs. RH=90%); (2)
wet vs. dry substrate at the time of repair; (3) normal vs. hydrophilic primer; and (4)
normal vs. ductile adhesive. It should be noted that for the purpose of this research
special form of CFRP, called carbon stranded sheet (CSS), was used. The CSS
consists of 1 to 2 mm in diameter circular carbon microbars, formed by pultruding dry
carbon fibers with epoxy. In pull-off test specimens a loss in capacity of up to 50% was
noted, while the loss in capacity in bending specimens peaked at around 40%. Based
on the results of the experimental program authors concluded the following:
1. Different curing conditions were not of critical importance on the bond capacity.
2. Wet concrete substrate at time of installation detrimentally affected the bond performance, however, only when the normal primer was used.
3. Wet-dry cycling caused shift of failure mode from cohesive to adhesive (between primer and concrete). This may be due to microcracks observed by microscope that formed at the primer-to-concrete interface that formed after wet-dry cycling.
4. No general trend was observed in bond capacity in respect to duration of wet-dry cycling. Bending specimens experienced both increase and decrease in capacity over time of conditioning.
5. Pull-off tests are not indicative of the overall bond condition, because they rather capture the local weaknesses at the interface. Pull-off test is, however, deemed sufficient to provide a conservative estimate of durability of the FRP-concrete bond capacity.
51
Figure 3-20. Three-point bending test setup
Cromwell et al. (2011) investigated influence of multiple aggressive environments
on performance of FRP reinforcement in concrete structures. Authors used two types of
CFRP in their test program: a laminate and a wet-layup system. Test program included
three different types of specimens: (1) tension coupon specimens – prepared as per
ASTM D3039; (2) bond specimens – “two 2 in. (51 mm) concrete cubes spaced 1 in. (25
mm) apart and bonded together using 0.75 in. (19 mm) wide by 5 in. (127 mm) long
FRP strips on opposing faces”; (3) beam flexure (three-point bending) specimens –
concrete beams reinforced with 2 #3 bars at top and bottom and U shaped stirrups
W2.9 spaced at 5.98 in. (152 mm) on center, and the following dimensions
D:W:L=6.1:8:96.1 in (154:203:2440 mm); reinforced with CFRP at the soffit. Specimens
were conditioned in the following environments: (a) water – RH=100% at 38˚C for 1000,
3000, and 10,000 as per ASTM D2247; (b) salt water solution - prepared as per ASTM
D1141, for 1000. 3000, and 10,000 h at 22˚C; (c) alkaline (CaCO3 solution) – at 22˚C for
1000, 3000, and 10,000 h; (d) dry heat - 60˚C in a forced-draft circulation-air furnace as
per ASTM D3045, for 1000 and 3000 h; (e) diesel fuel – immersion in diesel fuel at 22˚C
52
for 4 h as per ASTM C581; (f) weathering – UV340 light at 63˚C for 2 h, followed by
RH=100% at 22˚C for 2 h, for the total of 2000 h (1000 cycles); (g) freeze-heat – cycling
between -18˚C for 15 h, and RH=100% at 38˚C for 15 h (20 cycles in total), following the
exposure to RH=100% at 38˚C for 500 h and drying for 48 h; (h) freeze-thaw cycling –
360 cycles as follows: “(1) 70 min at -18˚C at 30% RH; (2) 20 min ramp up to 4.5˚C
(resulting in 90% RH); (3) 70 min at 4.5˚C at 50% RH with UV lights on; and (4) UV
lights off and 80 min ramp down to -18˚C (resulting in 40% RH)”. Control specimens
were conditioned in standard laboratory relative humidity and temperature. It should be
noted that only beam flexure specimens were exposed to freeze-thaw cycling. Tension
and bond specimens were conditioned in all other aforementioned environments.
Results from tension coupon tests showed that properties of both CFRP laminate and
fabric are not significantly affected by exposure to aggressive environments. In any of
the conditioning environments modulus of elasticity and ultimate did not fall below 95%
and 90% for CFRP laminate and fabric, respectively. Bond specimens showed a much
greater variation in results as well as a higher level of sensitivity to aggressive
environmental conditions. Specimens with bonded CFRP laminate reinforcement
showed the greatest reduction in bond capacity (of close to 20%) after exposure in salt
water for 10,000 h, and dry heat for 1000 h. On the other hand, specimens reinforced
with CFRP fabric proved to be mostly affected by dry heat condition where they showed
a reduction of close to 40% of control bond strength. Beam flexure specimens
experienced very low reductions in strength. Therefore, authors concluded that the
“intermediate-crack (IC) debonding” is unaffected by freeze-thaw cycling.
53
Figure 3-21. Bond test setup
Figure 3-22. Beam flexure specimen
Lai et al. (2009) performed a series of direct shear tests to determine effects of
high temperature and water ingress on durability of FRP-concrete bond. Specimens
were immersed for 5, 15 and 30 weeks in water at the following temperatures: (a) 25˚C;
(b) 40˚C; and (c) 60˚C. By digitally processing the visual images of FRP strips, authors
identified three distinguishing failure modes:
A. Failure in concrete
B. Failure at FRP-epoxy interface
C. Failure within adhesive bonding layer
54
Aside from a decrease in ultimate failure load (of up to 30%), authors observed
increase in average delamination (flaws in adhesive layer that form due to exposure to
aggressive environments) sizes in the 40 ˚C and 60˚C specimens, when compared to
control. In addition to that, they observed a shift from failure mode A in control and the
25˚C specimens, to predominantly failure modes B and C in specimens exposed to 40
and 60˚C, as presented in Table 3-1.
Table 3-1. Distribution of failure modes Exposure temperature (˚C)
Average failure mode (%)
Mode A Mode B Mode C Control 75.3 24.7 0 25 63.8 33.3 2.8 40 58.1 17.4 24.5 60 41.3 32.7 26
55
Figure 3-23. Direct shear test setup
In a different study on durability of FRP-concrete bond when conditioned in water
with elevated temperatures, Lai et al. (2013) used infrared thermography in conjunction
with direct shear test. Based on the thermographs, three distinguishing stages in
debonding process can be identified (Smith and Teng 2002, Colombi et al. 2010):
1. “Elastic stage (no interfacial softening or rupture can be found over the entire interface)”;
56
2. “Elastic-softening stage (local softening starts at the loaded end and some parts of the interfacial bonds become softened while the portion neat the fixed end, remains elastic)”;
3. “Elastic-softening-debonding stage and softening-debonding stage (local rupture of the bond layers happens and propagates from the loaded to the fixed ends)”
From the results of durability study authors noted an early occurrence of the
softening-ruptured state for all specimens that were conditioned at 60˚C. Control, the
25˚C and the 40˚C debonding process commenced with elastic-softening stage. The
degradation due to exposure caused a drop in ultimate shear force capacity from control
to specimens exposed at 60˚C of up to around 30%.
Srestha et al. (2013) examined influence of water on FRP-concrete bond in high
strength concrete by utilizing direct shear pull-off test. They tested specimens made of
normal strength concrete for comparison purposes. Specimens (Figure 3-24) were
immersed in water at 20˚C for up to 12 months. Two types of epoxy (Epoxy E:
combination of Bisphenol-A and Bisphenol-F epoxy resins; and Epoxy F: Bisphenol-A
epoxy resin), and one CFRP fabric were used in the study. Linear dependency of
ultimate bond strength in respect to exposure time was observed, with ultimate values
recorded in Table 3-2. Better performance of bond in lower strength concrete was
explained by differences in surface properties between the two. Namely, high strength
concrete is tightly packed and due to lack of pores and voids does not have much
available surface for transfer of frictional forces, whereas this is not the case in normal
strength concrete. As evidence to support this claim, authors compared the failure
surfaces, which revealed that less concrete debris was found on CFRP that debonded
from concrete surface (Figure 3-25 and Figure 3-26).
57
Table 3-2. Change in ultimate bond strength after 12 months of exposure Normal Strength
Concrete High Strength Concrete
Epoxy E ≈+40% ≈-32% Epoxy F ≈0% ≈-30%
Figure 3-24. Direct sehar test specimen
Figure 3-25. Failure surfaces for normal strength concrete
58
Figure 3-26. Failure surfaces for high strength concrete
59
CHAPTER 4DURABILITY TESTING APPROACH
A material characterization study was performed on epoxies (Stewart 2012) to
determine how the material degradation mechanism changes depending on the
conditioning environment. Epoxy samples were exposed to hygrothermal conditions at
30˚C through 90˚C, and UV radiation combined with high humidity. Stewart (2012)
studied differences in behavior that occurred due to the exposure to the aforementioned
conditions and proposed the following set of conditioning protocols for testing of FRP-
concrete bond:
1. Exposure to water immersion at temperatures that are 15˚C above and below the Tg for 1, 2, and 8 weeks
2. Exposure to UV and water since this condition changed epoxy mechanism of degradation from oxidation to hydrolysis
Based on the recommendations, exposure conditions and exposure times in
Table 4-1 were defined for FRP-concrete bond testing. Five composite systems and two
different concrete strengths were selected for the study. Three specimens per exposure
condition were tested. Three-point bending test was utilized to test FRP-concrete bond
durability (Gartner 2007).
Table 4-1. Summary of conditioning protocols
Exposure Condition Temp. (oC) Exposure Times (weeks)
Number of specimens
Immersed in water 30 1, 2, 8 105
Immersed in water 60 1, 2, 8 105
RH=100% 60 1, 2, 8 90 UV & RH=100% 60 1, 2, 8 15
Test matrix for FRP reinforced concrete samples presented in Figure 4-1 was
created for the purpose of durability study. It should be noted, however, that tests on
60
combined effect of UV and moisture at 60˚C were not performed due to unexpected
circumstances. Concrete strength for al samples was 10,000 psi except for Composite
D which was tested for concrete strengths of 4,000 psi and 10,000 psi. Therefore
designations such “D04” and “D10” signify the corresponding concrete compressive
strength.
1 2 8 1 2 8 1 2 8 1 2 81 in wide bonded
CFRP fabric 0.644 Composite A3 3 3 3 3 3 3 3 3 3 3 3 3 39
1 in wide bonded CFRP fabric 0.618 Composite B 3 3 3 3 3 3 3 3 3 3 3 3 3 39
1 in wide bonded CFRP fabric 0.6 Composite C 3 3 3 3 3 3 3 3 3 3 3 3 3 39
1 in wide bonded CFRP fabric 0.644 Composite D04 3 3 3 3 3 3 3 3 3 3 3 3 3 39
1 in wide bonded CFRP fabric 0.644 Composite D10 3 3 3 3 3 3 3 3 3 3 3 3 3 39
1 cm wide laminate N/A Composite E 3 3 3 3 3 3 3 3 3 3 3 3 36
Tota
l 4,0
00 p
si
Tota
l 10,
000
psi
FRP Reinforcement Material
Immersion + 30C
Exposure time (weeks)
Immersion + 60C
Exposure time (weeks)
Immersion + UV + 60CExposure
time (weeks)
100%RHSystem Fiber Weight (kg/m2) C
ontr
ol
Exposure time (weeks)
Figure 4-1. Test matrix
61
CHAPTER 5DURABILITY TEST SPECIMEN DESIGN AND FABRICATION
Specimen Design
All the concrete specimens had a square cross section measuring 4 in. x 4 in.
and were 14 in. long. This specimen size was deemed adequate to capture the bond
behavior in bending at a small scale. The size was also chosen to match the previous
work conducted at the University of Florida by Gartner et al. (2011). The amount of FRP
reinforcement was picked to enable the debonding failure of the FRP instead of a
concrete shear failure. If too much reinforcement is applied to the specimen the bond
strength cannot be fully utilized and the specimen is likely to fail in shear by reaching
the ultimate shear capacity of concrete. Adequate cross sectional area of surface
bonded FRP was determined based on the available experimental data (Gartner et al.
2011). FRP strips measuring 1 in. in width and 8 in. in length deemed appropriate to
achieve a desired failure mode of the test specimen. In addition, to better simulate the
behavior of FRP in flexural applications, by promoting Mode II loading condition, a 2 in.
deep notch was provided at the specimen midspan to simulate cracked concrete (as
shown in Figure 5-1). Furthermore, notch allows testing beam specimens in a three-
point bending test instead of a four-point bending test because the notch presence
eliminates the need for a constant moment region and reduces the possibility of a shear
failure.
62
Figure 5-1. Three-point bending test setup
4 in. 4 in.
6 in. 6 in.
12 in.
1 in.
4 in.
4 in
.2 in
.2
in.
1 in
.CFRP
notch
63
Three-point Bending Test Bond Strength Index
One of the most important details worth discussion is how the physical value that
is obtained from the three-point bending test relates to the actual bond strength. First, it
should be regarded that bond strength is usually defined in terms of loading condition.
Namely, two most commonly observed loading conditions are Mode I, Mode II, and a
mixture of the two. Mode I or the peel mode starts at the ends of the laminates and
propagates towards the midspan (Figure 5-2). Peeling occurs as a result of the end
offset of FRP reinforcement from the supports, which allows for the ends of FRP
reinforcement to be exposed somewhere along the span. If looked at boundary
conditions in FRP reinforcement at the ends (free end boundary condition) it can be
easily concluded that there is zero curvature at the location. To satisfy the boundary
conditions, and due to the existence of bending stresses in concrete, FRP laminate
needs to bend in the direction opposite to direction of beam bending, which will cause
Mode I loading at the location (Sebastian 2001).
Mode II, on the other hand, is observed in the vicinity of vertical flexural cracks.
According to Sebastian (2001), when concrete’s tensile capacity is reached, flexural
cracks open, which loads the FRP in direct shear (Figure 5-2).
Mixed mode (Figure 5-2) happens as a result of inclined cracks along the span
and is is a function of phase angle ψ (mode mixity parameter - I
II
KK1tan −=ψ ) which is
dependent on crack inclination angle (Sebastian 2001).
With the newly developed anchoring techniques, Mode I loading may be
neglected. Therefore, Mode II crack development is considered the most critical in
flexural FRP applications.
64
Figure 5-2. Loading modes in interfacial region
The purpose of three-point bending test, described previously, is to directly
simulate Mode II loading condition which is deemed representative of the FRP-
reinforced beam behavior when subjected to bending. The quantity recorded from these
tests is the ultimate load that caused failure of the test specimen. Even though the
specimen failure load is not representative of the actual bond stress that caused FRP to
debond, it provides a way to indirectly express the bond strength in flexural applications.
The ultimate exposed specimen failure load normalized to averaged control specimen
failure load will be referred to as bond strength index (BSI). Bond strength index, as
defined here, is representative of both peel mode and Mode II loading conditions, with
Mode II being more dominant. It should be noted that in this study terms such as bond
capacity, bond strength, and bond degradation, when used in relation to three-point
bending test, refer to bond strength index, and not the actual debonding stress.
CFRP Composites
All composite materials used in this study are commercially available by US
manufacturers. In the following subheadings, CFRP composite systems that were used
to reinforce the concrete beam specimens, and corresponding adhesives are described.
Mode I Mixed-modeMode II
65
Composite A is a custom, uni-directional carbon fabric orientated in the 0˚
direction that combined with Adhesive A forms a wet-layup composite system that is
used in infrastructure applications (Table 5-1).
Composite B is a high strength unidirectional carbon fiber fabric that is field
laminated by epoxy to form a carbon fiber reinforced polymer (CFRP). Properties are
specified in Table 5-1.
Composite C consists of Composite C Primer, Composite C Putty, Adhesive C
(Composite C Saturant) and dry fabric constructed of high strength aerospace grade
carbon fibers (Table 5-1):
• Composite C Primer is a low viscosity, 100% solids, polyamine cured epoxy. Being the first component of the system applied to the concrete surface, Primer is used to penetrate the pores of concrete substrate and to provide a high bond base coat for the Composite C system. According to the manufacturer’s product data sheet Primer should be mixed following these ratios: a) 3 parts of component A to 1 part of component B by volume; or b) 100.0 parts of component A to 30.0 parts of component B by weight.
• Composite C Putty is a 100% solid, non-sag paste epoxy material that is applied as a second layer of Composite C system. The purpose of Putty is to level the uneven surfaces before the application of Composite C fibers. Additionally, Putty improves adhesion of subsequent coatings on substrates. Putty shall be mixed according to the following ratios: a) 3 parts of component A to 1 part of component B by volume; or b) 100.0 parts of component A to 30.0 parts of component B by weight.
• Finally, fibers, when saturated with Adhesive C, form a high strength carbon fiber reinforced polymer (CFRP).This material, as stated by the manufacturer, can provide additional strength to concrete, masonry, steel and wood structural elements. Composite D consists of Composite A system carbon fiber fabric and Adhesive D
(Table 5-1).
Composite E a pultruded carbon fiber reinforced polymer (CFRP) laminate.
Composite E is bonded onto the structure as external reinforcement using Adhesive E
(Table 5-1).
66
Table 5-1. Properties of composite systems (information provided by manufacturers) Fabric
weight (g/m2)
Thickness (in)
Ultimate Tensile Strength (psi)
Modulus of Elasticity (106 psi)
Composite A
644 0.04 143,000 13.90
Composite B
618 0.04 123,200 10.24
Composite C
600 0.04-0.06 550,000 33.00
Composite D
644 0.04 n/a n/a
Composite E
n/a 0.047 449,000 23.90
Epoxy Adhesives
Adhesive A is a two component epoxy matrix material for bonding applications. It
a material used in structural applications to provide a wet-layup composite system for
strengthening structural members. Adhesive A provides a long working time, with no
offensive odor. Adhesive A is mixed according to the following ratios: a) 100.0 parts of
component A to 42.0 parts of component B by volume; or b) 100.0 parts of component
A to 34.5 parts of component B by weight. The recommended minimum cure time is 72
hours at 70 F. The preceding description of the material is provided by the
manufacturer.
Table 5-2. Adhesive A mechanical properties 72 hours post cure at 140˚ F (60˚ C) – as reported by the manufacturer
Property ASTM Method Typical Test Value* Tg D4065 180˚ F (82˚ C) Tensile Strength D638 Type 1 10,500 psi Tensile Modulus D638 Type 1 461,000 psi Elongation Percent D638 Type 1 5.0 % Compressive Strength D695 12,500 psi Compressive Modulus D695 465,000,000 psi
67
Adhesive B is a two-component 100% solids, epoxy, that is used as an
impregnating resin with Composite B CFRP fabric; and as a seal coat and impregnating
resin for horizontal and vertical applications. The recommended minimum cure time is
14 days at normal ambient conditions (73˚ F and 50% R. H.).
Table 5-3. Adhesive B mechanical properties (14 day cure at 73˚F (23˚C) and 50% R.H.) – as reported by the manufacturer
Property ASTM Method Typical Test Value* Tg D4065 46 Tensile Strength D638 8,000 psi Tensile Modulus D638 250,000 psi Elongation Percent D638 3.0 % Compressive Strength D695 N/A Compressive Modulus D695 N/A
Adhesive C is a 100% solids, low viscosity epoxy material that is used to saturate
the fibers of Composite C to form a carbon fiber reinforcing laminate (CFRP). Physical
properties of Adhesive C are provided Table 5-4.
Table 5-4. Adhesive C mechanical properties (based on cured samples at 72˚F (20˚C) and 40% R.H.) – as reported by the manufacturer
Tg D4065 163˚F (71˚C) Tensile Strength D638 8,000 psi Tensile Modulus D638 440,000 psi Elongation Percent D638 3.5 % Compressive Strength (28 day)
D695 12,500 psi
Compressive Modulus (7 day) D695 380,000 psi Adhesive D is a two-part epoxy with a known chemical composition, comprised of
diglycidyl ether of bisphenol A (DGEBA) and poly(oxypropylene) diamine (POPDA). The
mix ratio of DGEBA to POPDA was 100 to 32.9.
Adhesive E is a 2-component, 100% solids, structural epoxy paste adhesive.
This adhesive conforms to the current ASTM C881 and AASHTO M-235 specifications.
The epoxy is used as an adhesive for bonding external reinforcement to concrete,
masonry, steel, wood, stone, etc., structural bonding of composite laminates, structural
68
bonding of steel laminate