View
243
Download
2
Tags:
Embed Size (px)
DESCRIPTION
The Smart Grid is coming! But unfortunately most existing buildings cannot talk with the Smart Grid. Instead, most have pneumatic HVAC controls and lighting circuits that cannot respond to dynamic pricing signals or demand response events. Retrofitting them with conventional technologies is prohibitively costly and disruptive to occupants.In this session, Harry Sim, CEO of Cypress Envirosystems, will discuss new retrofit solutions that cost up to 80% less, do not disrupt occupants, and have a very good payback.
Citation preview
Making Dumb Buildings
“Smart”Harry Sim
CEO, Cypress Envirosystems
V4.0 081114
“Smart” Buildings
Typical Existing Buildings Today
Dial Gauges
Standalone Transducers,LED/LCD Displays
Pneumatic Thermostats
Manual Instrumentation, Not Programmable, No Diagnostics…
Equals: Wasted Energy, Higher Downtime, More Labor Required
Steam Traps
-80C FreezersUninterruptiblePower Supplies
Why Still So Many “Pneumatic” Buildings?
• High Cost
– Replace pneumatic piping with electrical wiring
– Replace pneumatic actuators with electric actuators
– Must go behind walls, above ceilings
– Lots of labor
– Market rate of $2500 - $3000 per zone for traditional DDC retrofit
– Payback of 4-7 years typical
• Disruptive to Tenants
– Exposure to Potential hazardous/toxic materials (e.g. Asbestos)
– Retrofits often happen only when there is tenant churn or other major
renovation
Most buildings built before 1995 are still pneumatically controlled,
or up to 70% of the commercial built environment.
What are the Consequences?
• Waste Energy
– No zone control for night setback, occupancy override, optimal
start/stop
– No ability to participate in Auto-Demand response or similar load
management strategies
– Out of calibration stats do not control temperature correctly
• More Labor for Maintenance
– Manual calibration of pneumatics
– Difficult to troubleshoot with no diagnostics, sensors
• Unhappy Tenants
– Building manager does not know of problem until tenant calls
– Many thermostats set at maximum or minimum – do not function
Real Impact to Energy Costs, Maintenance Costs, Tenant Satisfaction
Problem Right Here in Silicon Valley
• County of Santa Clara, Social Services Administration• 2 Buildings, each 5 story, built 2000• Total 300,000 sq-ft• 350 Pneumatic Thermostats, non-communicating• Estimated Demand Response load shed: 200kW• Would like to participate in PG&E Auto-DR program,
but challenging with pneumatic thermostats
But Can’t We do Something?!!
Silicon Valley
High Tech
Silicon Valley
Built Environment
40 Year Gap in Technology Co-Existing in Same Area
• Manual Setpoint Control
• No Remote Readings
• No Diagnostics
• Manual Calibration
Required
• Cannot support Demand
Response strategies
DDC in 20 Minutes!
New Technology to Enable Retrofit
Requires about 20% the cost and 10% of the time
compared to traditional DDC Retrofit
• Remote Wireless Setpoint Control
• Remote Monitoring of Temp & Pressure
• Pager/Cell Notification of Excursions
• Automatic Self-calibration
• Programmable Temperature Setbacks
• Occupancy Override
• Enables Demand Response strategies
• BACnet Interface to BMS
• 2yr+ battery life
Replacement in under 20 minutes
Project Comparison with DDC Retrofit
Santa Clara County Government Project
Tapping Utility Auto-DR Incentives
• Open A-DR communications link developed by Lawrence Berkeley National Labs.
• PG&E Technical Incentive 2009:• $230/kW for equipment and
installation• $20/kW for participant
incentive• $50/kW for Technical
Coordinator
Incentives Can Help Pay for Cost of Retrofit
Automating Gauge Reading
Non-Intrusive Reader Mounts On Top of Existing Gauge in Minutes…
Enables Alarming, Trending, Historization for Process/Asset Monitoring and Troubleshooting
• Thousands of gauges on Air Handlers, Boilers, Chillers, Heat Exchangers…
• Energy Savings Applications e.g.
– Compressed Air – ramp down compressor
– Audits for current, steam/water pressure, temp, flow
• Improved Equipment Uptime via Monitoring
– Filter changeouts (measure delta P)
– Pumps, compressors, fans (measure delta P)
• Reduced troubleshooting cost
– Fast non-invasive data gathering/logging/alarming
• Safety/Compliance
– Avoid difficult to reach or hazardous locations
– Monitor exhaust/venting (e.g. Magnehelic gauge)
• Reduce labor and consumable costs
– Gas Cylinders
Detecting Steam Trap Leaks
• Necessary part of the steam
distribution system, usually hundreds
of units per site
• 15-20% average failure rate;
leaks steam
• Failed traps lose $5-10K per year
• Wireless device clamps on non-
invasively and monitors trap health
for early detection and resolution.
• Typically less than one year payback
on investment.
Typical Steam TrapLeaking Traps Waste Energy
Save Energy and Time Locating Faulty Steam Traps
Connectivity to Existing Automation
Ethernet
BAS Controller
BACnet/IP
PC with Browser PC with Browser
Honeywell Building
Solutions
Honeywell ECC
Wixom, MI
Golden Valley, MNExcel EBI,
Tridium
Important to Work With Existing Automation…
Avoid: New Headend, New Software, Retraining of Staff