62
Libra Meter – MeterBuddy2 Handbook ANSI_3C MeterBuddy 2.2, The Program Tool of Libra Meter, obey ANSI C12.18-1996 and C12.19-1997 Greta Song 2012-8-10

Libra meter meter buddy handbook

Embed Size (px)

Citation preview

Page 1: Libra meter   meter buddy handbook

Libra Meter –

MeterBuddy2 Handbook

ANSI_3C

MeterBuddy 2.2, The Program Tool of Libra Meter, obey

ANSI C12.18-1996 and C12.19-1997

Greta Song

2012-8-10

Page 2: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

2 / 62

The information contained in this document is subject to change without notice.

WASION makes no warranty of any kind with regard to this material, including, but

not limited to, the implied warranties of merchantability and fitness for a particular

purpose. WASION will not be liable for errors contained herein or incidental

consequential damages in connection with the furnishing, performance, or use of

this material.

This document contains proprietary information that is protected by copyright. All

rights are reserved. No part of this document may be photocopied or otherwise

reproduced without consent of WASION.

Copyright© 2007-2012 by WASION

Published in a limited copyright sense, and all rights, including trade secrets are

reserved.

Document Edition – First 11/2007, Last 8/2012

Oversea D&R Department

Wasion GroupLimited

Hunan Province, China

Page 3: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

3 / 62

TABLE OF CONTENTS

1.0 Foreword ............................................................................................................... 5

2.0 Reference Documents ...................................................................................... 5

3.0 Requirement ........................................................................................................ 5

4.0 Software Setup .................................................................................................... 5

5.0 Operate guidline ................................................................................................ 7

5.1 Main Window Menu ................................................................................................... 8

5.2 Toolbar........................................................................................................................... 9

5.3 Connect MeterBuddy to Meter ............................................................................ 10

5.4 Editor Window ........................................................................................................... 14 5.4.1 Editor Window Menu .......................................................................................................................................... 15 5.4.2 Meter Image file .................................................................................................................................................. 15

5.5 Meter Window ........................................................................................................... 17 5.5.1 Meter Window Right Button Popup Menu .................................................................................................... 17 5.5.2 Read and Program Meter .................................................................................................................................. 19 5.5.3 Vector Diagram ................................................................................................................................................... 20

5.6 Date and Time Dialog ............................................................................................ 21

5.7 Input Meter Identification .................................................................................... 22

5.8 About MeterBuddy Dialog .................................................................................... 23

6.0 Program Libra-3 Meter .................................................................................. 23

6.1 Meter Info ................................................................................................................... 24

6.2 Nameplate ................................................................................................................... 25

6.3 Parameters ................................................................................................................. 28

6.4 Calibration .................................................................................................................. 28

6.5 Demand ....................................................................................................................... 29 6.5.1 NORMAL MODE .................................................................................................................................................... 29

6.5.1.1 Demand setting parameters. ............................................................................................................................... 29 6.5.1.2 Program Parameters to meter .............................................................................................................................. 30 6.5.1.3 Read Current Register Data about Demand ......................................................................................................... 30

6.5.2 TEST MODE ........................................................................................................................................................... 31 6.5.3 DEMAND RESET ................................................................................................................................................... 31

6.5.3.1 Demand Reset mode .......................................................................................................................................... 31 6.5.3.2 Read Previous Demand Reset Data .................................................................................................................... 32

6.6 Security Control ....................................................................................................... 33

6.7 LCD Menu .................................................................................................................... 33 6.7.1 Read current LCD Display Control ................................................................................................................. 35 6.7.2 Setting new LCD Display Parameter .............................................................................................................. 35 6.7.3 Read the programmable value ........................................................................................................................ 37 6.7.4 Displayable Data and It’s Menu ID ................................................................................................................. 37

7.0 Time Of Use ....................................................................................................... 37

Page 4: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

4 / 62

7.1.1 Overview ................................................................................................................................................................ 37 7.1.2 Enable TOU control ............................................................................................................................................ 40 7.1.3 Change Season & SCHEDULE according to ID_MATRIX. .......................................................................... 40

7.1.3.1 Change Season .................................................................................................................................................... 40 7.1.3.1.1 Non-Recurring Calendar ................................................................................................................................ 40 7.1.3.1.2 Fixed-Recurring Calendar .............................................................................................................................. 41

7.1.3.2 SCHEDULE according to ID_MATRIX. ........................................................................................................... 42 7.1.3.2.1 Search ID_MATRIX with Season & Day_Type......................................................................................... 42 7.1.3.2.2 Set SCHEDULE Tier with D_MATRIX ...................................................................................................... 42

7.1.3.3 Setting Notes ....................................................................................................................................................... 43 7.1.4 Read Real Time Clock ........................................................................................................................................ 44

8.0 Test Mode ........................................................................................................... 44

9.0 History & Event Logs...................................................................................... 45 9.1.1 Event LogsControl ............................................................................................................................................. 45

9.1.1.1 Event logs Enable ............................................................................................................................................... 45 9.1.1.2 Event Types ........................................................................................................................................................ 46 9.1.1.3 The threshold setting ........................................................................................................................................... 47

9.1.2 Read Event Data .................................................................................................................................................. 48 9.1.2.1 Config Monitored Events .................................................................................................................................... 48 9.1.2.2 Read Event logs record ...................................................................................................................................... 48

10.0 Load Profile ........................................................................................................ 49

10.1 Operation block diagram .................................................................................. 50

10.2 LP Settings Parameters ...................................................................................... 51

10.3 Program Parameters to meter ........................................................................ 51

10.4 Reset LP Data ......................................................................................................... 52

10.5 Re-start LP Data ................................................................................................... 53

10.6 Read LP Data ......................................................................................................... 53 10.6.1 Set LP Data Source............................................................................................................................................. 53 10.6.2 LP Data Source default ...................................................................................................................................... 54 10.6.3 Manufacturer Specific LP Data Source Tables ............................................................................................. 56 10.6.4 Read Daily LP Data ............................................................................................................................................ 58 10.6.5 Daily LP Data Bar-diagram ............................................................................................................................... 59

Appendix :Error Functional cod Specifications .......................................... 60

Page 5: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

5 / 62

1.0 Foreword

MeterBuddy 2.2, The Program Tool of Libra Meter, obey ANSI C12.18-1996 ,C12.19-

1997 .

The software is used to debug, test, read and program the Libra Meter. This is a full

version which includes all function. When it is provided to end-user, we will publish

a simple version which incluses basic function.

This document applies to the implementation of an ANSI C12.19 Standard Sub Set

inLIBRA_WASION _Meter AMR Test tool - MeterBuddy.

(LIBRA_WASION_Meter is an upgrade version of the Libra Meter, Designed for LIBRA

IEC Meter Project, so the MeterBuddy can be used to Test LibraI , LibraII and Libra III)

2.0 Reference Documents

Proposed AEIC Guidelines for implementation of ANSI, C12.19-1997, C12.18-

1996

ANSI C12-19-1997 American National standard Utility Industry End Device Data

Table.

Refer to “LIBRAMeter C12.19 Implementation Specification.doc”

Refer to “LIBRAMeter Handbook.doc”

3.0 Requirement

Operation System:

Windows Xp SP2, Win7 or newer version

Hardware Requirements and Version:

Computer: Pentium (PC586) or better

Memory: 32M at least.

Hard disk: 100M

CD ROM: 1

17-inch color CRT or LCD: 1, 1024*768dpi

Printer: 1(no requirements for the type)

Interface: Two RS232 at least.

4.0 Software Setup

1, Click the “Setup for MeterBuddy.exe” icon to startup.

2, Select installation folder, then click Next to continue.

Page 6: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

6 / 62

3, Click [Finish] to exit the installer.

Page 7: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

7 / 62

9, On your desktop, there are one new icon:

MeterBuddy, Libra AMR tools.

5.0 Operate guidline

When the software startup firstly, it will spend some time to load all module into RAM.

Figure 5.1 is the main window of MeterBuddy. This is a muti-window software,

MeterBuddy has 2 sub windows:

1)Editor Window : Edit the program file.

2)Communication Window: Connect to meter via optical port.

The tool is designed as a classical windows software.

Page 8: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

8 / 62

Figure 5.1, The main window of MeterBuddy

5.1 Main Window Menu

[Editor] Open program Editor window.

[Start Communication] Startup communication with meter.

Menu

Toolbar

Multi window

Status Bar

Page 9: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

9 / 62

[Stop Communication] Stop communication with meter.

[Exit] Exit MeterBuddy

Click [Start Communication] will open Communication dialog.

This dialog is used to set the communication parameters.

Figure 5.2, The dialog of communication parameters

After you complete the parameter setting and password inputing, Click [Start

Communication] button to continue.

The menu [Meter] will be enabled.

[Meter] Open a meter image file and connect, then open Meter Window.

Help and about dialog.

5.2 Toolbar

The toolbar list some shortcut key of menu. Refer to 5.1 Section.

Page 10: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

10 / 62

5.3 Connect MeterBuddy to Meter

MeterBuddy is a software tool developped for general debugging, meter reading and

configuration of the meter through far IR comm port of meter as well as UART port

of AMR module, see the figure below.

Refer to “LIBRA_WASION_Meter Handbook.doc”, use the Wasion Multi-Function

Communicate Cable (Type: WH109-1) to Link MeterBuddy and Meter.

MeterBuddy RS232-TTLMeter

RS232-Optical Port

Optical Port

UART Port

Figure 5.3, Link Diagram

Click [Start Communication] will open Communication dialog.

This dialog is used to select communication type and set the communication

parameters.

Page 11: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

11 / 62

Click [Settings…] to open extend settings view below:

Figure 5.4, Setting dialog of Optical Communication

Click [TCPIP Setting | Discoverer] to open TCPIP discoverer extend view below:

In the extend view, click [Discover] button to discover sub-net and list all of the

device.

Page 12: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

12 / 62

Figure 5.5, Setting dialog of TCP/IP

If you select [Zigbee] mode and [Ethernet+Zigbee] checkbox, Click [TCPIP Setting |

Discoverer] to open TCPIP discoverer extend view below:

Figure 5.6,Setting dialog of Zigbee

In the extend view, click [Discover] button to discover sub-net (include Zigbee Mesh

network) and list all of the device.

When the [Discover] button is clicked, this application will transmit a broadcast UDP

packet containing the message –“Discovery: Who is out there?” on the local network

to port 30303. Any Libra meters which include LibraDigiEth module and connect to

Page 13: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

13 / 62

the network, they will respond with a UDP packet containing their host name and

MAC address.

Double click a IP Address then copy it to IP input box. Caution: this function can

only discover the Libra device in the same subnet of computer.

Click [Read Meter ID] button to read the meter’s Identification according to the IP

Address.

After you complete the parameter setting and password inputing, Click [Start]

button to continue.

The menu [Meter] will be enabled.

Because the BaudRate of two kinds of ports are different, so you should make some

changes as below.

1) Remote or Local IR

2) PLC Port (UART port of AMR/AMI module)

Other Settings:

Libra-1,3 seris can only support Local Optical Port, Libra-2 seris can support

both Local and Remote Optical port. You should select the optical type before

you connect MeterBuddy to meter.

Page 14: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

14 / 62

When you use Remote Optical Port or RS485 connect to meter, you should set

the meters Address here.

The Address is the last two digits of the meter ID which is printed on the

Nameplate of meter.

When you connect to a meter (include LibraDigiEth card) via Ethernet (or Ethernet

+ Zigbee Mesh Network), you should input the meter’s IP Address and TCP port.

ANSI C12.18-1996, Type2 Optical Port standard. The protocol is used for Local

or Remote optical port, and can be used for Ethernet communication too when

LibraDigiEth works as a Ethernet Extender.

ANSI C12.22-2007, Network Data Communication Protocol.

5.4 Editor Window

This window is used to edit the program files which can be download to meter in

Meter Window.

Click the Main Window Menu [File | Editor] to open the Editor Window.

Page 15: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

15 / 62

Figure 5.7, Editor Window

5.4.1 Editor Window Menu

[Open]Open the file and edit.

[Save as…] Save the file as other name.

[Close] Close Editor Window.

5.4.2 Meter Image file

After click the [Meter] menu, Automatic testing will execute orderly: Reading Meter

Type, Reading Meter ID,Reading FORM,Reading Hardware Version,Reading Firmware

Version.

Page 16: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

16 / 62

When Reading Status table, Open image file dialog will display.

The image file name format: Type + Version .txt. e.g: Libra-3cV1.0 FW2.0.txt.

Note:select“Libra-3cV1.0 FW2.0.txt”for Ecuador

Caution:

1) Please confirm the type is same with the meter which you want to connect.

2) You can use Notepad or similar application to re-edit them base on the

document “Libra meter c12.19 implementation”.

Page 17: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

17 / 62

3) The file can be used to save the datas which are read from meter. Please use

“Save as …” command.

5.5 Meter Window

Click the Main Window Menu [Meter] to switch or open the Meter Window. Refer to

“LIBRAMeter Handbook.doc”.

Meter Window supports to edit parameters, read meter and program meter.

Figure 5.8, Meter Window

5.5.1 Meter Window Right Button Popup Menu

Click Right Button on Root, then active a popup menu, click [Read Current Decade].

Basic Information

Decade

Table

Caution and Error

Meter Window

Cell

Page 18: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

18 / 62

Click Right Button on Node, then active a popup menu, click [Read Current Table].

Click Right Button on Cell, then active a popup menu, click [Read Current Cell].

Page 19: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

19 / 62

5.5.2 Read and Program Meter

At the Meter Window, you can Read or Program a Meter with Cell, Table Decade or

All Tables.

The above figure is an example of Libra-3 meter.

Current Cell is [Libra-3cV1.0 | Program | Meter Info | Meter ID | Current Settings].

Current Table is [Libra-3c V1.0 | Program | Meter Info].

Current Decade is [Libra-3c V1.0 | Program].

All Tables is [Libra-3c V1.0].

Double click a Cell, if the the Cell is writable, there will be a textbox to receive your

typewriting.

Page 20: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

20 / 62

Change the value then Click Enter Keyboad to confirm. And send [Program Current

Cell] to download the value to meter immediately.

You can use the menu [File | Save as…] to save the image file to harddisk, then use

the menu [File | Open] to read back.if you want to program several meters on

different computer, this feathure is very useful.

Use the same method, you can read parameters from one meter, then program the

same parameters to other meter.

5.5.3 Vector Diagram (Only for Libra-3 Polyphase type)

Click the menu [Tool | Vector Diagram] to open the Vector Diagram window.

Then Click Menu [Read | Start Timer Reading] to click refresh automatically.

Page 21: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

21 / 62

You can read [Instantaneous Data] and Vector Diagram synchronous.

Click [Yes] to read synchronous.

5.6 Date and Time Dialog

Click the menu [Program| Date and Time] or the toolbar [Date] to open

the Date and Time dialog. User can use the dialog to modify the date of meter.

Page 22: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

22 / 62

Figure 5.9, Date and Time Dialog

5.7 Input Meter Identification

Click the toolbar [Ident] to open the dialog.

Page 23: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

23 / 62

Figure 5.10, ID Dialog

An identical way :Click menu [Program| Meter ID ] to open the dialog.

5.8 About MeterBuddy Dialog

Click the toolbar [Help] to open the dialog.

Figure 5.11 About Dialog

6.0 Program Libra-3 Meter

MeterBuddy supports to program meter such as LCD Menu, Meter Info, Demand,

TOU etc.This chapter takes several examples to discribe that how to program a

meter.

At the Meter Window, there is a node which named as “Program” at the treeview.

Click the node to expande, then there are several tables for program a meter.

Page 24: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

24 / 62

Note: the below is the example of Libra-3cV1.0 type meter. The operation method is

samed on other types.

6.1 Meter Info

Meter Information table [Table 01 – General Manufacturer Identification] dictated by

ANSI C12.19.

Page 25: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

25 / 62

6.2 Nameplate

Meter Nameplate table[Table 02 - Device Nameplate] dictated by ANSI C12.19.

Note: the setting values on “Elements” and “Volts” obey ANSI C12.19-2008.Following

chapter describe Data parsing details .

Elements:

Page 26: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

26 / 62

Volts:

Page 27: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

27 / 62

Page 28: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

28 / 62

6.3 Parameters

Parts of Meter running parameters table[Table 03 – Meter Parameters Table]

dictated by ANSI C12.19.

6.4 Calibration

This table is used to calibrate meter, don’t change without Wasion permission.

Parts of Meter calibration parameters table. This table is used to calibrate the meter.

[Table 06 – Utility information Table] dictated by ANSI C12.19.

Page 29: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

29 / 62

6.5 Demand

Demand operation includes setting parameter, reading Demand data and Deman-

reset which can be executed in Normal Mode or Test Mode.

Demand data is transported in the format dictated by ANSI C12.19.

Meter can be measured maximum active demand and date and time of EVENT,

Cumulative demand, maximum demand of 4 rates and data and time, sub-

interval time, etc.

Demand data support rewritable

The meter can be recalculated in accordance with the new set of parameters

automatically

Demand and the clock synchronization

6.5.1 NORMAL MODE

6.5.1.1 Demand setting parameters.

This table is used to set demand working parameters. The meaning of parameter

dictated by ANSI C12.19 Table 13- Demand Control Table. Demand Control, is used

to specify information affecting demand, such as interval size, reset exclusion, etc.

Notes: If no special requirements , the above four parameters, generally do not need

to set. If the meter to detect the error about parameters of the demand , it will

initialize the parameters to default values. the default value is 0.

Sub_Int, for Sliding demand, the value of minutes in the sub-interval. The value

is set from 1 to 15.

Int_Multiplier, for Sliding demand, minutes of multiplier.

Valid Demand Interval Length/Interval Multiplier Combinations

The valid interval lengths appear in the first column; interval multipliers are

listed across the top row. The intersection of any row/column will show a valid

subinterval size or '√' to indicate that the combination is supported.

Page 30: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

30 / 62

1 2 3 4 5 6 10 15 20 30 60

1(block demand) √ √ √ √ √ √ √ √ √ √ √

2 √ √ √ √ √ √ √ √

3 √ √ √ √ √ √

4 √ √ √ √

5 √ √ √ √

6 √ √ √ √

10 √ √ √ √

12 √ √

15 √ √ √

6.5.1.2 Program Parameters to meter

The reader/programmer inputs 1 to Interval Length value,then clock [Progam

Current Cell].

This dialog is used to indicate set successfully.

6.5.1.3 Read Current Register Data about Demand

After clock [Read Current Table],then the data is fllowing:

Page 31: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

31 / 62

This table is used to read [Current Register Data ]about Demand that can be

described in [Table 23 – Current Register Data] dictated by ANSI C12.19.

.

6.5.2 TEST MODE

Operation on Test mode of to be extended

6.5.3 DEMAND RESET

Meter record maximum demand automatically ,and Demand reset need be taken

automatically or manually to ensure measure demand correctly.

After Demand Reset completely, the number plus one automatically. If the

number exceeds 255 , the number value of demand reset will be restart at 0 to

ccumulate again.

Each of reset takes the amount of energy and demand data are automatically

saved .

6.5.3.1 Demand Reset mode

Demand Reset can be romote, local and TOU. Execution will be described as follows:

Local, Long keys demand reset button more than 3s , LCD full screen flash once , the demand will be reset .

Page 32: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

32 / 62

Romote, demand reset cab be executed by MeterBuddy.

Clock[Y],demand reset will occur.This dialog is used to indicate reset successfully.

The value[Number of Demand Rsets] of Current Register Data will plus one.

TOU , TOU settings can make the demand reset automatically which occurs at a

specific time ..

6.5.3.2 Read Previous Demand Reset Data

If the NBR_DEMAND_RESETS field in Table 23 is 0, the data in this table is not valid.

Data in this table is a snapshot of the current data table (Table 23) at the time of the

demand reset, with the exception of the CUM_DEMAND and rate data, which is

updated before the data is saved. Data items is samed with [Current Register Data ]

The form of [Previous Demand Reset Data] refer to [Table 25- Previous Demand

Reset Data Table] dictated by ANSI C12.19.

Page 33: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

33 / 62

6.6 Security Control

This table is used to set password of meter, only Master can set password. [Table 08

– Security Table] dictated by ANSI C12.19.

Note:This table can be edited-only with password, ReadDecade, ReadTable and

ReadCell are disable.

6.7 LCD Menu

Libra3C support display control , display source index and display table dictated in

ANSIC1219. Libra-3 meter can support 64 items of LCD display Screen. Libra-3

meter can support 78 ID.

Display mode , Display order ,Display format can be set separately . Which all

support the display format of the following form:

Alpha Display (MENU ID) DISP_FORMAT

Character Code Number (ASC II

Equivalent) Value Description Value Description

Page 34: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

34 / 62

fig All are support

(0 – 9)

0x01 Scale by 0.01

Format by xxxxx.x

0x10 Scale by 1

Format by xxxxxx

Capital All are support

(ABCD……XYZ)

0x02 Scale by 0.01

Format by xxxx.xx

0x11 Scale by 10

Format by xxxxx.x

lowercase Only support

a,b,c

0x03 Scale by 0.001

Format by xxxxxx

0x12 Date: YY MM DD

0x04 Scale by 1

Format by xxx.xxx 0x13

Time: HH MM SS

0x05 Scale by 10

Format by xxxxxx 0x14

Meter id : Char[6]

0x06 Scale by 1

Format by xxxx.xx 0x15

Time: HH MM

0x16 Date: MM DD YY

0x17 Date: DD MM YY

0xFF Means Format be

fixed

[Tables 30 & 31- Dimension Limiting & Actual Display ] give a detailed description on LCD display dictated in ANSI C 12.19.

[Table 32 – Display Source],This table contains manufacturer-defined display

sources. The size of this table is limited by memory availability; therefore, it

must be programmed with the subset (maximum of 64 sources) of display

sources actually referenced in Table 33, rather than the complete set of defined

sources.

Notes: See Chapter 6.7.3 of ’Libra3C handbook.doc’ for a complete list of items

available for display (MENU_ID).

LCD Menu can be programmed by Meterbuddy, there are 2 tables which are used for

display program duty.

LCD Display

LCD Display Control

Page 35: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

35 / 62

6.7.1 Read current LCD Display Control

This table is used to define 3 display modes of LCD.

Normal Mode

ALT Mode

Test Mode

Refer to “Libra-3cV1.0 Mutifunction Meter Handbook.pdf” chapter 2.3.2.

On Time (Sec), LCD on time is programmabel in Libra-3.

Number of Screen, display the number of screen corresponding to different

modes. The value is current actual number of screen in meter.

6.7.2 Setting new LCD Display Parameter

LCD Display Screen, LCD on time is programmabel in Libra-3. the prameter is

used to set the number of screen with each display mode, which will define the

mode position of Primary Display List Table.

ID, Refer to “Libra-3cV1.0 Mutifunction Meter Handbook.pdf” chapter 2.3.4.

Items,Refer to “Libra-3cV1.0 Mutifunction Meter Handbook.pdf” chapter 2.3.4.

Format, It is used to define the display format of quantity.

Mode, Normal Mode,Alternate Mode,Test Mode can be set one by one. Either of

the two modes which are Normal Mode and Alternate Mode must be given.

For example,user need to set 3 screens of Normal Mode, 5 screens of Alternate

Mode, And 2 screens of Test Mode. All Form are [03].Values of ID &Items are be

from 0 to 12.

Page 36: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

36 / 62

After set successfully, the imageis used to program the setting value download

to meter.

Notes: the 64 -screen all to be compiled Only when program ‘Mode’to meter.

The dialog is to describe program successfully.

Page 37: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

37 / 62

6.7.3 Read the programmable value

The image can be given the information about progamable parameter.

6.7.4 Displayable Data and It’s Menu ID

Note: The selection and delay value are the default setting in factory.

The table gives parts of Display Data. The remaining data refer to the

manual’Libra3C handbook.doc’.

7.0 Time Of Use

7.1.1 Overview

MeterBuddy supports to program Time Of Use(TOU), such as Real Time Clock,TOU

Control,Non-Recurring Calendar, Fixed-Recurring Calendar and Schedule. This

chapter takes several examples to discribe that how to program TOU.

The maximum total number of dates supported is 32, distributed between

recurring and non-recurring dates as desired. The meter require that the dates

be sorted(Small to large)

Tier switches must be sorted. Tiers must be grouped by daily schedule ID's and

sorted by time within each ID group.

TOU support maximum : 8 non-recurring dates, 32 recurring dates, 64 tier

switches( each DAILY_SCHEDULE_ID_MATRIX include 4 schedule tiers ),4

changed seasons, 4 day-type, 1 special schedule, 4 schedule

tiers(PEAK,BASE,REDUCE,VALLEY).

Page 38: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

38 / 62

Season changed can be permitted one time per day ,and data in accordance

with changed season save automatically.

This table [Table 50- Dimension Time of Use Table]will only be present when

the meter is in TOU or Demand/LP mode.

Field Name Description Size/Units Value Default Progr’m’ble Readable

TIME_FUNC_FLAG1

TOU_SELF_READ_FLAG Indicates whether

device is using TOU-

triggered self-reads.

(0 = False, 1 = True)

1 bit 1 1 No Yes

SEASON_SELF_READ_FLAG Indicates whether

device is performing

a self-read at season

change. (0 = False, 1

= True)

1 bit 0 or 1 0 Yes Yes

SEASON_DEMAND_RESET_FLA

G

Indicates whether

device is performing

an automatic

demand reset at

season change. (0 =

False, 1 = True)

1 bit 0 or 1 0 Yes Yes

SEASON_CHNG_ARMED_FLAG Indicates whether

device is configured

to arm season

changes, which then

occur on the next

demand reset. (0 =

False, 1 = True)

1 bit 0 0 No Yes

SORT_DATES_FLAG Indicates whether

device presorting of

non-recurring dates

has been done. (0 =

False, 1 = True)

1 bit 0 0 No Yes

ANCHOR_DATE_FLAG Indicates whether

device is using

anchor dates. (0 =

False, 1 = True)

1 bit 0 0 No Yes

FILLER 2 bits 0 0 No Yes

TIME_FUNC_FLAG2

CAP_DST_AUTO_FLAG Indicates whether

device is handling

daylight savings time

changes

independent of dates

1 bit 0 0 No Yes

Page 39: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

39 / 62

supplied in the

CALENDAR_TBL. (0

= False, 1 = True)

SEPARATE_WEEKDAYS_FLAG Indicates whether

device is supporting

a different schedule

for each of the 5

weekdays. (0 =

False, 1 = True)

1 bit 0 0 No Yes

SEPARATE_SUM_DEMANDS_F

LAG

Indicates if device is

of switching

summation and

demands

independently. (0 =

False, 1 = True)

1 bit 0 0 No Yes

SORT_TIER_SWITCHES_FLAG Indicates if device

requires tier switches

to be presorted. (0 =

False, 1 = True)

1 bit 1 1 No Yes

CAP_TM_ZN_OFFSET_FLAG Indicates whether

device supports time

zone offsets. (0 =

False, 1 = True)

1 bit 0 0 No Yes

FILLER 3 bits 0 0 No Yes

CALENDAR_BFLD

NBR_SEASONS Number of seasons

in use in the device.

4 bits 4 4 No Yes

NBR_SPECIAL_SCHED Number of special

schedules in use in

the device.

4 bits 1 1 No Yes

NBR_NON_RECURR_DATES Number of non-

recurring dates in

use in the device.

1 byte 8 8 No Yes

NBR_RECURR_DATES Number of recurring

dates in use in the

device.

1 byte 32 32 No Yes

NBR_TIER_SWITCHES Number of tier

switches in use in

the device.

2 bytes 64 64 Yes

CALENDAR_TBL_SIZE Size in bytes of the

CALENDAR_TBL

(Table 54)

2 bytes 328

max

- No Yes

TOTAL SIZE 9 bytes 2 bytes -

Page 40: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

40 / 62

7.1.2 Enable TOU control

The Table give parameters to enable TOU control. Other parameters can be

referred [Table 51- Actual Time of Use Table].

Field Name Description Size/Units Value Default Progr’m’ble Readable

TIME_FUNC_FLAG1

TOU_SELF_READ_FLAG Indicates whether

device is using TOU-

triggered self-reads.

(0 = False, 1 = True)

1 bit 1 1 No Yes

SEASON_SELF_READ_FLAG Indicates whether

device is performing

a self-read at season

change. (0 = False,

1 = True)

1 bit 0 or 1 0 Yes Yes

SEASON_DEMAND_RESET_FL

AG

Indicates whether

device is performing

an automatic

demand reset at

season change. (0 =

False, 1 = True)

1 bit 0 or 1 0 Yes Yes

This dialog in MeterBuddy2 is used to define TOU features of Libra meter.

7.1.3 Change Season & SCHEDULE according to ID_MATRIX.

After enable TOU Control, Setting parameters must be taken to ensure self-read

and demand-reset correctly connected to TOU.

7.1.3.1 Change Season

7.1.3.1.1 Non-Recurring Calendar

This dialog is used to change season with Non-Recurring Calendar working

parameters.

Page 41: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

41 / 62

Notes:The Date type dictated in ANSI C12.19 as follows:

7.1.3.1.2 Fixed-Recurring Calendar

This dialog is used to change season with Fixed-Recurring Calendar working

parameters.

Page 42: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

42 / 62

7.1.3.2 SCHEDULE according to ID_MATRIX.

7.1.3.2.1 Search ID_MATRIX with Season & Day_Type

If select 2012-09-03 to change season, set [Season1] on 2012-9-3, and search Day_type that be according to Calendar is[Monday] .

the value of DAILY_SCHEDULE_ID_MATRIX is [21].

Day_type Season

Season 1 Season 2 Season 3 Season 4

0 (Saturday) 01h 02h 03h 04h

1 (Sunday)

11h 12h 13h 14h

2 (Monday to Friday)

21h 22h 23h 24h

3 (holiday)

31h 32h 33h 34h

7.1.3.2.2 Set SCHEDULE Tier with D_MATRIX

Set 15:00 to self-read or/and demand reset.

So user can determine [hh-mm-tier-day_sch_cum] which correspond to

DAILY_SCHEDULE_ID_MATRIX[21].

This dialog is used to set Schedule tier switch working parameters.

Page 43: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

43 / 62

7.1.3.3 Setting Notes

1. TOU-refresh occur 5 seconds after each set time or TOU parameters

automatically , meter operate TOU based on the latest rate parameters .

2. If month is set to be 13 in Non-Recurring Calendar, The entry parameter is

invalid. And the following data in this entry data will not be identified.

3. If month is set to be 14 in Recurring Calendar, The entry parameter is invalid. And the following data in this entry data will not be identified.

4. If month is set to be 13 in Recurring Calendar, then each month will cycle at the

same method.

Page 44: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

44 / 62

5. If the date table coincide with schedule of rates ,meter will be set latter as the

criterion.for example, tier_switch[10] will be operated.

7.1.4 Read Real Time Clock

Meter Information table.

8.0 Test Mode

Libra-3 meter can support 3 display modes .

Normal Mode

ALT Mode

Test Mode

Test mode to test meter operation and site characteristics without effect on billing

quantities data.

This table is used to set working parameters of Test Mode.

Page 45: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

45 / 62

9.0 History & Event Logs

MeterBuddy supports to read History & Event Logs, such Power Down, Power Up,

Time Changed(old time), Time Changed(new time), Event log cleared,Demand Reset

Occurred,etc. This chapter takes several examples to discribe that how to operate

History & Event Logs.

Libra3C supported event can be individually set whether or not to save the

event _log , users can configure record the types of events according to their

needs.

Libra3C can take fault detection and save fault data automatically which help users to analyze .

To detect loss of voltage , phase loss , the reverse power such as the LCD will be the appropriate instructions . indication details, refer to ’Libra3c handbook.doc’ .

To save the data format dictated by ANSI C12.19

The fault detection threshold can be set with meterbuddy2 .

9.1.1 Event LogsControl

9.1.1.1 Event logs Enable

This table will be present only if the Event Log upgrade has been enabled. which can

be referred [Table 72- Events Identification Table]dictated by ANSI C12.19.

Field Name

Description

Size/

Units

Valu

e

Default

Prog

r’m’

ble

Readab

le

EVENTS_SUPPORTED_R

CD

STD_EVENTS_SUPPORT

ED[6]

Set variable

indicating

which standard

events are

supported.

One bit is

provided for

each standard

event (bit 0 =

6byte

s

0x000000 Yes Yes

Page 46: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

46 / 62

standard event

0, etc.) with 0

indicating that

the event is not

supported, 1

indicating the

event is

supported.

MFG_EVENTS_SUPPORT

ED[4]

Set variable

indicating

which

manufacturer

events are

supported.

One bit is

provided for

each

manufacturer

event. (0 = not

supported, 1 =

supported)

4

bytes

0x000000 Yes Yes

TOTAL SIZE 10byt

es

9.1.1.2 Event Types

The Event Logs can be referred AppendixB dictated by ANSI C12.19.

STD_EVENTS:

Event_index Event_type

01 PRIMARY_POWER_DOWN

02 PRIMARY_POWER_UP

03 TIME_CHANGED_OLD_1

04 TIME_CHANGED_NEW_1

18 EVENT_LOG_CLEARED

20 DEMAND_RESET_OCCURRED

32 TEST_MODE_STARTED

33 TEST_MODE_STOPPED

MFG_EVENTS:

Event_index Event_type

Page 47: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

47 / 62

07 OVER_VOLTAGE_START

08 LOW_VOLTAGE _START

09 OVER_CURRENT _START

16 OVER _VOLTAGE_STOP

17 LOW_VOLTAGE_STOP

18 OVER_CURRENT _STOP

19 LOSS_PHASE_START

20 LOSS_PHASE_STOP

21 MIN_POWER_FACTOR_START

22 MIN_POWER_FACTOR_STOP

23 REVERSE_POWER_START

24 REVERSE_POWER_STOP

25 CLEAR_DATA

26 COLD_START

27 WARM_START

28 CLEAR_SLEF_READ

29 RESET_LOAD_PROFILE

30 LOAD_PROFILE_START

31 LOAD_PROFILE_STOP

9.1.1.3 The threshold setting

This table is used to set threshold of Event_log. [Table 03 – Meter Parameters

Table] dictated by ANSI C12.19.

Page 48: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

48 / 62

9.1.2 Read Event Data

9.1.2.1 Config Monitored Events

This dialog is used to select Events that you want to monitor.

9.1.2.2 Read Event logs record

Libra-3 meter can support read previous and all of valid event records. This dialog

is used to set Event Log Status and how many items of Event records.

Page 49: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

49 / 62

This table is used to describe the date and trigger of Event Logs specification.

10.0 Load Profile

The reader/programmer will be able to initialize load profile memory or disable load

profile recording completely. On the Libra-3L meter the Load profile is stored on the

main board.

support 4MB Card which value can not be modified.

LP data is transported in the format dictated by ANSI C12.19.

Number of Data Blocks and Sectors can be set

Days in accordance with the order as a unit of data sub- blocks , each block

contains a block header and many sectors . The maximum number of sectors

can be set in which the block header contains a time data and a block read data

LP Data stores by the day , every day is stored as a data block. 0:00 daily

branch for block storage. The size of the data stored in each block is generated

automatically based on setting parameters .

The relationship between capacity and load profile interval length can be

calculated with Load Profile Data Set1 Table which can be referred Table 64

dictated by ANSI C12.19.

Page 50: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

50 / 62

Field Name Description Size/Units

Programa

ble

Readable

LP_DATA_SET1_RCD

LP_DATA_SETS1[NBR_BL

KS_SET1]

BLK_END_TIME End data/time of last interval in the

block.

5 bytes No Yes

END_READINGS[NBR_CHNS_S

ET1]

Array of readings taken at the end

time of the last interval in the block;

one reading per channel.

4bytes/chan No Yes

LP_INT[NBR_BLK_INTS_SET1]

INT_DATA[NBR_CHNS_SET1] Interval data. 2 bytes/chan No Yes

TOTAL SIZE **

** Table size must be computed based on NBR_BLKS_SET1, NBR_CHNS_SET1 and

NBR_BLK_INTS_SET1. Formula is

( ( ((NBR_CHNS_SET1 * 2)) * NBR_BLK_INTS_SET1) + 5 + 4(NBR_CHNS_SET1)) *

NBR_BLKS_SET1

Data Blocks not support rewritable, write operations can only be empty or

erased unit

Blocks should be cleared fistly when LP setting parameters program to meter

successfully, then LP Data can be read correctly

10.1 Operation block diagram

Block diagram describes the working process from written to read out.

END

Input setting parameter

YES

START

NO

Program Parameter to meter

Reset LP Data

YES

NO

Re-start LP Data

YES

NO

Read out LP Record

Set LP data source successfully

NO

YES

Read out LP data from meter

successfully

YES

NO

Export data as tables/FILE

Discribe as curve or

bar diagram

Page 51: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

51 / 62

10.2 LP Settings Parameters

This table is used to set Load Profile .

Memory Card Length(Bytes), Libra-3 meter support 4MB Card which value can

not be modified.

Number of Days, the value is calculated automatically .

Libra-3L meter optional recorder is capable of handling 42 days of 15 minute

load profile data on four channels with 32K or 42 days of 15-minute load profile

data on 15 channels with 128K bytes of memory. The number of days of

capacity is dependent upon the interval length duration and the number of

channels used.

Number of Intervals per day , max intervals based on interval length, the

value is calculated automatically .

Number of Channels, 1~16channels can be set.

Interval lengths , Load Profile interval lengths include, 1, 5, 15, 30 and 60

minutes. Each interval consists of two bytes.

The register records up to 15 channels of load profile data. The number of

channels is programmable. The available memory is distributed equally among

each channel.

10.3 Program Parameters to meter

The reader/programmer inputs 15 to Interval Length value,then clock [Progam

Current Cell].

Page 52: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

52 / 62

This dialog is used to indicate set successfully.

10.4 Reset LP Data

Reset LP Data to clear blocks that ensure write new data correctly

This dialog is used to whether or not to clear LP data

Page 53: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

53 / 62

After clock [Y], the LCD will display [CLR] for 15 seconds. When LCD display in

Normal Mode, clock [确定] in this dialog .

10.5 Re-start LP Data

This dialog is used to re-start LP data.

Clock[Y], wait for several seconds , Pop-up this dialog box to describe re-start

completely.

10.6 Read LP Data

10.6.1 Set LP Data Source

This dialog is used to set Load Profile Data Source.

Page 54: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

54 / 62

After set successfully, the table is used to describe Data Source specification which

include “Interval Data Source “and “End Read Data Source”.

10.6.2 LP Data Source default

The meter Maximum support 16 channels , source and scalars (1,100 or 1000) can

be individually set in each channel .

This table is the source for seting the INT_DATA and

END_BLOCK_READING_DATA.This Tabe is only for description. Can not be read

or programmed.

Size/Units of End Read Data Source is 4bytes/chan

Size/Units of Interval Data Source is 2bytes/chan, so scalars can be used to

Prevent from data overflow

Page 55: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

55 / 62

Page 56: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

56 / 62

10.6.3 Manufacturer Specific LP Data Source Tables

Table 62 – LP Data Source Table can bedictated by ANSI C12.19.

Source

Index

End Read Data

Source information

NOTE

S

Source

Index

Interval Data

Source information

NOTES

0 Total active energy 54 Total active energy Only for Interval Data

Source

1 Active energy of

Phase A

55 Active energy of

Phase A

Only for Interval Data

Source

2 Active energy of

Phase B

56 Active energy of

Phase B

Only for Interval Data

Source

3 Active energy of

Phase C

57 Active energy of

Phase C

Only for Interval Data

Source

4 Total reactive energy 58 Total reactive

energy

Only for Interval Data

Source

5 Reactive energy of

Phase A

59 Reactive energy of

Phase A

Only for Interval Data

Source

6 Reactive energy of

Phase B

60 Reactive energy of

Phase B

Only for Interval Data

Source

7 Reactive energy of 61 Reactive energy of Only for Interval Data

Page 57: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

57 / 62

Phase C Phase C Source

8 Total Delivered active

energy

62 Total Delivered

active energy

Only for Interval Data

Source

9 Delivered active

energy of Phase A

63 Delivered active

energy of Phase A

Only for Interval Data

Source

10 Delivered active

energy of Phase B

64 Delivered active

energy of Phase B

Only for Interval Data

Source

11 Delivered active

energy of Phase C

65 Delivered active

energy of Phase C

Only for Interval Data

Source

12 Total Delivered

reactive energy

66 Total Delivered

reactive energy

Only for Interval Data

Source

13 Delivered reactive

energy of Phase A

67 Delivered reactive

energy of Phase A

Only for Interval Data

Source

14 Delivered reactive

energy of Phase B

68 Delivered reactive

energy of Phase B

Only for Interval Data

Source

15 Delivered reactive

energy of Phase C

69 Delivered reactive

energy of Phase C

Only for Interval Data

Source

16 Total apparent energy 70 Total apparent

energy

Only for Interval Data

Source

17 Apparent energy of

phase A

71 Apparent energy of

phase A

Only for Interval Data

Source

18 Apparent energy of

phase B

72 Apparent energy of

phase B

Only for Interval Data

Source

19 Apparent energy of

phase C

73 Apparent energy of

phase C

Only for Interval Data

Source

20 Total Reveiced active

energy

74 Total Reveiced

active energy

Only for Interval Data

Source

21 Reveiced active

energy of Phase A

75 Reveiced active

energy of Phase A

Only for Interval Data

Source

22 Reveiced active

energy of Phase B

76 Reveiced active

energy of Phase B

Only for Interval Data

Source

23 Reveiced active

energy of Phase C

77 Reveiced active

energy of Phase C

Only for Interval Data

Source

24 Total Reveiced

reactive energy

78 Total Reveiced

reactive energy

Only for Interval Data

Source

25 Reveiced reactive

energy of Phase A

79 Reveiced reactive

energy of Phase A

Only for Interval Data

Source

26 Reveiced reactive

energy of Phase B

80 Reveiced reactive

energy of Phase B

Only for Interval Data

Source

27 Reveiced reactive

energy of Phase C

81 Reveiced reactive

energy of Phase C

Only for Interval Data

Source

28 Total Active net

energy

82 Total Active net

energy

Only for Interval Data

Source

Page 58: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

58 / 62

29 Active net energy of

Phase A

83 Active net energy

of Phase A

Only for Interval Data

Source

30 Active net energy of

Phase B

84 Active net energy

of Phase B

Only for Interval Data

Source

31 Active net energy of

Phase C

85 Active net energy

of Phase C

Only for Interval Data

Source

32 Total Reactive net

energy

86 Total Reactive net

energy

Only for Interval Data

Source

33 Reactive net energy of

Phase A

87 Reactive net energy

of Phase A

Only for Interval Data

Source

34 Reactive net energy of

Phase B

88 Reactive net energy

of Phase B

Only for Interval Data

Source

35 Reactive net energy of

Phase C

89 Reactive net energy

of Phase C

Only for Interval Data

Source

36 Ua

37 Ub

38 Uc

39 Ia

40 Ib

41 Ic

42 Total active power

43 A active power

44 B active power

45 C active power

46 Total reactive power

47 A reactive power

48 B reactive power

49 C reactive power

50 A power fatcor

51 B power fatcor

52 C power fatcor

53 frequency

10.6.4 Read Daily LP Data

This table is used to describe LP Data which record the time of Daily Reading

Occurrence.

Page 59: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

59 / 62

10.6.5 Daily LP Data Bar-diagram

This chapter takes another example to discribe that how to handle Load Profile data

analysis and reporting. Export current table of LP Records and save as excel table.

The excel table can shown through curve or bar diagram obviously.

Page 60: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

60 / 62

Appendix :Error Functional cod Specifications

Page 61: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

61 / 62

Page 62: Libra meter   meter buddy handbook

ANSI Meter Team, Greta Song Secret close No. CSDL-AMD-SN-022

ANSI_3C Libra Meter – MeterBuddy2 Handbook

Issue/Rev. 2.85 Date 08/10/2012

62 / 62