View
216
Download
0
Category
Preview:
Citation preview
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 1/27
Prepared For: Date: April 12, 2006
Customer P.O. Numb er: Customer Pro ject Number:
Sold To: Job Number: Job Name:
57Q874 - 57Q883 Feibo - Meyer
WI
Trane is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Air-Cooled Water Chillers (Large Tonnage)2 BCXC Blower Coil Air Handler
Trane
Phone:Fax:
The attached information describes the equipment we propose tofurnish for this project, and is submitted for your approval.
Trane
A Division of American Standard Inc. Submit tal
J:\JOBS\357\75777\1\57Q874-57Q883.doc
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 2/27
Table Of Contents
Product Summary ........................................................................................................................... 1
Air-Cooled Water Chillers (Large Tonnage) (Item A1) Tag Data .................................................................................................................................................. 3
Product Data ............................................................................................................................................ 3
Performance Data .................................................................................................................................... 3
Mechanical Specifications ........................................................................................................................ 5
Unit Dimensions ....................................................................................................................................... 7
Fan Curve ................................................................................................................................................ 8
Weight, Clearance & Rigging Diagram ..................................................................................................... 9
Field Wiring ............................................................................................................................................ 10
BCXC Blower Coil Air Handler (Items B1, B2) Tag Data ................................................................................................................................................ 13
Product Data .......................................................................................................................................... 13
Performance Data .................................................................................................................................. 13
Mechanical Specifications ...................................................................................................................... 15
Unit Dimensions ..................................................................................................................................... 17
Fan Curve .............................................................................................................................................. 20
Accessory .............................................................................................................................................. 22
Field Wiring ............................................................................................................................................ 26
Field Installed Options - Part/Order Number Summary
Air-Cooled Water Chillers (Large Tonnage) ........................................................................................... 27 BCXC Blower Coil Air Handler ............................................................................................................... 27
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 3/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 3 of 27
Tag Data - Air-Cooled Water Chillers (Large Tonnage) (Qty: 1)
Item Tag(s) Qty Description Model Number
A1 CGAF-1 1 20-60 Ton Packaged Air-Cooled Chiller - CGAFC60E
Product Data - Air-Cooled Water Chillers (Large Tonnage)
Item A1
Tags CGAF-1
Qty 1
60 ton Unit X
200 Volt 60 Hertz 3 Phase X40 to 50 degree F Water Setpoint Without Ice Making Control X
UL/ CSA Approval X
Unit Neoprene Isolators Fld
Unit Mounted Terminal Block X
Performance Data - Air-Cooled Water Chillers (Large Tonnage)
Tags CGAF-1
Ice machine? No
Elevation (ft) 2600
Total cooling capacity (tons) 55.58
Circuit 1 clg capacity (tons) 0
Circuit 2 clg capacity (tons) 0Ent evaporator temp (F) 54
Lvg evaporator temp (F) 44
Evaporator temp drop (F) 10
Ambient temperature (F) 90
Evaporator fouling factor (hr-sq ft-deg F/Btu) .0001
Evaporator flow rate (gpm) 132.98
Fluid type Water
Saturated suction temp (F) 37.95
Cooling fluid PD (ft H2O) 6.21
Fluid freeze pt (F) 32
Compressor power (kW) 60.28
Fan power (kW) 5.4System power (kW) 65.68
EER @ ARI (EER) 9.7
COP @ ARI (COP) 2.8
IPLV @ ARI (IPLV) 15
Min circuit ampacity (A) 270
Max fuse size (A) 300
Recommended dual element (A) 300
Circuit 1 compressor 1 LRA (A) 409
Circuit 1 compressor 1 RLA (A) 56.9
Circuit 1 compressor 2 LRA (A) 409
Circuit 1 compressor 2 RLA (A) 56.9
Circuit 2 compressor 1 LRA (A) 409
Circuit 2 compressor 1 RLA (A) 56.9
Circuit 2 compressor 2 LRA (A) 409
Circuit 2 compressor 2 RLA (A) 56.9
Fan quantity (Each) 6
FLA per fan (A) 4.1
Part load step 1 (%) 25
Ambient at step 1 (F) 55
Capacity at step 1 (tons) 15.86
Unit power at step 1 (kW) 11.45
EER @ ARI at step 1 (EER) 18.3
Part load step 2 (%) 50
Ambient at step 2 (F) 60
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 4/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 4 of 27
Tags CGAF-1
Capacity at step 2 (tons) 35.63
Unit power at step 2 (kW) 24.54
EER @ ARI at step 2 (EER) 15.2
Part load step 3 (%) 75
Ambient at step 3 (F) 75
Capacity at step 3 (tons) 46.93
Unit power at step 3 (kW) 42.16
EER @ ARI at step 3 (EER) 11.9
Outdoor - 63 Hz (dB) 97Outdoor - 125 Hz (dB) 92
Outdoor - 250 Hz (dB) 92
Outdoor - 500 Hz (dB) 94
Outdoor - 1 kHz (dB) 91
Outdoor - 2 kHz (dB) 89
Outdoor - 4 kHz (dB) 87
Outdoor - 8 kHz (dB) 85
A weighted sound power (dBA) 97
A weighted sound pressure (dBA) 70
Min operating weight (lb) 4885
Max operating weight (lb) 5820
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 5/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 5 of 27
Mechanical Specifications - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
General All chillers are factory run-tested to confirm proper operation. Units are checked on computer based test stand attypical ambient and water conditions and control operation is monitored. Units ship with a full operating charge ofrefrigerant and oil.
Units are constructed of 14-gauge welded galvanized steel frame with 14 and 16-gauge galvanized steel panels andaccess doors. Unit surface is phosphatized and finished with an air-dry paint. This air-dry paint finish is durable
enough to withstand a 1000-consecutive-hour salt spray application in accordance with standard ASTM B117.
A flow switch is included as ship-with item to be field installed at the outlet of the evaporator. The flow switch isrequired as a safety interlock to prevent operation of unit without evaporator flow.
General A strainer (with installation hardware) is included as a ship-with item to be field installed at the inlet of the evaporator.The strainer is required to prevent collection of particles within the evaporator. Strainer is field installed to facilitateease of installation.
Compressor Trane 3-D Scroll compressors have simple mechanical design with only three (3) major moving parts. Scroll typecompression provides inherently low vibration. 3-D compliance provides a completely enclosed compressionchamber which leads to increased efficiency. Exhaustive testing on the 3D Scroll, including start up with the shell fullof liquid, has proven that slugging does not fail involutes. Direct-drive, 3600 rpm, suction gas-cooled hermetic motor.Trane 3D Scroll compressor includes centrifugal oil pump, oil level sightglass and oil charging valve.
Evaporator The evaporator shall be braze plate construction with a waterside working pressure of 300 PSIG and a refrigerant sideof working pressure of 225. Etched foil heaters protect the evaporator to ambient of -20 degrees F.
Condenser Fans Direct-drive vertical discharge condenser fans are statically and dynamically balanced. Three phase thermal overloadprotected with permanently lubricated ball bearings.
Controls Compressor contactors and unit controls are in a weather tight enclosure with knockouts for field installed wiring. The
chiller unit utilizes a DDC microprocessor control system which is suitable for comfort and process coolingapplications. The control system is factory installed in the main control panel with the necessary internal controls andrun tested. Terminal blocks for field power wiring connections are standard. Units provide a location for a non-fuseddisconnect switch with an external handle for safety. Unit mounted microprocessor controls provide compressor anti-short cycle protection. The unit is equipped with a Human Interface Panel with a 16 key keypad, a 2 line by 40character English display to provide the operator with full adjustment and display of control data function. The unitcontrols can be used as a stand-alone controller or as part of a building management system. The display can beread and adjusted without opening any unit panels.
Decorative Grilles Decorative grilles provide protection from exterior damage to coil surface and other interior unit components. Grillesare factory mounted louvered, galvanized steel panels finished with an air dry paint. Grilles cover all air accessibleends of the unit.
Refrigerant Circuits with 4-Stage Capacity Modulation for 40 - 60 Ton Units The unit has dual refrigeration circuits. Each circuit has two (2) compressors manifolded together utilizing a passiveoil system. Each refrigerant circuit includes an liquid line solenoid valve, filter drier, sightglass with moistureindicator,thermostatic expansion valve and service valves (liquid and discharge). Capacity modulation isaccomplished by turning compressors on and off. The unit has four capacity stages. The standard leaving chilledwater temperature range is 40 to 50 F [4.5 to 10 C].
Neoprene Isolators Neoprene isolators are available for field installation under the unit frame.
Condenser Coils with Aluminum Fins Air-cooled condenser coils have configured aluminum fins mechanically bonded to seamless copper tubing and
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 6/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 6 of 27
integral subcooling circuits. Condenser coils are factory leak tested under water with 425 psig [2930.4 kPa] airpressure.
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 7/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 7 of 27
Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
CONTROL CONN.32mm X 114mm
1 1/4" X 5 1/4" SLOT
SEE DETAIL "A"
CONNECTIONS BOTTOM
NO OBSTRUCTIONS AIR FLOW
LEFT SIDE VIEW
C O M P
413mm1'-4 1/4"
OPTIONAL DAMPER
CONTROLPANEL 1371mm
4'-6"
1991mm
1854mm6'-1"
6'-6 3/8"
343mm1'-1 1/2"
2'-11"
889mm1006mm
3'-3 5/8"
3'-1 3/8"
949mm
3" CONDUIT MAIN POWER
76mm
DETAIL "A"
92mm
3 5/8"
83mm
149mm
7 1/8"181mm
5 7/8"
3 1/4"
248mm9 3/4"
2'-9"838mm
1 3/32" (1X) HEAT TAPE POWER
28mm
1 3/32" (4X) 30V MAX.
70mm2 3/4"
28mm
64mm2 1/2"LINE VOLTAGE
178mm
127mm
5"
356mm
1'-2"
7"
133mm
3 5/8" DIA
5 1/4"
92mm
FRONT VIEW
2629mm
8'-7 1/2"
DIA HOLES (4)
LIFTING LOCATIONS
32mm
2175mm
7'-1 5/8"
1 1/4"
1241mm1241mm
3/4" DIA. X 6 MTG HOLES
SWING
70mm
2 3/4"
1060mm180
19mm
1
3'-5 3/4" DOOR
2
TOP VIEW
3 5
4 6
206mm
8 1/8" 4'-0 7/8"
9'-5 7/8"
2892mm
4'-0 7/8"
8'-0"
2438mmMINIMUM CLEARANCE
2245mm
7'-4 3/8"
MINIMUM CLEARANCE2438mm
8'-0"
Rear View
Water Inlet
3" Grooved PipeConnection
Water Outlet
3" Grooved PipeConnection
1' 1"
5'
9-1/2"
2' 6"
Access Hole Locations336mm
1528mm
241mm
756mm
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 8/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 8 of 27
Fan Curve - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz
Unit Sound: 97 92 92 94 91 89 87 85
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 9/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 9 of 27
Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
4865 in3
4885.0 lb 885.0 lb 820.0 lb 855.0 lb 985.0 lb 985.0 lb 720.0 lb
8 3/16"
48 7/8" 48 7/8"
85 5/8"
1 5/16"
58"
47"
NOTES:
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENT
DAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPT
AS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORT
UNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCE AND RIGGING.
WARNING!!!
SHIPPING WEIGHT
OPERATING WEIGHT
1 2 3 4
UNIT MOUNTING POINTS
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER.2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES.3. IF THE UNIT IS INSTALLED IN A W ELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE
HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.
UNIT WEIGHT
UNIT CLEARANCE
UNIT RIGGING
CENTER OF GRAVITY AND UNIT WEIGHT
NO OBSTRUCTION AIR FLOW
CLEARANCE 96"
1 5
2 6
CONTROL PANEL DOOR SWING 180
FRONT OF UNIT
84" TO TOPOF UNIT
96" FIELD SUPPLIEDSPREADER BAR
5 6
4
3
CONTROL PANEL 2 1/2"X4 LIFTING HOLES
CLEARANCE 96"
CLEARANCE 96"CLEARANCE 96"
UNIT MOUNTING POINTS
CONTROL PANEL
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 10/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 10 of 27
Field Wiring - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
2. Phantom lines indicate alternate circuitry or available sales options.
447
448
449
450
495
500
501
502
503
533
534
537
12
NC
450
NO
498
499
448449
445
446
538
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
COM
ALARMOUTPUT
NC
447
NO
445446
COM
ICEMAKINGOUTPUT
1TB5
1
2
3
4
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
496
497
CAUTIONUSE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OF
CONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWERINCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LES
DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
447
448
449
450
495
500
501
502
503
533
534
537
12
NC
450
NO
498
499
448449
445
446
538
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE
HAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
COM
ALARMOUTPUT
NC
447
NO
445446
COM
ICEMAKINGOUTPUT
1TB5
1
2
3
4
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
496
497
CAUTIONUSE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OF
CONDUCTORS.FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWERINCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LES
DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUERL'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
Connect to 24VACclass 2 circuits only.
Connect to 24VACclass 2 circuits only.
Notes:
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 11/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 11 of 27
Field Wiring - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
2. Phantom lines indicate alternate circuitry or available sales options.
422
414
424
425411
ICSCONTROLLED 414
415
416
5RT19ICS DEFINED
TEMP
424
5S67EXTERNAL
AUTO/STOPSWITCH
434
425
438
437
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUT AND START-UP PROCEDUREHAS BEEN COMPLETED
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
NO
COM
NC
5S71EMERGENCY
STOPSWITCH
435431
5K86ICE
BUILDINGINITIATE
4101
2
3
4
12
13
14
15
5
6
7
8
9
16
17
18
19
20
10
11
21
22
1TB4
416
417
418
421
415
436
403
438
435
431
434
438437
24 VOLT CLASS 2
CIRCUIT ONLY)
(CONNECT TO
Remove jumper between 1tb4-16 & 17when required, Contacts rated 12mA @24VDC minimum.
Remove jumper between 1tb4-18 & 19 when required,Contacts rated 12mA @ 24VDC minimum.
Contacts rated12mA @ 24VDC
minimum.
Use BAYSENS016, BAYSENS017 or equivalent.
BLESSURES CORPORELLES SEVERESL'ENTRETIEN PEUT ENTRAINER DESELECTRIQUE AVANT D'EFFECTUERFAUTE DE DECONNECTER LA SOURCE
AVANT D'EFFECTUER L'ENTRETIEN.
DISJONCTEURS SITUES A DISTANCEELECTRIQUES INCLUANT LESDECONNECTEZ TOUTES LES SOURCES
VOLTAGE HASARDEUX!
AVERTISSEMENT
PERSONAL INJURY OR DEATH.BEFORE SERVICING CAN CAUSE SEVEREFAILURE TO DISCONNECT POWER
WARNING
INCLUDING REMOTE DISCONNECTSDISCONNECT ALL ELECTRIC POWER
BEFORE SERVICING.
HAZARDOUS VOLTAGE!
OU LA MORT.
DAMAGE TO THE EQUIPMENT.FAILURE TO DO SO MAY CAUSE
TO ACCEPT OTHER TYPES OFUNIT TERMINALS ARE NOT DESIGNED
USE COPPER CONDUCTORS ONLY!
CAUTION
CONDUCTORS.
Notes:
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 12/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 12 of 27
Field Wiring - Air-Cooled Water Chillers (Large Tonnage)Item: A1 Qty: 1 Tag(s): CGAF-1
2. Phantom lines indicate alternate circuitry or available sales options.
UNITS WITH MAIN POWERTERMINAL BLOCK (ALL VOLTAGES)
BLOCK SIZE
335 AMP 1
WIRE QTY.
(1) #6 - 350 MCM
CONNECTOR WIRE RANGE
NOTES
5B1
IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE
HAS BEEN COMPLETED
L1 L2 L3
SEE UNITNAMEPLATE FORLINE VOLTAGE
5K1
5K1-OL5T1 5K1
39
EQUIPMENT
GROUND
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
1
2
3
4
5
6
7
8
9
10
11
12
38
39
1TB6
38
CAUTIONUSE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.
FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWERINCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCE
AVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUER
L'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
NOTES
A. BLOCK SIZE & DISCONNECT SIZE ARE CALCULATED BY SELECTING THE SIZE GREATER THAN OR EQUAL TO 1.15 X (SUM OF UNIT LOADS). SEE UNIT LITERATURE FOR UNIT LOAD VALUES.
5B1
CUSTOMER CONNECTION WIRE RANGE IMPORTANT!DO NOT ENERGIZE
UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE
HAS BEEN COMPLETED
5S1
L1 L2 L3
SEE UNITNAMEPLATE FORLINE VOLTAGE
5K1
5K1-OL5T1 5K1
39
EQUIPMENT
GROUND
DEVICE PREFIX LOCATION CODE
AREA LOCATION
1
2
3
4
5
6
CONTROL PANEL
FAN SECTION
COMPRESSOR SECTION
EXTERNAL FACTORY MTD DEVICE
CUSTOMER OR FIELD PROVIDED
SHIP W/FIELD INSTALLED DEVICE
1
2
3
4
5
6
7
8
9
10
11
12
38
39
1TB6
38
CAUTIONUSE COPPER CONDUCTORS ONLY!
UNIT TERMINALS ARE NOT DESIGNEDTO ACCEPT OTHER TYPES OFCONDUCTORS.
FAILURE TO DO SO MAY CAUSEDAMAGE TO THE EQUIPMENT.
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWERINCLUDING REMOTE DISCONNECTSBEFORE SERVICING.
AVERTISSEMENTWARNINGVOLTAGE HASARDEUX!
FAILURE TO DISCONNECT POWERBEFORE SERVICING CAN CAUSE SEVEREPERSONAL INJURY OR DEATH.
DECONNECTEZ TOUTES LES SOURCESELECTRIQUES INCLUANT LESDISJONCTEURS SITUES A DISTANCE
AVANT D'EFFECTUER L'ENTRETIEN.FAUTE DE DECONNECTER LA SOURCEELECTRIQUE AVANT D'EFFECTUER
L'ENTRETIEN PEUT ENTRAINER DESBLESSURES CORPORELLES SEVERESOU LA MORT.
1TB1
5B1 CHILLER PUMP MOTOR
CHILLED SOL PUMP STARTER
ICE BUILDING INITIATE
5RT19
5S1
5K86
5K89
5K1
DEVICE DESIGNATION
DEMAND LIMIT RELAY
ICE DEFINED TEMP. SENSOR
FUSED DISCONNECT
EMERGENCY STOP5S71
5T1 CONTROL TRANSFORMER
5S67 EXTERNAL AUTO STOP SWITCH
HEAT TAPETO 4HR1HEAT TAPETO 4HR1
4HR1 - HEAT TAPE POWER WIRING4HR1 - HEAT TAPE POWER WIRING
200200 L1L1
201201 L2L2 H
N
H
N
115VAC/60HZ
15A MAX15A MAX
1TB121TB12
Notes:
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 13/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 13 of 27
Tag Data - BCXC Blower Coil Air Handler (Qty: 2)
Item Tag(s) Qty Description Model Number
B1 7.5 ton 1 BCXC Blower Coil Air Handler -BCXC
BCHC090E2**A1M06P000000B01ED100000000000
B2 2 ton 1 BCXC Blower Coil Air Handler -BCXC
BCHC024E2**A1M02G000000B01EB100000000000
Product Data - BCXC Blower Coil Air Handler
All UnitsHORIZONTAL CONFIGURATIONHorizontal Configuration208/60/3Foil Faced Insulation 1"Motor, drive & control box on Same Side as Coil & Drainpan ConnectionPVC Drainpan - Right Hand Coil & Drainpan Connections4 Row High Capacity Cooling Hydronic Coil2" Pleated Throwaway FilterControl Interface2-Way Modulating (Fld)Basic Piping Package (Fld)
Item B1 B2
Tags 7.5 ton 2 ton
Qty 1 1
Unit Size 90 - 7 1/2 Ton ( 26.4 KW ) X
Unit Size 24 - 2 Ton ( 7.0 KW ) X
2 Horse Power X
1/2 Horse Power X
1029-1332 RPM 60HZ / 853-1104 RPM 50HZ X
1000-1417 RPM 60HZ / 829-1174 RPM 50HZ X
6.0 CV, 1" Modulating, 1" PIPE Fld
3.3 CV, 1/2" Modulating, 3/4" PIPE Fld
Performance Data - BCXC Blower Coil Air HandlerTags 7.5 ton 2 ton
Design airflow (cfm) 3000 800
Total cooling capacity (MBh) 105.71 28.22
Sensible capacity (MBh) 69.48 18.73
Cooling EDB (F) 80 80
Cooling EWB (F) 67 67
Cooling LDB (F) 56.96 56.7
Cooling LWB (F) 55.38 55.36
Cooling ent fluid temp (F) 44 44
Cooling leaving fluid temp (F) 54 54
Cooling flow rate (gpm) 22.09 5.84
Cooling delta T (F) 10 10Cooling fluid PD (ft H2O) 8.66 5.95
Fluid type Water Water
Cooling face velocity (ft/min) 491 461
Auxiliary heat type None None
Unit length (in) 50 44
Unit width (in) 48 28
Unit height (in) 28 18
Installed weight (lb) 264 129.5
Rigging weight (lb) 224.6 122.5
Aux fluid type Water Water
Elevation (ft) 2600 2600
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 14/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 14 of 27
Tags 7.5 ton 2 ton
ESP (in H2O) 1 .5
TSP (in H2O) 1.69 1.09
Fan speed (rpm) 1161 1239
Motor heat calculation Include Include
Piping pkg PD (ft H2O) 35.9 7.69
Min circuit ampacity (A) 7.75 2.88
Coil design basis Cooling Cooling
Max fuse size (A) 15 15
Main coil type Hydronic HydronicInlet - 63 HZ (dB) 78 80
Inlet - 125 HZ (dB) 79 73
Inlet - 250 HZ (dB) 58 50
Inlet - 500 HZ (dB) 45 34
Inlet - 1 kHZ (dB) 42 22
Inlet - 2 kHZ (dB) 35 19
Inlet - 4 kHZ (dB) 29 16
Inlet - 8 kHZ (dB) 20 15
Casing - 63 HZ (dB) 83 81
Casing - 125 HZ (dB) 73 70
Casing - 250 HZ (dB) 70 66
Casing - 500 HZ (dB) 63 54
Casing - 1 kHZ (dB) 59 50
Casing - 2 kHZ (dB) 53 45
Casing - 4 kHZ (dB) 48 40
Casing - 8 kHZ (dB) 42 30
Discharge - 63 HZ (dB) 95 92
Discharge - 125 HZ (dB) 88 84
Discharge - 250 HZ (dB) 78 69
Discharge - 500 HZ (dB) 76 63
Discharge - 1 kHZ (dB) 76 63
Discharge - 2 kHZ (dB) 71 60
Discharge - 4 kHZ (dB) 69 58
Discharge - 8 kHZ (dB) 64 51
Actual motor power (hp) 1.64 .275Full load amps (A) 6.2 2.3
Lock rotor amps (A) 38.5 11.4
Outlet velocity (ft/min) 2536 676
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 15/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 15 of 27
Mechanical Specifications - BCXC Blower Coil Air HandlerItem: B1, B2 Qty: 2 Tag(s): 7.5 ton, 2 ton
BCHC General The product line consists of a horizontal air handling unit and mixing box. Units are tested in accordance with ARI430-1999 and ARI 260-2001. The unit is UL 1995 listed in U. S. and Canada and complies with NFPA 90A. Air handlers consist of a hydronic and/or DX coil, drain pan, and centrifugal fan with motor and drive mounted in acommon cabinet. Drive location and coil connections are independent for the same or opposite side location. Air handlers are provided with knockouts in all four corners for installing the unit suspended from the ceiling withthreaded rods.
Unit and accessories are insulated with one-inch, 1½ lbs./cu. ft. density fiberglass insulation. One-inch foil facedinsulation is also available.Large motor access panels are provided on both sides of the unit and accessories.
Casing Casings (structural components) are constructed of 18-gauge galvanized steel, insulated with one-inch, 1 ½ lb densityfiberglass fire resistant and odorless glass fiber material to provide thermal and acoustical insulation. Fan housingsides are directly attached to the air handler top and bottom panels strengthening the entire unit assembly. Coilaccess panels are located on both sides of the air handler and allow easy removal of the internal coils and drain pan.Main access panels provide generous access to the fan, motor and drive from both sides of the air handler.
Foil Faced Insulation The interior surface of the unit is acoustically and thermally lined with 1 inch [26 mm] 2.0 lb./cu. ft. [32 kgs./cu. m.], R-Value of 4.3 density glass fiber with a foil facing. The insulation is UL listed and meets NFPA-90A, UL 181, andbacteriological C665 standards.
Coil # 1 Hydronic Cooling Coils Cooling coils are two, four, or six-row, chilled water. All water coils are 12 fins per inch. All water coils use highlyefficient Trane Delta Flo?, Type H aluminum fins, mechanically bonded to seamless copper tubes. All coils arespecifically designed and circuited for water use. All coils are factory tested with 450 psi air under water. Maximumstandard operating conditions are: 300 psig, 200°F. Sweat type connections are standard.
Fan The fans are forward curved, centrifugal blower type equipped with heavy-duty adjustable speed V-belt drives. Thefan shaft is supported by heavy-duty, permanently sealed ball bearings. All fans are dynamically balanced. All airhandlers have a single fan.
2" [52 mm] Pleated Throw-Away Filter A 2 inch [52 mm] pleated standard efficiency (30%) throw-away filter(s).
60 Hertz Motor A 60 Hertz, 1750 RPM motor has a plus or minus 10% voltage utilization range. The motor is open drip-proof withpermanently sealed ball bearings, internal overload protection, and minimum 1.15 service factor and size 56 resilientbase frames. The motor is factory installed and wired to the air handler junction box.
Polymer Drain Pan The drain pan is noncorrossive and double-sloped to allow condensate drainage. The drainpan construction ispolymer. Coils mount above the drain pan, not in the drain pan - thus allowing the drain pan to be fully inspected andcleaned. The drain pan can also be removed for cleaning. The drain pan connections are unthreaded ¾" schedule 40
PVC for solvent bonding. The main drain connection is at the lowest point of the drain pan. An auxiliary drainconnection is provided on the same side as the main connection.
Thermostat Control Interface The thermostat control interface is intended to be used with a field supplied low voltage thermostat or controller. Thecontrol box contains a line voltage to 24 volt transformer; a one, two, or three-pole fan contactor; and a disconnectswitch. The wires from the fan contactor and the low voltage side of the transformer are pulled and terminated on theinside of the two-sided terminal strip. The end devices are mounted and the wires are pulled and terminated on theinside of the two-sided terminal strip. All customer connections other than power are on the outside of the two-sidedterminal strips.
Basic Piping Package - Coil #1 The basic piping package consists of two shutoff ball valves and, for three-way packages, a balancing fitting on the
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 16/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 16 of 27
bypass line. The maximum entering fluid temperature on the water valves is 200 deg. F. [93 deg. C.]. The stopvalves are ball type, and insulation on the piping package is by others.
2-Way, Modulating Control Valve - Coil #1 -Valve Type
2-way, Modulating VC Series (Honeywell)-Cv Ranges
3.3, 6.0, 9.0-Material
Body - Cast Bronze..
"O" Ring Seals - EPDM.Stem - Stainless Steel.Cartridge - Ryton TM, Noryl TM
-Temperature Limits200 deg. F [93 deg. C] fluid.125 deg. F [48 deg. C] ambient.
-Operating Pressure300 psi [2068 kpa] max.
-Close off Pressure60 psi @ 3.3 Cv60 psi @ 6.0 Cv60 psi @ 9.0 Cv
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 17/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 17 of 27
Unit Dimensions - BCXC Blower Coil Air HandlerItem: B1 Qty: 1 Tag(s): 7.5 ton
TOP VIEW
LEFT VIEW
FRONT VIEW RIGHT VIEW
WEIGHT
BASE UNIT
COIL #1
COIL #2
lb
174.8
97.9
1. CONTROL BOX IS PROVIDED WITH 7/8" [22mm] KNOCKOUTSFOR FIELD WIRING.
= AIR FLOW
NOTE:
MOTOR ACCESSPANEL
COIL ACCESS
PANEL26 1/8"
1"
13 1/2"
1 5/8"
1"1"
FILTER ACCESS
CONTROL BOX
14"
1/2"
12 1/2"17 3/4"
48"
MOTOR ACCESSPANEL
COIL ACCESS
PANEL
28 1/8"
52"
FILTER ACCESS
9 1/2"
1"
50"
40"1"
46"
4"
5"
7/8" [22mm] HANGER ROD KNOCKOUTS(4 PLACES)
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 18/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 18 of 27
Unit Dimensions - BCXC Blower Coil Air HandlerItem: B1, B2 Qty: 2 Tag(s): 7.5 ton, 2 ton
RIGHT HAND DRAIN CONNECTIONS
MAINDRAIN
AUXDRAIN
NOTE:DRAIN CONNECTION STUBOUTS EXTRUDE 2" [51mm] FROM SIDE OF UNIT.
1 3/8"2"
10 3/4"
12 3/4"
3/4" SCHEDULE 40 PVC PIPE CONNECTION
3/4" SCHEDULE 40 PVC PIPE CONNECTION
BOTTOM REAR CORNER OF UNIT
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 19/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 19 of 27
Unit Dimensions - BCXC Blower Coil Air HandlerItem: B2 Qty: 1 Tag(s): 2 ton
TOP VIEW
LEFT VIEW
FRONT VIEW RIGHT VIEW
WEIGHT
BASE UNIT
COIL #1
COIL #2
lb
104.1
30.6
1. CONTROL BOX IS PROVIDED WITH 7/8" [22mm] KNOCKOUTSFOR FIELD WIRING.
= AIR FLOW
NOTE:
MOTOR ACCESSPANEL
COIL ACCESS
PANEL16 1/8"
1"
13 1/2"
1 1/4"
1"1"
FILTER ACCESS
CONTROL BOX
14"
1/2"
12 1/2"7 3/4"
28"
MOTOR ACCESSPANEL
COIL ACCESS
PANEL
18 1/8"
46"
FILTER ACCESS
9 1/2"
1"
44"
22"1"
26"
3"
5"
7/8" [22mm] HANGER ROD KNOCKOUTS(4 PLACES)
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 20/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 20 of 27
Fan Curve - BCXC Blower Coil Air HandlerItem: B1 Qty: 1 Tag(s): 7.5 ton
0
. 2
5
0
. 3
3
0
. 5
0
1
. 0
0
1
. 5
0
2
. 0
0
3
. 0
0
5 0 0 RPM
6 0 0 RPM
7 0 0 RPM
8 0 0 RPM
9 0 0 RPM
1 0 0 0 RPM
1 1 0 0 RPM
1 2 0 0 RPM
1 3 0 0 RPM
1 4 0 0 RPM
1 5 0 0 RPM
2 5 %WO
5 0 %WO
6 0 %WO
7 0 %WO
8 0 %WO
9 0 %WO
UnitSize: 90
Operating Air flow: 3000.00 cfm
Operating Static Pressure: 1.69 in H2O
Operating RPM: 1161.00
Operating Brake Power: 1.64
Altitude: 2600.00 ft
De s ig n T e m p :8 0 .0 0 F
Date: 4/12/06
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
SIZE 90 HORIZONTAL
T
o
t a
l
S
t a
t i c
P
r e
s
s
u
r e
( i n
H
2
O
)
Airflow (cfm)
63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz
Discharge 95 88 78 76 76 71 69 64Casing 83 73 70 63 59 53 48 42
Inlet 78 79 58 45 42 35 29 20
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 21/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 21 of 27
Fan Curve - BCXC Blower Coil Air HandlerItem: B2 Qty: 1 Tag(s): 2 ton
0
. 2
5
0
. 3
3
0
. 5
0
1
. 0
0
1
. 5
0
6 0 0 RPM
8 0 0 RPM
1 0 0 0 RPM
1 2 0 0 RPM
1 4 0 0 RPM
1 6 0 0 RPM
1 8 0 0 RPM
2 5 %WO
5 0 %WO
6 0 %WO
7 0 %WO
8 0 %WO
9 0 %WO
UnitSize: 24
Operating Air flow: 800.00 cfm
Operating Static Pressure: 1.09 in H2O
Operating RPM: 1239.00
Operating Brake Power: 0.28
Altitude: 2600.00 ft
De s ig n T e m p :8 0 .0 0 F
Date: 4/12/06
0.0
0.5
1.0
1.5
2.0
2.5
3.0
0 500 1000 1500 2000 2500 3000 3500 4000 4500
SIZE 24 & 36 HORIZONTAL
T
o
t a
l
S
t a
t i c
P
r e
s
s
u
r e
( i n
H
2
O
)
Airflow (cfm)
63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz
Discharge 92 84 69 63 63 60 58 51Casing 81 70 66 54 50 45 40 30
Inlet 80 73 50 34 22 19 16 15
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 22/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 22 of 27
Accessory - BCXC Blower Coil Air Handler2 way basic piping package - coil #1Item: B1 Qty: 1 Tag(s): 7.5 ton
CONTROL VALVE
RETURN CONN.
BALL VALVE
BALL VALVECOIL CONNECTION
SUPPLY CONNECTION
COIL CONNECTION
= WATER FLOW
4 1/4"
13 1/4"
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 23/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 23 of 27
Accessory - BCXC Blower Coil Air HandlerCOIL 1 = HYDRONIC, COIL 2 = NONE, RH CONNECTIONSItem: B1 Qty: 1 Tag(s): 7.5 ton
INCH
COIL CONNECTION SIZE
RETURN
SUPPLY
mm
TOLERANCED WITHIN +/- 2 INCHES (51mm).NOTE: COIL CONNECTION LOCATIONS ARE
1 1/8
1 1/8
29
29
SUPPLY
RETURN
AIR FLOW
15 1/2"
12 1/2"
7 1/4"
10 1/2"
BOTTOM REAR OF UNIT
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 24/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 24 of 27
Accessory - BCXC Blower Coil Air Handler2 way basic piping package - coil #1Item: B2 Qty: 1 Tag(s): 2 ton
CONTROL VALVE
RETURN CONN.
BALL VALVE
BALL VALVECOIL CONNECTION
SUPPLY CONNECTION
COIL CONNECTION
= WATER FLOW
3 1/2"
14 1/4"
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 25/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 25 of 27
Accessory - BCXC Blower Coil Air HandlerCOIL 1 = HYDRONIC, COIL 2 = NONE, RH CONNECTIONSItem: B2 Qty: 1 Tag(s): 2 ton
INCH
COIL CONNECTION SIZE
RETURN
SUPPLY
mm
TOLERANCED WITHIN +/- 2 INCHES (51mm).NOTE: COIL CONNECTION LOCATIONS ARE
3/4
3/4
19
19
SUPPLY
RETURN
AIR FLOW
9 3/4"
6 3/4"
7 1/4"
10 1/2"
BOTTOM REAR OF UNIT
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 26/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
FLD = Furnished by Trane / Installed by Others Trane Equipment Submit ta l Page 26 of 27
Field Wiring - BCXC Blower Coil Air HandlerItem: B1, B2 Qty: 2 Tag(s): 7.5 ton, 2 ton
1TB5-1
1TB2-4
1TB2-5
1TB5-2
1TB3-1
1TB3-2
1TB3-6
1TB3-3
1TB3-4
1TB3-5
OPEN - DAMPER ACTUATOR
CLOSE - DAMPER ACTUATOR
EXHAUST FAN
OPEN - COIL #2 VALVE/
ELECTRIC HEAT 1st STAGE
CLOSE - COIL #2 VALVE/
ELECTRIC HEAT 2nd STAGE
FAN - HIGH SPEED
FAN - LOW SPEED
OPEN - COIL #1 VALVE
CLOSE - COIL #1 VALVE
FIELD SUPPLIED CONTROLLER24VAC, 15VA MAX.
EXHAUST FAN RELAY
24VAC, 2VA MAX.
UNIT CONTROL BOXTERMINAL BLOCK
NOTES:1. ALL FIELD WIRING MUST BE IN ACCORDANCE WITHTHE NATIONAL ELECTRIC CODE (NEC), STATE & LOCALREQUIREMENTS.2. DASHED LINES INDICATE RECOMMENDED FIELD WIRINGBY OTHERS. DASHED LINE ENCLOSURES &/OR DASHED DEVICEOUTLINES INDICATE COMPONENTS PROVIDED BY OTHERS.SOLID LINES INDICATE WIRING BY TRANE CO.3. CONTROL WIRING CONNECTIONS ARE 6-32 SCREWTERMINALS LOCATED ON OUTSIDE OF CONTROL BOX.
4. LINE VOLTAGE CONNECTIONS ARE TO BE SPLICED TOWIRES INSIDE OF UNIT CONTROL BOX OR TERMINATEDINSIDE OF ELECTRIC HEAT CONTROL BOX ON UNITSWITH ELECTRIC HEATERS.
GROUNDEQUIPMENT
208/60/3
DISCONNECTMANUAL
L1 L2 L3
UNIT POWERWIRING
COIL #1 VLV
1TB3-5
1TB3-4
1TB5-2 24V
OPEN
CLOSE7VA MAX.
INCLUDING REMOTE DISCONNECTS
AVERTISSEMENT ADVERTENCIA
NE PAS RESPECTER CES MESURES DE
PROCEDURES BEFORE SERVICING.INSURE THAT ALL MOTORCAPACITORS HAVE DISCHARGEDSTORED VOLTAGE. UNITS WITH
TO DRIVE INSTRUCTIONS FOR
BEFORE SERVICING COULD RESULT
INSTRUCTIONS DE L'ENTRAÎNEMENT POURVITESSE VARAIBLE, SE REPORTER AUX
DÉCHARGÉS. DANS LE CAS D'UNITÉSLES CONDENSATEURS DES MOTEURS SONTTOUTE INTERVENTION. VÉRIFIER QUE TOUSVERROUILLAGE ET DES ÉTIQUETTES AVANT
OUVRIR LES SECTIONNEURS À DISTANCE,
PRÉCAUTION PEUT ENTRAÎNER DESBLESSURES GRAVES POUVANT ÊTRE
DÉCHARGER LES CONDENSATEURS.
MORTELLES.
TENSION DANGEREUSE!
VARIABLE SPEED DRIVE, REFER
FAILURE TO DO THE ABOVE
COMPORTANT DES ENTRAÎNEMENTS À
PUIS SUIVRE LES PROCÉDURES DE
COUPER TOUTES LES TENSIONS ET
IN DEATH OR SERIOUS INJURY.
WARNING
DISCONNECT ALL ELECTRIC POWER
HAZARDOUS VOLTAGE!
AND FOLLOW LOCK OUT AND TAG
CAPACITOR DISCHARGE.
iVOLTAJE PELIGROSO!
O SERIAS LESIONES PERSONALES.INDICADO, PODRÍA OCASIONAR LA MUERTEEL NO REALIZAR LO ANTERIORMENTE
DESCARGA DEL CONDENSADOR.CONSULTE LAS INSTRUCCIONES PARA LADIRECCIÓN DE VELOCIDAD VARIABLE,PARA LAS UNIDADES CON EJE DEDESCARGADO EL VOLTAJE ALMACENADO.LOS CAPACITORES DEL MOTOR HAYANSERVICIO. ASEGÚRESE DE QUE TODOSETIQUETADO ANTES DE PROCEDER ALSIGA LOS PROCEDIMIENTOS DE CIERRE YINCLUSO LAS DESCONEXIONES REMOTAS YDESCONECTE TODA LA ENERGÍA ELÉCTRICA,
UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT
FAILURE TO DO SO MAY CAUSE DAMAGE TO THE
USE COPPER CONDUCTORS ONLY!
OTHER TYPES OF CONDUCTORS.
EQUIPMENT.
CAUTION
SI NO LO HACE, PUEDE OCASIONAR DAÑO AL EQUIPO.
LAS TERMINALES DE LA UNIDAD NO ESTÁN DISEÑADAS
¡UTILICE ÚNICAMENTE CONDUCTORES DE COBRE!
POUR RECEVOIR D'AUTRES TYPES DE CONDUCTEURS.
N'UTILISER QUE DES CONDUCTEURS EN CUIVRE!
L'UTILISATION DE TOUT AUTRE CONDUCTEUR PEUT
LES BORNES DE L'UNITÉ NE SONT PAS CONÇUES
ENDOMMAGER L'ÉQUIPEMENT.
PRECAUCIÓN
PARA ACEPTAR OTROS TIPOS DE CONDUCTORES.
ATTENTION
8/9/2019 Submittal 57q874_chiller Trane
http://slidepdf.com/reader/full/submittal-57q874chiller-trane 27/27
57Q874 - 57Q883 Feibo - Meyer April 12, 2006
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part ororder numbers for each field installed option, and references it to a specific product tag. It is NOT intended as abill of material for the job.
Product Family - Air-Cooled Water Chillers (Large Tonnage)
Item Tag(s) Qty Description Model Number
A1 CGAF-1 1 20-60 Ton Packaged Air-Cooled Chiller - CGAFC60E
Field Installed Option Description Part/Ordering Number
Unit Neoprene Isolators
Product Family - BCXC Blower Coil Air Handler
Item Tag(s) Qty Description Model Number
B1 7.5 ton 1 BCXC Blower Coil Air Handler -BCXC
BCHC090E2**A1M06P000000B01ED100000000000
Field Installed Option Description Part/Ordering Number
2-Way Modulating
6.0 CV, 1" Modulating, 1" PIPE
Basic Piping Package
Item Tag(s) Qty Description Model Number
B2 2 ton 1 BCXC Blower Coil Air Handler -BCXC
BCHC024E2**A1M02G000000B01EB100000000000
Field Installed Option Description Part/Ordering Number
2-Way Modulating
3.3 CV, 1/2" Modulating, 3/4" PIPE
Basic Piping Package
Recommended